buylog section 7 circuit breaker enclosures - abb...7-4 circuit breaker enclosures, buylog section...

14
BUYLOG SECTION 7 Circuit Breaker Enclosures

Upload: others

Post on 10-Feb-2021

161 views

Category:

Documents


4 download

TRANSCRIPT

  • — BUYLOG SEC TION 7

    Circuit Breaker Enclosures

  • 7-2 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

  • 7-3CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    — Table of contents

    7-4 NEMA Type 1 Enclosures7-6 NEMA Type 3R Enclosures7-8 NEMA Type 12 Enclosures7-9 NEMA Type 4/4X Enclosures7-10 Hubs and Other Accessories7-11 Dimensions and Outline Drawings7-14 Dimensions and Knockout Drawings

    edgardomendozaSection Updated 12/2020

  • 7-4 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    Type 1, Indoor Surface or Flush Mounting

    Product Features

    - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the

    installed breaker.

    To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.com

    NEMA Type 1

    Certifications Product NumberFor 3P4W Enclosures

    For Enclosures with Ground Fault Protection

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA Flush SurfaceSurface,Blank End Wall2

    Neutral Product Number

    Neutral Product Number3

    Neutral Sensor for Ground Fault

    70THQL, TXQL, THQL-GF

    1, 2, 3 • • - - TQL70F4 TQL70S4 - Included - -

    100THQL, TXQL, THQL-GF

    1, 2, 3 • • - - TQL100F4 TQL100S4 - Included - -

    125 THQL 2 • • - - TQL125F TQL125S - Included - -

    100THQC, THHQC, TXQC

    1, 2, 3 • • - - TQC100F4 TQC100S4 - Included - -

    250 Formula A2 2, 3 • • - - A2ENCL250F A2ENCL250S - Included - -

    100SE150, THED, TED, TEB

    2, 3 • • - - TE100F TE100S TE100SB Included - -

    150SE150, THED, TED

    2, 3 • • • - TE150F TE150S TE150SB Included - -

    125 Tmax XT1 3 • • - - XT1ENCL125F XT1ENCL125S - Included - -

    125 Tmax XT2 3 • • - - XT2ENCL125F XT2ENCL125S - TNIA2255 TNIA250XTGF

    1SDA067211R1 (10A DIP)1SDA067212R1 (25A DIP)1SDA081983R1 (60A DIP)1SDA069143R1 (100A DIP)1SDA081984R1 (125A DIP)1SDA101971R1 (60A Touch)1SDA101972R1 (100A Touch)1SDA107406R1 (60A Touch V)1SDA107407R1 (100A Touch V)

    225 Tmax XT3 3 • • - - XT3ENCL225F XT3ENCL225S - Included - -

    —Circuit Breaker EnclosuresNEMA Type 1

    1cUL Listed - Suitable for use as service equipment.2Enclosures with blank end walls (no Knockouts) and a feature to adjust the instantaneous setting on Spectra Circuit breakers.3Neutral for ground fault required to mount neutral sensor in enclosure.43-Pole breakers with an accessory cannot be installed in these enclosures.5For 250A rating, use copper cable only.

    (Table continued on next page.)

  • 7-5CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    —Circuit Breaker EnclosuresNEMA Type 1

    NEMA Type 1

    Certifications Product NumberFor 3P4W Enclosures

    For Enclosures with Ground Fault Protection

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA Flush SurfaceSurface,Blank End Wall2

    Neutral Product Number

    Neutral Product Number3

    Neutral Sensor for Ground Fault

    250 Tmax XT4 3 • • - - XT4ENCL250F XT4ENCL250S - TNIA2254 TNIA250XTGF

    1SDA066975R1 (40A DIP)1SDA081985R1 (60A DIP)1SDA066977R1 (100A DIP)1SDA081986R1 (150A DIP)1SDA081987R1 (225A DIP)1SDA066979R1 (250A DIP)1SDA101973R1 (Touch)1SDA107408R1 (Touch V)

