BSP B_ _0-DV001-I0_A0A-S4 Pressure Sensor User's Guide
English
M121
28.3
10.5
13ca
. 92
14 12
G''
SW2818.9
-
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
2
3
4
2
1 Notes to the user 31.1 About this guide 31.2 Structure of the guide 31.3 Typographical conventions 31.4 Symbols 31.5 Abbreviations 3
Safety 4
2.1 Intended use 42.2 Improper use 42.3 Meaning of the warnings 42.4 Safety Advisories 5
Getting Started 6
3.1 Connection overview 63.2 Mechanical connection 63.3 Electrical connection 63.4 IO-Link connection 6
IO-Link interface 7
4.1 IO-Link data 74.2 Process data/Output data 74.3 Process data/Input data 74.4 Parameter data/Required data 74.5 Error codes/Errors 94.6 Events 9
Technical Data 10
5.1 Dimensions 105.2 Mechanical data 105.3 Electrical data 105.4 Operating conditions 105.5 Measuring ranges 115.6 Function indicators 11
Appendix 12
Ordering code 12
5
-
www.balluff.com
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
3
Notes to the user
This guide describes the IO-Link pressure sensor BSP B__0-. Linking to the host Master module takes place using IO-Link protocol. The pressure sensor sends the actual value and 2 switching points over the IO-Link interface.
The Guide is organized so that the sections build on one another.Section 2: Basic safety information.Section 3: The main steps for installing the device.Section 4: IO-Link, parameter and process data for the sensor.Section 5: Technical data for the device.
The following typographical conventions are used in this Guide.
Enumerations are shown in list form with bullet points.Entry 1,Entry 2.
Action instructions are indicated by a preceding triangle. The result of an action is indicated by an arrow.
Action instruction 1.Action result.
Action instruction 2.
Numbers:Decimal numbers are shown without additional indicators (e.g. 123),Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex).
Cross-references indicate where additional information on the topic can be found (see Section 5 "Technical data").
This symbol indicates a risk of personal injury.Take the precautions described to prevent injury or death.
NoteThis symbol indicates general notes.
BNI Balluff Network InterfaceEMC Electromagnetic CompatibilityFE Function groundIOL IO-LinkLSB Least Significant BitMSB Most Significant BitDPP Direct Parameter PageSPDU Service Protocol Data Unit
1.1 About this guide
1.2 Structure of the guide
1.3 Typographical conventions
Enumerations
Actions
Syntax
Cross-references
1.4 Symbols
1.5 Abbreviations
1
-
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
4
Safety
The BSP B__0- pressure sensor is used for measuring media pressures and for transmitting the measured value as well as two switching points over the IO-Link interface.
Applications:Pressure measurement in hydraulic applicationsPressure measurement in pneumatic applicationsLubricant monitoring
The sensor is for use only with equipment in which the maximum pressure Pmax and the maxi-mum temperature Tmax is not exceeded (see part label or Section 5 Technical Data).The sensor may be operated only using an approved power supply (see Section 5 Technical Data). Only approved cables may be used.
Installation and startup are to be performed only by trained personnel. The pressure and electrical connections are to be made only by trained or experienced techni-cians according to the current state of the art.Any damage resulting from unauthorized manipulation or improper use voids the manufacturer's guarantee and warranty.
The device is an equipment in accordance with EMC Class A. Such equipment may generate RF noise. The operator must take precautionary measures accordingly.
Improper use is any which is not defined under intended use, in particular:Improper installation or operation in violation of the specifications in this User's Guide,use as a sole safety-relevant component per DGR 97/23/EC,use with aggressive media.
WARNINGPotential hazard which can result in death or severe injury.
Always observe the described measures for preventing this danger.
CAUTIONPotential hazard which can result in slight injury.
Always observe the described measures for preventing this danger.
CAUTIONPotential hazard which can result in equipment damage
Always take the precautions described in order to prevent equipment damage.
2.1 Intended use
2.2 Improper use
2.3 Meaning of the warnings
2
-
www.balluff.com
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
5
Safety2
2.4 Safety Advisories Installation and startup
WARNINGHot fluids escaping under high pressure may cause eye or skin injury (high pressure injection) and/or scalding.
Before assembly/disassembly ensure that the media transporting line or equip-ment is pressureless and that no medium can escape.Allow the transporting line or equipment to cool before assembly/disassembly.
CAUTIONDo not exceed the maximum specified tightening torque. Threads, fittings and the pressure sensor can otherwise be damaged.
Tighten the pressure sensor to a maximum tightening torque of 45 Nm.
Transport the pressure sensor carefully and do not drop. Even if the housing is not damaged, internal parts may be damaged and cause malfunction.
Avoid impact and strong vibration during transport.Do not place a damaged sensor into service.
