    CustomerService

    IfyouhavequestionsaboutInstallation,operationandMaintenanceoftheUnichillerorwouldliketoorder

    replacementpartspleaseusethefollowingcontactinformation.

    CustomerServiceandTechnicalSupport (7A.M.to5P.M.CentralTime)

    Phone:80052708963144819000

    Fax:3144579000

    WebSite

    Visitwww.unicosystem.comtofindinformationaboutUnicoProducts

    2009Unico

    Inc.

    All

    rights

    reserved

    Thisdocumentissubjecttochangewithoutnotice

    7401AlabamaAve.,SaintLouis,MO631113144819000

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    3/25

    Contents

    GeneralInstructions 1

    PlacementoftheUnichiller 2

    Location 2

    Clearances 2

    RoofRunoff 2

    EquipmentPad 2

    LawnIrrigation 2

    InstallationsNearSaltWater 3

    Electrical 3

    Piping 3

    ChillerPumpCharacteristics 3

    EffectOfWaterTemperatureOnPressureDrop 5

    UseofPropyleneorEthyleneGlycol 5

    Installation 6

    ConnectingChillertoWaterCircuit 6

    ChillerPumpCharacteristics 6

    Electrical 6

    WaterSide

    Only

    Start

    up

    6

    DigitalTemperatureController(DTC) 7

    ProgrammingtheDTC 7

    DTCTroubleShootingandErrorMessages 8

    FullSystemStartup 9

    ChillerMaintenance 10

    TroubleshootingGuide 11

    ChillerWiringDiagrams 12

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    4/25

    1

    GeneralInstructions

    TheUnichillerismanufacturedtomeetUSandEuropeanelectricalrequirements.

    Installationandservicemustbeperformedbyqualifiedinstallerorserviceagency,andmustconformtoallnational,

    state,andlocalcodesofthecountrywhereitistobeoperated.

    UnichillershaveselfcontainedfactorychargedandtestedrefrigerationsystemscontainingeitherR22or

    R407Crefrigerants.Thetypeofrefrigerantandquantityislistedonthefactoryinformationlabellocatedon

    thebackpanel.Itisnotnecessarytoaccesstherefrigerationsystemforsysteminstallationandstartup.

    AllUnichillersaretestedthroughafullcoolingandheatingcyclepriortoshipmentfromthefactory.

    Beforeoperating,besuretheunitisproperlygroundedtopreventinjuryordeath

    fromelectricalshock!

    Disconnect electrical supplybeforewiring unit toprevent injuryordeath from

    electricalshock!

    Do not handle the top half of the scroll compressor as it operates at a

    temperaturehighenoughtocauseseriousinjury.Operationofthechillerwithout

    properfreezeprotectionshallvoidthewarranty.

    Donotoperate this system for longperiodsof timewithwateralone.Aminimumof10%

    propyleneorethyleneglycol isessentialtopreventfreezing.Higherconcentrationsofglyco

    arerequiredtopreventheatexchangerfromrupturingincoldclimates.

    Recommendedoperating temperaturesare115F forhotwaterand40F forchilledwater

    Contact Customer Service if you wish to operate at water temperatures outside of the

    recommendedrange.

    Donotuseanyliquidsolutionotherthanthesolutionofwaterandpropyleneorethyleneglycolinthepiping

    system.ThesolutionmustbemixedinaccordancewiththeguidelinesintheUnichillerDesignManual.

    Pumpmustbeprimed(freeofairandsuctionpipefullof liquid)beforestarting. Ifpump isrundry,rotating

    partswillseizeandmechanicalsealwillbedamaged.

    All electrical wiring should be inaccordance with all local codes and regulations. A field provided electrica

    disconnectshallbeinstalled.Theunitsaresafetycertifiedtosafetycodesofthecountrytheyaresoldin(refer

    toUnichillerSpecificationsBulletinforfurtherdetails).

    Allpipingmustbeinaccordancewithalllocalcodesandordinances.

    Installationshouldbeinaccordancewithalllocalcodesandregulations.

    TheseunitsaredesignedtooperatewithR22orR407Cinaselfcontained,precharged

    refrigerantsystem.Donotaccesstheclosedrefrigerantsystemforanyreasonotherthan

    aftersale,afterinstallationcomponentreplacement.Suchserviceistobeconductedby

    qualifiedpersonnelonly.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    5/25

    2

    PlacementoftheUnichiller

    Location

    Alwayslocatethechilleroutdoors.Neverinstallinsidearoom.

