casali application manual eng

Upload: eric-tsai

Post on 26-Feb-2018

281 views

Category:

Documents


5 download

TRANSCRIPT

  • 7/25/2019 CASALI Application Manual Eng

    1/102

    a guidefor laying

    bituminous-polymermembranesfor roofing

    THE CASALI GUIDES

  • 7/25/2019 CASALI Application Manual Eng

    2/102

    2

  • 7/25/2019 CASALI Application Manual Eng

    3/102

    3

    A GUIDE FOR LAYING BITUMINOUS-POLYMER

    MEMBRANES FOR ROOFING

  • 7/25/2019 CASALI Application Manual Eng

    4/102

  • 7/25/2019 CASALI Application Manual Eng

    5/102

    5

    1. Introduction p. 72. The Casali Group p. 93. Technical terms - Glossary p. 134. Use of bituminous membranes - Application Procedures p. 15

    4.1 Reception p. 154.2 Handling and storage p. 154.3 Transport p. 164.4 Preparing the laying surface p. 16

    4.4.a Structures in r.c., floors in clay-cement mix or pre-compressed concrete p. 164.4.b Wooden structures p. 164.4.c Metal structures p. 164.4.d For all applications p. 17

    4.5 Laying procedure for polymer- bituminous membranes4.5.1 Hot laying procedure p. 17- Loose laid- Partially bonded- Fully bonded

    4.5.2 Cold laying procedure p. 18- Self-adhesive membranes- Membranes applied with bituminous glue4.5.3 Mechanical fixing p. 184.6 Basic laying rules p. 184.7 Different types of protection for waterproofing coverings p. 19- Heavy protection- Light protection- Self-protection

    5. The most frequently used coverings p. 216. Typical solutions - specifications p. 25

    - flat roofing p. 27

    - sloping coverings p. 297. Solutions for difficult applications p. 81

    A Structural joints p. 82B Vertical joints p. 84C Breather vents p. 87D Drain traps p. 93E Gutters p. 95

    9. Practical application of lab tests p. 10410. Notes p. 109

    CONTENTS

  • 7/25/2019 CASALI Application Manual Eng

    6/102

    6

    Project developed by the Casali S.p.A Technical Office

    Created and coordinated by:Antoine Melhem, Technical Office Manager

    With the collaboration of:Giorgio Antonini, Sales ManagerMarco Compagnucci, Laboratory & QS Manager

    Mauro Moreschi,Marketing Manager

    All rights reserved

  • 7/25/2019 CASALI Application Manual Eng

    7/102

    7

    1. INTRODUCTION

    The Technical Office of Casali S.p.A., an Italian leading Company with many years of experience in the production of materials and solutions

    for waterproofing problems, has developed this Guide as a quick reference for designers and operators to some of the roofing problems most

    commonly encountered in the field.

    In view of the vast range of waterproofing problems in the roofing sector it is obviously not possible to deal with them all.This Guide approa-

    ches some of the more common waterproofing situations.

    The Casali Servicing Department offers customers an efficient service and is ready to find tailor-made solutions to specific roofing problems.

    We hope that this Guide will be helpful to all those who deal with waterproofing problems in the field of roofing day after day.

    Casali S.p.A.welcomes any suggestions you may have to improve this Guide which has been created to ensure a service of increasingly high quality.

  • 7/25/2019 CASALI Application Manual Eng

    8/102

    CASALI, Certified Quality

    all over the world

    ITALY - AUSTRIA - BULGARIA

    BOSNIA-HERZEGOVINA - CROATIA

    CHILE - CYPRUS - COLUMBIA - CUBA

    EGYPT - ESTONIA - GERMANY - GREECE

    HOLLAND - IRELAND - LATVIA - LEBANON

    LITHUANIA - MALTA - NIGERIA - POLAND

    PORTO RICO - CZECH REPUBLIC - ROMANIA

    UNITED KINGDOM - RUSSIA - SLOVENIA

    SINGAPORE - SLOVAK REPUBLIC

    SOUTH AFRICA - SWEDEN - SPAINSWITZERLAND - TAIWAN - TURKEY

    UNITED ARAB EMIRATES

  • 7/25/2019 CASALI Application Manual Eng

    9/102

    Casali S.p.A. has been dealing in the field of waterproofing for the building trade

    since 1936.

    The company started off with rolled bituminous paper felt products but in 1976

    turned to the production of torched-on bituminous-polymer prefabricated mem-

    branes, an all-Italian invention that in very little time was to be used all over theworld and today still represents the ideal solution for the most common applica-

    tions such as flat and sloped roofing, bridges and viaducts, below ground applica-

    tions and roof gardens.

    Close liaison with customers and tailor-made solutions to their specific require-

    ments are the cornerstones of Casali's philosophy;strict testing, efficiency and qua-

    lity are its strong points. In an endeavour to meet these requirements and changing

    market needs,Casali keeps ahead of the times with targeted products and services.

    In 1992 the Membrane Division (with over 400 different types of prefabricated

    membranes) was extended with the introduced of the Synthetics Division for the

    2. THE CASALI GROUP

    9

  • 7/25/2019 CASALI Application Manual Eng

    10/102

    10

    production of liquid waterproofing and paints (supplementary or

    optional to traditional membranes), treatments and consolidating

    products for the building trade, special industrial and sports flooring

    and coverings.

    The family of Casali products continued to increased over the years,and in 1995 the Company acquired the French Brand MANTOLAMI-

    NA, well-known for its high quality and featuring a copper or alumi-nium lamina finish that provides a total barrier against exposure to UVrays, evaporation of plasticizing oils etc. as well as a beautiful finish.

    Casali has more than thirty years of experience oninternational markets.Thanks to partnerships crea-ted for product distribution and marketing, theCompany is present in many countries all over theworld.Casali S.p.A. is located in Italy.Thanks to its efficient

    organisation the Company offers excellent leadtimes and prices for projects and products alike.The two production facilities on an area of 23.000sq.m. (9.500 sq.m. under roofing) are a stone'sthrow from Ancona Airport and just a few kilome-tres from Falconara Marittima Railway Station andthe Ancona Sea Port.

    The experience acquired by Casali S.p.A. onworld markets and products and the introductionof innovative production systems, allow theCompany to provide tailor-made solutions to

    specific roofing problems as well as reliable andconstant quality which is guaranteed by a strict,

    round-the-clock monitoring system. In 1996 Casali's QualitySystem was awarded UNI EN ISO 9001 certification.

    Much of the company's success on the domestic and foreignmarkets is however also due to the enormous resources investedby Casali in R&D that have allowed the company to keep one stepahead of developments in production techniques, waterproofingproducts and the building trade developing its know-how to impro-

    ve the quality standard of processes and products. Highly qualifiedstaff and labs equipped with the most modern and sophisticatedequipment bear witness to all this.

  • 7/25/2019 CASALI Application Manual Eng

    11/102

    Below: Divine Love Sanctuary - Rome (Italy)

    1 - Romanina Shopping Centre - Rome (Italy)

    2 - Ulster Bank - Ireland3 - FIAT - Italy

    4 - Casaforte - Italy

    5 - Ritter - Germany6 - Chicco Artsana - Italy

    Casali, that can today truly call itself aGroup, represents the ideal combinationbetween research,design, product and ser-vice providing solutions to traditionalrequirements as well as to all the newestmarket needs.

    11

  • 7/25/2019 CASALI Application Manual Eng

    12/102

  • 7/25/2019 CASALI Application Manual Eng

    13/10213

    3. TECHNICAL TERMS - GLOSSARY

    This section provides the definition of some the technical terms used in this Guide.These terms, which are often used by operators in the sector, are also used in technical specification, directives and test descriptions.

    Cover ing A technological unit that contributes to realizing a specific ambient and use beneath itself with respect to external ambient and use.

    Drainage layer

    Directs the flow of runoff water in covering systems. Generally consists of suitably sized washed gravel.

    F i l t er ing Layer

    Holds back dusty material without impeding the runoff of rainwater.

    Laying surface

    Suitably prepared surface on which the covering components are applied.

    Pr iming layer

    Layer used to promote adhesion between the laying surface and the components applied on the same, generally by means of a bituminous

    primer applied by roller or brush.

    Protect ion layer

    Protects the covering from physical, chemical and mechanical stress. Protection layers may be light or heavyweight or self-protecting accor-

    ding to the intended use.

    Root stop layerProtects underlayers from the penetrating action of roots on roof garden coverings. Generally consists of a special bituminous membranecontaining a compound treated with chemical root stop additives.

    Slope layer

    A layer normally realised in hollow cement that gives the covering a minimum incline for the runoff of rainwater.

  • 7/25/2019 CASALI Application Manual Eng

    14/10214

    St i f fen ing Layer

    Uniformly shares the loads concentrated on the layers below.Generally consisting of a reinforced concrete slab with electrically welded square metal meshhaving a thickness of 4 cm.

    Suppo r t i ng e l emen t

    Element having the function of supporting permanent loads and overloads on the covering.The supporting element may be realised in reinforced concre-te, pre-compressed concrete, clay-cement mixes, metal, wood etc.

    Thermo- insu la t ing mater ia l

    Material applied to ensure a particular thermal resistance to the covering as a whole.

    Vapour bar r ier layer

    Impedes the passage of water vapour in the covering system.Generally, a bituminous membrane reinforced with aluminium lamina is used.

    Vapour d ispers ion layer

    This layer allows water vapour to transpire preventing pressure build-up under the waterproofing layer. Generally applied under the vapour barrier with abreather vent between the two layers.

    Vent i la t ion layer Helps to regulate temperature and humidity levels, through air exchange.

    Waterproofing e lem ent

    Element used to waterproof the covering from rainwater.The waterproofing element may be realised in many different ways, the most common of whichis by means of a double layer of bituminous membrane.

    Water runof f e lements

    Any element used to direct the flow and drainage of rainwater such as drainage traps, gutters and rain water pipes.

