![Page 1: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/1.jpg)
Seismic Retrofit
Case StudyBuilding Strengthening using CFRP
December 10th 2019
Avi Cohen
Yaron Offir Engineers / Exyte
![Page 2: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/2.jpg)
2Seismic Retrofit Case Study 10-Dec-2019 |
Content
1. Case study: Seismic Retrofit of an
office building into a high-tech
manufacturing facility
2. Near-surface-mounted CFRP rod
design
![Page 3: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/3.jpg)
3Seismic Retrofit Case Study 10-Dec-2019 |
Case Study:Seismic Retrofit of an office building into a high-
tech manufacturing facility
![Page 4: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/4.jpg)
4Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SEISMIC EVALUATION
ASCE/SEI 41-17
Seismic Evaluation and Retrofit of
Existing Buildings, ASCE/SEI-41-17
![Page 5: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/5.jpg)
5Seismic Retrofit Case Study 10-Dec-2019 |
Higher
Performance
(LESS Loss)
Lower
Performance
(MORE Loss)
Operational (1-A)Immediate
Occupancy (1-B)Life Safety (3-C)Collapse Prevention (5-E)
IO for a
Design
Earthquake
CP for the
Maximum
Considered
Earthquake
LS for a Design
Earthquake
Case Study
SEISMIC PERFORMANCE OBJECTIVE
![Page 6: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/6.jpg)
6Seismic Retrofit Case Study 10-Dec-2019 |
– Enhancement of Existing Concrete Shear Walls
– New Pile Foundation for the Shear Walls
– Collector reinforcements
– Structural Joint Connection
– Nonstructural Elements
Case Study
REINFORCEMENTS
– Slab Flexural Capacity
Enhancement
![Page 7: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/7.jpg)
7Seismic Retrofit Case Study 10-Dec-2019 |
– Installation of horizontal CFRP strips
– Increase in ductility, confinement and shear capacity
– Adequate plastic hinge development
– Control of energy dissipation during an earthquake prevent damage in undesired elements
Case Study
CONCRETE SHEAR WALL ENHANCEMENT
![Page 8: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/8.jpg)
8Seismic Retrofit Case Study 10-Dec-2019 |
– Installation of horizontal CFRP strips
– Increase in ductility, confinement and shear capacity
– Adequate plastic hinge development
– Control of energy dissipation during an earthquake prevent damage in undesired elements
Case Study
COLLECTOR REINFORCEMENT
![Page 9: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/9.jpg)
9Seismic Retrofit Case Study 10-Dec-2019 |
– Installation of horizontal CFRP strips
– Increase in ductility, confinement and shear capacity
– Adequate plastic hinge development
– Control of energy dissipation during an earthquake prevent damage in undesired elements
Case Study
SLAB FLEXURAL CAPACITY ENHANCEMENT
![Page 10: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/10.jpg)
10Seismic Retrofit Case Study 10-Dec-2019 |
Provide strength and ductility without adding stiffness or changing the period.
Addition of new piles to provide tensile capacity directly to the pile foundation.
Allow for controlled plastic hinge formation and energy dissipation in flexure of
existing concrete walls.
Increase the performance of existing walls (Level 1).
Ensure adequate load path transfer to walls – collector retrofit.
IO and CP criteria requirement are met for current retrofit
Case Study
OBJECTIVES
![Page 11: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/11.jpg)
11Seismic Retrofit Case Study 10-Dec-2019 |
• Displacement Demand (Performance Point):
0
20,000
40,000
60,000
80,000
100,000
120,000
140,000
0.0 2.0 4.0 6.0 8.0 10.0
Ba
se
Sh
ea
r (k
N)
Roof displacement (cm)
Pushover Curve in the Transverse Direction
First Yielding of Pile Rebar (T pier)
First Yielding of Pile Rebar (C pier)
Yield of Existing RC wall - L1 (T pier)
First SH of Pile Rebar (T pier)
First Failure of Pile Rebar (T pier)
First Rupture of Pile Rebar (T pier)
Deformation at Performance Point
Case Study
ANALYSIS RESULTS – EXISTING BUILDING
![Page 12: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/12.jpg)
12Seismic Retrofit Case Study 10-Dec-2019 |
0
20,000
40,000
60,000
80,000
100,000
120,000
140,000
160,000
180,000
200,000
0.0 2.0 4.0 6.0 8.0 10.0
Ba
se
Sh
ea
r (k
N)
Roof displacement (cm)
Pushover Curve in the Transverse Direction
• Failure Mechanism
Yield of Existing RC wall - L1 (C pier)
Yield of Existing RC wall - L2 (T pier)
Yield of Existing RC wall - L1 (T pier)
Yield of Existing RC wall - L2 (C pier)
First Yielding of Pile Rebar
First IO limit of Pile Rebar
Deformation at Performance Point
First SH of Pile Rebar (C pier)
First Failure of Pile Rebar (T pier)
Case Study
ANALYSIS RESULTS – RETROFITTED BUILDING
![Page 13: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/13.jpg)
13Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
INSTALLATION WORKS
SHEAR ENHANCEMENT OF RC WALLS
![Page 14: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/14.jpg)
14Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 15: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/15.jpg)
15Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 16: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/16.jpg)
16Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 17: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/17.jpg)
17Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 18: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/18.jpg)
18Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
INSTALLATION WORKS
RC SLAB FLEXURAL REINFORCEMENT
![Page 19: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/19.jpg)
19Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 20: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/20.jpg)
20Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 21: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/21.jpg)
21Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 22: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/22.jpg)
22Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 23: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/23.jpg)
23Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
INSTALLATION WORKS
SHEAR ENHANCEMENT OF DIAPHRAGMS
![Page 24: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/24.jpg)
24Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 25: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/25.jpg)
25Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 26: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/26.jpg)
26Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 27: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/27.jpg)
27Seismic Retrofit Case Study 10-Dec-2019 |
Case Study
SITE INSTALLATION
![Page 28: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/28.jpg)
28Seismic Retrofit Case Study 10-Dec-2019 |
Near Surface Mounted CFRP Rod
Reinforcement Design
![Page 29: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/29.jpg)
29Seismic Retrofit Case Study 10-Dec-2019 |
NSM-CFRP Design
• Alternative collector
reinforcement using
NSM-CFRP Rods
Technical Article Flexural strengthening with NSM reinforcement - SIKA
![Page 30: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/30.jpg)
30Seismic Retrofit Case Study 10-Dec-2019 |
NSM-CFRP Design
BENEFITS
• Construction benefits:
Reduced installation time (compared to SIKAWRAP equivalent)
Reduced disturbance area
Can be installed in slightly undulating surfaces
• Technical benefits:
Reduced risk of buckling due to confinement of CFRP.
