CKT.
NO.
POLETRIP A POLEC TRIP
BREAKER BREAKERPHASE
CKT.
NO.
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
LOAD
DESIGNATION
LOAD
DESIGNATION
PANELBOARD SCHEDULE
B
RATING:
DESIGNATION: REMARKS: SERVICE ENTRANCE RATED
225 AMPS
MAIN: 150A MCB
SERVICE: 120/208V, 3Ø, 4W
MOUNTING: SURFACE
S.C. RATING: 30,000A RMS SYM.PPH1
LOCATION: ELECTRICAL CABINET
--
100EXISTING PANEL
SPACE
SPACE
SPARE
SPARE
20SPARE
20RECEPTACLES
20RECEPTACLES
20RECEPTACLES
20RECEPTACLES
20RECEPTACLES
20RECEPTACLES
20RECEPTACLES
20CABINET LIGHTING AND RECEPTACLE
SPACE
SPACE
SPACE
SPACE
20
RECEPTACLES
20
RECEPTACLES
20
RECEPTACLES
30
-
30
TVSS
30
-
20
RECEPTACLES
20
RECEPTACLES
20
SITE LIGHTING
20
SITE LIGHTING
20SITE LIGHTING
ELECTRICAL ONE LINE DIAGRAM
UTILITY METER
GFI
S
LIGHT FIXTURE
WEATHERPROOF ELECTRICALENCLOSURE ON CONCRETE PAD.REFER TO DETAIL ON DRAWINGE1.02 FOR ADDITIONALREQUIREMENTS
2"C., 4#2/0 & 1#6GND
ELECTRONIC TIME CLOCK ANDMANUAL TIME ADJUSTABLEOVERIDE SWITCH QUANTITY ASREQUIRED.
M
REFER TO DRAWING E1.01FOR CONDUIT AND WIRE
REQUIREMENTS ANDROUTING
EXISTING UTILITYRISER POLE
UNDERGROUND ELECTRIC LINE
PP-1,3
ELECTRICAL SYMBOL LIST
WP WEATHERPROOF
POLYVINYL CHLORIDE CONDUIT
RIGID GALVANIZED STEEL CONDUIT
XFMR
RSC
V
TRANSFORMER
VOLTS
PVC
NTS
NIC
PNL
NOT TO SCALE
PANELBOARD
NOT IN CONTRACT
MECHANICAL CONTRACTOR
GROUND FAULT INTERRUPTER
MAIN CIRCUIT BREAKER
MTD
MCB
MLOMC
KW
MOUNTED
KILOWATT
MAIN LUGS ONLY
GND
JB
GFI
GC
JUNCTION BOX
GROUND
GENERAL CONTRACTOR
ELECTRICAL CONTRACTOR
ELECTRIC METALLIC TUBING
CONDUITC
EMT
CKT
CB
EC
CIRCUIT
CIRCUIT BREAKER
BKR
A AMPERE
BREAKER
RACEWAY AND WIRING
MISCELLANEOUS
AMPERE FRAMEAF
AMPERE TRIPAT
LIGHTING
1. DRAWINGS ARE DIAGRAMMATIC ONLY. THE EXACT LOCATION, MOUNTING HEIGHTS,
SIZE OF EQUIPMENT AND ROUTING OF RACEWAYS SHALL BE COORDINATED AND
DETERMINED IN THE FIELD.
2. WORK SHALL CONFORM TO THE MASSACHUSETTS ELECTRICAL CODE AND
MASSACHUSETTS BUILDING CODE AND REQUIREMENTS OF LOCAL AUTHORITIES
HAVING JURISDICTION.
3. THE WORD "CONTRACTOR" AS USED IN THE "ELECTRICAL WORK" SHALL MEAN THE
ELECTRICAL CONTRACTOR.
4. CONTRACTOR SHALL PAY FOR ALL PERMITS, INSURANCE AND TESTS, AND SHALL
PROVIDE LABOR AND MATERIAL TO COMPLETE THE ELECTRICAL WORK SHOWN.
5. CONTRACTOR SHALL PAY ELECTRIC UTILITY COMPANY BACKCHARGES AND PROVIDE
COORDINATION WITH SAME.