  • 7/25/2019 CASALI Application Manual Eng

    15/10215

    4. USE OF BITUMINOUS MEMBRANES - APPLICATION PROCEDURE

    This section provides useful suggestions on how to use the waterproofing membranes produced by CASALI S.p.A.Applying a bituminous membrane is simple but certain rules must be followed to ensure that the material is used correctly. In order to ensure state-of-the-art results remember that the waterproofing membrane should be applied only by skilled staff in accordance with the proper laying procedures, taking all

    the necessary precautions to prevent damage during transport - handling and storage.

    4.1) RECEPTION

    When checking the material on arrival to ensure that the description on the Delivery Document complies with the material requested, it may be useful touse the "fiscal" alphanumerical code shown on the invoice together with the description of the product.When reporting non conforming material, pleaseremember to indicate the data shown on the label on the pallet and/or the number on the roll.This is the only way for customers to ensure a quick andaccurate response.

    4.2) HANDLING AND STORAGE

    When stored for a lengthy period of time, the membrane must be protected from bad weather conditions, sunlight and excessively low temperatures.Remember that heavy blows, even on smooth surfaces, may cause tearing, cracking and bending that may compromise the waterproofing efficiency of the

    membrane.The lower the temperature, the higher this risk will become.

    Pallets should be stacked with care. Black membranes (separated by a rigid plane in order to share the load) must not be stacked by more than two levels.Slated membranes and self-protected mwmbranes with metal lamina must not be stacked at all.

    Materials in stock should be continuously rotated bearing in mind that materials delivered for example in January are designed for application at the weatherconditions experienced during that period.This property of the materials becomes a disadvantage if used for example in July. In addition to the above, anextra word of warning goes to the slated membranes where different lots may have different shades of the same colour.

    Never wind a rope around the middle of the roll when lifting or moving since the rope may bend or fold the roll. For handling purposes, lift or move thepallet on which the rolls are packaged, removing only the material required for the application.This considerably facilitates operations and work at the site.

    If the pallets of membranes are kept in the sun, even for short periods of time, remember to slit the shrink wrapping along the length of the roll at several

    points to allow air circulation and prevent hothouse effect overheating of the membrane that might damage the characteristics of the material or blackenthe talc and/or slate.

  • 7/25/2019 CASALI Application Manual Eng

    16/102

    16

    4.3) TRANSPORT

    During transport, ensure that the pallets are well secured using suitably padded angle bars to impede marks on the rolls. Protect the pallets from tearing,

    cuts and heavy impact, above all when temperatures are critical.

    4.4) PREPARING THE LAYING SURFACE

    4.4.a) Structures in reinforced concrete, clay-cement mix and pre-compressed concrete

    - Remove gravel,sand and other matter that might damage the waterproofing membrane or reduce adherence, levelling holes with cement mortar.- In winter ensure that the laying surface has cured properly, that no ice is present and that the laying surface is clean and dry. Do not apply the product

    when temperatures are below 5C.

    - If the laying surface does not have an incline of at least 2-4%, lay a sloped layer in cement mortar to ensure water runoff of rainwater.

    - Apply by brush or roller a 300 ml/sq.m.coat of DERMAPRIMER along the perimeter and on special points as well as on the adhesion surface of the next

    layer.When the primer is dry, start laying the membrane.

    4.4.b) Wooden structures

    - Apply by brush or roller a 300 ml/sq.m.coat of DERMAPRIMER on all the embossments.When the primer is dry, start laying the membrane.

    - Dry lay a polyester reinforced membrane on the wooden laying surface, orthogonal to the incline, securing the membrane with wide-head nails spaced

    at 33 cm in staggered lines.

    P.S.When overlapping the covering in areas exposed to strong winds, we suggest reinforcing the nails by applying a 300 ml/sq.m. coating of ECOMASTIC

    to ensure full adhesion of the separation layer, before laying.

    4.4.c)Metal structures

    - Ensure that the laying surface has no rough areas that might damage the membrane.

    - Apply by brush or roller a 200 ml/sq.m.coat of DERMAPRIMER along the perimeter and on special points as well as on the adhesion surface of the next

    layer.When the primer is dry, start laying the membrane.

    - Along the line where corrugated plate sheets overlap, lay a strip of elastomeric bituminous membrane at least 50 cm wide torching along one edge and

    leaving the other side free, before applying the next layer so as to impede from tearing due to contact with the edge and the nails on the sheets.4.4.d) For all applications

    - Proper design of the covering must include a temperature and humidity study of the system according to the climatic conditions and intended use; the choi-ce and dimensions of the insulation must be decided according to the results of this study following the application of a polyester reinforced vapour barrierUNDERLAY or an aluminium reinforced + overlay mat vapour barrier VAPOREX, applied as per the procedure described in order to prevent the formationof condensate on the concave surfaces of the covering and/or in the system itself.

  • 7/25/2019 CASALI Application Manual Eng

    17/102

    17

    4.5 LAYING PROCEDURE FOR POLYMER - BITUMINOUS MEMBRANES

    Bituminous membranes may be applied by hot or cold laying procedures.

    4.5.1) HOT LAYING PROCEDURE

    The hot laying procedure consists of torching on the membrane by means of a propane gas blowpipe.The choice of the laying procedure depends on the

    characteristics of the laying surface, the incline of the covering and its intended use.

    There are three different types of hot laying procedures:

    Loose laid

    Partialy bonded

    Fully bonded

    Loose laid

    This procedure consists of simply resting the membrane on the laying surfacing and then fully bonding the longitudinal and head

    joints, the perimeters, the vertical embossments, the areas close to the joints and drainage etc.The second layer is always fully bonded onto the first layer,

    with the sheets staggered sideways by 50 cm and longitudinally by a half roll.

    This procedure is used for flat coverings or those with an incline of less than 5% and in particular when the supporting structure is subject to differential

    movements that might damage the waterproofing element.The stability of the covering is ensured by heavy protection such as ballasting with gravel, cement

    blocks, cement slabs etc.

    Partialy bonded

    This procedure is used when the waterproofing element is the finishing or top layer, and it is necessary to provide ventilation and vapour pressure control

    on the covering. It is extremely important to calculate the wind pulling resistance of the fixing elements accurately. Uniform spot bonding

    may be ensured by using a membrane such as GRUVER with holes, suited to the waterproofing element, that guarantees a uniform density of the fixing

    points over the entire surface; this laying system may be used for laying surfaces with inclines of up to 30%.

    For major inclines, a membrane with holes should not be used and the surface bonded to the laying surface must be at least 50% of the total surface area.

    The compound is torched on by means of a propane gas blowpipe on parts of the under surface covered with the polyethylene film.

    Even in the case of partial bonding, the perimeter areas, the vertical embossments and critical points must be fully bonded.

    The second layer is fully bonded on to the first layer with sheets staggered sideways by 50 cm and longitudinally by half a roll.

  • 7/25/2019 CASALI Application Manual Eng

    18/102

    18

    Fully bonded

    This procedure consists of bonding the membrane to the laying surface including the lateral and head joints, the perimeter areas, the verticalembossments, the areas around the joints, drainage etc.The second layer is always fully bonded to the first layer, with the sheets staggered sideways by 50cm and longitudinally by a half roll.This laying procedure is used for coverings with rigid supporting elements (clay-cement and reinforced concrete floors), with coverings inclined by morethan 40%, in applications where the waterproofing element is visible and to guarantee the stability of the covering against wind action and that of the ver-tical walls. In this case, use of a polyester reinforced waterproofing membrane with suitable tear resistance characteristics, is recommended. Flame resistantinsulation should be used.

    4.5.2 COLD LAYING PROCEDURE

    Cold laying procedures are used above all when bonding is not possible but also on metal laying surfaces which are easy to nail or when the membrane islaid on flame-sensitive insulation.These are clean systems that do however require highly skilled labour in that there is very little room for error, above allin the case of single-layer applications.The most commonly used procedures are as follows:a) Self-adhesive membranesb) Membranes applied with bituminous glue

    a) Self-adhesive membranesThese are special membranes with a bottom self-adhesive layer generally protected by non-stick silicone paper which is removed before laying.

    b)Membranes applied with bituminous glue

    A layer of bituminous glue (generally solvent-based) is applied, on which the membrane is laid.

    4.5.3 MECHANICAL FIXING

    As mentioned previously, membranes are fixed mechanically above all in the case of wind exposure, vertical walls and when flame-sensitive materials areused (above all insulation).The membrane sheets are fixed to the laying surface with flat-head nails and washers.The fixing points are spaced evenly, depen-ding on the type of laying surface, and should be increased at special points and along the perimeters.The nails are fixed under the joint on the longitudi-nal and head overlaps.This system requires the use of membranes that are highly resistant to tearing and with high dimensional stability (laying membra-nes with polyester - fibre-glass thread reinforcement).

  • 7/25/2019 CASALI Application Manual Eng

    19/102

    19

    4.6 BASIC LAYING RULES

    - Check that the sheets are correctly aligned, unrolling them completely and positioning them.

    - In the case of flat coverings, always start at the drainage areas, while in the case of highly sloped coverings, the sheets may be placed parallel to the direc-

    tion of the slope.

    - The side joints must be at least 10 cm, while at the head joint should be approx. 15 cm.

    - Roll out half of the roll, then torch the under surface of the membrane, which generally is covered by a polyethylene film, with a propane gas blowpipe,

    softening the bituminous mass, and fixing first one half and then the other.

    - Pass a trowel or spatula over the overlaps, without reducing the thickness of the membrane or exposing the reinforcement.

    - The second layer must be fully bonded on to the first layer, staggering the side overlaps by 50 cm and the head overlaps by half a roll.

    4.7 DIFFERENT TYPES OF PROTECTION FOR WATERPROOFING COVERINGS

    There are three different types of protection for bituminous waterproofing membranes:

    - heavy protection

    - light protection

    - self-protection

    Heavy Protection

    Flat coverings (having slope of less than 5%) with loose laid waterproofing must be protected by any of the following heavy protections, according to inten-

    ded use:

    - Reinforced concrete cast with electrically welded metal mesh that distributes the loads, over a layer of sand of at least 2 cm.

