building design b

Upload: savio-wong

Post on 07-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/4/2019 Building Design b

    1/69

    Integrated Civil EngineeringDesign Project

    (Building Structure Design)

    CIVL 395

    HKUST

    By : Ir. K.S. Kwan

    Date: 3/07

  • 8/4/2019 Building Design b

    2/69

    Content

    1. Building Control in Hong Kong

    2. Design Criteria

    3. Structural Form (Residential Building)

    4. Hong Kong Wind Loading

    5. Computer Modeling6. Design Example

  • 8/4/2019 Building Design b

    3/69

    STRUCTURAL FORMfor Residential Building

    Tower

    Podium Structure

    Building adjacent to slope

  • 8/4/2019 Building Design b

    4/69

    Lintel beam

    To identify the wall as structuralelement and link them together by lintel

    beam to provide sufficient lateralstiffness

    Slab

    Wall

  • 8/4/2019 Building Design b

    5/69

    Slab DesignSlab Design

    Concrete gradeConcrete gradeGrade 30 to 35 (too high concrete grade may lead to thermal craGrade 30 to 35 (too high concrete grade may lead to thermal crackckduring large pour of concrete)during large pour of concrete)

    Steel reinforcement percentageSteel reinforcement percentageDesign as HKDesign as HK CoPCoP 2004 for structural use of concrete2004 for structural use of concrete

    Average steel ratio is around 120~140 Kg/mAverage steel ratio is around 120~140 Kg/m33

    Preliminary slab size estimationPreliminary slab size estimation

    About 100mm~400mm depending on theAbout 100mm~400mm depending on the span of slabspan of slab ( to minimize( to minimizethe number of different slab thickness, say 2 ~3 types, at typicthe number of different slab thickness, say 2 ~3 types, at typical flooral floor

    forfor buildabilitybuildability considerationconsideration

    To consider the following loadingTo consider the following loading

    Self weightSelf weight

    Finishes (domestic area/toilet/kitchen) (25mm to 80mm thick)Finishes (domestic area/toilet/kitchen) (25mm to 80mm thick) PartitionPartition

  • 8/4/2019 Building Design b

    6/69

    Slab is designed asone-way or two waysslab

  • 8/4/2019 Building Design b

    7/69

    Wall DesignWall Design

    Concrete gradeConcrete gradeGrade 30, 40, 60 or more is commonly used. By usingGrade 30, 40, 60 or more is commonly used. By using high strengthhigh strengthconcreteconcrete, it can optimize the wall thickness and increase the lateral, it can optimize the wall thickness and increase the lateralstiffness of wall. The concrete grade will also bestiffness of wall. The concrete grade will also be changed along thechanged along theheight of buildingheight of building e.g. from Grade 60 at lower floor to Grade 30 at tope.g. from Grade 60 at lower floor to Grade 30 at top

    roof.roof.

    TheThe thicknessthickness will bewill be trimmedtrimmed down along the height of building e.g.down along the height of building e.g.from 400 at 1/F and gradually changed to 200 at top floor. Thefrom 400 at 1/F and gradually changed to 200 at top floor. Thethickness will be changed every 10 ~20 storey to minimize thethickness will be changed every 10 ~20 storey to minimize the

    disturbance on construction.disturbance on construction.

    Steel reinforcement percentageSteel reinforcement percentageDesign as HKDesign as HK CoPCoP 20042004

    Average steel ratio is around 100~150Kg/mAverage steel ratio is around 100~150Kg/m33

    Preliminary wall size estimationPreliminary wall size estimationGravity LoadGravity Loadby tributary methodby tributary method

    Wind LoadWind Loadby simple computer modelby simple computer model

  • 8/4/2019 Building Design b

    8/69

    3-D

    Vertical Element Gravity Load Estimation byVertical Element Gravity Load Estimation byTributary Area MethodTributary Area Method

    Plan

    W2

    W1W1

    W3

    C1

    250250 200 26252625

    200

    3900

  • 8/4/2019 Building Design b

    9/69

    TRIBUTARY AREA METHODTRIBUTARY AREA METHOD

    No. of storey = 20

    Storey height = 2800

    Slab thickness = 150

    Beam size = 400x200 (ext.)