    Installingthe

    unit

    in

    apit

    will

    reduce

    performance

    Locatechillersothatgroundwaterwillnotentercabinet.

    Inareaswithheavysnowfallitisrecommendedthattheunitbeelevated.

    Donotattachductworktothechiller.IfairdeflectorsarenecessarycontactUnicoCustomerService

    forinstructions.

    Clearances

    Thechillermust beplacedtoprovideclearancesonallsidesformaintenanceandinspection.

    1. Atleast24mustbeavailableonthesideofthechillerthataccessesthecontrolbox,pumpand

    compressor.SeeFigure1.

    2. Allowatleast60onthefanside.

    3. Theremainingtwosidesshouldhaveaminimumclearanceof12

    RoofRunoff

    TheUnichillershouldnotbelocatedwherelargeamountsofwatermayrunofffromaroofontoorintothe

    unit.Best

    practices

    dictate

    that

    the

    chiller

    be

    protected

    from

    large

    amounts

    of

    run

    off.

    EquipmentPad

    Placethechilleronaflatsolidsurfacesuchasaconcreteorfabricatedslab.Theslabshouldbeslightlytiltedso

    thatcondensationfromthechillerwillrunofftheslabandnotpoolaroundthechiller.

    LawnIrrigation

    Makesurethatthereareabsolutelynosprinklerheadsnearenoughtothechillerthatwillspraywaterdirectly

    onorintotheunit.Keepinmindthatprevailingwindsmaycarrymistfromsprinklersintothechillercausing

    damagetoelectricalconnectionsandmechanicalparts.

    Figure 1: Unichiller Clearances

    12 inches(0.3 m)

    6 inches (0.15 m) minimum or24 inches (0.6 m) for service

    60 inches(1.5 m)

    service accessside

    air discharge

    air inlet

    air inlet

    12 inches(0.3 m)

    12 inches max(0.3 m)

    shrubs or porous wall

    Maximum height of wallis 4.5 ft (1.4 m)

    Overhang

    TOP VIEW

    FRONT VIEW

    24 inches(0.6 m)

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    6/25

    3

    InstallationsNearSaltWater

    Wheninstallingthechillerincoastalareasnearsaltwateritisbesttoinstallthechillersothatthebuildingis

    betweentheshoreandtheunit.Toimprovethelifetimeitisbesttorequestatechnicoatcondensercoil.

    Electrical

    AllelectricalconnectionssuppliedtothechillermustmeetNationalandlocalcodes.

    Checkforproperlinevoltageforthechillerandblowermodulesifused.Lowlinevoltagesmayrequirethe

    useofasoftstartupgrade.CheckwithCustomerServicetodeterminewhetherornotasoftstartupgradewill

    benecessary.

    Piping

    Makesureallpipesizingconformstoflowrequirements.

    Recommendedchillerpipingconnectionsis1minimum.

    Airinthepipingsystemcandamagethepumpseals.Makesurethatinthecaseofanonsealedwaterstorage

    systemthatairseparatorsorairventsareplacedininletsideofthepipingsystem.

    ChillerPumpCharacteristics

    Thechillercanbeorderedwithorwithoutaninternalwaterpump.Wheninstallingthechillertotheexisting

    watercircuititmaybenecessarytotroubleshootthewatercircuit.Figure2outlinesimportantdataregarding

    chillercharacteristicswithandwithoutthepumptoaidinthetroubleshootingprocess.

    0 5 10 15 20 25

    0

    5

    10

    15

    20

    25

    30

    35

    0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4

    0

    25

    50

    75

    100

    125

    150

    175

    200

    225

    0

    10

    20

    30

    40

    50

    60

    70

    80 PumpCurve

    ExternalStaticPressure(UniChillerwithpump)

    InternalPressureDrop(UniChillerwithoutpump)

    0601.UCH(R)06041,22.UCH(R)06043

    3.UCH(R)06046,7,8

    4.UCH(R)03641,2

    5.UCH(R)03643

    6.UCH(R)03646,7,8

    R0843:Catalog4

    6/3/2009

    PressureDifference

    Water Flow Rate

    GPM

    UniChiller models UCHR

    PSI

    16 2345

    036

    1/60/230V

    1/60/264V

    1/50/260V

    L/s

    GPM

    kPa

    ft.water

    Figure2. Waterflowandpressuredifferentialsforvariouschillermodels.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    7/25

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    8/25

    5

    EffectofWaterTemperatureonPressureDropThetemperatureofthewatercanaffectthepressuredroponthechillersystemTable2liststhecoefficients

    usedtocalculatepressuredropduetotemperature.

