carbohydrazide vs hydrazine: a comparative studynace-jubail.org/meetings/forum/tueaft/swcc.pdf ·...

43
Saline Water Desalination Research Institute www.swcc.com Saline Water Conversion Corporation www.swdri.com 1 CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Study Dr. Mohammed Mahmoodur Rahman Co-Investigators Mr. Saad A Al-Sulami Engr. Fahd Al-Muali Mr. Kither Mohammed Mr. A.J. Shahrani (Jubail Plants)

Upload: vanbao

Post on 12-Mar-2019

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

Saline Water Desalination

Research Institute

www.swcc.comSaline Water Conversion Corporation

www.swdri.com

1

CARBOHYDRAZIDE vs HYDRAZINE:

A Comparative Study

Dr. Mohammed Mahmoodur Rahman

Co-Investigators

Mr. Saad A Al-Sulami

Engr. Fahd Al-Muali

Mr. Kither Mohammed

Mr. A.J. Shahrani (Jubail Plants)

Page 2: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2

CONTENTS

2

Background1

Introduction 2

O3

Experimental4

Results and Discussion5

Conclusions6

Objectives

Page 3: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

3

www.swdri.com

3

BACKGROUND

Saline Water Conversion Corporation (SWCC) produceselectricity and drinking water through its dual-purposeplants. The total power generated from all these plantsexceeds 5000 MW. This enormous power is beinggenerated from 55 high pressure boilers.

Hydrazine has been extensively used in SWCC highpressure boilers as an effective oxygen scavenger for thelast several decades. However, recent studies withhydrazine have indicated some difficulties both oftechnological nature and those connected with its toxicityand explosion hazards.

Page 4: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

4

www.swdri.com

4

Despite the fact that all SWCC power plants are takingnecessary safety measures while handling hydrazine, ithas become a serious desire of the top SWCCmanagement to search for a suitable alternative tohydrazine for all SWCC boilers, that provides excellentoxygen scavenging, non-toxic and safe while handling.

Page 5: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

5

www.swdri.com

5

PURPOSE OF OXYGEN CORROSION CONTROL

FAILURE PREVENTION

Corrosion Minimisation

EQUIPMENT RELIABILITY

Uninterrupted Production

Routine Maintenance

• reduces crisis maintenance

• allows planned preventive maintenance

ECONOMICS

Decrease Overall Maintenance Cost

Decrease Downtime Cost

Page 6: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

6

www.swdri.com

6

OXYGEN CORROSION

CORROSION RATE DOUBLES WITH EVERY

10°C INCREASE IN WATER TEMPERATURE

METAL LOSS

LOCALISED

RAPID FAILURE

PIT FORMATION

Page 7: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

77

WATER

Fe(OH)3

O2

Fe2+OH- O2

ANODE CATHODE

ANODE REACTION

Fe. = Fe++ 2e-

CATHODE REACTION

1/2 O2 + H2O + 2e- = 20H-

ELECTRON FLOW

IRON IS OXIDISED ON THE SURFACE (ANODE) - METAL LOSS

OXYGEN IS REDUCED (CATHODE)

MECHANISM

DETAILED OXYGEN CORROSION OF IRON

Page 8: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

8

www.swdri.com

8

OXYGEN REDUCTION

(CATHODE) (2)

O2 OH-

ELECTRON

FLOW

HYDROGEN

EVOLUTION

(CATHODE) (4)

ACID SOLUTION

WITH REDUCED

OXYGEN CONTENT

H2

Fe(OH)2+ + FeOH++

Fe3O4

H+ + FeOH+

PIT Fe++

Fe2O3

RED OXIDE

PRECIPITATION (8)

CAP

RED OXIDE

BLACK OXIDE

MAGNETITE

BLACK OXIDE

PRECIPITATION

(CATHODE) (7)

OXIDATION (5) AND

HYDROLYSIS (6)

HYDROLYSIS OF

DISSOLVED IRON

LOWERS pH (3)