    Beam size = 450x250 (int.)

    Dead Load = 10KPa

    Live Load = 3KPa

    AssumptionAssumption

  • 8/4/2019 Building Design b

    10/69

    Plan

    1266W3

    2568W2

    2264W1

    1686C1

    (KN)

    W2

    W1W1

    W3

    C1

    250250 20026252625

    200

    3900

    TRIBUTARY AREA METHODTRIBUTARY AREA METHOD

  • 8/4/2019 Building Design b

    11/69

    Lintel Beam DesignLintel Beam Design (where linking shear(where linking shearwall together to transmit wind shear force)wall together to transmit wind shear force)

    SizeSizeWidth as wall thicknessWidth as wall thickness

    Depth controlled by headroom (min.Depth controlled by headroom (min.under side of beam i.e. 2100 at doorunder side of beam i.e. 2100 at doorand 2300 under beamand 2300 under beam

    Concrete grade same as floor slabConcrete grade same as floor slabfor easy concrete pour with slab orfor easy concrete pour with slab ormore if requiredmore if required

    Steel reinforcement percentageSteel reinforcement percentageDesign as HKDesign as HK CoPCoP 20042004

    Average steel ratio is around 120Average steel ratio is around 120~160 Kg/m~160 Kg/m33

    Preliminary lintel size estimationPreliminary lintel size estimationWind LoadWind Loadby simple computerby simple computer

    model; the size is always controlledmodel; the size is always controlledby wind shear transmission (in someby wind shear transmission (in somecritical case, steel plate will be usedcritical case, steel plate will be usedto replaceto replace r.cr.c. design to enhance the. design to enhance thewind shear transmission)wind shear transmission)

    Gravity LoadGravity Loadby tributary methodby tributary method

    (not the controlled case)(not the controlled case)

    LintelBeam

    Steel plate at lintelbeam

  • 8/4/2019 Building Design b

    12/69

    TransferStructure

    Podium(Plate Structure)

    Tower(Shear Wall system)

    Supporting Column

    (Rigid Frame)

  • 8/4/2019 Building Design b

    13/69

    Transfer Girder Structure

    The behavior is similar to deep beam whenthe wall extending to columns such as case a,

    b & c.

  • 8/4/2019 Building Design b

    14/69

    Transfer Plate StructureShear WallStructure atTower above

    Transfer Plate

    ColumnStructure belowTransfer Plate

    Thick plate structure

    to support all wallstructures above

  • 8/4/2019 Building Design b

    15/69

    Transfer Plate

  • 8/4/2019 Building Design b

    16/69

  • 8/4/2019 Building Design b

    17/69

    Transfer Structure Design (Plate or Girder)Transfer Structure Design (Plate or Girder)

    Design similar toDesign similar to pilecappilecap or beamor beam

    Closed column spacing under the transfer structure to allow trusClosed column spacing under the transfer structure to allow truss effects effect

    at transfer structure to minimize the deformation of transfer stat transfer structure to minimize the deformation of transfer structureructure

    ((PrestressedPrestressedtransfer structure is required for large span )transfer structure is required for large span )

    Steel reinforcement percentageSteel reinforcement percentage

    Design as HKDesign as HK CoPCoP 20042004Average steel ratio is around 240~280 Kg/mAverage steel ratio is around 240~280 Kg/m33

    Preliminary size estimation (1.5m ~5m)Preliminary size estimation (1.5m ~5m)

    Depend on the spacing of columns and tower loadingDepend on the spacing of columns and tower loading

    Gravity loadGravity loadas the wall load transmitted tower load to plate levelas the wall load transmitted tower load to plate level

    Wind loadWind loadthe platethe plate behaviourbehaviour as frame structure integrated with columnsas frame structure integrated with columns

    belowbelow

    Normally, the thickness is controlled by shear stressNormally, the thickness is controlled by shear stress

  • 8/4/2019 Building Design b

    18/69

    Loading from towerincluding:

    (P) Axial Load(M) Moment

    (V) Shear

    Transfer Plate Design

    To cater for gravity load andwind load from tower

    structure including axial load,moment and shear

    The transfer plate with

    column below to form a rigidframe structure

    All loadings are transmitted

    to foundation by shear,moment and axial force.