    - Marble or tiled flooring in the case of treadable surfaces

    - Cement blocks placed on wide-based plastic support

    - Self-blocking elements or similar over a layer of sand

    - Bituminous conglomerate or asphalting for surfaces suitable for vehicle traffic

    - Green roof system for roof gardens

    - Ballasting consisting of 15 mm washed river gravel in layers of 4 - 8 cm depending on wind conditions

    For all the solutions proposed, we recommend laying a dividing layer between the waterproofing membrane and the overlying structure in high grammage

    polyester TNT (250-300 / sq.m.), bituminous paper felt or polyethylene film etc., according to the application requirements.

    Light protection

    This type of protection is used for black membranes using aluminium or copper based reflecting paints such as REFLEX AR,REFLEX MR or REFLEX Rame

    to prevent the natural ageing of bitumen caused by UV rays and to impede the "crocodile skin" phenomenon that appears on unprotected bitumen. This

    treatment is indispensable when thermal insulation is laid under the waterproofing element.

  • 7/25/2019 CASALI Application Manual Eng

    20/102

    20

    Remember that this type of protection requires maintenance every 3 - 5 years to restore the reflecting capacity of the paint that may be damaged by atmo-spheric agents, animal droppings etc.

    Self-protection

    This protection is applied during production by coating the upper surface with slate chips (e.g. slated DERMABIT 43170) or copper or aluminium covering(e.g. MANTOLAMINA Al, MANTOLAMINA Cu).

    The latter is recommended for non-treadable coverings and/or coverings with particular architectural structure (domes, complex shapes etc.) and gives avery attractive finish.

  • 7/25/2019 CASALI Application Manual Eng

    21/102

    21

    The following are the most frequently used coverings:- Non-insulated, non ventilated coverings- Non-insulated, ventilated coverings- Insulated, non ventilated coverings

    - Insulated, ventilated coverings- Hot roofing- Inverted roofing

    5.1) CRITERIA FOR IDENTIFYING APPROPRIATE SOLUTIONSCorrectly designing a covering system means taking into account all the parameters that affect the system as a whole.The "appropriate" solutions are givenbelow according to the geometry, access level and characteristics of the supporting element.

    5.1.a) GeometryFlat roofing: this class includes horizontal coverings with slope of less than 5%Sloped roofing: this class includes coverings with slope between 5 and 50%

    5.1.b) Access level

    Non-treadable roofing: coverings to which access is allowed only for maintenance of machinery or the waterproofing membraneTreadable roofing: coverings for pedestrian traffic, designed for pedestrian traffic loads of 400 kg/sq.m.Roofing suitable for traffic: coverings for light (2t per axis) traffic"Green roof": coverings for roof gardens on which a layer of soil is laid

    5.1.c) Characteristics of the supporting element

    Floors in clay-cement/r.c.: floors cast in situ in reinforced clay-cement, floors cast in reinforced concrete etc.Pre-compressed reinforced concrete: prefabricated elements with metal reinforcement subjected to prior tensile stress.These elements have a high tensile strength.

    Metal sheet plate: Galvanised corrugated sheet plate floors with different profiles.Wooden structures: trusses ,solid wood beams, planking, panelling etc.

    The following diagram provides a quick reference to the choice of the most appropriate solution described by the corresponding specification.

    5. THE MOST FREQUENTLY USED COVERINGS

  • 7/25/2019 CASALI Application Manual Eng

    22/102

  • 7/25/2019 CASALI Application Manual Eng

    23/102

  • 7/25/2019 CASALI Application Manual Eng

    24/102

    5 TIPICAL SOLUTIONS SPECIFICATIONS

  • 7/25/2019 CASALI Application Manual Eng

    25/102

    25

    Important Instructions!Please note that the typical solutions described are not the only solutions possible: for the same design, the choice of membrane depends on numerous fac-tors such as climatic conditions, temperature and humidity, budget etc. Remember that the materials indicated by the specifications may be changed accordingto specific project requirements.

    5. TIPICAL SOLUTIONS - SPECIFICATIONS

    This section develops the solutions described in the two previous diagrams showing the recommended layers for each system.

    The recommendations given in paragraph 4 on preparing the laying surface and laying the waterproofing membranes apply to all the specifications.

  • 7/25/2019 CASALI Application Manual Eng

    26/102

  • 7/25/2019 CASALI Application Manual Eng

    27/102

    FLAT ROOFING

    A1

  • 7/25/2019 CASALI Application Manual Eng

    28/102

    28

    Specifications

    Prepare the laying surface by applying a coating of oxidised additive and solventbased bituminous primer such as DERMAPRIMER with wet volume mass of:

    0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cup No. 3 at

    23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%, applying 200g/sq.m. by brush or roller.

    Lay an aluminium reinforced vapour barrier such as VAPOREX 2.2

    kg/.sq.m. (EN 1849-1), with longitudinal and transverse load at break of

    300B (EN 12311-1), maximum longitudinal and transverse elongation atbreak 3% (EN 12311-1), vapour resistance factor >200.000 (EN 1931).

    Fully bond on the underside of the membrane covered with polyethylene

    film by means of a propane gas blowpipe, making longitudinal joints of at

    least 10 cm and head joints of 15 cm,gluing it to the perimeter embossments

    at least 10 cm beyond the thickness of the thermal-acoustic insulation.

    Lay the thermal and/or acoustic insulation sheets with thickness and characte-

    ristics as per the design specifications and nail to the metal laying surface. Inthe case of wind exposure or slopes exceeding 20%, the first waterproofing

    membrane and overlaps must be nailed spacing the nails at 5 nails per sq.m.

    Dry lay a vapour dispersion layer such as GRUVER,with mass per unit area

    of 1.3 kg/sq.m., thickness 1.3 mm (EN 1849-1), flexibility at low temperatu-

    res -10C (EN 1109), 119 holes /sq.m..The membrane must be laid with over-

    laps of at least 10 cm.

    Position the double breather vents, for the elimination of excess water vapour,

    at the junction points of the thermal insulation.The breather vents must be

    positioned at an average of one per 25 sq.m., between the dispersion layer and

    the vapour barrier for the main element, while the second element must be

    inserted between the insulation and the double waterproofing layer.

    Lay a waterproofing membrane consisting of a distilled bituminous compound

    modified with APAO resins (Amorphe - Poly - Alpha-Olefine) such as DER-

    MABIT-EXTRA 4 mm,with mass per unit area of 4 kg/sq.m., (EN 1849-1), load

    at break, long. 800N, transverse 650N (EN 12311-1), maximum longitudinaland transverse elongation at break 45% (EN 12311-1), flexibility at low tem-

    peratures -25C (EN 1109), flexibility at low temperatures after thermal

    ageing in air (EN 1296) -20C. Fully bond on the underside of the membrane

    covered by polyethylene film by means of a propane gas blowpipe onto the

    flame resistant insulation, making a longitudinal joint of at least 10 cm and a

    head joint of at least 15 cm, closing them over, including the joint necks with

    the vertical walls that must rise at least 10 cm over the maximum water level

    when the covering is finished.

    Lay a second waterproofing membrane consisting of a distilled bituminous

    compound modified with APAO resins (Amorphe-poly-Alpha-Olefine)

    such as DERMABIT-EXTRA 4 mm, with mass per unit area of 4 kg/sq.m.,

    (EN 1849-1), load at break, long. 800N, transverse 650N (EN 12311-1),

    maximum longitudinal and transverse elongation at break 45% (EN 12311-1),

    flexibility at low temperatures -25C (EN 1109), flexibility at low temperatu-

    res after thermal ageing in air (EN 1296) -20C.The membrane must be fully

    bonded with sheets staggered by 50 cm with respect to the first layer, tor-

    ching the underside covered by polyethylene film by means of a propane gas

    blowpipe, and making a longitudinal joint of at least 10 cm and a head joint of

    at least 15 cm, closing them over, including the joint necks with the vertical

    walls that must rise at least 20 cm over the maximum water level when the

    covering is finished.

    Apply two coats of highly reflecting aluminium paint for bituminous membra-

    nes such as REFLEX AR, with wet volume mass: 0.94 kg/dm3;; dry volume

    residue; 39%; viscosity at 23C with FORD cup No.3; applying at least 0.130

    l/sq.m. per coating by brush or roller or compressed air.

    SUPPORTING STRUCTURE: CORRUGATED SHEET PLATE - FINISH: BLACK PAINTED MEMBRANE - NON TREADABLE-INSULATEDA1

  • 7/25/2019 CASALI Application Manual Eng

    29/102

    29

    A2 SUPPORTING STRUCTURE CORRUGATED SHEET PLATE FINISH SLATED MEMBRANE NON TREADABLE INSULATED

  • 7/25/2019 CASALI Application Manual Eng

    30/102

    30

    A2 SUPPORTING STRUCTURE: CORRUGATED SHEET PLATE - FINISH: SLATED MEMBRANE - NON TREADABLE-INSULATED

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with SBS copolymers (Styrene-Butadiene-Styrene) such as

    EXTENSA 40180 cpv., thickness 4 mm,with mass per unit area of 4 kg/sq.m.,(EN 1849-1), load at break, long. 850N, transverse 650N (EN 12311-1),maxi-mum longitudinal and transverse elongation at break 50% (EN 12311-1),flexibility at low temperatures -30C (EN 1109), flexibility at low tempera-tures after thermal ageing in air (EN 1296) -25C. Fully bond on the under-side of the membrane covered by polyethylene film by means of a propanegas blowpipe, onto the flame resistant insulation, making a longitudinal jointof at least 10 cm and a head joint of at least 15 cm,closing them over, inclu-ding the joint necks with the vertical walls that must rise at least 10 cm overthe maximum water level when the covering is finished.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with SBS copolymers (Styrene-Butadiene-Styrene) self-protected with slate chips of the colour selected, such as EXTENSA 45180polyester, with mass per unit area of 4.5 kg/sq.m.,(EN 1849-1), load at break,long. 850N, transverse 650N (EN 12311-1), maximum longitudinal and tran-sverse elongation at break 50C (EN 12311-1), flexibility at low temperatu-res -30C (EN 1109), flexibility at low temperatures after thermal ageing inair (EN 1296) -25C.The membrane must be fully bonded with sheets stag-gered by 50 cm with respect to the first layer, torching the underside cove-red by polyethylene film by means of a propane gas blowpipe and making alongitudinal joint of at least 10 cm and a head joint of at least 15 cm, closing

    them over, including the joint necks with the vertical walls that must rise atleast 20 cm over the maximum water level when the covering is finished.

