Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630 kW) HFC-410A Refrigerant 60/50 Hz

Upload: phamanh

Post on 14-Feb-2018

219 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

Catalog 624-4Trailblazertrade

Air-Cooled Scroll Compressor ChillersModel AGZ E Vintage 030 to 180 Tons (100 to 630 kW) HFC-410A Refrigerant 6050 Hz

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 2 wwwDaikinAppliedcom

Table of ConTenTs

Table of ConTenTs

copy2015 Daikin Applied Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at any time without notice

0DQXIDFWXUHGLQDQ6262FHUWLiquestHGIDFLOLW

Introduction 3)HDWXUHVDQGHQHiquestWV 4Application Considerations 8Sound Data 16Selection Procedure 20Performance Data 21Pressure Drop Data 23

3KVLFDODWD3DFNDJHG8QLWV 24LPHQVLRQVDQGHLJKWV3DFNDJHG8QLWV 28Isolators 34Electrical Data 35Options and Accessories 43(QJLQHHULQJXLGH6SHFLiquestFDWLRQV 46

InTroduCTIon

wwwDaikinAppliedcom 3 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

The Trailblazertrade family of air-cooled scroll chillers continues WKHDLNLQ$SSOLHGOHJDFRIKLJKTXDOLWKLJKHIiquestFLHQFlatest technology and quiet operation These features make the Trailblazertrade family the best overall value in air-cooled packaged chillers available today The Trailblazertrade series offers a wide selection of units from 30 to 180 tons with dual refrigerant circuits available as packaged units with remote evaporators or with an optional pump package

(IiquestFLHQW2SHUDWLRQThe Trailblazertrade units utilize environmentally acceptable R-410A refrigerant and meet the performance requirements RI$6+5$(6WDQGDUGIRUHIiquestFLHQF([FHOOHQWSDUWORDGSHUIRUPDQFHLVDFKLHYHGZLWKIRXURUVL[VFUROOFRPSUHVVRUV+LJKRYHUDOOHIiquestFLHQF ORZHUDQQXDOHQHUJFRVWV

RapidRestorereg and Fast LoadingWhen power has been interrupted the Trailblazertrade has the capability to restore cooling quickly by using RapidRestorereg and Fast Loading These options make Trailblazertrade ideal for mission critical buildings data centers healthcare facilities and manufacturing processes Once power is restored after a power loss duration of up to 180 seconds the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds

$SSOLFDWLRQ)OH[LELOLWTrailblazertrade units are available as packaged chillers or with remote evaporators Information on remote evaporator models and factory-installed pump packages can be found in a separate installation manual available on wwwDaikinAppliedcom

Quiet OperationThe Trailblazertrade units live up to the Daikin Applied reputation for low operating sound levels and make these chillers ldquoneighborhood friendlyrdquo Full load sound pressure levels as low as 60dB without insulation

LEEDreg Points Developed by the US Green Building Council (USGBC) in 1998 Leadership in Energy and Environmental Design (LEEDregLVDQLQWHUQDWLRQDOOUHFRJQL]HGFHUWLiquestFDWLRQSURJUDPand intends to provide building owners and operators a consistent structure for identifying and implementing practical and measurable green building design construction operations and maintenance solutions

For building owners who want to pursue LEEDreg Green Building ampHUWLiquestFDWLRQWKH7UDLOEOD]HUtrade series of air-cooled chillers does qualify for the Energy and Atmosphere Credit 4 Enhanced Refrigerant Management worth 2 points

Air-Cooled Chiller Products

1000 200 300 400 500 600

Pathfinderreg Air-Cooled Screw Compressor ChillerModel AWS bull 170 - 550 RT

Standard High and Premium EfficencyVFD and Remote Evaporator options available

Air-Cooled Scroll Compressor ChillerModel AGZ-B bull 10 - 34 RT

TrailblazerTM Air-Cooled Scroll Compressor ChillerModel AGZ-E bull 30 - 180 RTRemote Evaporator and Pump Package options available

AGZ-E

InTroduCTIon

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 4 wwwDaikinAppliedcom

feaTures and benefITs

CHILLER NOMENCLATURE

A G Z XXX E H

8QLWHVLJQ)HDWXUHVDaikin Trailblazertrade air-cooled chillers are a product of our FRPPLWPHQWWRRIIHUTXLHWUHOLDEOHHQHUJHIiquestFLHQWHTXLSPHQWincorporating high quality compressors and innovative packaging

ConstructionTrailblazertrade chillers are factory-assembled and mounted on a heavy-gauge steel base The base distributes the unit weight for roof loading Their small footprint allows smaller PRXQWLQJSDGVRUVXSSRUWVWUXFWXUHVDQGLVDSOXVIRUUHWURiquestWRUreplacement applications

CompressorsReliable hermetic scroll compressors with cast iron scrolls DQGWKUHH7HAgraveRQreg impregnated bearings are used on the Trailblazertrade chillers to promote longevity

Each model has the ability to modulate its capacity Models with four compressors will have four steps of capacity PRGXODWLRQZKLOHPRGHOVZLWKVL[FRPSUHVVRUVZLOOKDYHVL[steps Compressors stage on depending on the load of the VVWHP7KLVUHVXOWVLQH[FHOOHQWSDUWORDGHIiquestFLHQFDQGreduced annual operating costs

Features include motor temperature protection scroll temperature protection missing phase protection reverse phase protection low control circuit voltage protection short cycling detection and alert Modbusreg communication to system controller operational and fault history storage and LED status display

Evaporator7KHHYDSRUDWRULVDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUFRQVLVWLQJRISDUDOOHOVWDLQOHVVVWHHOSODWHV7KHVHKHDWH[FKDQJHUVSURYLGHH[FHOOHQWKHDWH[FKDQJHHIiquestFLHQFLQDFRPSDFWIRRWSULQWDQGare especially attractive for smaller capacity units Evaporators are designed and constructed according to and listed by Underwriters Laboratories (UL)

Optional Remote Evaporator Units with the optional remote evaporator will have the HYDSRUDWRUVKLSSHGVHSDUDWHOIRUiquestHOGPRXQWLQJDQGSLSLQJWRthe outdoor unit

Condenser CoilsCondenser coils are all aluminum alloy microchannel design ZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifold piping A variety of optional coil materials and coatings are available so that the unit can be constructed to meet almost any environment Packaged unit options include

bull FRSSHUWXEHDOXPLQXPiquestQVWRQPRGHOVRQObull FRSSHUWXEHFRSSHUiquestQVWRQPRGHOVRQObull FRSSHUWXEHDOXPLQXPODFNiquestQVWRQPRGHOVRQObull ElectroFinreg coating can be applied to any coil option

See ldquoCondenser Coil Options and Coating Considerationsrdquo on page 14 for discussion of environmental factors related to material and coating options

Figure 1 Microchannel Coil

Air-Cooled

Global Design

Scroll Compressor

Application + 6WDQGDUG3DFNDJHG 5HPRWH(YDSRUDWRU

Design VintageNominal Tons

feaTures and benefITs

feaTures and benefITs

wwwDaikinAppliedcom 5 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Condenser Fans and MotorsMultiple direct-drive dynamically balanced propeller fans operate in formed venturi openings at low tip speeds for PD[LPXPHIiquestFLHQFDQGPLQLPXPQRLVHDQGYLEUDWLRQ$heavy-gauge vinyl-coated fan guard protects each fan

Each condenser fan motor (including the optional VFD fan motor) is Totally Enclosed Air Over (TEAO) heavy-duty 3-phase with permanently lubricated ball bearings and inherent RYHUORDGSURWHFWLRQ7KHVHPRWRUVDUHGHVLJQHGVSHFLiquestFDOOIRUoutdoor use

Figure 2 Trailblazertrade with Optional Full Louver Package

ampRQWURO6VWHPThe MicroTechreg III advanced DDC chiller controller surpasses all other microprocessor-based chiller control systems available today This powerful user-friendly control system SURYLGHVWKHAgraveH[LELOLWDQGSHUIRUPDQFHQHHGHGIRUHLWKHUstand-alone unit operation or the controller can be easily tied into the building automation system of choice using the Daikin Open Choicestrade feature Open Choicestrade allows one to choose from open standard protocols such as BACnetreg Modbusreg and LonWorksreg to communicate easily with the building automation system that best meets the facility requirements These optional communications modules are available factory LQVWDOOHGRUFDQEHHDVLOiquestHOGLQVWDOOHG

The MicroTechreg III controllerrsquos design will not only permit WKHFKLOOHUWRUXQPRUHHIiquestFLHQWOEXWZLOODOVRVLPSOLItroubleshooting if a system failure occurs Every MicroTechreg III controller is programmed and tested prior to shipment to help provide a trouble-free start-up

Operator-friendlyThe MicroTechreg III control menu structure is separated into four distinct categories that provide the operator or service technician with a full description of current unit status control parameters and alarms Security protection helps prevent unauthorized changing of the setpoints and unit control parameters

MicroTechreg III control continuously performs important self-diagnostic checks while monitoring system temperatures pressures and protection devices It will automatically shutdown a compressor a refrigerant circuit or the entire unit if a fault occurs The cause of the shutdown will be retained in memory and can be easily displayed in plain English or metric units for operator review In addition to displaying alarm diagnostics the MicroTechreg III chiller controller also provides the operator with a warning of pre-alarm conditions Alarm QRWLiquestFDWLRQGDWDFDQDOVREHSDVVHGWRD$6WKURXJKDQoptional communication module

StagingThe scroll compressors are staged on and off as a function of leaving chilled water temperature Leadlag is automatic and switched based on starts and operating hours

Equipment ProtectionThe unit is protected in three ways

1 alarms that shut the unit down and require manual reset to restore unit operation

2 alarms that shut the unit down and then restart automatically (do not require manual restart)

3 limit alarms that reduce unit capacity in response to some out-of-limit conditions

Shut down alarms activate an alarm signal that can be H[SRUWHGWRDUHPRWHORFDWLRQLPLWDODUPVDFWLYDWHDOLJKWRQthe controller and do not trigger a remote alarm

Building Automation System (BAS) InterfaceThe following BAS protocols are supported

bull BACnetregIPbull BACnetreg MSTPbull LonWorksreg (FTT-10A)bull Modbusreg

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 6 wwwDaikinAppliedcom

feaTures and benefITs

Optional Remote Interface Panel In addition to the unit-mounted user interface provided with MicroTechreg III controls the Trailblazertrade chillers can be individually equipped with a remote user interface It provides convenient access to unit diagnostics and control adjustments without having to access a rooftop or outdoor location One remote panel can be connected to up to eight chillers

Featuresbull Each remote user interface is similar to its unit-mounted

counterpart and offers the same functionality and displaybull Three buttons and a navigating wheel with a 8 line by

30-character display formatbull Digital display of messages in English languagebull All operating conditions system alarms control bull parameters and schedules are monitoredbull ampDQEHZLUHGXSWRIHHWPHWHUVIURPWKHXQLWIRUAgraveH[LELOLWLQSODFLQJHDFKUHPRWHXVHULQWHUIDFHZLWKLQthe building

HQHiquestWVbull Allows access to the user interface for each unit from one

location inside the buildingbull Users need to learn one format because the remote user

interface is identical to the unit-mounted versionbull 1RDGGLWLRQDOiquestHOGFRPPLVVLRQLQJLVUHTXLUHGIRUWKH

remote user interfacebull ampDQEHUHWURiquestWDIWHUXQLWLQVWDOODWLRQbull Is fully compatible with the optional BAS communication

modulesThe current manual for the MicroTechreg III Remote User Interface is available on wwwDaikinAppliedcom

Optional Pump PackageThe on-board integrated chilled water pump package provides LPSRUWDQWEHQHiquestWV

bull Simplify the chilled water system design and installation bull 3URYLGHLQVWDOODWLRQVDYLQJVEUHGXFLQJiquestHOGSLSLQJ

wiring and control costsbull 6DYHYDOXDEOHAgraveRRUVSDFHLQVLGHWKHEXLOGLQJbull Reduce project engineering contentbull Greatly reduce pump operating cost with the optional YDULDEOHAgraveRZSXPS9)

Standard ComponentsSingle Pump Model 4380 single spring inside seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly can be serviced without removing the pump casing from the line

Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and RXWOHWFRQQHFWLRQDQGLQFOXGLQJDAgraveDSSHUYDOYHWRSUHYHQW

recirculation when only one pump is operating An isolation valve is included that allows one pump to operate when the other is removed The pumps are designed for dutystandby not parallel operation All information and performance curves for the single pump arrangement (Model 4380) can be used for the dual pump arrangement (Model 4392)

The package is also is equipped with a ldquoYrdquo type inlet strainer a combination triple-duty outlet valve having a discharge shutoff YDOYHFKHFNYDOYHDQGAgraveRZWKURWWOLQJYDOYHDFRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWYDQHVDQGVWDLQOHVVVWHHOVWUDLQHUZLWKDGLVSRVDEOHiquestQHPHVKVWDUWXSVWUDLQHUDAgraveRZVZLWFKPRXQWHGDQGZLUHGIDFWRUSRZHUDQGFRQWUROwiring interconnecting piping and insulation of all cold surfaces Various tank and connection options are available for iquestHOGPRXQWLQJ

Figure 3 Optional Pump Package Schematic

Dual Vertical Pumps

ldquoYrdquo TypeInlet

Strainer

ChilledWaterInlet

InletGuide Optional

VFDControllers Chilled

WaterOutlet

Triple-DutyOutlet Valve Flow

SwitchDrain Evap Out Press

Gauge Port

PumpPackageControlPanel

Brazed-PlateEvaporator

Evap In PressGauge Port

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 2: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 2 wwwDaikinAppliedcom

Table of ConTenTs

Table of ConTenTs

copy2015 Daikin Applied Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at any time without notice

0DQXIDFWXUHGLQDQ6262FHUWLiquestHGIDFLOLW

Introduction 3)HDWXUHVDQGHQHiquestWV 4Application Considerations 8Sound Data 16Selection Procedure 20Performance Data 21Pressure Drop Data 23

3KVLFDODWD3DFNDJHG8QLWV 24LPHQVLRQVDQGHLJKWV3DFNDJHG8QLWV 28Isolators 34Electrical Data 35Options and Accessories 43(QJLQHHULQJXLGH6SHFLiquestFDWLRQV 46

InTroduCTIon

wwwDaikinAppliedcom 3 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

The Trailblazertrade family of air-cooled scroll chillers continues WKHDLNLQ$SSOLHGOHJDFRIKLJKTXDOLWKLJKHIiquestFLHQFlatest technology and quiet operation These features make the Trailblazertrade family the best overall value in air-cooled packaged chillers available today The Trailblazertrade series offers a wide selection of units from 30 to 180 tons with dual refrigerant circuits available as packaged units with remote evaporators or with an optional pump package

(IiquestFLHQW2SHUDWLRQThe Trailblazertrade units utilize environmentally acceptable R-410A refrigerant and meet the performance requirements RI$6+5$(6WDQGDUGIRUHIiquestFLHQF([FHOOHQWSDUWORDGSHUIRUPDQFHLVDFKLHYHGZLWKIRXURUVL[VFUROOFRPSUHVVRUV+LJKRYHUDOOHIiquestFLHQF ORZHUDQQXDOHQHUJFRVWV

