Product Data
24ACC6Performancet16 Air Conditionerwith Puron Refrigerant1---1/2 to 5 Tons
the environmentally sound refrigerant
Carriers Air Conditioners with Puronr refrigerant provide acollection of features unmatched by any other family ofequipment. The 24ACC has been designed utilizing CarriersPuron refrigerant. The environmentally sound refrigerant allowsyou to make a responsible decision in the protection of the earthsozone layer.
This product has been designed and manufactured to meetEnergy Starr criteria for energy efficiency when matched withappropriate coil components. Refer to the combination ratings inthe Product Data for system combinations that meet Energy Starrguidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
INDUSTRY LEADINGFEATURES / BENEFITSEfficiency
S 14 -- 16.5 SEER / 11.5-- 13.5 EER
S Microtube Technologytrefrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 72 dBA
S Compressor sound blanket standard
Comfort
S System supports Edger Thermidistatt or standardthermostat controls
Reliability
S Puronr refrigerant -- environmentally sound, wontdeplete the ozone layer and low lifetime servce cost.
S Scroll compressor
S Internal pressure relief valve
S Internal thermal overload
S Filter drier
S High and low pressure switches
S Balanced refrigeration system for maximum reliability
Durability
WeatherArmor Ultratprotection package:
S Solid, durable sheet metal construction
S Louvered coil guard
S Baked--on, complete outer coverage, powder paint
Applications
S Long--line -- up to 250 feet (76.20 m) total equivalentlength, up to 200 feet (60.96 m) condenser aboveevaporator, or up to 80 ft. (24.38 m) evaporator abovecondenser (See Longline Guide for more information.)
S Low ambient (down to --20_F/--28.9_C)) withaccessory kit
-
7/26/2019 Carrier 24ACC6
2/202
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8 9 10 1 1 12 13
N N A A A/ N N N N A/ N A/ N A/ N N N
2 4 A C C 6 3 6 A 0 0 3 0
ProductSeries
ProductFamily
Tier Major
Se ri e s SEER
Cooli ngCapaci t y
Gri lleVari at i ons
Open Open Volta ge Ser ies
2 4=AC A=RE S AC C=Per for ma nce C=Puron 6=16 SEE R A = Sta ndar d 0 =N ot
De fi ne d0 =N ot
De fi ne d3=208/230 ---1
0 =Original
Se ri e s
the environmentally sound refrigerant
This produc t has be e n de s igne d and manufac t ure d t ome e t Ene rgy St ar c rit e ria for e ne rgy e ffic ie nc y whe nmat c he d wit h appropriat e c oil c ompone nt s . Howe ve r,p r o pe r r e f r i ge r a nt c h a r ge a n d p r o p e r a i r f l o w a r e c r i t i c alt o ac hie ve rat e d c apac it y and e ffic ie nc y. I ns t allat ion oft h i s p r o d u c t s h o u l d f o l l o w a l l m a n u f ac t u r i ng r e f r i ge r a n tc h a r g i n g a n d a i r f l o w i n s t r u c t i o n s . Failure to confirmproper charge and air flow may reduce energyefficiency and shorten equipment life.
Use of the AHRI CertifiedTM Mark indicates amanufacturersparticipation in theprogram For verificationof certification for individualproducts, go towww.ahridirectory.org.
STANDARD FEATURESFeature 18 24 30 36 42 48 60
Pur on Refr iger ant X X X X X X X
Maximum SEE R * 16. 0 1 6.0 16 .5 16.5 16 .0 16.0 1 6.0
Scrol l Compre ssor X X X X X X X
F iel d Insta lle d Filter Dr ier X X X X X X X
Fron t Se ating Ser vice Val ves X X X X X X X
Inter na l Pr essur e Re lie f Val ve X X X X X X X
Inter na l Ther mal Over load X X X X X X X
L ong Line capa bil it y X X X X X X X
L ow Ambient capability with K it X X X X X X X
High Pr essure Swit ch X X X X X X X
L ow Pre ssur e Switch X X X X X X X
C ompr essor Sound Bla nke t X X X X X X X
L ouver ed Coil Gua rd X X X X X X X
* W i th a p p r ov e d c o m bi n a ti o n s
X = S t a n d a r d
PHYSICAL DATAUNIT SIZE --- VOLTAGE,
SERIES 18--- 30 24--- 30 30--- 30 36--- 30 42--- 30 48--- 30 60--- 30
Oper ating We ight lb ( kg) 13 6 ( 61. 7) 1 63 ( 73 .9) 16 7 ( 75. 7) 1 80 ( 81 .6) 234 (1 06. 1) 24 8 ( 112 .5) 337 (1 52. 9)
Shipping Weight lb (kg) 16 3 ( 73. 9) 1 98 ( 89 .8) 20 4 ( 92. 5) 2 19 ( 99 .3) 281 (1 27. 5) 29 1 ( 132 .0) 372 (1 88. 7)
Compressor Type Scroll
REFRIGERANT Puron (R ---410 A)
C ontr ol TX V ( Pur on Ha rd Shutof f)
C har ge l b (kg) 4.6 0 ( 2.0 9) 6 .00 (2 .72) 6.8 1 ( 3.0 9) 7 .00 (3 .18) 8.6 2 ( 3.91 ) 10 .50 (4 .76) 14.5 0 ( 6.5 8)
COND FAN Prope lle r Type , Di re ct Dri ve
Ai r Di scharge Ve rt i cal
Ai r Qt y ( CFM) 1 8 8 1 2 6 1 4 2 6 1 4 3 2 2 3 3 8 1 0 4 0 4 6 4 0 4 6Motor HP 1 / 12 1/ 10 1 / 10 1/ 12 1 / 5 1/ 4 1 / 4
Motor RPM 11 00 800 8 00 800 80 0 8 00 80 0
COND COIL
Face Ar ea ( Sq ft) 11 .50 1 5.1 0 17 .20 1 7.6 0 25. 15 2 0.10 30. 15
Fins per In. 2 5 25 2 5 25 2 5 20 2 0
Rows 1 1 1 1 1 2 2
C ir cuits 3 4 4 4 6 7 8
VALVE CONNECT. (In. ID)
Va por 3/ 4 3/ 4 3/ 4 7/ 8 7 / 8 7/ 8 7 / 8
L iquid 3/ 8 3/ 8 3/ 8 3/ 8 3 / 8 3/ 8 3 / 8
REFRIGERANT TUBES (In. OD)
Rate d Vapor * 3/ 4 7 / 8 1 1/ 8
Max Liquid Line 3/ 8* U n i t s a r e r a t e d w i th 2 5 f t ( 7 . 6 m ) o f l i n e s et l e n g t h . S e e V a p o r L i n e S i z in g a n d C o o l in g C a p a c i ty L o s s t a b l e w h e n u s i n g o t h e r s i z e s a n d l e n g th s o f l i n es e t.
Note: S e e u n i t I n s t a l l a ti o n I n s t r u ct i o n f o r p r o p er i n st a l l a ti o n .
{ Se eLiquid Line Sizing For Cooling Only Systems with Puron Refrigerant t able s.
24ACC6
-
7/26/2019 Carrier 24ACC6
3/203
REFRIGERANT PIPING LENGTH LIMITATIONSLiquid Line Sizingand Maximum Total Equivalent Lengths{ for Cooling Only Systems with Puron Refrigerant:
The maximum allowable length of a residential split system depends on the liquid line diameter and vertical separation between indoor andoutdoor units.
