C13-SeriesEngineering Guide
Effective August 2019
HorizontalAir-Cooled, Water-Cooled, Chilled Water and Heat Pump
Engineering Guide
C13-Series
2Subject to change without notice. 10.20-TD (0819)
Product Features � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 3Product Options � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 4Air-Cooled Physical Data� � � � � � � � � � � � � � � � � � � � � � � � � 5Water-Cooled Physical Data � � � � � � � � � � � � � � � � � � � � � � 6Air-Cooled Performance Data (a) (b) � � � � � � � � � � � � � � � 7Air Source Heat Pump Unit Performance Data (a) (b)� � 7Water-Cooled Performance Data (a) (c) (d) (e)� � � � � � � � 8Water Source Heat Pump Performance Data (a) (c) (d) (e) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 8Blower Performance Data (a) (b) (c) � � � � � � � � � � � � � � � � 9
Evaporator � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9Condenser � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 9
Hot Water Coil Performance (a) (b) (c) (d) (e) (f) � � � � � 10Chilled Water Coil Performance (a) (b) (c) (e) (f) � � � � � 11Steam Coil Performance (a) (b) (c) (d) � � � � � � � � � � � � � 11Electrical Data� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 12Electrical Data� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 13Electrical Data� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 14
Compressor RLA Electrical Data:� � � � � � � � � � � � � � � � � 14Evaporator Motor FLA:� � � � � � � � � � � � � � � � � � � � � � � � � 14Condenser Motor FLA:� � � � � � � � � � � � � � � � � � � � � � � � � 14
Electrical Data� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15Electric Heat FLA: (Heaters nominally rated at 220 or 460 volts�)� � � � � � � � � � � � � � � � � � � � � � � � � � � � �15Humidifier FLA: � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 15
Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 16Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 17Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 18Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 19Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 20Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 21Electrical Data - Air-Cooled (c) (d) (e)� � � � � � � � � � � � � � 22
Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 23Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 24Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 25Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 26Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 27Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 28Electrical Data - Water-Cooled (c) (d) (e) � � � � � � � � � � � 29Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 30Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 31Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 32Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 33Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 34Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 35Electrical Data - Evaporator Section (c) (d) (e) � � � � � � 36Electrical Data - Air-Cooled Condensing Section (a) (b) (c) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 37Electrical Data - Air-Cooled Condensing Section (a) (b) (c) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 38Electrical Data - Air-Cooled Condenser (a) (b) (c) � � � � 39Electrical Data - Water-Cooled Condensing Section (a) (b) (c) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 40Water-Cooled Piping Arrangements � � � � � � � � � � � � � � � 41Water-Cooled Piping Arrangements � � � � � � � � � � � � � � � 42Water-Cooled Piping Arrangements � � � � � � � � � � � � � � � 43Basic Model Configurations � � � � � � � � � � � � � � � � � � � � � 44Basic Model Configurations � � � � � � � � � � � � � � � � � � � � � 45Basic Unit Dimensions� � � � � � � � � � � � � � � � � � � � � � � � � � 46Service Clearance - Plan View� � � � � � � � � � � � � � � � � � � � 47Miscellaneous Technical Data� � � � � � � � � � � � � � � � � � � � 47Options � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � 48BASIC MODEL DESIGNATION� � � � � � � � � � � � � � � � � � � � 49
Contents
Engineering Guide
C13-Series
3Subject to change without notice. 10.20-TD (0819)
• Air-Cooled, Water-Cooled or Heat Pump Configurations• R-410A Refrigerant• Ceiling Mounted or Slab Mounted Package• 2 & 3-Ton Unit Height of 23-1/8" (Includes the mounting rails)• 4 & 5-Ton Unit Height of 26-1/8" (Includes the mounting rails)• 6, 8 & 10 - Ton Unit Height of 33-1/8" (Includes the mounting rails)• Cabinets Constructed of Scratch Resistant Heavy Duty 18 Gauge Galvanized Steel• Splitable using Resealable Refrigerant Fittings• Can locate sections with up to 100’ equivalent lengths of refrigerant tubing
(Contact the factory for specific details and for lengths more than noted above)• Completely Serviceable at Ceiling• Access From Both Sides of Unit• Saves Valuable Floor Space when Ceiling Mounted• Functionally Run Tested at the Factory • (Limited Testing done when only one section ordered)• 1/2" Fiber Glass Lined Cabinet (Thermal/Acoustical, min� density of 2 Pounds)• 3/4" Drain Connections on Both Evaporator and Condensing Sections• 304 Stainless Steel Double Sloped Drain Pan in Evaporator Section• 1" ESP Capability (Contact factory with specific requirements, may require motor / drive upgrade)• Belt Driven Blowers• Ball Bearing Motors• Resiliently Mounted Ball Bearings for Blowers• Cast Iron Pulleys and Sheaves• Inherently Protected Motors and Compressors • Premium Efficiency Motors• Adjustable Motor Mounts• High and Low Refrigerant Pressure Safeties• Loss of Air Safety Switch (when electric heat used)• Individual Contactor for each Motor and Compressor• Individual Contactor for Each Stage of Electric Heat• Adjustable Expansion Valve with External Equalizer• Sight Glass / Moisture Indicators• Filter Driers• 2" Pleated Filters• Draw Through Air Flow• Dual Electrical Control Boxes• High and Low Side Schrader Valve Refrigerant Access Fittings• Co-axial Counterflow Heat Exchanger on Water-Cooled Units
Product Features
The C13-Series of units are unique in that they can be applied as close coupled or split with the evaporator remote from the condensing section� They are available as air-cooled, water-cooled or heat pump configurations.
The units can be ceiling or slab mounted� Additionally the units can be tailored for a specific application as a made to order unit� Individual sections can be used with other product series�
Engineering Guide
C13-Series
4Subject to change without notice. 10.20-TD (0819)
CONTACT THE FACTORY FOR OTHER OPTIONAL FEATURES�
Options (Items in BOLD are factory installed):
• Electric Heat or Reheat• Protective Coil Coatings• Steam Canister Humidifier• SCR Controllers• Vertical Stacking Unit Configuration• Steam Coils• Air or Water Side Economizer• Hot Water Coils• Drain Pan Overflow Switch• Double Wall Construction• Stainless Steel Cabinets• Condenser Drain Pan• 2-Way, 3-Way and / or 350 psig Water Regulating Valves
(Mechanical or Electronic)• Hot Gas Bypass w/ Manual Shut Off Valve• Hot Gas Reheat• Modulating Hot Gas Bypass• Low Ambient Controls (Flooded Condenser or VFD)• Freezestat• Mixing Box• Phase Protection• Microprocessor Controls• Copper / Copper Coils (Contact Factory)• Coated Cabinets (Contact Factory)• Non-Fused Disconnects• Variable Frequency Drive (VFD) (Evaporator or Low Ambient)• Thermostats• Condensate Pump (shipped loose)
Product Options
Engineering Guide
C13-Series
5Subject to change without notice. 10.20-TD (0819)
(a) Certain options may affect motor size� Run unit in UCA Select for proper motor HP� (b) Net operating weight is for basic unit only� Options will add weight�(c) Pulley & Belt upgrade only�(d) R-410A Refrigerant charge is for base unit configuration. Addition of some options may alter refrigerant amount.
Air-Cooled Physical Data
Tons 2 3 4 5 6 8 10Evaporator Supply Air CFM 800 1200 1600 2000 2400 3200 4000
Evaporator BlowerSize 10-8 12-9 15-15Qty 1
Evaporator Motors (a)Std. HP @ 0.25" ESP 1/3 1/2 3/4 1-1/2Opt. HP @ 1.0" ESP 1/3 (c) 1/2 3/4 1 1-1/2 2
Evaporator CoilRows 2 3 4Face Area 3.44 4.31 6.11 6.11 8.94 8.94 10.94FPI 12
Filter
Type Pleated ThrowawayQty 1 2 4Dimensions 25 x 20 x 2 20 x 16 x 2Efficiency MERV 8
CompressorType ScrollQty 1 2
Condenser Air CFM 1600 2000 2500 2900 4000 5200 5000
Condenser BlowerSize 10-10 12-9 15-15 18-13Qty 1
Condenser Motors (a)Std. HP @ 0.25" ESP 1/2 3/4 1-1/2 3 1-1/2Opt. HP @ 1.0" ESP 3/4 1 1-1/2 1-1/2 (c) 2 3 (c) 2
Condenser CoilRows 4 5Face Area 5.56 7.5 12.1 12.29FPI 16 14
Charge R-410A (Lbs-Ozs) (Charge per circuit) (d)
Air-Cooled 6-8 6-9 8-12 8-13 9-9 9-10Air Source Heat Pump
Weight (Net Operating) (b)Air-Cooled 725 730 1055 1075 1575 1610 1720Air Source Heat Pump 750 755 1080 1100 1625 1660 1795
Available Voltages208/230-1-60 • • • • n/a n/a n/a208/230-3-60 • • • • • • •460-3-60 • • • • • • •
Engineering Guide
C13-Series
6Subject to change without notice. 10.20-TD (0819)
(a) Certain options may affect motor size� Run unit in UCA Select for proper motor HP� (b) Net operating weight is for basic unit only� Options will add weight�(c) Pulley & Belt upgrade only�(d) R-410A Refrigerant charge is for base unit configuration. Addition of some options may alter refrigerant amount.
Water-Cooled Physical Data
Tons 2 3 4 5 6 8 10Evaporator Supply Air CFM 800 1200 1600 2000 2400 3200 4000
Evaporator BlowerSize 10-8 12-9 15-15Qty 1
Evaporator Motors (d)Std. HP @ 0.25" ESP 1/3 1/2 3/4 1-1/5Opt. HP @ 1.0" ESP 1/3 (c) 1/2 3/4 1 1-1/2 2
Evaporator CoilRows 2 3 4Face Area 3.44 4.31 6.11 8.94 10.94FPI 12
Filter
Type Pleated ThrowawayQty 1 2 4Dimensions 25 x 20 x 2 20 x 16 x 2Efficiency MERV 8
CompressorType ScrollQty 1 2
Water-Cooled CondenserType Co-AxialQty 1 2
Charge R-410A (Lbs-Ozs) (Charge per circuit) (d)
Water-Cooled 2-12 3-11 4-15 5-1 4-15 5-2Water Source Heat Pump
Weight (Net Operating) (b)Water-Cooled 580 590 860 885 1190 1260 1500Water Source Heat Pump 605 615 885 910 1240 1310 1575
Available Voltages208/230-1-60 • • • • n/a n/a n/a208/230-3-60 • • • • • • •460-3-60 • • • • • • •
Engineering Guide
C13-Series
7Subject to change without notice. 10.20-TD (0819)
(a) Capacities are gross values, not adjusted for motor heat�(b) Some refrigerant circuit components may impact on unit capacities�(c) Supplemental heat is recommended with all heat pump configurations.
