Customer: Contego International, Inc. BTC 18175F: Page 1 of 26 The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected] No. 0296 Customer: Contego International, Inc. PO Box 684 Westfield Indiana 46074 Report Number BTC 18175F A REACTION TO FIRE TEST REPORT COVERING A SINGLE BURNING ITEM TEST ON CONTEGO HS INTUMESCENT FIRE BARRIER PAINT (HIGH SOLIDS VERSION), CONDUCTED IN ACCORDANCE WITH EN 13823: 2010. Test Date: 18 th April 2013 www.btconline.co.uk

Upload: hoanganh

Post on 03-Oct-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 1 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Customer: Contego International, Inc. PO Box 684 Westfield Indiana 46074

Report Number BTC 18175F A REACTION TO FIRE TEST REPORT COVERING A SINGLE BURNING ITEM TEST ON CONTEGO HS INTUMESCENT FIRE BARRIER PAINT (HIGH SOLIDS VERSION), CONDUCTED IN ACCORDANCE WITH EN 13823: 2010.

Test Date: 18th April 2013

www.btconline.co.uk

Page 2: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 2 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

A REACTION TO FIRE TEST REPORT COVERING A SINGLE BURNING ITEM TEST ON CONTEGO HS INTUMESCENT FIRE BARRIER PAINT (HIGH SOLIDS VERSION) CONDUCTED IN ACCORDANCE WITH EN 13823: 2010. TABLE OF CONTENTS

FOREWORD ___________________________________________________________ 3 REPORT AUTHORISATION _______________________________________________ 3 TEST MATERIALS ______________________________________________________ 4

Norbord OSB Sheathing Board____________________________________________________ 4 Contego HS Intumescent Fire Barrier Paint (High Solids Version)_________________________ 4

TEST SPECIMEN CONSTRUCTION ________________________________________ 5 TEST PROCEDURE _____________________________________________________ 5 TEST SPECIMEN MOUNTING _____________________________________________ 6 TEST RESULTS ________________________________________________________ 7 LIMITATIONS __________________________________________________________ 8 APPENDIX 1 - TEST DATA________________________________________________ 9

Specimen 1___________________________________________________________________ 9 Specimen 2__________________________________________________________________ 12 Specimen 3__________________________________________________________________ 15

APPENDIX 2 – PHOTOS OF SPECIMENS BEFORE TESTING __________________ 18 APPENDIX 3 – PHOTOS OF SPECIMENS AFTER TESTING ____________________ 21

Page 3: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 3 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

FOREWORD This test report details a single burning item test conducted on Contego HS Intumescent Fire Barrier Paint (High Solids Version), in accordance with EN 13823: 2010. The test sponsor was JPQ International Consultants Ltd. Contego International, Inc. manufactured and Biokjemi Norge as Norsk Trepleie supplied the products used to construct the test specimens. The products were received for testing by the Building Test Centre in April 2013. The test specimens were prepared and inspected prior to testing by the Building Test Centre in April 2013. The Building Test Centre played no role in the design or selection of the materials comprising the test specimens. REPORT AUTHORISATION

Report date 19/04/13 The Building Test Centre will not discuss the content of this report without written permission from the test sponsor. The Building Test Centre retains ownership of the test report content but authorises the test sponsor to reproduce the report as necessary in its entirety only.

Report Author

Paul Davies MEng. (Hons.), Scientist

Authorised by

Mark Shortland BSc. (Hons.), Scientist

Page 4: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 4 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TEST MATERIALS Norbord OSB Sheathing Board Nominally 12mm thick Norbord OSB Sheathing Board supplied by Biokjemi Norge as Norsk Trepleie pre-painted with Contego HS Intumescent Fire Barrier Paint (High Solids Version). Measured thickness 12.307 mm Measured density 671.3 kg/m³ The thickness and density were calculated using a sample without paint applied of sufficient size to be representative of the product without paint. Contego HS Intumescent Fire Barrier Paint (High Solids Version) The test material was supplied pre-painted onto a timber OSB sheathing board. Measured thickness 0.491 mm The thickness of the paint was calculated using the test specimens. Where measurements could not be taken then weight and dimensions were provided by the customer or the manufacturer e.g. from material labelling. Material information was recorded according to procedure MAT/1.