See Table below for liquid line sizing and maximum lengths :
Maximum Total Equivalent Length
Outdoor Unit BELOW Indoor Unit
Size Liquid Line
Connection
LiquidLine
Diam.
w/ TXV
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit BELOW IndoorVertical Separation ft ( m)
0---5(0---1.5)
6--- 10(1.8---3.0)
11---20(3.4---6.1)
21---30(6.4---9.1)
31--- 40(9.4---12.2)
41--- 50(12.5 --- 15.2)
51--- 60(15.5 --- 18.3)
61---70(18.6---21.3)
71---8 0(21.6---24.4)
18000 AC wi t h
Puron3 / 8
1/ 4 15 0 150 12 5 100 100 75 --- --- --- --- --- ---
5/ 16 250 * 250 * 250 * 250 * 2 50* 2 50* 250* 225 * 1 50
3/ 8 250 * 250 * 250 * 250 * 2 50* 2 50* 250* 250 * 25 0*
24000 AC wi t h
Puron3 / 8
1/ 4 75 75 75 50 50 --- --- --- --- --- --- --- ---
5/ 16 250 * 250 * 250 * 250 * 2 50* 2 25* 175 12 5 1 00
3/ 8 250 * 250 * 250 * 250 * 2 50* 2 50* 250* 250 * 25 0*
30000 AC wi t h
Puron3 / 8
1/ 4 30 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- ---
5/ 16 17 5 225 * 20 0 175 125 1 00 75 --- --- --- ---
3/ 8 250 * 250 * 250 * 250 * 2 50* 2 50* 250* 250 * 25 0*
36000 AC wi t h
Puron3 / 8
5/ 16 17 5 150 15 0 100 100 1 00 75 --- --- --- ---
3/ / 8 250 * 250 * 250 * 250 * 2 50* 2 50* 250* 250 * 25 0*
42000 AC wi t h
Puron3 / 8
5/ 16 12 5 100 10 0 75 75 50 --- --- --- --- --- ---
3/ 8 250 * 250 * 250 * 250 * 2 50* 2 50* 250* 250 * 1 50
48000 AC wi t h
Puron3/ 8 3/ 8 250 * 250 * 250 * 250 * 2 50* 2 50* 230 16 0 --- ---
60000 AC wi t h
Puron3/ 8 3/ 8 250 * 250 * 250 * 225 * 190 1 50 110 --- --- --- ---
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = outside acceptable range
Maximum Total Equivalent Length
Outdoor Unit ABOVE Indoor Unit
Size Liquid Line
Connection
LiquidLine
Diam.w/ TXV
AC with Puron Refrigerant Maximum Total Equivalent Length{: Outdoor unit ABOVE IndoorVertical Separation ft ( m)
25(7.6)
26--- 50(7.9---15.2)
51---75(15.5---22.9)
76---100(23.2---30.5)
101 --- 125(30.8 --- 38.1)
126 --- 150(38.4---45.7)
151---175(46.0---53.3)
176---200(53.6 --- 61.0)
18000 AC wi t h
Puron3 / 8
1/ 4 1 75 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*5/ 16 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
24000 AC wi t h
Puron3 / 8
1/ 4 1 00 125 17 5 2 00 2 25* 250 * 25 0* 25 0*
5/ 16 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
30000 AC wi t h
Puron3 / 8
1/ 4 3 0 --- --- --- --- --- --- --- --- --- --- --- --- --- ---
5/ 16 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
36000 AC wi t h
Puron3 / 8
5/ 16 22 5* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
42000 AC wi t h
Puron3 / 8
5/ 16 1 75 200 250 * 25 0* 2 50* 250 * 25 0* 25 0*
3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
48000 AC wi t h
Puron
3/ 8 3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
60000 AC wi t h
Puron3/ 8 3/ 8 25 0* 2 50* 250 * 25 0* 2 50* 250 * 25 0* 25 0*
* Maximum actual length not to exceed 200 ft (61 m)
{ Total equivalent length accounts for losses due to elbows or fitting. See the Long Line Guideline for details.
--- --- = outside acceptable range
-
7/26/2019 Carrier 24ACC6
4/204
REFRIGERANT CHARGE ADJUSTMENTS
Liquid Line Size Puron Charge oz/ft
3 / 8 0 .6 0
( F a c t o r y c h a r g e f o r l i n e s e t = 9 o z )
5/ 16 0.4 0
1/ 4 0.2 7
Units are factory charged for 15 ft (4.6 m) of 3/8 liquid line. The factory charge for 3/8 lineset 9 oz. When using other length or diameterliquid lines, charge adjustments are required per the chart above.
Charging Formula:
[(Lineset oz/ft x total length) (factory charge for lineset)] = charge adjustment
Example 1:System has 15 ft of line set using existing 1/4 liquid line. What charge adjustment is required?
Formula: (.27 oz/ft x 15ft) (9 oz) = (-4.95) oz.
Net result is to remove 4.9 5 oz of refrigerant from th e system
Example 2: System has 45 ft of existing 5/16 liquid line. What is the charge adjustment?
Formula: (.40 oz/ft. x 45ft) (9 oz.) = 9 oz.
Net result is to add 9 oz of refrigerant to the system
LONG LINE APPLICATIONSAn application is considered Long Line, when the refrigerant level in the system requires the use of accessories to maintain acceptablerefrigerant management for systems reliability. See Accessory Usage Guideline table for required accessories. Defining a system as long linedepends on the liquid line diameter, actual length of the tubing, and vertical separation between the indoor and outdoor units.
For Air Conditioner systems, the chart below shows when an application is considered Long Line.
AC WITH PURON REFRIGERANT LONG LINE DESCRIPTION ft (m)
Beyond these lengths, long line accessories are required
Liquid Line Size Units On Same Level Outdoor Below Indoor Outdoor Above Indoor
1 / 4 N o acce ssori es ne e de d wi t hi n allowe d
le ngt hsN o acce ssori e s ne e de d wi t hi n allowe dle ngt hs
1 7 5 ( 5 3 .3 )
5 /1 6 120 (3 6.6) 50 ( 15.2 ) 1 20 ( 36 .6)
3 / 8 80 ( 24 .4) 35 ( 10.7 ) 8 0 ( 24. 4)
Note: S e e L o n g L i n e G u i d e l in e f o r d e t ai l s
VAPOR LINE SIZING AND COOLING CAPACITY LOSSAcceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for AC systems with Puron refrigerant:
UnitNominal
Size (Btuh)
MaximumLiquid LineDiameters
(In. OD)
Vapor LineDiameters
(In. OD)
Cooling Capacity Loss (%)Total Equivalent Line Length ft. (m)
26--- 50(7.9--- 15.2)
51--- 80(15.5 --- 24.4)
81--- 100(24.7---30.5)
101--- 125(30.8 --- 38.1)
126--- 150(38.4---45.7)
151 --- 175(46.0---53.3)
176--- 200(53.6 --- 61.0)
201--- 225(61.3---68.6)
226 --- 250(68.9---76.2)
180001 StageAC with
Puron
3 / 8
1/ 2 1 2 3 5 6 7 8 9 1 1
5/ 8 0 1 1 1 2 2 2 3 3
3/ 4 0 0 0 0 1 1 1 1 1
240001 StageAC with
Puron
3 / 8
5/ 8 0 1 2 2 3 3 4 5 5
3/ 4 0 0 1 1 1 1 1 2 2
7/ 8 0 0 0 0 0 1 1 1 1
300001 StageAC with
Puron
3 / 8
5/ 8 1 2 3 3 4 5 6 7 8
3/ 4 0 0 1 1 1 2 2 2 3
7/ 8 0 0 0 0 1 1 1 1 1
360001 StageAC with
Puron
3 / 85/ 8 1 2 4 5 6 8 9 10 123/ 4 0 1 1 2 2 3 3 4 4
7/ 8 0 0 0 1 1 1 1 2 2
420001 StageAC with
Puron
3 / 8
3/ 4 0 1 2 2 3 4 4 5 6
7/ 8 0 0 1 1 1 2 2 2 3
1 1/ 8 0 0 0 0 0 0 0 0 0
480001 StageAC with
Puron
3 / 8
3/ 4 0 1 2 3 4 5 5 6 7
7/ 8 0 0 1 1 2 2 2 3 3
1 1/ 8 0 0 0 0 0 0 0 1 1
600001 StageAC with
Puron
3 / 8
3/ 4 1 2 4 5 6 7 9 10 11
7/ 8 0 1 2 2 3 4 4 5 5
1 1/ 8 0 0 0 1 1 1 1 1 1
Appli cat ions i n t hi s are a may be long li ne and may have he i ght re st ri ct ions. Se e t heResidential Piping and Long Line Guideline .