    Apply a styrene-acrylic resin based transparent fixative in water emulsion,highly resistant to UV rays for the slate chips, such as DERMAFIX, with wetvolume mass: 1.3 kg/dm3; dry residue; 48%; spraying on a coating of at least

    Specifications

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cup

    No. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%applying 200 g/sq.m. by brush or roller.

    Lay an aluminium reinforced vapour barrier such as VAPOREX 2.2kg/.sq.m. (EN 1849-1), with longitudinal and transverse load at break of300B (EN 12311-1), maximum longitudinal and transverse elongation atbreak 3% (EN 12311-1), vapour resistance factor >200.000 (EN 1931).Fully bond on the underside of the membrane covered with polyethylenefilm by means of a propane gas blowpipe, making longitudinal joints of at least10 cm and head joints of 15 cm, gluing the membrane to the perimeterembossments at least 10 cm beyond the thickness of the thermal-acoustic

    insulation.Lay the thermal and/or acoustic insulation sheets with thickness and charac-teristics as per the design specifications and nail to the metal laying surface.In the case of wind exposure or slopes exceeding 20%, the first waterproo-fing membrane and overlaps must be nailed spacing the nails at 5 nails persq.m.

    Dry lay a vapour dispersion layer such as GRUVER,with mass per unit areaof 1.3 kg/sq.m., thickness 1.3 mm (EN 1849-1), flexibility at low temperatu-res -10C (EN 1109), 119 holes /sq.m.. The membrane must be laid withoverlaps of at least 10 cm.

    Position the double breather vents for the elimination of excess watervapour, at the junction points of the thermal insulation.The breather ventsmust be positioned at an average of one per 25 sq.m., between the disper-sion layer and the vapour barrier for the main element, while the secondelement must be inserted between the insulation and the double water-proofing layer.

  • 7/25/2019 CASALI Application Manual Eng

    31/102

    31

    A3 SUPPORTING STRUCTURE: CORRUGATED SHEET PLATE WITH FLOOR FINISH: SLATED MEMBRANE NON TREADABLE INSULATED

  • 7/25/2019 CASALI Application Manual Eng

    32/102

    32

    A3 SUPPORTING STRUCTURE: CORRUGATED SHEET PLATE WITH FLOOR - FINISH: SLATED MEMBRANE - NON TREADABLE-INSULATED

    Lay a second waterproofing membrane consisting of a distilled bitumi-nous compound modified with SBS copolymers (Styrene-Butadiene-Styrene) self-protected with slate chips of the colour selected, such as

    EXTENSA FIL 45200 polyester, with mass per unit area of 4.5 kg/sq.m., (EN1849-1), load at break, long. 650N,transverse 500N (EN 12311-1),maximumelongation at break long.40% and trans. 50% (EN 12311-1), flexibility at lowtemperatures -20C (EN 1109), flexibility at low temperatures after thermalageing in air (EN 1296) -10C. The membrane must be fully bonded withsheets staggered by 50 cm with respect to the first layer, torching the under-side covered by polyethylene film by means of a propane gas blowpipe, andmaking a longitudinal joint of at least 10 cm and a head joint of at least 15cm, closing them over, including the joint necks with the vertical walls thatmust rise at least 20 cm over the maximum water level when the coveringis finished.

    Apply a styrene-acrylic resin based transparent fixative in water emulsion,highly resistant to UV rays for the slate chips, such as DERMAFIX,with wetvolume mass: 1.3 kg/dm3; dry residue; 48%; spraying on a coating of at least300 g/sq.m. with or without air.

    Specifications

    Lay the r.c. concrete slab which will act as thermal insulation according tothe design specifications, then carry out the following steps:

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%applying 200 g/sq.m. by brush or roller.

    Dry lay a vapour dispersion layer such as GRUVER,with mass per unit areaof 1.3 kg/sq.m., thickness 1.3 mm (EN 1849-1), flexibility at low temperatu-res -10C (EN 1109), 119 holes /sq.m.. The membrane must be laid withoverlaps of at least 10 cm.

    Lay a waterproofing membrane consisting of a distilled bituminous compoundmodified with SBS copolymers (Styrene-Butadiene-Styrene) such as EXTENSAFIL 40200,thickness 4 mm,with mass per unit area of 4.4 kg/sq.m., (EN 1849-1),load at break, long. 650N, transverse 500N (EN 12311-1),maximum elongationat break,long. 40% and trans.50% (EN 12311-1), flexibility at low temperatu-res -20C (EN 1109), flexibility at low temperatures after thermal ageing inair (EN 1296) -10C. Fully bond on the underside of the membrane cove-red by polyethylene film by means of a propane gas blowpipe, onto thelaying surface previously prepared, making a longitudinal joint of at least 10cm and a head joint of at least 15 cm, closing them over, including the jointnecks with the vertical walls that must rise at least 10 cm over the maximum

    water level when the covering is finished. In the case of wind exposure orslopes exceeding 50%, the overlaps must also be nailed in, spacing the nailsat 5 nails per sq.m.

  • 7/25/2019 CASALI Application Manual Eng

    33/102

    33

    SUPPORTING STRUCTURE: R C /P R C /CLAY-CEMENT MIX - FINISH: SLATED MEMBRANE - NON TREADABLE - NON-INSULATEDA4

  • 7/25/2019 CASALI Application Manual Eng

    34/102

    34

    Specifications

    On the supporting structure, lay a concrete slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%applying 300 g/sq.m. by brush or roller.

    Dry lay a vapour dispersion layer such as GRUVER with mass per unit areaof 1.3 kg/sq.m., thickness 1.3 mm (EN 1849-1), flexibility at low temperature-10C (EN 1109), 119 holes/sq.m.Lay the membrane with overlaps of 10 cm.

    Lay a waterproofing membrane consisting of a distilled bituminous com-

    pound modified with plastomer polymers such as OLYMPIA, thickness 4 mm,polyester, with mass per unit area of 4 kg/sq.m., (EN 1849-1), load at break,long. 500N,trans. 400N (EN 12311-1), maximum elongation at break, long.35% and trans. 40% (EN 12311-1), flexibility at low temperatures -10C(EN 1109).When the bituminous primer is thoroughly dry, fully bond onthe underside of the membrane covered by polyethylene film by means of apropane gas blowpipe,onto the concrete slab previously prepared, making alongitudinal joint of at least 10 cm and a head joint of at least 15 cm, closingthem over, including the joint necks with the vertical walls that must rise atleast 10 cm over the maximum water level when the covering is finished.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with plastomer polymers, self-protected with slate chipsof the colour selected, such as OLYMPIA 45200r, with mass per unit area of4.5 kg/sq.m., (EN 1849-1), load at break, long. 500N, transverse 400N (EN12311-1), maximum elongation at break long.35% and trans.40% (EN 12311-1),flexibility at low temperatures -10C (EN 1109).The membrane must be fully

    bonded with sheets staggered by 50 cm with respect to the first layer, tor-ching the underside covered by polyethylene film by means of a propane gasblowpipe, overlapping the longitudinal joints by at least 10 cm and the head

    joints by least 15 cm, closing them over, including the joint necks with thevertical walls that must rise at least 20 cm over the maximum water levelwhen the covering is finished.

    Apply a styrene-acrylic resin based transparent fixative in water emulsion,highly resistant to UV rays for the slate chips, such as DERMAFIX,with wetvolume mass: 1.3 kg/dm3; dry residue; 48%; spraying on a coating of at least300 g/sq.m. with or without air.

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAYCEMENT MIX FINISH: SLATED MEMBRANE NON TREADABLE NON INSULATEDA4

  • 7/25/2019 CASALI Application Manual Eng

    35/102

    35

    A5 SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: BALLASTING WITH WASHED GRAVEL- NON TREADABLE - NON-INSULATED

  • 7/25/2019 CASALI Application Manual Eng

    36/102

    36

    A5

    covered by polyethylene film by means of a propane gas blowpipe, overlap-ping the longitudinal joints by at least 10 cm and the head joints by at least15 cm, closing them over, including the joint necks with the vertical walls

    that must rise at least 20 cm over the maximum water level when the cove-ring is finished.

    Apply a dividing layer in high grammage polyester TNT (250 - 300 g/sq.m.)

    Lay a 4-5 cm covering of 15 mm rounded washed river gravel.

    Specifications

    On the laying supporting structure, lay a concrete slab with a slope of 2-4%to ensure water runoff to the drainage.

    Prepare the laying surface along the perimeters and at the special points onthe covering and on the sections where the membrane is fully bonded, byapplying a coating of oxidised additive and solvent based bituminous primersuch as DERMAPRIMER with wet volume mass of: 0.98 kg/dm3 ; residue at450C: 0%; effusion time with FORD cup No. 3 at 23C:30 sec.;dry volumeresidue: 38%; dry mass residue: 40% applying 300 g/sq.m. by brush or roller.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as MULTIPLAST 40200 polye-ster, with mass per unit area of 4.4 kg/sq.m. ,thickness 4 mm, (EN 1849-1),load at break,long. 500N,trans. 400N (EN 12311-1),maximum elongation at

    break, long. 35% and trans. 40% (EN 12311-1), flexibility at low temperatures-10C (EN 1109).When the bituminous primer is thoroughly dry, torch theunderside of the membrane covered by polyethylene film by means of a pro-pane gas blowpipe, loose laying the membrane and making longitudinal over-laps of at least 10 cm and transverse overlaps of at least 15 cm, closing themover, including the joint necks with the vertical walls that must rise at least10 cm over the maximum water level when the covering is finished. Themembrane must be fully bonded along the perimeters and on the pointstreated previously.