    250 SF250 2, 3 • - - • SF250F SF250S SF250SB TNIA2254 - -

    600 Tmax XT5 3 • • - - XT5ENCL600F XT5ENCL600S -TNIA400TNIA600

    TNIA400XTGFTNIA600XTGF

    1SDA101966R1 (250A DIP)1SDA105152R1 (300A DIP)1SDA105154R1 (400A DIP)1SDA105155R1 (600A DIP)1SDA101974R1 (Touch)1SDA107409R1 (Touch V)

    400 SG400 2, 3 • - - • SG400F SG400S SG400SB TNIA400 TNIA400VGTSRG201TSRG204

    600 SG600 2, 3 • - - • SG600F SG600S SG600SB TNIA600 TNIA600VG TSRG206

    800 Tmax XT6 3 • • - - XT6ENCL800F XT6ENCL800S - TNIA800 TNIA800XTGF1SDA105158R1 (800A)

    1200 Tmax XT7 3 • • - - XT7ENCL1200F XT7ENCL1200S - TNIA1200 TNIA1200XTGF 1SDA082134R1

    1200 SK1200 2, 3 • - - • TK4V1200F5,6 TK4V1200S5,6 TK4V1200SB5,6

    TNIA400TNIA600TNIA800TNIA1200TNIAC1200

    TNIA800GTNIA1200G

    TSKG408TSKG410TSKG412

    1cUL Listed - Suitable for use as service equipment.2Enclosures with blank end walls (no Knockouts) and a feature to adjust the instantaneous setting on Spectra Circuit breakers.3Neutral for ground fault required to mount neutral sensor in enclosure.4For 250A rating, use copper cable only.5Not suitable for 100% rated 1200A SK breakers.6Suitable for parallel 500 kcmil maximum.

    (continued)

  • 7-6 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    Type 3R, Outdoor, Raintight

    Product Features - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the

    installed breaker.

    To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.com

    NEMA Type 3R

    CertificationsFor 3P4W Enclosures

    For Enclosures with Ground Fault Protection

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA Product Number9Neutral Product Number

    Neutral Product Number2

    Neutral Sensor for Ground Fault

    100 THQL, TXQL, THQL-GF 1, 2, 3 • - - • TQL70R3 Included - -100 THQL, TXQL, THQL-GF 1, 2, 3 • - - • TQL100R3 Included - -125 THQL 2 • - - • TQL125R Included - -100 THQC, THHQC, TXQC 1, 2, 3 • - - • TQC100R3 Included - -250 Formula A2 2, 3 • • • - A2ENCL250R Included - -100 SE150, THED, TED, TEB 2, 3 • - - • TE100R Included - -125 Tmax XT1 3 • • • - XT1ENCL125R Included - -

    125 Tmax XT2 3 • • • - XT2ENCL125R TNIA2254 TNIA250XTGF

    1SDA067211R1 (10A DIP)1SDA067212R1 (25A DIP)1SDA081983R1 (60A DIP)1SDA069143R1 (100A DIP)1SDA081984R1 (125A DIP)1SDA101971R1 (60A Touch)1SDA101972R1 (100A Touch)1SDA107406R1 (60A Touch V)1SDA107407R1 (100A Touch V)

    150 SE150, THED, TED 2, 3 • - - • TE150R Included - -225 Tmax XT3 3 • • • - XT3ENCL225R Included - -

    250 Tmax XT4 3 • • • - XT4ENCL250R TNIA2254 TNIA250XTGF

    1SDA066975R1 (40A DIP)1SDA081985R1 (60A DIP)1SDA066977R1 (100A DIP)1SDA081986R1 (150A DIP)1SDA081987R1 (225A DIP)1SDA066979R1 (250A DIP)1SDA101973R1 (Touch)1SDA107408R1 (Touch V)

    250 SF250 2, 3 • - - • TF225R TNIA2254 - -

    —Circuit Breaker EnclosuresNEMA Type 3R

    1cUL Listed - Suitable for use as service equipment.2Neutral for ground fault required to mount neutral sensor in enclosure.33-Pole breakers with an accessory can not be installed in these enclosures.4For 250A rating, use copper cable only.5Suitable for parallel 250 kcmil maximum. If larger cable is required, use 600A enclosure.6Not suitable for 100% rated 1200A SK breakers.7Suitable for parallel 500 kcmil maximum.8Service rated equipment only.9100-250A devices have removable closing cap. Larger ampere devices require field cut openings. Order hubs separately. See page 7-10.