24ACC6
-
7/26/2019 Carrier 24ACC6
5/205
ACCESSORY THERMOSTATS
PART NUMBER PROGRAM GAS ELECTRIC HEAT PUMP HYBRID
HEAT H EAT COOL
Performance
TP --- PRH01 --- A 7 --- Da y 3 2
TP --- PAC 01 7 --- Da y 1 1
TP --- NRH01 --- A NP 3 2
TP --- NAC01 NP 1 1
THERMOSTAT ACCESSORIES
PART NUMBER BRIEF DESCRIPTION THERMOSTATS USED WITH
SYSTXCCRRS01 Indoor Remote Roo m Tempe ra ture Sensor All TP --- the rmost ats
TP --- E X P0 1 --- A E xP Computer Pro gra mming Accessory TP --- P ther mostat s
T STAT XXC NV10 The rmost at Conver sion Kit ( 4 to 5 wir e) --- 1 0 pa ck All Car r ier bra nded the rmost ats
TX --- LBP01 L ar ge De cor ative Backpl ate TP --- Pxx, TP --- Nxx, TC --- Pxx
TSTATXX SE N01 --- B* Outdoor Air Temper atur e Sensor All TP --- the rmost ats
ACCESSORIESKIT NUMBER DESCRIPTION 18--- 30 24--- 30 30--- 30 36--- 30 42--- 30 48--- 30 60--- 30
K AAF T0 101 AAA FRE E ZE THERMOSTAT X X X X X X X
K AATD010 1TDR TIME DE LAY RE LAY X X X X X X X
K SALA0 3014 10 LOW AMBIENT PSW X X X X X X X
K SALA0 601AAA MOTORMASTER 23 0V X X X X X X X
HC3 2GE 234 MOTOR FAN BALL BE ARIN G X
HC3 4GE 240 MOTOR FAN BALL BE ARIN G X X
HC3 2GE 229 MOTOR FAN BALL BE ARIN G X
HC3 8GE 228 MOTOR FAN BALL BE ARIN G X
HC4 0GE 228 MOTOR FAN BALL BE ARIN G X X
K SAHS170 1AAA H ARD START ( CAP/ RE LAY) X X X X X X X
K SACY0 101 AAA CYCL E PROTECTOR X X X X X X X
K SASF010 1AAA SUPPORT FE ET X X X X X X X
K AAC S020 1PTC START AS SIST PTC X X X X X X X
K AAL S0 201L LS LIQUID LINE SOLE NOID X X X X X X X
K AAWS0 101AAA WINTE R START X X X X X X X
K AAC H170 1AAA CRANKCASE HTR X X X X
K AAC H160 1AAA CRANKCASE HTR X S S
K SATX 0 201 PU R TX V PU RON HSO X X X
K SATX 0 301 PU R TX V PU RON HSO X
K SATX 0 401 PU R TX V PU RON HSO X
K SATX 0 501 PU R TX V PU RON HSO X X
{ R e qu i r e d a c c e ss o r ie s i n c lu d e b a l l b e a r in g f a n m o t or , c o m p r e ss o r s t a r t a s s is t ( C A P / R e l a y) , c r a n k ca s e h e a t e r, e v a po r a t o r f r e e z e s t a t, h a r d s h u t - -- o f f T X V.
X = A c c es s o r y / S --- S t a n da r d
-
7/26/2019 Carrier 24ACC6
6/206
ACCESSORY USAGE GUIDELINE
ACCESSORY
REQUIRED FOR LOW---A MBI-ENT COOLING APPLICATIONS
(Below 55F/12.8C)
REQUIRED FOR LONGLINE
APPLICATIONS*(Over 80 ft./24.38 m)
REQUIRED FORSEA COAST
APPLICATIONS(Within 2 miles/3.22 km)
Ball Bearing Fan Motor Yes{ No N o
Compressor Start Assist Capacitor and Relay Yes Yes N o
Crankcase Heater Yes Yes N o
Evaporator Freeze Thermostat Yes No N o
Hard Shut---Off TXV Yes Yes Yes
Liquid Line Solenoid Valve N o No N o
Motor Master Control orLow---a mbient Pressure Switch
Yes No N o
Support Feet Recommen ded No Recommend ed
Winter Start Control Yes No N o
* F o r t u b i n g l i n e s e t s b e t w e en 8 0 a n d 2 0 0 f t . ( 2 4 .3 8 a n d 6 0 . 9 6 m ) a n d / o r 2 0 f t . ( 6 . 0 9 m ) v e r t ic a l d i f f e r e nt i a l, r e f e r t o R e si d en t i al S p l it - -- S y s t e m L o n g l in e Appli cat ion Gui de li ne.
{ R e qui re d for Low---Ambi e nt Cont rolle r ( full modulat i on fe at ure ) Mot orMast e rr Cont rol.
Accessory Description and Usage (Listed Alphabetically)1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reductionwhile maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a hard boost to compressormotor at each start up.
Usage Guideline:
Required for reciprocating compressors in thefollowing applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in thefollowing applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history oflow voltage problems.
3. Compressor Start Assist PTC Type
Solid state electrical device which gives a soft boost to thecompressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of thecompressor to keep the lubricant warm during off cycles.Improves compressor lubrication on restart and minimizes thechance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor shortcycling. This control provides an approximate 5 --minute delayafter power to the compressor has been interrupted for anyreason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operationwhen evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unitservice valve. It is designed to cycle the outdoor fan motor inorder to maintain head pressure within normal operating limits(approximately 100 psig to 225 psig). The control will maintain
working head pressure at low--ambient temperatures down to 0_F(--18_C) when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterrLow--Ambient Controller must be used when cooling operation isused at outdoor temperatures below 55_F (12.8_C).
8. MotorMaster Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,designed to control condenser fan motor speed in response to thesaturated, condensing temperature during operation in coolingmode only. For outdoor temperatures down to --20_F (--28.9_C),it maintains condensing temperature at 100_F 10_F (37.8_C 5.5_C).
Usage Guideline:
A MotorMasterr Low Ambient Controller orLow--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperaturesbelow 55_F (12.8_C).
Suggested for all commercial applications.
9. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in thispublication. This device enables the thermostat to display theoutdoor temperature. This device also
is required to enable special thermostat features such as auxiliaryheat lock out.
Usage Guideline:
Suggested for all Carrier thermostats listed in thispublication.
24ACC6
-
7/26/2019 Carrier 24ACC6
7/207
Accessory Description and Usage (Listed Alphabetically) (Continued)10. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)above the mounting pad. This allows sand, dirt, and other debristo be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.11. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquidflow rate into the evaporator in response to the superheat of therefrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase
reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
combinations. Refer to combination ratings.Hard shut off TXV or LLS required in air conditionerlong line applications.