RapidRestorereg and Fast LoadingWhen power has been interrupted the Trailblazertrade has the capability to restore cooling quickly by using RapidRestorereg and Fast Loading These options make Trailblazertrade ideal for mission critical buildings data centers healthcare facilities and manufacturing processes Once power is restored after a power loss duration of up to 180 seconds the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds

$SSOLFDWLRQ)OH[LELOLWTrailblazertrade units are available as packaged chillers or with remote evaporators Information on remote evaporator models and factory-installed pump packages can be found in a separate installation manual available on wwwDaikinAppliedcom

Quiet OperationThe Trailblazertrade units live up to the Daikin Applied reputation for low operating sound levels and make these chillers ldquoneighborhood friendlyrdquo Full load sound pressure levels as low as 60dB without insulation

LEEDreg Points Developed by the US Green Building Council (USGBC) in 1998 Leadership in Energy and Environmental Design (LEEDregLVDQLQWHUQDWLRQDOOUHFRJQL]HGFHUWLiquestFDWLRQSURJUDPand intends to provide building owners and operators a consistent structure for identifying and implementing practical and measurable green building design construction operations and maintenance solutions

For building owners who want to pursue LEEDreg Green Building ampHUWLiquestFDWLRQWKH7UDLOEOD]HUtrade series of air-cooled chillers does qualify for the Energy and Atmosphere Credit 4 Enhanced Refrigerant Management worth 2 points

Air-Cooled Chiller Products

1000 200 300 400 500 600

Pathfinderreg Air-Cooled Screw Compressor ChillerModel AWS bull 170 - 550 RT

Standard High and Premium EfficencyVFD and Remote Evaporator options available

Air-Cooled Scroll Compressor ChillerModel AGZ-B bull 10 - 34 RT

TrailblazerTM Air-Cooled Scroll Compressor ChillerModel AGZ-E bull 30 - 180 RTRemote Evaporator and Pump Package options available

AGZ-E

InTroduCTIon

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 4 wwwDaikinAppliedcom

feaTures and benefITs

CHILLER NOMENCLATURE

A G Z XXX E H

8QLWHVLJQ)HDWXUHVDaikin Trailblazertrade air-cooled chillers are a product of our FRPPLWPHQWWRRIIHUTXLHWUHOLDEOHHQHUJHIiquestFLHQWHTXLSPHQWincorporating high quality compressors and innovative packaging

ConstructionTrailblazertrade chillers are factory-assembled and mounted on a heavy-gauge steel base The base distributes the unit weight for roof loading Their small footprint allows smaller PRXQWLQJSDGVRUVXSSRUWVWUXFWXUHVDQGLVDSOXVIRUUHWURiquestWRUreplacement applications

CompressorsReliable hermetic scroll compressors with cast iron scrolls DQGWKUHH7HAgraveRQreg impregnated bearings are used on the Trailblazertrade chillers to promote longevity

Each model has the ability to modulate its capacity Models with four compressors will have four steps of capacity PRGXODWLRQZKLOHPRGHOVZLWKVL[FRPSUHVVRUVZLOOKDYHVL[steps Compressors stage on depending on the load of the VVWHP7KLVUHVXOWVLQH[FHOOHQWSDUWORDGHIiquestFLHQFDQGreduced annual operating costs

Features include motor temperature protection scroll temperature protection missing phase protection reverse phase protection low control circuit voltage protection short cycling detection and alert Modbusreg communication to system controller operational and fault history storage and LED status display

Evaporator7KHHYDSRUDWRULVDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUFRQVLVWLQJRISDUDOOHOVWDLQOHVVVWHHOSODWHV7KHVHKHDWH[FKDQJHUVSURYLGHH[FHOOHQWKHDWH[FKDQJHHIiquestFLHQFLQDFRPSDFWIRRWSULQWDQGare especially attractive for smaller capacity units Evaporators are designed and constructed according to and listed by Underwriters Laboratories (UL)

Optional Remote Evaporator Units with the optional remote evaporator will have the HYDSRUDWRUVKLSSHGVHSDUDWHOIRUiquestHOGPRXQWLQJDQGSLSLQJWRthe outdoor unit

Condenser CoilsCondenser coils are all aluminum alloy microchannel design ZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifold piping A variety of optional coil materials and coatings are available so that the unit can be constructed to meet almost any environment Packaged unit options include

bull FRSSHUWXEHDOXPLQXPiquestQVWRQPRGHOVRQObull FRSSHUWXEHFRSSHUiquestQVWRQPRGHOVRQObull FRSSHUWXEHDOXPLQXPODFNiquestQVWRQPRGHOVRQObull ElectroFinreg coating can be applied to any coil option

See ldquoCondenser Coil Options and Coating Considerationsrdquo on page 14 for discussion of environmental factors related to material and coating options

Figure 1 Microchannel Coil

Air-Cooled

Global Design

Scroll Compressor

Application + 6WDQGDUG3DFNDJHG 5HPRWH(YDSRUDWRU

Design VintageNominal Tons

feaTures and benefITs

feaTures and benefITs

wwwDaikinAppliedcom 5 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Condenser Fans and MotorsMultiple direct-drive dynamically balanced propeller fans operate in formed venturi openings at low tip speeds for PD[LPXPHIiquestFLHQFDQGPLQLPXPQRLVHDQGYLEUDWLRQ$heavy-gauge vinyl-coated fan guard protects each fan

Each condenser fan motor (including the optional VFD fan motor) is Totally Enclosed Air Over (TEAO) heavy-duty 3-phase with permanently lubricated ball bearings and inherent RYHUORDGSURWHFWLRQ7KHVHPRWRUVDUHGHVLJQHGVSHFLiquestFDOOIRUoutdoor use

Figure 2 Trailblazertrade with Optional Full Louver Package

ampRQWURO6VWHPThe MicroTechreg III advanced DDC chiller controller surpasses all other microprocessor-based chiller control systems available today This powerful user-friendly control system SURYLGHVWKHAgraveH[LELOLWDQGSHUIRUPDQFHQHHGHGIRUHLWKHUstand-alone unit operation or the controller can be easily tied into the building automation system of choice using the Daikin Open Choicestrade feature Open Choicestrade allows one to choose from open standard protocols such as BACnetreg Modbusreg and LonWorksreg to communicate easily with the building automation system that best meets the facility requirements These optional communications modules are available factory LQVWDOOHGRUFDQEHHDVLOiquestHOGLQVWDOOHG

The MicroTechreg III controllerrsquos design will not only permit WKHFKLOOHUWRUXQPRUHHIiquestFLHQWOEXWZLOODOVRVLPSOLItroubleshooting if a system failure occurs Every MicroTechreg III controller is programmed and tested prior to shipment to help provide a trouble-free start-up

Operator-friendlyThe MicroTechreg III control menu structure is separated into four distinct categories that provide the operator or service technician with a full description of current unit status control parameters and alarms Security protection helps prevent unauthorized changing of the setpoints and unit control parameters

MicroTechreg III control continuously performs important self-diagnostic checks while monitoring system temperatures pressures and protection devices It will automatically shutdown a compressor a refrigerant circuit or the entire unit if a fault occurs The cause of the shutdown will be retained in memory and can be easily displayed in plain English or metric units for operator review In addition to displaying alarm diagnostics the MicroTechreg III chiller controller also provides the operator with a warning of pre-alarm conditions Alarm QRWLiquestFDWLRQGDWDFDQDOVREHSDVVHGWRD$6WKURXJKDQoptional communication module

StagingThe scroll compressors are staged on and off as a function of leaving chilled water temperature Leadlag is automatic and switched based on starts and operating hours

Equipment ProtectionThe unit is protected in three ways

1 alarms that shut the unit down and require manual reset to restore unit operation

2 alarms that shut the unit down and then restart automatically (do not require manual restart)

3 limit alarms that reduce unit capacity in response to some out-of-limit conditions

Shut down alarms activate an alarm signal that can be H[SRUWHGWRDUHPRWHORFDWLRQLPLWDODUPVDFWLYDWHDOLJKWRQthe controller and do not trigger a remote alarm

Building Automation System (BAS) InterfaceThe following BAS protocols are supported

bull BACnetregIPbull BACnetreg MSTPbull LonWorksreg (FTT-10A)bull Modbusreg

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 6 wwwDaikinAppliedcom

feaTures and benefITs

Optional Remote Interface Panel In addition to the unit-mounted user interface provided with MicroTechreg III controls the Trailblazertrade chillers can be individually equipped with a remote user interface It provides convenient access to unit diagnostics and control adjustments without having to access a rooftop or outdoor location One remote panel can be connected to up to eight chillers

Featuresbull Each remote user interface is similar to its unit-mounted

counterpart and offers the same functionality and displaybull Three buttons and a navigating wheel with a 8 line by

30-character display formatbull Digital display of messages in English languagebull All operating conditions system alarms control bull parameters and schedules are monitoredbull ampDQEHZLUHGXSWRIHHWPHWHUVIURPWKHXQLWIRUAgraveH[LELOLWLQSODFLQJHDFKUHPRWHXVHULQWHUIDFHZLWKLQthe building

HQHiquestWVbull Allows access to the user interface for each unit from one

location inside the buildingbull Users need to learn one format because the remote user

interface is identical to the unit-mounted versionbull 1RDGGLWLRQDOiquestHOGFRPPLVVLRQLQJLVUHTXLUHGIRUWKH

remote user interfacebull ampDQEHUHWURiquestWDIWHUXQLWLQVWDOODWLRQbull Is fully compatible with the optional BAS communication

modulesThe current manual for the MicroTechreg III Remote User Interface is available on wwwDaikinAppliedcom

Optional Pump PackageThe on-board integrated chilled water pump package provides LPSRUWDQWEHQHiquestWV

bull Simplify the chilled water system design and installation bull 3URYLGHLQVWDOODWLRQVDYLQJVEUHGXFLQJiquestHOGSLSLQJ

wiring and control costsbull 6DYHYDOXDEOHAgraveRRUVSDFHLQVLGHWKHEXLOGLQJbull Reduce project engineering contentbull Greatly reduce pump operating cost with the optional YDULDEOHAgraveRZSXPS9)

Standard ComponentsSingle Pump Model 4380 single spring inside seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly can be serviced without removing the pump casing from the line

Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and RXWOHWFRQQHFWLRQDQGLQFOXGLQJDAgraveDSSHUYDOYHWRSUHYHQW

recirculation when only one pump is operating An isolation valve is included that allows one pump to operate when the other is removed The pumps are designed for dutystandby not parallel operation All information and performance curves for the single pump arrangement (Model 4380) can be used for the dual pump arrangement (Model 4392)

The package is also is equipped with a ldquoYrdquo type inlet strainer a combination triple-duty outlet valve having a discharge shutoff YDOYHFKHFNYDOYHDQGAgraveRZWKURWWOLQJYDOYHDFRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWYDQHVDQGVWDLQOHVVVWHHOVWUDLQHUZLWKDGLVSRVDEOHiquestQHPHVKVWDUWXSVWUDLQHUDAgraveRZVZLWFKPRXQWHGDQGZLUHGIDFWRUSRZHUDQGFRQWUROwiring interconnecting piping and insulation of all cold surfaces Various tank and connection options are available for iquestHOGPRXQWLQJ

Figure 3 Optional Pump Package Schematic

Dual Vertical Pumps

ldquoYrdquo TypeInlet

Strainer

ChilledWaterInlet

InletGuide Optional

VFDControllers Chilled

WaterOutlet

Triple-DutyOutlet Valve Flow

SwitchDrain Evap Out Press

Gauge Port

PumpPackageControlPanel

Brazed-PlateEvaporator

Evap In PressGauge Port

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 3: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

InTroduCTIon

wwwDaikinAppliedcom 3 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

The Trailblazertrade family of air-cooled scroll chillers continues WKHDLNLQ$SSOLHGOHJDFRIKLJKTXDOLWKLJKHIiquestFLHQFlatest technology and quiet operation These features make the Trailblazertrade family the best overall value in air-cooled packaged chillers available today The Trailblazertrade series offers a wide selection of units from 30 to 180 tons with dual refrigerant circuits available as packaged units with remote evaporators or with an optional pump package

(IiquestFLHQW2SHUDWLRQThe Trailblazertrade units utilize environmentally acceptable R-410A refrigerant and meet the performance requirements RI$6+5$(6WDQGDUGIRUHIiquestFLHQF([FHOOHQWSDUWORDGSHUIRUPDQFHLVDFKLHYHGZLWKIRXURUVL[VFUROOFRPSUHVVRUV+LJKRYHUDOOHIiquestFLHQF ORZHUDQQXDOHQHUJFRVWV

RapidRestorereg and Fast LoadingWhen power has been interrupted the Trailblazertrade has the capability to restore cooling quickly by using RapidRestorereg and Fast Loading These options make Trailblazertrade ideal for mission critical buildings data centers healthcare facilities and manufacturing processes Once power is restored after a power loss duration of up to 180 seconds the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds

$SSOLFDWLRQ)OH[LELOLWTrailblazertrade units are available as packaged chillers or with remote evaporators Information on remote evaporator models and factory-installed pump packages can be found in a separate installation manual available on wwwDaikinAppliedcom

Quiet OperationThe Trailblazertrade units live up to the Daikin Applied reputation for low operating sound levels and make these chillers ldquoneighborhood friendlyrdquo Full load sound pressure levels as low as 60dB without insulation

LEEDreg Points Developed by the US Green Building Council (USGBC) in 1998 Leadership in Energy and Environmental Design (LEEDregLVDQLQWHUQDWLRQDOOUHFRJQL]HGFHUWLiquestFDWLRQSURJUDPand intends to provide building owners and operators a consistent structure for identifying and implementing practical and measurable green building design construction operations and maintenance solutions

For building owners who want to pursue LEEDreg Green Building ampHUWLiquestFDWLRQWKH7UDLOEOD]HUtrade series of air-cooled chillers does qualify for the Energy and Atmosphere Credit 4 Enhanced Refrigerant Management worth 2 points

Air-Cooled Chiller Products

1000 200 300 400 500 600

Pathfinderreg Air-Cooled Screw Compressor ChillerModel AWS bull 170 - 550 RT

Standard High and Premium EfficencyVFD and Remote Evaporator options available

Air-Cooled Scroll Compressor ChillerModel AGZ-B bull 10 - 34 RT

TrailblazerTM Air-Cooled Scroll Compressor ChillerModel AGZ-E bull 30 - 180 RTRemote Evaporator and Pump Package options available

AGZ-E

InTroduCTIon

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 4 wwwDaikinAppliedcom

feaTures and benefITs

CHILLER NOMENCLATURE

A G Z XXX E H

8QLWHVLJQ)HDWXUHVDaikin Trailblazertrade air-cooled chillers are a product of our FRPPLWPHQWWRRIIHUTXLHWUHOLDEOHHQHUJHIiquestFLHQWHTXLSPHQWincorporating high quality compressors and innovative packaging

