Reference Revision Client Date Author
Trident /FRA - Formal Investments September 2015 LJ
APPENDIX D
Gloucestershire Strategic Flood Risk Assessment – Tile A3, Watercourse Map Gloucester
City Council reference WB/GLOS/DRAWING-019 dated 26th March 2008
Gloucestershire Strategic Flood Risk Assessment – Tile E3, Historic Flooding Gloucester City Council reference WB/GLOS/DRAWING-026 dated 26th March 2008
Reference Revision Client Date Author
Trident /FRA - Formal Investments September 2015 LJ
APPENDIX E
IH124 Drainage Calculation
Simpson Associates Page 1
Unit B10, Elmbridge Court
Business Park
Gloucester GL3 1JZ
Date 29/11/2016 12:04 Designed by luke.johnson
File Checked by
XP Solutions Source Control 2014.1.1
IH 124 Mean Annual Flood
©1982-2014 XP Solutions
Input
Return Period (years) 100 Soil 0.400
Area (ha) 50.000 Urban 0.000
SAAR (mm) 700 Region Number Region 4
Results l/s
QBAR Rural 170.1
QBAR Urban 170.1
Q100 years 437.2
Q1 year 141.2
Q2 years 152.5
Q5 years 209.2
Q10 years 253.5
Q20 years 302.4
Q25 years 319.5
Q30 years 333.3
Q50 years 374.6
Q100 years 437.2
Q200 years 513.7
Q250 years 539.3
Q1000 years 707.7
Reference Revision Client Date Author
Trident /FRA - Formal Investments September 2015 LJ
APPENDIX F
Unit Discharge Method Results: New Extension – Existing Flows
New Extension – Proposed Flows New Teaching Block – Existing Flows
New Teaching Block – Existing Flows less Redundant Sources New Teaching Block – Proposed Flows
C21396 - Beaufort Academy, Gloucester Foul flow rate calculation in accordance With BS EN 12056-2
New Extension - Existing Flows Prepaired LJ Checked LJ Approved RW
Schedule to be read in conjunction with Architects, M&E Engineers drawings SHEET 1.0
REV A
(SCHOOL) k
0.5
0.7
Congested Use eg, toilets, and/or showers open to public 1.0
1.2
System I System II System III System IIII
DU Sum of DU Sum of DU Sum of DU Sum of
L/sec DU L/sec DU L/sec DU L/sec DU
0.5 26.5 0.3 15.9 0.3 15.9 0.3 15.9
0.6 0.0 0.4 0.0 0.4 0.0 0.4 0.0
0.8 0.0 0.5 0.0 1.3 0.0 0.5 0.0
0.8 18.4 0.5 11.5 0.4 9.2 0.5 11.5
0.5 0.0 0.3 0.0 no data - 0.3 0.0
0.2 0.0 0.2 0.0 0.2 0.0 0.2 0.0
0.8 0.0 0.6 0.0 1.3 0.0 0.5 0.0
0.8 1.6 0.6 1.2 1.3 2.6 0.5 1.0
0.8 0.0 0.6 0.0 0.2 0.0 0.5 0.0
0.8 0.0 0.6 0.0 0.6 0.0 0.5 0.0
1.5 0.0 1.2 0.0 1.2 0.0 1.0 0.0
N/A - 1.8 0.0 N/A - N/A -
2.0 0.0 1.8 0.0 1.7 0.0 2.0 0.0
2.0 70.0 1.8 63.0 1.8 63.0 2.0 70.0
2.5 0.0 2.0 0.0 2.0 0.0 2.5 0.0
0.8 0.0 0.9 0.0 no data - 0.6 0.0 1 2 3 4
1.5 0.0 0.9 0.0 no data - 1.0 0.0 System I System II System III System IIII
2.0 4.0 1.2 2.4 no data - 1.3 2.6
120.5 94.0 90.7 101.07.035
1
Waste Water Flowrate (Qww)
7.684 6.787 6.6672
0
0
Date 05/12/16
Typical Frequency Factor (k)
Usage of Applications
Intermittent use eg, dwelling, guesthouse, office
0
0
Frequent use eg, hospital, school, restaurant, hotel
Special Use eg, laboratory
Floor gully DN 50