    Podium

    Structure

    Behavior

  • 8/4/2019 Building Design b

    19/69

  • 8/4/2019 Building Design b

    20/69

    Transfer Plate withPrestressed Tendon

  • 8/4/2019 Building Design b

    21/69

    Building DevelopmentAdjacent to Slope

    Retaining structure isrequired for buildingnear the slope

    The extent ofexcavation willdepend on the subsoil

    condition of slope i.e.Rock / Soil

    ????

    ????

    ???

  • 8/4/2019 Building Design b

    22/69

    Building Developmentnear Slope

    Column undertransfer structure

    Transfer Plate

    Walls at Tower

    Large Diameter

    Bored Pile Pile Cap

  • 8/4/2019 Building Design b

    23/69

    Retaining Wall Structure

    Pile Cap

  • 8/4/2019 Building Design b

    24/69

    Retaining structure forsemi-basement

    construction

  • 8/4/2019 Building Design b

    25/69

    Retaining WallStructure with

    deep excavationrequired

  • 8/4/2019 Building Design b

    26/69

    Two levels

    basement toreduce the deep

    excavation

  • 8/4/2019 Building Design b

    27/69

    HONG KONG

    WIND LOAD

    Wind Load

    Assessment Procedure

  • 8/4/2019 Building Design b

    28/69

    Wind Responses of a Building

    Static

    Dynamic

    No movement Wind direction

    - Along wind

    response

    - Cross wind

    response

    - Torsional wind

    response

    EquivalentStatic Load

    WC 2004

    Gust Factor

    Method

    WC 2004

    Literature/ Wind Tunnel Test

    WC 2004

    Wi L A t P

  • 8/4/2019 Building Design b

    29/69

    Win Loa Assessment Proce ure

    (1)

    (i) Open frame with significantresonant dynamic response, or

    (ii) f natural < 0.2Hz, or

    (iii) Significant cross wind /

    torsional resonant response

    (i) fnatural 5 x Min (B, D); or

    H > 100m

    (i) fnatural > 1Hz; or

    (ii) H

  • 8/4/2019 Building Design b

    30/69

    Buildingheight (H)

    Building leasthorizontal dimension(B,D)

    B

    Building on plan

    To determine building

    height (H) and width

    (B,D)

  • 8/4/2019 Building Design b

    31/69

    h

    B

    H

    b

    To define the heightand least dimension

    of building

    Sec A-A

    Sec B-B

    A-A

    B-B

  • 8/4/2019 Building Design b

    32/69

    Wind Load Assessment Procedure (2)

    Calculate Force Coefficients (Cf)

    Height Aspect Factor, ChShape Factor, Cs

    [Appendix D, p.14~15]

    Calculate Force Coefficients (Cf)

    Height Aspect Factor, ChShape Factor, Cs

    Reduction Factor, RA[Appendix D, p.14~16]

    4

    Calculate Gust Response Factor (G)

    [Appendix F, p.19~21]

    2b

    Calculate Total Along-Wind Force

    F = G. Cf . qz .Az[Eqn (3), p. 4]

    Calculate Topography Factor

    [Appendix C, p.10~13]

    Calculate Design Hourly Mean Wind

    Pressure

    [Table 2, p.5]

    Method 2 Slightly Dynamic Building

    Calculate Total Wind Force

    F = Cf. qz .Az[Eqn (1), p. 3]

    5

    Calculate Topography Factor

    [Appendix C, p.10~13]

    3

    Calculate Design Wind Pressure

    (3-sec. gust pressure)

    [Table 1, p.3]