    (Table continued on next page.)

  • 7-7CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    —Circuit Breaker EnclosuresNEMA Type 3R

    NEMA Type 3R

    CertificationsFor 3P4W Enclosures

    For Enclosures with Ground Fault Protection

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA Product Number9Neutral Product Number

    Neutral Product Number2

    Neutral Sensor for Ground Fault

    600 Tmax XT5 3 • • • - XT5ENCL600RTNIA400TNIA600

    TNIA400XTGFTNIA600XTGF

    1SDA101966R1 (250A DIP)1SDA105152R1 (300A DIP)1SDA105154R1 (400A DIP)1SDA105155R1 (600A DIP)1SDA101974R1 (Touch)1SDA107409R1 (Touch V)

    400 SG400 2, 3 • - - • SG400R TNIA400 TNIA400VGTSRG201TSRG204

    600 SG600 2, 3 • - - • SG600R TNIA600 TNIA600VG TSRG206

    800 Tmax XT6 3 • • • - XT6ENCL800R TNIA800 TNIA800XTGF1SDA107671R1 (600A)1SDA105158R1 (800A)

    1200 Tmax XT7 3 • • • - XT7ENCL1200R TNIA1200 TNIA1200XTGF 1SDA082134R1

    1200 SK1200 2, 3 • - - • TK4V1200R6, 7

    TNIA400TNIA600TNIA800TNIA1200TNIAC1200

    TNIA800GTNIA1200G

    TSKG408TSKG410TSKG412

    CertificationsFor 3P4W Enclosures

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA Product Number9Neutral Product Number

    Notes

    100 THQL, TXQL, THQL-GF 1, 2, 3 • • - - TQL70RE3 Included 100A circuit breaker factory installed (2-pole)150 Formula A2 2 • • • - A2A250W150ECB Included 150A circuit breaker factory installed (2-pole)200 Formula A2 2 • • • - A2A250W200ECB Included 200A circuit breaker factory installed (2-pole)150 THQMV 2 • • • - THQMV150NRE8 Included 150A circuit breaker factory installed (2-pole)200 THQMV 2 • • • - THQMV200NRE8 Included 200A circuit breaker factory installed (2-pole)

    1cUL Listed - Suitable for use as service equipment.2Neutral for ground fault required to mount neutral sensor in enclosure.33-Pole breakers with an accessory can not be installed in these enclosures.4For 250A rating, use copper cable only.5Suitable for parallel 250 kcmil maximum. If larger cable is required, use 600A enclosure.6Not suitable for 100% rated 1200A SK breakers.7Suitable for parallel 500 kcmil maximum.8Service rated equipment only.9100-250A devices have removable closing cap. Larger ampere devices require field cut openings. Order hubs separately. See page 7-10.

    (continued)

  • 7-8 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    Types 12K and 12,Rotary Handle Integral with Breaker

    Product Features

    - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the

    installed breaker.