    Table2.PressureDropCorrectionFactorBasedonTemperature(forwater)

    TemperatureF 32 40 50 60 68 90 100 110 120 130

    C (0) (4.4) (10) (15.6) (20) (32.2) (37.8) (43.3) (48.9) (54.4)

    Factor

    1.16

    1.12

    1.05 1.03 1.00 0.93 0.91 0.89

    0.86

    0.84

    UseofPropyleneorEthyleneGlycolTheChillercanreachwatertemperatureswellbelowfreezing.Thereforeitisrecommendedthatthewater

    systembechargedwithaminimum10%glycolsolution.Higherpercentagesofglycolwillbenecessarywhen

    thechillerisoperatedinregionsofthecountrywhereoutdoortemperaturesfallbelowfreezing. Table3gives

    therecommendedglycolpercentagesdependingontheexpectedlowtemperaturesfortheregion.

    Table3. Percentageofpropyleneglycolsolutionnecessarytoprotectchillersystemincoldweather.

    %PropyleneGlycol 10% 20% 30% 40% 50%

    Minimum

    Ambient

    Temperature

    F 26 18 8 7 29

    C 3.3 7.8 12.8 21.7 33.9

    Thepercentageofpropyleneglycolcanaffectthepressuredroponthesystem.Table4liststhecorrection

    factorsrecommendtocalculatepressuredropbasedonthepercentageofglycolinthesystem.

    Table4. PressureDropCorrectionFactorBasedonPercentageofGlycol

    %Glycol

    0

    10

    20

    30

    40

    50

    PropyleneGlycol 1.00 1.10 1.20 1.34 1.50 1.65

    EthyleneGlycol 1.00 1.00 1.06 1.16 1.25 1.36

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    9/25

    6

    ChillerInstallationConnectingthechillertoinstalledplumbingMakesureallpipesizingconformstoflowrequirements.

    1. ChillerPipingconnections:

    a. Supply1NPT

    b. Return11/4NPT

    2. Unitswithoutpumpsareprovidedwithaflowmeter.

    3. Whenattaching

    piping

    to

    chiller

    double

    wrench

    to

    prevent

    damage

    to

    chiller.

    4. Installstrainer(suppliedtochiller)intoreturnline.

    5. Installfullportisolationvalvesinsupplyandreturnpiping.

    6. Onmultiplechillerinstallations,installacheckvalveinsupplylinesofeachchiller.

    7. Installallpipingvalvesflowregulators,pumpsandstoragetankspersystemdesign.

    8. Locateallventsathighpointsofpipingsystemforeasyventing.

    9. Makeaccommodationsforfillingsystemandaddingglycoltosystem10%glycolminimumrequired.

    ElectricalInstallation

    1. Installlinevoltagewiringincludingmanualdisconnectatunitperlocalcode.

    2. Seewiringdiagramonunitorindocumentationpacketforspecificconnectioninformation.

    3.

    Install

    low

    voltage

    control

    wiring

    per

    code.

    See

    wiring

    diagram

    on

    unit

    or

    in

    documentation

    packet

    forspecificinformation.

    Therearemanypossiblecontrolwiringvariations.Consultwiringdiagramsinbackofbulletinformost

    commonhookups.AdditionalwiringinformationcanbeobtainedbycallingUnicocustomerserviceat

    18005270896.

    WaterSideOnlyStartUp

    1. RemoveServiceaccesspanelfromchiller.Removechillertoppanel.

    2. DisconnectorangeJumperfromterminalS1toS1ontheprintedcircuitcontrolboard.Thiswilldisable

    thecompressorcontrolcircuit.

    3. Fillsystemwithwateronly.Donotuseaglycolsolution.Youmayneedtodrainthesystemtorepair

    leakswhichwouldmeanhavingtorecovertheglycol.

    4. Checkforleaks.

    5. TurnchillerpumponusingtheON/AUTOswitchonthecontrolboard.

    6. Bleedairoutofthesystemandadjustflowrates.Usethechartsbelowtosetflowratebymeasuring

    pumpcurrentdraw.Designflowratefor3Tonchillersis7.2gpmand

    5Tonchillersare12.0gpm.Ifthereisnoflowmeterinthehydronicsystemflowratecanbe

    determinedbythecurrentdrawonthepump.Refertotablexforampdrawonvariouschillemodels

    attherecommendedflowrates.