Air-Cooled Performance Data (a) (b) (c)
Air Source Heat Pump Unit Performance Data (a) (b) (c)
Tons CFM Entering Air Temp. (°F) Air Over Condenser (°F)75 95 115
DB WB Total Sensible Total Sensible Total Sensible
2 80080 67 26,700 18,300 24,100 17,200 21,400 15,80075 62.5 24,500 18,300 22,300 17,000 19,900 15,50072 60 23,300 18,100 21,400 16,700 19,200 15,100
3 120080 67 40,500 28,000 36,400 26,300 32,400 24,60075 62.5 37,500 27,800 33,900 26,100 30,100 24,20072 60 35,900 27,400 32,500 25,700 28,900 23,800
4 160080 67 50,800 36,300 45,900 34,100 40,900 32,10075 62.5 47,200 35,900 42,500 33,700 38,200 31,40072 60 45,300 35,200 40,700 33,100 36,800 30,600
5 200080 67 64,800 44,400 58,300 41,800 51,600 39,30075 62.5 59,900 44,000 54,400 41,600 47,800 38,90072 60 57,100 43,300 52,200 41,100 45,800 38,300
6 240080 67 83,500 57,900 75,300 54,600 66,400 51,40075 62.5 77,500 57,600 70,000 54,300 61,900 50,80072 60 74,100 56,700 67,000 53,300 59,300 49,700
8 320080 67 99,200 69,900 89,300 66,300 80,000 62,00075 62.5 91,700 69,500 82,900 65,600 74,000 61,50072 60 87,700 68,600 79,300 64,500 70,600 60,300
10 400080 67 126,600 94,400 114,200 89,600 101,400 84,40075 62.5 117,800 93,200 106,400 88,400 94.600 83,00072 60 113,200 91,800 102,200 86,800 90,800 81,400
Tons Return Air Temp DB Outdoor Entering Air Temperature47 / 43 17 / 15
2 70 22,560 14,25060 23,320 15,300
3 70 33,540 21,45560 34,390 22,115
4 70 41,730 25,45560 43,430 27,270
5 70 53,460 35,95560 55,060 37,750
6 70 64,285 41,21560 66,655 43,440
8 70 82,340 52,28060 84,565 55,445
10 70 105,400 70,40060 107,000 73,400
Engineering Guide
C13-Series
8Subject to change without notice. 10.20-TD (0819)
(a) Capacities are gross values, not adjusted for motor heat�(b) Pressure drop is for heat exchanger only and does not include piping, valves, fittings, etc.(c) Some refrigerant circuit components may impact on unit capacities�(d) Applications with water conditions 75° F and lower may require additional refrigerant circuit components�(e) Consult factory for details�(f) Contact factory for geothermal applications�
Water-Cooled Performance Data (a) (c) (d) (e)
Water Source Heat Pump Performance Data (a) (c) (d) (e)
Tons GPM CFM Entering Air Temp. (°F) Entering Water Temperature (°F)80 85 90
DB WB Total Sensible Total Sensible Total Sensible
2 6 80080 67 25,300 17,900 24,700 17,700 24,100 17,40075 62.5 23,400 17,700 22,900 17,400 22,300 17,20072 60 22,500 17,400 21,900 17,100 21,400 16,900
3 9 120080 67 38,700 27,200 37,700 26,800 36,800 26,40075 62.5 35,600 26,900 34,700 26,500 33,800 26,10072 60 34,000 26,500 33,200 26,000 32,300 25,600
4 12 160080 67 49,200 35,300 48,000 34,700 46,800 34,20075 62.5 45,500 35,200 44,400 34,700 43,300 34,10072 60 43,500 34,900 42,400 34,300 41,400 33,700
5 15 200080 67 63,000 44,000 61,400 43,300 59,800 42,70075 62.5 58,100 43,500 56,700 42,900 55,300 42,20072 60 55,600 42,700 54,200 42,100 52,900 41,500
6 18 240080 67 80,000 56,300 77,900 55,500 75,900 54,60075 62.5 73,900 55,700 72,100 54,800 70,300 54,00072 60 70,800 55,000 69,100 54,100 67,400 53,100
8 24 320080 67 96,300 69,100 93,700 68,100 91,100 67,00075 62.5 89,400 68,500 87,000 67,500 84,700 66,40072 60 85,600 67,600 83,300 66,500 81,100 65,400
10 30 400080 67 130,600 95,600 127,400 94,400 124,200 93,20075 62.5 120,800 94,200 118,000 92,800 115,000 91,60072 60 115,600 92,400 112,800 91,200 110,000 90,000
Tons Return Air Temp. DB 70° F Entering Water Temp. GPM Pressure Drop PSI (b) CFMHeating
2 70 28,500 6 6.7 80060 28,990
3 70 43,300 9 4.9 120060 44,600
4 70 53,700 12 5.2 160060 54,900
5 70 70,200 15 5.4 200060 71,600
6 70 86,700 18 4.9 ea. 240060 89,400
8 70 106,200 24 5.2 ea. 320060 107,300
10 70 142,000 30 8.9 ea. 400060 145,600
Engineering Guide
C13-Series
9Subject to change without notice. 10.20-TD (0819)
(a) Contact factory for values outside the data�(b) Blower performance of basic unit with standard filter and wet coil 80 / 67.(c) Performance with nominal CFM. For other CFM or ESP contact the factory for your specific application.
EvaporatorBlower performance of basic unit with 2”, MERV 8 pleated filter and wet coil 80 / 67 / 95 Standard Air Path Configuration
CondenserBasic unit at 95 outdoor ambient. Standard Air Path Configuration
Non-standard drive set or motor� Contact factory�
Blower Performance Data (a) (b) (c)
Tons CFMExternal Static Pressure (ESP)
0.25” 0.50” 0.75” 1.0”RPM BHP HP RPM BHP HP RPM BHP HP RPM BHP HP
2900 615 0.11 1/3 768 0.16 1/3 907 0.22 1/3 1034 0.29 1/3800 589 0.09 1/3 754 0.14 1/3 901 0.20 1/3 1033 0.26 1/3700 567 0.07 1/3 746 0.12 1/3 899 0.17 1/3 1033 0.26 1/3
31350 748 0.26 1/3 860 0.33 1/2 967 0.40 1/2 1070 0.48 3/41200 697 0.20 1/3 821 0.26 1/3 938 0.33 1/2 1049 0.41 1/21050 650 0.15 1/3 788 0.21 1/3 916 0.27 1/3 1035 0.34 1/2
41800 633 0.32 1/2 737 0.41 1/2 834 0.50 3/4 926 0.61 3/41600 593 0.24 1/3 706 0.33 1/2 811 0.41 1/2 909 0.51 3/41400 556 0.18 1/3 680 0.26 1/3 793 0.34 1/2 897 0.43 1/2
52250 734 0.55 3/4 820 0.66 3/4 903 0.77 1 982 0.89 12000 680 0.41 1/2 774 0.51 3/4 865 0.61 3/4 951 0.72 11750 627 0.30 1/2 733 0.39 1/2 832 0.48 3/4 925 0.58 3/4
62700 507 0.43 1/2 607 0.59 3/4 697 0.77 1 778 0.97 1-1/22400 480 0.34 1/2 588 0.49 3/4 682 0.66 3/4 764 0.85 12100 455 0.26 1/3 570 0.40 1/2 667 0.57 3/4 749 0.75 1
83600 600 0.84 1 682 1.04 1-1/2 758 1.25 1-1/2 831 1.47 23200 559 0.64 3/4 648 0.82 1 731 1.02 1-1/2 807 1.23 1-1/22800 520 0.47 3/4 618 0.64 3/4 706 0.82 1 786 1.03 1-1/2
103500 578 0.76 1 662 0.94 1-1/2 741 1.14 1-1/2 814 1.37 1-1/24000 629 1.06 1-1/2 704 1.25 1-1/2 776 1.47 2 844 1.70 24500 678 1.41 2 746 1.62 2 812 1.85 3 875 2.10 3
Tons CFMExternal Static Pressure (ESP)
0.25” 0.50” 0.75” 1.0”RPM BHP HP RPM BHP HP RPM BHP HP RPM BHP HP
2 1600 788 0.32 1/2 909 0.41 1/2 1023 0.51 3/4 1131 0.62 3/43 2000 906 0.55 3/4 1007 0.65 3/4 1103 0.76 1 1197 0.88 14 2500 734 0.64 3/4 814 0.75 1 892 0.87 1 967 1.00 1-1/25 2900 821 0.95 1-1/2 891 1.07 1-1/2 959 1.21 1-1/2 1026 1.34 1-1/26 4000 609 1.00 1-1/2 686 1.21 1-1/2 759 1.43 2 828 1.66 28 5200 736 1.97 3 797 2.22 3 857 2.49 3 914 2.76 310 5000 521 1.10 1-1/2 589 1.32 1-1/2 654 1.56 2 716 1.81 2
Engineering Guide
C13-Series
10Subject to change without notice. 10.20-TD (0819)
Tons CFM GPM PD Ft. H2O Capacity (MBH)2 800 3.5 10.0 34.13 1200 4.3 15.1 42.64 1600 5.5 3.5 53.95 2000 6.2 4.4 60.86 2400 8.0 2.0 76.38 3200 9.0 2.5 88.310 4000 13.5 2.71 131.7
(a) Hot Water Coil Valves are optional� (b) Valves are spring return, On / Off operation only�(c) Entering water at 180° F� Leaving water at approximately 160° F�(d) Entering air temperature 65° F�(e) For other operating conditions or fluid type, contact the factory for performance.(f) Hot Water Coil Valve Sizes:
Tons Valve Size2 3/4"3 3/4"4 3/4"5 3/4"6 1"8 1"
10 1-1/4"
Hot Water Coil Performance (a) (b) (c) (d) (e) (f)
Engineering Guide
C13-Series
11Subject to change without notice. 10.20-TD (0819)
(a) Capacity based on 80° F DB / 67° F WB with 45° F EFT�(b) Chilled water entering at 45° F�(c) For other operating conditions or fluid type, contact the factory for performance.(d) Chilled Water Coil Valves are optional� (e) Valves are spring return, On / Off operation only�(f) Chilled Water Coil Valve Sizes:
Tons CFM GPM PD Ft. H2O Total (MBH) Sensible (MBH)2 800 5.3 3.5 26.4 19.23 1200 6.8 5.6 33.9 25.84 1600 8.6 2.6 43.1 33.55 2000 9.9 3.4 49.3 39.36 2400 13.9 3.1 69.2 52.48 3200 16.5 4.3 82.2 64.210 4000 25 7.1 124.8 93.9
Tons Valve Size2 3/4"3 3/4"4 3/4"5 3/4"6 1"8 1"
10 1-1/4”
Chilled Water Coil Performance (a) (b) (c) (e) (f)
Tons CFM2 psi
Capacity (MBH) Condensate (lb. / hr.) LAT2 800 46.5 48.2 118.43 1200 57.1 59.1 108.74 1600 89.4 92.6 116.35 2000 100.4 104.0 111.16 2400 138.8 143.7 118.18 3200 160.8 166.5 111.110 4000 189.3 196 108.4
(a) Low pressure, less than 10 psig�(b) Entering air at 65° F�(c) For other operating pressures, air flows and entering air conditions contact factory.(d) Steam valves and components by others, field installed.