Page 5: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 5 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TEST SPECIMEN CONSTRUCTION The boards were tested in a corner configuration comprising two wings, constructed using GypFrame 72C50 channel and GypFrame 70S50 studs. The boards were screw fixed to the metal frame using 36mm Gyproc Drywall Screws at 300mm ± 30mm centres measured along the length of each supporting member. A calcium silicate backing board was positioned freely against the GypFrame with a second metal framework secured with brackets behind it to hold it in place. The description of the test material was provided by the customer and was checked for accuracy wherever possible. TEST PROCEDURE The test was conducted following procedure EN/13823 issue 5. The test specimens were conditioned at 23 ± 2°C and 50 ± 5% RH prior to testing. The test specimen and the main burner were mounted on a trolley, which for the test, was placed under a hood. The trolley fitted into a frame, which supported this hood. The frame was mounted in a small chamber with two windows, allowing observations to be made from the outside during the test. Three minutes prior to the testing period a secondary burner, located away from the specimen, was used to adjust settings and measure the heat output of the burner alone. The test specimen, consisting of two vertical wings forming a right-angled corner, was then exposed to the main burner for a period of 21 minutes. The flames were obtained by combustion of propane gas, injected through a sandbox. The material was tested in an unmodified form.

Page 6: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 6 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TEST SPECIMEN MOUNTING

Page 7: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 7 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TEST RESULTS

Specimen No.→ 1 2 3 Graph reference

Total Heat Release of specimen in first 600 s of the exposure period (MJ) 1.03 0.92 0.88 b

Fire Growth Rate Index FIGRA 0.2MJ (W/s) 56.46 48.23 2.722 c

Fire Growth Rate Index FIGRA 0.4MJ (W/s) 3.04 0 2.722 -

Total smoke production from the specimen in first 600 s of the exposure period (m2) 24.82 25.97 28.11 -

Smoke Growth Rate Index SMOGRA (cm2/s2) 0 0 0 f

Lateral flame spread < edge of specimen Yes Yes Yes -

Fallen droplet / particle No No No -

Fallen droplet / particle > 10 seconds No No No -

Other observations None None None -

Page 8: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 8 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

LIMITATIONS The specification and interpretation of fire test methods are the subject of ongoing development and refinement. It is therefore recommended that, following further developments of the standard, the relevance of this report should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test to ensure that they are consistent with current practices, and if required may endorse the test report. The test results relate only to the behaviour of the test specimens of a product under the particular conditions of test; they are not intended to be the sole criterion for assessing the potential fire hazard of the product in use.

Page 9: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 9 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

APPENDIX 1 - TEST DATA Specimen 1

Average HRR (kW)

0

1

2

3

4

5

6

0 300 600 900 1200 1500Time (s)

HR

R (k

W)

Figure 1a. Relative heat release for specimen 1.

Total Heat Release (MJ)

0

0.5

1

1.5

2

2.5

0 300 600 900 1200 1500Time (s)

HR

(MJ)

Figure 1b. Total heat release for specimen 1.

Page 10: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 10 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

RHRav(t)/(t-300)1000

0

20

40

60

80

100

120

0 300 600 900 1200 1500Time (s)

FIG

RA

(w/s

)

Figure 1c. Fire growth rate for specimen 1.

RSPav(t)

0.0

0.1

0.2

0.3

0.4

0.5

0 300 600 900 1200 1500Time (s)

RSP

(m²/s

)

Figure 1d. Relative smoke production for specimen 1.

Page 11: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 11 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TSP(t)

0

10

20

30

40

50

60

0 300 600 900 1200 1500Time (s)

TSP

(m²)

Figure 1e. Total smoke production for specimen 1.

RSPav(t) 10000/t-300

0.00

10.00

20.00

30.00

40.00

50.00

0 300 600 900 1200 1500Time (s)

SMO

GR

A (m

²/s)

Figure 1f. Smoke growth rate for specimen 1.