    To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.com

    NEMA Type 12

    CertificationsProduct Number

    Suffix Options (Mounting)

    For 3P4W Enclosures

    For Enclosures with Ground Fault Protection

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA PrefixWith Knock Outs

    Without Knock Outs

    Neutral Product Number

    Neutral Product Number2

    Neutral Sensor for Ground Fault

    100 THED, TED, TEB 3 • - • • TE100_ D J Included - -100 SE150 2, 3 • - • • SE100_ D J Included - -250 SF250 2, 3 • - - • SF250_ D J TNIA2254 - -400 TJD, TJJ, TJK, THJK 2, 3 • - - • TJ400_3 - J TNIA400 - -

    600 TJK, THJK 2, 3 • - - • TJ600_ - JTNIA400TNIA600

    - -

    400 SG400 2, 3 • - - • SG400_ D J TNIA400 TNIA400VGTSRG201TSRG204

    600 SG600 2, 3 • - - • SG600_ - J TNIA600 TNIA600VG TSRG206

    1200 SK1200 2, 3 • - - • SK1200_5, 6 - J

    TNIA400TNIA600TNIA800TNIA1200TNIAC1200

    TNIA800GTNIA1200G

    TSKG408TSKG410TSKG412

    1cUL Listed - Suitable for use as service equipment.2Neutral for ground fault required to mount neutral sensor in enclosure.3Suitable for parallel 250 kcmil maximum. If larger cable is required, use 600A enclosure.4For 250A rating, use copper cable only.5Not suitable for 100% rated 1200A SK breakers.6Suitable for parallel 500 kcmil maximum.

    —Circuit Breaker EnclosuresNEMA Type 12

  • 7-9CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    Type 4/4X,Stainless Steel, Watertight, Dust Tight

    Product Features

    - Suitable for use as service equipment (SE) as noted. - 60°C/75°C conductor ratings - Short circuit ratings are equal to the rating of the

    installed breaker.

    To order enclosed or accessorized circuit breakers, a configurator is available at: empower.abb.com

    NEMA Type 4/4X

    CertificationsFor 3P4W Enclosures

    For Enclosures with Ground Fault Protection

    Max. Ampere Rating

    Frame TypeNo. ofPoles

    ULSE

    cULcULSE1

    CSA Product NumberNeutral Product Number

    Neutral Product Number2

    Neutral Sensor for Ground Fault

    100 THED, TED, TEB 2, 3 • - - - TE100CS TNI100 - -100 SE150 2, 3 • - - - SE150CS TNI100 - -250 SF250 2, 3 • - - - SF250CS TNIA2253 - -400 TJD, TJJ, TJK, THJK 2, 3 - - - - TJ400CS4 TNIA400 - -

    600 TJK, THJK 2, 3 - - - - TJ600CSTNIA400TNIA600

    - -

    400 SG400 2, 3 • - - - SG400CS5 TNIA400 - -1cUL Listed - Suitable for use as service equipment.2Neutral for ground fault required to mount neutral sensor in enclosure.3For 250A rating, use copper cable only.4Suitable for parallel 250 kcmil maximum. If larger cable is required, use 600A enclosure.5Not suitable for 3-Phase, 4-wire or Single-Phase, 4 wire ground fault applications that require Neutral sensor mounted in enclosure.

    —Circuit Breaker EnclosuresNEMA Type 4/4X

  • 7-10 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    TC150

    Universal Raintight Hubs, AluminumFor outdoor enclosures that have removable closing caps.

    Nominal Conduit Diameter (in.) Standard Package Product Number3/4 10 TC751 10 TC1001 1/4 10 TC1251 1/2 10 TC1502 10 TC2002 1/2 10 TC2503 5 TC300Closing Cap 10 TCCP

    Stainless Steel CoverFor flush mounted Type 1 circuit breaker enclosures, field installed only.

    For Use with Product NumberTE100F TE100FSS

    Insulated Groundable NeutralsMax. Ampere Rating Lug Wire Size (Cu-Al) AWG/kcmil Standard Package Product Number100 14-1/0 Cu, 12-1/0Al 1 TNI100225 1-300 1 TNIA2251