Steam Coil Performance (a) (b) (c) (d)
Engineering Guide
C13-Series
12Subject to change without notice. 10.20-TD (0819)
The following sections provide the formulas and the data to calculate the Minimum Circuit Ampacity (MCA) and the Maximum Overcurrent Protection (MOP) for your specific unit configuration.There are a variety of unit configurations. Please make sure to use the correct formulas per your configuration.
It must be noted that the formulas refer to the largest motor amps� This typically is the compressor (RLA), but it can also be one of the blower motors (FLA)�The data provided will cover the majority of available unit configurations. However, it should be noted that additional combinations may be available and the factory can be contacted for this data�
Examples have also been provided for each configuration.RLA = Compressor Rated Load AmpsFLA = Full Load Amps (Used for Blower Motors and Electric Heaters)MCA = Minimum Circuit Ampacity (Calculated value)MOP = Maximum Fuse Size (Calculated value)
Cooling Only:
Close Coupled Unit (Can be single or dual compressor)
NOTE: Largest motor amps may not always be the compressor�MCA = (1�25 x largest motor amps) + the sum of the remaining motorsMOP = (2�25 x largest motor amps) + the sum of remaining motors
Evaporator Only SectionMCA = (1�25 x Evap� Blower Motor Amps)MOP = (2�25 x Evap� Blower Motor Amps)
Examples
Cooling Only:
Close Coupled Unit (Can be single or dual compressor)NOTE: Largest motor amps may not always be the compressor�
MCA = (1�25 x largest motor amps) + the sum of the remaining motorsMOP = (2�25 x largest motor amps) + the sum of remaining motors
Single Compressor RLA = 7�8 Dual Compressors RLA = 10�4 each Evap� Blower Motor FLA = 1�3 Evap� Blower Motor FLA = 1�8 Cond� Blower Motor FLA = 1�3 Cond� Blower Motor FLA = 6 MCA = (1�25 x 7�8) + 1�3 + 1�3 = 12�4 MCA = (1�25 x 10�4) + 10�4 + 1�8 + 6 = 31�2 MOP = (2�25 x 7�8) + 1�3 + 1�3 = 20 MOP = (2�25 x 10�4) + 10�4 + 1�8 + 6 = 45 Rounded down to 40Evaporator Only Section
MCA = (1�25 x Evap� Blower Motor Amps)MOP = (2�25 x Evap� Blower Motor Amps) Evap� Blower Motor FLA = 3�2 MCA = (1�25 x 3�2) = 4�0
MOP = (2�25 x 3�2) = 7�2 Rounded to 10
Electrical Data
Engineering Guide
C13-Series
13Subject to change without notice. 10.20-TD (0819)
Cooling with Electric Heat:Close Coupled Unit (Can be single or dual compressor) NOTE: Largest motor amps may not always be the compressor�
Electric Heat
On equipment with multiple modes of operation (i�e� cooling or heating), each mode shall be evaluated and whichever load condition provides the highest value shall be used�
Use the larger of the following: MCA = (1�25 x largest motor amps) + the sum of the remaining motors or MCA = (Heater FLA + Evap� Motor FLA) x 1�25 MOP = (2�25 x largest motor amps) + the sum of the remaining motors
or MOP = (Evap� Blower Motor x 2�25) + Heater Amps
Evaporator Only SectionElectric Heat
MCA = (Heater FLA + Evap� Motor FLA) x 1�25 MOP = (Evap� Blower Motor x 2�25) + Heater Amps
Examples
Cooling with Electric Heat:Close Coupled Unit
NOTE: Largest motor amps may not always be the compressor�
Electric Heat
Use the larger of the following: MCA = (1�25 x 26�4) + 4�2 + 4�2 = 41�4 or MCA = (36�11 + 4�2) x 1�25 = 50�4 Use this value MOP = (2�25 x 26�4) + 4�2 + 4�2 = 67�8 Use this value Rounded to 70
or MOP = (4�2 x 2�25) + 36�11 = 45�6
Evaporator Only SectionElectric Heat
MCA = (36�11 + 4�2) x 1�25 = 50�4 MOP = (4�2 x 2�25) + 36�11 = 45�6 MOP can’t be lower than MCA Rounded Up to 55
Electrical Data
Engineering Guide
C13-Series
14Subject to change without notice. 10.20-TD (0819)
Electrical Data
Compressor RLA Electrical Data:
Tons Compressor (Qty) 208/230-1-60 208/230-3-60 460-3-602 1 13.5 7.1 3.53 1 17.0 12.8 6.44 1 21.0 14.7 7.75 1 26.4 17.6 8.36 2 - - - 12.8 ea. 6.4 ea.8 2 - - - 14.7 ea. 7.7 ea.10 2 - - - 16.7 ea. 8.6 ea.
Evaporator Motor FLA:
HP Used In Tons 208/230-1-60 208/230-3-60 460-3-601/3 2, 3, 4 1.7 1.3 0.651/2 3, 4, 5, 6 2.5 1.8 0.93/4 2, 3, 4, 5, 6, 8 3.2 2.4 1.21 3, 4, 5, 6, 8 4.2 3.2 1.6
1-1/2 4, 5, 6, 8, 10 - - - 4.8 2.42 6, 8, 10 - - - 6.8 2.93 10 - - - 8.4 4.05 10 - - - 13.6 6.4
Condenser Motor FLA:HP Used In Tons 208/230-1-60 208/230-3-60 460-3-601/3 2 1.7 1.3 0.651/2 2, 3 2.5 1.8 0.93/4 2, 3, 4 3.2 2.4 1.21 3, 4, 5 4.2 3.2 1.6
1-1/2 2, 3, 4, 5, 6, 8, 10 6.5 4.8 2.42 3, 4, 5, 6, 8, 10 - - - 6.8 2.93 6, 8 - - - 8.4 4.05 8, 10 - - - 13.6 6.4
Engineering Guide
C13-Series
15Subject to change without notice. 10.20-TD (0819)
Electrical Data
Electric Heat FLA: (Heaters nominally rated at 220 or 460 volts�)
Nom. kW Used In Tons 220-1-60 220-3-60 460-3-605 2, 3, 4 22.7 13.1 6.310 3, 4, 5, 6, 8 45.5 26.2 12.615 4, 5, 6, 8 68.2 39.4 18.820 6, 8 - - - 52.5 25.125 8 - - - 65.6 31.435 10 - - - 91.9 43.945 10 - - - 118.1 56.5
NOTE: Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Humidifier FLA:
Used In Tons Unit Voltage Lbs. / Hr.208-1-60 208-3-60 460-3-60
Amps Amps Amps2
208/230-1-60or
208/230-3-60or
460-3-60
4.95 10.8 6.2 2.83 6.6 10.8 6.2 2.84 8.25 18.0 10.4 4.75 11.0 18.0 10.4 4.76 13.2 - - - 16.7 7.58 17.6 - - - 16.7 7.510 22.0 - - - 20.8 9.4
CAUTION: HUMIDIFIER SHOULD NOT BE LOCATED IN SPACE SUBJECT TO FREEZING TEMPERATURES
Water Supply Connection:(1) A 1/4" flare fitting is provided on an exterior panel.(2) Run a 1/2" water line to within 1 foot of the unit before reducing to 1/4" OD for the connector�
Water Quality:(a) Inlet water pressure must be between 15 and 150 psi� If higher than 150 psi, install a regulator�(b) Use only potable water�(c) Water conductivity should be between 125 and 1,250 Micromhos (optimum is 150 to 350 Micromhos)�(d) If water conductivity is over 250 Micromhos, do not use softened water�(e) De-mineralized water cannot be used, as there are no minerals to conduct the electricity�(f) Water pH range of 6�5 to 7�5�
Cylinder Life:
The normal life expectancy of a steam cylinder ranges from 500 to 4,000 hours, dependent upon the water quality and the use profile. Generally it can be expected to be around 2,000 hours.
Engineering Guide
C13-Series
16Subject to change without notice. 10.20-TD (0819)
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized and actual voltage applied�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
2 Ton
Sin
gle C
ircui
t
208/230-1-60 13.5
1/3 1.7 1/2 2.5 - - - - - - - - - - - - 21.1 301/3 1.7 3/4 3.2 - - - - - - - - - - - - 21.8 351/3 1.7 1/2 2.5 5 22.7 Heat - - - 30.5 351/3 1.7 1/2 2.5 5 22.7 Heat 10.8 41.3 451/3 1.7 3/4 3.2 5 22.7 Heat - - - 30.5 351/3 1.7 3/4 3.2 5 22.7 Heat 10.8 41.3 451/3 1.7 1/2 2.5 5 22.7 Reheat - - - 49.5 551/3 1.7 1/2 2.5 5 22.7 Reheat 10.8 60.3 651/3 1.7 3/4 3.2 5 22.7 Reheat - - - 50.2 551/3 1.7 3/4 3.2 5 22.7 Reheat 10.8 61.0 65
208/230-3-60 7.1
1/3 1.3 1/2 1.8 - - - - - - - - - - - - 12.0 151/3 1.3 3/4 2.4 - - - - - - - - - - - - 12.6 151/3 1.3 1/2 1.8 5 13.1 Heat - - - 18.0 201/3 1.3 1/2 1.8 5 13.1 Heat 6.2 24.2 251/3 1.3 3/4 2.4 5 13.1 Heat - - - 18.0 201/3 1.3 3/4 2.4 5 13.1 Heat 6.2 24.2 251/3 1.3 1/2 1.8 5 13.1 Reheat - - - 28.4 301/3 1.3 1/2 1.8 5 13.1 Reheat 6.2 34.6 351/3 1.3 3/4 2.4 5 13.1 Reheat - - - 29.0 301/3 1.3 3/4 2.4 5 13.1 Reheat 6.2 35.2 40
460-3-60 3.5
