Energy modeling during design can be valuable, but calibrated modeling post-construction tells the truth. Learn the tools available for calibrated modeling, and how they use energy bills, digital control systems data, and metering data to assess the actual functionality of a building. Calibrated modeling completes a valuable feedback loop that can help direct future building decisions and, in some cases, uncover additional savings opportunities in existing structures.TRANSCRIPT
![Page 1: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/1.jpg)
Presented by
Eveline Killian, CEM
Calibrated Modeling: How Well Does
My Building Perform?
![Page 2: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/2.jpg)
Learning Objectives
By the end of this program, participants will be able to:
Understand the value of energy models
Understand the value of calibrated modeling for:
existing building savings potential
adjustments to future building designs
determine impact of interactive effects
Understand the process of calibrating an energy model
![Page 3: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/3.jpg)
Presentation Overview
3
What Is A Calibrated Model?
Building A Model
Common Challenges
Results and Conclusions
Attribution for lightbulb photo: Randy Joy and Co.
![Page 4: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/4.jpg)
Calibrated Modeling Using M&V
4
What Is A Calibrated Model?
Attribution for lightbulb photo: Randy Joy and Co.
![Page 5: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/5.jpg)
Definition of Energy Modeling
An evaluation of the energy use of a building through simulation, accounting for the many energy related components
5
![Page 6: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/6.jpg)
Modeling Components
6
• construction, orientation, location
• HVAC, lighting, controls
• occupancy levels and schedules
• plug loads and internal energy uses (such as refrigeration or process loads)
![Page 7: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/7.jpg)
Uses for Modeling
7
• Energy impacts of alternative designs • LEED credits • Efficiency program incentives
Typical issues
Does not incorporate final design changes Actual usage of differs from original intent
![Page 8: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/8.jpg)
Definition of “Calibrated” Modeling
An energy analysis using an energy model calibrated to utility data and/or end-use metering.
Specifications from the International Performance Measurement and Verification Protocol (IPMVP) Option D: Calibrated Simulation
8
![Page 9: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/9.jpg)
Why Use Calibrated Modeling?
Increases accuracy and credibility of energy savings claims
Conveys an accurate representation of measure interactive effects
Provides feedback on effectiveness of measures
9
![Page 10: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/10.jpg)
Uses for Calibrated Modeling
10
LEED EAc5.1 M&V Credit and Verification
Energy Efficiency Programs and Impact Evaluations
Demand Resource Certification
Retrocommissioning (RCx)/Troubleshooting
Performance Contracting / Energy Service Companies (ESCO)
Building Feedback – is the building performing as expected? Energy Audits/Benchmarking/Assessments
![Page 11: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/11.jpg)
Alternatives to Calibrated Modeling
Retrofit Isolation (IPMVP Option B) Submetering of components and subsystems
Approved for LEED verification
Whole Facility Analysis (IPMVP Option C) Utility data analysis of whole building
No modeling
Not approved for LEED verification
Mathematical formulas and spreadsheets Not calibrated to actual energy consumption
Not approved for LEED verification
11
![Page 12: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/12.jpg)
What Modeling Tools Exist?
12
eQuest
EnergyPlus and DOE2
Software Sponsored by Commercial Firms
![Page 13: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/13.jpg)
Who Performs Such Work
13
Energy Consultants
Energy Modeling Firms
Design Engineering Firms
Evaluation, Measurement and Verification Specialists
![Page 14: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/14.jpg)
Calibrated Modeling Using M&V
14
Building a Calibrated Model
![Page 15: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/15.jpg)
15
I. Obtain and Update or Develop Initial Model
II. Equipment Level Calibration via Metering and Field Validation
III. Utility Data Calibration of As-built Model
IV.Development of Energy Savings
Calibration Modeling Steps
![Page 16: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/16.jpg)
16
I. Obtain and Update or Develop Initial Model
II. Equipment Level Calibration via Metering and Field Validation
III. Utility Data Calibration of As Built Model
IV. Development of Energy Savings
Calibrated Modeling - Step I
![Page 17: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/17.jpg)
Model Development with Architectural Elements
17
Build model with the available information.