Required for use on all zoning systems.
12. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoorblower motor to provide additional cooling after the compressorcycles off.
NOTE: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certaincombinations of indoor and outdoor units. Refer to
AHRI Unitary Directory.
13. Winter Start Control
This control is designed to alleviate nuisance opening of thelow--pressure switch by bypassing it for the first 3 minutes ofoperation.
-
7/26/2019 Carrier 24ACC6
8/208
ELECTRICAL DATA
UNIT SIZE V/PH
OPER VOLTS* COMPR FAN
MCA
MINWIRESIZE{60 C
MINWIRESIZE{75 C
MAXLENGTHft. (m)}
60 C
MAXLENGTHft. (m)}
75 C
MAXFUSE**or CKT
BRKAMPS
MAX MIN LRA RLA FLA
18--- 30
2 08/ 2 30/ 1 --- 60 2 53 1 97
48 .0 9.0 0.50 1 1.8 14 1 4 6 7 ( 20. 4) 64 ( 19 .5) 2 0
24--- 30 58 .3 13. 5 0.70 1 7.6 14 1 4 4 6 ( 14. 0) 43 ( 13 ..1) 2 5
30--- 30 64 .0 12. 8 0.70 1 6.7 14 1 4 4 4 ( 13. 4) 41 ( 12 .5) 2 5
36--- 30 77 .0 14. 1 0.50 1 8.1 12 1 2 5 7 ( 17. 4) 54 ( 16 .5) 3 0
42--- 30 112 .0 17. 9 1.20 2 3.6 10 1 0 8 5 ( 25. 9) 81 ( 24 .7) 4 0
48--- 30 109 .0 19. 9 1.20 2 6.1 10 1 0 7 0 ( 21. 3) 67 ( 20 .4) 4 0
60--- 30 135 .0 21. 4 1.20 2 8.0 8 1 0 9 1 ( 27. 7) 56 ( 17 .1) 4 0* P e rm i ss i bl e l i m it s o f t h e v o l t a g e r a n g e a t w h i ch t h e u n i t w i l l o p e r a t e s a t i sf a c t o ri l y
{ I f w i r e i s a p p l i e d a t a m b i en t g r e a t e r t h a n 3 0_C , c o n s ul t t a b l e 3 1 0 --- 1 6 o f t h e N E C ( N F PA 7 0 ) . T h e a m p a c i t y o f n o n --- m e t a l l ic - -- s h e a t h ed c a b l e ( N M ) , t r a d en a me R OM E X , s h a ll b e t h a t o f 6 0_C c o n d it i o ns , p e r t h e N E C ( N F PA 7 0 ) A r t ic l e 3 3 6 - -- 2 6 . I f o t h er t h a n u n c o a t ed ( n o --- p l a t e d) , 6 0 o r 7 5_C i n s ul a t io n , c o p p erw i r e ( s o l id w i r e f o r 1 0 A W G o r s m a l le r, s t r a nd e d w i r e f o r l a r g e r t h a n 1 0 A WG ) i s u s e d, c o n s ul t a p p l i c a bl e t a b l es o f t h e N E C ( N F PA 7 0 ) .
} L e n g th s h o w n i s a s m e a s u r e d o n e w a y a l o n g w i r e p a t h b e tw e e n u n it a n d s e r v i c e p a n el f o r v o l t a ge d r o p n o t t o e x c ee d 2 % .
** Ti me ---De lay fuse .
FLA --- Full Load Amps
LRA --- Locke d R ot or Amps
MCA --- Mi ni mum Ci rcui t Amps
RLA --- R at e d Load Amps
NOTE: C o n t r ol c i r cu i t i s 2 4 --- V o n a l l u n i ts a n d r e q u ir e s e x t e r n a l p o w e r s o u r c e. C o p pe r w i r e m u s t b e u s e d f r o m s e r v ic e d i s c o nn e c t t o u n i t . All mot ors/ compre ssors cont ai n i nt e rnal ove rload prot e ct i on.
Compli e s wi t h 2 0 1 0 re qui re me nt s of ASHR AE St andards 9 0 .1
A--WEIGHTED SOUND POWER LEVEL (dBA)Unit Size ---
Voltage, Series
Standard
Rating (dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
125 250 500 1000 2000 4000 800018--- 30 73 49. 5 58.5 64.5 69 .0 63.0 5 9.5 52 .4
24--- 30 74 54. 5 62.0 67.0 71 .5 66.0 6 2.0 53 .0
30--- 30 74 56. 0 62.5 66.0 68 .5 64.5 6 1.0 53 .5
36--- 30 72 52. 0 61.0 64.0 66 .0 61.0 5 8.5 51 .5
42--- 30 74 56. 5 61.5 65.0 66 .5 63.5 6 1.0 56 .5
48--- 30 73 58. 0 61.0 65.0 66 .0 62.0 5 8.0 51 .0
60--- 30 74 56. 5 62.5 66.5 68 .0 63.0 5 9.5 51 .5
NOTE: Te s te d i n a c c o r da n c e w i t h A H R I S t a n d a r d 2 7 0 --- 0 8 ( n o t l i s t ed i n A H R I ) .
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)UNIT SIZE--- VOLTAGE, SERIES REQUIRED SUBCOOLING F (C)
18--- 30 1 0 ( 5 . 6 )
24--- 30 1 0 ( 5 . 6 )
30--- 30 1 0 ( 5 . 6 )
36--- 30 1 0 ( 5 . 6 )42--- 30 9 ( 5 . 0)
48--- 30 1 0 ( 5 . 6 )
60--- 30 9 ( 5 . 0)
24ACC6
-
7/26/2019 Carrier 24ACC6
9/209
DIMENSIONS--ENGLI
SH
3"
K
5/16"
L
N
M
E
F
G
C
31/2
"
17/8"
P
A
B
208-230-1-60
230-1-60
208/230-3-60
460-3-60
UNIT
SERIES
ELECTRICA
L
CHARACTERISTICSA
B
C
D
E
F
G
K
L
M
N
P
OPERATING
WEIGHT(lbs)S
HIPPING
WEIGHT(lbs
)
SHIPPING
DIMENSIONS(LxW
xH)
24ACC618
0
X
O
O
O
253/4"
2811/16"
33/4"
3/4"
47/16"
211/4"
713/16"
213/16"
1/2"
131/4"
133/4"
123/4"
136
163
267/8"X301/16"X329/16"
24ACC624
0
X
O
O
O
313/16"
285/16"
33/4"
3/4"
69/16"
2411/16"
91/8"
213/16"
1/2"
155/8"
151/2"
14"
163
198
323/8"X351/2"X329/16"
24ACC630
0
X
O
O
O
313/16"
325/16"
33/4"
3/4"
69/16"
2411/16"
91/8"
213/16"
1/2"
161/2"
15"
143/4"
167
204
323/8"X351/2"X3515/16"
24ACC636
0
X
O
O
O
35"
285/16"
37/8"
7/8"
69/16"
287/16"
91/8"
215/16"
5/8"
181/4"
167/8"
14"
180
219
361/8"X395/16"X329/16"
24ACC642
0
X
O
O
O
35"
391/8"
37/8"
7/8"
69/16"
287/16"
91/8"
215/16"
5/8"
18"
16"
171/2"
234
281
361/8"X395/16"X423/4"
24ACC648
0
X
O
O
O
35"
325/16"
37/8"
7/8"
69/16"
287/16"
91/8"
215/16"
5/8"
17"
171/2"
14"
248
291
361/8"X395/16"X3515/16"
24ACC660
0
X
O
O
O
35"
4515/16"
37/8"
7/8"
69/16"
287/16"
91/8"
215/16"
5/8"
177/8"
185/8"
201/4"
337
372
361/8"X395/16"X499/16"
UNITSIZE
MINIMU
M
MOUNTINGPAD
DIMENSIONS
18
26"X26"
24,30
311/2"X311/2
"
36THRU60
35"X35"
AIRDISCHARGE
AIRIN
AIRIN
AIRIN
AIRIN
3/8"TIEDOWNK
NOCKOUTS
(2)PLACES
X=YES
O=NO
NOTES:
1.ALLOW
30"CLEARANCETOSERVICESIDEOFUNIT,
48"ABOVEUNIT,6"ONONESIDE,12"ONREMAININGSIDE,
AND24"BETWEENUNITSFORPR
OPERAIRFLOW.
