NYY LOW VOLTAGE NON ARMOURED CABLE (COPPER CONDUCTOR, PVC INSULATED AND PVC SHEATHED) Type of Cable Rated Voltage Size Range Specification NYY 0.6/1 kV 1 x 1.5 ... 500 m m 2 2 x 1 . 5 ... 150 m m 2 3 x 1.5 ... 300 m m 2 4 x 1.5 ... 300 m m 2 5 x 1.5 ... 50 m m 2 7 x 1.5 ... 61 x 6 m m 2 SPLN 43-1 : 1994 SNI 04-2701-1999 VDE 0271 IEC 60502 Other Specification ate available on reguest Application Identification of Cotes Single-Core Twin-Cores Three-Cores Four-Cores Five-Cores Above Five Cores Indoor and Outdoor induct installation or of laying in the ground where not sustain mechanical damage Black Light-Blue, Black System 1 Green/Yellow, Light-blue, Black System O Light-Blue, Yellow, Black System 1 Green/Yellow, Light-blue Yellow, Black System O Light-blue, Red Yellow, Black Green/Yellow, Light-blue, Red, Yellow, Black Black with white number Other colours are available on request Construction : 1. Annealed Copper Conductor 2. Extruded PVC Insulated 3. Extruded PVC Outer Sheathed SINGLE - CORE NON ARMOURED CABLE Type of Cable Rated Voltage NYY 0.6/1 kV Specification : SPLN 43-1 : SNI 04-270' IEC 60502 (other specifications are available on request) 1994 : 1999 CONSTRUCTION No. Of Core - Size mm 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 Conductor Construction - re/rm re/rm re/rm re/rm re/rm rm rm rm rm rm rm rm rm rm rm rm rm rm No. of Wire - 1/7 1/7 1/7 1 1 7 7 7 19 19 19 37 37 37 61 61 61 61 Wall Thickness Insulation mm 0.8 0.9 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.6 3.0 Sheath mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.2 2.2 1] mm 6.8 7.4 8.0 8.5 9.4 10.8 12.5 13.8 15.8 17.2 19.4 21.0 23.0 25.6 28.6 31.3 35.1 38.9 Approx Net. Weight Kg/Km 69 80 103 130 175 252 365 470 645 832 1115 1360 1680 2070 2685 3294 4210 5240 Standard Length m 100 100 100 100 100 100 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Packing - Cdl Coil Coll Coil Coil Coil Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum CHARACTERISTICS No Of. Core - 1 1 1 1 1 1 1 1 1 Size mm 2 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 Resistance at 20"C Conductor Insulation Ohm/km M.Ohm.km 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 50 50 50 40 30 30 30 20 20 20 20 20 20 20 20 20 20 20 Current Carying Capacity at 30"C In Ground In Air (&/G00 $>/G0© Amper 33 45 58 74 98 129 / 132 169/172 210/214 250 / 255 310/316 375 / 383 425 / 434 480/490 550 / 561 640/653 730/745 855/872 990/1010 Amper 26 35 46 58 80 105/107 140/143 175/179 215/219 270/275 335 / 342 390 / 398 445/454 510/520 620/632 710/724 850/867 1000/1020 Short Circuit Current at I sec. KA 0.17 0.29 0.46 0.70 1.16 1.86 2.91 4.07 5.81 8.14 11.05 13.95 17.44 21.51 27.91 34.88 46.51 58.14 AC Voltage Test KV/5min 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 Note': It site condition are different ratings should be multiplied by rating factors as show In table page 78-83

Upload: others

Post on 05-Dec-2020

6 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: CABLE (COPPER CONDUCTOR, PVC1).pdf · SPLN 43-1 : 1994 SNI 04-2701-1999 VDE 0271 IEC 60502 Other Specification ate available on reguest Application Identification of Cotes Single-Core

NYY LOW VOLTAGE NON ARMOURED CABLE (COPPER CONDUCTOR, PVC INSULATED AND PVC SHEATHED)