![Page 18: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/18.jpg)
18
Example Input Screen
![Page 19: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/19.jpg)
Input available component information:
Equipment types and capacities
Thermal zones
Temperature control schemes
Lighting control schemes
Occupancy schedules
19
To The Best of Our Knowledge…
![Page 20: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/20.jpg)
20
I. Obtain and Update or Develop Initial Model
II. Equipment Level Calibration via Metering and Field Validation
III. Utility Data Calibration of As Built Model
IV. Development of Energy Savings
Calibrated Modeling – Step II
![Page 21: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/21.jpg)
21
Development of M&V Plan
Describe efficiency measures
Identify baseline for each
measure
Describe the analysis approach
• Identify features to field verify
• Describe measure metering
• Determine measure level
sampling
![Page 22: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/22.jpg)
22
Meters and Loggers
![Page 23: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/23.jpg)
23
Proxy Variables
Remote
temperature
sensor
Light
Intensity
Logger
![Page 24: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/24.jpg)
Determining the required quantity of meters
24
Stratified Random Sampling
![Page 25: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/25.jpg)
25
Meter Deployment Sheet
Equipment
Logger
Tag Logger Location Logging Interval
CT size
CT Qty
Begin Date
End Date
Chiller 1 main power
EML-5 basement MEP 5 min 500 3 2-Aug 2-Oct
Chiller 2 main power
EML-6 basement MEP 5 min 600 3 2-Aug 2-Oct
P-1 chilled water pump
EML-7 penthouse MEP 5 min 150 3 2-Aug 2-Oct
P-2 chilled water pump
EML-8 penthouse MEP 5 min 150 3 2-Aug 2-Oct
Outdoor air temp and %RH
TRHE-21
outdoors in a safe place away from mechanical air, shaded from direct sun
5 min na na 2-Aug 2-Oct
![Page 26: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/26.jpg)
Interview building operator
Install meters on key equipment
Obtain trend data
26
Implementation of the M&V Plan
![Page 27: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/27.jpg)
27
Building Management System Data
![Page 28: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/28.jpg)
Implementation of M & V Plan
28
Lighting Zones
Ballasts and Lamp Types
Window Type
Roof Type
Square Foot Spot Checks
HVAC Equipment Types and Capacities
Thermal Zones
HVAC System Setpoints
HVAC Control Configuration
Field Verify:
![Page 29: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/29.jpg)
Modify your model using M&V: Is the expected equipment installed?
Is the equipment still in operation?
Scheduled hours and occupancy
Setpoints and control schemes
Match modeled kW to metered kW
29
Model Adjustments – Round 1
![Page 30: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/30.jpg)
30
Case Study Model Inputs
![Page 31: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/31.jpg)
31
HVAC VFD fan kW
Metered and Modeled Equipment Calibration
![Page 32: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/32.jpg)
32
Case Study Meter Findings
Corridor Lighting
![Page 33: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/33.jpg)
33
Packaged HVAC Schedule
Case Study Meter Findings
![Page 34: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/34.jpg)
34
I. Obtain and Update or Develop Initial Model
II. Equipment Level Calibration via Metering and Field Validation
III.Utility Data Calibration of As Built Model
IV.Development of Energy Savings
Calibrated Modeling – Step III
![Page 35: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/35.jpg)
35
Obtain All Energy Use Information
![Page 36: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/36.jpg)
Input local weather data for utility period
Compare model outputs to energy use
Adjust system/building level parameters: Infiltration
Thermal mass
Occupancy schedules
Control schedules and setpoints
36
Model Adjustments – Round 2
![Page 37: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/37.jpg)
Be Careful That…
The metered component demand and energy values remain true to the meter data
The building’s unmet load hours are appropriate
The adjustments on each immeasurable component remain realistic
37
![Page 38: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/38.jpg)
38
Allowed amount of variation across all of the months (CVRMSE) = 15%
Overall allowed amount of variation in the total annual energy use (NMBE) = 5%
ASHRAE Guideline 14 Section 5.3.2.4 Whole Building Calibrated Simulation
Performance Path
Project Evaluation Tolerances
CVRMSE = Coefficient of Variation Root Mean Square Error NMBE = Net Mean Bias Error
![Page 39: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/39.jpg)
39
Case Study Model Correlation to Energy Consumption
![Page 40: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/40.jpg)
40
Case Study Model Outputs
![Page 41: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/41.jpg)
41
Re-run using local TMY3 data
Weather Normalization
![Page 42: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/42.jpg)
Uses of this Analysis Level
This analysis is sufficient for:
Retrocommissioning/Troubleshooting
Further energy saving opportunities
Energy Audit/Assessment/Benchmarking
Owner information on Building Performance
Performance Contracting
42
![Page 43: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/43.jpg)
43
I. Obtain and Update or Develop Initial Model