ConstructionTrailblazertrade chillers are factory-assembled and mounted on a heavy-gauge steel base The base distributes the unit weight for roof loading Their small footprint allows smaller PRXQWLQJSDGVRUVXSSRUWVWUXFWXUHVDQGLVDSOXVIRUUHWURiquestWRUreplacement applications

CompressorsReliable hermetic scroll compressors with cast iron scrolls DQGWKUHH7HAgraveRQreg impregnated bearings are used on the Trailblazertrade chillers to promote longevity

Each model has the ability to modulate its capacity Models with four compressors will have four steps of capacity PRGXODWLRQZKLOHPRGHOVZLWKVL[FRPSUHVVRUVZLOOKDYHVL[steps Compressors stage on depending on the load of the VVWHP7KLVUHVXOWVLQH[FHOOHQWSDUWORDGHIiquestFLHQFDQGreduced annual operating costs

Features include motor temperature protection scroll temperature protection missing phase protection reverse phase protection low control circuit voltage protection short cycling detection and alert Modbusreg communication to system controller operational and fault history storage and LED status display

Evaporator7KHHYDSRUDWRULVDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUFRQVLVWLQJRISDUDOOHOVWDLQOHVVVWHHOSODWHV7KHVHKHDWH[FKDQJHUVSURYLGHH[FHOOHQWKHDWH[FKDQJHHIiquestFLHQFLQDFRPSDFWIRRWSULQWDQGare especially attractive for smaller capacity units Evaporators are designed and constructed according to and listed by Underwriters Laboratories (UL)

Optional Remote Evaporator Units with the optional remote evaporator will have the HYDSRUDWRUVKLSSHGVHSDUDWHOIRUiquestHOGPRXQWLQJDQGSLSLQJWRthe outdoor unit

Condenser CoilsCondenser coils are all aluminum alloy microchannel design ZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifold piping A variety of optional coil materials and coatings are available so that the unit can be constructed to meet almost any environment Packaged unit options include

bull FRSSHUWXEHDOXPLQXPiquestQVWRQPRGHOVRQObull FRSSHUWXEHFRSSHUiquestQVWRQPRGHOVRQObull FRSSHUWXEHDOXPLQXPODFNiquestQVWRQPRGHOVRQObull ElectroFinreg coating can be applied to any coil option

See ldquoCondenser Coil Options and Coating Considerationsrdquo on page 14 for discussion of environmental factors related to material and coating options

Figure 1 Microchannel Coil

Air-Cooled

Global Design

Scroll Compressor

Application + 6WDQGDUG3DFNDJHG 5HPRWH(YDSRUDWRU

Design VintageNominal Tons

feaTures and benefITs

feaTures and benefITs

wwwDaikinAppliedcom 5 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Condenser Fans and MotorsMultiple direct-drive dynamically balanced propeller fans operate in formed venturi openings at low tip speeds for PD[LPXPHIiquestFLHQFDQGPLQLPXPQRLVHDQGYLEUDWLRQ$heavy-gauge vinyl-coated fan guard protects each fan

Each condenser fan motor (including the optional VFD fan motor) is Totally Enclosed Air Over (TEAO) heavy-duty 3-phase with permanently lubricated ball bearings and inherent RYHUORDGSURWHFWLRQ7KHVHPRWRUVDUHGHVLJQHGVSHFLiquestFDOOIRUoutdoor use

Figure 2 Trailblazertrade with Optional Full Louver Package

ampRQWURO6VWHPThe MicroTechreg III advanced DDC chiller controller surpasses all other microprocessor-based chiller control systems available today This powerful user-friendly control system SURYLGHVWKHAgraveH[LELOLWDQGSHUIRUPDQFHQHHGHGIRUHLWKHUstand-alone unit operation or the controller can be easily tied into the building automation system of choice using the Daikin Open Choicestrade feature Open Choicestrade allows one to choose from open standard protocols such as BACnetreg Modbusreg and LonWorksreg to communicate easily with the building automation system that best meets the facility requirements These optional communications modules are available factory LQVWDOOHGRUFDQEHHDVLOiquestHOGLQVWDOOHG

The MicroTechreg III controllerrsquos design will not only permit WKHFKLOOHUWRUXQPRUHHIiquestFLHQWOEXWZLOODOVRVLPSOLItroubleshooting if a system failure occurs Every MicroTechreg III controller is programmed and tested prior to shipment to help provide a trouble-free start-up

Operator-friendlyThe MicroTechreg III control menu structure is separated into four distinct categories that provide the operator or service technician with a full description of current unit status control parameters and alarms Security protection helps prevent unauthorized changing of the setpoints and unit control parameters

MicroTechreg III control continuously performs important self-diagnostic checks while monitoring system temperatures pressures and protection devices It will automatically shutdown a compressor a refrigerant circuit or the entire unit if a fault occurs The cause of the shutdown will be retained in memory and can be easily displayed in plain English or metric units for operator review In addition to displaying alarm diagnostics the MicroTechreg III chiller controller also provides the operator with a warning of pre-alarm conditions Alarm QRWLiquestFDWLRQGDWDFDQDOVREHSDVVHGWRD$6WKURXJKDQoptional communication module

StagingThe scroll compressors are staged on and off as a function of leaving chilled water temperature Leadlag is automatic and switched based on starts and operating hours

Equipment ProtectionThe unit is protected in three ways

1 alarms that shut the unit down and require manual reset to restore unit operation

2 alarms that shut the unit down and then restart automatically (do not require manual restart)

3 limit alarms that reduce unit capacity in response to some out-of-limit conditions

Shut down alarms activate an alarm signal that can be H[SRUWHGWRDUHPRWHORFDWLRQLPLWDODUPVDFWLYDWHDOLJKWRQthe controller and do not trigger a remote alarm

Building Automation System (BAS) InterfaceThe following BAS protocols are supported

bull BACnetregIPbull BACnetreg MSTPbull LonWorksreg (FTT-10A)bull Modbusreg

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 6 wwwDaikinAppliedcom

feaTures and benefITs

Optional Remote Interface Panel In addition to the unit-mounted user interface provided with MicroTechreg III controls the Trailblazertrade chillers can be individually equipped with a remote user interface It provides convenient access to unit diagnostics and control adjustments without having to access a rooftop or outdoor location One remote panel can be connected to up to eight chillers

Featuresbull Each remote user interface is similar to its unit-mounted

counterpart and offers the same functionality and displaybull Three buttons and a navigating wheel with a 8 line by

30-character display formatbull Digital display of messages in English languagebull All operating conditions system alarms control bull parameters and schedules are monitoredbull ampDQEHZLUHGXSWRIHHWPHWHUVIURPWKHXQLWIRUAgraveH[LELOLWLQSODFLQJHDFKUHPRWHXVHULQWHUIDFHZLWKLQthe building

HQHiquestWVbull Allows access to the user interface for each unit from one

location inside the buildingbull Users need to learn one format because the remote user

interface is identical to the unit-mounted versionbull 1RDGGLWLRQDOiquestHOGFRPPLVVLRQLQJLVUHTXLUHGIRUWKH

remote user interfacebull ampDQEHUHWURiquestWDIWHUXQLWLQVWDOODWLRQbull Is fully compatible with the optional BAS communication

modulesThe current manual for the MicroTechreg III Remote User Interface is available on wwwDaikinAppliedcom

Optional Pump PackageThe on-board integrated chilled water pump package provides LPSRUWDQWEHQHiquestWV

bull Simplify the chilled water system design and installation bull 3URYLGHLQVWDOODWLRQVDYLQJVEUHGXFLQJiquestHOGSLSLQJ

wiring and control costsbull 6DYHYDOXDEOHAgraveRRUVSDFHLQVLGHWKHEXLOGLQJbull Reduce project engineering contentbull Greatly reduce pump operating cost with the optional YDULDEOHAgraveRZSXPS9)

Standard ComponentsSingle Pump Model 4380 single spring inside seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly can be serviced without removing the pump casing from the line

Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and RXWOHWFRQQHFWLRQDQGLQFOXGLQJDAgraveDSSHUYDOYHWRSUHYHQW

recirculation when only one pump is operating An isolation valve is included that allows one pump to operate when the other is removed The pumps are designed for dutystandby not parallel operation All information and performance curves for the single pump arrangement (Model 4380) can be used for the dual pump arrangement (Model 4392)

The package is also is equipped with a ldquoYrdquo type inlet strainer a combination triple-duty outlet valve having a discharge shutoff YDOYHFKHFNYDOYHDQGAgraveRZWKURWWOLQJYDOYHDFRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWYDQHVDQGVWDLQOHVVVWHHOVWUDLQHUZLWKDGLVSRVDEOHiquestQHPHVKVWDUWXSVWUDLQHUDAgraveRZVZLWFKPRXQWHGDQGZLUHGIDFWRUSRZHUDQGFRQWUROwiring interconnecting piping and insulation of all cold surfaces Various tank and connection options are available for iquestHOGPRXQWLQJ

Figure 3 Optional Pump Package Schematic

Dual Vertical Pumps

ldquoYrdquo TypeInlet

Strainer

ChilledWaterInlet

InletGuide Optional

VFDControllers Chilled

WaterOutlet

Triple-DutyOutlet Valve Flow

SwitchDrain Evap Out Press

Gauge Port

PumpPackageControlPanel

Brazed-PlateEvaporator

Evap In PressGauge Port

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 4: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 4 wwwDaikinAppliedcom

feaTures and benefITs

CHILLER NOMENCLATURE

A G Z XXX E H

8QLWHVLJQ)HDWXUHVDaikin Trailblazertrade air-cooled chillers are a product of our FRPPLWPHQWWRRIIHUTXLHWUHOLDEOHHQHUJHIiquestFLHQWHTXLSPHQWincorporating high quality compressors and innovative packaging

ConstructionTrailblazertrade chillers are factory-assembled and mounted on a heavy-gauge steel base The base distributes the unit weight for roof loading Their small footprint allows smaller PRXQWLQJSDGVRUVXSSRUWVWUXFWXUHVDQGLVDSOXVIRUUHWURiquestWRUreplacement applications

CompressorsReliable hermetic scroll compressors with cast iron scrolls DQGWKUHH7HAgraveRQreg impregnated bearings are used on the Trailblazertrade chillers to promote longevity

Each model has the ability to modulate its capacity Models with four compressors will have four steps of capacity PRGXODWLRQZKLOHPRGHOVZLWKVL[FRPSUHVVRUVZLOOKDYHVL[steps Compressors stage on depending on the load of the VVWHP7KLVUHVXOWVLQH[FHOOHQWSDUWORDGHIiquestFLHQFDQGreduced annual operating costs

Features include motor temperature protection scroll temperature protection missing phase protection reverse phase protection low control circuit voltage protection short cycling detection and alert Modbusreg communication to system controller operational and fault history storage and LED status display

Evaporator7KHHYDSRUDWRULVDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUFRQVLVWLQJRISDUDOOHOVWDLQOHVVVWHHOSODWHV7KHVHKHDWH[FKDQJHUVSURYLGHH[FHOOHQWKHDWH[FKDQJHHIiquestFLHQFLQDFRPSDFWIRRWSULQWDQGare especially attractive for smaller capacity units Evaporators are designed and constructed according to and listed by Underwriters Laboratories (UL)

Optional Remote Evaporator Units with the optional remote evaporator will have the HYDSRUDWRUVKLSSHGVHSDUDWHOIRUiquestHOGPRXQWLQJDQGSLSLQJWRthe outdoor unit

Condenser CoilsCondenser coils are all aluminum alloy microchannel design ZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifold piping A variety of optional coil materials and coatings are available so that the unit can be constructed to meet almost any environment Packaged unit options include

bull FRSSHUWXEHDOXPLQXPiquestQVWRQPRGHOVRQObull FRSSHUWXEHFRSSHUiquestQVWRQPRGHOVRQObull FRSSHUWXEHDOXPLQXPODFNiquestQVWRQPRGHOVRQObull ElectroFinreg coating can be applied to any coil option

See ldquoCondenser Coil Options and Coating Considerationsrdquo on page 14 for discussion of environmental factors related to material and coating options

Figure 1 Microchannel Coil

Air-Cooled

Global Design

Scroll Compressor

Application + 6WDQGDUG3DFNDJHG 5HPRWH(YDSRUDWRU

Design VintageNominal Tons

feaTures and benefITs

feaTures and benefITs

wwwDaikinAppliedcom 5 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Condenser Fans and MotorsMultiple direct-drive dynamically balanced propeller fans operate in formed venturi openings at low tip speeds for PD[LPXPHIiquestFLHQFDQGPLQLPXPQRLVHDQGYLEUDWLRQ$heavy-gauge vinyl-coated fan guard protects each fan

Each condenser fan motor (including the optional VFD fan motor) is Totally Enclosed Air Over (TEAO) heavy-duty 3-phase with permanently lubricated ball bearings and inherent RYHUORDGSURWHFWLRQ7KHVHPRWRUVDUHGHVLJQHGVSHFLiquestFDOOIRUoutdoor use

Figure 2 Trailblazertrade with Optional Full Louver Package

ampRQWURO6VWHPThe MicroTechreg III advanced DDC chiller controller surpasses all other microprocessor-based chiller control systems available today This powerful user-friendly control system SURYLGHVWKHAgraveH[LELOLWDQGSHUIRUPDQFHQHHGHGIRUHLWKHUstand-alone unit operation or the controller can be easily tied into the building automation system of choice using the Daikin Open Choicestrade feature Open Choicestrade allows one to choose from open standard protocols such as BACnetreg Modbusreg and LonWorksreg to communicate easily with the building automation system that best meets the facility requirements These optional communications modules are available factory LQVWDOOHGRUFDQEHHDVLOiquestHOGLQVWDOOHG

The MicroTechreg III controllerrsquos design will not only permit WKHFKLOOHUWRUXQPRUHHIiquestFLHQWOEXWZLOODOVRVLPSOLItroubleshooting if a system failure occurs Every MicroTechreg III controller is programmed and tested prior to shipment to help provide a trouble-free start-up

Operator-friendlyThe MicroTechreg III control menu structure is separated into four distinct categories that provide the operator or service technician with a full description of current unit status control parameters and alarms Security protection helps prevent unauthorized changing of the setpoints and unit control parameters

MicroTechreg III control continuously performs important self-diagnostic checks while monitoring system temperatures pressures and protection devices It will automatically shutdown a compressor a refrigerant circuit or the entire unit if a fault occurs The cause of the shutdown will be retained in memory and can be easily displayed in plain English or metric units for operator review In addition to displaying alarm diagnostics the MicroTechreg III chiller controller also provides the operator with a warning of pre-alarm conditions Alarm QRWLiquestFDWLRQGDWDFDQDOVREHSDVVHGWRD$6WKURXJKDQoptional communication module

StagingThe scroll compressors are staged on and off as a function of leaving chilled water temperature Leadlag is automatic and switched based on starts and operating hours

Equipment ProtectionThe unit is protected in three ways

1 alarms that shut the unit down and require manual reset to restore unit operation

2 alarms that shut the unit down and then restart automatically (do not require manual restart)

3 limit alarms that reduce unit capacity in response to some out-of-limit conditions

Shut down alarms activate an alarm signal that can be H[SRUWHGWRDUHPRWHORFDWLRQLPLWDODUPVDFWLYDWHDOLJKWRQthe controller and do not trigger a remote alarm