IRON DISSOLUTION

(ANODE) (1)

e-

Fe

DETAILED OXYGEN CORROSION OF IRON

Page 9: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

9

www.swdri.com

9

OXYGEN CONTROL PROGRAM

MECHANICAL

Deaerators

CHEMICALS

(Oxygen Scavengers)

Page 10: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

10

www.swdri.com

10

INORGANIC (non volatile )

Contribute to the TDS of

the Boiler Water

ORGANIC (volatile )

Do NOT contribute to the

TDS of the Boiler Water

SOLID SODIUM BISULFITE

SODIUM SULFITE

NON-SOLIDS HYDRAZINE

HYDROQUINONE

DEHA

CARBOHYDRAZIDE

ASCORBIC ACID

ISO-ASCORBIC ACID

TYPES OF OXYGEN SCAVENGERS

Page 11: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

11

www.swdri.com

11

REACTION:

2Na2SO3 + O2 2Na2SO4

SCAVENGER DECOMPOSITION:

Na2SO3 + H2O SO2 + 2 NaOH

4 Na2SO3 3 Na2SO4 + Na2S

Na2S + 2H2O NaOH + H2S

Sulphite

Page 12: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

12

www.swdri.com

12

ADVANTAGES:

TRUE RESIDUAL TEST

VERY FAST REACTIVITY

WITH OXYGEN

AVAILABLE IN LIQUID AND

DRY FORMS

INEXPENSIVE

SULFITE : FDA Approved

DISADVANTAGES:

CONTRIBUTES TO TDS

BREAKS DOWN AT 42

Kg/cm² DRUM PRESSURE

Sulphite

Page 13: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

13

www.swdri.com

13

REACTION:

N2H4 + O2 N2 + 2H2O

DECOMPOSITION REACTION:

2N2H4 + HEAT + 2H2O 4NH3 + O2

CONTROL LIMITS:

RESIDUAL N2H4 AT ECONOMIZER INLET

Hydrazine

Page 14: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

14

www.swdri.com

14

ADVANTAGES:

DOESN’T CONTRIBUTE TO TDS

TRUE RESIDUAL TEST

DISADVANTAGES:

POOR REACTIVITY WITH LOW TEMPERATURE

EXPENSIVE COMPARED TO SULFITE

SUSPECT CARCINOGEN

REQUIRES SPECIAL HANDLING / FEED EQUIPMENT

DECOMPOSES TO NH3 WHICH CAN LEAD TO

COPPER CORROSION

Hydrazine

Page 15: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

15

www.swdri.com

15

Hydroquinone

+ 1/2 O2

Hydroquinone Benzoquinone

OH

OH

O

O

O O

REACTION:

C6H6O2 + 1/2O2 H2O + C6H4O2

CONTROL LIMITS:

DISSOLVED OXYGEN TEST

TYROSINE AND LEUCO CRYSTALS VIOLET

TEST

IRON REDUCTION TEST

Page 16: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

16

www.swdri.com

16

DISADVANTAGES:

MORE EXPENSIVE

THAN HYDRAZINE

CAN INCREASE

CATION CONDUCTIVITY

ADVANTAGES:

DOESN’T CONTRIBUTE TO TDS

REACTS FASTER THAN

HYDRAZINE AT LOWER Temp

DOESN’T REQUIRE SPECIAL

HANDLING

GOOD FOR LAY-UP

NOT CARCINOGENIC

Hydroquinone

Page 17: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

17

www.swdri.com

17

Ascorbic acid

CH2OH

CHOH

CH

OH OH

C C

O

C + 1/2 O2

CH2OH

CHOH

CH

O O

C

O

C + H2O

O O

Ascorbic Acid Dehydroascorbate

REACTION:

C6H8O6 + 1/2O2 C6H6O6 + H2O

CONTROL LIMITS:

DISSOLVED O2 TEST

IRON REDUCTION TEST

Page 18: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

18

www.swdri.com

18

Ascorbic acid

ADVANTAGES:

WORKS WELL IN pH

RANGE (7-11)

CONTRIBUTES NO

TDS

OXYGEN

SCAVENGING

DISADVANTAGES:

COST PER Kg is HIGH

IS NOT THERMALLY STABLE

NON-VOLATILE PRODUCT

(ACIDIC)

ATTEMPERATE WITH CAUTION

DECOMPOSITION OF ACIDIC

PRODUCTS MAY END UP IN

CONDENSATE CIRCUIT

Page 19: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

19

www.swdri.com

19

Diethyl hydroxylamine (DEHA)

CH3 CH2

CH 3 CH 2

N - OH + 9 O2 8 CH3 - C + 2N2 + 6H2O

OH

O

Diethyl HydroxylamineAcetic acid

4

2(C2H5)2NOH + O2 2(C2H5)CH3 CHN=O + 2H2O

2(C2H5)CH3CHN=O + 2H2O 2C2H5HNOH + 2CH3CHO

2C2H5HNOH + O2 2CH3CH=NOH + 2H2O

CH3CH=NOH + H2O CH3CHO + NH2OH

4NH2OH + O2 2N2 + 6H2O

2CH3CHO + O2 2CH3COOHAcetaldehyde

DEHA Oxygen Nitrone Water

Nitrone Water Ethylhydroxylamine Acetaldehyde

Ethylhydroxylamine Oxygen Acelaloxime Water

Acetaloxime Water Acetaldehyde

Oxygen Nitrogen Water

Oxygen Acetic acid

Page 20: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

20

www.swdri.com

20

ADVANTAGES:

No solids contribution to the

boiler

Steam volatile magnetite

promoter

Simple to dose and control

Effective oxygen scavenger

DISADVANTAGES:

Cost per kg is high

Is not thermally stable

Non-volatile product (acidic)

Decomposition of acidic products

may end up in condensate circuit

Diethyl hydroxylamine (DEHA)

Page 21: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

21

www.swdri.com

21

ADVANTAGES

No solids contribution to the

boiler

Steam volatile magnetite

promoter

Simple to dose and control

Effective oxygen scavenger

ORGANIC OXYGEN SCAVENGERS

DISADVANTAGES

all organic oxygen

scavengers contribute

to cation conductivity

all organic oxygen

scavengers potentially

decompose into acid

species (organic acids)

Page 22: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

22

Performance Criteria for Oxygen Scavenger

22

The scavenger itself does not react corrosively with materials of

construction and does not lower the pH to corrosive levels (pH < 8).

Its reaction with oxygen is as rapid as possible, particularly in

systems with high flow rates.

The scavenger promotes the formation of passivating metal oxide

films.

Reaction products with oxygen are not corrosive.

Dissolved solids contribution avoided.

The scavenger should not interfere with the action of other treatment

chemicals.

It should not be toxic and much safer and easy to handle.

It should be economical.

Page 23: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2323

Carbohydrazide

NH2 NH - C - NH - NH2 + 2 O2 CO2 + 2N2 + 3H2O

O

-

Indirect reaction

l (N2H3)2CO + H2O 2 N2H4 + CO2

l 2 N2H4 + 2 O2 4 H2O + 2 N2

Decomposition

l (N2H3)2CO + H2O 2 NH3 + N2 + H2 + CO2

l 1 ppm Carbohydrazide liberates

l 15 ppb NH3

l 14 ppb CO2

> 135°C

> 200°C

Page 24: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2424

Carbohydrazide

An oxygen scavenger that contributes no

inorganic solids to the feed water or boiler

water

An oxygen scavenger that DOES NOT

decomposes in organic acid species

Contributes to passivation

Controls oxygen corrosion

Page 25: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2525

Carbohydrazide

The byproducts and the percentage

carbon content of oxygen scavengers

in the table clearly illustrates that the

byproducts of carbohydrazide contain

no harmful organic compounds or

acids [CEGB Report V 14, 1991].