    2a

    Method 1 Static BuildingStep

    Steps 2 - 5

  • 8/4/2019 Building Design b

    33/69

    Wind Code 2004 Only One Terrain

    Open Sea Terrain

    Step 2a Design Wind Pressure/ DesignHourly Mean Wind Pressure

  • 8/4/2019 Building Design b

    34/69

  • 8/4/2019 Building Design b

    35/69

  • 8/4/2019 Building Design b

    36/69

    Wind Profiles Below 200m

    Wind Pressure Profile Under 200m

    0

    50

    100

    150

    200

    250

    0.00 1.00 2.00 3.00 4.00 5.00

    Pressure (KPa)

    Heig

    ht(m)

    1983

    1983

    (Stepwise)

    PNAP150

    2004

    Step 2b Along Wind Dynamic

  • 8/4/2019 Building Design b

    37/69

    The original method was developed by Davenport

    (1967) and Vickery (1966 and 1971)

    In Wind Code 2004, the equation is simplified to:

    (Refer to Wind Code 2004 Appendix F for

    description of the other variables)

    Step 2b - Along Wind Dynamic

    Resonant Response by Gust Factor

    Method (1)

    SEgBgIG fvh

    2

    221 ++=

    St 2b Al Wi d D i R t

  • 8/4/2019 Building Design b

    38/69

    Dynamic resonant response is dependant on the

    magnitude of the fluctuating load as well as its size

    (or scale) in relation to the size of the structure

    The size reduction factor, S, accounts for the

    correlation of pressures over a building and is equal

    to

    The reduction factor, RA, in Table D3 (p.16) does

    not apply to the Gust Factor Method in

    Appendix F

    +

    +

    h

    a

    h

    a

    V

    bn

    V

    hn 41

    5.31

    1

    Step 2b - Along Wind Dynamic Resonant

    Response by Gust Factor Method (2)

    h/

    b/

    representsthe size of the

    wind gust

  • 8/4/2019 Building Design b

    39/69

    Step 3 Topography Factor (1)

    Wind Code 2004 Speed up ratio adopted from BS6399-2:1995

    except that the altitude factor in BS6399-2 wasexcluded

    (In BS6399-2, altitude factor is used to adjust

    the basic wind speed for the altitude of the siteabove seal level.)

    St 3 T h F t (2)

  • 8/4/2019 Building Design b

    40/69

    Step 3 Topography Factor (2)

    St 3 T h F t (3)

  • 8/4/2019 Building Design b

    41/69

    Step 3 Topography Factor (3)

    St 3 T h F t (4)

  • 8/4/2019 Building Design b

    42/69

    Step 3 Topography Factor (4)

    St 3 T h F t (5)

  • 8/4/2019 Building Design b

    43/69

    These examples are taken

    from British reference bookbased on British Code. Due tothe different requirements in

    British Code and Hong KongCode regarding the idealization

    of the hill/slope, the actualhill/slope shall be differentlyidealized under the two Codes.

    These examples from Britishwere for illustration only and

    the method of idealizing thehill/slope should not be copiedfor application to Hong Kong

    Code.

    Step 3 Topography Factor (5)

    Step 3 Topography Factor (6)

  • 8/4/2019 Building Design b

    44/69

    Step 3 Topography Factor (6)

    Step 3 Topography Factor (7)

  • 8/4/2019 Building Design b

    45/69

    Comment: Idealized slope (a) may be more appropriate for Hong Kong Code.

