cat automatic transfer switches (ats) - carter...
TRANSCRIPT
Cat Automatic Transfer Switches (ATS)
Bruce Newhouse
Cat ATS Application Engineer
Alpharetta, GA
Page 2
Two Product Line Offerings
Contactor Based Switch • 40A through 4000A • CTX • CTG • CTS • CTE • CT30
Contactor Based Switch • 100A through 1600A*
Circuit Breaker Based Switch • 40A through 1000A MCCB
(Molded Case Circuit Breaker) • 200A through 5000A ICCB
(Insulated Case Circuit Breaker)
ATC Nomenclature
* Available on Open Transition & Dual Drawout Bypass Isolation with Delayed or Open Transition Types
Manufactured by G.E. Zenith Manufactured by Eaton Corporation
Page 3
ATS Types Available
• Open Transition • Closed Transition • Bypass Isolation • Delayed Transition • Service Entrance Rated • Standard Enclosure NEMA 1 • Optional NEMA 3R, NEMA 4X & NEMA 12 • Full Range of Accessories and Communications
Page 4
Application / Market Focused
• Caterpillar offers three transfer switch technologies providing a solutions based approach to customers’ CSA/UL 1008 listed applications: • Molded-Case Switch or
Breaker • Power Case Switch or
Breaker (4000A and 5000A are UL 1008 and UL891)
• Contactor
All are available in Bypass/Isolation configuration
Page 5
• Manufactured in: • Asheville, NC – ATC type Floor-Standing Units
• Contactors, ATC type Magnum and Bypass Isolation Contactor
• Juarez, MX – ATC type Wall-Mounted Units • ATC type Molded-Case and Contactor Final Assembly
• North Carolina & Illinois. - MX product line • ISO 9001 Certified (ATC & MX products)
Page 6
Product Recap
Page 7
MX Products
CTG CTS CTE CT30
MX150 Controller
MX250 Controller
MX350 Controller
Page 8
ATC Products ATC Contactor Based
ATS ATC Molded Case
Breaker Based ATS
ATC Bypass Isolation Contactor Based ATS
ATC Power Breaker ATS
ATC-300+ Controller
ATC-900 Controller
Page 9
Cat® ATC Contactor Transfer Switch
• 40A – 1600A 100% Rated • 2, 3, 4-Poles • ATC-100, ATC-300+, ATC-900 • Open, Closed & Delayed Transition • Automatic, Non-Automatic • In-phase Available on 40A – 400A • Open In-Phase on 600A-1600A • Time Delay Neutral Available on 40A -1600A • NEMA 1, 3R, 12, Open Type • Seismic Qualified • UL 1008 / CSA • Manufactured in NC and Mexico
Page 10
ATC Contactor Bypass Isolation Transfer Switch
• New Design – New Contactor • UL 1008 100% rated units • 100 – 1600 Amps • 3-pole and 4-pole units • Up to 600 Volts AC • Open and Closed Transition types • Time Delay Neutral Feature Available • Drawout Type Design is Standard
Page 11
ATC Contactor Bypass Isolation Transfer Switch
• Both the ATS (primary) and bypass switching mechanisms are controlled by the automatic transfer switch controller
• For Life Safety / Critical applications a transfer will be Initiated AUTOMATICALLY when in bypass mode.
• Unique to our design
Page 12
ATC Contactor Bypass Isolation Transfer Switch
Field Reconfigurable Bus
Page 13
Multi-Tap Transformer – Application Flexibility
1200A Frame Design 400A Frame Design
• Accommodates multiple source voltages via Quick-Connect plug • 50/60Hz – 600, 480, 415, 380, 240, 220, 208, VAC • 60Hz – 600, 480, 240, 120 VAC
Page 14
Product Differentiators: Competitor Overview
Page 15
Power Breaker Based Transfer Switch
• 200A - 5000A 100% rated • 4000A-5000A UL 891 & UL1008 • 2, 3, 4-Poles • ATC-900 Controller • Fixed or Drawout • Open or Closed Transition • Automatic or Non-Automatic Bypass Isolation • Optional Electronic Trip Unit(s) • Available Time Delay Neutral or In-
Phase Transition • Withstand: 100KA, 600V, 3 cycles,
85 KA, 600V, 30 cycles • NEMA 1, 3R, Open (excluding
Bypass) • Seismic Qualified • UL 1008 / CSA
Page 16
Cat ATC ATS Controllers
ATC-100 • Mimic Diagram with source available and connected LED indications • Plant Exerciser - 7, 14 or 28 day w/fixed 15 min run time • Jumper Programmable
ATC-300+ • Fully programmable w/7 field selectable time delays • 3-phase sensing on both sources • Pre-transfer signal contacts (1 N.O. & 1 N.C.)