Floor gully DN 70
WC with 9.0L cistern
Dishwasher (Household)
Washing machine (up to 6kg)
0
0
0
0
35
Floor gully DN 100
Type of development
Typical Frequency Factor (k)
Port Terminal
System Reference (1, 2, 3 or 4) 1
0.7
Wash basin, bidet
Shower without plug
Slab urinal
Number of
Similar
Buildings
3 4
Urinal with flushing valve
53
0
0
23
0
0
Shower with plug
Single urinal with cistern
Bath
Kitchen Sink
0
2
total 115
1 2
Appliance TypeTotal Number of
Applicances
Washing machine (up to 12kg)
WC with 4.0L cistern
WC with 6.0L cistern
WC with 7.5L cistern
C21396 - Beaufort Academy, Gloucester Foul flow rate calculation in accordance With BS EN 12056-2
New Extension - Proposed Flows Prepaired LJ Checked LJ Approved RW
Schedule to be read in conjunction with Architects, M&E Engineers drawings SHEET 1.0
REV A
(SCHOOL) k
0.5
0.7
Congested Use eg, toilets, and/or showers open to public 1.0
1.2
System I System II System III System IIII
DU Sum of DU Sum of DU Sum of DU Sum of
L/sec DU L/sec DU L/sec DU L/sec DU
0.5 1.5 0.3 0.9 0.3 0.9 0.3 0.9
0.6 0.0 0.4 0.0 0.4 0.0 0.4 0.0
0.8 0.0 0.5 0.0 1.3 0.0 0.5 0.0
0.8 0.0 0.5 0.0 0.4 0.0 0.5 0.0
0.5 0.0 0.3 0.0 no data - 0.3 0.0
0.2 0.0 0.2 0.0 0.2 0.0 0.2 0.0
0.8 0.0 0.6 0.0 1.3 0.0 0.5 0.0
0.8 0.8 0.6 0.6 1.3 1.3 0.5 0.5
0.8 0.0 0.6 0.0 0.2 0.0 0.5 0.0
0.8 0.0 0.6 0.0 0.6 0.0 0.5 0.0
1.5 0.0 1.2 0.0 1.2 0.0 1.0 0.0
N/A - 1.8 0.0 N/A - N/A -
2.0 0.0 1.8 0.0 1.7 0.0 2.0 0.0
2.0 4.0 1.8 3.6 1.8 3.6 2.0 4.0
2.5 0.0 2.0 0.0 2.0 0.0 2.5 0.0
0.8 0.0 0.9 0.0 no data - 0.6 0.0 1 2 3 4
1.5 0.0 0.9 0.0 no data - 1.0 0.0 System I System II System III System IIII
2.0 0.0 1.2 0.0 no data - 1.3 0.0
6.3 5.1 5.8 5.4
Date 05/12/16
Type of development Port Terminal Typical Frequency Factor (k)
Typical Frequency Factor (k) 0.7 Usage of Applications
System Reference (1, 2, 3 or 4) 1 Intermittent use eg, dwelling, guesthouse, office
Frequent use eg, hospital, school, restaurant, hotel
Special Use eg, laboratory
Appliance TypeTotal Number of
Applicances
Number of
Similar
Buildings
1 2 3 4
Wash basin, bidet 3
1
Shower without plug 0
Shower with plug 0
Single urinal with cistern 0
Urinal with flushing valve 0
Slab urinal 0
Bath 0
Kitchen Sink 1
Dishwasher (Household) 0
Washing machine (up to 6kg) 0
Washing machine (up to 12kg) 0
WC with 4.0L cistern 0
WC with 6.0L cistern 0
WC with 7.5L cistern 2Waste Water Flowrate (Qww)
WC with 9.0L cistern 0
Floor gully DN 50 0
1.686 1.627total 6
Floor gully DN 70 0
Floor gully DN 100 01.757 1.581
C21396 - Beaufort Academy, Gloucester Foul flow rate calculation in accordance With BS EN 12056-2
New Teaching Block - Existing Flows Prepaired LJ Checked LJ Approved RW
Schedule to be read in conjunction with Architects, M&E Engineers drawings SHEET 1.0
REV A
(SCHOOL) k
0.5
0.7
Congested Use eg, toilets, and/or showers open to public 1.0
1.2
