cal 2 circuits
TRANSCRIPT
ENGINEERING DATA MANUAL
Condensatori remoti bicircuitoDual circuit remote condensers
1802P – 2002P – 3002P – 4002P – 5002P
(57 - 124 kW)
VERSIONE PRELIMINAREPRELIMINARY VERSION
05CON991X1A - Page 2
UNIFLAIR ITALIA S.p.A.Via dell’Industria, 10
35020 BRUGINE (Padova) ItalyTel. +39 (0)49 9713211Fax. +39 (0)49 5806906
Internet: www.UNIFLAIR.comE-Mail: [email protected]
Release: 1.1 Date: 03 - 04 - 2002
Checked by:
UNIFLAIR persegue una politica di costanteinnovazione tecnologica riservandosi il diritto di variaresenza preavviso le caratteristiche qui riportate.
UNIFLAIR policy is one of continuous technologicalinnovation and the Company therefore reserves theright to amend any data herein without prior notice.
VERSIONE PRELIMINAREPRELIMINARY VERSION
05CON991X1A - Page 3
CAL__________________________________________________________________
Condensatori remoti bicircuito__________________________________________________________________
Versioni disponibiliDescrizione generaleDimensioni e pesiDati tecnici__________________________________________________________________
__________________________________________________________________
Dual circuit remote condensers__________________________________________________________________
Unit codesGeneral decriptionDimensions and weightsTechnical Data__________________________________________________________________
05CON991X1A - Page 4
Schema d’impianto – System Overview
Condensatori remoti con ventilatore assiale a basso numero di giri idonei ad installazione all’aperto,completamente assemblati e collaudati in fabbrica. I condensatori possono essere installati sia in posizioneverticale (flusso aria orizzontale) oppure in posizione orizzontale (flusso aria verticale). Le unità sono dotatedi controllo della pressione di condensazione per ciascuno dei due circuiti mediante regolazione della velocitàdei motoventilatori: in questo caso è data priorità al circuito in cui la pressione è maggiore.
Remote condensers with axial fans for outdoor installation, fully factory assembled and tested. Thecondenser can be installed in a vertical position with horizontal air flow or, with the addition of appropriatebrackets, in a horizontal position with vertical air flow. Units are equipped with condensing pressure controlfor both circuits modulating the fan speed by taking in consideration the higher pressure of the two circuits.
1802P – 2002P – 3002P – 4002P – 5002P
05CON991X1A - Page 5
VERSIONI DISPONIBILI UNIT CODESM
odel
li
1802P2002P3002P4002P5002P
1802P2002P3002P4002P5002P
Mod
els
Con
figur
azio
ni
PO: Controllo di velocità modulante – flussoaria orizzontalePV: Controllo di velocità modulante - flusso ariaverticale
PO: version with modulating fan control – horizontalair flowPV: version with modulating fan control – Vertical AirFlow
Con
figur
atio
ns
DESCRIZIONE GENERALE
Carrozzeria: i condensatori bicircuito CAL sonorealizzati con struttura autoportante in alluminiogoffrato con elevatissima resistenza alla corrosione.
Ventilatori: di tipo assiale bilanciati staticamente edinamicamente su due piani, con pale di disegnoinnovativo realizzate in alluminio pressofuso. Ilmotore elettrico è del tipo a rotore esterno, IP54classe “F”, particolarmente adatto alla regolazione divelocità con sistemi a taglio di fase. La griglia disicurezza a protezione del ventilatore è conformealle vigenti norme di sicurezza.
Batteria condensante: ad ampia superficie frontalee disposta a monte dei ventilatori per un’ottimaledistribuzione dell’aria. E’ realizzata con tubi in rameespansi meccanicamente su alette d’alluminio.
Collegamenti frigoriferi: le connessioni sono di tipoROTALOCK maschio disposte su un lato dell’unitàper un collegamento rapido e sicuro alle tubazioniprovenienti dall’unità motoevaporante.
Impianto elettrico: interruttore sezionatoregenerale con grado di protezione IP44 disposto sullato ventilatori dell’unità, trasduttori di pressione eregolatore di velocità precablati e protetti daun’opportuna carenatura.
GENERAL DESCRIPTION
Case: self supporting and constructed entirely inaluminium for outdoor installation in demandingoperating conditions.
Fan motor: of the axial type, with a new bladedesign, made in aluminium. The external rotor typemotor is designed to allow speed regulation withhigh efficiency and low magnetic noises.