    250 1-300 1 TNIA250EGF1, 3

    250 1-300 1 TNIA250XTGF4

    400 (2) 1/0-250 or (1) 4-600 1 TNIA400400 (2) 1/0-250 or (1) 4-600 1 TNIA400VG2

    400 (2) 1/0-250 or (1) 4-600 1 TNIA400GGF3

    400 (2) 1/0-250 or (1) 4-600 1 TNIA400XTGF4

    600 (2) 2/0-500 1 TNIA600600 (2) 2/0-500 1 TNIA600VG2

    600 (2) 2/0-500 1 TNIA600GGF3

    600 (2) 2/0-500 1 TNIA600XTGF4

    800 (3) 250-500 1 TNIA800800 (3) 250-500 1 TNIA800XTGF4

    800 (3) 250-350 Cu or (3) 250-500 Al 1 TNIA800G2

    1200 (4) 250-350 Cu or (4) 250-500 Al 1 TNIA12001200 (4) 250-350 Cu or (4) 250-500 Al 1 TNIA1200G2

    1200 (4) 250-350 Cu or (4) 250-500 Al 1 TNIA1200XTGF4

    1200 (4) 250-400 Cu Only 1 TNIAC12001For 250A rating, use copper cable only.2Neutral required for Spectra Circuit Breakers with ground fault.3Neutral required for Record Plus Circuit Breakers with ground fault.4Neutral required for Tmax XT Circuit Breakers with ground fault.

    Ground KitsAmpere Rating Product Number70-125 amp TGL1

    150-400 amp(1) TGL1 plus(1) TGL20

    600-1200 amp TGL6

    —Circuit Breaker EnclosuresHubs and Other Accessories

  • 7-11CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    NEMA Type 1 Enclosures

    Product NumberDimension1

    A (in.)Dimension1

    B (in.)Dimension1

    C (in.)Dimension1

    D (in.)Dimension1

    E (in.)OutlineDrawing No.

    TE100F, S, SB2 17.000 - 7.875 5.500 4.750 208C2891SH3XT1ENCL125F, S 19.440 9.740 9.740 6.260 5.490 139C5497SH14TE150F, S, SB2 26.438 8.875 8.875 6.188 5.500 139C5497SH1XT2ENCL125F, S 19.440 9.740 9.740 6.260 5.490 139C5497SH15SF250F, S, SB2 29.875 8.875 8.875 6.188 5.500 139C5497SH2XT3ENCL225F, S 31.240 10.500 10.500 6.260 5.490 139C5497SH16XT4ENCL250F, S 31.240 10.500 10.500 6.260 5.490 139C5497SH17SG400F 31.375 - 15.156 7.313 6.625 208C2891SH1SG400S, SB2 30.313 - 14.125 7.313 6.625 208C2891SH1SG600F 44.000 - 18.188 9.000 8.375 208C2891SH2SG600S, SB2 42.750 - 17.125 9.000 8.375 208C2891SH2FG600F, S, SB2 42.750 - 17.125 9.000 8.375 208C2891SH7XT5ENCL600F, S 43.965 17.180 17.180 9.120 8.350 208C2891SH11XT6ENCL800F, S 45.650 21.330 22.320 6.890 7.510 1SQC930053D0201XT7ENCL1200F, S 48.640 21.920 21.920 8.800 9.420 139C5497SH18TK4V1200F, S, SB 48.125 21.313 - - - 139C5497SH5TQC100F, S 15.250 - 6.875 4.750 4.000 139C5651SH1TQD225F, S 26.438 8.875 8.875 6.188 5.500 139C5497SH1A2ENCL250F, S 31.240 10.500 10.500 6.260 5.490 139C5497SH13TQL70F, S 12.875 - 5.750 4.750 4.063 208C2817SH1TQL100F, S 15.250 - 6.875 4.750 4.000 139C5651SH2TQL125F, S 16.875 - 6.750 5.188 4.500 139C5651SH2

    NEMA Type 1Suffix F (Flush)

    Suffix S (Surface)

    —Circuit Breaker EnclosuresDimensions and Outline Drawings

    1Flush front extends approximately 0.625-inch beyond each side.2NEMA Type 1 Enclosure Product Numbers ending in "SB" contain blank end walls (No Knockouts).