System I System II System III System IIII
DU Sum of DU Sum of DU Sum of DU Sum of
L/sec DU L/sec DU L/sec DU L/sec DU
0.5 1.0 0.3 0.6 0.3 0.6 0.3 0.6
0.6 0.0 0.4 0.0 0.4 0.0 0.4 0.0
0.8 0.0 0.5 0.0 1.3 0.0 0.5 0.0
0.8 0.0 0.5 0.0 0.4 0.0 0.5 0.0
0.5 0.0 0.3 0.0 no data - 0.3 0.0
0.2 0.0 0.2 0.0 0.2 0.0 0.2 0.0
0.8 0.0 0.6 0.0 1.3 0.0 0.5 0.0
0.8 8.8 0.6 6.6 1.3 14.3 0.5 5.5
0.8 0.0 0.6 0.0 0.2 0.0 0.5 0.0
0.8 0.0 0.6 0.0 0.6 0.0 0.5 0.0
1.5 0.0 1.2 0.0 1.2 0.0 1.0 0.0
N/A - 1.8 0.0 N/A - N/A -
2.0 0.0 1.8 0.0 1.7 0.0 2.0 0.0
2.0 6.0 1.8 5.4 1.8 5.4 2.0 6.0
2.5 0.0 2.0 0.0 2.0 0.0 2.5 0.0
0.8 0.0 0.9 0.0 no data - 0.6 0.0 1 2 3 4
1.5 0.0 0.9 0.0 no data - 1.0 0.0 System I System II System III System IIII
2.0 14.0 1.2 8.4 no data - 1.3 9.1
29.8 21.0 20.3 21.23.154 3.223
total 23
Floor gully DN 70 0
Floor gully DN 100 73.821 3.208
WC with 7.5L cistern 3Waste Water Flowrate (Qww)
WC with 9.0L cistern 0
Floor gully DN 50 0
Washing machine (up to 12kg) 0
WC with 4.0L cistern 0
WC with 6.0L cistern 0
Kitchen Sink 11
Dishwasher (Household) 0
Washing machine (up to 6kg) 0
0
Urinal with flushing valve 0
Slab urinal 0
Bath 0
3 4
Wash basin, bidet 2
1
Shower without plug 0
Shower with plug 0
Single urinal with cistern
System Reference (1, 2, 3 or 4) 1 Intermittent use eg, dwelling, guesthouse, office
Frequent use eg, hospital, school, restaurant, hotel
Special Use eg, laboratory
Appliance TypeTotal Number of
Applicances
Number of
Similar
Buildings
1 2
Date 05/12/16
Type of development Port Terminal Typical Frequency Factor (k)
Typical Frequency Factor (k) 0.7 Usage of Applications
C21396 - Beaufort Academy, Gloucester Foul flow rate calculation in accordance With BS EN 12056-2
New Teaching Block - Existing Flows less Redundant Sources Prepaired LJ Checked LJ Approved RW
Schedule to be read in conjunction with Architects, M&E Engineers drawings SHEET 1.0
REV A
(SCHOOL) k
0.5
0.7
Congested Use eg, toilets, and/or showers open to public 1.0
1.2
System I System II System III System IIII
DU Sum of DU Sum of DU Sum of DU Sum of
L/sec DU L/sec DU L/sec DU L/sec DU
0.5 0.5 0.3 0.3 0.3 0.3 0.3 0.3
0.6 0.0 0.4 0.0 0.4 0.0 0.4 0.0
0.8 0.0 0.5 0.0 1.3 0.0 0.5 0.0
0.8 0.0 0.5 0.0 0.4 0.0 0.5 0.0
0.5 0.0 0.3 0.0 no data - 0.3 0.0
0.2 0.0 0.2 0.0 0.2 0.0 0.2 0.0
0.8 0.0 0.6 0.0 1.3 0.0 0.5 0.0
0.8 7.2 0.6 5.4 1.3 11.7 0.5 4.5
0.8 0.0 0.6 0.0 0.2 0.0 0.5 0.0
0.8 0.0 0.6 0.0 0.6 0.0 0.5 0.0
1.5 0.0 1.2 0.0 1.2 0.0 1.0 0.0
N/A - 1.8 0.0 N/A - N/A -
2.0 0.0 1.8 0.0 1.7 0.0 2.0 0.0
2.0 4.0 1.8 3.6 1.8 3.6 2.0 4.0
2.5 0.0 2.0 0.0 2.0 0.0 2.5 0.0
0.8 0.0 0.9 0.0 no data - 0.6 0.0 1 2 3 4
1.5 0.0 0.9 0.0 no data - 1.0 0.0 System I System II System III System IIII
2.0 14.0 1.2 8.4 no data - 1.3 9.1
25.7 17.7 15.6 17.92.765 2.962
total 19
Floor gully DN 70 0
Floor gully DN 100 73.549 2.945
WC with 7.5L cistern 2Waste Water Flowrate (Qww)