T y p e of C a b l e

Ra ted Vo l t age

Size Range

Spec i f i ca t i on

NYY

0.6/1 kV

1 x 1.5 ... 500 m m 2

2 x 1 . 5 ... 150 m m 2

3 x 1.5 ... 300 m m 2

4 x 1.5 ... 300 m m 2

5 x 1.5 ... 50 m m 2

7 x 1.5 ... 61 x 6 m m 2

SPLN 43-1 : 1994

SNI 04 -2701 -1999

VDE 0271

IEC 60502

Other Spec i f i ca t i on a t e ava i l ab l e o n reguest

App l i ca t i on

Ident i f i ca t ion o f Co tes

Single-Core

Twin-Cores

Three-Cores

Four-Cores

Five-Cores

A b o v e Five Cores

Indoor a n d Ou tdoo r

i n d u c t insta l lat ion or o f

lay ing in t h e g r o u n d where

not sustain m e c h a n i c a l

d a m a g e

Black

Light-Blue, Black

System 1

Green/Yel low, L ight-b lue, Black

System O

Light-Blue, Yellow, Black

System 1

Green/Yel low, Light-blue

Yel low, Black

System O

L ight -b lue, Red

Yel low, Black

Green/Yel low, L ight-b lue,

Red, Yel low, Black

Black with whi te n u m b e r

Other colours are available on request

Construction :

1. Annealed Copper Conductor

2. Extruded PVC Insulated

3. Extruded PVC Outer Sheathed

SINGLE - CORE NON ARMOURED CABLE

Type of Cable Rated Voltage

NYY 0.6/1 kV

Specification : SPLN 43-1 : SNI 04-270' IEC 60502

(other specifications are available on request)

1994 : 1999

CONSTRUCTION

No. Of Core

-

Size

m m 2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500

Conductor

Construct ion

-

re/rm re/rm re/rm re/rm re/rm

rm rm rm rm rm rm rm rm rm rm rm rm rm

No. of Wire

-

1/7 1/7 1/7 1 1 7 7 7 19

19 19 37 37 37 61 61 61 61

Wall Thickness

Insulation

m m

0.8 0.9 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4

1.6 1.6 1.8 2.0 2.2 2.4

2.6 3.0

Sheath

m m

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.2 2.2

1] m m

6.8 7.4 8.0 8.5 9.4 10.8 12.5 13.8 15.8 17.2 19.4

21.0 23.0 25.6 28.6 31.3 35.1 38.9

Approx Net. Weight

Kg/Km

69 80 103 130 175 252 365 470 645 832 1115 1360 1680 2070 2685 3294

4210 5240

Standard Length

m

100 100 100 100 100 100

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Packing

-

C d l Coil Coll Coil Coil Coil

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

No Of. Core

-

1 1 1 1 1 1 1 1 1

Size

m m 2

1.5 2.5

4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500

Resistance at 20"C

Conductor Insulation

O h m / k m M.Ohm.km

12.1 7.41 4.61 3.08 1.83 1.15

0.727 0.524 0.387

0.268 0.193 0.153 0.124

0.0991

0.0754 0.0601 0.0470

0.0366

50 50 50 40 30 30 30 20 20 20 20 20 20 20 20 20 20 20

Current Cary ing Capac i ty at 30"C

In Ground In Air

( & / G 0 0 $ > / G 0 ©

Amper

33 45 58 74 98

129 / 132 1 6 9 / 1 7 2 2 1 0 / 2 1 4 250 / 255 3 1 0 / 3 1 6 375 / 383 425 / 434 4 8 0 / 4 9 0 550 / 561 6 4 0 / 6 5 3 7 3 0 / 7 4 5 8 5 5 / 8 7 2

9 9 0 / 1 0 1 0

Amper

26 35 46 58 80

1 0 5 / 1 0 7 1 4 0 / 1 4 3 1 7 5 / 1 7 9 2 1 5 / 2 1 9 2 7 0 / 2 7 5 335 / 342 390 / 398 4 4 5 / 4 5 4

5 1 0 / 5 2 0 6 2 0 / 6 3 2 7 1 0 / 7 2 4 8 5 0 / 8 6 7

1000 /1020

Short Circuit Current at

I sec.