Building Automation System (BAS) InterfaceThe following BAS protocols are supported

bull BACnetregIPbull BACnetreg MSTPbull LonWorksreg (FTT-10A)bull Modbusreg

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 6 wwwDaikinAppliedcom

feaTures and benefITs

Optional Remote Interface Panel In addition to the unit-mounted user interface provided with MicroTechreg III controls the Trailblazertrade chillers can be individually equipped with a remote user interface It provides convenient access to unit diagnostics and control adjustments without having to access a rooftop or outdoor location One remote panel can be connected to up to eight chillers

Featuresbull Each remote user interface is similar to its unit-mounted

counterpart and offers the same functionality and displaybull Three buttons and a navigating wheel with a 8 line by

30-character display formatbull Digital display of messages in English languagebull All operating conditions system alarms control bull parameters and schedules are monitoredbull ampDQEHZLUHGXSWRIHHWPHWHUVIURPWKHXQLWIRUAgraveH[LELOLWLQSODFLQJHDFKUHPRWHXVHULQWHUIDFHZLWKLQthe building

HQHiquestWVbull Allows access to the user interface for each unit from one

location inside the buildingbull Users need to learn one format because the remote user

interface is identical to the unit-mounted versionbull 1RDGGLWLRQDOiquestHOGFRPPLVVLRQLQJLVUHTXLUHGIRUWKH

remote user interfacebull ampDQEHUHWURiquestWDIWHUXQLWLQVWDOODWLRQbull Is fully compatible with the optional BAS communication

modulesThe current manual for the MicroTechreg III Remote User Interface is available on wwwDaikinAppliedcom

Optional Pump PackageThe on-board integrated chilled water pump package provides LPSRUWDQWEHQHiquestWV

bull Simplify the chilled water system design and installation bull 3URYLGHLQVWDOODWLRQVDYLQJVEUHGXFLQJiquestHOGSLSLQJ

wiring and control costsbull 6DYHYDOXDEOHAgraveRRUVSDFHLQVLGHWKHEXLOGLQJbull Reduce project engineering contentbull Greatly reduce pump operating cost with the optional YDULDEOHAgraveRZSXPS9)

Standard ComponentsSingle Pump Model 4380 single spring inside seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly can be serviced without removing the pump casing from the line

Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and RXWOHWFRQQHFWLRQDQGLQFOXGLQJDAgraveDSSHUYDOYHWRSUHYHQW

recirculation when only one pump is operating An isolation valve is included that allows one pump to operate when the other is removed The pumps are designed for dutystandby not parallel operation All information and performance curves for the single pump arrangement (Model 4380) can be used for the dual pump arrangement (Model 4392)

The package is also is equipped with a ldquoYrdquo type inlet strainer a combination triple-duty outlet valve having a discharge shutoff YDOYHFKHFNYDOYHDQGAgraveRZWKURWWOLQJYDOYHDFRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWYDQHVDQGVWDLQOHVVVWHHOVWUDLQHUZLWKDGLVSRVDEOHiquestQHPHVKVWDUWXSVWUDLQHUDAgraveRZVZLWFKPRXQWHGDQGZLUHGIDFWRUSRZHUDQGFRQWUROwiring interconnecting piping and insulation of all cold surfaces Various tank and connection options are available for iquestHOGPRXQWLQJ

Figure 3 Optional Pump Package Schematic

Dual Vertical Pumps

ldquoYrdquo TypeInlet

Strainer

ChilledWaterInlet

InletGuide Optional

VFDControllers Chilled

WaterOutlet

Triple-DutyOutlet Valve Flow

SwitchDrain Evap Out Press

Gauge Port

PumpPackageControlPanel

Brazed-PlateEvaporator

Evap In PressGauge Port

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 5: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

feaTures and benefITs

wwwDaikinAppliedcom 5 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Condenser Fans and MotorsMultiple direct-drive dynamically balanced propeller fans operate in formed venturi openings at low tip speeds for PD[LPXPHIiquestFLHQFDQGPLQLPXPQRLVHDQGYLEUDWLRQ$heavy-gauge vinyl-coated fan guard protects each fan

Each condenser fan motor (including the optional VFD fan motor) is Totally Enclosed Air Over (TEAO) heavy-duty 3-phase with permanently lubricated ball bearings and inherent RYHUORDGSURWHFWLRQ7KHVHPRWRUVDUHGHVLJQHGVSHFLiquestFDOOIRUoutdoor use

Figure 2 Trailblazertrade with Optional Full Louver Package

ampRQWURO6VWHPThe MicroTechreg III advanced DDC chiller controller surpasses all other microprocessor-based chiller control systems available today This powerful user-friendly control system SURYLGHVWKHAgraveH[LELOLWDQGSHUIRUPDQFHQHHGHGIRUHLWKHUstand-alone unit operation or the controller can be easily tied into the building automation system of choice using the Daikin Open Choicestrade feature Open Choicestrade allows one to choose from open standard protocols such as BACnetreg Modbusreg and LonWorksreg to communicate easily with the building automation system that best meets the facility requirements These optional communications modules are available factory LQVWDOOHGRUFDQEHHDVLOiquestHOGLQVWDOOHG

The MicroTechreg III controllerrsquos design will not only permit WKHFKLOOHUWRUXQPRUHHIiquestFLHQWOEXWZLOODOVRVLPSOLItroubleshooting if a system failure occurs Every MicroTechreg III controller is programmed and tested prior to shipment to help provide a trouble-free start-up

Operator-friendlyThe MicroTechreg III control menu structure is separated into four distinct categories that provide the operator or service technician with a full description of current unit status control parameters and alarms Security protection helps prevent unauthorized changing of the setpoints and unit control parameters

MicroTechreg III control continuously performs important self-diagnostic checks while monitoring system temperatures pressures and protection devices It will automatically shutdown a compressor a refrigerant circuit or the entire unit if a fault occurs The cause of the shutdown will be retained in memory and can be easily displayed in plain English or metric units for operator review In addition to displaying alarm diagnostics the MicroTechreg III chiller controller also provides the operator with a warning of pre-alarm conditions Alarm QRWLiquestFDWLRQGDWDFDQDOVREHSDVVHGWRD$6WKURXJKDQoptional communication module

StagingThe scroll compressors are staged on and off as a function of leaving chilled water temperature Leadlag is automatic and switched based on starts and operating hours

Equipment ProtectionThe unit is protected in three ways

1 alarms that shut the unit down and require manual reset to restore unit operation

2 alarms that shut the unit down and then restart automatically (do not require manual restart)

3 limit alarms that reduce unit capacity in response to some out-of-limit conditions

Shut down alarms activate an alarm signal that can be H[SRUWHGWRDUHPRWHORFDWLRQLPLWDODUPVDFWLYDWHDOLJKWRQthe controller and do not trigger a remote alarm

Building Automation System (BAS) InterfaceThe following BAS protocols are supported

bull BACnetregIPbull BACnetreg MSTPbull LonWorksreg (FTT-10A)bull Modbusreg

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 6 wwwDaikinAppliedcom

feaTures and benefITs

Optional Remote Interface Panel In addition to the unit-mounted user interface provided with MicroTechreg III controls the Trailblazertrade chillers can be individually equipped with a remote user interface It provides convenient access to unit diagnostics and control adjustments without having to access a rooftop or outdoor location One remote panel can be connected to up to eight chillers

Featuresbull Each remote user interface is similar to its unit-mounted

counterpart and offers the same functionality and displaybull Three buttons and a navigating wheel with a 8 line by

30-character display formatbull Digital display of messages in English languagebull All operating conditions system alarms control bull parameters and schedules are monitoredbull ampDQEHZLUHGXSWRIHHWPHWHUVIURPWKHXQLWIRUAgraveH[LELOLWLQSODFLQJHDFKUHPRWHXVHULQWHUIDFHZLWKLQthe building

HQHiquestWVbull Allows access to the user interface for each unit from one

location inside the buildingbull Users need to learn one format because the remote user

interface is identical to the unit-mounted versionbull 1RDGGLWLRQDOiquestHOGFRPPLVVLRQLQJLVUHTXLUHGIRUWKH

remote user interfacebull ampDQEHUHWURiquestWDIWHUXQLWLQVWDOODWLRQbull Is fully compatible with the optional BAS communication

modulesThe current manual for the MicroTechreg III Remote User Interface is available on wwwDaikinAppliedcom

Optional Pump PackageThe on-board integrated chilled water pump package provides LPSRUWDQWEHQHiquestWV

bull Simplify the chilled water system design and installation bull 3URYLGHLQVWDOODWLRQVDYLQJVEUHGXFLQJiquestHOGSLSLQJ

wiring and control costsbull 6DYHYDOXDEOHAgraveRRUVSDFHLQVLGHWKHEXLOGLQJbull Reduce project engineering contentbull Greatly reduce pump operating cost with the optional YDULDEOHAgraveRZSXPS9)

Standard ComponentsSingle Pump Model 4380 single spring inside seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly can be serviced without removing the pump casing from the line

Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and RXWOHWFRQQHFWLRQDQGLQFOXGLQJDAgraveDSSHUYDOYHWRSUHYHQW

recirculation when only one pump is operating An isolation valve is included that allows one pump to operate when the other is removed The pumps are designed for dutystandby not parallel operation All information and performance curves for the single pump arrangement (Model 4380) can be used for the dual pump arrangement (Model 4392)

The package is also is equipped with a ldquoYrdquo type inlet strainer a combination triple-duty outlet valve having a discharge shutoff YDOYHFKHFNYDOYHDQGAgraveRZWKURWWOLQJYDOYHDFRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWYDQHVDQGVWDLQOHVVVWHHOVWUDLQHUZLWKDGLVSRVDEOHiquestQHPHVKVWDUWXSVWUDLQHUDAgraveRZVZLWFKPRXQWHGDQGZLUHGIDFWRUSRZHUDQGFRQWUROwiring interconnecting piping and insulation of all cold surfaces Various tank and connection options are available for iquestHOGPRXQWLQJ

Figure 3 Optional Pump Package Schematic

Dual Vertical Pumps

ldquoYrdquo TypeInlet

Strainer

ChilledWaterInlet

InletGuide Optional

VFDControllers Chilled

WaterOutlet

Triple-DutyOutlet Valve Flow

SwitchDrain Evap Out Press

Gauge Port

PumpPackageControlPanel

Brazed-PlateEvaporator

Evap In PressGauge Port

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 6: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 6 wwwDaikinAppliedcom

feaTures and benefITs

Optional Remote Interface Panel In addition to the unit-mounted user interface provided with MicroTechreg III controls the Trailblazertrade chillers can be individually equipped with a remote user interface It provides convenient access to unit diagnostics and control adjustments without having to access a rooftop or outdoor location One remote panel can be connected to up to eight chillers

Featuresbull Each remote user interface is similar to its unit-mounted

counterpart and offers the same functionality and displaybull Three buttons and a navigating wheel with a 8 line by

30-character display formatbull Digital display of messages in English languagebull All operating conditions system alarms control bull parameters and schedules are monitoredbull ampDQEHZLUHGXSWRIHHWPHWHUVIURPWKHXQLWIRUAgraveH[LELOLWLQSODFLQJHDFKUHPRWHXVHULQWHUIDFHZLWKLQthe building

HQHiquestWVbull Allows access to the user interface for each unit from one

location inside the buildingbull Users need to learn one format because the remote user

interface is identical to the unit-mounted versionbull 1RDGGLWLRQDOiquestHOGFRPPLVVLRQLQJLVUHTXLUHGIRUWKH

remote user interfacebull ampDQEHUHWURiquestWDIWHUXQLWLQVWDOODWLRQbull Is fully compatible with the optional BAS communication

modulesThe current manual for the MicroTechreg III Remote User Interface is available on wwwDaikinAppliedcom

Optional Pump PackageThe on-board integrated chilled water pump package provides LPSRUWDQWEHQHiquestWV

bull Simplify the chilled water system design and installation bull 3URYLGHLQVWDOODWLRQVDYLQJVEUHGXFLQJiquestHOGSLSLQJ

wiring and control costsbull 6DYHYDOXDEOHAgraveRRUVSDFHLQVLGHWKHEXLOGLQJbull Reduce project engineering contentbull Greatly reduce pump operating cost with the optional YDULDEOHAgraveRZSXPS9)

Standard ComponentsSingle Pump Model 4380 single spring inside seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly can be serviced without removing the pump casing from the line

Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and RXWOHWFRQQHFWLRQDQGLQFOXGLQJDAgraveDSSHUYDOYHWRSUHYHQW

recirculation when only one pump is operating An isolation valve is included that allows one pump to operate when the other is removed The pumps are designed for dutystandby not parallel operation All information and performance curves for the single pump arrangement (Model 4380) can be used for the dual pump arrangement (Model 4392)

The package is also is equipped with a ldquoYrdquo type inlet strainer a combination triple-duty outlet valve having a discharge shutoff YDOYHFKHFNYDOYHDQGAgraveRZWKURWWOLQJYDOYHDFRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWYDQHVDQGVWDLQOHVVVWHHOVWUDLQHUZLWKDGLVSRVDEOHiquestQHPHVKVWDUWXSVWUDLQHUDAgraveRZVZLWFKPRXQWHGDQGZLUHGIDFWRUSRZHUDQGFRQWUROwiring interconnecting piping and insulation of all cold surfaces Various tank and connection options are available for iquestHOGPRXQWLQJ

Figure 3 Optional Pump Package Schematic

Dual Vertical Pumps

ldquoYrdquo TypeInlet

Strainer

ChilledWaterInlet

InletGuide Optional

VFDControllers Chilled

WaterOutlet

Triple-DutyOutlet Valve Flow

SwitchDrain Evap Out Press

Gauge Port

PumpPackageControlPanel

Brazed-PlateEvaporator

Evap In PressGauge Port

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 7: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

feaTures and benefITs

ZZZDLNLQ$SSOLHGFRP amp$775$$=(5trade MODEL AGZ CHILLERS

Optional Variable Flow VFDThe operating cost savings resulting from using variable FKLOOHGZDWHUAgraveRZYLDDSXPS9)LVZHOONQRZQQWKHSDVWhowever its usage has been somewhat limited by the cost DQGXQFHUWDLQWRIiquestHOGLQVWDOOLQJWKHUHTXLUHGVVWHPSUHVVXUHdifferential sensors

DLNLQ$SSOLHGFDQQRZRIIHUAgraveRZFRQWUROWKURXJKWKHSXPS9)ZLWKRXWWKHQHHGIRUH[WHUQDOSUHVVXUHVHQVRUVQDGGLWLRQto the sensorless operation there are three other selectable operating modes

BAS Input7KHSXPSVSHHGDQGVVWHPAgraveRZZLOOEHcontrolled from a customer-supplied BAS input signal

Remote Sensor Control The VFD is wired to a pressure sensor mounted in the chilled water piping system This is the standard VFD control when a sensorless VFD is not used

RFDOO6HOHFWHGampRQVWDQW6SHHGampRQWUROProvides manual control of the pump speed overriding any current automatic speed control