WC with 9.0L cistern 0
Floor gully DN 50 0
Washing machine (up to 12kg) 0
WC with 4.0L cistern 0
WC with 6.0L cistern 0
Kitchen Sink 9
Dishwasher (Household) 0
Washing machine (up to 6kg) 0
0
Urinal with flushing valve 0
Slab urinal 0
Bath 0
3 4
Wash basin, bidet 1
1
Shower without plug 0
Shower with plug 0
Single urinal with cistern
System Reference (1, 2, 3 or 4) 1 Intermittent use eg, dwelling, guesthouse, office
Frequent use eg, hospital, school, restaurant, hotel
Special Use eg, laboratory
Appliance TypeTotal Number of
Applicances
Number of
Similar
Buildings
1 2
Date 056/12/16
Type of development Port Terminal Typical Frequency Factor (k)
Typical Frequency Factor (k) 0.7 Usage of Applications
C21396 - Beaufort Academy, Gloucester Foul flow rate calculation in accordance With BS EN 12056-2
New Teaching Block - Proposed Flows Prepaired LJ Checked LJ Approved RW
Schedule to be read in conjunction with Architects, M&E Engineers drawings SHEET 1.0
REV A
(SCHOOL) k
0.5
0.7
Congested Use eg, toilets, and/or showers open to public 1.0
1.2
System I System II System III System IIII
DU Sum of DU Sum of DU Sum of DU Sum of
L/sec DU L/sec DU L/sec DU L/sec DU
0.5 6.5 0.3 3.9 0.3 3.9 0.3 3.9
0.6 0.0 0.4 0.0 0.4 0.0 0.4 0.0
0.8 0.0 0.5 0.0 1.3 0.0 0.5 0.0
0.8 0.0 0.5 0.0 0.4 0.0 0.5 0.0
0.5 0.0 0.3 0.0 no data - 0.3 0.0
0.2 0.0 0.2 0.0 0.2 0.0 0.2 0.0
0.8 0.0 0.6 0.0 1.3 0.0 0.5 0.0
0.8 0.8 0.6 0.6 1.3 1.3 0.5 0.5
0.8 0.0 0.6 0.0 0.2 0.0 0.5 0.0
0.8 0.0 0.6 0.0 0.6 0.0 0.5 0.0
1.5 0.0 1.2 0.0 1.2 0.0 1.0 0.0
N/A - 1.8 0.0 N/A - N/A -
2.0 0.0 1.8 0.0 1.7 0.0 2.0 0.0
2.0 26.0 1.8 23.4 1.8 23.4 2.0 26.0
2.5 0.0 2.0 0.0 2.0 0.0 2.5 0.0
0.8 0.0 0.9 0.0 no data - 0.6 0.0 1 2 3 4
1.5 0.0 0.9 0.0 no data - 1.0 0.0 System I System II System III System IIII
2.0 2.0 1.2 1.2 no data - 1.3 1.3
35.3 29.1 28.6 31.7
Date 05/12/16
Type of development Port Terminal Typical Frequency Factor (k)
Typical Frequency Factor (k) 0.7 Usage of Applications
System Reference (1, 2, 3 or 4) 1 Intermittent use eg, dwelling, guesthouse, office
Frequent use eg, hospital, school, restaurant, hotel
Special Use eg, laboratory
Appliance TypeTotal Number of
Applicances
Number of
Similar
Buildings
1 2 3 4
Wash basin, bidet 13
1
Shower without plug 0
Shower with plug 0
Single urinal with cistern 0
Urinal with flushing valve 0
Slab urinal 0
Bath 0
Kitchen Sink 1
Dishwasher (Household) 0
Washing machine (up to 6kg) 0
Washing machine (up to 12kg) 0
WC with 4.0L cistern 0
WC with 6.0L cistern 0
WC with 7.5L cistern 13Waste Water Flowrate (Qww)
WC with 9.0L cistern 0
Floor gully DN 50 0
3.744 3.941total 28
Floor gully DN 70 0
Floor gully DN 100 14.159 3.776
Reference Revision Client Date Author
Trident /FRA - Formal Investments September 2015 LJ
APPENDIX G
Below Ground Drainage General Arrangement rev P1 ref C21396-0500 by Simpson Associates LLP