building 1 electrical riser diagram riser notes · electrical riser diagram not to scale riser...

1
RESIDENTIAL LOAD CENTER TYPICAL OF 11 PANEL U LO - - < Ø FOURTH FLOOR RESIDENTIAL LOAD CENTER TYPICAL OF 11 PANEL PANEL T HP13 THIRD FLOOR RESIDENTIAL LOAD CENTER TYPICAL OF 11 PANEL T [- SECOND FLOOR 14,750A AVAILABLE FAULT CURRENT - On On On On On On On On On ° 7 7 On On On On On On On On O - @ 570- @ EL PAPNE On On On On On On On On . __ 38,993A AVAILABLE FAULT CURRENT 12 GRADE 29,904A AVAILABLE FAULT CURRENT 42015A AVALABLE FAULT CURRENT- ----------------------------------------------------------------- ----------- _-_-_-_-_- ___ _-_-_-_-_----_-_-_- L_____________________________.______________________________J BUILDING 1 ELECTRICAL RISER DIAGRAM NOT TO SCALE RISER NOTES UTILITY TRANSFORMER, PROVIDE AND INSTALL CONCRETE PAD PER THE UTILITY'S ELECTRICAL SERVICE STANDARDS. PROVIDE AND INSTALL MODULAR METERING FOR RESIDENTIAL TENANTS. METERING TO CONSIST OF A THREE PHASE 1200A MAIN CIRCUIT BREAKER, A THREE PHASE HORIZONTAL BUS, AND 9-4 HIGH METER STACKS. EACH METER STACK SHALL BE SINGLE PHASE AND EACH METER CAN SHALL CONTAIN A METER SOCKET AND A 125A/2P LOAD CIRCUIT BREAKER. METER SOCKETS SHALL BE ACCEPTABLE TO THE ELECTRICAL UTILITY. PROVIDE AND INSTALL A UTILITY APPROVED CT CABINET. INSTALL A UTILITY PROVIDED METER SOCKET. CONNECT TO THE CT CABINET WITH A 1 1/4" CONDUIT. 800A SERVICE SWITCH FUSED AT 400A WITH CLASS L FUSES. 200A SERVICE SWITCH FUSED AT 200A WITH CLASS J FUSES. INSTALL ABOVE THE METER, SHOWN BESIDE THE METER ON THE RISER FOR CLARITY. THREE PHASE RETAIL TENANT PANELBOARD. THREE PHASE DISTRIBUTION PANELBOARD FOR THE HOUSE SERVICE. 4 SETS OF 4-500 KCMIL, EACH SET IN A 4" CONDUIT. 4-#4/0 IN A 3" CONDUIT. 2 SETS OF 4-500 KCMIL, EACH SET IN A 4" CONDUIT. 4-#4/0, 1-#4 GROUND WIRE IN 2 1/2" CONDUlT. 4-500 KCMIL, 1-#3 GROUND WIRE IN A 3 1/2" CONDUIT. GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEEL WITH #3/0 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER. GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEEL WITH #2 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER. PROVIDE ANY OTHER GROUNDING REQUIRED BY THE UTILITY FOR THEIR EQUIPMENT. GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEEL WITH #2/0 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER. PROVIDE ANY OTHER GROUNDING REQUIRED BY THE UTILITY FOR THEIR EQUIPMENT. 3-#1, 1-#6 GROUND WIRE IN A 1 1/4" CONDUIT. 4" PVC CONDUIT TO THE UTILITY TRANSFORMER FOR PRIMARY SERVICE. COORDINATE EXACT ROUTING AND REQUIREMENTS WITH THE UTILITY. PROVIDE AND INSTALL A UTILITY APPROVED 200A THREE PHASE FEED THROUGH METER SOCKET. GROUND PER UTILITY REQUIREMENTS. 2 SETS OF 4-500 KCMIL AND 1-#1/0 GROUND WIRE, EACH SET IN A 3 1/2" CONDUIT. 4-#1/0, 1-#4 GROUND WIRE IN 2" CONDUlT. PANEL HP11 1 I FIRST FLOOR BASEMENT DRAWING RELEASE {OG J3-21-14 - PDP Submittal 12-01-14 - 65% Set J1-09-15 - FDP Submittal J1-14-15 - Permit Set J3-20-15 - 98% Review Set J4-03-15 - 98% CD's REVISIONS DATE March 21, 2014 [os No. 908 Broadway, Suite 200 Kansas City, MO 64105-1590 3HEET No. Ph: 816.842.2800 Fx: 816.842.4884 www.bgrengineers.com

Upload: others

Post on 16-Nov-2020

21 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: BUILDING 1 ELECTRICAL RISER DIAGRAM RISER NOTES · electrical riser diagram not to scale riser notes utility transformer, provide and install concrete pad per the utility's electrical