2.MINIMUMOUTDOOROPERATING
AMBIENTINCOOLING
MODEIS55
F,MAX.125
3.SERIESDESIGNATIONISTHE13TH
POSITIONOFTHE
UNITMODELNUMBER.
4.CENTEROFGRAVITY
.
5.ALLDIMENSIONSAREIN"INCHES"UNLESSNOTED.
AIRDISCHARGE
SQ.
VAPORLINECON
N.
FIELDCONTROL
SUPPLYCONN
.
7/8"HOLE
FIELDPOWERSUPPLYCONN.
7/8"HOLEWITH
11/8"KNOCKOU
T
D
-
7/26/2019 Carrier 24ACC6
10/2010
DIMENSIONS--SI
76.2
K
8.0
L
N
M
E
F
G
A
P
47.6
C
88.9
B
208-230-1-60
230-1-60
208/230-3-60
460-3-60
UNIT
SERIES
ELECTRIC
AL
CHARACTER
ISTICSA
B
C
D
E
F
G
K
L
M
N
P
OPERATING
WEIGHT(Kgs)S
HIPPING
WEIGHT(Kgs
)
SHIPPING
D
IMENSIONS(LxW
xH)
24ACC618
0
X
O
O
O
654.0
728.7
95.2
19.0
112.7
539.8
198.4
71.4
12.7
336.6
349.3
323.9
61.7
73.9
682.6X763.6X827.1
24ACC624
0
X
O
O
O
792.2
719.2
95.2
19.0
166.7
627.1
231.8
71.4
12.7
396.9
393.7
355.6
73.9
89.8
822.3X901.7X827.1
24ACC630
0
X
O
O
O
792.2
820.8
95.2
19.0
166.7
627.1
231.8
71.4
12.7
419.1
381.0
374.7
75.7
92.5
822.3X901.7X912.8
24ACC636
0
X
O
O
O
889.0
719.2
98.6
22.2
166.7
722.3
231.8
74.6
15.9
463.6
428.6
355.6
81.6
99.3
917.6X998.6X827.1
24ACC642
0
X
O
O
O
889.0
993.8
98.6
22.2
166.7
722.3
231.8
74.6
15.9
457.2
406.4
444.5
106.1
127.5
917.6X998.6X1085.8
24ACC648
0
X
O
O
O
889.0
820.8
98.6
22.2
166.7
722.3
231.8
74.6
15.9
431.8
444.5
355.6
112.5
132.0
917.6X998.6X912.8
24ACC660
0
X
O
O
O
889.0
1166.8
98.6
22.2
166.7
722.3
231.8
74.6
15.9
454.0
473.1
514.4
152.9
168.7
917.6X998.6X1173.2
UNITSIZE
MINIMUM
MOUNTINGPAD
DIMEN
SIONS
18
660.4X660.4
24,30
800.1X800.1
36THRU60
889.0X889.0
AIRDISCHARGE
AIRIN
AIRIN
AIRIN
AIRIN
9.53TIEDOWNKN
OCKOUTS
(2)
PLACES
X=YES
O=NO
NOTES:
1.ALLOW
762.0CLEARANCETOSERVICE
SIDEOFUNIT,
1219.2ABOVEUNIT,152.4ONONESIDE
,304.8ONREMAININGSIDE,
AND609.6BETWEENUNITSFORPROPERAIRFLOW.
2.MINIMUMOUTDOOROPERATINGAMBIENTINCOOLING
MODEIS13
C,MAX.52
3.SERIESDESIGNATIONISTHE10THPOSIT
IONOFTHE
UNITMODELNUMBER.
4.CENTEROFGRAVITY
.
5.ALLDIMENSIONSAREIN"MM"UNLESSNOTED.
AIRDISCHARGE
SQ.
VAPORLINECO
NN.
FIELDCONTRO
L
SUPPLYCONN.
22.23HOL
E
FIELDPOWERSUPPLYC
ONN.
22.23HOLEW
ITH
28.58KNOCK
OUT
D
24ACC6
-
7/26/2019 Carrier 24ACC6
11/2011
CLEARANCES
Clearances(variousexamples)
Wall
Wall
Wall
Wall
24
Service
6
(152.4mm)
2
4
(60
9.6
)
Service
24
(609.6
)
Service
24
(609.6
)
Service
24
(609.6
)
Service
24
(609.6
)
24
(609
.6)
24
(609.6)
1
2
(304.8
)
12
(304.8
)
12
(304.8)
12
(304.8
)
6
(152.4
)
Note:Numbersin()=mm
IMPORTANT:Wheninstallingmultipleunitsinanalcove,roofwell,orpartiallyenclosedarea,ensurethereisadequateventilationtopreventre--circulationofdischarg
eair.
-
7/26/2019 Carrier 24ACC6
12/2012
TESTED AHRI COMBINATION RATINGS*
NOTE: Ratings contained in this document are subject to change at any time.
For AHRI ratings certificates, please refer to the AHRI directory www.ahridirectory.org
Additional ratings and system combinations can be accessed via the Carrier database at:
http://cactaxcredits.info/carrier-ratings/ac_ratings_srch .php
Equipment performance calculator can be accessed at: http://rpmob.wrightsoft.com/
Model Number Indoor Model Furnace Model Capacity EER SEER
24ACC6 18 A**3 0 CNPV*19 17 A**+TDR 1 8,00 0 1 2.0 1 4.5
24ACC6 24 A**3 0 CNPV*31 17 A**+TDR 2 3,60 0 1 2.0 1 4.524ACC6 30 A**3 0 CNPV*31 17 A**+TDR 2 8,60 0 1 2.0 1 4.5
24ACC6 36 A**3 0 CNPV*37 17 A**+TDR 3 4,40 0 1 2.0 1 4.5
24ACC6 42 A**3 0 CNPV*43 24 A**+TDR 4 1,50 0 1 2.0 1 4.5
24ACC6 48 A**3 0 CNPV*61 24 A**+TDR 4 6,50 0 1 2.5 1 4.5
24ACC6 60 A**3 0 CNPV*61 24 A**+TDR 5 5,00 0 1 2.5 1 4.5
* A H R I = A i r C o n d i t i on i n g, H e a t i ng & R e f ri g e r at i o n I n s t i t ut eEER E n e rg y E ffic ie n c y Rat io --- A c on d it ion s --- 8 0_F ( 2 6 . 6_C ) i n d oo r d b / 67_F ( 1 9 . 4_C ) i n d o o r w b & 9 5_F ( 3 5_C ) o u t do o r w b .SEER S e a s on a l E n er g y E f f i ci e n cy R a t i oTDR T i m e --- D e l a y R e l a y. I n m o s t c a s e s , o n l y o n e m e t h od s h o u l d b e u s e d t o a c h i e v e T D R f u n c t io n . U s i n g m o r e t h a n o n e m e th o d i n a s y s t em m a y c a u s e d e g ra d a t i on i n
p e r fo r m a nc e . U s e e i t h e r t h e a c c es s o r y T i m e --- D e l a y R e l ay , K A A T D 01 0 1 TD R , o r a f u r na c e e q ui p p ed w i t h T D R . M o s t C a r r i e r f u r na c e s a r e e q u ip p ed w i t h T D R .NOTES:
1 . R a t i ng s a r e n e t v a l u es r e f le c t in g t h e e f f ec t s o f c i r cu l a t in g f a n m o t o r h e a t. S u pp l e me n t al e l e ct r i c h e a t i s n o t i n c l u d ed .