KA

0.17 0.29 0.46 0.70 1.16 1.86 2.91 4.07 5.81 8.14 11.05 13.95 17.44

21.51 27.91 34.88 46.51 58.14

AC Voltage Test

K V / 5 m i n

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': It site condition are different ratings should be multiplied by rating factors as show In table page 78-83

Page 2: CABLE (COPPER CONDUCTOR, PVC1).pdf · SPLN 43-1 : 1994 SNI 04-2701-1999 VDE 0271 IEC 60502 Other Specification ate available on reguest Application Identification of Cotes Single-Core

TWIN - CORES NON ARMOURED CABLED ^CINSUI NDSH1

Type of Cable Rated Voltage

NYY 0,6/1 kV

Specification : SPLN 43-1 : 1994 SNI 04-2701 : 1999 IEC 60502

(other specifications ore available on reauest)

CONSTRUCTION

No. of Core

2 2 2 2 2 2 2 2 2 2 2 2 2

Size

m m 2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150

Conductor

Construction

re/rm re/rm re/rm re/rm re/rm

rm rm rm

rm/sm rm/sm rm/sm rm/sm rm/sm

No. of Wire

-

1/7 1/7 1/7

1 1 7

7 7 19 19 19 37 37

Wall Thickness

Insulation

m m

0.8 0.9 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8

Sheath

m m

1,8 1,8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.2 2,2 2,2 2.6

Approx Overall

Diameter

m m

11.4 12.5 13.8 14.8 16.4 19.4 23.9 30.0 30.0 32.9 37.9 41.1 45,9

Approx Net. Weight

Kg/Km

170 216 280 341 451 669 1033 1310 1748 2232 2982 3565 4538

Standard Length

m

100 100 100 100 100

1000 1000 1000 1000 1000 500 500 500

Packing

-

Coll Coll Coil Coil Coil Coil

Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

N<5£ si~

m m 2

2 1.5 2 2.5 2 4 2 6 2 10 2 16 2 25 2 35 2 50 2 70 2 95 2 120 2 150

Resistance at 20'C

Conductor Insulation

O h m / k m

12.1 7.41 4.61 3.08 1.83 1.15

0.727 0.524 0.387 0.268 0.193 0.153 0.124

M.Ohm.km

50 50 50 40 30 30 30 20 20 20 20 20 20

Current Carylng Capac i ty at 30 'C

In Ground In Air

Short Circuit AC Vol tage 1 sec. T e s t

Amper Amper KA

27 36 47 59 78 102 134 160 187 230 280 320 355

21 29 38 48 66 90 120 150 180 230 275 320 375

0.17 0.29 0.46 0.70 1.16 1.86 2.90 4,06 5,80 8.12 11.02 13.92 17.40

K V / 5 m l n

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition ore different ratings should be multiplied by rating factors as show in table page 78-83

THREE - CORES NON ARMOURED CABLED ■

Type of Cable Rated Voltage

NYY 0.6/1 kV

Specification : SPLN 43-1 : SNI 04-270' IEC 60502

(other specifications are available on request)

1994 : 1999

CONSTRUCTION

No. Of Core

-

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Size

m m 2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Conductor

Construct ion No. of Wire

-

re/rm 1/7 re/rm re/rm re/rm re/rm

rm rm rm sm sm sm sm sm sm sm

1/7 1/7 1 1 7 7 7 19

19 19 37 37 37 61

sm 61

Wall Thickness

Insulation

m m

0.8 0.9 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4

1.6 1.6 1.8 2.0 2,2 2,4

Sheath

m m

1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.2 2.2 2.6 2.6 2.6 3.0

Approx Overal l

Diameter

m m

11.8 13.0 14.5 15.6 17.3 21.3 25.3 27.9 27.9 31.2 35.7 38.3 42.3 46.9 51.7

56.2

Approx Net. Weight

Kg/Km

192

251 330 413 563 882 1302 1670 1945 2613 3467 4217 5234

6478 9102

10020

Standard Length

m

100 100 100 100 100 1000 1000 1000 1000 500 500 500 300 300 250 250

Packing

Coil Coil Coil Coil Coil

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

No Of. Core

-

3

3 3

3 3 3 3 3 3 3 3 3 3 3 3 3

Size

m m 2

1.5 2.5

4 6 10 16 25 35 50 70 95 120 150 185 240 300

Resistance at 20"C

Conductor Insulation

O h m / k m M.Ohm.km

12.1 7.41 4,61 3.08 1,83 1.15

0.727 0.524 0.387

0.268 0.193 0.153 0.124

0.0991

0.0754 0.0601

50 50 50 40 30 30 30 20 20 20 20 20 20 20 20 20

Current Cary lng Capac i ty at 30'C

In Ground

Amper

24 32 42 53 69 91 119 142 166 205 249 285 316 355 415 465

In Air

Amper

19 26 34 43 59 80 107 134

160 205 245 285 325 370 435 500

Short Circuit Current at

I sec.