6. EXCEPT AS OTHERWISE NOTED, THE ELECTRICAL WORK SHALL INCLUDE
PANELBOARDS, CIRCUIT BREAKERS, FEEDERS, WIRING, RACEWAYS, LIGHTING
FIXTURES, DEVICES, SAFETY SWITCHES, MOUNTING AND WIRING, TRANSFORMERS
AND CONNECTIONS NECESSARY TO OPERATE ALL EQUIPMENT.
7. DURING CONSTRUCTION, THE ELECTRICAL CONTRACTOR SHALL KEEP HIS PORTION
OF THE WORK NEAT, CLEAN AND ORDERLY.
8. ALL SYSTEMS SHALL BE TESTED FOR SHORT CIRCUIT AND GROUNDS PRIOR TO
ENERGIZING AND ANY DEFECTS SHALL BE CORRECTED.
9. ALL CUTTING, PATCHING AND TRENCHING REQUIRED FOR ELECTRICAL WORK SHALL
BE INCLUDED AS PART OF THIS SECTION.
10. COMPLETE SHOP DRAWINGS SHALL BE SUBMITTED FOR ELECTRICAL EQUIPMENT.
WHERE SPECIFIED, ELECTRICAL EQUIPMENT IS SUBSTITUTED. THE ELECTRICAL
CONTRACTOR SHALL SUBMIT COMPLETE SPECIFICATIONS ON THE SUBSTITUTE AS
WELL AS THE ITEM ORIGINALLY SPECIFIED.
11. MATERIALS SHALL BE SPECIFICATION GRADE AND UL LISTED.
12. WHERE MATERIAL IS CALLED OUT IN THE LEGEND BY MANUFACTURER, TYPE OR
CATALOG NUMBER, SUCH DESIGNATIONS ARE TO ESTABLISH STANDARDS OR
DESIRED QUALITY. ACCEPTANCE OR REJECTIONS OF PROPOSED SUBSTITUTIONS
SHALL BE SUBJECT TO THE APPROVAL OF THE OWNER.
13. WORK SHALL BE COORDINATED WITH EXISTING CONDITIONS TO ELIMINATE
INTERFERENCES.
14. ELECTRICAL WORK SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM
DATE OF WHICH SYSTEM IS PUT INTO SERVICE.
15. WORK SHALL BE GROUNDED IN ACCORDANCE WITH CODE REQUIREMENTS.
COMPLETE EQUIPMENT (INSULATED GREEN WIRE) GROUNDING SYSTEM SHALL BE
INSTALLED.
16. WIRING METHODS:
A. BELOW GRADE WIRING SHALL BE SCHEDULE 40 PVC.
19. PANELBOARDS SHALL BE DEAD FRONT, THERMAL MAGNETIC BOLT-ON CIRCUIT
BREAKER TYPE, DESIGNED FOR SURFACE MOUNTING AS INDICATED ON PLAN, AND
HAVING CONNECTIONS TO 120/240 VOLT, 3 PHASE, 4 WIRE SERVICE. ALL BUS BARS
SHALL BE COPPER. CABINETS SHALL BE MADE OF CODE GAUGE GALVANIZED SHEET
STEEL, WITH A MINIMUM OF 4 INCH GUTTERS, DOOR IN DOOR CONSTRUCTION,
LOCKED DOOR, AND FLUSH HINGES. TYPEWRITTEN INDEX SHALL BE MOUNTED ON
DOOR INSIDE TRANSPARENT COVER INDICATING LOAD SERVED. PANELS SHALL
INCLUDE SEPARATE EQUIPMENT GROUND BUS.
20. CONDUIT RUNS AS SHOWN ON THE PLANS ARE DIAGRAMMATIC ONLY; EXACT
LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD.
21. CONTRACTOR SHALL CHECK EXISTING CONDITIONS TO DETERMINE EXACT EXTENT
OF WORK TO BE PERFORMED PRIOR TO BIDDING. DIMENSIONS RELEVANT TO
EXISTING WORK SHALL BE VERIFIED IN THE FIELD.