On the basis of above data and its

wide application in different power

houses internationally as well as

locally Carbohydrazide was selected

for the evaluation.

Chemical/Formula% C

(wt.)Reaction and/ Breakdown Products

Hydrazine

N2H4

0

Nitrogen,

Water,

Ammonia

Cabohydrazide

(N2H3)2CO

13.3

Hydrazine,

Nitrogen,

Water,

Ammonia

Carbon Dioxide

Erythrobic acid

C6H8O6 40.9

Dihydroascorbic acid

Salts of Lactic and Glycolic

Carbon Dioxide

Diethylhydroxylamine

(CH3CH2)2NOH

53.9

Acetaldehyde

Acetic acid

Acetate ion

Dialkylamines

Ammonia

Nitrate

Nitrite

Methylethylketoxime

(CH3)(CH3CH2)C=NOH

55.2

Methylethylketone

Hydroxylamine

Nitrogen

Nitrous Oxide

Ammonia

Carbon Dioxide

Hydroquinone

C6H4(OH)2

65.5

Benzoquinone

Light Alcohols

Ketones

Low Molecular Weight Species

Carbon Dioxide

Page 26: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2626

To evaluate the suitability and efficiency of carbohydrazide

as an alternative oxygen scavenger to hydrazine in the

high-pressure boiler.

To determine the consequences of degradation by-

products on boiler system.

To evaluate the ability of the alternative oxygen scavenger

in forming and maintaining an oxide film in the boiler.

To evaluate whether the alternative oxygen scavenger is

generating any negative effects on the efficiency of the

boiler.

OBJECTIVES

Page 27: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2727

Two boilers # 81 and # 82 of Phase–II at Al-Jubail

Plants, each generating 130 MW/h, were selected

for the trial tests in consultation with chemical

manufacturing company.

Boiler # 81 was run with carbohydrazide and

boiler # 82 with hydrazine. Both these boilers are

pressurized box type water tube boilers. The

maximum continuous rating (MCR) of steam is

710 tons/h.

EXPERIMENTAL

Page 28: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

28

Test Conditions (Boiler chemistry)

28

Parameters/

SamplesCondensate

Daerator

out

Feed Water/

Economizer

inlet

Boiler Blow

Down (Drum)

Saturated

Steam

pH 8.5 – 9.2 ------- 8.7 – 9.2 9 – 9.8 8.7 – 9.2

Sp. Conductivity (μS/cm) <3 ------- <3 <50 <3

Cat. Conductivity (μS/cm) <0.5 ------- ------- ------- <0.5

Copper (ppb) <5 -------- <5 <20 ----

Ammonia (ppm) <0.3 ------- <0.3 ------- <0.3

Iron (ppb) <10 ------ <10 <50 ------

Dissolved O2 (ppb) <20 <10 Nil or <7 ------ ------

Hydrazine (ppb) ------ ------- 10 - 20 ------ ------

Silica (ppb) <20 ------- <20 1000 <20

Sodium (ppb) <10 ------- <10 ------ <10

Chloride (ppm) <0.01 ------- <0.05 <0.5 <0.05

Phosphate (ppm) ------ ------- ------- 5 - 10 ------

P-Alkalinity(ppm) ------ ------- ------- <5 ------

M-Alkalinity(ppm) ------ ------- ------- <15 ------

Page 29: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

2929

S. No. Equipment Capacity

Water/Steam

Pres.

(Bar)

Temp.0C

Flow

M3/H

1 Condensate ---------- 9.5-9.8 99-121 ----

2 Deaerator 86 M3 5 156 700

3 25 M3 ---- --- ----

4 Boiler feed Pump 900 M3 103 ---- 697

5 HP Heater 1 ---- 103 160-195 697

6 HP Heater 2 ----- 103 195-233 697

7 Economizer ----- 102 230-295 700

8 Boiler 12 1M3 104 310 700

9 Super heater 39 M3 95 515 700

10Hydrazine tank

pump560 L 150 ---- 50L/H

11Phosphate tank

pump560 L 150 -------- 50L/H

Test Conditions (Operations)

Page 30: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

30

TYPICAL BOILER SHOWING WATER AND STEAM FLOW

30

Page 31: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

31

BOILER WATER CYCLE AND SAMPLING POINTS

31

Boiler water (boiler drum)

Feed water

Brine heater condensate

Make-up water

Saturated steam

Page 32: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

32

RESULTS AND DISCUSSIONS

32

Optimization of Carbohydrazide

Chemical feed rates for hydrazine were established to maintain hydrazine residual

around 20 ppb in feed water.