    Step 3 Topography Factor (7)

    Topography FactorTopography Factor (App. C of HK Wind Code)(App. C of HK Wind Code)

  • 8/4/2019 Building Design b

    46/69

    opog ap y actop g p y ( pp C C )( pp )

  • 8/4/2019 Building Design b

    47/69

    Forces on Buildings1. Total Force on a Building

    F = Cf qz Azwhere Cf= force coefficient

    qz = design wind pressure at height z

    Az = effective projected area of that part of the

    building corresponding to qz

    2. The effective projected area of an enclosed building shallbe the frontal projected area

    3. The effect projected area of an open framework buildingshall be the aggregate projected area of all members on aplane normal to the direction of the wind

    4. Each building shall be designed for the effects of windpressures acting along each of the critical directions

  • 8/4/2019 Building Design b

    48/69

    Force CoefficeintsA. For Enclosed Building

    a) Cf = Ch x Cs

    b) From other international codes accetped byBA

    c) For building with isolated blocks projecting

    above a general roof level, individual forcecoefficients corresponding to the heightand shape of each block shall be applied.

    d) For building composed of similar contiguousstructures separated by expansion joints,the force coefficients shall be applied tothe entire building.

  • 8/4/2019 Building Design b

    49/69

    Height Aspect Ratio Ch

    Height Aspect Factor Ch

    1.21.210.0

    1.4-20.0 and over

    1.11.16.0

    1.051.054.0

    1.01.02.0

    0.950.951.0 or less

    20041983

    HeightBreadth

    Remark: Linear Interpolation to obtain intermediate values

  • 8/4/2019 Building Design b

    50/69

    Shape Factors Cs for Enclosed Building

    1.33.0 and over

    1.12.0

    1.01.0 or less

    Csb/dPlan Shape

    d

    b

    wind

    Remark: Interpolate linearly

    Rectangular

    b

    d

    Cs for buildingswith closed

    spacing

  • 8/4/2019 Building Design b

    51/69

    Shape Factors Cs for Enclosed Building

    wind

    Cs for the Respective enclosingrectangular shape in the direction ofthe wind

    Other Shapes

    0.75

    Circular

    CsPlan Shape

    Note:When the actual shape of a building renders it to become sensitiveto wind acting not perpendicular to its face, the diagonal windeffects and torsional wind effects should be considered

    Reduction Factor RA

  • 8/4/2019 Building Design b

    52/69

    Reduction Factor RA

    Gusts are the results of eddies and vortices

    The speed of gust is a function of its duration

    The smaller the size of the gust, the shorter will be its duration and thehigher will be the gust speed

    The larger the size of gust, the longer will be its duration and the lower theaverage gust speed

    A small gust can only create high wind loading on a small local area of thestructure

    The whole structure should be designed with the speed of a gust which isjust big enough to affect the whole structure simultaneously

    A 3 second gust can normally engulf a building with frontal area of 300 to800m2, a longer duration gust is required to be effective on the whole ofthe structure

    A reduction factor is therefore applied when designing buildings of largerdimensions

    (E.C.C.Choi Commentary on 1983 wind codes)

    Not applicable for buildings with significant resonant dynamic responsedesigned by using hourly mean wind pressure

    Reduction Factor RA for Enclosed

  • 8/4/2019 Building Design b

    53/69

    Reduction Factor RA for Enclosed

    Buildings

    0.8015000 and over

    0.8410000

    0.868000

    0.8950000.923000

    0.961000

    0.978001.00500 or less

    2004

    Reduction Factor RAFrontal Projected Area m2

    Note : Linear Interpolation may be used to obtain intermediate values

  • 8/4/2019 Building Design b

    54/69

    Wind Load Case

    X & Y directions are commonly accepted

    Additional wind direction (e.g. diagonal wind

    for Y-shape building) is required For large frontal area building (say >50m),

    additional torsional wind load (10% of long

    face dimension) is required

  • 8/4/2019 Building Design b

    55/69

    Wind Load Distribution

    at Building

    Wind Load Calculation as HK CoP

  • 8/4/2019 Building Design b

    56/69

    Wind Load Calculation as HK CoP

    (Building is considered as significant resonant dynamic structure)

    Wind load

  • 8/4/2019 Building Design b

    57/69

    Wind loadcalculation at each

    floor for a building with40 storey (with 3 floorsabove domestic floor)and the building width

    is 40.23m

    Building structure as

    significant resonantdynamic structure \

    Sa=topography

    factor

  • 8/4/2019 Building Design b

    58/69

    Wind Load Calculation as HK CoP

  • 8/4/2019 Building Design b

    59/69

    Wind Load Calculation as HK CoP

    (Building is not considered as significant resonant dynamic structure)