    7. Checksecondarypumpoperationandflowratesifapplicable.

    8. Checkforleaks.

    9. Itis

    recommended

    that

    system

    be

    leak

    tight

    prior

    to

    starting

    full

    operation.

    10.Oncewatersystemisfreeofleaksthesystemshouldbedrainedandthewaterreplacedwitha

    minimum10%glycolmixture.Table3liststhepercentageofpropyleneglycolsolutionrecommended

    basedonminimumambienttemperaturesexpectedintheareatheunitisinstalled.Unico

    recommendsthoroughlymixingthepropyleneglycolwithwaterbeforeaddingtothesystem.

    11.Insulatepipingtolimitheatlossandsweating

    12.Restartsystemandventair.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    10/25

    7

    DigitalTemperatureController(DTC)

    Programming the DTC

    1. PressSet keytoenterprogrammode.

    2. AnnunciatorwilldisplayeitheranFforFahrenheitoraCforCelsius. Usetheupordownarrow

    keystotogglebetweenthetwoselections.PressSetwhenthedesiredtemperaturescale hasbeen

    selected.PressSetkeyto inputthescaleandmovetothenextsetting.

    3. Annunciatorwill

    now

    display

    S1

    heating

    set

    point.

    Use

    the

    up

    or

    down

    arrow

    keys

    to

    change

    the

    set

    point.Reccomendedheatingsetpointforstartuppurposesis115F.Presssetkeytoinputdesired

    temperaturevalueandmovetonextsetting.

    4. AnnunciatorwillnowdisplayablinkingDIF1theheatingdifferential temperaturesetting.

    Recommendedsettingis10.Usetheupanddownarrowkeystosetto10.Presssetkeytoinput

    desiredtemperaturevalueandmovetonextsetting.

    5. AnnunciatorwillnowdisplayC1/H1CoolingorHeatingmode.Useupordownarrowkeytotoggle

    betweenC1andH1.ChooseH1.PressSetkey.

    6. AnnunciatorwillnowdisplayablinkingS2Coolingsetpoint.Useupanddownarrowkeystoselect

    thedesired

    temperature.

    Recommended

    cooling

    temperature

    at

    start

    up

    is

    44

    F.

    Press

    set

    key

    to

    inputdesiredtemperaturevalueandmovetonextsetting.

    7. AnnunciatorwillnowdisplayablinkingDIF2CoolingDifferentialTemperature.Recommended

    settingis10.Usetheupanddownarrowkeystosetto10.Presssetkeytoinputdesired

    temperaturevalueandmovetonextsetting.

    8. AnnunciatorwillnowdisplayC2/H2CoolingorHeatingmode.Useupordownarrowkeytoselect

    C2.Presssetkeytoinputdesiredtemperaturevalue.andmovetonextsetting.

    9. DTCwillnowbeinoperatingmodeandwilldisplaycurrentwatertemperature.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    11/25

    8

    DTCTroubleShootingandErrorMessages

    Whennotworkingproperly,theDTCwilldisplayerrorcodesontheannunciator.Adescriptionoftheerror

    codes,whatconditionmaycausethecodetocomeupandhowtocleartheerrorarelistedintable5.

    Table5. DTCTroubleshootingErrorMessages

    Display

    Message

    Description ToCorrect

    E1Appearswheneithertheup ordown

    keyispressedwhennotintheprogramming

    mode.

    IftheE1messageappearseven

    whennokeysarebeingpressed,

    replacethecontrol.

    E2Appearsifthecontrolsettingsarenot

    properlystoredinmemory.

    Checkallsettingsandcorrectif

    necessary.

    EPAppearswhentheprobeisopen,shortedor

    sensingatemperature

    that

    is

    out

    of

    range.

    Checktoseeifthesensed

    temperatureisoutofrange.If

    not,checkforprobedamageby

    comparingittoaknownambient

    temperaturebetween30Fand220F.Replacetheprobeif

    necessary.

    EEAppearsiftheEEPROMdatahasbeen

    corrupted.

    Thisconditioncannotbefield

    repaired.Replacethecontrol.

    CL Appearsifcalibrationmodehasbeenentered.