Consult the current version of the installation manual for additional detailed information It is available from the local DLNLQ$SSOLHGVDOHVRIiquestFHRURQwwwDaikinAppliedcom

2SHUDWLQJDQG6WDQGELPLWV

Table 1 Operating Limits

0D[LPXPVWDQGEDPELHQWWHPSHUDWXUH 130degF (54degC)

0D[LPXPRSHUDWLQJDPELHQWWHPSHUDWXUH 105degF (41degC)

-with optional high ambient package (see ldquoHigh Ambient Operationrdquo on page 14) 125degF (52degC)

Minimum operating ambient temperature (standard control) 32degF (0degC)

-with optional low ambient control (see ldquoLow Ambient Operationrdquo on page 14) -10degF (-23degC)

Leaving chilled water temperature 40degF to 65degF (4degC to 18degC)

HDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHVZLWKDQWLIUHH]H1RWHWKDWLQFDVHVRIKLJKDPELHQWtemperature the lowest leaving water temperature settings may be outside of the chiller operating envelope consult Daikin Toolstrade to ensure chiller is capable of the required lift

15degF to 65degF (-9degC to 18degC)

Operating chilled water delta-T range 6degF to 16degF (33degC to 89degC)

0D[LPXPHYDSRUDWRURSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH )amp0D[LPXPHYDSRUDWRUQRQRSHUDWLQJLQOHWAgraveXLGWHPSHUDWXUH 100degF (38degC)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 8: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 8 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

8QLW3ODFHPHQWTrailblazertrade units are for outdoor applications and can be mounted either on a roof or at ground level For roof mounted applications install the unit on a steel channel or I-beam frame to support the unit above the roof For ground level applications install the unit on a substantial base that will not VHWWOH8VHDRQHSLHFHFRQFUHWHVODEZLWKIRRWLQJVH[WHQGHGbelow the frost line Be sure the foundation is level within 05rdquo (13 mm) over its length and width The foundation must be strong enough to support the unit weight - see the Dimensions section starting on page 28

Service ClearanceSides

bull 30-70 Ton Models Minimum of 4 feet (12 meters)bull 75-180 Ton Models It is highly recommended to

provide a minimum of 8 feet (24 meters) on one side to allow for coil replacement Coils can be removed from the top allowing a minimum of 4 feet (12 meters) of side clearance however the unit performance may be derated

Control Panel End

bull All Models Minimum of 4 feet (12 meters)Opposite Control Panel End

bull 30-70 Ton Models with Microchannel Coils Minimum RIIHHWPHWHUV

bull All Other Models Minimum of 4 feet (12 meters)

Figure 4 Service Clearance

Spacing Requirements6XIiquestFLHQWFOHDUDQFHPXVWEHPDLQWDLQHGEHWZHHQWKHXQLWand adjacent walls or other units to allow the required unit DLUAgraveRZWRUHDFKWKHFRLOV)DLOXUHWRGRVRZLOOUHVXOWLQDcapacity reduction and an increase in power consumption No obstructions are allowed above the unit at any height

Graphs on the following pages give the minimum clearance for different types of installations and also capacity reduction and power increase if closer spacing is used

Case 1 Building or Wall on One Side of Unit For models AGZ030-100E maintain a 4 feet minimum from a wall of any height

For models AGZ110-180E maintain a 6 feet minimum from a wall of any height

Figure 5 Building or Wall on One Side of Unit

Case 2 Two Units Side-by-SideFor all models there must be a minimum of 4 feet between two units placed side-by-side however performance may be affected at this distance )LJXUH and Figure 8 depict Case 2 performance adjustments as the distance between two units increases

Figure 6 Two Units Side-by-Side Minimum = 4 ft (12 m)

Minimum = 4 ft (12 m)

Minimum = 4 ft(12 m)

Minimum = 75 ft (23 m) for models 030-070

with Microchannel Coils

Con

trol P

anel

Minimum = 4 ft (12 m) for all other models

75-180 Ton Models 8ft (24 m) recommended on one side

Heightof

Wall

DistanceBetween

WallandUnit

D

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 9: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 9 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 7 Case 2 - Full Load Capacity Reduction

Figure 8 Case 2 - Power Increase

Case 3 Three or More Units Side-by-SideFor all models there must be a minimum of 4 feet between any two units placed side-by-side however performance may be affected at this distance Figure 10 and Figure 11 depict Case 3 performance adjustments as the distance between two units increases

NOTE Data in Figure 10 and Figure 11 is for the middle unit with a unit on each side See Case 2 adjustment factors for the two outside units

Figure 9 Three or More Units Side-by-Side

Figure 10 Case 3 - Full Load Capacity Reduction

Figure 11 Case 3 - Power Increase

00

05

10

15

20

25

30

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWVIW

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

05

10

15

20

25

30

35

40

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

4 5 6 8

ampDSDFLW

5HGXFWLR

Q

LVWDQFHHWZHHQ8QLWV

)XOORDGampDSDFLW5HGXFWLRQ

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

00

10

20

30

40

50

60

80

4 5 6 8

P

ower

Incr

ease

LVWDQFHHWZHHQ8QLWVIW

Power Increase

AGZ030-035E AGZ040-( $=-100E

AGZ0110-130E AGZ140-180E

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 10: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 10 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Case 4 Open Screening Walls Decorative screening walls are often used to help conceal a unit either on grade or on a rooftop When possible design these walls such that the combination of their open area and distance from the unit do not require performance adjustment It is assumed that the wall height is equal to or less than the unit height when mounted on its base support If the wall height is greater than the unit height see Case 5 Pit Installation The distance from the sides of the unit to the side walls must EHVXIiquestFLHQWIRUVHUYLFHVXFKDVRSHQLQJFRQWUROSDQHOGRRUVFor uneven wall spacing the distance from the unit to each wall can be averaged providing no distance is less than 4 feet Values are based on walls on all four-sides

Figure 12 Case 4 Adjustment Factor

Case 5 Pit Installation Pit installations can cause operating problems resulting from DLUUHFLUFXODWLRQDQGUHVWULFWLRQDQGUHTXLUHFDUHWKDWVXIiquestFLHQWair clearance is provided safety requirements are met and service access is provided Pit covers must have abundant open area at least equal to the chiller footprint A solid wall surrounding a unit is substantially a pit and this data should be used

Steel grating is sometimes used to cover a pit to prevent accidental falls or trips into the pit The grating material and installation design must be strong enough to prevent such accidents yet provide abundant open area to avoid recirculation problems Have any pit installation reviewed by the Daikin Applied sales representative prior to installation to HQVXUHLWKDVVXIiquestFLHQWDLUAgraveRZFKDUDFWHULVWLFVDQGDSSURYHGEthe installation design engineer to avoid risk of accident

Figure 13 Case 5 - Pit Installation

Models AGZ030-070E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 4 feet 5 feet and 6 feet

Figure 14 Case 5 - Full Load Capacity Reduction (AGZ030E-070E)

Figure 15 Case 5 - Power Increase (AGZ030-070E)

30

40

50

60

80

0 10 20 30 40 50

LVWDQFHIURP

DOOWR8QLWIW

Open Wall Area

Wall Free Area vs Distance

AGZ030-( $=-100E AGZ110-130E AGZ140-180E

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ030-070E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 11: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 11 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Models AGZ075-130E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 5 feet 6 feet and 8 feet

Figure 16 Case 5 - Full Load Capacity Reduction (AGZ075-130E)

Figure 17 Case 5 - Power Increase (AGZ075-130E)

Models AGZ140-180E7KHampDVHiquestJXUHVIRUPRGHOV$=(VKRZDGMXVWPHQWfactors for pitwall heights of 6 feet 8 feet and 10 feet

Figure 18 Case 5 - Full Load Capacity Reduction (AGZ140-180E)

Figure 19 Case 5 - Power Increase (AGZ140-180E)

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ075-130E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

0 8 10 12 13 14

ampDSDFLW

5HGXFWLR

Q

Depth of Pit Wall Height (ft)

)XOORDGampDSDFLW5HGXFWLRQ$=-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

00

10

20

30

40

50

60

80

90

0 8 10 12 13 14

P

ower

Incr

ease

Depth of Pit Wall Height (ft)

Power Increase (AGZ140-180E)

LVWDQFH I W LVWDQFH I W LVWDQFH I W

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 12: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 12 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water Piping IMPORTANT 3LSLQJGHVLJQPXVWEHSURYLGHGEDTXDOLiquestHGArchitect or Systems HVAC Design Engineer familiar with piping design as well as local codes and regulations The manufacturer recommendations provided here are to be used as a general guide but do not replace system design EDTXDOLiquestHGSURIHVVLRQDO)ROORZDOOLQVWUXFWLRQVDQGrecommendations for chilled water piping in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

Design the water piping so the chilled water circulating pump discharges into the evaporator inlet A cleanable perforated basket strainer with 0062-inch perforations and 41 open area must be installed in the water line just prior to the inlet of the evaporator See the ldquoOptional Inlet Strainerrdquo section for more information

$ZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHGLQWKHKRUL]RQWDOSLSLQJ

of the supply (evaporator outlet) water line to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7KHAgraveRZVZLWFKPDEHRUGHUHGDVDIDFWRULQVWDOOHGRSWLRQDiquestHOGLQVWDOOHGNLWRUPDEHVXSSOLHGDQGLQVWDOOHGLQWKHiquestHOG6HH2SWLRQVDQGAccessories page 43 for more information)

Vibration eliminators are recommended in both the supply and return water lines Pressure gauges must be installed in the inlet and outlet water lines to the evaporator

Piping for units with brazed-plate evaporators must have a drain and vent connection provided in the bottom of the lower connection pipe and to the top of the upper connection pipe respectively see Figure 20 These evaporators do not have drain or vent connections due to their construction

Insulate chilled water piping to reduce heat loss and prevent condensation For information on freeze protection see ldquoEvaporator Freeze Protectionrdquo on page 13

Figure 20 Typical Piping Brazed-Plate Evaporator

Optional Inlet Strainer$QLQOHWZDWHUVWUDLQHUNLWLVDYDLODEOHDVDIDFWRURUiquestHOGinstalled accessory sized per Table 2 and with the pressure drop shown in Figure 22 This pressure drop must be accounted for in the total system pressure drop The kit consists of

bull (1) Y-type strainer with 304 stainless steel 40 or 41 open area perforated basket grooved pipe connections and strainer cap

bull ([WHQVLRQSLSHZLWK6FKUDGHUiquestWWLQJVWKDWFDQEHXVHGIRUDSUHVVXUHJDXJHDQGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK7KHSLSHSURYLGHVVXIiquestFLHQWFOHDUDQFHIURPWKHevaporator for strainer basket removal

bull (1) frac12-inch blowdown valvebull (2) Grooved clamps

Figure 21 Factory Installed Strainer

AirVent

FlowSwitch

VibrationEliminators

Drain

Outlet

Inlet

PIsolationValves

Strainer

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 13: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 13 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 2 Strainer Data

Trailblazertrade Model Strainer Size in (mm)

Strainer Weight lbs (kg)

030-070E 25 (64) 18 (82)

075-130E 23 (104)

140-180E 40 (102) 42 (191)

Figure 22 Strainer Pressure Drop

Water Flow Limitations Constant Flow7KHHYDSRUDWRUAgraveRZUDWHVDQGSUHVVXUHGURSVVKRZQLQFigure RQSDJH and Table 14 on page 23 are for full load GHVLJQSXUSRVHV7KHPD[LPXPAgraveRZUDWHDQGSUHVVXUHGURSare based on a 6degF temperature drop Flow rates above the PD[LPXPYDOXHVZLOOUHVXOWLQXQDFFHSWDEOHWHPSHUDWXUHDQGSUHVVXUHGURSVDQGFDQFDXVHH[FHVVLYHHURVLRQSRWHQWLDOOleading to failure

7KHPLQLPXPAgraveRZDQGSUHVVXUHGURSLVEDVHGRQDIXOOORDGHYDSRUDWRUWHPSHUDWXUHGURSRI)(YDSRUDWRUAgraveRZUDWHVEHORZWKHPLQLPXPYDOXHVFDQUHVXOWLQODPLQDUAgraveRZFDXVLQJfreeze-up problems scaling and poor control

Variable Flow5HGXFLQJHYDSRUDWRUAgraveRZLQSURSRUWLRQWRORDGFDQUHGXFHVVWHPSRZHUFRQVXPSWLRQ7KHUDWHRIAgraveRZFKDQJHVKRXOGEHDPD[LPXPRISHUFHQWRIWKHAgraveRZSHUPLQXWH)RUH[DPSOHLIWKHPD[LPXPGHVLJQAgraveRZLVJSPDQGLWZLOOEHUHGXFHGWRDAgraveRZRIJSPWKHFKDQJHLQAgraveRZLVJSP7HQSHUFHQWRI200 gpm equals 20 gpm change per minute or a minimum of WKUHHPLQXWHVWRJRIURPPD[LPXPWRGHVLUHGAgraveRZ7KHZDWHUAgraveRZWKURXJKWKHHYDSRUDWRUPXVWUHPDLQEHWZHHQWKHPLQLPXPDQGPD[LPXPYDOXHVOLVWHGLQTable 14 on page 23IAgraveRZdrops below the minimum allowable large reductions in heat WUDQVIHUFDQRFFXUIWKHAgraveRZH[FHHGVWKHPD[LPXPUDWHH[FHVVLYHSUHVVXUHGURSDQGWXEHHURVLRQFDQRFFXU

6VWHPDWHU9ROXPHampRQVLGHUDWLRQVAll chilled water systems need adequate time to recognize a load change respond to the change and stabilize to avoid undesirable short cycling of the compressors or loss of temperature control In air conditioning systems the potential IRUVKRUWFFOLQJXVXDOOH[LVWVZKHQWKHEXLOGLQJORDGIDOOVbelow the minimum chiller plant capacity or on close-coupled systems with very small water volumes Some of the things the designer should consider when looking at water volume are the minimum cooling load the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown a rule of thumb of ldquogallons of water volume equal to two to WKUHHWLPHVWKHFKLOOHGZDWHUJSPAgraveRZUDWHacuteLVRIWHQXVHG$storage tank may have to be added to the system to reach the recommended system volume

Evaporator Freeze ProtectionEvaporator freeze-up can be a concern in the application of DLUFRROHGZDWHUFKLOOHUVLQDUHDVH[SHULHQFLQJEHORZIUHH]LQJtemperatures To protect against freeze-up insulation and an electric heater are furnished with the evaporator Models 030 WKURXJKKDYHDQH[WHUQDOSODWHKHDWHUDQGWKHUPRVWDW7KLVhelps protect the evaporator down to -20degF (-29degC) ambient air temperature The evaporator heater cable is factory wired WRWKHYROWFRQWUROFLUFXLWWUDQVIRUPHULQWKHFRQWUROER[A 115V power source for the heater and controls may also EHVXSSOLHGIURPDVHSDUDWHSRZHUIHHGWRPD[LPL]HXQLWSURWHFWLRQLIGHVLUHG5HIHUWRWKHiquestHOGZLULQJGLDJUDPRQpage 36 for additional information on supplying a separate 115V power feed