1/3 0.65 1/2 0.9 - - - - - - - - - - - - 5.9 101/3 0.65 3/4 1.2 - - - - - - - - - - - - 6.2 101/3 0.65 1/2 0.9 5 6.3 Heat - - - 8.7 101/3 0.65 1/2 0.9 5 6.3 Heat 2.8 11.5 151/3 0.65 3/4 1.2 5 6.3 Heat - - - 8.7 101/3 0.65 3/4 1.2 5 6.3 Heat 2.8 11.5 151/3 0.65 1/2 0.9 5 6.3 Reheat - - - 13.8 151/3 0.65 1/2 0.9 5 6.3 Reheat 2.8 16.6 201/3 0.65 3/4 1.2 5 6.3 Reheat - - - 14.1 151/3 0.65 3/4 1.2 5 6.3 Reheat 2.8 16.9 20
Engineering Guide
C13-Series
17Subject to change without notice. 10.20-TD (0819)
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized and actual voltage applied�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
3 Ton
Sin
gle C
ircui
t
208/230-1-60 17.0
1/3 1.7 3/4 3.2 - - - - - - - - - - - - 26.2 401/2 2.5 1 4.2 - - - - - - - - - - - - 28.0 401/3 1.7 3/4 3.2 5 22.7 Heat - - - 30.5 401/3 1.7 3/4 3.2 5 22.7 Heat 10.8 41.3 451/2 2.5 1 4.2 10 45.5 Heat - - - 60.0 651/2 2.5 1 4.2 10 45.5 Heat 10.8 70.8 751/3 1.7 3/4 3.2 5 22.7 Reheat - - - 54.5 651/3 1.7 3/4 3.2 5 22.7 Reheat 10.8 65.3 751/2 2.5 1 4.2 10 45.5 Reheat - - - 84.8 901/2 2.5 1 4.2 10 45.5 Reheat 10.8 95.6 100
208/230-3-60 12.8
1/3 1.3 3/4 2.4 - - - - - - - - - - - - 19.7 301/2 1.8 1 3.2 - - - - - - - - - - - - 21.0 301/3 1.3 3/4 2.4 5 13.1 Heat - - - 19.7 301/3 1.3 3/4 2.4 5 13.1 Heat 6.2 24.2 301/2 1.8 1 3.2 10 26.2 Heat - - - 35.0 401/2 1.8 1 3.2 10 26.2 Heat 6.2 41.2 451/3 1.3 3/4 2.4 5 13.1 Reheat - - - 36.1 451/3 1.3 3/4 2.4 5 13.1 Reheat 6.2 42.3 501/2 1.8 1 3.2 10 26.2 Reheat - - - 53.8 601/2 1.8 1 3.2 10 26.2 Reheat 6.2 60.0 65
460-3-60 6.4
1/3 0.65 3/4 1.2 - - - - - - - - - - - - 9.9 151/2 0.9 1 1.6 - - - - - - - - - - - - 10.5 151/3 0.65 3/4 1.2 5 6.3 Heat - - - 9.6 151/3 0.65 3/4 1.2 5 6.3 Heat 2.8 11.5 151/2 0.9 1 1.6 10 12.6 Heat - - - 16.9 201/2 0.9 1 1.6 10 12.6 Heat 2.8 19.7 201/3 0.65 3/4 1.2 5 6.3 Reheat - - - 17.7 201/3 0.65 3/4 1.2 5 6.3 Reheat 2.8 20.5 251/2 0.9 1 1.6 10 12.6 Reheat - - - 26.3 301/2 0.9 1 1.6 10 12.6 Reheat 2.8 29.1 30
Engineering Guide
C13-Series
18Subject to change without notice. 10.20-TD (0819)
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
4 Ton
Sin
gle C
ircui
t
208/230-1-60 21.0
1/3 1.7 3/4 3.2 - - - - - - - - - - - - 31.2 503/4 3.2 1-1/2 6.5 - - - - - - - - - - - - 36.0 551/3 1.7 3/4 3.2 5 22.7 Heat - - - 31.2 501/3 1.7 3/4 3.2 5 22.7 Heat 18.0 48.5 503/4 3.2 1-1/2 6.5 15 68.2 Heat - - - 89.3 903/4 3.2 1-1/2 6.5 15 68.2 Heat 18.0 107.3 1101/3 1.7 3/4 3.2 5 22.7 Reheat - - - 59.5 701/3 1.7 3/4 3.2 5 22.7 Reheat 18.0 77.5 903/4 3.2 1-1/2 6.5 15 68.2 Reheat - - - 121.2 1253/4 3.2 1-1/2 6.5 15 68.2 Reheat 18.0 139.2 140
208/230-3-60 14.7
1/3 1.3 3/4 2.4 - - - - - - - - - - - - 22.1 353/4 2.4 1-1/2 4.8 - - - - - - - - - - - - 25.6 401/3 1.3 3/4 2.4 5 13.1 Heat - - - 22.1 351/3 1.3 3/4 2.4 5 13.1 Heat 10.4 28.4 353/4 2.4 1-1/2 4.8 15 39.4 Heat - - - 52.3 553/4 2.4 1-1/2 4.8 15 39.4 Heat 10.4 62.7 651/3 1.3 3/4 2.4 5 13.1 Reheat - - - 38.5 451/3 1.3 3/4 2.4 5 13.1 Reheat 10.4 48.9 603/4 2.4 1-1/2 4.8 15 39.4 Reheat - - - 74.8 753/4 2.4 1-1/2 4.8 15 39.4 Reheat 10.4 85.2 90
460-3-60 7.7
1/3 0.65 3/4 1.2 - - - - - - - - - - - - 11.5 153/4 1.2 1-1/2 2.4 - - - - - - - - - - - - 13.2 201/3 0.65 3/4 1.2 5 6.3 Heat - - - 11.5 151/3 0.65 3/4 1.2 5 6.3 Heat 4.7 13.4 153/4 1.2 1-1/2 2.4 15 18.8 Heat - - - 25.0 303/4 1.2 1-1/2 2.4 15 18.8 Heat 4.7 29.7 301/3 0.65 3/4 1.2 5 6.3 Reheat - - - 19.4 251/3 0.65 3/4 1.2 5 6.3 Reheat 4.7 24.1 303/4 1.2 1-1/2 2.4 15 18.8 Reheat - - - 36.7 403/4 1.2 1-1/2 2.4 15 18.8 Reheat 4.7 41.4 45
Engineering Guide
C13-Series
19Subject to change without notice. 10.20-TD (0819)
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
5 Ton
Sin
gle C
ircui
t
208/230-1-60 26.4
1/2 2.5 1-1/2 6.5 - - - - - - - - - - - - 42.0 651 4.2 1-1/2 6.5 - - - - - - - - - - - - 43.7 70
1/2 2.5 1-1/2 6.5 10 45.5 Heat - - - 60.0 651/2 2.5 1-1/2 6.5 10 45.5 Heat 18.0 78.0 801 4.2 1-1/2 6.5 15 68.2 Heat - - - 90.5 951 4.2 1-1/2 6.5 15 68.2 Heat 18.0 108.5 110
1/2 2.5 1-1/2 6.5 10 45.5 Reheat - - - 98.9 1101/2 2.5 1-1/2 6.5 10 45.5 Reheat 18.0 116.9 1301 4.2 1-1/2 6.5 15 68.2 Reheat - - - 129.0 1351 4.2 1-1/2 6.5 15 68.2 Reheat 18.0 147.0 155
208/230-3-60 17.6
1/2 1.8 1-1/2 4.8 - - - - - - - - - - - - 28.6 451 3.2 1-1/2 4.8 - - - - - - - - - - - - 30.0 45
1/2 1.8 1-1/2 4.8 10 26.2 Heat - - - 35.0 451/2 1.8 1-1/2 4.8 10 26.2 Heat 10.4 45.4 501 3.2 1-1/2 4.8 15 39.4 Heat - - - 53.3 551 3.2 1-1/2 4.8 15 39.4 Heat 10.4 63.7 65
1/2 1.8 1-1/2 4.8 10 26.2 Reheat - - - 61.4 701/2 1.8 1-1/2 4.8 10 26.2 Reheat 10.4 71.8 801 3.2 1-1/2 4.8 15 39.4 Reheat - - - 79.3 851 3.2 1-1/2 4.8 15 39.4 Reheat 10.4 89.7 95
460-3-60 8.3
1/2 0.9 1-1/2 2.4 - - - - - - - - - - - - 13.7 201 1.6 1-1/2 2.4 - - - - - - - - - - - - 14.4 20
1/2 0.9 1-1/2 2.4 10 12.6 Heat - - - 16.9 201/2 0.9 1-1/2 2.4 10 12.6 Heat 4.7 21.6 251 1.6 1-1/2 2.4 15 18.8 Heat - - - 25.5 301 1.6 1-1/2 2.4 15 18.8 Heat 4.7 30.2 35
1/2 0.9 1-1/2 2.4 10 12.6 Reheat - - - 29.4 301/2 0.9 1-1/2 2.4 10 12.6 Reheat 4.7 34.1 351 1.6 1-1/2 2.4 15 18.8 Reheat - - - 37.9 401 1.6 1-1/2 2.4 15 18.8 Reheat 4.7 42.6 45
Engineering Guide
C13-Series
20Subject to change without notice. 10.20-TD (0819)
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
6 Ton
Dua
l Circ
uit
208/230-3-60 12.8 ea.
1/2 1.8 1-1/2 4.8 - - - - - - - - - - - - 35.4 451 3.2 2 6.8 - - - - - - - - - - - - 38.8 50
1/2 1.8 1-1/2 4.8 10 26.2 Heat - - - 35.4 451/2 1.8 1-1/2 4.8 10 26.2 Heat 16.7 51.7 551 3.2 2 6.8 20 52.5 Heat - - - 69.6 701 3.2 2 6.8 20 52.5 Heat 16.7 86.3 90
1/2 1.8 1-1/2 4.8 10 26.2 Reheat - - - 68.2 751/2 1.8 1-1/2 4.8 10 26.2 Reheat 16.7 84.9 901 3.2 2 6.8 20 52.5 Reheat - - - 104.4 1051 3.2 2 6.8 20 52.5 Reheat 16.7 121.1 125
460-3-60 6.4 ea.
1/2 0.9 1-1/2 2.4 - - - - - - - - - - - - 17.7 201 1.6 2 2.9 - - - - - - - - - - - - 18.9 25
1/2 0.9 1-1/2 2.4 10 12.6 Heat - - - 17.7 201/2 0.9 1-1/2 2.4 10 12.6 Heat 7.5 24.4 251 1.6 2 2.9 20 25.1 Heat - - - 33.4 351 1.6 2 2.9 20 25.1 Heat 7.5 40.9 45
1/2 0.9 1-1/2 2.4 10 12.6 Reheat - - - 33.6 351/2 0.9 1-1/2 2.4 10 12.6 Reheat 7.5 41.0 451 1.6 2 2.9 20 25.1 Reheat - - - 50.3 551 1.6 2 2.9 20 25.1 Reheat 7.5 57.8 60
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
21Subject to change without notice. 10.20-TD (0819)
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
8 Ton
Dua
l Circ
uit
208/230-3-60 14.7 ea.
3/4 2.4 3 8.4 - - - - - - - - - - - - 43.9 551-1/2 4.8 3 8.4 - - - - - - - - - - - - 46.3 603/4 2.4 3 8.4 10 26.2 Heat - - - 43.9 553/4 2.4 3 8.4 10 26.2 Heat 16.7 52.5 55
1-1/2 4.8 3 8.4 25 65.6 Heat - - - 88.0 901-1/2 4.8 3 8.4 25 65.6 Heat 16.7 104.7 1053/4 2.4 3 8.4 10 26.2 Reheat - - - 76.6 803/4 2.4 3 8.4 10 26.2 Reheat 16.7 93.3 100
1-1/2 4.8 3 8.4 25 65.6 Reheat - - - 128.3 1301-1/2 4.8 3 8.4 25 65.6 Reheat 16.7 145.0 150
460-3-60 7.7 ea.
3/4 1.2 3 4.0 - - - - - - - - - - - - 21.4 251-1/2 2.4 3 4.0 - - - - - - - - - - - - 23.7 303/4 1.2 3 4.0 10 12.6 Heat - - - 21.4 253/4 1.2 3 4.0 10 12.6 Heat 7.5 24.8 25
1-1/2 2.4 3 4.0 25 31.4 Heat - - - 42.3 451-1/2 2.4 3 4.0 25 31.4 Heat 7.5 49.8 503/4 1.2 3 4.0 10 12.6 Reheat - - - 37.2 403/4 1.2 3 4.0 10 12.6 Reheat 7.5 44.7 45
1-1/2 2.4 3 4.0 25 31.4 Reheat - - - 63.0 651-1/2 2.4 3 4.0 25 31.4 Reheat 7.5 70.5 75
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
22Subject to change without notice. 10.20-TD (0819)
Electrical Data - Air-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Condenser Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA HP FLA KW Amps Used As Amps MCA MOP
10 To
n Du
al Ci
rcui
t
208/230-3-60 16.7 ea.
