CANATAL

Applying Precision Air Conditioning Systems

Canatal International Inc.

Page 2: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Introduction

Application of Precision Air Conditioning Data Centers Switching Stations Co-Location Facilities

Page 3: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Topics of Discussion

Servers / Switch Gear Temperature & Humidity Control Air Distribution Redundancy Alternating Cold Aisle, Hot Aisle Perforated Tile Capacity Design & Planning Stage Maintenance

Page 4: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Servers / Switch Gear

Smaller, More Powerful

Driven by semi-conductor capacity More transistors on a chip More power consumption per chip More heat generation

Page 5: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

New ASHRAE Document

“Thermal Guidelines for Data Processing Environments” Equipment Environment Specifications Facility Temperature & Humidity Measurement Equipment & Facility Layout Equipment Manufacturers Heat & Airflow

Reporting

Available @www.ashrae.org, Item Number 90431, or D90431

Page 6: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Equipment Environment Specifications

Page 7: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Equipment Environment Specifications

Page 8: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

ASHRAE Class 1 Operating Conditions

Page 9: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

ASHRAE Class 1 Operating Conditions

Increase Equipment Failures

Page 10: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

ASHRAE Class 1 Operating Conditions

Increase HVAC Energy Use

Page 11: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Facility Temperature & Humidity Measurement

Page 12: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Equipment & Facility Layout Recommended Airflow Protocol for Computer

Equipment

Page 13: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Equipment & Facility Layout Recommended Airflow Protocol for Computer

Equipment

Page 14: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Equipment & Facility Layout Recommended Airflow Protocol for Computer

Equipment

Page 15: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

“Thermal Guidelines for Data Processing Environments”

Equipment Manufacturers Heat & Airflow Reporting

Page 16: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Server / Switch Gear

Back View Front View

1U (1.70” H) Server

Page 17: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Server / Switch Gear

Back View Front View

2U (3.50” H) Server

Page 18: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Server / Switch Gear

Back View Front View

4U (6.80” H) Server

Page 19: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Server / Switch Gear

Back View Front View

5U Server – Tower Configuration

Page 20: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Server / Switch Gear

Back View Front View

Page 21: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Heat Density Trends

Source: Uptime Institute

Page 22: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

What is wrong with this picture?

Page 23: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

What is wrong with this picture?

1a 1b2

3

4

5

1a, 1b Cold aisles. 1a has less airflow then 1b - WHY?

2 Hot aisles

3 Top of hot aisle (from right to left – warm to hot)

4 Insufficient cold air and recirculation from hot aisle to cold aisle

5 Mixed return air path

22

Page 24: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

External re-circulation: Top 1/3 portion likely to have higher failure rate

Page 25: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

• Internal re-circulation:• Add blanking panels to eliminate the problem

Page 26: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Positioning of PAC units Parallel or Perpendicular to aisles

Page 27: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Temperature Control

Challenges Hot Spots / Hot Zones / Hot Room Uneven heat load on the floor space Fluctuating heat loads Initial low loads

Page 28: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Temperature Control

Servers/Switches generate sensible heat Utilize Precision Air Conditioning

Systems with high sensible heat ratios Unwanted dehumidification is a waste of

energy and money

Page 29: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Humidity Control

Independently operated units will fight- simultaneously humidify and dehumidify

Wasting energy and money Units should work together as a Team

Page 30: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution

Raised Floor System Generally more flexible Easy to move perforated tiles

Overhead System Ducted or Plenum Make the last length of duct flexible to

enable movement of discharge grilles

Page 31: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution

Deliver Cool Air to the Heat Source

Eliminate Short Circuiting Anytime air returns to the PAC without

passing through heat generating servers, routers, switches etc.

Page 32: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution

Short Circuiting - Common Causes Obstructions to airflow Air Leakage Location of discharge grilles and

perforated tiles

Page 33: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Raised Floor System Electric cable trays,

especially with shallow floor heights

Water damp

Page 34: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – ObstructionsPractice Recommendations for Position

Equipment Racks & Cabinets Power Distribution Unit (PDU) cables should

run under the “Cold Aisles” Cable trays for telecom cablings should locate

under the “ Hot Aisles” Cabinet should be aligned with one edge along

the edge of the cold aisle floor tile Floor tile cuts should be no larger then

necessary to minimize air pressure loss

Page 35: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Practice Recommendations for Position Equipment Racks & Cabinets

Power Distribution Unit (PDU) cables should run under the “Cold Aisles”

Cable trays for telecom cablings should locate under the “ Hot Aisles”

Page 36: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Practice Recommendations for Position Equipment Racks & Cabinets

Power Distribution Unit (PDU) cables should run under the “Cold Aisles”

Cable trays for telecom cablings should locate under the “ Hot Aisles”

Page 37: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Practice Recommendations for Position Equipment Racks & Cabinets

Power Distribution Unit (PDU) cables should run under the “Cold Aisles”

Cable trays for telecom cablings should locate under the “ Hot Aisles”

Page 38: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Practice Recommendations for Position Equipment Racks & Cabinets

Cabinet should be aligned with one edge along the edge of the cold aisle floor tile