Operation of the heaters is automatic through the ambient sensing thermostat that energizes the evaporator heaters for protection against freeze-up Unless the evaporator is drained in the winter or contains an adequate concentration of anti-freeze the disconnect switch to the evaporator heater must not be open

Although the evaporator is equipped with freeze protection LWGRHVQRWSURWHFWZDWHUSLSLQJH[WHUQDOWRWKHXQLWRUWKHevaporator itself if there is a power failure or heater burnout or if the chiller is unable to control the chilled water pumps Use one of the following recommendations for additional freeze protection

1 If the unit will not be operated during the winter drain the HYDSRUDWRUDQGFKLOOHGZDWHUSLSLQJDQGAgraveXVKZLWKJOFRO

2 Add a glycol solution to the chilled water system Burst SURWHFWLRQVKRXOGEHDSSUR[LPDWHO)EHORZPLQLPXPdesign ambient temperature

3 QVXODWHWKHH[SRVHGSLSLQJ

4 Add thermostatically controlled heat by wrapping the lines with heat tape

01

10

100

1000

100 1000 10000

Pres

sure

Dro

p ( f

t)

Flow Rate (gpm)25 in 30 in 40 in

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 14: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 14 wwwDaikinAppliedcom

applICaTIon ConsIderaTIons

Chilled Water PumpIt is important that the chilled water pumps be wired to and controlled by the chillerrsquos microprocessor The chiller controller has the capability to selectively send the signal to a pump relay (by others) to start pump A or B or automatically alternate pump selection and also has standby operation capability The controller will energize the pump whenever at least one circuit on the chiller is enabled to run whether there is a call for cooling or not This helps ensure proper unit start-up sequence The pump will also be turned on when the water temperature goes below the Freeze Setpoint for longer WKDQDVSHFLiquestHGWLPHWRKHOSSUHYHQWHYDSRUDWRUIUHH]HXSConnection points are shown in the Field Wiring Diagram on page 36 and SDJH

amp$8721Adding glycol or draining the system is the recommended method of freeze protection If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing catastrophic evaporator failure may occur

Failure to allow pump control by the chiller may cause the following problems

1 If any device other than the chiller attempts to start the FKLOOHUZLWKRXWiquestUVWVWDUWLQJWKHSXPSWKHFKLOOHUZLOOORFNout on the No Flow alarm and require manual reset

2 If the chiller evaporator water temperature drops below the ldquoFreeze setpointrdquo the chiller will attempt to start the water pumps to avoid evaporator freeze If the chiller does not have the ability to start the pumps the chiller ZLOODODUPGXHWRODFNRIZDWHUAgraveRZ

3 If the chiller does not have the ability to control the pumps and the water system is not drained in temperatures below freezing the chiller may be subject to catastrophic evaporator failure due to freezing The freeze rating of the evaporator is based on the immersion heater and pump operation The immersion heater itself may not be able to properly protect the evaporator from freezing without circulation of water

Low Ambient OperationCompressor staging is adaptively determined by system load ambient air temperature and other inputs to the MicroTechreg III control The standard minimum ambient temperature is 32degF (0degC) A low ambient option with fan VFD allows operation down to -10degF (-23degC) The minimum ambient temperature is based on still conditions where the wind is not greater than 5 mph Greater wind velocities will result in reduced discharge pressure increasing the minimum operating ambient temperature Field installed louvers are available and recommended to help allow the chiller to operate effectively down to the ambient temperature for which it was designed

High Ambient OperationTrailblazertrade units for high ambient operation (105degF to 125degF 40degC to 52degC) require the addition of the optional high ambient SDFNDJHWKDWLQFOXGHVDVPDOOIDQZLWKDiquestOWHULQWKHDLULQWDNHto cool the control panel

All units with the optional VFD low ambient fan control automatically include the high ambient option

Condenser Coil Options and Coating ConsiderationsThe standard coils on the Trailblazertrade chiller are an all DOXPLQXPDOORPLFURFKDQQHOGHVLJQZLWKDVHULHVRIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZPLFURFKDQQHOVODHUHGbetween the refrigerant manifolds The microchannel coils are GHVLJQHGWRZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDZDWHUfog (SWAAT) test (ASTM G85-02) at 120degF (49degC) with 0 iquestQORVVDQGGHYHORSQROHDNV7KHDOODOXPLQXPPLFURFKDQQHOcoils provide superior longevity and durability for non-corrosive applications

Should the standard microchannel coil not meet the corrosion requirements for the application additional coil options are available

$OXPLQXPiquestQFRSSHUWXEHFRLOV consist of 38 inch (10 mm) seamless copper tubes mechanically bonded into plate-type DOXPLQXPiquestQV7KHiquestQVKDYHIXOOGUDZQFROODUVWRFRPSOHWHOFRYHUWKHWXEHV7KHDOXPLQXPiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWGXUDELOLWLQQRQFRUURVLYHHQYLURQPHQWVDQGDGGVWKHEHQHiquestWRIHDVHRIiquestHOGUHSDLU7KLVRSWLRQLVRQODYDLODEOHIRUPRGHOV$=(

Figure 23 Aluminum FinCopper Tube Coils

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 15: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

applICaTIon ConsIderaTIons

wwwDaikinAppliedcom 15 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

BlackFintradeFRLOVLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDGXUDEOHSKHQROLFHSR[FRDWLQJQDGGLWLRQWRSURYLGLQJDGXUDEOHFRDWLQJRQWKHiquestQPDWHULDOWKHODFN)LQtrade coils provide DQGHSR[EDUULHUEHWZHHQWKHDOXPLQXPiquestQVWRFNDQGWKHcopper tube to prevent the galvanic corrosion that can occur between the dissimilar metals This option will provide a 1000+ KRXUVDOWVSUDUDWLQJSHU$6707KHODFN)LQtrade option provides an economical solution for enhanced protection in mildly corrosive environments This option is only available IRUPRGHOV$=(

ampRSSHUiquestQFRLOV consist of 38 inch (10 mm) seamless copper WXEHVPHFKDQLFDOOERQGHGLQWRSODWHWSHFRSSHUiquestQV7KHiquestQVhave full drawn collars to completely cover the tubes Since the iquestQDQGWKHWXEHPDWHULDOVDUHVLPLODUWKHRSSRUWXQLWIRUJDOYDQLFFRUURVLRQLVHOLPLQDWHG7KHFRSSHUiquestQFRSSHUWXEHRSWLRQSURYLGHVH[FHOOHQWORQJHYLWLQPDULQHHQYLURQPHQWVhowever this option is not well suited for industrial or chemical atmospheric contamination This option is only available for PRGHOV$=(

Table 3 CoilCoating Selection Matrix

Coil Option Non-Corrosive1 8QSROOXWHG0DULQH2 Industrial3 Combined Marine-Industrial4

Standard Microchannel +++ - - -

Aluminum FinCopper Tube5 +++ - - -

Copper FinCopper Tube5 +++ +++ - -

BlackFintrade5 +++ + + -

ElectroFinreg +++ +++ +++ ++

NOTE 1 1RQFRUURVLYHHQYLURQPHQWVPDEHHVWLPDWHGEWKHDSSHDUDQFHRIH[LVWLQJHTXLSPHQWLQWKHLPPHGLDWHDUHDZKHUHWKH

chiller is to be placed

2 0DULQHHQYLURQPHQWVVKRXOGWDNHLQWRFRQVLGHUDWLRQSUR[LPLWWRWKHVKRUHDVZHOODVSUHYDLOLQJZLQGGLUHFWLRQ

3 Industrial contaminants may be general or localized based on the immediate source of contamination (ie diesel fumes due WRSUR[LPLWWRDORDGLQJGRFN

4 ampRPELQHGPDULQHLQGXVWULDODUHLQAgraveXHQFHGESUR[LPLWWRVKRUHSUHYDLOLQJZLQGVJHQHUDODQGORFDOVRXUFHVRIcontamination

5 $YDLODEOHIRUPRGHOV$=(RQO

ElectroFinregFRLOFRDWLQJLVDZDWHUEDVHGH[WUHPHOAgraveH[LEOHDQGGXUDEOHHSR[SROPHUFRDWLQJXQLIRUPODSSOLHGWRDOOcoil surfaces through a multi-step submerged electrostatic coating process ElectroFinreg condenser coils provide a KRXUVDOWVSUDUHVLVWDQFHSHU$670applied to both the coil and the coil frames The ElectroFinreg coated coils also receive a UV-resistant urethane top-coat to provide superior resistance to degradation from direct sunlight This coil coating option provides the best overall protection against corrosive marine industrial or combined atmospheric contamination This coating option may be applied to any of the untreated coil options offered to SURYLGHH[FHOOHQWORQJHYLWDQGUHVLVWDQFHWRFRUURVLRQ

Figure 24 ElectroFinreg Coil Coating

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 16: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 16 wwwDaikinAppliedcom

sound daTa

Background6RXQGOHYHOVFDQEHDVLPSRUWDQWDVXQLWFRVWDQGHIiquestFLHQFThe inherently quiet scroll compressors used in Trailblazertrade chillers are coupled with precision engineering for industry-leading sound levels

AHRI has established standards to provide uniform methods for the determination of the sound levels of equipment For ODUJHDLUFRROHGFKLOOHUVLWLV$+56WDQGDUG6RXQGRatings of Large Outdoor Refrigeration and Air-Conditioning Equipment Data contained in this section are in accordance with this standard

ldquoArdquo WeightingSound values may be represented several ways One of the more common forms is the ldquoArdquo weighted value which adds or VXEWUDFWVDVSHFLiquestFDPRXQWWRHDFKFHQWHUEDQGIUHTXHQFthen logarithmically adds the values to establish a single value The ldquoArdquo scale is used to represent how the human ear receives sound The amount added in each frequency band directly corresponds to how sensitive the human ear is to each frequency

Table 4 ldquoArdquo Scale Relative Response to Human Ear

)UHTXHQFILQ+]

315 63 125 250 500 1K 2K 4K 8K 16K

dB(A) iacute iacute iacute iacute iacute 0 +12 +10 iacute iacute

Sound Pressure Levels - Full LoadSound pressure is the sound level that can be measured at some distance from the source Sound pressure varies with distance from the source and depends on the surroundings )RUH[DPSOHDEULFNZDOODUHAgraveHFWLYHVXUIDFHORFDWHGfeet from a unit will affect the sound pressure measurements differently than a brick wall at 20 feet Sound pressure is measured in decibels (dB)

All sound pressure data in the following pages are considered WSLFDORIZKDWFDQEHPHDVXUHGLQDIUHHiquestHOGZLWKDKDQGKHOGVRXQGPHWHULQWKHDEVHQFHRIDQQHDUEUHAgraveHFWLYHVXUIDFHVH[FHSWWKHAgraveRRUXQGHUWKHXQLW6RXQGSUHVVXUHOHYHOVDUHmeasured at 30 feet (10 meters) from the side of the unit at 100 load and standard AHRI conditions (per AHRI standard 550590-2003) of 95degF (35degC) ambient air temperature and )ampOHDYLQJHYDSRUDWRUZDWHUWHPSHUDWXUHVIRUDLUcooled units

Sound Power LevelsSound power is a calculated quantity and cannot be measured directly like sound pressure Sound power is not dependent on the surrounding environment or distance from the source as is sound pressure It can be thought of as basic sound level emanating from the unit without consideration of distance or obstructions Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB Acoustical consultants sometimes use sound power octave band data to perform a detailed acoustical analysis

Figure 25 Sound Power vs Sound Pressure

The data in Table 6 on page 18 and Table 8 on page 19 SUHVHQWVRXQGSRZHUOHYHOVSHU$+56WDQGDUGsup36RXQGRating of Large Outdoor Refrigerating and Air Conditioning Equipmentrdquo This standard was developed to establish uniform methods of determining the sound power radiated by large outdoor equipment Measurements are taken over a prescribed area around the unit and the data is mathematically calculated to give the sound power dB

Sound Reduction due to Distance from WKH8QLWThe distance between a source of sound and the location of the sound measurement plays an important role in minimizing sound problems Sound pressure can be calculated at any distance from the unit if sound power and ldquoQrdquo the directionality factor are known ldquoQrdquo is a dimensionless number that FRPSHQVDWHVIRUWKHWSHRIVRXQGUHAgraveHFWLRQIURPWKHVRXUFH)RUH[DPSOHDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRRWKHUUHAgraveHFWLYHVXUIDFHVRUDWWHQXDWLRQGXHWRJUDVVVQRZHWFEHWZHHQVRXUFHDQGUHFHLYHUZLOOKDYH4 6HHFigure 26 for GHiquestQLWLRQVRI4 4 DQG4

Sound Source(Sound Power)

Sound Pressure

Measured at 30ft (10m)

sound daTa

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 17: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

sound daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 26 sup34acute5HAgraveHFWLYH6RXUFHVOOXVWUDWLRQ

Once sound power and ldquoQrdquo are known sound pressure at any distance from the unit can be calculated using the following equation

Lp = Lw - (20 log r) + (10 log Q) - 05Where

S VRXQGSUHVVXUH

Z VRXQGSRZHU

U GLVWDQFHIURPXQLWLQIHHW

4 GLUHFWLRQDOLWIDFWRU

LWK4 8QLWVXVSHQGHGLQVSDFHWKHRUHWLFDOFRQGLWLRQWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) -05LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 25LWK4 IRUDXQLWVLWWLQJRQDAgraveDWURRIRUJURXQGZLWKRQHDGMDFHQWYHUWLFDOZDOODVDUHAgraveHFWLYHVXUIDFHWKHHTXDWLRQVLPSOLiquestHVWR

Lp = Lw - (20 log r) + 55

Results for typical distances and the two most usual cases of ldquoQrdquo are tabulated in Table 5

Table 5 dB Conversion of Sound Power to Pressure

Distance from Sound Source

ft (m)

DB Reduction from Sound Power at the Source to Sound Pressure at Referenced Distance

Q=2 Q=4

30 (9) 240

50 (15) 316 285

351 320

100 (30) 345

150 (46) 411 380

200 (61) 436 405

300 (91) 440

Sound Data Notes1 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLV$ZHLJKWHG

2 Sound pressure data taken at 30 feet (9 meters) from VLGHRIXQLW4 XQLWRQAgraveDWVXUIDFHZLWKQRDGMDFHQWwall

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 18: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 18 wwwDaikinAppliedcom

sound daTa

Table 6 60 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHDWAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 7 60 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 92 91 88 83 68 88 85

35 92 91 89 83 68 88 85

40 92 91 90 88 84 69 89 85

45 93 92 91 89 85 69 90

50 93 93 91 89 85 69 90

55 93 93 93 89 86 81 91

60 94 93 94 89 86 81 91

65 95 94 94 89 81 92

70 95 95 94 89 81 92

75 95 95 95 89 81 92 88

80 95 95 95 89 81 92 88

90 94 95 92 91 89 83 81 81 93 88

100 93 95 92 92 89 83 82 82 94 88

110 93 96 92 92 90 84 84 82 95 88

120 93 96 92 92 90 84 84 82 95 89

130 94 93 93 91 85 85 84 96 89

140 95 98 93 94 93 86 85 89

150 96 99 95 94 95 90 88 85 99 91

160 96 98 96 94 91 88 85 91

170 96 98 96 94 91 88 88 85 91

180 96 98 96 94 91 88 88 85 91

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 65 64 61 60 56 51 46 41 61 58