2 . Te s t e d o u t d o or / i n do o r c o m bi n a t io n s h a v e b e e n t e s t ed i n a c c o rd a n ce w i t h D O E t e s t p r o c e d ur e s f o r c e n tr a l a i r c o n di t i o ne r s . R a t i n g s f o r o t h erc om b in at ion s are d e t e rm in e d u n d e r D O E c om p u t e r sim u lat ion p roc e d u re s.
3 . D e t e r m i ne a c t ua l C F M v a l u e s o b t a i n a bl e f o r y o u r s y s t e m b y r e f er r i ng t o f a n p e rf o r m an c e d a t a i n f a n c o i l o r f u r na c e c o i l l i t e ra t u r e.
4 . D o n o t a p p l y w i t h c a p i l l a ry t u b e c o i l s a s p e r fo r m a nc e a n d r e l i a bi l i t y a r e s i g ni f i c a nt l y a f f e c t ed .
24ACC6
-
7/26/2019 Carrier 24ACC6
13/20
-
7/26/2019 Carrier 24ACC6
14/20
-
7/26/2019 Carrier 24ACC6
15/20
-
7/26/2019 Carrier 24ACC6
16/20
-
7/26/2019 Carrier 24ACC6
17/2017
CONDENSER ONLY RATINGSSST
F ( C)CONDENSER ENTERING AIR TEMPERATURES F ( C)
55 (12.78) 65 (18.33) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 115 (46. 11) 125 (51.67)
24ACC618A**30
30( --- 1.11)
TCG 15. 70 14 .90 14.1 0 13 .20 1 2.30 11. 30 1 0.20 9.2 0
SDT 66. 60 76 .20 85.8 0 95 .30 1 04.8 0 114 .30 12 3.70 1 33. 10
KW 0.7 5 0 .87 0.9 9 1. 12 1.26 1.4 1 1 .60 1.8 1
35(1.67)
TCG 17. 50 16 .60 15.7 0 14 .70 1 3.70 12. 60 1 1.50 10.3 0
SDT 67. 80 77 .30 86.8 0 96 .30 1 05.7 0 115 .10 12 4.40 1 33. 80
KW 0.7 5 0 .87 0.9 9 1. 12 1.26 1.4 2 1 .60 1.8 1
40(4.44)
TCG 19. 40 18 .40 17.4 0 16 .30 1 5.20 14. 00 1 2.80 11.5 0
SDT 69. 00 78 .50 87.9 0 97 .30 1 06.6 0 115 .90 12 5.20 1 34. 50
KW 0.7 4 0 .87 0.9 9 1. 12 1.26 1.4 2 1 .60 1.8 1
45(7.22)
TCG 21. 50 20 .30 19.2 0 18 .00 1 6.70 15. 50 1 4.10 12.8 0
SDT 70. 40 79 .70 89.0 0 98 .30 1 07.6 0 116 .90 12 6.10 1 35. 30
KW 0.7 4 0 .86 0.9 9 1. 13 1.27 1.4 3 1 .61 1.8 2
50(10.0)
TCG 23. 60 22 .40 21.1 0 19 .70 1 8.40 17. 00 1 5.60 14.1 0
SDT 71. 60 80 .90 90.1 0 99 .40 1 08.6 0 117 .80 12 7.00 1 36. 20
KW 0.7 3 0 .86 1.0 0 1. 13 1.28 1.4 4 1 .62 1.8 2
55(12.78)
TCG 25. 90 24 .50 23.1 0 21 .60 2 0.10 18. 60 1 7.10 15.5 0
SDT 73. 00 82 .10 91.3 0 100 .50 1 09.7 0 118 .80 12 8.00 1 37. 10
KW 0.7 3 0 .86 1.0 0 1. 14 1.29 1.4 5 1 .63 1.8 4
24ACC624A**30
30( --- 1.11)
TCG 21. 10 20 .10 19.0 0 17 .90 1 6.70 15. 40 1 4.10 12.7 0
SDT 66. 10 75 .80 85.3 0 94 .90 1 04.4 0 114 .00 12 3.40 1 32. 80
KW 1.0 0 1 .15 1.3 1 1. 47 1.65 1.8 6 2 .09 2.3 7
35(1.67)
TCG 23. 40 22 .20 21.0 0 19 .80 1 8.50 17. 10 1 5.60 14.1 0
SDT 67. 20 76 .80 86.3 0 95 .80 1 05.3 0 114 .70 12 4.10 1 33. 50
KW 0.9 9 1 .15 1.3 1 1. 47 1.66 1.8 6 2 .10 2.3 7
40(4.44)
TCG 25. 80 24 .60 23.2 0 21 .80 2 0.40 18. 90 1 7.30 15.7 0
SDT 68. 40 77 .90 87.3 0 96 .70 1 06.1 0 115 .50 12 4.80 1 34. 10
KW 0.9 8 1 .14 1.3 1 1. 48 1.66 1.8 7 2 .10 2.3 7
45(7.22)
TCG 28. 50 27 .00 25.5 0 24 .00 2 2.40 20. 80 1 9.10 17.4 0
SDT 69. 60 79 .00 88.3 0 97 .70 1 07.0 0 116 .30 12 5.60 1 34. 90
KW 0.9 7 1 .14 1.3 1 1. 48 1.67 1.8 7 2 .11 2.3 7
50(10.0)
TCG 31. 20 29 .60 28.0 0 26 .30 2 4.60 22. 80 2 1.00 19.1 0
SDT 70. 80 80 .10 89.4 0 98 .70 1 07.9 0 117 .20 12 6.40 1 35. 60
KW 0.9 6 1 .14 1.3 1 1. 49 1.67 1.8 8 2 .12 2.3 8
55(12.78)
TCG 34. 20 32 .40 30.6 0 28 .80 2 6.90 25. 00 2 3.00 20.9 0
SDT 72. 10 81 .30 90.5 0 99 .70 1 08.9 0 118 .10 12 7.30 1 36. 40
KW 0.9 5 1 .13 1.3 1 1. 49 1.69 1.9 0 2 .13 2.3 9
24ACC630A**30
30( --- 1.11)
TCG 24. 90 23 .50 22.2 0 20 .80 1 9.40 17. 90 1 6.20 14.4 0
SDT 68. 10 77 .50 87.0 0 96 .40 1 05.8 0 115 .10 12 4.40 1 33. 60
KW 1.2 7 1 .43 1.6 0 1. 78 1.99 2.2 3 2 .50 2.8 1
35(1.67)
TCG 27. 50 26 .00 24.5 0 23 .10 2 1.50 19. 90 1 8.10 16.2 0
SDT 69. 40 78 .70 88.1 0 97 .40 1 06.7 0 116 .00 12 5.30 1 34. 40
KW 1.2 8 1 .44 1.6 1 1. 79 2.00 2.2 4 2 .51 2.8 2
40(4.44)
TCG 30. 30 28 .60 27.1 0 25 .50 2 3.80 22. 00 2 0.10 18.1 0
SDT 70. 70 79 .90 89.2 0 98 .50 1 07.7 0 117 .00 12 6.20 1 35. 30KW 1.2 9 1 .44 1.6 1 1. 80 2.01 2.2 5 2 .52 2.8 3
45(7.22)
TCG 33. 30 31 .50 29.8 0 28 .00 2 6.20 24. 30 2 2.30 20.1 0
SDT 72. 00 81 .20 90.4 0 99 .60 1 08.8 0 118 .00 12 7.20 1 36. 30
KW 1.2 9 1 .44 1.6 1 1. 80 2.01 2.2 6 2 .53 2.8 5
50(10.0)
TCG 36. 50 34 .50 32.6 0 30 .70 2 8.80 26. 70 2 4.50 22.2 0
SDT 73. 50 82 .50 91.7 0 100 .80 1 10.0 0 119 .20 12 8.20 1 37. 20
KW 1.2 9 1 .44 1.6 1 1. 80 2.02 2.2 6 2 .54 2.8 6
55(12.78)
TCG 39. 90 37 .80 35.7 0 33 .60 3 1.50 29. 30 2 6.90 24.4 0
SDT 75. 00 84 .00 93.0 0 102 .10 1 11.2 0 120 .30 12 9.30 1 38. 20
KW 1.2 9 1 .44 1.6 1 1. 80 2.02 2.2 7 2 .54 2.8 6
24ACC636A**30
30( --- 1.11)
TCG 30. 40 28 .80 27.2 0 25 .60 2 3.90 22. 10 2 0.20 18.2 0
SDT 68. 90 78 .20 87.5 0 96 .80 1 06.2 0 115 .50 12 4.90 1 34. 20