ATC-900 • Closed transition and modbus
communication controller • Optional load sequencing • Unlimited historical data with remote
software
Page 17
ATC-900 Controller
• Power quality metering • User assigned I/O • Modular construction & pricing:
– Base – Ethernet communications card – Metering inputs (CT and PT) – Additional I/O
• Enhanced communications • Data logging • Load shed capabilities • 3 source capabilities • DC powered
Page 18
Cat Traditional Solenoid Operated vs Circuit Breaker ATS
Traditional ATS Installation ATS with Service Entrance Equipment Rating
Page 19
Cat ATS Products
ATC Part Number Breakdown
Contactor Product Family Family Function Controller Frame Size
ATC General Purpose / Specif ied ATC-300+/900 40-1600A BIC By pass Isolation ATC-300+/900 40-1600A CBC By pass Closed Trandition ATC-900 40-1600A CTC Closed Transition ATC-900 40-1600A
Breaker Product Family (Service Entrance Rated Available*)
ATV/H* MCCB Vertical/Horizontal General Purpose / Specif ied
ATC-300+/900 30-1000A
ATV-MG* Power Breaker Open Trandition ATC-900 200-5000A CTV-MG* Power Breaker Closed Transition ATC-900 200-5000A BIV-MG* Power Breaker By pass Isolation ATC-900 200-5000A
CBV-MG* Power Breaker By pass Isolation Closed Transition ATC-900 200-5000A
MX Part Number Breakdown
Contactor Product Family Function Controller Frame Size
CTX Residential MX60 40-400A CTG/D General Purpose MX150 40-3000A CTS/D Specif ied MX250 100-4000A
CBTS/D By pass Isolation & Delay ed Transition MX250 40-1600A
CTSCT/CBTSCT Closed Transition & By pass Isolation Closed Transition MX150 40-3000A
CTE/D Custom Specif ied MX350 40-4000A CT30 30 Cy cle MX250 or MX350 1600-2000A
Page 20
Cat MX Contactor Transfer Switch
• 40A – 4000A 100% rated • 2, 3, 4-Poles • MX60, MX150, & MX250 • Any Breaker rating MX250 only • Open, Closed, Bypass & Delayed
Transition • Automatic, Non-Automatic • In-phase • Time Delay Neutral • NEMA 1, 3R, 4X 12, Open • Seismic qualified • UL 1008 / CSA • Manufactured in NC & IL
MX60 Controller
MX350 Controller
MX250 Controller
MX150 Controller
Page 21
CTX Automatic Transfer Switch
• Residential and Light Commercial
• Microprocessor based controls • Standard ATS control • LED annunciation of position
and source availability • Designed primarily for basic
applications • Used on 40-400A, single and
three Phase, 120-480V, 2, 3 & 4-Poles
Page 22
CTG Automatic Transfer Switch
• Industrial, Commercial and Other Applications
• MX150 controller • Used on 40-3000A, single &
three phase, 120-600V, 2, 3 & 4-poles
• Available in open & delayed transition (CTG & CTGD) types
Optional Package: MEXEG – Adds aux contacts, programmable exerciser and voltage imbalance relay
Page 23
CTS Automatic Transfer Switch
• Full line of options for critical applications
• MX250 controller • Used on 40-4000A, single & • 3 phase, 120-600V, 2, 3 & 4-poles • Available in all configurations
– Open Transition – Delayed Transition – Closed Transition – Bypass Isolation
• Communicates with Cat switchgear via Modbus
Page 24
CTE Automatic Transfer Switches
Page 25
CTE with MX Controller
• User configurable alarms • 256 event log • 1 MSEC event time stamping • System test report - JCAHO
• Power Quality Metering – Wave form capture triggered by
event – % THD
• User Programmable I/O – Built-in load shed – User configurable alarms
• Modular Construction & Pricing: – Base – Communications card (Modbus,
Ethernet, USB) – Metering inputs (CT & PT) – Additional I/O
Page 26
MX CT30 Automatic Transfer Switch
• Industry-leading durability and fault tolerance (85kA short-time rating)
• Maximizes system uptime / reliability Withstands and closes on a fault Supplies 100% rated power to loads after
overcurrent event
• Electrical and mechanical interlock prevents source 1 and source 2 from being inadvertently closed at the same time (Standard/Delayed Transition)
30-Cycle ATS 1600-3000A Only
Page 27
ATC 30-Cycle ATS • Highest withstand