35 65 64 62 60 56 51 46 41 61 58

40 65 64 63 61 52 42 62 58

45 66 65 64 62 58 52 42 63 60

50 66 66 64 62 58 52 42 63 60

55 66 66 66 62 59 54 49 44 64 60

60 66 62 59 54 49 44 64 60

65 68 62 60 54 49 44 65 60

70 68 68 62 60 54 49 44 65 60

75 68 68 68 62 60 54 49 44 65 61

80 66 63 63 63 62 56 53 53 66 61

90 64 62 56 54 54 61

100 66 68 65 65 62 56 55 61

110 66 69 65 61 55 55 55 61

120 68 65 61 59 60 68 61

130 68 68 64 61 60 60 55 68 62

140 68 69 69 65 61 60 61 56 69 63

150 69 65 62 62 62 56 64

160 69 69 64 61 60 58 64

170 69 69 64 61 60 58 64

180 69 69 64 61 61 58 64

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 19: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

sound daTa

wwwDaikinAppliedcom 19 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 8 50 Hz Sound Power

NOTE 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Table 9 50 Hz Sound Pressure (at 30 feet from side of unit)

NOTE Data at 1) 30 feet (9 meters) from side of unit 4 XQLWRQDAgraveDWURRIRUJURXQGZLWKQRDGMDFHQWZDOO 2FWDYHEDQGUHDGLQJVDUHAgraveDWGRYHUDOOLVsup3$acuteZHLJKWHG

Model 2FWDYHDQGDWampHQWHU)UHTXHQF Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 89 88 85 84 80 65 85 82

35 89 88 85 84 80 65 85 82

40 89 88 86 84 80 65 85 82

45 89 88 85 81 66 86 84

50 90 89 88 86 82 66 84

55 90 90 88 86 82 66 84

60 90 90 90 86 83 68 88 84

65 91 90 91 86 83 68 88 84

70 92 91 91 86 84 68 89 84

75 92 92 91 86 84 68 89 85

80 92 92 91 86 84 68 89 85

90 91 92 88 88 86 80 90 85

100 90 92 88 89 86 80 91 85

110 90 93 88 89 81 81 91 85

120 90 93 88 89 81 81 91 86

130 91 94 89 90 88 82 82 80 92 86

140 92 95 89 91 90 84 83 81 94 86

150 93 96 91 91 92 85 81 95 88

160 92 94 92 90 84 84 81 93 88

170 93 95 93 90 84 84 82 94 88

180 93 95 93 91 88 85 84 82 94 88

Model 2FWDYHDQGDWampHQWHU)UHTXHQFIWIURPXQLW Overall A-Weighted

63 125 250 500 1000 2000 4000 8000 Without Sound Insulation

With Sound Insulation

30 62 61 58 53 48 43 38 58 55

35 62 61 59 53 48 43 38 58 55

40 62 61 60 58 54 49 44 39 59 55

45 63 62 61 59 55 49 44 39 60

50 63 63 61 59 55 49 44 39 60

55 63 63 63 59 56 51 46 41 61

60 64 63 64 59 56 51 46 41 61

65 65 64 64 59 51 46 41 62

70 65 65 64 59 51 46 41 62

75 65 65 65 59 51 46 41 62 58

80 63 60 60 60 59 53 50 49 63 58

90 64 64 64 61 59 53 51 51 64 58

100 63 65 62 62 59 53 54 52 64 58

110 63 66 64 62 58 52 52 52 64 58

120 65 64 64 62 58 56 54 65 58

130 64 65 65 61 58 52 65 59

140 65 66 66 62 58 58 53 66 60

150 66 68 62 59 59 59 53 60

160 66 68 66 64 61 58 55 61

170 66 68 66 64 61 58 55 61

180 66 68 66 64 61 58 58 55 61

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 20: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 20 wwwDaikinAppliedcom

seleCTIon proCedure

Selection with Inch-Pound (IP) unitsTrailblazertrade chillers are ideal for a wide range of applications and operating conditions The performance tables beginning on page 22 cover the standing application rating conditions of the current AHRI Standard 550590 The tables are based on a 10degF (55degC) temperature drop through the evaporator Adjustment factors for applications having other than a 10degF (55degC) drop can be found in Table 12 on page 21

The minimum leaving chilled water temperature setpoint without glycol is 40degF (4degC) For brine selections see Table 10 and Table 11 on page 21 for glycol adjustment factors Ratings are based on a 00001 ft2[KU[)WXIRXOLQJIDFWRULQthe evaporator at sea level operation For other fouling factors different Delta-Ts or altitude correction factors see Table 12 on page 21 For applications outside the catalog ratings please contact a local Daikin Applied sales representative

Selection exampleGiven

bull 50 tons minimumbull 95degF ambient temperaturebull 120 gpm 54degF to 44degF chilled waterbull 00001 evaporator fouling factor

1 From Table 13 on page 22 an AGZ055E at the given conditions will produce 518 tons with a unit kW input of 596 and a unit EER of 104

2 Use the following formula to calculate any unknown elements (water only)

3 Determine the evaporator pressure drop Using )LJXUHon page 23 enter at about 124 gpm and follow up to the AGZ055E line intersect Read horizontally to obtain an evaporator pressure drop of 13 feet of water

Selection example using ethylene glycolGiven

bull 44 tons minimumbull 95degF ambient air temperaturebull 54degF - 44degF chilled water temperaturebull 00001 evaporator fouling factorbull Protect from freezing down to 0degF

1 From Table 10 on page 21 select an ethylene glycol concentration of 40 to protect against freezing at 0degF

2 At 40 ethylene glycol the adjustment factors are

bull ampDSDFLW bull N bull 30 bull 3UHVVXUHURS

3 Select the AGZ050E from Table 13 on page 22 and correct with 40 ethylene glycol factors

4 ampRUUHFWFDSDFLW WRQV WRQV5 ampRUUHFWN N N

6 ampDOFXODWHFKLOOHGZDWHUAgraveRZbull DWHUAgraveRZFRUUHFWHGFDSDFLW

bull OFROAgraveRZDWVROXWLRQ

Determine the evaporator pressure drop Using )LJXUHon page 23 enter at 1285 gpm (water) and follow up to the AGZ050E line intersect Read horizontally to obtain an HYDSRUDWRUSUHVVXUHGURSRIIHHWampRUUHFWWKHSUHVVXUHGURSIRUVROXWLRQ [IHHW IHHWIRUHWKOHQHglycol using Table 10 on page 21

Selection with SI unitsUse the SI tables and the same procedures as with IP units Use the following formula to calculate any missing elements (water only)

ݏݐ ൈ ʹͶοሺܨሻ ൌ

ͶǤ͵ݏݐ ൈ ʹͶͳͲιܨ ൌ ͳͳ͵Ǥͷ

ͳǤͳ͵ʹ ൈ ͳͳ͵Ǥͷ ൌ ͳʹͺǤͷ

ͳͶǤͳͺ ൈ οሺܥሻ ൌ

ͳ ݏ

seleCTIon proCedure

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 21: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

performanCe daTa

wwwDaikinAppliedcom 21 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

(WKOHQH3URSOHQHOFRO)DFWRUVTrailblazertradeXQLWVFDQRSHUDWHZLWKDOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHUDQJHRI)ampWR)amp$JOFROVROXWLRQLVUHTXLUHGZKHQOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHis below 40degF (4degC) The use of glycol will reduce the performance of the unit depending on concentration

NOTE Ethylene and propylene glycol ratings are outside the scope of the current AHRI Standard 550590 FHUWLiquestFDWLRQSURJUDP

Table 10 Ethylene Glycol Correction Factors

Table 11 Propylene Glycol Correction Factors

Altitude Correction FactorsPerformance tables are based at sea level Elevations other than sea level affect the performance of the unit The decreased air density will reduce condenser capacity consequently reducing the unitrsquos performance For performance at elevations other than sea level refer to Table 12

Evaporator Temperature Drop FactorsPerformance tables are based on a 10degF (5degC) temperature drop through the evaporator Adjustment factors for applications with temperature ranges from 6degF to 16degF (33degC to 89degC) are in Table 12 Temperature drops outside this 6degF to 16degF (33degC to 89degC) range can affect the control systemrsquos capability to maintain acceptable control and are not recommended

Table 12 Capacity and Power Derates

NOTE Derate factors for models with remote evaporators can be found in the current installation manual at wwwDaikinAppliedcom

$+5ampHUWLiquestFDWLRQPerformance on all 60Hz standard packaged models is FHUWLiquestHGSHU$+5VWDQGDUGampKLOOHUVWKDWDUH+]RUthat have an optional remote evaporator are outside the scope of the AHRI rating program

EGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0999 1028 1090

20 18 0993 1059 1216

30 -14 0995 1094

40 -22 0981 0993 1132

50 -28 -33 099 1811

PGFreeze Point

ampDSDFLW Power Flow Pressure Dropdeg F deg C

10 26 -33 0995 0998 1011 1025

20 19 0988 0995 103 115

30 9 -14 0992 1056

40 -5 -22 0968 0988 109

50 -33 0955 0983 1131 2128

AltitudeWater

Delta T

Fouling Factor

00001(00176)

000025(0044)

000075(0132)

000175(0308)

degF degC Cap Power Cap Power Cap Power Cap Power

Sea Level

6 33 0978 0993 0975 0991 0963 0987 0940 0980

8 44 0989 0996 0986 0994 0973 0990 0950 0983

10 56 1000 1000 0996 0999 0984 0994 0961 0987

12 67 1009 1003 1005 1001 0993 0997 0969 0990

14 77 1018 1004 1014 1003 1002 0999 0978 0991

16 89 1025 1007 1021 1006 1009 1001 0985 0994

2000 feet

6 33 0977 1001 0973 1000 0961 0996 0938 0989

8 44 0987 1006 0984 1004 0971 1000 0948 0993

10 56 0998 1009 0995 1007 0982 1003 0959 0996

12 67 1007 1011 1004 1010 0991 1006 0967 0998

14 77 1014 1014 1011 1013 0998 1009 0974 1001

16 89 1022 1016 1018 1014 1005 1010 0981 1003

4000 feet

6 33 0973 1011 0970 1010 0957 1006 0935 0998

8 44 0984 1014 0980 1013 0968 1009 0945 1001

10 56 0995 1019 0991 1017 0979 1013 0955 1005

12 67 1004 1021 1000 1020 0987 1016 0964 1008

14 77 1011 1024 1007 1023 0994 1018 0971 1011

16 89 1018 1027 1014 1026 1002 1021 0978 1014

6000 feet

6 33 0969 1021 0966 1020 0954 1016 0931 1008

8 44 0980 1026 0977 1024 0964 1020 0942 1013

10 56 0989 1029 0986 1027 0973 1023 0950 1015

12 67 0998 1033 0995 1031 0982 1027 0959 1020

14 77 1007 1036 1004 1034 0991 1030 0967 1022

16 89 1014 1037 1011 1036 0998 1031 0974 1024

performanCe daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 22: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 22 wwwDaikinAppliedcom

performanCe daTa

Table 13 60 Hz Part Load Performance Data (IP) Table 13 continued 60 Hz Part Load Performance Data (IP)

Model Load Tons kW EER IPLV

030

100 281 330 102

151 211 194 130

50 141 104 163

25 180

035

100 349 410 102

154 262 239 131

50 126

25 56 188

040

100 392 412 114

165 294 245 144

50 196 132

25 98 62 191

045

100 426 465 110

164 320 268 143

50 213 143

25 66 193

050

100 483 546 106

160 362 313 139

50 242

25 121 189

055

100 518 596 104

159 389 346 135

50 259 180

25 130 196

060

100 649 105

158 428 140

50 285 201

25 143 93 183

065

100 665 106

158 440 381 139

50 294

25 98 180

070

100 651 101

158 488 433 135

50 326

25 163 104 188

075

100 802 109

158 141

50 365 262

25 182 116 189

080

100 854 108

158 496 140

50 386 169

25 193 125 186

090

100 844 964 105

157 632 554

50 422 300 169

25 211 136 186

100

100 1149 102

154 136

50 489 354 166

25 245 164

Model Load Tons kW EER IPLV

110

100 1239 104

155 804 136

50 536 388 166

25 268 181

120

100 1188 1396 102

154 891 136

50 594 435 164

25 198 180

130

100 1499 101

154 942 831 136

50 629 460 164

25 314 208 182

140

100 1389 106

157 1041 916 136

50 694 491

25 226 184

150

100 1462 1661 106

156 1096 960

50 526

25 365 239 183

160

100 1545 104

156 1158 1000 139

50 564 164

25 386 188

170

100 1651 101

157 1238 139

50 825 166

25 413 263 188

180

100 2180

161 1318 1116 142

50 614

25 439 191

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 23: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

pressure drop daTa

wwwDaikinAppliedcom 23 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 27 Pressure Drop Curves

Table 14 Pressure Drop Data

A

A

A

B

B

B

C

C

C

D

D

D

E

E

E

F

F

F

G

G

G

H

H

H

I

I

I

J

J

J

K

K

K

L

L

L

M

M

M

N

N

N

O

O

O

P

P

P

Q

Q

Q

S

S

S

T

T

T

8

8

8

1

10

100

10 100 1000

Diff

eren

tial P

ress

ure

(ft)

Flow Rate (gpm)

ABCDEFGHIJKLMNOPQRST8

9DULDEOH)ORZ6VWHP2QO )L[HG)ORZ6VWHP2QO )L[HGDQG9DULDEOH)ORZ6VWHPV

Minimum Flow Rate Minimum Flow Rate Nominal Flow Rate Maximum Flow Rate

Curve Ref Model

IP SI IP SI IP SI IP SI

GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa GPM DP ft lps DP kpa

A 030E 51 422 40 120 98 43 294 1124 260

B 035E 335 24 21 524 56 33 838 53 409 1396 364 88

C 040E 25 23 58 926 142 58 425 1544 1126

D 045E 409 23 26 68 639 53 40 158 1022 132 65 394 344 108

E 050E 464 29 62 46 185 1159 152 453 1932 400 122 1196

F 055E 23 31 55 49 163 1243 134 400 356 131 1062

G 060E 540 23 34 69 843 54 53 161 1349 131 85 393 2248 142 1036

H 065E 555 24 35 55 139 88 414 2312 366 146 1093

I 070E 615 30 39 88 961 69 61 206 1538 169 504 2564 445 162 1330

J 075E 698 12 44 36 1091 28 69 84 69 110 205 2908 182 183 543

K 080E 12 1154 29 86 1846 116 213 189 194 566

L 090E 801 14 51 43 1251 34 101 2002 83 126 248 3336 221 210 661

M 100E 924 13 58 40 1443 32 91 95 2309 146 233 3848 208 243 622

N 110E 1020 14 64 42 1595 33 101 99 2551 82 161 244 4252 216 268 646

O 120E 1131 15 45 36 111 88 264 235

P 130E 1195 15 44 1868 35 118 104 2988 86 189 4980 229 314 683

Q 140E 1289 81 51 2015 40 121 3223 99 203 264 339

R 150E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

S 160E 1436 18 91 55 2244 44 142 130 3590 108 324 5984 291

T 170E 1541 19 56 2408 45 152 134 3852 112 243 334 6420 302 405 902

8 180E 1648 23 104 69 53 162 159 4121 128 260 383 6868 335 433 999

pressure drop daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 24: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 24 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 15 Physical Data - AGZ030E - AGZ040E