Page 12: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 12 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Specimen 2

Average HRR (kW)

00.5

11.5

22.5

33.5

44.5

5

0 300 600 900 1200 1500Time (s)

HR

R (k

W)

Figure 2a. Relative heat release for specimen 2.

Total Heat Release (MJ)

0

0.5

1

1.5

2

2.5

0 300 600 900 1200 1500Time (s)

HR

(MJ)

Figure 2b. Total heat release for specimen 2.

Page 13: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 13 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

RHRav(t)/(t-300)1000

0

20

40

60

80

100

120

0 300 600 900 1200 1500Time (s)

FIG

RA

(w/s

)

Figure 2c. Fire growth rate for specimen 2.

RSPav(t)

0.0

0.1

0.2

0.3

0.4

0.5

0 300 600 900 1200 1500Time (s)

RSP

(m²/s

)

Figure 2d. Relative smoke production for specimen 2.

Page 14: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 14 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TSP(t)

0

10

20

30

40

50

60

0 300 600 900 1200 1500Time (s)

TSP

(m²)

Figure 2e. Total smoke production for specimen 2.

RSPav(t) 10000/t-300

0.00

10.00

20.00

30.00

40.00

50.00

0 300 600 900 1200 1500Time (s)

SMO

GR

A (m

²/s)

Figure 2f. Smoke growth rate for specimen 2.

Page 15: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 15 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Specimen 3

Average HRR (kW)

00.5

11.5

22.5

33.5

44.5

5

0 300 600 900 1200 1500Time (s)

HR

R (k

W)

Figure 3a. Relative heat release for specimen 3.

Total Heat Release (MJ)

0

0.5

1

1.5

2

2.5

0 300 600 900 1200 1500Time (s)

HR

(MJ)

Figure 3b. Total heat release for specimen 3.

Page 16: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 16 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

RHRav(t)/(t-300)1000

0102030405060708090

100

0 300 600 900 1200 1500Time (s)

FIG

RA

(w/s

)

Figure 3c. Fire growth rate for specimen 3.

RSPav(t)

0.0

0.1

0.2

0.3

0.4

0.5

0 300 600 900 1200 1500Time (s)

RSP

(m²/s

)

Figure 3d. Relative smoke production for specimen 3.

Page 17: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 17 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

TSP(t)

0

10

20

30

40

50

60

0 300 600 900 1200 1500Time (s)

TSP

(m²)

Figure 3e. Total smoke production for specimen 3.

RSPav(t) 10000/t-300

0.00

10.00

20.00

30.00

40.00

50.00

0 300 600 900 1200 1500Time (s)

SMO

GR

A (m

²/s)

Figure 3f. Smoke growth rate for specimen 3.

Page 18: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 18 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

APPENDIX 2 – PHOTOS OF SPECIMENS BEFORE TESTING

Photograph 1. Exposed surface (specimen 1).

Page 19: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 19 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 2. Exposed surface (specimen 2)

Page 20: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 20 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 3. Exposed surface (specimen 3)

Page 21: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 21 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

APPENDIX 3 – PHOTOS OF SPECIMENS AFTER TESTING

Photograph 4. Exposed surface (specimen 1)

Page 22: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 22 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 5. Close-up on bottom corner (specimen 1)

Page 23: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 23 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 6. Exposed surface (specimen 2)

Page 24: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 24 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 7. Close-up of bottom corner (specimen 2)

Page 25: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 25 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 8. Exposed surface (specimen 3)

Page 26: BTC 18175F - Contegocontegointernational.com/.../uploads/2013/11/Intl-BTC-18175F.pdf · Customer: Contego International, Inc. BTC 18175F: Page 3 of 26 The Building Test Centre British

Customer: Contego International, Inc. BTC 18175F: Page 26 of 26

The Building Test Centre British Gypsum East Leake Loughborough Leics. LE12 6NP Tel (0115) 945 1564 Fax (0115) 945 1562 email [email protected]

No. 0296

Photograph 9. Close-up of bottom corner (specimen 3)