KW 1.4 9 1 .72 1.9 5 2. 21 2.49 2.8 1 3 .20 3.6 4
35(1.67)
TCG 33. 50 31 .80 30.1 0 28 .30 2 6.50 24. 50 2 2.50 20.3 0
SDT 70. 10 79 .30 88.6 0 97 .90 1 07.2 0 116 .50 12 5.80 1 35. 00
KW 1.4 9 1 .73 1.9 6 2. 22 2.50 2.8 2 3 .20 3.6 5
40(4.44)
TCG 37. 00 35 .10 33.2 0 31 .20 2 9.20 27. 10 2 4.90 22.6 0
SDT 71. 40 80 .60 89.8 0 99 .00 1 08.2 0 117 .40 12 6.70 1 35. 90
KW 1.5 0 1 .73 1.9 7 2. 23 2.51 2.8 4 3 .21 3.6 5
45(7.22)
TCG 40. 60 38 .60 36.5 0 34 .30 3 2.10 29. 80 2 7.40 24.9 0
SDT 72. 80 81 .90 91.0 0 100 .20 1 09.4 0 118 .50 12 7.70 1 36. 80
KW 1.5 1 1 .75 1.9 9 2. 24 2.53 2.8 5 3 .23 3.6 6
50(10.0)
TCG 44. 50 42 .30 40.0 0 37 .70 3 5.20 32. 70 3 0.10 27.4 0
SDT 74. 40 83 .30 92.4 0 101 .50 1 10.5 0 119 .60 12 8.70 1 37. 70
KW 1.5 3 1 .76 2.0 1 2. 26 2.55 2.8 7 3 .24 3.6 7
55(12.78)
TCG 48. 70 46 .20 43.7 0 41 .20 3 8.50 35. 80 3 3.00 30.0 0
SDT 76. 00 84 .90 93.8 0 102 .80 1 11.8 0 120 .80 12 9.80 1 38. 70
KW 1.5 5 1 .79 2.0 3 2. 29 2.57 2.9 0 3 .26 3.6 9
S e e n o t e s o n p a g e 1 8
-
7/26/2019 Carrier 24ACC6
18/2018
CONDENSER ONLY RATINGS CONTINUEDSST
F ( C)CONDENSER ENTERING AIR TEMPERATURES F ( C)
55 (12.78) 65 (18.33) 75 (23.89) 85 (29.44) 95 (35.0) 105 (40.56) 115 (46. 11) 125 (51.67)
24ACC642A**30
30( --- 1.11)
TCG 37. 90 36 .20 34.3 0 32 .30 3 0.10 27. 90 2 5.50 23.0 0
SDT 69. 80 79 .20 88.7 0 98 .10 1 07.4 0 116 .70 12 5.90 1 35. 10
KW 1.8 3 2 .03 2.2 6 2. 54 2.86 3.2 2 3 .63 4.0 9
35(1.67)
TCG 41. 90 40 .00 37.9 0 35 .70 3 3.30 30. 80 2 8.30 25.6 0
SDT 71. 20 80 .60 89.9 0 99 .20 1 08.4 0 117 .70 12 6.80 1 36. 00
KW 1.8 4 2 .04 2.2 8 2. 56 2.88 3.2 4 3 .65 4.1 0
40(4.44)
TCG 46. 10 44 .00 41.7 0 39 .20 3 6.70 34. 00 3 1.20 28.3 0
SDT 72. 70 81 .90 91.2 0 100 .40 1 09.6 0 118 .70 12 7.80 1 36. 90
KW 1.8 5 2 .05 2.3 0 2. 58 2.90 3.2 6 3 .67 4.1 3
45(7.22)
TCG 50. 70 48 .30 45.8 0 43 .10 4 0.20 37. 30 3 4.30 31.1 0SDT 74. 20 83 .30 92.5 0 101 .60 1 10.8 0 119 .80 12 8.90 1 37. 90
KW 1.8 6 2 .07 2.3 2 2. 60 2.92 3.2 9 3 .70 4.1 5
50(10.0)
TCG 55. 50 52 .90 50.1 0 47 .10 4 4.00 40. 80 3 7.50 34.1 0
SDT 75. 80 84 .80 93.9 0 103 .00 1 12.0 0 121 .00 13 0.00 1 38. 90
KW 1.8 7 2 .09 2.3 4 2. 63 2.95 3.3 2 3 .73 4.1 9
55(12.78)
TCG 60. 70 57 .70 54.6 0 51 .30 4 7.90 44. 40 4 0.80 37.1 0
SDT 77. 40 86 .40 95.4 0 104 .40 1 13.4 0 122 .30 13 1.20 1 40. 00
KW 1.8 9 2 .11 2.3 6 2. 66 2.99 3.3 6 3 .77 4.2 2
24ACC648A**30
30( --- 1.11)
TCG 41. 30 39 .10 36.9 0 34 .70 3 2.40 30. 00 2 7.50 24.8 0
SDT 67. 80 77 .20 86.6 0 96 .00 1 05.4 0 114 .70 12 4.00 1 33. 30
KW 2.0 1 2 .31 2.5 9 2. 89 3.19 3.5 4 3 .93 4.3 8
35(1.67)
TCG 45. 60 43 .20 40.8 0 38 .30 3 5.80 33. 20 3 0.40 27.6 0
SDT 69. 00 78 .30 87.7 0 97 .00 1 06.3 0 115 .60 12 4.80 1 34. 10
KW 1.9 4 2 .27 2.5 8 2. 89 3.21 3.5 6 3 .95 4.3 9
40(4.44)
TCG 50. 50 47 .70 45.0 0 42 .20 3 9.40 36. 60 3 3.60 30.5 0
SDT 70. 40 79 .60 88.8 0 98 .00 1 07.2 0 116 .50 12 5.70 1 34. 80
KW 1.8 4 2 .20 2.5 4 2. 87 3.21 3.5 7 3 .97 4.4 1
45(7.22)
TCG 55. 70 52 .60 49.5 0 46 .50 4 3.40 40. 20 3 6.90 33.5 0
SDT 71. 80 80 .80 90.0 0 99 .10 1 08.3 0 117 .40 12 6.60 1 35. 70
KW 1.6 9 2 .09 2.4 6 2. 83 3.19 3.5 7 3 .98 4.4 3
50(10.0)
TCG 61. 40 57 .90 54.5 0 51 .00 4 7.60 44. 10 4 0.50 36.7 0
SDT 73. 20 82 .20 91.3 0 100 .30 1 09.4 0 118 .50 12 7.50 1 36. 50
KW 1.5 0 1 .94 2.3 6 2. 76 3.15 3.5 5 3 .98 4.4 4
55(12.78)
TCG 67. 60 63 .60 59.8 0 55 .90 5 2.10 48. 20 4 4.20 40.1 0
SDT 74. 70 83 .70 92.6 0 101 .60 1 10.6 0 119 .60 12 8.50 1 37. 40
KW 1.2 6 1 .75 2.2 1 2. 65 3.08 3.5 1 3 .97 4.4 4
24ACC660A**30
30( --- 1.11)
TCG 45. 10 43 .80 42.3 0 40 .50 3 8.50 36. 20 3 3.50 30.5 0
SDT 69. 00 78 .40 87.7 0 97 .10 1 06.4 0 115 .60 12 4.80 1 34. 00
KW 2.2 2 2 .52 2.8 3 3. 17 3.56 4.0 0 4 .53 5.1 5
35(1.67)
TCG 50. 00 48 .40 46.7 0 44 .70 4 2.50 40. 00 3 7.10 33.8 0
SDT 70. 40 79 .70 89.0 0 98 .20 1 07.4 0 116 .60 12 5.80 1 34. 90
KW 2.2 1 2 .52 2.8 5 3. 19 3.58 4.0 3 4 .55 5.1 6
40(4.44)
TCG 55. 10 53 .40 51.4 0 49 .20 4 6.70 44. 00 4 0.80 37.3 0
SDT 71. 90 81 .10 90.2 0 99 .40 1 08.5 0 117 .60 12 6.70 1 35. 70KW 2.2 1 2 .53 2.8 6 3. 21 3.61 4.0 5 4 .57 5.1 8
45(7.22)
TCG 60. 70 58 .60 56.4 0 54 .00 5 1.20 48. 20 4 4.80 41.0 0
SDT 73. 50 82 .50 91.6 0 100 .70 1 09.7 0 118 .70 12 7.70 1 36. 70
KW 2.2 0 2 .53 2.8 7 3. 23 3.63 4.0 8 4 .60 5.2 0
50(10.0)
TCG 66. 50 64 .20 61.7 0 59 .00 5 6.00 52. 60 4 8.90 44.7 0
SDT 75. 10 84 .00 93.0 0 102 .00 1 11.0 0 119 .90 12 8.80 1 37. 60
KW 2.1 9 2 .53 2.8 9 3. 26 3.66 4.1 1 4 .63 5.2 2
55(12.78)
TCG 72. 80 70 .10 67.3 0 64 .20 6 0.90 57. 20 5 3.10 48.6 0
SDT 76. 80 85 .70 94.5 0 103 .40 1 12.3 0 121 .10 12 9.90 1 38. 60
KW 2.1 8 2 .54 2.9 0 3. 28 3.69 4.1 5 4 .66 5.2 5