Operation and testing
CAUTIONThe surface of the housing may become hot during operation. This can result in burns upon contact.
Allow the pressure sensor (line/equipment) to cool before touching.
CAUTIONA defect or fault in the pressure sensor may, depending on the application, result in equipment damage or personal injury.
Visually inspect at regular intervals for leaks andcheck the switching points with a pressure gauge.When defects and non-clearable faults occur in the device, take it out of service and secure against unauthorized use.
The operator is responsible for observing local prevailing safety regulations.
-
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
6
Getting Started3
3.1 Connection overview
3.2 Mechanical connection
3.3 Electrical connection
3.4 IO-Link connection
Fig. 3-1: Connection overview BSP B_ _0-DV001-I0_A0A-S4
1 IO-Link interface2 Status LED3 Part label
4 28 mm flat-to-flat5 O-ring6 Media connection G" external thread
CAUTIONDo not exceed the maximum specified tightening torque. Threads, fittings or the pressure sensor may be damaged.
Tighten the pressure sensor to a maximum torque of 45 Nm.
Ensure correct seating of the O-ring.Tighten the pressure sensor using a 28mm wrench and to a maximum torque of 45 Nm.
The pressure sensor requires no separate power supply. The supply voltage is provided by the IO-Link Master through the IO-Link interface.
The IO-Link connection is made using a standard sensor cable (M12 connector).
IO-Link port (M12, A-coded, male)
PIN Requirement
1 Supply voltage, +24 V, max. 1.6 A
2 -
3 GND, reference potential
4 Q/C, IO-Link data transmission channel
Connect the incoming IO-Link cable to the pressure sensor.
CAUTIONA defect or fault in the pressure sensor may, depending on the application, result in equipment damage or personal injury.
Visually inspect at regular intervals for leaks andcheck the switching points with a pressure gauge.When defects and non-clearable faults occur in the device, take it out of service and secure against unauthorized use.
-
www.balluff.com
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
7
IO-Link interface4
4.1 IO-Link data
4.2 Process data/Output data
4.3 Process data/Input data
4.4 Parameter data/Required data
Baud rate COM2 (38.4 Kbaud)
Frame type 2.2
Minimum cycle time 3 ms
Process data cycle 3 ms at minimum cycle time
Process data length 2 bytes:
Byte 0 Byte 1 Byte 2
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
0 0 0 0 0 0
SP
2
SP
1 MSB
Pressure ValueLSB
SP 1: Switching point 1; SP 2: Switching point 2Pressure Value: Current measured pressure value
There are no input data for the pressure sensors.
DPP SPDU Parameter Data width
Value range
Default value
Index Index Sub-index
Iden
tific
atio
n D
ata
07hexVendor ID 2 bytes
Rea
d on
ly
0378hex08hex
09hex
Device ID 3 bytes
050501hex050502hex050503hex050504hex050505hex
(10 bar)/(50 bar)/(100 bar)/(250 bar)/(400 bar)/
0Ahex
0Bhex
10hex 0 Vendor Name 8 bytes Balluff
11hex 0 Vendor text 16 bytes www.balluff.com
12hex 0 Product Name 28 bytes
BSP B010-DV001-I00A0A-S4/BSP B050-DV001-I00A0A-S4/BSP B100-DV001-I00A0A-S4/BSP B250-DV001-I00A0A-S4/BSP B400-DV001-I00A0A-S4/BSP B600-DV001-I00A0A-S4/
13hex 0 Product ID 25 bytes
159871159872159873159874159875159876
(10 bar)/(50 bar)/(100 bar)/(200 bar)/(400 bar)/(600 bar)/
-
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
8
IO-Link interface4
Parameter data/Required data (cont.)