1-1/2 4.8 1-1/2 4.8 - - - - - - - - - - - - 47.2 602 6.8 2 6.8 - - - - - - - - - - - - 51.2 65
1-1/2 4.8 1-1/2 4.8 35 91.9 Heat - - - 120.9 1251-1/2 4.8 1-1/2 4.8 35 91.9 Heat 20.8 141.7 145
2 6.8 2 6.8 45 118.1 Heat - - - 156.1 1602 6.8 2 6.8 45 118.1 Heat 20.8 176.9 180
1-1/2 4.8 1-1/2 4.8 35 91.9 Reheat - - - 162.1 1651-1/2 4.8 1-1/2 4.8 35 91.9 Reheat 20.8 182.9 185
2 6.8 2 6.8 45 118.1 Reheat - - - 198.8 2002 6.8 2 6.8 45 118.1 Reheat 20.8 219.6 220
460-3-60 8.6 ea.
1-1/2 2.4 1-1/2 2.4 - - - - - - - - - - - - 24.2 302 2.9 2 2.9 - - - - - - - - - - - - 25.2 30
1-1/2 2.4 1-1/2 2.4 35 43.9 Heat - - - 57.9 601-1/2 2.4 1-1/2 2.4 35 43.9 Heat 9.4 67.3 70
2 2.9 2 2.9 45 56.5 Heat - - - 74.3 752 2.9 2 2.9 45 56.5 Heat 9.4 83.7 85
1-1/2 2.4 1-1/2 2.4 35 43.9 Reheat - - - 79.0 801-1/2 2.4 1-1/2 2.4 35 43.9 Reheat 9.4 88.4 90
2 2.9 2 2.9 45 56.5 Reheat - - - 95.8 1002 2.9 2 2.9 45 56.5 Reheat 9.4 105.2 110
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
23Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
2 Ton
Sin
gle C
ircui
t
208/230-1-60 13.5
1/3 1.7 - - - - - - - - - - - - 18.6 301/3 1.7 5 22.7 Heat - - - 30.5 351/3 1.7 5 22.7 Heat 8.1 41.3 451/3 1.7 5 22.7 Reheat - - - 47.0 501/3 1.7 5 22.7 Reheat 8.1 57.8 65
208/230-3-60 7.1
1/3 1.3 - - - - - - - - - - - - 10.2 151/3 1.3 5 13.1 Heat - - - 18.0 201/3 1.3 5 13.1 Heat 4.7 24.2 251/3 1.3 5 13.1 Reheat - - - 26.6 301/3 1.3 5 13.1 Reheat 4.7 32.8 35
460-3-60 3.5
1/3 0.65 - - - - - - - - - - - - 5.0 101/3 0.65 5 6.3 Heat - - - 8.7 101/3 0.65 5 6.3 Heat 2.1 11.5 151/3 0.65 5 6.3 Reheat - - - 12.9 151/3 0.65 5 6.3 Reheat 2.1 15.7 20
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
24Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
3 Ton
Sin
gle C
ircui
t
208/230-1-60 17.0
1/3 1.7 - - - - - - - - - - - - 23.0 351/2 2.5 - - - - - - - - - - - - 23.8 401/3 1.7 5 22.7 Heat - - - 30.5 351/3 1.7 5 22.7 Heat 10.8 41.3 451/2 2.5 10 45.5 Heat - - - 60.0 651/2 2.5 10 45.5 Heat 10.8 70.8 751/3 1.7 5 22.7 Reheat - - - 51.3 601/3 1.7 5 22.7 Reheat 10.8 62.1 701/2 2.5 10 45.5 Reheat - - - 80.6 851/2 2.5 10 45.5 Reheat 10.8 91.4 95
208/230-3-60 12.8
1/3 1.3 - - - - - - - - - - - - 17.3 301/2 1.8 - - - - - - - - - - - - 17.8 301/3 1.3 5 13.1 Heat - - - 18.0 301/3 1.3 5 13.1 Heat 6.2 24.2 301/2 1.8 10 26.2 Heat - - - 35.0 401/2 1.8 10 26.2 Heat 6.2 41.2 451/3 1.3 5 13.1 Reheat - - - 33.7 401/3 1.3 5 13.1 Reheat 6.2 39.9 451/2 1.8 10 26.2 Reheat - - - 50.6 551/2 1.8 10 26.2 Reheat 6.2 56.8 60
460-3-60 6.4
1/3 0.65 - - - - - - - - - - - - 8.7 151/2 0.9 - - - - - - - - - - - - 8.9 151/3 0.65 5 6.3 Heat - - - 8.7 151/3 0.65 5 6.3 Heat 2.8 11.5 151/2 0.9 10 12.6 Heat - - - 16.9 201/2 0.9 10 12.6 Heat 2.8 19.7 201/3 0.65 5 6.3 Reheat - - - 16.5 201/3 0.65 5 6.3 Reheat 2.8 19.3 201/2 0.9 10 12.6 Reheat - - - 24.7 251/2 0.9 10 12.6 Reheat 2.8 27.5 30
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
25Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
4 Ton
Sin
gle C
ircui
t
208/230-1-60 21.0
1/3 1.7 - - - - - - - - - - - - 28.0 453/4 3.2 - - - - - - - - - - - - 29.5 501/3 1.7 5 22.1 Heat - - - 29.8 451/3 1.7 5 22.1 Heat 18.0 47.8 503/4 3.2 15 68.2 Heat - - - 89.3 903/4 3.2 15 68.2 Heat 18.0 107.3 1101/3 1.7 5 22.1 Reheat - - - 55.6 701/3 1.7 5 22.1 Reheat 18.0 73.6 853/4 3.2 15 68.2 Reheat - - - 114.7 1153/4 3.2 15 68.2 Reheat 18.0 132.7 135
208/230-3-60 14.7
1/3 1.3 - - - - - - - - - - - - 19.7 303/4 2.4 - - - - - - - - - - - - 20.8 351/3 1.3 5 13.1 Heat - - - 19.7 301/3 1.3 5 13.1 Heat 10.4 28.4 303/4 2.4 15 39.4 Heat - - - 52.3 553/4 2.4 15 39.4 Heat 10.4 62.7 651/3 1.3 5 13.1 Reheat - - - 36.1 451/3 1.3 5 13.1 Reheat 10.4 46.5 553/4 2.4 15 39.4 Reheat - - - 70.0 753/4 2.4 15 39.4 Reheat 10.4 80.4 85
460-3-60 7.7
1/3 0.65 - - - - - - - - - - - - 10.3 153/4 1.2 - - - - - - - - - - - - 10.8 151/3 0.65 5 6.3 Heat - - - 10.3 151/3 0.65 5 6.3 Heat 4.7 13.4 153/4 1.2 15 18.8 Heat - - - 25.0 303/4 1.2 15 18.8 Heat 4.7 29.7 301/3 0.65 5 6.3 Reheat - - - 18.2 201/3 0.65 5 6.3 Reheat 4.7 22.9 253/4 1.2 15 18.8 Reheat - - - 34.3 353/4 1.2 15 18.8 Reheat 4.7 39.0 40
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
26Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
5 Ton
Sin
gle C
ircui
t
208/230-1-60 26.4
1/2 2.5 - - - - - - - - - - - - 35.5 601 4.2 - - - - - - - - - - - - 37.2 60
1/2 2.5 10 45.5 Heat - - - 60.0 651/2 2.5 10 45.5 Heat 18.0 78.0 801 4.2 15 68.2 Heat - - - 90.5 951 4.2 15 68.2 Heat 18.0 108.5 110
1/2 2.5 10 45.5 Reheat - - - 92.4 1051/2 2.5 10 45.5 Reheat 18.0 110.4 1251 4.2 15 68.2 Reheat - - - 122.5 1301 4.2 15 68.2 Reheat 18.0 140.5 145
208/230-3-60 17.6
1/2 1.8 - - - - - - - - - - - - 23.8 401 3.2 - - - - - - - - - - - - 25.2 40
1/2 1.8 10 26.2 Heat - - - 35.0 401/2 1.8 10 26.2 Heat 10.4 45.4 501 3.2 15 39.4 Heat - - - 53.3 551 3.2 15 39.4 Heat 10.4 63.7 65
1/2 1.8 10 26.2 Reheat - - - 56.6 651/2 1.8 10 26.2 Reheat 10.4 67.0 751 3.2 15 39.4 Reheat - - - 74.5 801 3.2 15 39.4 Reheat 10.4 84.9 90
460-3-60 8.3
1/2 0.9 - - - - - - - - - - - - 11.3 151 1.6 - - - - - - - - - - - - 12.0 20
1/2 0.9 10 12.6 Heat - - - 16.9 201/2 0.9 10 12.6 Heat 4.7 21.6 251 1.6 15 18.8 Heat - - - 25.5 301 1.6 15 18.8 Heat 4.7 30.2 35
1/2 0.9 10 12.6 Reheat - - - 27.0 301/2 0.9 10 12.6 Reheat 4.7 31.7 351 1.6 15 18.8 Reheat - - - 35.5 401 1.6 15 18.8 Reheat 4.7 40.2 45
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
27Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
6 Ton
Dua
l Circ
uit
208/230-3-60 12.8 ea.
1/2 1.8 - - - - - - - - - - - - 30.6 401 3.2 - - - - - - - - - - - - 32.0 40
1/2 1.8 10 26.2 Heat - - - 35.0 401/2 1.8 10 26.2 Heat 16.7 51.7 551 3.2 20 52.5 Heat - - - 69.6 701 3.2 20 52.5 Heat 16.7 86.3 90
1/2 1.8 10 26.2 Reheat - - - 63.4 651/2 1.8 10 26.2 Reheat 16.7 80.1 851 3.2 20 52.5 Reheat - - - 97.6 1001 3.2 20 52.5 Reheat 16.7 114.3 115
460-3-60 6.4 ea.
1/2 0.9 - - - - - - - - - - - - 15.3 201 1.6 - - - - - - - - - - - - 16.0 20
1/2 0.9 10 12.6 Heat - - - 16.9 201/2 0.9 10 12.6 Heat 7.5 24.4 251 1.6 20 25.1 Heat - - - 33.4 351 1.6 20 25.1 Heat 7.5 40.9 45
1/2 0.9 10 12.6 Reheat - - - 31.1 351/2 0.9 10 12.6 Reheat 7.5 38.6 401 1.6 20 25.1 Reheat - - - 47.4 501 1.6 20 25.1 Reheat 7.5 54.9 55
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
28Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
8 Ton
Dua
l Circ
uit
208/230-3-60 14.7 ea.