22. PROVIDE AS-BUILT "CADD" DRAWINGS AT THE COMPLETION OF THE PROJECT.
23. ALL EXCAVATION AND BACKFILL SHALL BE BY THE ELECTRICAL CONTRACTOR.
GENERAL ELECTRICAL NOTES :
HANDHOLE SEE DETAIL ON E1.3 THIS DRAWING
-HOMERUN TO PANELBOARD, NUMBER OF SLASH MARKS INDICATES NUMBER OF #12 AWG CONDUCTORS INMINIMUM 3/4" CONDUIT. NO SLASH MARKS INDICATE 2#12 & 1#12G, 3/4"C UNLESS NOTED OTHERWISE. -GREENGROUND CONDUCTOR IS NOT INDICATED BUT SHALL BE INCLUDED IN EACH RACEWAY. SIZE SHALL BE #12UNLESS INDICATED OTHERWISE. -HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE PHASECONDUCTORS (ONE PER PHASE) PLUS NEUTRAL AND GROUND CONDUCTOR IN EACH CONDUIT.
ABBREVIATIONS
DEMOLITION NOTES:
1. THE ELECTRICAL CONTRACTOR WILL DEMOLISH THE EXISTING
ELECTRICAL SYSTEMS ASSOCIATED WITH ALL EXISTING
EQUIPMENT TO BE REMOVED. THE ELECTRICAL CONTRACTOR IS
TO DEACTIVATE, DISCONNECT AND REMOVE THOSE SYSTEMS
WHICH WILL BE DEMOLISHED. THE ELECTRICAL CONTRACTOR
WILL REMOVE AND DISPOSE OF ALL ELECTRICAL SYSTEM
MATERIALS INCLUDING DEVICES, FIXTURES, RACEWAYS, CABLE
AND APPURTENANCES.
2. MAKE ANY NECESSARY RE-CIRCUITING, EXTENSIONS OF EXISTING
CIRCUITS AND RELOCATIONS REQUIRED TO PROPERLY RE-ENERGIZE
REMAINING EXISTING SERVICES OR EQUIPMENT THAT MAY BE
INTERFERED WITH BY NEW CONSTRUCTION, REMOVALS OR
RELOCATIONS. ALL SHUT DOWNS TO RELOCATE ACTIVE FEEDERS
OR BRANCH CIRCUITS WILL BE PERFORMED ON HOURS MUTUALLY
AGREED TO WITH THE OWNER.
3. PRIOR TO REMOVAL OF EQUIPMENT, CONFIRM THAT FEEDER AND
BRANCH CIRCUITS ARE NO LONGER ACTIVE. SHOULD IT BE
DISCOVERED THE FEEDER OR BRANCH CIRCUITS ARE ACTIVE,
NOTIFY THE ENGINEER IMMEDIATELY FOR DIRECTION.
4. EXISTING ABANDONED HIGH AND LOW TENSION SYSTEMS ARE TO BE
REMOVED. UNDER NO CIRCUMSTANCES ARE ABANDONED HIGH AND
LOW TENSION SYSTEMS OR SYSTEM COMPONENTS TO REMAIN.
GFI
2"C., 4#2/0 & 1#6GND
XM
XR
XM
TVSS
WP
A
4
XM
4
LOCKABLE FUSEDDISCONNECTSWITCH
6
4
20
20
08/09/2017Date:
BURLINGTON
COMMONS
CENTER STREET
BURLINGTON, MA 01803
Drawn By:
Reviewed By:
Approved By:
Drawing Title:
Sheet Number:
Seal:
Revisions:
No. Date Description
Project:
TOWN OF BURLINGTON, MA
Consultants:
W&S Project No:2170150
COPYRIGHT 2017 WESTON & SAMPSON
Scale:
978.532.1900
www.westonandsampson.com
800.SAMPSON
Issued For:
Weston & Sampson Engineers, Inc.