Reduced required anchorage length.
Enhanced adhesion between CFRP (increased contact area)
![Page 31: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/31.jpg)
31Seismic Retrofit Case Study 10-Dec-2019 |
NSM-CFRP Design
MODES OF FAILURE
Technical Article Flexural strengthening with NSM reinforcement - SIKA
Adhesive
SplittingConcrete
Splitting
CFRP
Rupture
Concrete
Cover
Separation
![Page 32: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/32.jpg)
32Seismic Retrofit Case Study 10-Dec-2019 |
NSM-CFRP Design
Design Guidelines
ACI 440
Design guidance for strengthening
concrete structures using fibre
composite materials, reported by the
Concrete Society.
Technical Report No.55
Guide for the Design and Construction
of Externally Bonded FRP Systems for
Strengthening Concrete Structures
![Page 33: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/33.jpg)
33Seismic Retrofit Case Study 10-Dec-2019 |
NSM-CFRP Design
Type of Rods - SIKA
PRODUCT DATA SHEET Sika® CarboDur® Rods
![Page 34: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/34.jpg)
34Seismic Retrofit Case Study 10-Dec-2019 |
NSM-CFRP Design
Retrofit Design
ACI 440 TR-55
Design rupture strain:
Debonding strain:
Effective strength:
Design strain:
Design E-modulus: strain:
Effective strength:
DETERMINATION OF THE EFFECTIVE STRAIN
𝑓𝑓𝑒 = ε𝑓𝑑𝐸𝑓𝑑
![Page 35: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/35.jpg)
35Seismic Retrofit Case Study 10-Dec-2019 |
ACI 440 TR-55
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
DETERMINATION OF THE EFFECTIVE STRAIN
![Page 36: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/36.jpg)
36Seismic Retrofit Case Study 10-Dec-2019 |
TR-55
Anchorage force
Anchorage length
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
FAILURE MODE CHECK: CONCRETE SPLITTING
![Page 37: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/37.jpg)
37Seismic Retrofit Case Study 10-Dec-2019 |
TR-55
Actual Anchorage force
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
FAILURE MODE CHECK: CONCRETE SPLITTING (cont)
![Page 38: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/38.jpg)
38Seismic Retrofit Case Study 10-Dec-2019 |
TR-55
Avoid concrete cover separation:
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
FAILURE MODE CHECK: CONCRETE COVER SEPARATION
![Page 39: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/39.jpg)
39Seismic Retrofit Case Study 10-Dec-2019 |
TR-55
Mechanical capacity of adhesive at anchorage:
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
FAILURE MODE CHECK: ADHESIVE LAYER AT ANCHORAGE
![Page 40: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/40.jpg)
40Seismic Retrofit Case Study 10-Dec-2019 |
TR-55
Separation due to the longitudinal shear stress
in the yield zone:
Shear stress limit:
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
FAILURE MODE CHECK: ADHESIVE FAILURE
![Page 41: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/41.jpg)
41Seismic Retrofit Case Study 10-Dec-2019 |
TR-55
Separation due to the longitudinal shear stress
in the yield zone:
Shear stress limit:
NSM-CFRP Design
Retrofit Design
Technical Article Flexural strengthening with NSM reinforcement - SIKA
FAILURE MODE CHECK: CONCRETE FAILURE
![Page 42: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/42.jpg)
42Seismic Retrofit Case Study 10-Dec-2019 |
ACI 440
Sustained plus cyclic stress limit:
Concrete stress limit:
Steel stress limit:
NSM-CFRP Design
Retrofit Design
From: ACI440.2R-17
SERVICEABILITY LIMITS
𝑓𝑓𝑠 = 0.55𝑓𝑓𝑢
𝑓𝑐𝑠 = 0.60𝑓𝑐𝑒′
𝑓𝑓𝑠 = 0.80𝑓𝑦𝑒
![Page 43: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/43.jpg)
43Seismic Retrofit Case Study 10-Dec-2019 |
FRP solutions provided effective concrete capacity enhancement.
Increased shear strength without sacrificing ductility.
Numerous construction benefits.
Further research for NSM FRP rods in shear applications is still required.
Straightforward design.
Flexibility in on-site repair solutions.
FINAL REMARKS
![Page 44: Case Study · 2019. 12. 23. · Design Guidelines ACI 440 Design guidance for strengthening concrete structures using fibre composite materials, reported by the Concrete Society](https://reader035.vdocument.in/reader035/viewer/2022070221/61354fb1dfd10f4dd73c4ac0/html5/thumbnails/44.jpg)
44Seismic Retrofit Case Study 10-Dec-2019 |
Comments / Questions