KA

0.17 0.29 0.46 0.70 1,16 1.86 2.90 4.06 5.80 8.12 11,02 13.92 17.40 21.51 27,91 34.88

AC Voltage Test

K V / 5 m l n

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition are different ratings should be multiplied by rating factors as show in table page 78-83

Page 3: CABLE (COPPER CONDUCTOR, PVC1).pdf · SPLN 43-1 : 1994 SNI 04-2701-1999 VDE 0271 IEC 60502 Other Specification ate available on reguest Application Identification of Cotes Single-Core

FOUR- CORES NON ARMOURED CABLED NSUL iND

Type of Cable Rated Voltage

NYY 0,6/1 kV

Specification : SPLN 43-1 : 1994 SNI 04-2701 : 1999 IEC 60502

(other specifications ore available on reauest)

CONSTRUCTION

No. of Core

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Size

mm2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Conductor

Construction

re/rm re/rm re/rm re/rm re/rm

rm rm rm sm sm sm sm sm sm sm sm

No. of Wire

-

1/7 1/7 1/7 1 1 7 7 7

19 19 19 37 37 37 61 61

Wall Thickness A p p m x

Insulation

mm

0.8 0.9 1.0 1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4

Sheath Diameter

mm mm

1,8 12.5 1,8 14.0 1.8 15.7 1.8 16.9 1.8 18,7 1.8 23.6 2.0 27.6 2.0 30.6 2.0 30.6 2.2 33.8 2,2 39.0 2,2 42.2 2.6 47.1 2.6 51.7 3.0 57.5 3.4 65.9

Approx Net. Weight

Kg/Km

225 299 399 503 697 1117 1625 2096 2388 3205 4225 5264 5526 8033 10633 13343

Standard Length

m

100 100 100 100 1000 1000 1000 1000 1000 500 500 500 300 300 250 200

Coll Coll Coil Coil

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

No Of. Core

-

4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

Size

mm2

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

Resistance at 20'C

Conductor Insulation

Ohm/km

12.1 7.41 4.61 3.08 1.83 1.15

0.727 0.524 0.387 0.268 0.193 0.153 0.124

0.0991 0.0754 0.0601

M.Ohm.km

50 50 50 40 30 30 30 20 20 20 20 20 20 20 20 20

Current Carylng Capacity at 30'C

In Ground In Air

Amper Amper

24 32 42 53 69 91 119 142 166 205 249 285 316 355 415 465

19 26 34 43 59 80 107 134 160 205 245 285 334 370 435 500

Short Citcuit Current at

1 sec.

KA

0.17 0.29 0.46 0.70 1.16 1.86 2.90 4.06 5.80 8.12 11.02 13.92 17.40 21.51 27.91 34.88

AC Voltage Test

KV/5mln

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition are different ratings should be multiplied by rating factors as show in table page 78-83

FIVE - CORES NON ARMOURED CABLED PVC IN

Type of Cable Rated Voltage

NYY 0.6/1 kV

Specification : SPLN 43-1 : SNI 04-270' IEC 60502

(other specifications are available on request)