    Lay a second waterproofing membrane consisting of a distilled bituminous

    compound modified with plastomer polymers such as MULIPLAST 40200polyester, with mass per unit area of 4.4 kg/sq.m., thickness 4 mm,(EN 1849-1),load at break, long. 500N, transverse 400N (EN 12311-1), maximum elonga-tion at break long. 35% and trans. 40% (EN 12311-1), flexibility at low tem-peratures -10C (EN 1109).The membrane must be fully bonded with sheetsstaggered by 50 cm with respect to the first layer, torching the underside

  • 7/25/2019 CASALI Application Manual Eng

    37/102

    37

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: SLATED MEMBRANE - NON TREADABLE - INSULATEDA6

  • 7/25/2019 CASALI Application Manual Eng

    38/102

    38

    Specifications

    On the supporting structure,lay a concrete slab with a slope of 2-4% to ensu-re water runoff to the drainage.

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volume massof: 0.98 kg/dm3 ;residue at 450C: 0%; effusion time with FORD cup No.3 at23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40% applying 300g/sq.m.by brush or roller.

    Dry lay a vapour dispersion layer such as GRUVER with mass per unit areaof 1.3 kg/sq.m., thickness 1.3 mm (EN 1849-1), flexibility at low temperature-10C (EN 1109), 119 holes/sq.m.Lay the membrane with overlaps of 10 cm.

    Install breather vents for the elimination of excess water vapour, at the junc-tion points of the thermal insulation.The breather vents must be positioned

    at an average of one per 25 sq.m., between the dispersion layer and the dou-ble waterproofing layer for the main element,while the second element mustbe inserted between the insulation and the double waterproofing layer.

    Lay a reinforced aluminium vapour barrier such as VAPOREX 2.2. kg/sq.m.with longitudinal and transversal load at break.300N (EN 12311-1),maximumlongitudinal and transverse elongation at break,3% (EN 12311-1),vapour resi-stance factor >200.000 (EN 1931).The underside of the membrane coveredwith polyethylene film must be partially bonded or spot bonded by means ofa propane gas blowpipe, onto the dispersion layer, making longitudinal jointsof at least 10 cm and head joints of 15 cm, including the joint necks with thevertical walls that must rise at least 10 cm over the maximum water level

    when the covering is finished.

    Lay the flame resistant thermal and/or acoustic insulation with thickness and cha-racteristics as per the design specifications.Dry lay a vapour dispersion layer such as GRUVER,with mass per unit area of 1.3kg/sq.m.,thickness 1.3 mm (EN 1849-1), flexibility at low temperatures -10C (EN1109),119 holes sq.m.The membrane must be laid with overlaps of at least 10 cm.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as POLTEX 40180 Polyester,with mass per unit area of 4 kg/sq.m, thickness 4 mm, (EN 1849-1), load at

    break, long. 750N,transverse 550N (EN 12311-1),maximum longitudinal andtransverse elongation at break 45% (EN 12311-1), flexibility at low tempera-tures -15C (EN 1109).The underside of the membrane covered by polyethy-lene film must be partially bonded or spot bonded by means of a propanegas blowpipe onto the dispersion layer,making a longitudinal joints of at least10 cm and head joints of at least 15 cm, closing them over, including the jointnecks with the vertical walls that must rise at least 20 cm over the maximumwater level when the covering is finished.The membrane must be fully bon-ded along the perimeter and at the special points.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with plastomer polymers, self-protected with slate chipsof the colour selected, such as POLTEX 45180 Polyester,, with mass per unitarea of 4.5 kg/sq.m., load at break,long. 750N,transverse 550N (EN 12311-1),maximum longitudinal and transverse elongation at break 45% (EN 12311-1),flexibility at low temperatures -15C (EN 1109).The membrane must be fullybonded with sheets staggered by 50 cm with respect to the first layer, tor-ching the underside covered by polyethylene film by means of a propane gasblowpipe, and overlapping the longitudinal joints by at least 10 cm and thetransverse joints by at least 15 cm, closing them over, including the jointnecks with the vertical walls that must rise at least 20 cm over the maximumwater level when the covering is finished.

    Apply a styrene-acrylic resin based transparent fixative in water emulsion,highly resistant to UV rays for the slate chips, such as DERMAFIX,with wetvolume mass: 1.3 kg/dm3; dry residue; 48%; spraying on a coating of at least300 g/sq.m. with or without air.

  • 7/25/2019 CASALI Application Manual Eng

    39/102

    39

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: WASHED GRAVEL - NON TREADABLE - INSULATEDA7

  • 7/25/2019 CASALI Application Manual Eng

    40/102

    Specifications

    On the supporting structure, lay a concrete slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface along the perimeters and special points on thecovering and at the points where the membrane is fully bonded, by applyinga coating of oxidised additive and solvent based bituminous primer such asDERMAPRIMER with wet volume mass of: 0.98 kg/dm3 ; residue at 450C:0%; effusion time with FORD cup No.3 at 23C: 30 sec.; dry volume residue:38%; dry mass residue: 40% applying 300 g/sq.m. by brush or roller.

    Install breather vents for the elimination of excess water vapour, at the junc-tion points of the thermal insulation.The breather vents must be positionedat an average of one per 25 sq.m. under the vapour barrier layer.

    Lay a reinforced aluminium vapour barrier such as VAPOREX 2.2.kg/sq.m. (EN 1849-1), with longitudinal and transversal load at break.300N (EN 12311-1), maximum longitudinal and transverse elongation atbreak, 3% (EN 12311-1), vapour resistance factor >200.000 (EN 1931).The membrane are loose laid making longitudinal joints of at least 10 cmand head joints of at least 15 cm, closing them over, gluing the membraneover the perimeter embossments by at least 10 cm above the thickness ofthe thermal-acoustic insulation, and torching the underside covered bypolyethylene film by means of a propane gas blowpipe.The membrane mustbe fully bonded along the perimeters and on the special points previouslytreated.

    Lay the flame resistant thermal and/or acoustic insulation with thickness andcharacteristics as per the design specifications for application of the mem-brane.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as DERMAFIL 40200 SP CPV,with mass per unit area of 4.4 kg/sq.m,thickness 4 mm, (EN 1849-1), load at

    break, long. 650N, transverse 450N (EN 12311-1), maximum elongation atbreak long. 40% and trans. 45%(EN 12311-1), flexibility at low temperatu-res -10C (EN 1109).The membrane is loose laid, torching the undersidecovered by polyethylene film by means of a propane gas blowpipe makinglongitudinal joints of at least 10 cm and head joints of at least 15, torchingthe underside covered by polyethylene film by means of a propane gas blow-pipe, closing them over, including the joint necks with the vertical walls thatmust rise at least 20 cm over the maximum water level when the coveringis finished. The membrane must be fully bonded along the perimeter and atthe special points.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with plastomer polymers such as DERMAFIL 40200 SP,polyester, with mass per unit area of 4.4 kg/sq.m,thickness 4 mm, (EN 1849-1),load at break, long.700N, transverse 550N (EN 12311-1),maximum longitu-dinal and transverse elongation at break 45% (EN 12311-1), flexibility at lowtemperatures -10C (EN 1109).The membrane must be fully bonded withsheets staggered by 50 cm with respect to the first layer, torching the under-side covered by polyethylene film by means of a propane gas blowpipe,making longitudinal overlaps of at least 10 cm and head overlaps of at least15 cm, torching the underside covered by polyethylene film by means of apropane gas blowpipe, closing them over, including the joint necks with the

    vertical walls that must rise at least 20 cm over the maximum water levelwhen the covering is finished.

    Apply a dividing layer in high grammage polyester TNT (250 - 300 g/sq.m.)

    Lay a 4-5 cm covering of 15mm rounded washed river gravel.

  • 7/25/2019 CASALI Application Manual Eng

    41/102

    41

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: SQUARE R.C. BLOCKS - NON TREADABLE - NON-INSULATEDA8

  • 7/25/2019 CASALI Application Manual Eng

    42/102

    42

    Specifications

    On the supporting structure, lay a concrete slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface along the perimeters and special points on thecovering and at the points where the membrane is fully bonded, by applyinga coating of oxidised additive and solvent based bituminous primer such asDERMAPRIMER with wet volume mass of: 0.98 kg/dm3; residue at 450C:0%; effusion time with FORD cup No.3 at 23C: 30 sec.; dry volume residue:38%; dry mass residue: 40% applying 300 g/sq.m. by brush or roller.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as DERMAFLEX 30160 CPV,with mass per unit area of 3 kg/sq.m, thickness 3 mm, (EN 1849-1), load atbreak, long. 700N, transverse 500N (EN 12311-1),maximum longitudinal and

    transverse elongation at break 45% (EN 12311-1), flexibility at low tempe-ratures -15C (EN 1109).The membrane is loose laid, torching the undersi-de covered by polyethylene film by means of a propane gas blowpipe andmaking longitudinal joints of at least 10 cm and head joints of at least 15, tor-ching the underside covered by polyethylene film by means of a propane gasblowpipe, closing them over, including the joint necks with the vertical wallsthat must rise at least 10 cm over the maximum water level when the cove-ring is finished. The membrane must be fully bonded along the perimeter andat the special points.

    Lay a second waterproofing membrane consisting of a distilled bituminous

    compound modified with plastomer polymers such as DERMAFLEX 40180polyester, with mass per unit area of 4 kg/sq.m, thickness 4 mm,(EN 1849-1),load at break, long. 900N, transverse 700N (EN 12311-1), maximum longitu-dinal and transverse elongation at break 50% (EN 12311-1), flexibility at lowtemperatures -15C (EN 1109).The membrane must be fully bonded withsheets staggered by 50 cm with respect to the first layer, torching the under-

    side covered by polyethylene film by means of a propane gas blowpipe,making longitudinal overlaps of at least 10 cm and head overlaps of at least15 cm, closing them over, including the joint necks with the vertical walls

    that must rise at least 20 cm over the maximum water level when the cove-ring is finished.