  • 7-12 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    —Circuit Breaker EnclosuresDimensions and Outline Drawings

    NEMA Type 3R Enclosures

    Product NumberDimension1

    A (in.)Dimension1

    B (in.)Dimension1

    C (in.)Dimension1

    D (in.)Dimension1

    E (in.)OutlineDrawing No.

    TE100R 18.056 7.875 7.500 5.688 5.375 139C5652SH1XT1ENCL125R 20.470 10.240 9.960 6.744 5.688 139C5498SH7TE150R 27.438 10.250 10.000 6.250 5.500 139C5498SH1XT2ENCL125R 20.470 10.240 9.960 6.744 5.688 139C5498SH7TF225R 30.813 10.250 10.000 7.000 6.250 139C5498SH2XT3ENCL225R 32.216 10.952 10.720 6.744 5.688 139C5498SH6XT4ENCL250R 32.216 10.952 10.720 6.744 5.688 139C5498SH6SG400R 30.813 14.938 14.625 9.125 8.000 208C2837SH1SG600R 43.000 18.875 18.063 8.813 7.688 208C2838SH1FG600R 43.000 18.875 18.063 8.813 7.688 208C2838SH2XT5ENCL600R 43.186 18.611 18.030 9.040 7.980 208C2838SH3XT6ENCL800R 45.200 22.190 21.500 8.920 8.190 1SQC930059D0201XT7ENCL1200R 48.190 23.220 22.530 11.920 10.870 139C5498SH8TK4V1200R 47.750 23.375 22.563 9.438 8.313 139C5520SH1TQC100R 15.750 7.875 7.500 5.688 5.375 139C5652SH1TQD150NRE 26.813 7.813 7.625 5.125 4.438 139C5498SH3TQD200NRE 26.813 7.813 7.625 5.125 4.438 139C5498SH3TQD225NR 26.813 7.813 7.625 5.125 4.438 139C5498SH3TQD225R 26.375 10.250 10.000 6.250 5.500 139C5498SH1A2ENCL250R 32.210 10.260 10.720 6.560 5.560 139C5498SH6A2A250W150ECB 32.210 10.260 10.720 6.560 5.560 139C5498SH6A2A250W200ECB 32.210 10.260 10.720 6.560 5.560 139C5498SH6TQL70R 17.000 - 6.875 5.938 5.000 208C3061SH1TQL100R, RE 17.000 7.250 6.875 6.000 5.000 139C5652SH1TQL125R 18.313 7.688 7.500 6.313 5.188 139C5652SH1THQMV150NRE 18.813 9.500 9.313 5.500 4.875 208C3061SH2THQMV200NRE 18.813 9.500 9.313 5.500 4.875 208C3061SH2

    1Flush front extends approximately 0.625-inch beyond each side.

    NEMA Type 3ROutdoor Enclosure

  • 7-13CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    —Circuit Breaker EnclosuresDimensions and Outline Drawings

    NEMA Type 4/4X Enclosures

    Product NumberDimensionA (in.)

    DimensionB (in.)

    DimensionC (in.)

    DimensionD (in.)

    DimensionE (in.)

    OutlineDrawing No.

    SE100CS 19 1/4 18 1/2 8 1/2 7 5 139C5654 Sh 1TE100CS 19 1/4 17 1/4 8 1/2 7 5 139C5654 Sh 1SF250CS 36 5/8 34 13/16 9 1/4 7 27/32 5 29/32 168D1626 Sh 1TJ400CS1 29 1/4 27 1/2 16 1/4 9 1/16 7 1/8 139C5496 Sh 2SG400CS2 32 31 1/4 14 1/8 9 5/16 7 7/16 208C2887 Sh 1TJ600CS 46 1/4 45 1/2 19 1/8 9 1/16 7 1/8 139C5496 Sh 3

    NEMA Type 12 and 12K Enclosures

    Product NumberDimensionA (in.)

    DimensionB (in.)

    DimensionC (in.)

    DimensionD (in.)

    DimensionE (in.)

    DimensionF (in.)