and capacity in the industry
– 100kAIC, 3 Cycles – 85kAIC, 30 Cycles
• Enclosure types – NEMA 1 – NEMA 3R
• NEMA 1 enclosure styles
– “Behind the Door” (Figure 1)
– “Through the Door” (Figure 2)
Figure 1 Figure 2
Pictures shown may not reflect actual configuration
Page 28
Standards & Certifications UL1008, CSA, NFPA, IBC, CBC & OSHPD
• UL1008 - 4000-5000A Breakers are listed to UL891
• CSA Listed (Canadian) • IBC 2006 • CBC 2007 • NFPA70, 99, 101, & 110 • OSHPD
Page 29
Seismic Certifications
4000A and below meet all applicable seismic requirements of 2006 IBC International Build Code & 2007 CBC California Building Codes
Page 30
Seismic Certifications
Page 31
ATS Comparisons
Small Frame Residential, Commercial & Light Industrial
General Purpose, Commercial & Industrial Factories, & Institutional
Business & Industrial Critical, Financial, Telecommunications / Cell Towers
Mission, Process & Healthcare Critical, Data Centers
165 (100, 200, 230A) Standard Transition Only
300 (30-3000A) Standard Transition Only
-SE & Non-SE-
4000 (30-4000A) Standard, Delayed &
Closed Transition -Non-Bypass Only-
7000 (30-4000A) Bypass & Non-Bypass
-Standard, Delayed, Closed Transition & Softload-
CTX (40-400A) Basic Standby Operation
–Standard Transition Only-
CTG (40-3000A) Reliable Standby Power
Standard & Delayed Transition -SE & Non-SE
CTS / CTSD / CTSCT (40-4000A) CBTS / CBTSD / CBTCT )40-4000A)
Specification Grade
CTE (40-4000A) Life & Business Critical Applications
Standard, Delayed & Closed Transition -Bypass & Non-Bypass-
ASCO Cat MX Market
Segments
BETTER
GOOD
FANTASTIC!
BEST
Page 32
Questions?
CUSTOM CAT ATS SOLUTIONS
Page 34
Cat MX 3 Source ATS
• Three-source switching systems are available in several basic configurations and may be configured from a list of transition types and accessories offered with the CTS series of products. Available from 40-4000A in 2, 3 or 4-pole
Page 35
Cat 3-Source Switching System
CT3110 CT3120 for 1st up – 1st on CT3130 for prime source selection
Page 36
Cat ATC 3-Source ATS With the ATC-900 Controller
ATC-900 Acts as the master controller • Requires accessory 90A
ATC-900 also functions as the slave controller • Requires accessory 90B
Page 37
Cat ATS – Medium Voltage
Medium voltage breaker based automatic transfer switches are available with our ATC controller. Indoor (NEMA 1) or Outdoor (NEMA 3R) In 5kV, 15kV for 28kV with 1200A or 2000A bus. • Open or closed transition only
NEMA 3R Type
Page 38
Cat ATS – Medium Voltage
• Standard Features – IQ Transfer Logic Controller – Digitrip 3000 – Line & Load VT’s (Bus VTs not
required – Safe Manal Transfer Under Load
• Available Options: – IL Listing – Metering – Control Power Transformers – Delayed Transition or In-Phase
Monitoring
Page 39
Cat ATS – Soft Load Solution
• We have the new breaker pair transfer scheme offering for soft load applications
• ATS consists of two (2) breakers with Engine Transfer Load Manager ( EXL) controls only
• Rated UL 1008
Page 40
Cat ATS Custom Solutions
Emergency Pull Section Added to the Line Up
TVSS Installed in the Cabinet
Distribution Breakers added to the Line Up
ATC Power Breaker Pair Service Entrance Rated
Page 41
CAT Remote Annunciator
• Provides Displays of Over 31 Automatic Transfer Switches
• Control & Monitoring • Ethernet Communications • Monitors ANY ATS with
Modbus Communications Capabilities
• Integral UPS • Adjusts Setpoints and Timers • Power Monitoring Display
Available
Page 42
Cat Automatic Transfer Switches
• Widest Range of Product Offerings • Cat Dealer Service and Support Network
– Over 1,800 Dealer Branch Stores Operating in 200 Countries
Information contained in this publication may be considered confidential. Discretion is recommended when distributing. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate and product identity
used herein, are trademarks of Caterpillar and may not be used without permission.