  • 7/27/2019 Bus Bar Tubing[1]

    1/2

    Reduces bus bar clearance

    requirements

    Protects against accidental flashover

    Continuous operatingo o

    temperature: -40 C to 125 C

    Meets the requirements ofESI 09 13

    Halogen free

    oShrink Temperature : 120 C

    Track Resistant

    Suitable for medium voltage

    switchgear applications up to36 kV

    High dielectric strength

    Good Weather/ UV

    M-Seal Bus Bar Tubings are made of specially formulated, irradiation cross-linked,

    flame-retardant, track-resistant polyolefins which will shrink to fit rectangular,

    square or round bus bars. These tubing's are especially designed for insulating

    medium voltage bus bars (till 36kV). We have developed M-seal Bus Bar Insulation

    tubings with only one word in mind: SAFETY. These are highly recommended for

    covering exposed bus bars in pillar, boxes, electrical switch gears, cabinets and bus

    ducts. This greatly reduces the risk of accidental electrocution of personnel

    working on or near live bus bars.

    The tubes are highly flexible, enabling them to be easily installed on curves and

    bends without fear of cracking. They are available in different sizes to cover the

    entire range of copper and aluminum bus bars. They are available in wide range of

    expansion ratios so each size of tubing fits over a wide range of bus bars. The

    tubings are ideal for original equipment assembly and for retrofit applications

    where access to only one end is available. The M-Seal bus bar heat-shrinkable

    tubes are also ideal for installation on overhead lines to protect against accidental

    bridging caused by birds and animals.

    Bus Bar Tubing

  • 7/27/2019 Bus Bar Tubing[1]

    2/2

    Fully Shrunk

    di wi

    Expanded

    Di

    Dimensions Chart

    Said Size

    MAT 30/10

    MAT 35/12

    MAT 40/16

    MAT 42/19 mw

    MAT 42/19 tw

    MAT 60/29

    MAT 76/38

    MAT 100/49

    MAT 130/50

    Internal diameter

    as recovered

    10

    11

    16

    17

    17

    27

    36

    49

    49

    di

    Recovered

    Wall thickness

    2.5

    3

    4

    3.5

    4.5

    3.5

    3.5

    3.8

    4

    wi

    Diameter as

    supplied

    32

    37

    42

    44

    44

    62

    78

    102

    134

    Di

    Technical Specifications

    Properties

    Density

    Longitudinal Change

    Tensile strength

    Ultimate Elongation

    Shrink Temperature

    Continuous Operating

    Temperature0

    Heat Shock, 4 Hrs @ 225 C

    Properties after Thermal Aging0

    168 hrs @ 150 C

    Tensile strength

    Ultimate Elongation

    Corrosion Resistance

    Low Temperature Flexibility

    Flammability

    Fungus Resistance

    Di-electric strength

    Relative Permittivity

    Volume ResistivityTracking Resistance

    Water Absorption

    Unit

    gm/cc

    %2

    N/mm

    %0C

    0C

    2N/mm

    %

    kV/mm

    ohm.cm

    %

    Testing Methods

    ASTM D 792

    ESI 09-13

    ASTM D 638

    ASTM D 638

    ASTM D 2671

    ASTM D 2671

    ASTM D 638

    ASTM D 638

    ASTM D 2671

    ESI 09-13

    UL 94HB

    ASTM D 2671

    ASTM D 149

    ASTM D 150

    ASTM D 257ASTM D 2303

    ASTM D 570

    Typical Value

    1.22