3/4 2.4 - - - - - - - - - - - - 35.5 501-1/2 4.8 - - - - - - - - - - - - 37.9 503/4 2.4 10 26.2 Heat - - - 35.8 503/4 2.4 10 26.2 Heat 16.7 52.5 55
1-1/2 4.8 25 65.6 Heat - - - 88.0 901-1/2 4.8 25 65.6 Heat 16.7 104.7 1053/4 2.4 10 26.2 Reheat - - - 68.2 753/4 2.4 10 26.2 Reheat 16.7 84.9 90
1-1/2 4.8 25 65.6 Reheat - - - 119.9 1201-1/2 4.8 25 65.6 Reheat 16.7 136.6 140
460-3-60 7.7 ea.
3/4 1.2 - - - - - - - - - - - - 18.5 251-1/2 2.4 - - - - - - - - - - - - 19.7 253/4 1.2 10 12.6 Heat - - - 18.5 253/4 1.2 10 12.6 Heat 7.5 24.8 25
1-1/2 2.4 25 31.4 Heat - - - 42.3 451-1/2 2.4 25 31.4 Heat 7.5 49.8 503/4 1.2 10 12.6 Reheat - - - 34.3 353/4 1.2 10 12.6 Reheat 7.5 41.8 45
1-1/2 2.4 25 31.4 Reheat - - - 59.0 601-1/2 2.4 25 31.4 Reheat 7.5 66.5 70
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
29Subject to change without notice. 10.20-TD (0819)
Electrical Data - Water-Cooled (c) (d) (e)
Tons Voltage Compressor RLA
Evaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
10 To
n Du
al Ci
rcui
t 208/230-3-60 16.7 ea.
1-1/2 4.8 - - - - - - - - - - - - 42.4 552 6.8 - - - - - - - - - - - - 44.4 60
1-1/2 4.8 35 91.9 Heat - - - 120.9 1252 6.8 45 118.1 Heat 20.8 176.9 180
1-1/2 4.8 35 91.9 Reheat - - - 157.3 1602 6.8 45 118.1 Reheat 20.8 192.0 195
460-3-60 8.6 ea.
1-1/2 2.4 - - - - - - - - - - - - 21.8 302 2.9 - - - - - - - - - - - - 22.3 30
1-1/2 2.4 35 43.9 Heat - - - 57.9 602 2.9 45 56.5 Heat 9.4 83.7 85
1-1/2 2.4 35 43.9 Reheat - - - 76.6 802 2.9 45 56.5 Reheat 9.4 102.3 105
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
30Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
2 Ton Single Circuit
208/230-1-60
1/3 1.7 - - - - - - - - - - - - 2.1 51/3 1.7 5 22.7 Heat - - - 30.5 351/3 1.7 5 22.7 Heat 10.8 41.3 451/3 1.7 5 22.7 Reheat - - - 30.5 351/3 1.7 5 22.7 Reheat 10.8 41.3 45
208/230-3-60
1/3 1.3 - - - - - - - - - - - - 1.6 51/3 1.3 5 13.1 Heat - - - 18.0 201/3 1.3 5 13.1 Heat 6.2 24.2 251/3 1.3 5 13.1 Reheat - - - 18.0 201/3 1.3 5 13.1 Reheat 6.2 24.2 25
460-3-60
1/3 0.65 - - - - - - - - - - - - 0.8 51/3 0.65 5 6.3 Heat - - - 8.7 101/3 0.65 5 6.3 Heat 2.8 11.5 151/3 0.65 5 6.3 Reheat - - - 8.7 101/3 0.65 5 6.3 Reheat 2.8 11.5 15
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations/applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
31Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
3 Ton Single Circuit
208/230-1-60
1/3 1.7 - - - - - - - - - - - - 2.1 51/2 2.5 - - - - - - - - - - - - 3.1 51/3 1.7 5 22.7 Heat - - - 30.5 351/3 1.7 5 22.7 Heat 10.8 41.3 451/2 2.5 10 45.5 Heat - - - 60.0 651/2 2.5 10 45.5 Heat 10.8 70.8 751/3 1.7 5 22.7 Reheat - - - 30.5 351/3 1.7 5 22.7 Reheat 10.8 41.3 451/2 2.5 10 45.5 Reheat - - - 60.0 651/2 2.5 10 45.5 Reheat 10.8 70.8 75
208/230-3-60
1/3 1.3 - - - - - - - - - - - - 1.6 51/2 1.8 - - - - - - - - - - - - 2.3 51/3 1.3 5 13.1 Heat - - - 18.0 201/3 1.3 5 13.1 Heat 6.2 24.2 251/2 1.8 10 26.2 Heat - - - 35.0 401/2 1.8 10 26.2 Heat 6.2 41.2 451/3 1.3 5 13.1 Reheat - - - 18.0 201/3 1.3 5 13.1 Reheat 6.2 24.2 251/2 1.8 10 26.2 Reheat - - - 35.0 401/2 1.8 10 26.2 Reheat 6.2 41.2 45
460-3-60
1/3 0.65 - - - - - - - - - - - - 0.8 51/2 0.9 - - - - - - - - - - - - 1.1 51/3 0.65 5 6.3 Heat - - - 8.7 101/3 0.65 5 6.3 Heat 2.8 11.5 151/2 0.9 10 12.6 Heat - - - 16.9 201/2 0.9 10 12.6 Heat 2.8 19.7 201/3 0.65 5 6.3 Reheat - - - 8.7 101/3 0.65 5 6.3 Reheat 2.8 11.5 151/2 0.9 10 12.6 Reheat - - - 16.9 201/2 0.9 10 12.6 Reheat 2.8 19.7 20
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
32Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
4 Ton Single Circuit
208/230-1-60
1/3 1.7 - - - - - - - - - - - - 2.1 53/4 3.2 - - - - - - - - - - - - 4.0 51/3 1.7 5 22.7 Heat - - - 30.5 351/3 1.7 5 22.7 Heat 18.0 48.5 503/4 3.2 15 68.2 Heat - - - 89.3 903/4 3.2 15 68.2 Heat 18.0 107.3 1101/3 1.7 5 22.7 Reheat - - - 30.5 351/3 1.7 5 22.7 Reheat 18.0 48.5 503/4 3.2 15 68.2 Reheat - - - 89.3 903/4 3.2 15 68.2 Reheat 18.0 107.3 110
208/230-3-60
1/3 1.3 - - - - - - - - - - - - 1.6 53/4 2.4 - - - - - - - - - - - - 3.0 51/3 1.3 5 13.1 Heat - - - 18.0 201/3 1.3 5 13.1 Heat 10.4 28.4 303/4 2.4 15 39.4 Heat - - - 52.3 553/4 2.4 15 39.4 Heat 10.4 62.7 651/3 1.3 5 13.1 Reheat - - - 18.0 201/3 1.3 5 13.1 Reheat 10.4 28.4 303/4 2.4 15 39.4 Reheat - - - 52.3 553/4 2.4 15 39.4 Reheat 10.4 62.7 65
460-3-60
1/3 0.65 - - - - - - - - - - - - 0.8 53/4 1.2 - - - - - - - - - - - - 1.5 51/3 0.65 5 6.3 Heat - - - 8.7 101/3 0.65 5 6.3 Heat 4.7 13.4 153/4 1.2 15 18.8 Heat - - - 25.0 303/4 1.2 15 18.8 Heat 4.7 29.7 301/3 0.65 5 6.3 Reheat - - - 8.7 101/3 0.65 5 6.3 Reheat 4.7 13.4 153/4 1.2 15 18.8 Reheat - - - 25.0 303/4 1.2 15 18.8 Reheat 4.7 29.7 30
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations/applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
33Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
5 Ton Single Circuit
208/230-1-60
1/2 2.5 - - - - - - - - - - - - 3.1 51 4.2 - - - - - - - - - - - - 5.3 10
1/2 2.5 10 45.5 Heat - - - 60.0 651/2 2.5 10 45.5 Heat 18.0 78.0 801 4.2 15 68.2 Heat - - - 90.5 951 4.2 15 68.2 Heat 18.0 108.5 110
1/2 2.5 10 45.5 Reheat - - - 60.0 651/2 2.5 10 45.5 Reheat 18.0 78.0 801 4.2 15 68.2 Reheat - - - 90.5 951 4.2 15 68.2 Reheat 18.0 108.5 110
208/230-3-60
1/2 1.8 - - - - - - - - - - - - 2.3 51 3.2 - - - - - - - - - - - - 4.0 5
1/2 1.8 10 26.2 Heat - - - 35.0 401/2 1.8 10 26.2 Heat 10.4 45.4 501 3.2 15 39.4 Heat - - - 53.3 551 3.2 15 39.4 Heat 10.4 63.7 65
1/2 1.8 10 26.2 Reheat - - - 35.0 401/2 1.8 10 26.2 Reheat 10.4 45.4 501 3.2 15 39.4 Reheat - - - 53.3 551 3.2 15 39.4 Reheat 10.4 63.7 65
460-3-60
1/2 0.9 - - - - - - - - - - - - 1.1 51 1.6 - - - - - - - - - - - - 2.0 5
1/2 0.9 10 12.6 Heat - - - 16.9 201/2 0.9 10 12.6 Heat 4.7 21.6 251 1.6 15 18.8 Heat - - - 25.5 301 1.6 15 18.8 Heat 4.7 30.2 35
1/2 0.9 10 12.6 Reheat - - - 16.9 201/2 0.9 10 12.6 Reheat 4.7 21.6 251 1.6 15 18.8 Reheat - - - 25.5 301 1.6 15 18.8 Reheat 4.7 30.2 35
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
34Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
6 Ton Dual
Circuit
208/230-3-60
1/2 1.8 - - - - - - - - - - - - 2.3 51 3.2 - - - - - - - - - - - - 4.0 5
1/2 1.8 10 26.2 Heat - - - 35.0 401/2 1.8 10 26.2 Heat 16.7 51.7 551 3.2 20 52.5 Heat - - - 69.6 701 3.2 20 52.5 Heat 16.7 86.3 90
1/2 1.8 10 26.2 Reheat - - - 35.0 401/2 1.8 10 26.2 Reheat 16.7 51.7 551 3.2 20 52.5 Reheat - - - 69.6 701 3.2 20 52.5 Reheat 16.7 86.3 90
460-3-60
1/2 0.9 - - - - - - - - - - - - 1.1 51 1.6 - - - - - - - - - - - - 2.0 5
1/2 0.9 10 12.6 Heat - - - 16.9 201/2 0.9 10 12.6 Heat 7.5 24.4 251 1.6 20 25.1 Heat - - - 33.4 351 1.6 20 25.1 Heat 7.5 40.9 45
1/2 0.9 10 12.6 Reheat - - - 16.9 201/2 0.9 10 12.6 Reheat 7.5 24.4 251 1.6 20 25.1 Reheat - - - 33.4 351 1.6 20 25.1 Reheat 7.5 40.9 45
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
35Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
8 Ton Dual
Circuit
208/230-3-60
3/4 2.4 - - - - - - - - - - - - 3.0 51-1/2 4.8 - - - - - - - - - - - - 6.0 103/4 2.4 10 26.2 Heat - - - 35.8 403/4 2.4 10 26.2 Heat 16.7 52.5 55
1-1/2 4.8 25 65.6 Heat - - - 88.0 901-1/2 4.8 25 65.6 Heat 16.7 104.7 1053/4 2.4 10 26.2 Reheat - - - 35.8 403/4 2.4 10 26.2 Reheat 16.7 52.5 55
1-1/2 4.8 25 65.6 Reheat - - - 88.0 901-1/2 4.8 25 65.6 Reheat 16.7 104.7 105
460-3-60
3/4 1.2 - - - - - - - - - - - - 1.5 51-1/2 2.4 - - - - - - - - - - - - 3.0 53/4 1.2 10 12.6 Heat - - - 17.3 203/4 1.2 10 12.6 Heat 7.5 24.8 25
1-1/2 2.4 25 31.4 Heat - - - 42.3 451-1/2 2.4 25 31.4 Heat 7.5 49.8 503/4 1.2 10 12.6 Reheat - - - 17.3 203/4 1.2 10 12.6 Reheat 7.5 24.8 25
1-1/2 2.4 25 31.4 Reheat - - - 42.3 451-1/2 2.4 25 31.4 Reheat 7.5 49.8 50
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
36Subject to change without notice. 10.20-TD (0819)
Electrical Data - Evaporator Section (c) (d) (e)
Tons VoltageEvaporator Motor Electric Heat (a) (b) (f) Humidifier UnitHP FLA KW Amps Used As Amps MCA MOP