At the start with the recommended dosage of 1.5 ppm of carbohydrazide, determination

of carbohydrazide in feed water was observed to give inconsistent values. The

inconsistency observed was attributed to the high temperature of the feed water (235oC)

because at temperatures above 150oC carbohydrazide hydrolyzes to hydrazine.

0

5

10

15

20

25

30

0

50

100

150

200

250

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

FW

Hyd

razin

e (

pp

b)

FW

CH

DZ

(p

pb

)

Date

CHDZ Limit CHDZ Hydrazine Limit Hydrazine

Page 33: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

33

Optimization of Carbohydrazide

33

0

0.2

0.4

0.6

0.8

1

1.2

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05FW

Am

monia

(ppm

)DateCHDZ Hydrazine Limit

0

0.2

0.4

0.6

0.8

1

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05SS

Am

monia

(ppm

)

DateCHDZ Hydrazine Limit

0

0.2

0.4

0.6

0.8

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

BH

C A

mm

onia

(ppm

)

DateCHDZ Hydrazine Limit

At the start with the

recommended dosage

of 1.5 ppm of

carbohydrazide, high

values for ammonia

and copper were

recorded.

The dose rate was

later reduced from 1.5

to 0.7 ppm till the

parameters (copper &

ammonia) were

maintained within the

normal range and

stabilized.

Page 34: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

34

Boiler Chemistry

34

8.2

8.7

9.2

9.7

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

FW

pH

DateCarbohydrazide Hydrazine Limit

8.2

10.2

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

BB

D p

H

DateCarbohydrazide Hydrazine Limit

8.28.48.68.8

99.29.4

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

BH

C p

H

DateCarbohydrazide Hydrazine Limit

8.28.48.68.8

99.29.4

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

SS

pH

DateCarbohydrazide Hydrazine Limit

8.28.48.68.8

99.29.4

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

DA

O p

H

DateCarbohydrazide Hydrazine Limit

pH Control

pH values for both

hydrazine and

Carbohydrazide

were found to be

maintained in the

range of 8.6 and 9.0

for Brine heater

condensate (BHC),

Feed water (FW),

Saturated steam

(SS) and Deaerator

outlet (DAO)

whereas for Boiler

blow down (BBD) it

was in the range of

9.0 and 10.

Page 35: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

3535

0

2

4

6

8

10

12

14

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05D

AO

Dis

ol. O

2Date

CHDZ Hydrazine

0

50

100

150

200

250

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

BH

C D

isol. O

2

DateCHDZ Hydrazine

Boiler Chemistry

Dissolved Oxygen

Average dissolved oxygen

with both hydrazine and

Carbohydrazide in the DAO

was found to be ≤ 7 ppb,

whereas in the BHC it was

found to be high at an

average of 87 ppb. This

was attributed to the air

leakage.

Page 36: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

3636

Boiler Chemistry

0

5

10

15

20

25

30

35

40

5/17/055/31/056/14/056/28/057/12/057/26/05 8/9/05 8/23/05 9/6/05 9/20/0510/4/05

FW

Copper

(ppb)

DateCHDZ

0

5

10

15

20

25

30

35

40

45

50

5/17/055/31/056/14/056/28/057/12/057/26/05 8/9/05 8/23/05 9/6/05 9/20/0510/4/05

BB

D C

opper

(ppb)

DateCHDZ

Control of Copper levels

With hydrazine, the average

concentrations for copper in feed

water was found to be 3 ppb and

in boiler water it was found to be

6 ppb, whereas with

carbohydrazide dosing, the

average concentrations for

copper in feed water was found

to be 3 ppb and in boiler water it

was found to be 4 ppb.