II. Equipment Level Calibration via Metering and Field Validation
III. Utility Data Calibration of As Built Model
IV. Development of Energy Savings
Calibration Step IV
![Page 44: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/44.jpg)
Baseline Model
Can be a combination of code and standard practice
Accurately verifies impact of efficiency measures - including interactive effects
44
![Page 45: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/45.jpg)
Create Baseline Model by changing: Equipment efficiencies
Building shell properties
Controls
Do NOT change: Occupancy level
Occupancy schedule
Usage Type
45
Develop Baseline Model
![Page 46: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/46.jpg)
Example of the Impact of Energy Saving Measures over Baseline:
46
Energy Savings Calculations
Modeling Iterations Savings runs MWh MMBtu
As-Built Efficient Building 2,548.5 3,752.2
Iterations toward Baseline Building:
1 As-Built with Code HVAC 2,667.2 3,593.8
2 Iteration 1 with Code Lighting 2,877.3 3,447.5
3 Iteration 2 with Code Windows 2,918.0 3,770.7
4 Iteration 3 with Code Insulation 2,927.5 4,030.1
Baseline Building 2,927.5 4,030.1
Savings 379.0 277.9
![Page 47: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/47.jpg)
Uses of this Analysis Level
Evaluation energy saving realization rates
LEED model comparison metrics (actual vs projected use)
Retrocommissioning implementation
Energy audit
Performance contract: normalized annual savings
47
![Page 48: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/48.jpg)
Calibrated Modeling Using M&V
48
Common Challenges
![Page 49: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/49.jpg)
Common Challenges
49
Typical calibration issues and solutions:
Multiple iterations needed – time consuming
Solutions: Consider overall impact on kWh/MMBtu Consolidate inputs when possible Use global inputs vs. zonal inputs
![Page 50: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/50.jpg)
50
Software model assumptions conflict
Solutions: Avoid over-specifying inputs – allow
program to use defaults Avoid conflicts between global and zonal
inputs
Common Challenges
![Page 51: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/51.jpg)
51
Analysis Outcomes Can Be Counterintuitive
More Usage = More Savings
Building consumption
Equipment savings
Analysis Examples
![Page 52: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/52.jpg)
52
Lower Baseline = Less Savings
Baseline use
Control measure savings
Controls Measures - savings depend strongly on Baseline
Analysis Examples
![Page 53: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/53.jpg)
Calibrated Modeling Using M&V
53
Results and Conclusions
![Page 54: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/54.jpg)
Reasons for Using Calibrated Modeling
54
Determine if the efficient building design is realizing the predicted claimed savings
Analyze opportunities for more
savings
![Page 55: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/55.jpg)
Building Life Cycle Costing (BLCC)
55
Calibrated modeling provides confidence in the value of investing in efficient design, and a measure of the potential risk
Modeling can reveal the reasons for the level of savings impacts over the life of the building
![Page 56: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/56.jpg)
Use of Energy Saving Analysis
This level of analysis is used for:
LEED EAc5.1 M&V Credit and Verification
Energy Efficiency Programs and Impact Evaluations
Identification of energy savings opportunities
Performance Contracting / Energy Service Companies
Building feedback to designers – are the energy measures performing as expected?
Building feedback to owners – how is my building performing compared to my expectations?
56
![Page 57: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/57.jpg)
Learning Objectives
57
Understand the energy models on the market today
Understand the value of calibrated modeling for architects,
engineers and owners for existing building savings potential and
adjustments to future building designs
Understand the impact of interactive effects and other variables
difficult to quantify at the design stage
Understand the process of calibrating an energy model
![Page 58: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/58.jpg)
References and Resources
58
Resource Purpose
Link
Modeling software Select modeling software apps1.eere.energy.gov/buildings/tools_directory/alpha_list.cfm
IPMVP Develop Metering Plan http://www.nrel.gov/docs/fy02osti/31505.pdf
Stratified Random Sampling
Develop Metering Plan implementation and meter selection
http://www.socialresearchmethods.net/kb/sampprob.php
Weather data instructions
Put weather data into eQuest
http://bepan.info/yahoo_site_admin/assets/docs/7_-_Customizing_eQUEST_Weather_Data_by_Jeff_Hirsch.138125735.pdf
ASHRAE Guideline 14 Reference for calibration metrics
http://webstore.ansi.org/RecordDetail.aspx?sku=ASHRAE+Guideline+14-2002
BLCC spreadsheets Impact of savings differentials on lifetime return on investment
http://www.doe2.com/download/lcc/ DOE2 BLCC spreadsheet http://fire.nist.gov/bfrlpubs/build96/art068.html NIST BLCC
LEED modeling reference
Comply with LEED http://www.usgbc.org/ShowFile.aspx?DocumentID=7795
![Page 59: Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian](https://reader033.vdocument.in/reader033/viewer/2022042714/554a3adcb4c90582328b4b79/html5/thumbnails/59.jpg)
Questions ?
59
Eveline Killian
110 Main Street Studio 1B Burlington, VT 05401 802.861.2715