10 Ton Dual
Circuit
208/230-3-60
1-1/2 4.8 - - - - - - - - - - - - 6.0 102 6.8 - - - - - - - - - - - - 8.5 15
1-1/2 4.8 35 91.9 Heat - - - 120.9 1252 6.8 35 91.9 Heat 20.8 144.2 145
1-1/2 4.8 45 118.1 Heat - - - 153.6 1552 6.8 45 118.1 Heat 20.8 176.9 180
1-1/2 4.8 35 91.9 Reheat - - - 120.9 1252 6.8 35 91.9 Reheat 20.8 144.2 145
1-1/2 4.8 45 118.1 Reheat - - - 153.6 1552 6.8 45 118.1 Reheat 20.8 176.9 180
460-3-60
1-1/2 2.4 - - - - - - - - - - - - 3.0 52 2.9 - - - - - - - - - - - - 3.6 5
1-1/2 2.4 35 43.9 Heat - - - 57.9 602 2.9 35 43.9 Heat 9.4 67.9 70
1-1/2 2.4 45 56.5 Heat - - - 73.6 752 2.9 45 56.5 Heat 9.4 83.7 85
1-1/2 2.4 35 43.9 Reheat - - - 57.9 602 2.9 35 43.9 Reheat 9.4 67.9 70
1-1/2 2.4 45 56.5 Reheat - - - 73.6 752 2.9 45 56.5 Reheat 9.4 83.7 85
(a) Electric heaters nominally rated and listed at 220 or 460 volts�(b) Electric heaters listed being used for heat or reheat as indicated�(c) Use Copper Conductors Only�(d) Values listed are typical and may vary dependent upon components utilized�(e) All unit electrical capabilities not shown. Contact factory for specific unit combinations.(f) Under some situations / applications it may be required to provide dual point power to units with electric heat� This is beyond the
Engineering Guide capability� Use UCA Select to get a determination or contact a local rep or the factory for a determination�
Engineering Guide
C13-Series
37Subject to change without notice. 10.20-TD (0819)
(a) Use Copper Conductors Only�(b) Values listed are typical and may vary dependent upon components utilized�(c) All unit electrical capabilities not shown. Contact factory for specific unit combinations.
Electrical Data - Air-Cooled Condensing Section (a) (b) (c)
Tons Voltage Compressor RLACondenser Motor Unit
HP FLA MCA MOP
2 Ton Single Circuit
208/230-1-60 13.51/2 2.5 19.4 303/4 3.2 20.1 30
208/230-3-60 7.11/2 1.8 10.7 153/4 2.4 11.3 15
460-3-60 3.51/2 0.9 5.3 103/4 1.2 5.6 10
3 Ton Single Circuit
208/230-1-60 17.03/4 3.2 24.5 401 4.2 25.5 40
208/230-3-60 12.83/4 2.4 18.4 301 3.2 19.2 30
460-3-60 6.43/4 1.2 9.2 151 1.6 9.6 15
4 Ton Single Circuit
208/230-1-60 21.03/4 3.2 29.5 50
1-1/2 6.5 32.8 50
208/230-3-60 14.73/4 2.4 20.8 35
1-1/2 4.8 23.2 35
460-3-60 7.73/4 1.2 10.8 15
1-1/2 2.4 12.0 15
5 Ton Single Circuit
208/230-1-60 26.4 1-1/2 6.5 39.5 65208/230-3-60 17.6 1-1/2 4.8 26.8 40
460-3-60 8.3 1-1/2 2.4 12.8 20
Engineering Guide
C13-Series
38Subject to change without notice. 10.20-TD (0819)
(a) Use Copper Conductors Only�(b) Values listed are typical and may vary dependent upon components utilized�(c) All unit electrical capabilities not shown. Contact factory for specific unit combinations.
Electrical Data - Air-Cooled Condensing Section (a) (b) (c)
Tons Voltage Compressor RLACondenser Motor Unit
HP FLA MCA MOP
6 Ton Dual Circuit
208/230-3-60 12.8 ea.1-1/2 4.8 33.6 45
2 6.8 35.6 45
460-3-60 6.4 ea.1-1/2 2.4 16.8 20
2 2.9 17.3 206 Ton
Dual Circuit208/230-3-60 14.7 ea. 3 8.4 41.5 55
460-3-60 7.7 ea. 3 4.0 21.3 25
10 Ton Dual Circuit
208/230-3-60 16.7 ea.1-1/2 4.8 42.4 55
2 6.8 44.4 60
460-3-60 8.6 ea.1-1/2 2.4 21.8 30
2 2.9 22.3 30
Engineering Guide
C13-Series
39Subject to change without notice. 10.20-TD (0819)
Electrical Data - Air-Cooled Condenser (a) (b) (c)
Tons VoltageCondenser Motor Unit
HP FLA MCA MOP
2 Ton Single Circuit
208/230-1-601/2 2.5 3.1 53/4 3.2 4.0 5
208/230-3-601/2 1.8 2.3 53/4 2.4 3.0 5
460-3-601/2 0.9 1.1 53/4 1.2 1.5 5
3 Ton Single Circuit
208/230-1-603/4 3.2 4.0 51 4.2 5.3 10
208/230-3-603/4 2.4 3.0 51 3.2 4.0 5
460-3-603/4 1.2 1.5 51 1.6 2.0 5
4 Ton Single Circuit
208/230-1-603/4 3.2 4.0 5
1-1/2 6.5 8.1 10
208/230-3-603/4 2.4 3.0 5
1-1/2 4.8 6.0 10
460-3-603/4 1.2 1.5 5
1-1/2 2.4 3.0 5
5 Ton Single Circuit
208/230-1-60 1-1/2 6.5 8.1 10208/230-3-60 1-1/2 4.8 6.0 10
460-3-60 1-1/2 2.4 3.0 5
6 Ton Dual Circuit
208/230-3-601-1/2 4.8 6.0 10
2 6.8 8.5 15
460-3-601-1/2 2.4 3.0 5
2 2.9 3.6 58 Ton
Dual Circuit208/230-3-60 3 8.4 10.5 15
460-3-60 3 4.0 5.0 10
10 Ton Dual Circuit
208/230-3-601-1/2 4.8 6.0 10
2 6.8 8.5 15
460-3-601-1/2 2.4 3.0 5
2 2.9 3.6 5
(a) Use Copper Conductors Only�(b) Values listed are typical and may vary dependent upon components utilized�(c) All unit electrical capabilities not shown. Contact factory for specific unit combinations.
Engineering Guide
C13-Series
40Subject to change without notice. 10.20-TD (0819)
(a) Use Copper Conductors Only�(b) Values listed are typical and may vary dependent upon components utilized�(c) All unit electrical capabilities not shown. Contact factory for specific unit combinations.
Electrical Data - Water-Cooled Condensing Section (a) (b) (c)
Tons VoltageCompressor Unit
RLA MCA MOP
2 Ton Single Circuit
208/230-1-60 13.5 16.9 30208/230-3-60 7.1 8.9 15
460-3-60 3.5 4.4 5
3 Ton Single Circuit
208/230-1-60 17.0 21.3 35208/230-3-60 12.8 16.0 25
460-3-60 6.4 8.0 10
4 Ton Single Circuit
208/230-1-60 21.0 26.3 45208/230-3-60 14.7 18.4 30
460-3-60 7.7 9.6 15
5 Ton Single Circuit
208/230-1-60 26.4 33.0 55208/230-3-60 17.6 22.0 35
460-3-60 8.3 10.4 156 Ton
Dual Circuit208/230-3-60 12.8 ea. 28.8 40
460-3-60 6.4 ea. 14.4 208 Ton
Dual Circuit208/230-3-60 14.7 ea. 33.1 45
460-3-60 7.7 ea. 17.3 2510 Ton
Dual Circuit208/230-3-60 16.7 ea. 37.6 50
460-3-60 8.6 ea. 19.4 25
Engineering Guide
C13-Series
41Subject to change without notice. 10.20-TD (0819)
Water-Cooled Piping Arrangements
2-Way Single Circuit
2-Way Valve 2-Way Valve
3-Way Valve
3-Way Valve
3-Way Valve
Condensing Coil Condensing Coil
Condensing Coil
Water In
Water Out
Water In
N.O. Solenoid Valve
N.O. Solenoid Valve
Water Out
Water In
Water Out
3-Way Single Circuit
2-Way Valve
Condensing Coil
Water In
Water Out
2-Way Dual Circuit with Water Side Economizer
2-Way Single Circuit with Bypass
Water Side Economizer
Evaporator Section
Condensing Section
3-Way Valve3-Way Valve
Condensing Coil
Water In
Water Out
3-Way Single Circuit with Water Side Economizer
Water Side Economizer
Evaporator Section
Condensing Section
2-Way Valve
Condensing Coil
Water In
Water Out
2-Way Single Circuit with Bypassand Water Side Economizer
Water Side Economizer
Evaporator Section
Condensing Section
Engineering Guide
C13-Series
42Subject to change without notice. 10.20-TD (0819)
Water-Cooled Piping Arrangements
2-Way Valve
2-Way Valve
2-Way Valve
3-Way Valve
2-Way Valve
2-Way Valve
Condensing Coil
Condensing Coil
Condensing Coil
Condensing Coil
Condensing Coil
Condensing Coil
Water In
N.O. Solenoid Valve
Water Out
Water In
Water Out
Water In
Water Out
2-Way Dual Circuit
2-Way Valve
2-Way Valve
Condensing Coil
Condensing Coil
Water Out
2-Way Dual Circuit with Bypassand Water Side Economizer
3-Way Dual Circuit
2-Way Dual Circuit with Bypass
Evaporator Section
Condensing Section3-Way Valve
N.O. Solenoid Valve
Water In
Water Side Economizer
3-Way Valve
2-Way Valve
Condensing Coil
Condensing Coil
Water Out
3-Way Dual Circuit withWater Side Economizer
Evaporator Section
Condensing Section
Water Side Economizer
3-Way ValveWater In
Engineering Guide
C13-Series
43Subject to change without notice. 10.20-TD (0819)
Water-Cooled Piping Arrangements
2-Way Valve
2-Way Valve
Condensing Coil
Condensing Coil
Water Out
2-Way Dual Circuit with Bypassand Water Side Economizer
Evaporator Section
Condensing Section3-Way Valve
N.O. Solenoid Valve
Water In
Water Side Economizer
2-Way Valve
2-Way Valve
Condensing Coil
Condensing Coil
Water Out
2-Way Dual Circuit withWater Side Economizer
Evaporator Section
Condensing Section
Water Side Economizer
3-Way ValveWater In
Engineering Guide
C13-Series
44Subject to change without notice. 10.20-TD (0819)
Illustrated below are possible cabinet configurations. Not all combinations are shown. If a configuration is required that is not shown, please contact the factory to confirm if it is possible.