    Apply a dividing layer in high grammage polyester TNT (250 - 300 g/sq.m.)

    Lay the flooring consisting of cmxcm r.c.concrete blocks. Place theflooring on wide-base plastic supports.

  • 7/25/2019 CASALI Application Manual Eng

    43/102

    43

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: CONRETE SLAB CAST IN SITU - NON TREADABLE - NON-INSULATEDA9

  • 7/25/2019 CASALI Application Manual Eng

    44/102

    44

    Specifications

    On the supporting structure, lay a concrete slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%applying 200 g/sq.m. by brush or roller.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with APAO resins (Amorphe - Poly - Alpha-Olefine) such asDERMABIT 4170, polyester, thickness 4 mm, with mass per unit area of 4kg/sq.m, (EN 1849-1), load at break, long. 800N,transverse 650N (EN 12311-1),maximum longitudinal and transverse elongation at break 45% (EN 12311-1),

    flexibility at low temperatures -20C (EN 1109), recognised by ITC No.617/03 Technical Agreement. Fully bond on the underside covered bypolyethylene film by means of a propane gas blowpipe, onto the laying surfa-ce prepared previously, with longitudinal overlaps of at least 10 cm and headoverlaps of at least 15, closing them over, including the joint necks with thevertical walls that must rise at least 10 cm over the maximum water levelwhen the covering is finished.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with APAO resins (Amorphe - Poly - Alpha-Olefine)such as DERMABIT 4170, polyester, thickness 4 mm, with mass per unit

    area of 4 kg/sq.m, (EN 1849-1), load at break, long. 800N, transverse 650N(EN 12311-1), maximum longitudinal and transverse elongation at break45% (EN 12311-1), flexibility at low temperatures -20C (EN 1109), reco-gnised by ITC No. 617/03 Technical Agreement. The membrane must be fullybonded with sheets staggered by 50 cm with respect to the first layer, tor-ching the underside covered by polyethylene film by means of a propane gas

    blowpipe, and making longitudinal joints of at least 10 cm and head joints ofat least 15 cm, closing them over, including the joint necks with the verticalwalls that must rise at least 20 cm over the maximum water level when the

    covering is finished.

    Apply a protecting and creep layer in high grammage polyester TNT (250 -300 g/sq.m.)

    Cast a concrete floor in situ reinforced with 4 cm, 15x 5 cm square meshelectrically welded with 6 mm reinforcing rods.

  • 7/25/2019 CASALI Application Manual Eng

    45/102

    45

    A10 SUPPORTING STRUCTURE: R.C./P.R.C./CLAY - FINISH: SQUARE CONCRETE BLOCKS - NON TREADABLE - INSULATED (HOT ROOF)

  • 7/25/2019 CASALI Application Manual Eng

    46/102

    46

    underside covered by polyethylene film by means of a propane gas blowpi-pe and making longitudinal joints of at least 10 cm and head joints of at least15, closing them over, including the joint necks with the vertical walls that

    must rise at least 10 cm over the maximum water level when the coveringis finished. The membrane must be fully bonded along the perimeter and atthe special points.

    Lay a second waterproofing membrane consisting of a distilled bitumi-nous compound modified with plastomer polymers such as EXTENSA40180 CPV polyester,with mass per unit area of 4 kg/sq.m, thickness 4 mm,(EN 1849-1), load at break, long. 850N, transverse 650N (EN 12311-1),maximum longitudinal and transverse elongation at break 50% (EN12311-1), flexibility at low temperatures -30C (EN 1109).The membranemust be fully bonded with sheets staggered by 50 cm with respect to the

    first layer, torching the underside covered by polyethylene film by means ofa propane gas blowpipe, making longitudinal overlaps of at least 10 cm andhead overlaps of at least 15 cm, closing them over, including the joint neckswith the vertical walls that must rise at least 20 cm over the maximumwater level when the covering is finished.

    Apply a dry laid dividing layer in high grammage polyester TNT (250 - 300g/sq.m.)

    Lay the flooring consisting of cmxcm square concrete blocks, placingthe flooring on wide-base plastic supports.

    Specifications

    On the supporting structure, lay a concrete slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface along the perimeters and special points on thecovering and at the points where the membrane is fully bonded, by applyinga coating of oxidised additive and solvent based bituminous primer such asDERMAPRIMER with wet volume mass of: 0.98 kg/dm3 ; residue at 450C:0%; effusion time with FORD cup No.3 at 23C: 30 sec.; dry volume residue:38%; dry mass residue: 40% applying 300 g/sq.m. by brush or roller.

    Lay a reinforced aluminium vapour barrier such as VAPOREX 2.2. kg/sq.m.(EN 1849-1), with longitudinal and transversal load at break. 300N (EN12311-1), maximum longitudinal and transverse elongation at break, 3%(EN 12311-1), vapour resistance factor >200.000 (EN 1931).The mem-

    brane is loose laid making longitudinal joints of at least 10 cm and headjoints of at least 15 cm, closing them over, gluing the membrane over theperimeter embossments by at least 10 cm above the thickness of the ther-mal - acoustic insulation, and torching the underside covered by polyethyle-ne film by means of a propane gas blowpipe. The membrane must be fullybonded along the perimeters and on the special points previously treated.

    Lay the flame resistant thermal and/or acoustic insulation with thickness andcharacteristics as per the design specifications for application of the mem-brane.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as EXTENSA-FIL 30200 spcpv polyester,, with mass per unit area of 3.3 kg/sq.m, thickness 3 mm, (EN1849-1), load at break, long. 650N, transverse 500N (EN 12311-1),maximumelongation at break long. 40% and trans. 50%(EN 12311-1), flexibility at lowtemperatures -20C (EN 1109). The membrane is loose laid, torching the

  • 7/25/2019 CASALI Application Manual Eng

    47/102

    47

    A11 SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: SQUARE CONCRETE BLOCKS - TREADABLE - INVERTED ROOF

  • 7/25/2019 CASALI Application Manual Eng

    48/102

    longitudinal overlaps of at least 10 cm and head overlaps of at least 15 cm,closing them over, including the joint necks with the vertical walls that mustrise at least 20 cm over the maximum water level when the covering is fini-

    shed.

    Lay the flame resistant thermal and/or acoustic insulation with thickness andcharacteristics as per the design specifications.

    Apply a dividing layer in high grammage polyester TNT (250 - 300 g/sq.m.)to protect the insulation.

    Lay the flooring consisting of . cmxcm square concrete blocks, pla-cing the flooring over wide-base plastic supports.

    Specifications

    On the supporting structure, lay a concrete slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface along the perimeters and special points on thecovering and at the points where the membrane is fully bonded, by applyinga coating of oxidised additive and solvent based bituminous primer such asDERMAPRIMER with wet volume mass of: 0.98 kg/dm3 ; residue at 450C:0%; effusion time with FORD cup No.3 at 23C: 30 sec.; dry volume residue:38%; dry mass residue: 40% applying 300 g/sq.m. by brush or roller.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as DERMAFIL 30200 SP, polye-ster, with mass per unit area of 3 kg/sq.m, thickness 3.3 mm,(EN 1849-1),loadat break, long. 700N, transverse 500N (EN 12311-1), maximum longitudinal

    and transverse elongation at break 45% (EN 12311-1), flexibility at low tem-peratures -10C (EN 1109).The membrane is loose laid, torching the under-side covered by polyethylene film by means of a propane gas blowpipe tomake longitudinal joints of at least 10 cm and head joints of at least 15, clo-sing them over, including the joint necks with the vertical walls that must riseat least 10 cm over the maximum water level when the covering is finished.The membrane must be fully bonded along the perimeter and at the specialpoints.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with polymers such as DERMAFIL 40200 SP polyester,with mass per unit area of 4.4 kg/sq.m, thickness 4 mm, (EN 1849-1), load atbreak, long. 700N, transverse 500N (EN 12311-1),maximum longitudinal andtransverse elongation at break 45% (EN 12311-1), flexibility at low tempera-tures -10C (EN 1109). The membrane must be fully bonded with sheetsstaggered by 50 cm with respect to the first layer, torching the undersidecovered by polyethylene film by means of a propane gas blowpipe, making

  • 7/25/2019 CASALI Application Manual Eng

    49/102

    49

    SUPPORTING STRUCTURE: R.C OR P.R.C - FINISH: R.C. FLOOR - SUITABLE FOR TRAFFIC - INSULATED (PARKING ROOF)A12

  • 7/25/2019 CASALI Application Manual Eng

    50/102

    over the maximum water level when the covering is finished.

    Lay the compression resistant thermal and/or acoustic insulation with thick-

    ness and characteristics as per the design specifications.

    Apply a dividing layer in high grammage polyester TNT >_ 500g/sq.m.).

    Lay a 2 cm layer of dry sand.

    Cast a concrete floor in situ reinforced with 4 cm, 15x 5 cm square meshelectrically welded with 6/8 mm reinforcing rods. Make longitudinal andtransverse joints >_ 2 cm at intervals of 5 m over the entire thickness of theflooring.

    Specifications

    On the supporting structure, lay a concrete slab reinforced with 15x15 cmsquare mesh electrically welded with 6/8 mm 5 cm rods, with a slope of2-4% in cement mortar to ensure water runoff to the drainage.

    Apply a dry laid dividing layer in high grammage polyester TNT >_ 300 g/sq.m.).