RESIDENTIAL LOAD CENTERTYPICAL OF 11

PANEL

U LO-- < Ø

FOURTH FLOOR

RESIDENTIAL LOAD CENTERTYPICAL OF 11

PANEL PANELT HP13

THIRD FLOOR

RESIDENTIAL LOAD CENTERTYPICAL OF 11

PANELT [-

SECOND FLOOR

14,750A AVAILABLE FAULT CURRENT -

On On On On On On On On On °7 7

On On On On On On On On O - @�570- @ EL PAPNE

On On On On On On On On . __

38,993A AVAILABLE FAULT CURRENT 12GRADE

29,904A AVAILABLE FAULT CURRENT

42015A AVALABLE FAULT CURRENT- ----------------------------------------------------------------- ----------- _-_-_-_-_- ___ _-_-_-_-_----_-_-_-L_____________________________.______________________________J

BUILDING 1ELECTRICAL RISER DIAGRAMNOT TO SCALE

RISER NOTESUTILITY TRANSFORMER, PROVIDE AND INSTALL CONCRETE PAD PER THE UTILITY'SELECTRICAL SERVICE STANDARDS.

PROVIDE AND INSTALL MODULAR METERING FOR RESIDENTIAL TENANTS. METERINGTO CONSIST OF A THREE PHASE 1200A MAIN CIRCUIT BREAKER, A THREE PHASEHORIZONTAL BUS, AND 9-4 HIGH METER STACKS. EACH METER STACK SHALL BESINGLE PHASE AND EACH METER CAN SHALL CONTAIN A METER SOCKET AND A125A/2P LOAD CIRCUIT BREAKER. METER SOCKETS SHALL BE ACCEPTABLE TO THEELECTRICAL UTILITY.

PROVIDE AND INSTALL A UTILITY APPROVED CT CABINET.

INSTALL A UTILITY PROVIDED METER SOCKET. CONNECT TO THE CT CABINET WITH A1 1/4" CONDUIT.

800A SERVICE SWITCH FUSED AT 400A WITH CLASS L FUSES.

200A SERVICE SWITCH FUSED AT 200A WITH CLASS J FUSES. INSTALL ABOVE THEMETER, SHOWN BESIDE THE METER ON THE RISER FOR CLARITY.

THREE PHASE RETAIL TENANT PANELBOARD.

THREE PHASE DISTRIBUTION PANELBOARD FOR THE HOUSE SERVICE.

4 SETS OF 4-500 KCMIL, EACH SET IN A 4" CONDUIT.

4-#4/0 IN A 3" CONDUIT.

2 SETS OF 4-500 KCMIL, EACH SET IN A 4" CONDUIT.

4-#4/0, 1-#4 GROUND WIRE IN 2 1/2" CONDUlT.

4-500 KCMIL, 1-#3 GROUND WIRE IN A 3 1/2" CONDUIT.

GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEELWITH #3/0 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER.

GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEELWITH #2 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER.PROVIDE ANY OTHER GROUNDING REQUIRED BY THE UTILITY FOR THEIR EQUIPMENT.

GROUND SERVICE TO INCOMING WATER SERVICE PIPE AND ANY STRUCTURAL STEELWITH #2/0 COPPER, AND TO FOOTING REINFORCING STEEL WITH #4 COPPER.PROVIDE ANY OTHER GROUNDING REQUIRED BY THE UTILITY FOR THEIR EQUIPMENT.

3-#1, 1-#6 GROUND WIRE IN A 1 1/4" CONDUIT.

4" PVC CONDUIT TO THE UTILITY TRANSFORMER FOR PRIMARY SERVICE.COORDINATE EXACT ROUTING AND REQUIREMENTS WITH THE UTILITY.

PROVIDE AND INSTALL A UTILITY APPROVED 200A THREE PHASE FEED THROUGHMETER SOCKET. GROUND PER UTILITY REQUIREMENTS.

2 SETS OF 4-500 KCMIL AND 1-#1/0 GROUND WIRE, EACH SET IN A 3 1/2"CONDUIT.

4-#1/0, 1-#4 GROUND WIRE IN 2" CONDUlT.

PANELHP11

1I

FIRST FLOOR

BASEMENT

DRAWING

RELEASE {OG

J3-21-14 - PDP Submittal12-01-14 - 65% SetJ1-09-15 - FDP SubmittalJ1-14-15 - Permit SetJ3-20-15 - 98% Review SetJ4-03-15 - 98% CD's

REVISIONS

DATE

March 21, 2014

[os No.

908 Broadway, Suite 200Kansas City, MO 64105-1590 3HEET No.Ph: 816.842.2800Fx: 816.842.4884

www.bgrengineers.com