Basic Model Configurations
Due to product flexibility some options and configurations may not be shown. Contact factory for specials.
Plan Views, Not To Scale
Condensing Section
Evaporator Section
Filter Box
Control Boxes
Condensing Section - Back Inlet & Outlet Evaporator Section - Front Return & Supply
Condensing Section
Condensing Section - Back Inlet & Outlet Evaporator Section - Side Return / Front Supply
Condensing Section
Evaporator Section
Condensing Section - Back Inlet & Outlet Evaporator Section - Front Return / Top Supply
Top Supply
Condensing Section
Evaporator Section
Condensing Section - Back Inlet / Top Discharge Evaporator Section - Front Return & Supply
Top Discharge
Condensing Section
Evaporator Section
Condensing Section - Side Inlet & Back Outlet Evaporator Section - Front Return & Supply
Filter Box
Filter Box
Filter Box
Filter Box
Control Boxes
Control Boxes
Control Boxes
Control Boxes
Engineering Guide
C13-Series
45Subject to change without notice. 10.20-TD (0819)
Basic Model Configurations
Illustrated below are possible cabinet configurations. Not all combinations are shown. If a configuration is required that is not shown, please contact the factory to confirm if it is possible.
Due to product flexibility some options and configurations may not be shown. Contact factory for specials.
Plan Views, Not To Scale
Evaporator Section
Evaporator Section - Front Return & Rear Supply
Condensing Section
Condensing Section - Back Inlet & Rear Discharge
Evaporator Section
Evaporator Section - Side Return & Front Supply
Condensing Section
Condensing Section - Back Inlet / Top Discharge
Top Discharge
Evaporator Section
Evaporator Section - Front Return & Top Supply
Condensing Section - Side Inlet & Rear Discharge
Condensing Section
Control Box
Control Box
Control Box
Control Box
Control Box
Control Box
Filter Box
Filter Box
Filter Box
Engineering Guide
C13-Series
46Subject to change without notice. 10.20-TD (0819)
For specific unit dimensions, please visit our website at www.unitedcoolair.com/c-series-drawings or click here if you are viewing this document electronically�
Tons A B
Air-Cooled
2 - 3 78 444 - 5 86 466 - 8 108-1/2 6310 112 58
Water-Cooled
2 - 3 58 244 - 5 64 246 - 8 75-1/2 3010 84 30
Basic Unit Dimensions
C- SERIES WATER-COOLED ONLY
70 58
35 716
80 34
1-1.5 TONSINGLE CIRCUIT
35 1516
1655 38
47 38
272-5 TONSINGLE CIRCUIT
22
4-8 TONDUAL CIRCUIT
10-15 TONDUAL / TRIPLE CIRCUIT
29
71 34
40 38
31 916
66 516
51 58
34 34
29 916
EVAPORATORSECTION
CONDENSINGSECTION
22 116
45 516
31 38
4-5 TONSINGLE CIRCUIT
34
A
EVAPORATORSECTION
22
2-3 TONSINGLE CIRCUIT
56B
CONDENSINGSECTION
64 70 12
32
25
6-8 TONDUAL CIRCUIT
ABB A
40 45 12
45 516
29
80
AB
54
32
10 TONDUAL CIRCUIT
48 12
93 1316
80 38
10-15 TON EXTENDEDDUAL / TRIPLE CIRCUIT
Engineering Guide
C13-Series
47Subject to change without notice. 10.20-TD (0819)
Cooling (Air Entering Evaporator)
DB (min�/max�) 65 / 110WB (min�/max) 57 / 72
Water-CooledGPM / Ton (min�/max�) 2�5 / 3�5
Leaving Water Temp (min�/max) 60 / 115
Miscellaneous Technical Data
Voltage 208 / 230 460Variation 187 / 253 414 / 504
Condensate Drain Pipes: 3/4” IPS
Water Regulating Valves (a)Unit Sizing
Tons Circuits (Qty) Size2 Single (1) 1/2"3 Single (1) 3/4"4 Single (1) 3/4"5 Single (1) 1"6 Dual (2) 3/4"8 Dual (2) 3/4"10 Dual (2) 1"
Note: (a) Use when entering water temperature
will be < 65° F�
Condensate Pump: (a) Shipped loose�(b) Externally mounted on left side of cabinet�Evaporator Blower VFD: (a) Must include Hot Gas Bypass or Freezestat on each circuit�(b) Pressure Transducer shipped loose for duct mounting�(c) Field installed and programmed�Motors: (a) 2 and 3 HP motors not available in Premium Efficiency in single phase.Electric Heaters: • Finned Tubular type with individual contactor and circuit breaker for each
stage�• When the heater amps exceed 48 for a bank of heaters, SCR (Vernier control)
is required�• Electric heaters only available for use in return air stream�• 300 FPM minimum face velocity�Hot Gas Bypass: (a) Modulating Hot Gas Bypass can only be used on the lead circuit� Can put
standard hot gas bypass on 2nd stage�(b) Must use Marvel Microprocessor or Johnson Control with Modulating HGB�Hot Gas Reheat: (a) Not available for split systems�
Service Clearance - Plan View
Note: (a) Not all combinations may be valid(b) Dependent upon specific application, some additional
refrigerant circuit considerations may be required�
Note: (a) Not all combinations may be valid(b) Dependent upon specific application, some additional refrigerant circuit considerations may be required.
36"
36"
Engineering Guide
C13-Series
48Subject to change without notice. 10.20-TD (0819)
(a) (b) (c) (d) Equivalent Feet Oil Separator Accumulator Quench ValveDischarge Line > 100 X
External Hot Gas Bypass Line > 50 XLiquid Line Net Down and > 50
Suction Line > 100 X X XSuction Line in > 100° F Ambient and > 50 X X
Suction Line Down and > 50 X
Note:(a) It is the customer’s responsibility to verify refrigerant concentration limit compliance with the latest edition of
ANSI / ASHRAE Std� 15�(b) Guidelines for cooling only applications� Contact factory for heat pump systems�(c) External Hot Gas Bypass Line Sizing - use half of the nominal compressor tonnage as a discharge line�(d) All field piping is to follow current industry accepted practices.
SCR - Vernier control on first bank of electric heat. Requires a Marvel microprocessor or Johnson Controller for signal.Unit Interconnect Kits (Shipped Loose) - Used when system will be split in application�Condensate Pump (Shipped Loose) - Requires separate 115 volt power supply� Pump provided with power cord with 3-prong plug�Refrigerant Component Guidelines
Options
Microprocessors
Marvel Mini – Basic MicroprocessorWall Display (shipped loose), Main Control Board, Real Time Clock Board, Air Proving Switch, Compressor High / Low Refrigerant Pressure Safeties and 100’ of CableMarvel Plus – Full Featured MicroprocessorWall Display (shipped loose), Main Control Board, Real Time Clock Board, Air Proving Switch, Dirty Filter Switch, Drain Pan Overflow Switch, Compressor High / Low Refrigerant Pressure Safeties and 100’ of Cable (Must use UCA provided cable, longer lengths available)Sensors – Wall or Duct Mounted TemperatureWall or Duct Mounted HumidityWall or Duct Mounted Temperature / HumidityBMS Serial Communication Board - BACnet™ (MS/TP or Ethernet), ModBus�Duct Mounted Pressure Transformer (If VAV Application is Specified) Not Available with Marvel Mini.
Engineering Guide
C13-Series
49Subject to change without notice. 10.20-TD (0819)
BASIC MODEL DESIGNATION
EXAMPLE: C1
52
G3
34
AS5
H6
A7
158
- X10
1. “C”, “CW”, “H”, “HW”, “CCW”, “E”, “B” or “BC”“C” Air-Cooled Air Conditioner“CW” Water-Cooled Air Conditioner“H” Air-Cooled Heat Pump“HW” Water-Cooled Heat Pump“CCW” Chilled Water Unit“E” Evaporator Section only of the unit (can be a prefix for some of the above)“B” Condensing Section only of the unit“BC” Condenser Section only of the unit
2. “2”, “3”, “4”, “5”, “6”, “8”, “10” Nominal Cooling Capacity in Tons3. “G” Common to all4. “1”, “3”, “4” or “5” Indicates Voltage
“1” 208-230V, 1 PH (277 Volt Handled by Optional Buck-Boost Transformer)“3” 208-230V, 3 PH“4” 460V, 3 PH“5” 575V, 3 PH
5. “AS”, “A” Quantity of Refrigerant Circuits“AS” Indicates 1 Circuit“A” Indicates 2 Circuit
6. “H” Unit Series7. “A” Refrigerant Type
“A” R-410A8. “05”, “10”, “15”, “20”, “25” Indicates kW Rating for Heaters9. “V” Indicates Vertical Stacking Unit10. “X” Special Configuration
Not all combinations of Basic Model Designations are valid. Check with the factory for correct model identification.
Engineering Guide
C13-Series
50Subject to change without notice. 10.20-TD (0819)
NOTES:
��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
Engineering Guide
C13-Series
51Subject to change without notice. 10.20-TD (0819)
NOTES:
��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������
10.20-TD (0819)
Scan to learn more about all of our
products!
491 East Princess Street, York, PA 17403 Phone: 717-843-4311 Fax: 717-854-4462email: [email protected] web: www.unitedcoolair.com
Copyright © by United CoolAir Corporation 2019. All rights reserved. Manufacturer reserves the right to make changes without notice.
Unique Solutions for All-Indoor HVAC Projects
Authorized Distributor: LIMITED WARRANTYUnited CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor (labor not included). Maintenance items such as filters and belts are excluded under this limited warranty�FACTORY TESTEDAll units are functionally run tested before shipment to ensure a trouble-free start-up and unit commissioning� Industry proven components are used throughout to enhance system reliability and peace of mind�
VertiCool ClassicVertical, 3 - 30 Ton
VertiCool Aurora Vertical, 3 - 35 Tons
VariCool® VAV, 9 - 70 Tons
VariCool® EZ-FitVAV, 12 - 90 Tons
Alpha Aire100 – 500 CFM
Portable Cooling and Heating Units
3-30 Tons
C13-Series Horizontal2 - 10 Tons
C-Series Horizontal1 - 15 Tons
Special Configuration Engineered to Order
OmegaAir Horizontal and Vertical100% Outside Air 150 – 3000 CFM