    Wind loadcalculation at each

  • 8/4/2019 Building Design b

    60/69

    calculation at eachfloor for a building

    with 40 storey (with 3floors abovedomestic floor) andthe building width is

    40.23m

    Building structure

    not considered assignificant resonant

    dynamic structure

    (Note: Total wind

    shear is larger basedon static wind loadapproach for buildingaspect ratio just

    greater than 5)

    Sa = topographyfactor

  • 8/4/2019 Building Design b

    61/69

    COMPUTER MODELING

    Common Structural AnalysisCommon Structural Analysis

  • 8/4/2019 Building Design b

    62/69

    Common Structural AnalysisCommon Structural Analysis

    Software used in Hong KongSoftware used in Hong Kong

    ETABSETABS

    SAP2000SAP2000

    SAFESAFE

    SADSSADS

    GSAGSA STARIIISTARIII

    GTSTRUDLGTSTRUDL

    PAFECPAFEC

    STANSTAN

    Tall Building Modelling AssumptionsTall Building Modelling Assumptions

  • 8/4/2019 Building Design b

    63/69

    Tall Building Modelling AssumptionsTall Building Modelling Assumptions

    1.1. MaterialMaterialAll structuralAll structuralcomponents behavecomponents behavelinearly elastically.linearly elastically.

    2.2. ParticipatingParticipatingComponentsComponentsonly theonly theprimary structuralprimary structural

    componentscomponents participateparticipatein the overall behaviourin the overall behaviour

    3.3. Floor slabsFloor slabsFloor slabFloor slab

    are assumed to beare assumed to be rigidrigidin planein plane unless theyunless theycontain large openingscontain large openingsor are long and narrowor are long and narrow

    in planin plan

    Only the primary

    structuralcomponents are

    put in model

    Rigid in plane

    Tall Building Modelling AssumptionsTall Building Modelling Assumptions

  • 8/4/2019 Building Design b

    64/69

    g g pg g p

    4.4. Negligible stiffnessNegligible stiffnesscomponent stiffness ofcomponent stiffness ofrelatively small magnituderelatively small magnitude

    are assumed negligibleare assumed negligible

    5.5. Negligible deformationsNegligible deformationsdeformations that aredeformations that are

    relatively small and of littlerelatively small and of littleinfluence are neglected.influence are neglected.

    6.6. CrackingCrackingthe effects ofthe effects ofcracking in reinforcedcracking in reinforcedconcrete members toconcrete members toflexural tensile stresses mayflexural tensile stresses maybe represented by abe represented by areduced stiffnessreduced stiffness

    This line should be astraight line in

    assumption due to thesmall deformation

    How to apply wind loading inHow to apply wind loading incomputer model?computer model?

    V

  • 8/4/2019 Building Design b

    65/69

    computer model?computer model?In common building shape

    with the rigid diaphragmassumption, the wind loadshould be applied at the

    geometry centre of each floor

    Windload

    appliedat floor

    Wind load applied at

    centre of frontal area

    What can you find inWhat can you find in

    computer modeling?computer modeling?

  • 8/4/2019 Building Design b

    66/69

    computer modeling?computer modeling?

    Seismic, wind and gravitySeismic, wind and gravity

    analysisanalysis

    Deformation of buildingDeformation of buildingunder different loadingunder different loading

    conditionsconditions

    Member force underMember force underdifferent loading conditionsdifferent loading conditions

    Deflection of building at topfloor including the X & Y

    displacement and Z direction

  • 8/4/2019 Building Design b

    67/69

    d sp ace e t a d d ect o

    rotation

  • 8/4/2019 Building Design b

    68/69

  • 8/4/2019 Building Design b

    69/69

    Q & AIf you have any questions about the structural design, pleaseforward email (with your Name and Student ID no.)

    to :[email protected]