Five Centennial Drive,
Peabody, MA 01960
ELECTRICAL
LEGEND,
ABBREVIATIONS
AND GENERAL
NOTES
E1.00
NONE
DNM
RFM
RFM
EXISTING ELECTRICAL
CABINET (SEE PHOTO #3)
EXISTING ELECTRICAL
SERVICE DROP TO BE
REMOVED (SEE PHOTO #1)
EXISTING ELECTRICAL
SERVICE TO BE REMOVED
(SEE PHOTO #2)
EXISTING ELECTRICAL
CABINET TO BE REMOVED
(SEE PHOTO #2)
EXISTING ELECTRICAL
CABINET TO REMAIN
EXISTING FLOOD
LIGHT
XM
XR
XM
XM
XM
XM
XM
XM
XR
XM
XM
XM
XM
XR
XR
XM
XM
XM
XM
XM
XM
XM
XR
XR
XR
XR
XR
XR
XR
XR
XR
XR
XR
XR
XR
XM
XM
XR
EXISTING POLE LIGHT
FIXTURE TO REMAIN AND BE
REWIRED. (SEE NOTE #2)
(TYPICAL)
EXISTING
FLOOD LIGHT
XM
XM
EXISTING
SPOT LIGHTS
EXISTING
TRAFFIC
CABINET
XM
XM
EXISTING ELECTRICAL
CABINET TO REMAIN
EXISTING IN-GROUND
LIGHT FIXTURE
EXISTING IN-GROUND
LIGHT FIXTURE
EXISTING IN-GROUND
LIGHT FIXTURE
EXISTING UNDERGROUND
ELECTRIC SERVICE TO BE
REMOVED (SEE PHOTO #3)
XR
EXISTING UNDERGROUND
ELECTRIC SERVICE
FEEDING PANELS UNDER
BANDSTAND TO BE
REMOVED (SEE PHOTO #1)
T
EXISTING UTILITY COMPANY
POLE MOUNTED TRANSFORMER
T
EXISTING UTILITY COMPANY
POLE MOUNTED TRANSFORMER
EXISTING GAZEBO
XM
XM
XM
EXISTING TREE MOUNTED
RECEPTACLE TO BE REMOVED
(TYPICAL)
EXISTING LIGHT POLE
FIXTURE WITH BASE
MOUNTED RECEPTACLE TO
BE REWIRED. SEE NOTE #1
(TYPICAL)
EXISTING PANEL BOARD MOUNTED UNDER GAZEBO TO
REMAIN AND BE RE-FED FROM NEW SERVICE, SEE
DRAWING E1.02. ALL EXISTING POWER AND
COMMUNICATIONS EQUIPMENT UNDER GAZEBO SHALL
REMAIN.
08/09/2017Date:
BURLINGTON
COMMONS
CENTER STREET
BURLINGTON, MA 01803
Drawn By:
Reviewed By:
Approved By:
Drawing Title:
Sheet Number:
Seal:
Revisions:
No. Date Description
Project:
TOWN OF BURLINGTON, MA
Consultants:
W&S Project No:2170150
COPYRIGHT 2017 WESTON & SAMPSON
Scale:
978.532.1900
www.westonandsampson.com
800.SAMPSON
Issued For:
Weston & Sampson Engineers, Inc.
Five Centennial Drive,
Peabody, MA 01960
ELECTRICAL SITE
DEMOLITION PLAN
E1.01
1" = 40' - 0"
DNM
RFM
RFM
ELECTRICAL DEMOLITION SITE PLAN
PHOTO NO.2
PHOTO NO.2
PHOTO NO.3
PHOTO NO.1
NOTES:
1. TYPICAL FOR ALL EXISTING LIGHT POLES WITH BASE
MOUNTED RECEPTACLES. EXISTING LIGHT POLE REMAIN
AND BE REWIRED TO NEW CIRCUIT VIA A NEW HAND HOLE.
EXISTING LIGHT POLE BASE MOUNTED RECEPTACLE TO BE
REPLACED AND REWIRED TO NEW CIRCUIT.
2. TYPICAL FOR ALL EXISTING LIGHT POLES AND GROUND
MOUNTED SPOT, FLOOD AND ACCENT LIGHTING EXISTING
FIXTURES ARE TO BE REWIRED TO NEW CIRCUIT.
3. TO THE EXTENT POSSIBLE EXISTING CONDUIT NO LONGER
IS USE SHALL BE REMOVED. ALL EXISTING WIRING IS TO BE
REMOVED.