1994 : 1999

CONSTRUCTION

No. Of Core

5 5 5 5 5 5 5 5 5

Size

mm2

1.5 2.5 4 6 10 16 25 35 50

Conductor

Construction

-

re/rm re/rm re/rm re/rm re/rm rm rm rm

rm/sm

No. of Wire

1/7 1/7 1/7 1/7 1/7

7 7 7 19

Wall Thickness

Insulation

mm

0.8 0.9 1.0 1.0 1.0 1.0 1.2 1.2 1.4

Sheath

1] mm mm

1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0

13.3 15.0 16.9 18.8 20.3 25.9 29.8 33.1 38.1

Approx Net. Weight

Kg/Km

260 346 468 591 828 1331 1918 2491 3427

Standard Length

m

100 100 100 100 1000 1000 1000 1000 500

Packing

Coil Coil Coil Coil

Drum Drum Drum Drum Drum

CHARACTERISTICS

No Of. Core

-

5 5 5 5 5 5 5 5 5

Size

mm2

1.5 2.5 4 6 10 16 25 35 50

Resistance at 20"C

Conductor Insulation

Ohm/km M.Ohm.km

12.1 7.41 4.61 3.08 1.83 1.15

0.727 0.524 0.387

50 50 50 40 30 30 30 20 20

Current Carylng Capacity at 30'C

In Ground In Air

Amper Amper

24 19 32 42 53 69 91 119 142

26 34 43 59 80 107 134

166 160

Short Circuit Current at

I sec.

KA

0.17 0.29 0.46 0.70 1,16 1.86 2.90 4.06 5.80

AC Voltage Test

KV/5mln

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition are different ratings should be mulliplied by rating factors as show in table page 78-83

Page 4: CABLE (COPPER CONDUCTOR, PVC1).pdf · SPLN 43-1 : 1994 SNI 04-2701-1999 VDE 0271 IEC 60502 Other Specification ate available on reguest Application Identification of Cotes Single-Core

NON ARMOURED CONTROL CABLED NSUI iND

Type of Cable Rated Voltage

NYY 0.6/1 kV

Specification : SPLN 43-1 : 1994 SNI 04-2701 : 1999 IEC 60502

(other specifications ore available on reauest)

CONSTRUCTION

No. Of Core

7 8 10 12 14 16 19 21 24 30 40 52 61

Size

mm2

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Conductor

Construction

re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm

No. of Wire

-

1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7

Wall Thickness

Insulation

mm

0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 08

Sheath

mm

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.0

Approx Overall

Diameter

mm

13.7 16.7 16.7 17.6 17.6 18.6 19.6 22.5 22.5 24.5 29.4 30.4 32.4

Approx Net. Weight

Kg/Km

304 348 372 471 485 580 599 681 744 903 1184 1444 1681

Standard Length

m

500 500 500 500 500 500 500 500 500 500 500 500 500

Packing

-

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

No Of. Core

-

7 8 10 12 14 16 19 21 24 30 40 52 61

Size

mm2

1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5

Resistance at 20'C

Conductor Insulation

Ohm/km

12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1 12.1

M.Ohm.km

50 50 50 50 50 50 50 50 50 50 50 50 50

Current Carving Capacity at 30'C

In Ground In Air

Amper Amper

14 10 14 12 10 10 10 9 8 8 8 7 7 6

10 9 8 8 8 8 7 7 7 6 6 5

Short Circuit Current at

1 sec.

KA

0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17

AC Voltage Test

KV/5mln

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition are different ratings should be multiplied by rating factors as show In table page 78-83

NON ARMOURED CONTROL CABLED (COPPER

Type of Cable Rated Voltage

: NYY : 0.6/1 kV

Specification : SPLN 43-1 : SNI 04-270' IEC 60502

(other specifications are available on request)

1994 : 1999

CONSTRUCTION

No. Of Core

-

7 8 10 12 14 16 19 21 24 30 40 52 61

Size

mm 2

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

Conductor

Construction

-

re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm

No. of Wire

1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7

Wall Thickness

Insulation

mm

0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8

Sheath

Approx Overall

Diameter

mm mm

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.0

15.7 18.5 18.6 20.6 20.6 21.6 24.6 26.5 26.5 28.4 34.3 36.3 38.2

Approx Net. Weight

Kg/Km

423 483 522 691 710 768 1001 1038 1097 1295 1758 2179 2512

Standard Length

m

500 500 500 500 500 500 500 500 500 500 500 500 500

Packing

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

No of. Core

-

7 8 10 12 14 16 19 21 24 30 40 52 61

Size

mm2

2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

Resistance at 20"C

Conductor Insulation

Ohm/km M.Ohm.km

7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41 7.41

50 50 50 50 50 50 50 50 50 50 50 50 50

Current Carylng Capacity at 30'C

In Ground

Amper

19 19 16 14 14 14 12 11 11 11 10 0 8

In Air

Amper

16 16 13 12 12 12 12 11 11 11 9 9 8

Short Circuit Current at

I sec.