Condensing Coil: with large frontal area,upstream the fans for an efficient air distribution,constructed of copper tubes mechanicallyexpanded into aluminium fins.
Refrigerant connections: Rotalock typeconnections, located on one side of the condenserfor the rapid and secure connection to therefrigerant pipe lines from/to the motoevaporatingunit.
Electrical Panel: main Switch in an IP 44 box onthe fan’s side of the condenser and easilyaccessible from outside; pressure sensors andspeed control device protected by means of analuminium cover on one side of the condenser.
05CON991X1A - Page 6
SPAZIO OPERATIVO
In figura sono indicate le distanze minimeconsigliate per il corretto funzionamento dellamacchina e per l’accessibilità agli organi interni incaso di manutenzione.
WORKING SPACE
The diagram below shows the minimumrecommended distance to be left clear for acorrect unit function and to allow access to the unitfor maintenance.
05CON991X1A - Page 7
DUAL CIRCUIT
DUAL CIRCUITDIMENSIONI E PESII condensatori remoti bicircuito della serie CAL sonosviluppati in tre classi dimensionali.
DIMENSIONS AND WEIGHTSThe CAL dual circuit remote condensers aredeveloped in three dimension groups
Dimensioni e pesi 1802PPV(*)
2002PPV
3002PPV
4002PPV
5002PPV
Dimensions andweights
Altezza (mm) 960 960 960 960 960 Height
Profondità (mm) 1110 1110 1110 1110 1110 Depth
Lunghezza (mm) 2215 2215 3215 3215 4215 Width
Ingombro in pianta (m2) 2,4 2,4 3,6 3,6 4,6 Footprint
Peso (kg) 135 147 182 210 280 Weight
(*) PV = flusso aria verticale(*) PV = vertical air flow
Dimensioni e pesi 1802PPO(*)
2002PPO
3002PPO
4002PPO
5002PPO
Dimensions andweights
Altezza (mm) 1140 1140 1140 1140 1140 Height
Profondità (mm) 540 540 540 540 540 Depth
Lunghezza (mm) 2215 2215 3215 3215 4215 Width
Ingombro in pianta (m2) 1,2 1,2 1,7 1,7 2,3 Footprint
Peso (kg) 135 147 182 210 280 Weight
(*) PO = flusso aria orizzontale(*) PO = horizontal air flow
DATI TECNICI TECHNICAL DATA
Dati tecnici 1802P 2002P 3002P 4002P 5002P Technical data
Potenza termica (kW) (*) 57 63 85 93 124 Heating Capacity
Portata d’aria (m3/h) 20800 20800 31200 29400 39200 Air Volume (m3/h)
Numero di ventilatori 2 2 3 3 4 Number of fans
Livello di pressione sonora (**) 49 49 51 51 52 Sound pressure level (**)
Alimentazione elettrica 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 Power supply
Potenza elettrica assorbita (kW) 1,56 1,56 2,34 2,34 3,12 Electrical power input
Corrente elettrica assorbita (A) 7 7 10,5 10,5 14 Absorbed current
Volume totale interno (dm3) 23,9 29,7 36,1 44,9 60,1 Coil internal volume
Geometria pacco alettato 25 x 21,65 25 x 21,65 25 x 21,65 25 x 21,65 25 x 21,65 Coil geometry
Passo alette (mm) 2,1 2,1 2,1 2,1 2,1 Fin Pitch
Superficie totale di scambio termico(m2)
166 207 249 311 415 Heat exchanger externalsurface
Numero circuiti frigoriferi 2 2 2 2 2 Refrigerant circuits
(*) Dati riferiti ad R407C con un DT = 15° fra aria esterna e Temperatura di condensazione al punto di rugiada(*) Data refers to R407C refrigerant with a DT = 15° between outside air temperature and dew point condensing temperature
(**) In campo libero a 10 m di distanza(**) Free Field at 10 m distance
A
B
1178
A
CAL1802...5002/P
05CON991X1A - Page 12
UNIFLAIR ITALIA S.p.A.Via dell’industria, 1035020 BRUGINE (Padova) - ItalyTel. +39 (0)49 9713211Fax +39 (0)49 5806906
Internet: www.UNIFLAIR.comE-mail: [email protected]
Man
ual c
ode
@ d
igit:
06M
M07
2@00
M01
10