NEW ELECTRICAL
CABINET
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
XM
XM
XM
XM
XM
XM
XM
XM
XM
XMXM
XM
XM
XM
XM
XM
XM
XM
HANDHOLE (TYPICAL)
(SEE NOTE #2)
EXISTING UTILITY RISER POLE
WITH NEW POLE MOUNTED
TRANSFORMERS
C1,C4,C16
2
3
2
2
2
2
9
C1,C4
C1,C4,C16
C4
C1,C16
C1
C1
2" DIRECT BURIED
CONDUIT FOR
SECONDARY POWER
C2,C5,C6
C2,C5,C6
4
5
5
5
5
5
4
4
4
4
4
7
7
7
C6
C2
C2,C5
C2,C6
C6
C6
C5
C6
C6
C2,C5
C5
C1,C4,C16
C4
3
3
3
11
6
6
6
6
6
6
6
6
12
8
12
8
12
10
10
C3
C3,C7,C8,C14
C3,C7,C8
C3,C7,C8,C14
C8
C3,C8
C14
C14
C3,C7,C14
C3,C7
C3,C8
C8
C8
XM
6
C3
4
C2
EXISTING FLOOD
LIGHT
EXISTING
FLOOD
LIGHT
XM
XM
EXISTING
SPOT LIGHT
C1
C3,C11
C3
XM
XM
XM
EXISTING IN-GROUND
LIGHT FIXTURE
EXISTING IN-GROUND
LIGHT FIXTURE
EXISTING
IN-GROUND
LIGHT FIXTURE
NEW POLE MOUNTED
LIGHT FIXTURE OMNI
LIGHT 6130 LED
HERITAGE SERIES
C1,C4
C3,C7,C8,C14
C3,C7,C8,C14
SPEAKER
SPEAKER
GFI
WP
9
C10
GFI
WP
9
C10,C15
C4
SPEAKER
SPEAKER
GFI
WP
8
GFI
WP
8
C7
C7
C9 (SEE NOTE #1)
7
C10,
C15
6
6
6
GFI
WP
8
C12
C12
A
C12
C12
C7
NEW POST MOUNTED
DUPLEX RECEPTACLE
SEE DETAIL 7/E1.03.
(TYPICAL)
GFI
WP
7
GFI
WP
13
GFI
WP
13
GFI
WP
13
GFI
WP
13
GFI
WP
13
C13
C13
C13
C13
C13
C13
GFI
WP
14 1618
C15
GFI
WP
GFI
WP
3
GFI
WP
C4
C16
TERMINATE CONDUCTORS IN
HANDHOLE FOR FUTURE
CONNECTION TO ELECTRONIC SIGN
GFI
WP
8
GFI
WP
7
C6
08/09/2017Date:
BURLINGTON
COMMONS
CENTER STREET
BURLINGTON, MA 01803
Drawn By:
Reviewed By:
Approved By:
Drawing Title:
Sheet Number:
Seal:
Revisions:
No. Date Description
Project:
TOWN OF BURLINGTON, MA
Consultants:
W&S Project No:2170150
COPYRIGHT 2017 WESTON & SAMPSON
Scale:
978.532.1900
www.westonandsampson.com
800.SAMPSON
Issued For:
Weston & Sampson Engineers, Inc.
Five Centennial Drive,
Peabody, MA 01960
ELECTRICAL SITE
NEW WORK PLAN
E1.02
1" = 40' - 0"
DNM
RFM
RFM
ELECTRICAL NEW WORK SITE PLAN
C1SITE LIGHTING1"C., 2#10 & 1#10GND PPH1-2
CONDUIT & WIRING SCHEDULE
CONDUIT
TAG
FEEDER
REMARKS
TOFROM
C2SITE LIGHTING
DIRECT BURIED,VIA
TIMECLOCK CONTROLLED
CONTACTOR
1"C., 2#10 & 1#10GND PPH1-4
C3SITE LIGHTING1"C., 2#10 & 1#10GND PPH1-6
C4SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND
PPH1-3
C5SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-5
C6SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND
PPH1-7
C7
C8
SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-8
SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-10
C9
EXISTING GAZEBO
PANEL
DIRECT BURIED
SEE NOTE 1
2"C., 4#2/0 & 1#6GNDPPH1-27,29
C10SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-9
C11SITE RECEPTACLES
DIRECT BURIED, SEE
SPEAKER NOTES BELOW
1"C., 2#10 & 1#10GNDPPH1-11
C12SPEAKER WIRING DIRECT BURIED1"C. N/A
NOTES:
1. ELECTRICAL CONTRACTOR SHALL RUN NEW CONDUITS UNDERGROUND TO
RE-FEED EXISTING POWER PANEL LOCATED UNDER GAZEBO.