    OutlineDrawing No.

    SE100J, D 19 1/4 17 7/8 9 5 5 3/4 4 7/8 139C5653 Sh 1TE100J, D 19 1/4 17 7/8 9 5 5 3/4 4 7/8 139C5653 Sh 1SF250D 36 1/4 35 3/8 9 13/16 9 3/16 7 9/16 6 1/2 208C2884 Sh 1SF250J 36 1/4 35 3/8 9 13/16 9 3/16 7 9/16 6 1/2 208C2884 Sh 2SG400D 31 3/8 30 1/2 16 5/16 15 11/16 7 7/8 6 9/16 208C2885 Sh 1SG400J 31 3/8 30 1/2 16 5/16 15 11/16 7 7/8 6 9/16 208C2885 Sh 2TJ400J1 29 5/16 27 13/16 14 1/4 13 3/16 7 7/8 6 7/16 139C5682 Sh4SG600J 44 7/8 44 18 17 3/8 9 9/16 8 3/8 208C2886 Sh 1TJ600J 48 7/16 46 15/16 17 3/4 17 3/16 9 3/4 8 3/8 139C5682 Sh 5SK1200J 56 5/16 55 7/16 22 11/16 22 10 7/16 8 11/16 139C5682 Sh 6

    1Suitable for parallel 250 kcmil maximum. If larger cable is applied, use 600 amp enclosure.2Not Suitable for use with ground fault.

    NEMA Type 12 and 12KSuffix D (with KOs)

    Suffix J (without KOs)

    NEMA Type 4/4XStainless Steel

  • 7-14 CIRCUIT BREAKER ENCLOSURES, BUYLOG SECTION 7

    —Circuit Breaker EnclosuresDimensions and Knockout Drawings

    Symbol A ⊕ B C D E F G H I J K L M N P Q R S T U V W X Y Z

    ConduitSize(Inches)

    9/32 - 3/8 - - - - - - 3/8 - - - - - - - - - - - - - - - -- 1/2 1/2 1/2 - 1/2 - 1/2 - 1/2 - - - - - - - - - - - - - - - -- - 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4 - - - - 3/4 - - - - - 3/4 - - - -- - - - - 1 1 1 1 1 1 1 - 1 - 1 1 - - - - 1 - - - -- - - - - - - 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4 - - 1 1/4 - - 1 1/4 - - - -- - - - - - - - - 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 - - - - - -- - - - - - - - - - - - - 2 2 2 2 2 2 2 2 - 2 2 - 2- - - - - - - - - - - - - - - 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 2 1/2 - 2 1/2 - - 2 1/2- - - - - - - - - - - - - - - - - - 3 3 3 - 3 3 3 3- - - - - - - - - - - - - - - - - - - - - 3 1/2 3 1/2 3 1/2 3 1/2 3 1/2- - - - - - - - - - - - - - - - - - - - - - - - - 4

    Circuit Breaker EnclosuresProduct Number Knockout Figure No.TE100F, S 1TE100R 10TE100F, S 4TE150R 7SF250F, S 4TF225R 7TJ400F, S, SG400F, S 5TJ400R, SG400R 6TJ600R, SG600R, FG600R 9TJ600F, S, SG600F, S, FG600F, S 3TK4V1200F, S No KOTK4V1200R No KOTQC100F, S 2TQC100R 10TQD225F, S 4TQD225NR 8TQD225R 7TQL100F,S 2TQL100R 10

    Figure 1

    Figure 6Figure 5

    Figure 2

    Figure 7

    Figure 3

    Figure 9Figure 8

    Figure 4

    Figure 10

    Section 7: Circuit Breaker EnclosuresNEMA Type 1 Enclosures…..7-4NEMA Type 3R Enclosures…..7-6NEMA Type 12 Enclosures…..7-8NEMA Type 4/4X Enclosures…..7-9Hubs and Other Accessories…..7-10Dimensions and Outline Drawings…..7-11Dimensions and Knockout Drawings…..7-14