    Removepowertothecontrolfor

    atleastfiveseconds.Reapply

    power.IftheCLmessagestill

    repairs,replacethecontrol.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    12/25

    9

    FullSystemStartUp

    1. Shutdownmainpowertochiller,

    2. ReconnectorangewiretoterminalsS1andS1oncontrolboard.

    3. Turnonmainpowertochillers,AirHandlers,PumpsandControls.

    4. UseRun/Autoswitchonchillercontrolboardtooperatechiller.

    5. Using Table6determinethecorrectswitchpositionsforthedesiredchilleroperation.

    Table6. Chilleroperationasdeterminedbycontrolboardswitchpositions.

    Run/AutoSwitch

    Position

    Heat/CoolSwitch

    PositionResultingChillerOperation

    Run Heat Heatingmodeonly.WatertemperaturecontrolledbyDTC.

    Run Cool CoolingModeonly.WatertemperaturecontrolledbyDTC.

    Auto Heat Externallycontrolledheatingonly.

    Auto Cool Externallycontrolledheatingandcooling.

    6. Checkflowratesthroughsystemandadjustasnecessary.

    7. Duringnormaloperationthereshouldbea810Ftemperaturedifferencebetweenwatergoinginto

    thechillerandwatercomingout.Temperaturedifferencesgreaterorlessthan810mayindicatea

    waterflowproblem.

    8. After24hoursruntimeremovestrainerandcleanfilterscreenofdirtanddebris.Thescreencanbe

    removesbutshouldberetainedincaseitisnecessarytodoanymajorrepairsorupgradesonthewater

    system.

    9. Accessingrefrigerantsystemisnotnecessaryundernormalcircumstances.

    10.Fillout

    bulletin

    30

    101

    unichiller

    service

    report.

    Leave

    acopy

    with

    the

    customer

    and

    retain

    one

    for

    yourfiles.

    11.Ifchillerdoesnotoperateproperly,refertothetroubleshootingguideinthismanualorcontactUnico

    Customerserviceat8005270896.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    13/25

    10

    UnichillerMaintenance

    ThefollowingaretheperiodicmaintenancerequirementsofUnichillers

    1. Cleanthecoilsurfacesatleasttwiceayearorwhenvisiblydirtybyhosingthecoilwithwater.Usinga

    coilcleanerisoptional.

    Donotusehighpressuresprayertocleanthecoilasthismaydamageor

    flattenthefins.

    2. Ifthereistheproperleveloffreezeprotectioninthelines,thereisnoneedtodrainthesystemifitwil

    notberunoverthewintermonths.Unicorecommendsusingpropyleneglycolforfreezeprotection.

    RefertoTable3forrequiredpercentagesofpropyleneglycol.

    Tomeasurethefreezeprotectionlevelinthesystemtakeasampleofthefluidthroughthedrainor

    storagetankanduseanantifreezetesteroranantifreezerefractometerthatissuitablefortheglycol

    (ethyleneorpropylene)thatisused inthesystem.

    3. Ifthechilleristobedrainedoverthewintermonthsitisimportantthatallwaterisremovedfromthe

    heatexchanger.DrainsystemfromtheInletconnection.Useawet/dryvacuumtoremoveresidual

    water.Orblowtheexcesswateroutfromtheoutputwaterconnection.

    4. TheUnichillersareprechargedwithR22orR407Crefrigerants.Onlyexperiencedlicensedrefrigerant

    servicepersonnelshouldcheckthechargeandrepairleaksshouldtheyoccur.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    14/25

    11

    TroubleshootingGuide

    Theprintedcircuitboardhastestpointswhichcanbeusedfortroubleshooting.Whentroubleshootinginsert

    thecommonprobeofthevoltmeterintotheCOMterminalonthecircuitboardandprobethetestpointsfor

    voltagereadings.Table7listscommontroubleshootingtestpointsandwhatitmeanswhentheyread24V+/

    2volts.

    Socket For Common Probe

    From Volt Meter

    Figure4. CloseupoflowerleftHandcornerofprintedcircuitboardshowingsometestpinscommonprobe

    socket.