DPP SPDU Parameter Data width
Value range
Default value
Index Index Sub-index
14hex 0 Product text 28 bytes
Rea
d on
ly
IO-Link Pressure Sensor 10 bar/
IO-Link Pressure Sensor 50 bar/
IO-Link Pressure Sensor 100 bar/
IO-Link Pressure Sensor 250 bar/
IO-Link Pressure Sensor 400 bar/
IO-Link Pressure Sensor 600 bar/
16hex 0 Hardware Revision 3 bytes 1.00
17hex 0 Firmware Revision 3 bytes 1.00
Par
amet
er D
ata
40hex64
0 Pressure Value 2 bytes Read only
41hex65
0 Switching point 1 2 bytes -999 9999 550
42hex66
0 Back Switching point 1 2 bytes -999 9999 450
43hex67
0 Logic 1 1 byte
44hex68
0 Switching point 2 2 bytes -999 9999 550
45hex69
0 Back Switching point 2 2 bytes -999 9999 450
46hex70
0 Logic 2 1 byte
48hex72
0 Unit 1 byte 0 0
4Ahex74
0 Maximum Value Storage 2 bytes Read only
4Chex76
0 Switching Delay 1 2 bytes 0 99 0
4Dhex77
0 Back Switching Delay 1 2 bytes 0 99 0
4Fhex78
0 Switching Delay 2 2 bytes 0 99 0
46hex79
0 Back Switching Delay 2 2 bytes 0 99 0
-
www.balluff.com
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
9
Error code Additional Code
Device application error: 80hex
11hex Index not available
12hex SubIndex not available
30hex Value out of range
Class /Qualifier Code (high + low)
Mode Type Instance
appears Error AL Device Hardware supplySupply low
voltage U2 = supply + 24V
C0hex 30hex 03hex 5000hex 0100hex 0010hex 0002hex
F3hex 5112hex
disappears Error AL Device Hardware supplySupply low
voltage U2 = supply + 24V
80hex 30hex 03hex 5000hex 0100hex 0010hex 0002hex
B3hex 5112hex
appears Error AL Device Hardware supply supply periphery
C0hex 30hex 03hex 5000hex 0100hex 0060hex
F3hex 5160hex
disappears Error AL Device Hardware supply supply periphery
80hex 30hex 03hex 5000hex 0100hex 0060hex
B3hex 5160hex
4.5 Error codes/Errors
4.6 Events
IO-Link interface4
-
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
10
Technical Data5
5.1 Dimensions
5.2 Mechanical data
5.3 Electrical data
5.4 Operating conditions
M121
28.3
10.5
13ca
. 92
14 12 G''
SW2818.9
Fig. 5-1: Dimensions in mm
MaterialHousingMedia-contacting parts
stainless steelStainless 1.4301, AL3O2, FKM (O-ring)
Process connection G" external thread
IO-Link connection M12, A-coded, male
Enclosure rating IP67 (only when plugged-in and threaded-in)
Weight approx. 200 g
Dimensions (L D, excluding connector) 93 32 mm
Operating voltage 15 ... 32 V DC, per EN 50178, SELV, PELV
Insulation class III
Ripple < 1 %
Current draw without load 40 mA
Measured value acquisition:ResolutionSampling rate
10 Bit2 ms
Operating temperature:MediumElectronics
Tmax:-25 C +100 C-25 C +70 C
Compensation range -10 C +100 C
Storage temperature -40 C +85 C
EMCEN 61000-4-2/3/4/5/6 Severity level 4A/3A/4B/2A/3A
Vibration/shock EN 60068 Part 2-6/27
-
www.balluff.com
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
11
Pressure sensor:BSP B010-_V001-I0_A0A-S4BSP B050-_V001-I0_A0A-S4BSP B100-_V001-I0_A0A-S4BSP B250-_V001-I0_A0A-S4BSP B400-_V001-I0_A0A-S4BSP B600-_V001-I0_A0A-S4
Operating pressure P:10 bar50 bar100 bar250 bar400 bar600 bar
Overload Pmax:15 bar75 bar15 bar375 bar600 bar800 bar
Output curve deviation 0.5 % of max. value at +25 C
Fig. 5-2: Status LED
Status LED, IO-Link communication
Display Function
Green No communication
Green negatively pulsed Communication OK
Red Short circuit on the IO-Link interface
Off No power to module
Technical Data
5.5 Measuring ranges
5.6 Function indicators
5
Status LED
-
Pressure sensorBSP B_ _0-DV001-I0_A0A-S4
12
BSP B 010 D V 001 I 01 A0 A S4
Balluff Sensor Pressure
Physical unit
M = Millibar B = Bar K = Kilobar
Pressure range (max.)
010 = 10 bar 050 = 50 bar 100 = 100 bar 250 = 250 bar 400 = 400 bar 600 = 600 bar
Process connection
D = Thread " E = Thread "
O-ring
V = Viton (FKM: Fluorocarbon rubber)
Housing type
001 = Single piece, stainless
Interface
I = IO-Link: 1 M121 external thread
Data map
01 = IO-Link pressure sensor without SIO Mode= IO-Link pressure sensor with SIO Mode
Process data: 3 bytesPressure actual value2 switching points
Parameter data:2 switching points2 Back switching points2 Switching delay2 Back switching delayStored maximum valueUnit2 Output logic (bits)
02
Variants
A = Balluff Version 1.0 (Firmware/chipset) 0 = Basis version
Operating elements
A = No indicators, no keys
Connector system
S4 = M12, 4-pin
Appendix
Ordering code
-
Balluff GmbHSchurwaldstrae 973765 Neuhausen a.d.F.GermanyTel. +49 7158 173-0Fax +49 7158 [email protected]
www.balluff.com