    Lay a waterproofing membrane consisting of a distilled bituminous compoundmodified with APAO resins (Amorphe - Poly - Alpha-Olefine) such as DER-MABIT 4170,polyester, thickness 4 mm, with mass per unit area of 4 kg/sq.m,(EN 1849-1), load at break, long. 800N, transverse 650N (EN 12311-1), maxi-mum longitudinal and transverse elongation at break 45% (EN 12311-1), flexi-bility at low temperatures -20C (EN 1109), recognised by ITC No. 617/03Technical Agreement.The membrane is loose laid making longitudinal joints ofat least 10 cm and head joints of at least 15 cm, torching the underside cove-red by polyethylene film by means of a propane gas blowpipe and closingthem over; glue the membrane on to the perimeter embossments that mustrise at least 10 cm over the maximum water level when the covering is fini-shed.The membrane must be fully bonded along the perimeters and the spe-cial points previously treated.

    Lay a second waterproofing membrane consisting of a distilled bituminous com-pound modified APAO resins (Amorphe - Poly - Alpha-Olefine) such as DER-MABIT 4170 polyester, thickness, 4 mm, with mass per unit area of 4 kg/sq.m,(EN 1849-1), load at break, long. 800N, transverse 650N (EN 12311-1), maxi-mum longitudinal and transverse elongation at break 45% (EN 12311-1), flexi-bility at low temperatures -20C (EN 1109), recognised by ITC No. 617/03Technical Agreement.The membrane must be fully bonded with sheets stagge-red by 50 cm with respect to the first layer, torching the underside covered bypolyethylene film by means of a propane gas blowpipe, making longitudinal

    joints of at least 10 cm and head joints of at least 15 cm, closing them over,including the joint necks with the vertical walls that must rise at least 20 cm

  • 7/25/2019 CASALI Application Manual Eng

    51/102

    A13 SUPPORTING STRUCTURE: R.C OR P.R.C - FINISH: BITUMINOUS CONGLOMERATE - SUITABLE FOR TRAFFIC - NON-INSULATED

  • 7/25/2019 CASALI Application Manual Eng

    52/102

    52

    Specifications

    On the supporting structure, lay a cement mortar slab with a slope of 2-4%ensure water runoff to the drainage.

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%applying 300 g/sq.m. by brush or roller.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as DERMAFIL 50300 SP, withmass per unit area of 5.5 kg/sq.m, thickness 5 mm, (EN 1849-1), load atbreak, long. 1250N, transverse 1050N (EN 12311-1), maximum longitudinaland transverse elongation at break 50% (EN 12311-1), flexibility at low tem-peratures -10C (EN 1109). When the bituminous primer has cured, fullybond on the underside covered by polyethylene film by means of a propanegas blowpipe to glue the membrane onto the sloping slab prepared previou-sly, making longitudinal joints of at least 10 cm and head joints of at least 15cm, closing them over, including the joint necks with the vertical walls thatmust rise at least 10 cm over the maximum water level when the coveringis finished.

    Lay a 5-6 cm layer of bituminous conglomerate flooring consisting of closedcurve aggregate grading and sharp edged inert material. Compact immedia-tely to compress into the waterproofing.

  • 7/25/2019 CASALI Application Manual Eng

    53/102

    53

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: SOIL BED - ROOF GARDEN - NON-INSULATEDA14

  • 7/25/2019 CASALI Application Manual Eng

    54/102

    54

    Specifications

    On the supporting structure, lay a cement mortar slab with a slope of 2-4%to ensure water runoff to the drainage.

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%applying 300 g/sq.m. by brush or roller.

    Dry lay a vapour dispersion layer such as GRUVER with holes, having massper unit area of 1.3 kg/sq.m.,thickness 1.3 mm (EN 1849-1), flexibility at lowtemperatures -10C (EN 1109), 119 holes/sq.m.The membrane must be laidwith overlaps of at least 10 cm.

    Lay a waterproofing membrane consisting of a distilled bituminous com-pound modified with plastomer polymers such as DERMAFLEX 40180 polye-ster,, with mass per unit area of 4 kg/sq.m, thickness 4 mm, (EN 1849-1), loadat break, long. 900N, transverse 700N (EN 12311-1), maximum longitudinaland transverse elongation at break 50% (EN 12311-1), flexibility at low tem-peratures -15C (EN 1109). Glue on the membrane by partially bonding orspot bonding the underside covered by polyethylene film by means of a pro-pane gas blowpipe over the dispersion layer, making longitudinal joints of atleast 10 cm and head joints of at least 15, closing them over, including the

    joint necks with the vertical walls that must rise at least 10 cm over themaximum water level when the covering is finished. The membrane must befully bonded along the perimeter and at the special points.

    Lay a second waterproofing membrane consisting of a distilled bituminouscompound modified with root stop plastomer polymers such as ERADIX40200, with mass per unit area of 4 kg/sq.m, thickness 4 mm, (EN 1849-1),load at break, long. 900N, transverse 900N (EN 12311-1), maximum longitu-

    dinal and transverse elongation at break 50% (EN 12311-1), flexibility at lowtemperatures -15C (EN 1109). On 5/10/1998, the membrane was awardedcertification after successfully passing the German FLL root propagationtests under the strictest conditions provided by DIN 4062, lasting 4 years.The membrane must be fully bonded with sheets staggered by 50 cm withrespect to the first layer, torching the underside covered by polyethylenefilm by means of a propane gas blowpipe, and overlapping the longitudinal

    joints by least 20 cm, closing them over, including the joint necks with thevertical walls that must rise at least 20 cm over the maximum water levelwhen the covering is finished.

    Dry lay a dividing layer in high grammage polyester TNT (250 - 300 g/sq.m.).

    Lay a 6-8 cm drainage layer consisting of rounded river gravel.

    Dry lay a dividing layer in high grammage polyester TNT (250 - 300 g/sq.m.).

    Lay the soil bed prepared according to the design specifications.

  • 7/25/2019 CASALI Application Manual Eng

    55/102

    55

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: SOIL BED - ROOF GARDEN - INSULATEDA15

  • 7/25/2019 CASALI Application Manual Eng

    56/102

    56

    Specifications

    On the supporting structure, lay a cement mortar slab with a slope of 2-4% toensure water runoff to the drainage.

    Prepare the laying surface by applying a coating of oxidised additive and solvent

    based bituminous primer such as DERMAPRIMER with wet volume mass of:0.98kg/dm3 ; residue at 450C: 0%; effusion time with FORD cup No. 3 at 23C: 30sec.; dry volume residue: 38%; dry mass residue: 40% applying 300 g/sq.m. bybrush or roller.Dry lay a vapour dispersion layer such as GRUVER with holes,having mass perunit area of 1.3 kg/sq.m., thickness 1.3 mm (EN 1849-1), flexibility at low tem-peratures -10C (EN 1109), 119 holes/sq.m..The membrane must be laid withoverlaps of at least 10 cm leaving vertical embossments of at least 20 cm beyondthe depth of the soil bed.

    Lay an aluminium reinforced vapour barrier such as VAPOREX 2.2 kg/.sq.m. (EN

    1849-1), with longitudinal and transverse load at break of 300N (EN 12311-1),maximum longitudinal and transverse elongation at break 3% (EN 12311-1),vapour resistance factor >200.000 (EN 1931).Glue the membrane,by partial-ly bonding or spot bonding the underside covered with polyethylene film bymeans of a propane gas blowpipe over the vapour dispersion layer, making lon-gitudinal joints of at least 10 cm and gluing the membrane to the perimeterembossments by at least 20 cm.

    Lay the thermal and/or acoustic insulation with thickness and characteristics asper the design specifications

    Dry lay a vapour dispersion layer such as GRUVER, having mass per unit area of1.3 kg/sq.m.,thickness 1.3 mm (EN 1849-1),flexibility at low temperatures -10C(EN 1109),119 holes/sq.m..The membrane must be laid with overlaps of at least10 cm leaving vertical embossments of at least 20 cm beyond the depth of thesoil bed.Lay a waterproofing membrane consisting of a distilled bituminous compound

    modified with plastomer polymers such as DERMAFIL 30200 SP, with mass perunit area of 3.3 kg/sq.m, thickness 3 mm,(EN 1849-1), load at break,long. 700N,transverse 7500N (EN 12311-1),maximum longitudinal and transverse elonga-tion at break 45% (EN 12311-1), flexibility at low temperatures -10C (EN1109).Fully bond on the underside covered by polyethylene film by means of apropane gas blowpipe on the flame resistant self-protected insulation or lay adividing layer in heat resistant high grammage polyester 200-250 g/sq.m. TNT,making longitudinal joints of at least 10 cm, closing them over, including the jointnecks with the vertical walls. On the perimeter embossments, the membranemust be fully bonded by at least 20 cm beyond the depth of the soil bed.

    Lay a second waterproofing membrane consisting of a distilled bituminous com-pound modified with root stop plastomer polymers such as ERADIX 50200,with mass per unit area of 5 kg/sq.m,thickness 5 mm,(EN 1849-1),longitudinaland transverse load at break 800N (EN 12311-1), maximum longitudinal and

    transverse elongation at break 50% (EN 12311-1), flexibility at low temperatu-res -15C (EN 1109).On 5/10/1998, the membrane was awarded certificationafter successfully passing the German FLL root propagation tests under thestrictest conditions provided by DIN 4062, lasting 4 years.The membrane mustbe fully bonded with sheets staggered by 50 cm with respect to the first layer,torching the underside covered by polyethylene film by means of a propane gasblowpipe, overlapping the longitudinal joints by least 20 cm, closing them over,including the joint necks with the vertical walls.On the perimeter embossments,the membrane must be fully bonded by at least 20 cm beyond the depth of thesoil bed.

    Dry lay a dividing layer in high grammage polyester TNT (200-250g/sq.m.).

    Lay a 6-8 cm drainage layer consisting of rounded river gravel.

    Dry lay a dividing layer in high grammage polyester TNT (200-250 g/sq.m.).

    Lay the soil bed prepared according to the design specifications.

  • 7/25/2019 CASALI Application Manual Eng

    57/102

  • 7/25/2019 CASALI Application Manual Eng

    58/102

  • 7/25/2019 CASALI Application Manual Eng

    59/102

    SLOPED ROOFING

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: TILES ON SLATED COVERING (UNDERTILE) - SLOPED - INSULATEDB1

  • 7/25/2019 CASALI Application Manual Eng

    60/102

    60

    Specifications

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%

    applying 300 g/sq.m. by brush or roller.