KA

0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29

AC Voltage Test

KV/5mln

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition are different ratings should be multiplied by rating factors as show In table page 78-B3

Page 5: CABLE (COPPER CONDUCTOR, PVC1).pdf · SPLN 43-1 : 1994 SNI 04-2701-1999 VDE 0271 IEC 60502 Other Specification ate available on reguest Application Identification of Cotes Single-Core

NON ARMOURED CONTROL CABLED NSUI iND

Type of Cable Rated Voltage

NYY 0.6/1 kV

Specification : SPLN 43-1 : 1994 SNI 04-2701 : 1999 IEC 60502

(other specifications ore available on reauest)

CONSTRUCTION

No. Of Core

7 8 10 12 14 16 19 21 24 30 40 52 61

Size

m m 2

4 4 4 4 4 4 4 4 4 4 4 4 4

Conductor

Construction No. of Wire

re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm

-

1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7

Wall Thickness

Insulation

m m

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Sheath

m m

1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.0

Approx Overall

Diameter

m m

17.6 22.5 22.5 22.5 23.5 25.5 26.5 31.4 31.4 33.3 40.2 42.2 44.1

Approx Net. Weight

Kg/Km

522 696 754 864 976 1116 1275 1444 1594 1913 2560 3203 3691

Standard Length

m

500 500 500 500 500 500 500 500 500 500 500 500 500

Packing

-

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

■&S- si~

m m 2

7 4 8 4 10 4 12 4 14 4 16 4 19 4 21 4 24 4 30 4 40 4 52 4 61 4

Resistance at 20 'C

Conductor Insulation

O h m / k m

4.61 4.61 4.61 4.61 4.61 4.61 4.61 4.61 4.61 4.61 4.61 4.61 4.61

Current Carving Capac i ty at 30"C

In Ground In Air

Short Circuit AC Vol tage 1 sec. T e s t

M.Ohm.km Amper Amper KA

50 50 50 50 50 50 50 50 50 50 50 50 50

24 24 20 18 18 18 17 15 15 15 13 13 11

22 22 18 17 17 17 16 14 14 14 12 12 10

0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46 0.46

K V / 5 m l n

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': It site condition are different ratings should be multiplied by rating factors as show In table page 78-83

16

NON ARMOURED CONTROL CABLED (COPPER

Type of Cable Rated Voltage

: NYY : 0.6/1 kV

Specification : SPLN 43-1 : SNI 04-270' IEC 60502

(other specifications are available on request)

1994 : 1999

CONSTRUCTION

No. Of Core

-

7 8 10 12 14 16 19 21 24

30 40 52 61

Size

m m 2

6 6 6 6 6 6 6 6 6 6 6 6 6

Conductor

Construct ion

-

re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm re/rm

No. of Wire

1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7 1/7

Wall Thickness

Insulation

m m

1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0

Sheath

m m

1.8 1.8 1.8 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

Approx Overal l

Diameter

m m

18.6 23.5 23.5 24.5 26.5 27.5 29.5 34.3 34.3 35.3 44.1 46.0 49.0

Approx Net. Weight

Kg/Km

681 874 986 1169 1314 1478 1681 1974 2155 2594 3464

4401 5087

Standard Length

m

500 500 500 500 500 500 500 500 500 500 500 500 500

Packing

Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum Drum

CHARACTERISTICS

No Of. Core

-

7

8 10 12 14 16 19 21 24

30 40 52 61

Size

m m 2

6

6 6

6 6 6 6

6 6 6 6 6 6

Resistance at 20"C

Conductor Insulation

O h m / k m M.Ohm.km

3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08 3.08

40 40 40 40 40 40 40 40 40 40 40 40 40

Current Cary lng Capac i ty at 30'C

In Ground In Air

Amper Amper

31 28 31 26 23 23 23 23 2.0 2.0 2.0 15 15 13

28 24 22 22 22 22 19 19 19 15 15 13

Short Circuit Current at

I sec.

KA

0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69

0.69

AC Voltage Test

K V / 5 m l n

3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

Note': If site condition are different ratings should be multiplied by rating factors as show In table page 78-83

17