2. FOR EACH EXISTING TO REMAIN SITE PEDESTRIAN LIGHT POLE CONTRACTOR
SHALL PROVIDE A NEW HAND HOLE FROM WHICH NEW POWER FEED TO
EXISTING POLE ENTRANCE AND IF PRESENT EXISTING REPLACED BASE
MOUNTED RECEPTACLE.
SPEAKER NOTES:
1. FROM EACH SPEAKER JACK LOCATION (4 TOTAL) ELECTRICAL CONTRACTOR
SHALL RUN A 1" PVC CONDUIT FROM THE SPEAKER LOCATION TO THE GAZEBO
AND TERMINATE IN A DOUBLE GANG BOX.
2. AT EACH SPEAKER JACK LOCATION. ELECTRICAL CONTRACTOR SHALL FURNISH
AND INSTALL A SINGLE GANG WATERPROOF BOX. (SEE DETAIL 7/E1.03)
DIRECT BURIED,VIA
TIMECLOCK CONTROLLED
CONTACTOR
DIRECT BURIED,VIA
TIMECLOCK CONTROLLED
CONTACTOR
C13SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-13
C14SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-15
C15SITE RECEPTACLES DIRECT BURIED1"C., 2#10 & 1#10GND PPH1-18,20,22
C16FUTURE SIGN DIRECT BURIED1"C., 2#10 & 1#10GND
PPH1-17
3'-0
"
PLAN
1'-6
"
ELEVATION
CONDUIT
NEW ELECTRIC METERMOUNTED TOENCLOSURE
FINISHEDGRADE
3'-0"
3'-0"
EMBEDDED LEVELINGCHANNELS
2-1/2" ANCHOR BOLTS16" ON CENTER
6"2'
-0"
COPPER GROUND ROD3/4"x10' LONG
#5 BARS @ 12" CENTERS
1/4" x 1 1/2" STRAPWELDED TO CHANNEL2'-0" OC
3" MINIMUMCOVER OVERREBAR
NOTE: FINAL CABINET SIZE SHALL BE DETERMINED BASED ON ACTUALEQUIPMENT AND LAYOUT OF EQUIPMENT
PAD MOUNTED ELECTRICAL ENCLOSURE NO SCALE
4
FINISHED GRADE
ANCHOR BOLTS WITH LEVELING
NUTS BY POLE MFR
SELECT COMMON FILL
COMPACTED IN 12" LIFTS
#4 HOOPS AT 12" ON CENTER
8-#5 EQUALLY SPACED
CONCRETE BASE
DIM
"A
"
SE
E T
AB
LE
B
EL
OW
30"
6"
24" DIA
UNDISTURBED
EARTH
POLE HEIGHT
10'-0"
20'-0"
DIMENSION "A"
4'-6"
4'-6"
BOND CIRCUIT GROUND-
ING CONDUCTOR TO POLE
INSULATED GROUNDING
BUSHINGS BONDED
TO POLE (TYPICAL)
POLE WITH HANDHOLE AND
INTERNAL GROUNDING STUD
2" CHAMFER
GROUT
CONDUIT SEE SITE PLAN (TYP)
TYPICAL NEW LIGHT POLE BASE DETAIL NO SCALE3
NOTE:
18"
6"
1'-4"
8" 8"
C TRENCH& CONDUIT
LFINISH GRADE
COMPACTED SUITABLE BACKFILL- BY GENERAL CONTRACTOR
COMPACTED SUBGRADE OR SUITABLEBACKFILL - ALL EXCAVATION ANDBACKFILL SHALL BE BY THEELECTRICAL CONTRACTOR
SCHEDULE 40 PVCCONDUIT, SIZED ASNOTED ON THE PLAN
12"
TYPICAL DIRECT BURIED CONDUIT DETAIL NO SCALE1
PLASTIC CAUTION TAPE -BY GENERAL CONTRACTOR
EXISTING PRIMARY RISER POLE
48" RADIUS x 90° GALVANIZED STEELSWEEP. SPARE SWEEP MUST HAVE ATHREADED CAP AND GROUNDBUSHING JUST ABOVE GRADE. (2) 4"CONDUITS
PVC TO STEEL CONDUITADAPTER
3/4" DIA. x 10'-0" COPPER CLADGROUND ROD
BOND TO GROUND
SPARE (1) 2" CONDUIT (CAPPED)
1" PVC CONDUIT 10'-0" MINIMUMABOVE GRADE
CONCRETE DUCTBANK TO NEWMANHOLES
RGS SERVICE CONDUIT, TERMINATE10'-0" ABOVE FINISH GRADE MIN.