* A H RI l i s ti n g a p p l i e s o n l y t o s y s te m s s h o w n i n C o m b in a t io n R a t in g s t a b l e .
KW --- O u t do o r U n i t K il o w a tt s O n l y.
SDT --- S a t u r at e d T e mp e r a tu r e L e a v in g C o m pr e s so r ( F )
SST --- S a t u r a te d T e m pe r a t ur e E n t e r in g C o m p r e s so r ( F / C )
TCG --- G r o s s C o o l i n g C a p a c it y ( 1 0 00 B t u h)
24ACC6
-
7/26/2019 Carrier 24ACC6
19/2019
GUIDE SPECIFICATIONSGENERALSystem Description
Outdoor--mounted, air--cooled, split--system air conditioner unitsuitable for ground or rooftop installation. Unit consists of ahermetic compressor, an air--cooled coil, propeller--typecondenser fan, and a control box. Unit will discharge supply airupward as shown on contract drawings. Unit will be used in arefrigeration circuit to match up to a packaged fan coil or coilunit.
Quality Assurance Unit will be rated in accordance with the latest edition
of AHRI Standard 210.
Unit will be certified for capacity and efficiency, andlisted in the latest AHRI directory.
Unit construction will comply with latest edition ofANSI/ ASHRAE and with NEC.
Unit will be constructed in accordance with ULstandards and will carry the UL label of approval. Unit
will have c--UL--us approval.
Unit cabinet will be capable of withstanding FederalTest Method Standard No. 141 (Method 6061) 500 --hrsalt spray test.
Air--cooled condenser coils will be leak tested at 150psig and pressure tested at 450 psig.
Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and isstored and handled per unit manufacturersrecommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
PRODUCTSEquipment
Factory assembled, single piece, air--cooled air conditioner unit.Contained within the unit enclosure is all factory wiring, piping,
controls, compressor, refrigerant charge Puronr (R--410A), andspecial features required prior to field start--up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel,bonderized, and coated with a powder coat paint.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
24ACC61--1/2 TO 5 NOMINAL TONS
Fans
Condenser fan will be direct--drive propeller type,discharging air upward.
Condenser fan motors will be totally enclosed, 1--phasetype with class B insulation and permanently lubricatedbearings. Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibrationisolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanicallybonded to copper tubes which are then cleaned,dehydrated, and sealed.
Refrigeration Components
Refrigeration circuit components will includeliquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,system charge of Puronr (R--410A) refrigerant, andcompressor oil.
Unit will be equipped with high--pressure switch, lowpressure switch and filter drier for Puron refrigerant.
Operating Characteristics
The capacity of the unit will meet or exceed _____Btuh at a suction temperature of _____ _F/_C. Thepower consumption at full load will not exceed _____kW.
Combination of the unit and the evaporator or fan coilunit will have a total net cooling capacity of _____Btuh or greater at conditions of _____ CFM enteringair temperature at the evaporator at _____ _F/_C wetbulb and _____ _F/_C dry bulb, and air entering theunit at ______F/_C.
The system will have a SEER of _____ Btuh/watt orgreater at DOE conditions.
Electrical Requirements
Nominal unit electrical characteristics will be _____ v,single phase, 60 hz. The unit will be capable ofsatisfactory operation within voltage limits of _____ vto _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Special Features
Refer to section of this literature identifying accessories
and descriptions for specific features and availableenhancements.
-
7/26/2019 Carrier 24ACC6
20/20
SYSTEM DESIGN SUMMARY1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low--ambient operation accessory is 55_F (12.8_C).
3. Maximum outdoor operating air temperature is 125_F (51.7_C).
4. For reliable operation, unit should be level in all horizontal planes.
5. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult ResidentialPiping and Longline Guideline and Service Manual available from equipment distributor.
6. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubinglengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4mm).
7. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connectorprovided.
8. Do not apply capillary tube indoor coils to these units.
9. Factory--supplied filter drier must be installed.
Cop y rig h t 2 0 1 2 Carrie r Corp . S 7 3 1 0 W . M o r r i s S t . S I n d i a n a po l i s , I N 4 6 2 3 1 Catalog No: 24ACC6 ---4 PDE d i t i o n D a t e : 0 9 / 1 2
24ACC6