    Install special breather vents for the elimination of excess water vapour, atthe junction points of the thermal insulation. The breather vents must bepositioned between the dispersion layer and the vapour barrier and chan-nelled into special ventilation tiles.

    Lay an aluminium reinforced vapour barrier such as VAPOREX 2.2kg/.sq.m. (EN 1849-1), with longitudinal and transverse load at break of300N (EN 12311-1), maximum longitudinal and transverse elongation atbreak 3% (EN 12311-1), vapour resistance factor >200.000 (EN 1931).

    Glue the membrane, by partially bonding (in strips) the underside coveredwith polyethylene film by means of a propane gas blowpipe, making longitu-dinal joints of at least 10 cm and head joints of 15 cm, including the jointnecks with the vertical walls that must rise by at least 10 cm over the thick-ness of the thermal - acoustic insulation.

    Lay the flame-resistant thermal and/or acoustic insulation sheets with thick-ness and characteristics as per the design specifications. Fix the sheets withoxidised bitumen and 4 nails per sheet; place wooden slats treated withDERMAPRIMER of the same thickness between the insulation sheets,nailingand sealing the wooden slats to the supporting structure.

    Lay a second waterproofing membrane parallel to the gutter line, consistingof a distilled bituminous compound modified with plastomer polymers self-protected by slate chips in the colour selected, such as DERMAFIL 45200CPV, with mass per unit area of 4.5 kg/sq.m., thickness 4 mm, (EN 1849-1),

    load at break, long. 650N, transverse 450N (EN 12311-1), maximum longi-tudinal and transverse elongation at break 45% (EN 12311-1), flexibility atlow temperatures -10C (EN 1109). Lay the membrane in on insulationsheet by fully bonding the underside covered by polyethylene film by means

    of a propane gas blowpipe, and making longitudinal overlaps of at least 10cm and head overlaps of at least 15 cm, closing them over. If necessary, nailthe sections where the membranes overlap,and seal perfectly.

    Lay the masonry or cement tiles on cement mortar seams, directly on theslated membrane.

  • 7/25/2019 CASALI Application Manual Eng

    61/102

    61

    B2 SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: SLATED COVERING - SLOPED - INSULATED

    Sp ifi ti

  • 7/25/2019 CASALI Application Manual Eng

    62/102

    62

    ce previously prepared, by partially bonding the underside covered bypolyethylene film by means of a propane gas blowpipe, and making longitu-dinal overlaps of at least 10 cm and head overlaps of at least 15 cm, closingthem over. The first waterproofing element may be nailed through to the

    overlap area so that the overlaps seal the membrane.The membrane mustbe fully bonded along the perimeters and over the special points (projectingparts).

    Lay a second waterproofing membrane layer parallel to the slope line, con-sisting of a distilled bituminous compound modified with plastomer polymers,self-protected with slate chips of the colour selected, such as POLTEX 45180Polyester,, with mass per unit area of 4.5 kg/sq.m., load at break, long. 750N,transverse 550N (EN 12311-1), maximum longitudinal and transverse elonga-tion at break 45% (EN 12311-1), flexibility at low temperatures -15C (EN1109).The membrane must be fully bonded with sheets staggered by 50 cm

    with respect to the first layer, torching the underside covered by polyethy-lene film by means of a propane gas blowpipe, overlapping the longitudinal

    joints by at least 10 cm and the transverse joints by at least 15 cm, closingthem over, including the joint necks with the vertical walls that must rise atleast 20 cm over the maximum water level when the covering is finished.

    Apply a styrene-acrylic resin based transparent fixative in water emulsion,highly resistant to UV rays for the slate chips, such as DERMAFIX,with wetvolume mass: 1.3 kg/dm3; dry residue; 48%; spraying on a coating of at least300 g/sq.m. with or without air.

    Specifications

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%

    applying 300 g/sq.m. by brush or roller.

    Install special breather vents for the elimination of excess water vapour, atthe junction points of the thermal insulation. The breather vents must beinserted under the vapour barrier.

    Lay an aluminium reinforced vapour barrier such as VAPOREX 2.2 kg/.sq.m. (EN1849-1), with longitudinal and transverse load at break of 300N (EN 12311-1),maximum longitudinal and transverse elongation at break 3% (EN 12311-1),vapour resistance factor >200.000 (EN 1931).Glue the membrane by partial lybonding (in strips) the underside covered with polyethylene film by means of

    a propane gas blowpipe,making longitudinal joints of at least 10 cm and headjoints of 15 cm, including the joint necks with the vertical walls that must riseby at least 10 cm over the thickness of the thermal - acoustic insulation.

    Lay the flame-resistant thermal and/or acoustic insulation sheets with thick-ness and characteristics as per the design specifications. Fix the sheets withoxidised bitumen and 4 nails per sheet; place wooden slats treated withDERMAPRIMER having the same thickness between the insulation sheets,nailing and sealing the wooden slats to the supporting structure.

    Lay a waterproofing membrane parallel to the slope line,consisting of a distil-

    led bituminous compound modified with plastomer polymers such as DER-MAFIL 40200 SP CPV, thickness 4 mm, with mass per unit area of 4.4kg/sq.m., load at break, long. 650N, transverse 450N (EN 12311-1),maximumelongation at break long.40% and transverse 45% (EN 12311-1), flexibility atlow temperatures - 10C (EN 1109). Lay the membrane on the laying surfa-

  • 7/25/2019 CASALI Application Manual Eng

    63/102

    63

    Specifications

    SUPPORTING STRUCTURE: R.C./P.R.C./CLAY-CEMENT MIX - FINISH: WITH MANTOLOMINA - SLOPED - INSULATEDB3

  • 7/25/2019 CASALI Application Manual Eng

    64/102

    64

    Specifications

    Prepare the laying surface by applying a coating of oxidised additive and sol-vent based bituminous primer such as DERMAPRIMER with wet volumemass of: 0.98 kg/dm3 ; residue at 450C: 0%; effusion time with FORD cupNo. 3 at 23C: 30 sec.; dry volume residue: 38%; dry mass residue: 40%

    applying 300 g/sq.m. by brush or roller.

    Install special breather vents for the elimination of excess water vapour, atthe junction points of the thermal insulation. The breather vents must beinserted under the vapour barrier.

    Lay an aluminium reinforced vapour barrier such as VAPOREX 2.2kg/.sq.m. (EN 1849-1), with longitudinal and transverse load at break of300N (EN 12311-1), maximum longitudinal and transverse elongation atbreak 3% (EN 12311-1), vapour resistance factor >200.000 (EN 1931).Glue the membrane, by partially bonding (in strips) the underside covered

    with polyethylene film by means of a propane gas blowpipe, making longitu-dinal joints of at least 10 cm and head joints of 15 cm, including the jointnecks with the vertical walls that must rise by at least 10 cm over the thick-ness of the thermal - acoustic insulation.

    Lay the flame-resistant thermal and/or acoustic insulation sheets with thick-ness and characteristics as per the design specifications. Fix the sheets withoxidised bitumen and 4 nails per sheet; place wooden slats treated withDERMAPRIMER of the same thickness between the insulation sheets,nailingand sealing the wooden slats to the supporting structure.

    Lay a waterproofing membrane parallel to the slope line,consisting of a distil-led bituminous compound modified with plastomer polymers such as POL-TEX 40180 polyester,, thickness 4 mm,with mass per unit area of 4 kg/sq.m.,load at break, long. 750N, transverse 550N (EN 12311-1), maximum longitu-dinal and transverse elongation 45% (EN 12311-1), flexibility at low tempe-

    ratures -15C (EN 1109). Lay the membrane in on the laying surface pre-viously prepared, by partially bonding the underside covered by polyethyle-ne film by means of a propane gas blowpipe, and making longitudinal over-laps of at least 10 cm and head overlaps of at least 15 cm, closing them over.

    The first waterproofing element may be nailed through to the overlap areaso that the overlaps seal the membrane.The membrane must be fully bon-ded along the perimeters and over the special points (projecting parts).

    Lay a second waterproofing membrane layer consisting of an elastomer bitu-minous compound ARMA, reinforced with woven glass fabric, self-protectedby a 99.75 pure tempered copper lamina, such as MANTOLAMINA**TS/Rame EL,, with mass per unit area of 4.7 kg/sq.m., tensile strength:600N/5cm, elongation at break: 3% flexibility at low temperatures -5C

    (EN 1109), fire reaction class M1.The membrane, which is available in dif-ferent colours, must be fully bonded with sheets staggered by 50 cm with

    respect to the first layer, torching the underside covered by polyethylenefilm by means of a propane gas blowpipe, and regulating the flame with themembrane of the subgrade.The side joints must cover the entire weldingstrip and 1 cm of the lamina, while the head joint is made by removing a stripof lamina at least 5 cm wide.

    *P.S.: the MANTOLAMINA line also includes:TS/Colour and Aluver: in Aluminium 8/100Coppermant: in copper 6/100

  • 7/25/2019 CASALI Application Manual Eng

    65/102

    65

    Specifications

    SUPPORTING STRUCTURE: WOOD - FINISH: TILE ON DOUBLE FRAME - SLOPED - INSULATEDB4

  • 7/25/2019 CASALI Application Manual Eng

    66/102

    66

    p f

    Dry lay a high mechanical resistance continuous fibre polyester membranecoated on one side only with bituminous-polymer covering such as UNI-VERSAL UNDERLAY, 2 kg/sq.m.(EN 1849-1),with load at break, long.700Nand transverse 500 N (EN 12311-1), maximum longitudinal and transverse

    elongation at break 35% (EN 12311-1), flexibility at low temperatures -10C/EN 1109). Nail the membrane to the wooden supports torching on longi-tudinal joints of at least 10 cm and head joints of 15 cm, by means of a pro-pane gas blow-pipe, including the joint necks with projecting parts that mustbe fully bonded at