RGS CONDUITCLIP 4'-0" O.C.MIN.
10'-0" ABOVEFIN. GRADE
No. 4 AWG BARE COPPER WIRE
INSULATED GROUND BUSHING
BOND TO GROUND
TYPICAL RISER POLE DETAIL NO SCALE5
17.5"
NOTES:
1. THIS HANDHOLE IS INTENDED FOR NON-DELIBERATE VEHICULAR TRAFFIC ONLY.
2. HANDHOLE SHALL BE PREFABRICATED POLYMER CONCRETE AGGREGATE EQUAL TO QUAZITE OR EQUAL PRE CASTCONCRETE CONSTRUCTION OR APPROVED EQUAL
18.5"
11.5" 13.5"
38" STAINLESS
STEEL BOLTS W/WASHERS(TYPICAL FOR 4)
NON METALLIC SKIDRESISTANT SURFACE
6" MIN
OPENBOTTOM
CRUSHEDSTONE BASE 6"
MIN6"
MIN
18.5"
12" MIN.
TYPICAL PREFABRICATED HANDHOLE DETAIL NO SCALE6
LOAM AND SEED
CONCRETE
18"
6"X6" PRESSURE
TREATED POST
PAINTED WHITE
24"
6"
DECORATIVE CAP (TO BE
APPROVED BY TOWN) PAINTED
WHITE
42" P
OS
T H
EIG
HT
30" T
O B
OT
TO
M O
F
RE
CE
PT
AC
LE
DUPLEX RECEPTACLE GFCI
WITH WEATHERPROOF,
LOCKABLE IN-USE COVER
CONDUIT
18"
POST AND RECEPTACLE DETAIL NO SCALE7
POST AND RECEPTACLE DETAIL NO SCALE8
NEW HANDHOLE
1"C. QUANTITY AND WIRING AS
INDICATED ON DRAWING E1.02
GFI
WP
1"C. WITH WIRING TO FEED
LIGHT AS INDICATED ON PLANS.
1"C. WITH WIRING TO FEED
WHERE PRESENT
RECEPTACLE
EXISTING LIGHT POLE
ALL EXCAVATION, BACKFILL & CONCRETE SHALL BE BY THE
ELECTRICAL CONTRACTOR.
LOCKABLE FUSEDDISCONNECTSWITCH
TYPICAL FOR 4 LOCATIONS
ONLY PROVIDE SINGLE GANG
WATERPROOF BOX TO HOUSE
THE XLR CABLE AND SPEAKER
JACK.
USE 1 1/2" CRUSHEDSTONE BEDDING IF
WATER ISENCOUNTERED
08/09/2017Date:
BURLINGTON
COMMONS
CENTER STREET
BURLINGTON, MA 01803
Drawn By:
Reviewed By:
Approved By:
Drawing Title:
Sheet Number:
Seal:
Revisions:
No. Date Description
Project:
TOWN OF BURLINGTON, MA
Consultants:
W&S Project No:2170150
COPYRIGHT 2017 WESTON & SAMPSON
Scale:
978.532.1900
www.westonandsampson.com
800.SAMPSON
Issued For:
Weston & Sampson Engineers, Inc.
Five Centennial Drive,
Peabody, MA 01960
ELECTRICAL
DETAILS
E1.03
NONE
DNM
RFM
RFM