Page 39: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Page 40: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Oversized Openings

Practice Recommendations for Position Equipment Racks & Cabinets

Floor tile cuts should be no larger then necessary to minimize air pressure loss

Page 41: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Oversized Openings

Page 42: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution ObstructionsMaximize Floor Height Floor height restricts air flow volume High airflow velocities under the floor

can negate static pressure differentials and entrain air from above to below

May need scoops

Page 43: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution Obstructions

Page 44: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution Obstruction

Overhead System Light fixtures, overhead cable trays Equipment that is taller than the

discharge plenum

Page 45: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Flow Obstruction

Page 46: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Page 47: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Obstructions

Page 48: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Air LeakageRaised Floor System Behind the PAC unit Improper Wire/Cable openings

- remove one tile to run wires Around the perimeter of room

Adversely effects the under floor static pressure hindering the control of airflow

Page 49: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Air Leakage

Page 50: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cleanliness and Proper Vapor Barrier in Subfloor

Page 51: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Page 52: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

What is the right distancefrom PAC to the 1st Rack

Page 53: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

None-Direction Airflow

Pressure = Static Pressure + Velocity Pressure

Page 54: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Perform Better

Page 55: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Air LeakageOverhead System No shut off dampers on redundant units Back draft dampers or motorized

discharge dampers with timers

Page 56: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Raised Floor System Perforated tile quantity and layout Perforated tiles too close to the PAC 3 foot clearance above computer racks Drop ceiling = return air plenum

Page 57: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Page 58: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Page 59: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Overhead System Discharge diffuser too close to the PAC Air discharge from one unit enters the

return air of another

Page 60: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Page 61: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Redundancy

N+1 PAC Unitsi.e. 20 ton load, three 10 ton units

Only one pump on glycol/water loop Multiple feeds to PAC units, but only

one breaker for all rooftop condensers

Page 62: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Redundancy of Airflow

Can air reach each part of the room from more than one unit?

If the answer is no, then N+1 may be negated

Page 63: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Alternating Cold Aisle, Hot Aisle

Computer Equipment Air Flow Pattern In the front, out the back

Racks face each other along one aisle Backs face each other on alternate aisle

Page 64: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Alternating Cold Aisle, Hot Aisle

Page 65: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Alternating Cold Aisle, Hot Aisle

Page 66: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Alternating Cold Aisle, Hot Aisle

Page 67: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Raised Floor System Controlling the Return Air

Drop ceiling = return air plenum

Page 68: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Air Distribution – Airflow Pattern

Page 69: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cost Effective Solution

Page 70: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – One Tile

Perforated Tile Cooling Capacity

Page 71: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – One Tile

Directly dependent on the airflow volume deliver through each tile

Air volume dependent on static pressure under the floor

Page 72: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – One Tile

One 2’ x 2’ Perforated Tile Typical Airflow

600 cfm @ 0.10” w.c.

200 cfm @ 0.02” w.c. Thus, leakage and too many perf. tiles

will reduce static pressure and reduce the ability to control air flow

Page 73: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – One Tile

Maintain high sensible heat ratio AT 72˚F, 50%RH or 68˚F, 50%RH,

excessive condensation occurs after a 17˚F temperature drop

Page 74: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – One Tile

29.921 inHg0 ft

F 45 50 55 60 65 70 75 80 85 90

0.002lbm/lbm

0.004

0.006

0.008

0.01

0.012

0.014

0.016

0.018

0.02

0.022

0.024

0.026

0.028

1

Btu/lbm 45

40

35

30

25

20

15

10

ft^3/lbm 12.6 13.2 13.8

17˚F

Page 75: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – One Tile

Cooling Capability

600 cfm x 17˚F x 1.08 = 11,000 Btuh

Airflow volume critical to cooling capacity

Page 76: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Cooling Capacity – Per Rack

Four foot wide aisles 22,000 Btuh sensible cooling per two

feet of aisle With racks on both sides of the aisle, the

heat load is 3,200 Watts per two feet of racking

Page 77: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Downflow Front Discharge

Page 78: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Design & Planning Stage

Capacity and placement of PAC Room Geometry

Initial & final room layoutInitial & final load

Factors affecting air flow distributionPlenum static pressureObstructions beneath plenum Configuration to prevent air mixing

Page 79: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Design & Planning Stage Mechanical system selection:

Air / water cool Refrigeration/water piping layout Keep it simple

Noise concerns: Local or remote compressor Condenser / condensing

Energy factor Dual / Free Cooling NSB, increase of useable floor space Free cooling system

Risk factor Chilled water /water cooled system

Page 80: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Maintenance

Commissioning of basic systemsRefrigeration, electrical, blower RPM, etc.

Programming of controllerConfigure alarm responses

Train End-user Follow Maintenance Program

Page 81: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc

CANATAL

Maintenance

Common Deficiencies Dirty or blocked filters Undercharged DX systems Un-calibrated or damaged sensors Poor water flow, partially closed valves

or other piping obstructions Chilled water supply temp. (49 - 54˚F)

Page 82: CANATAL Applying Precision Air Conditioning Systems Canatal International Inc