This showed that copper levels in

feed water were maintained at

the baseline value whereas a

33% reduction was found in the

boiler water (drum).

Page 37: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

3737

0

5

10

15

20

25

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

FW

Iro

n (

ppb)

DateCHDZ

0

10

20

30

40

50

60

5/17/05 5/31/05 6/14/05 6/28/05 7/12/05 7/26/05 8/9/05 8/23/05 9/6/05 9/20/05 10/4/05

BB

D Iro

n (

ppb)

DateCHDZ

Control of Iron levels

With hydrazine, the average

concentrations for iron in feed

water was found to be 8 ppb

and in boiler water it was found

to be 19 ppb whereas with

carbohydrazide dosing, the

average concentrations for iron

in feed water was found to be 2

ppb and in boiler water it was

found to be 17 ppb.

This showed a reduction of iron

levels in the feed water by 75%

and in the boiler water (drum) a

reduction of 10%.

Boiler Chemistry

Page 38: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

38

Corrosion studies

38

Coupons

in Boiler

Drum

Before

test

Coupons

in Boiler

Drum

after test

Coupons in

HP heaters

Before test

Coupons

in HP

heaters

after test

The exposed coupons were

visually examined. A uniform

and non-porous oxide film

was found to be adhered on

the coupons indicating the

protective nature of the

films. The corrosion rate of

0.044 mpy determined for

carbon steel coupons fixed

in drum at water side with

hydrazine dosing indicates

extremely low corrosion.

Page 39: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

3939

BackFront

BackFront

Wate

r sid

eS

tea

m s

ide

Carbon steel coupons after exposure in water drum under Carbohydrazide dosing boiler

#81

BackFront

Cupronickel coupons after exposure in HP heater under Carbohydrazide dosing boiler

#81

The corrosion rates

determined with

carbohydrazide dosing for

carbon steel coupons fixed

in drum at water side and

steam side were 0.384 mpy

and 0.444 mpy respectively,

whereas that determined for

carbon steel and 70/30

cupronickel in HP heaters

were 0.251 mpy and 0.128

mpy respectively. The

corrosion rates of the

material appear to be low

and effect of corrosion

appears to be insignificant.

Corrosion studies

Page 40: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

40

CONCLUSIONS

40

The results indicated the suitability and efficiency of

Carbohydrazide oxygen scavenger as an alternative to

hydrazine in SWCC high pressure boiler provided the

concentration of residual hydrazine (decomposition by-

product of Carbohydrazide) is maintained at levels

between 30-40 ppb in the feed water.

No harmful degradation by-products were found.

Carbohydrazide was found to be a good oxygen scavenger

at a concentration dose rate of 0.7ppm.

Optimized dose rate resulted in maintaining the boiler

chemistry within design limits.

Page 41: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

4141

CONCLUSIONS

Iron levels measured at economizer inlet (boiler

feed water) were reduced by 75% whereas for

copper it was found to be maintained at the

baseline value. In the boiler water (drum) the

reduction in Fe and Cu were 10% and 33%,

respectively.

The corrosion rates indicated very little or

negligible corrosion due to either hydrazine or

Carbohydrazide. However hydrazine showed much

lower rates compared to Carbohydrazide.

Page 42: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

4242

The authors gratefully acknowledge:

The cooperation of Jubail Plant personnel.

Acknowledgment

Page 43: CARBOHYDRAZIDE vs HYDRAZINE: A Comparative Studynace-jubail.org/Meetings/Forum/TueAft/SWCC.pdf · 26 26 To evaluate the suitability and efficiency of carbohydrazide as an alternative

Saline Water Desalination

Research Institute

www.swcc.comSaline Water Conversion Corporation

www.swdri.com

43