    Table7. LowVoltageTestPinsat24VAC

    TestPin

    NumberAreadingof24Vfromthetestpinlistedtocommonindicatesthefollowing:

    19 Chillerhaspower;Transformerconnectedandgood

    6

    Externalcall

    for

    chiller;

    enable

    pump

    18 Flowswitchortimerisclosed

    14 Externalcallforcompressor

    13 HighPressureSwitchisclosed

    12 LowPressureSwitchisclosed(ordefrostrelayisenergizedifindefrost)

    17 DigitalTemperatureControllerCallingforHeatingorCooling

    8 TimerIsNotInTimeDelayMode;ContactorIsEnergized

    7 NotinDefrostOrDefrostPressureSwitch(DPS)IsClosedDueToHighPressure

    9PressuresNormal,LowAmbientPressureSwitch(ifcooling)MildWeatherPressure

    Switch(ifheating)areclosed;Fanrelayisenergized

    10

    FanRelay

    Is

    Energized

    4 InDefrostMode;Defrostrelayisenergized

    1 ExternalCallForHeatMode

    Table8. HighVoltageTestPins

    22and24 UnitiscorrectlyPowered

    22and23 FanRelayIsClosed(FanShouldBeOn)

    22and21 PumpRelayisClosed(PumpRelayShouldbeOn)

    22and26 HeaterRelayIsClosed(ShouldBeInDefrostMode)

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    15/25

    12

    The following table is to be used for troubleshooting problems that may occur with the chiller. This table

    shouldbeusedonlyiftherearenomodificationstothecontrols.

    Table9a:UnichillerTroubleshootingChart Main

    Problem ProbableCause CorrectiveAction

    Uponstartupnothinghappens

    Powernotgettingtothechillerorthe

    controlboard.

    Checkpowercomingintotheunit.

    ConfirmAuto/RunSwitchissettoRun.

    Testfor230VbetweenTP22andTP24.

    277Vfor3p/460Vchillersunitis

    correctlypowered.

    Checkcircuitboardterminalblockfor24

    voltsbetweenRandCBoardpowered

    up.

    BypassTimerBad

    Pumpdoes

    not

    come

    on.

    Waterflowrestricted,defectiveflow

    switch,pumprelaynotclosed Seepumptroubleshooting.

    Pumpdoesnotstayon

    Nowaterinthesystem. Putwaterinthesystem.

    Watertemperaturesetpointistoo

    high/low.

    Adjustthetemperaturecontrollerset

    point(nolowerthan38Fforcooling,no

    higherthan125Fforheating).

    Faultytemperaturecontroller.Checktheoperationofthetemperature

    controller. Iffaulty,replace.

    NoLowvoltageCheckfor24Vontransformer.Fuseon

    controlboard

    Unichillershutsdowncompletely

    (includingthepump).

    Openflowswitch(Liquidsolutionis

    interruptedorairinthesystem).Checkforairordebrisinthesystem.

    Table9b:UnichillerTroubleshootingChart Compressor

    Problem ProbableCause CorrectiveAction

    Compressorandfanmotorsshutdown

    beforethesetwatertemperatureis

    reached.

    Openlowpressureswitch.

    Checkforarefrigerantleak,inoperative

    thermalexpansionvalve,lowliquid

    solutioncontrolsetting,lowambient

    operation,orlowliquidsolutionflow.

    OpenCompressortimedelay

    BadDefrostBoard

    BadDTC

    Openhigh

    pressure

    switch.

    Checkforadirtycondenser,inoperable

    fanmotor(s),

    or

    the

    re

    circulation

    of

    condenserair.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    16/25

    13

    Table9c:UnichillerTroubleshootingChart Pump

    Problem ProbableCause CorrectiveAction

    Pumpshutsoffshortlyafterthepoweris

    appliedfrom

    the

    circuit

    breaker

    with

    switchturnedtocoolorheatposition.

    Airinthesystemorlackofwaterinthe

    system.

    Purgetheairinthesystembyopeningthe

    ventplugonthepump. Installautoair

    vent.Checkwyestrainer.

    Lowwater

    flow.

    Check

    pipe

    sizing

    and

    operation

    of

    the

    pump.Flowswitchwillopenatflowrates

    lessthan3gpm.

    Faultyflowswitch.Checkcontinuityoftheflowswitch. If

    faulty,replace.

    Table9d:UnichillerTroubleshootingChart Other

    Problem ProbableCause CorrectiveAction

    Airinthesystemorlackofwaterinthe

    system.Waterleak.

    Checkforcrackedpipeorloosefittings.

    Repair,ifnecessary.

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    17/25

    14

    ThisPageIsIntentionallyLeftBlank

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    18/25

    14

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    19/25

    15

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    20/25

    16

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    21/25

    17

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    22/25

    18

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    23/25

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    24/25

    20

  • 8/3/2019 Bulletin 30-32-2011-01_ Chiller Installation Manual

    25/25