Table 16 Physical Data - AGZ045E - AGZ055E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ030E AGZ035E AGZ040Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 15 (168) 15 (168) 14 (64) 14 (64) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 90 90 100 100 100 100 100 100

Oil charge per Compressor oz (g)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410) 85 (2410)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 249 (23) 249 (23) 249 (23) 249 (23) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 84 (381) 91 (413) 98 (445)Water Volume gallons (liters) 22 (84) 24 (92)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ045E AGZ050E AGZ055Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 120 120 120 120 130 130 130 130 130 130 150 150

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 15 (11) 15 (11))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 112 (501) 133 (603)Water Volume gallons (liters) 26 (98) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

physICal daTa - paCkaged unITs

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 25: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

physICal daTa - paCkaged unITs

wwwDaikinAppliedcom 25 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 17 Physical Data - AGZ060E - AGZ070E

Table 18 Physical Data - AGZ075E - AGZ090E

NOTE 1) Models 030-060 )DQ0RWRUKS IRU9+]9+]9+] All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ060E AGZ065E AGZ070Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATAUnit Operating Charge lbs (kg) - Sealed Filter Drier 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) 21 (95) - Replaceable Core Filter Drier 23 (105) 23 (105) 23 (105) 23 (105) 23 (105) 23 (105)COMPRESSORS SCROLL HERMETICNominal HP 150 150 150 150 150 150 150 150 150 200 150 200

Oil charge per Compressor oz (g)110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 110 (3119) 152 (4309) 152 (4309)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46) 498 (46)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) (for 208V230V460V60Hz)1 15 (11) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 48000 (22654) 48000 (22654)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 150 (681) 150 (681) 150 (681)Water Volume gallons (liters) 28 (106) 28 (106) 28 (106)Grooved inletoutlet connection in (mm)2 25 (65) 25 (65) 25 (65)0D[DWHU3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)0D[5HIULJHUDQW3UHVVXUHSVLN3D 653 (4502) 653 (4502) 653 (4502)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ075E AGZ080E AGZ090Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 46 (209) 46 (209) 46 (209) 46 (209) 48 (218) 48 (218)

COMPRESSORS SCROLL HERMETICNominal HP 200 200 200 150 200 200 200 200 250 200 200 250

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495) 152 (4495)152 (4495) 110 (3253) 152 (4495) 152 (4495) 152 (4495) 152 (4495)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 244 (111) 266 (121) 266 (121)Water Volume gallons (liters) Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 26: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 26 wwwDaikinAppliedcom

physICal daTa - paCkaged unITs

Table 19 Physical Data - AGZ100E - AGZ120E

Table 20 Physical Data - AGZ130E - AGZ150E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ100E AGZ110E AGZ120Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 49 (223) 49 (223) 64 (291) 64 (291) 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 250 250 250 300 300 250 250 300 300 300 300 300

Oil charge per Compressor oz (g)152 (4495) 152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead)

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 106 (99) 106 (99)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 339 (154) 369 (168)Water Volume gallons (liters) 106 (41) 114 (44) 125 (48)Grooved inletoutlet connection in (mm)2 0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ130E AGZ140E AGZ150Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 65 (295) 65 (295)

COMPRESSORS SCROLL HERMETICNominal HP 300 300 300 400 400 300 300 400 400 300 400 400

Oil charge per Compressor oz (g)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 4 Stages (If Circuit is in Lead) 0-23-46-69-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 106 (99) 106 (99) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 406 (185) 435 (198) 465 (211)Water Volume gallons (liters) 138 (53) 161 (61)Grooved inletoutlet connection in (mm)2 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 27: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

physICal daTa - paCkaged unITs

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 21 Physical Data - AGZ160E - AGZ180E

NOTE 1) All Models)DQ530 IRU9+]$LUAgraveRZ [+]$LUAgraveRZIRU9+] 2) Water connection shown is nominal pipe size UD]HGSODWHHYDSRUDWRUVGRQRWKDYHGUDLQRUYHQWFRQQHFWLRQVLQWHJUDOWRWKHKHDWH[FKDQJHU7KHFRQQHFWLRQVPXVWEHLQVWDOOHGLQWKHiquestHOGLQOHWDQG outlet piping as shown in Piping Section in the current version of the Installation and Operation Manual available on wwwDaikinAppliedcom

3KVLFDODWDAGZ-E (Microchannel Packaged Chiller)

AGZ160E AGZ170E AGZ180Eamp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87 amp5amp87

BASIC DATA

Unit Operating Charge lbs (kg) - Replaceable Core Filter Drier 80 (363) 80 (363) 80 (363) 80 (363)

COMPRESSORS SCROLL HERMETICNominal HP 25 25 30 30 25 25 25 25 30 30 30 30 30 30 30 30 30 30

Oil charge per Compressor oz (g)152 (4495) 213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299)152 (4495) 152 (4495) 152 (4495) 213 (6299) 213 (6299) 213 (6299)213 (6299) 152 (4495) 213 (6299) 213 (6299) 213 (6299) 213 (6299)

Staging 6 Stages (If Circuit is in Lead) 0-16-34-50-68-84-100

0-19-34-50-66-81-100

82-100

0-18-32-50-65-82-100

83-100

83-100

CONDENSER MICROCHANNELCoil Inlet Face Area sq ft (sq m) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124) 1324 (124)Rows DeepFins Per Inch 1 21 1 21 1 21 1 21 1 21 1 21CONDENSER FANS DIRECT DRIVE PROPELLER of Fans per Circuit - Fan Diameter in (mm) Fan Motor hp (kW) 20 (15) 20 (15) 20 (15))DQ0RWRU530IRUDOO+]1 1140 1140 1140$LUAgraveRZFIPOV1 112900 (53283) 112900 (53283) 112900 (53283)EVAPORATOR BRAZED PLATE3

Dry Weight lbs (kg) 465 (211) 494 (225) 531 (241)Water Volume gallons (liters) 161 (61) Grooved inletoutlet connection in (mm)2 40 (102) 40 (102) 40 (102)0D[DWHU3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)0D[5HIULJHUDQW3UHVVXUHSVLN3D 650 (4482) 650 (4482) 650 (4482)

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 28: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 28 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 28 AGZ030E - AGZ035E

1822

718

209

82

REF

2389

941

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B 153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

BLAN

K PA

NEL

S AR

EU

SED

ON

UN

IT S

IDES

SL

OPE

D 5

0 C

OIL

S U

SED

ON

INSI

DE

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

337

133

1721

678

337

133

52 20

52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

L1 -

L4

LIFT

ING

LOCA

TIO

NS

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

30E

2947

(133

7)29

60 (1

343)

1011

(459

)79

9 (3

62)

635

(288

)50

2 (2

28)

980

(445

)77

5 (3

52)

673

(305

)53

2 (2

41)

AG

Z035

E28

73 (1

303)

2887

(131

0)10

51 (4

77)

861

(391

)52

8 (2

40)

433

(196

)10

05 (4

56)

824

(374

)58

1 (2

64)

476

(216

)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

XY

ZA

GZ0

30E

389

(988

)44

5 (1

130)

409

(103

9)A

GZ0

35E

397

(100

8)45

5 (1

156)

381

(968

)

UNIT

MO

DEL

CG

LO

CA

TIO

N IN

(MM

)PA

CK

AG

E U

NIT

S W

ITH

MIC

RO

CH

AN

NEL

CO

ILS

AB

AG

Z030

E24

2 (6

15)

29

(74)

25

(64)

AG

Z035

E23

5 (5

97)

22

(56)

25

(64)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

0

33454711

AG

Z-E

FA

NS

dImensIons and WeIghTs - paCkaged unITs

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 29: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 29 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 29 AGZ040E - AGZ070E

1822

718

208

82

REF

2389

940

2546

100

2

165

65

370

146

2X

64 25

497

196

1094

431

22 875

KN

OCK

OU

TSFI

ELD

CO

NTR

OL

CON

NEC

TIO

NS

QTY

3

2235

880

DIM

ENSI

ON

DO

ES N

OT

INCL

UD

ELI

FTIN

G B

RACK

ETS

B

153

60A

X

Y

CON

TRO

LBO

X

FRO

NT

LEFT

CO

RNER

PO

ST

PURP

OSE

LY

HID

DEN

EVAP

WYE

-STR

AIN

ER

REQ

UIR

ED(F

ACTO

RY O

R FI

ELD

IN

STAL

LED

OPT

ION

)

[22]

Oslash8

75PO

WER

EN

TRY

KNO

CKO

UTS

FRO

NT

OR

RIG

HT

SID

E

635

250

266

105

797

314

506

199

2396

943

506

199

51 20 80 32

152

60

127

50

Z

[22]

Oslash8

75 K

NO

CKO

UTS

POW

ER E

NTR

Y KN

OCK

OU

TSAR

E O

N T

HE

OPP

OSI

TESI

DE

OF

CON

TRO

L BO

X

EVAP

W

ATER

INLE

T

EVAP

W

ATER

OU

TLET

L1 L2L3 L4

L1 -

L4

LIFT

ING

LOCA

TIO

NS

337

133

1721

678

337

133

52 20 52 20

19 750

QTY

4

M1

- M4

ISO

LATO

R M

OU

NTI

NG

HO

LE L

OCA

TIO

NS

ON

BO

TTO

M S

URF

ACE

OF

UN

IT B

ASE

M3

M1 M2

M4

L4L2L1

L3

COM

PRES

SORS

CIRC

UIT

2

COM

PRES

SORS

CIRC

UIT

1

TOP

VIEW

WIT

H

COIL

S AN

D

FAN

S RE

MO

VED

XY

ZA

GZ0

40E

398

(101

1)45

9 (1

166)

384

(975

)A

GZ0

45E

389

(988

)44

5 (1

130)

412

(104

7)A

GZ0

50E

391

(993

)44

9 (1

141)

412

(104

7)A

GZ0

55E

391

(993

)44

8 (1

138)

412

(104

7)A

GZ0

60E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

65E

392

(996

)44

6 (1

133)

411

(104

4)A

GZ0

70E

368

(935

)41

8 (1

062)

426

(108

2)

PAC

KA

GE

UN

ITS

WIT

H M

ICR

OC

HA

NN

EL C

OIL

SUN

IT M

OD

ELC

G L

OC

ATI

ON

IN (M

M)

SHIP

PING

WEI

GHT

OPE

RA

TING

W

EIG

HTLB

S (K

G)

LBS

(KG

)L1

L2L3

L4M

1M

2M

3M

4A

GZ0

40E

2948

(133

7)29

64 (1

345)

1067

(484

)88

1 (4

00)

548

(249

)45

3 (2

06)

1022

(464

)84

4 (3

83)

601

(273

)49

6 (2

25)

AG

Z045

E30

94 (1

403)

3112

(141

2)10

51 (4

77)

832

(377

)67

6 (3

07)

535

(243

)10

21 (4

63)

809

(367

)71

5 (3

24)

567

(257

)A

GZ0

50E

3093

(140

3)31

14 (1

413)

1049

(476

)83

7 (3

80)

671

(304

)53

6 (2

43)

1020

(463

)81

4 (3

69)

712

(323

)56

8 (2

58)

AG

Z055

E31

06 (1

409)

3128

(141

9)10

52 (4

77)

840

(381

)67

5 (3

06)

539

(245

)10

23 (4

64)

817

(371

)71

6 (3

25)

572

(260

)A

GZ0

60E

3130

(142

0)31

55 (1

431)

1059

(480

)85

1 (3

86)

676

(307

)54

3 (2

46)

1031

(468

)82

8 (3

76)

718

(326

)57

7 (2

62)

AG

Z065

E31

30 (1

420)

3155

(143

1)10

59 (4

80)

851

(386

)67

6 (3

07)

543

(246

)10

31 (4

68)

828

(376

)71

8 (3

26)

577

(262

)A

GZ0

70E

3472

(157

5)34

97 (1

586)

1180

(535

)84

7 (3

84)

842

(382

)60

4 (2

74)

1157

(525

)83

0 (3

77)

880

(399

)63

1 (2

86)

PAC

KA

GE

UNIT

S W

ITH

MIC

RO

CHA

NNEL

CO

ILS

UNIT

MO

DEL

LIFT

ING

(SHI

PPIN

G) W

EIG

HT B

Y C

OR

NER

LB

S (K

G)

MO

UNTI

NG (O

PER

ATI

NG) W

EIG

HT L

BS

(KG

)

AB

AG

Z040

E22

8 (5

79)

15

(38)

25

(64)

AG

Z045

E21

4 (5

44)

011

(3)

25

(64)

AG

Z050

E20

(508

)2

7 (6

9)2

5 (6

4)A

GZ0

55E

193

(490

)2

0 (5

1)2

5 (6

4)A

GZ0

60E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

65E

176

(447

)0

3 (8

)2

5 (6

4)A

GZ0

70E

176

(447

)0

3 (8

)2

5 (6

4)

UNIT

MO

DEL

EVA

P D

IMEN

SIO

NS IN

(MM

)C

ONN

ECTI

ON

SIZE

(V

ICTA

ULIC

)

0

33

45

47

11

AG

Z-E

FA

NS

127(

)71

(+76

$5($6(218176+331

(+76

028171

(+76

$5($6(2181723(5$71

(+77+(9$325$72

5

$7(

51

amp8

(

6+331$123(5$71

(+76

21271amp8

(7+(

(+76

2)$1lt23721625$ampamp(6625(6

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 30: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 30 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 30 AGZ075E - AGZ100E

PO

WE

R E

NT

RY

KN

OC

KO

UT

S

OF

TH

E C

ON

TR

OL

BO

XA

RE

ON

TH

E O

PP

OS

ITE

SID

E

22 8

75

KN

OC

KO

UT

S

Z

X

Y

L3

L4

L2

WA

TE

RIN

LE

T

EV

AP

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

OU

TL

ET

EV

AP

W

AT

ER

L1

WY

E-S

TR

AIN

ER

RE

QU

IRE

D

2051

3180

60

92

40

37

15

12

0

91

63

61

15

36

0

37

33

14

70

11

42

90

12

75

0

30

5

85

83

38

LO

CA

TIO

NS

LIF

TIN

G

L1

- L

4

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

00

33

45

47

11

1A

GZ

-E

6 F

AN

S

BO

XC

ON

TR

OL

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

65

98

62

50

6

29

2

64

11

5

2564

25

16

5

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS

69

17

5

21

38

4

23

55

92

7

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M1

CO

MP

R

CIR

CU

IT 2

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M3

M2

L4 M

4

L1

L3

CIR

CU

IT 1

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

44

0

20

A

19 75

0Q

TY

4

52

24

33

12

43

15

38

79

84

52

20

95

8

11

18

B

AB

AG

Z0

75

E5

56

(1

41

2)

27

1 (

68

8)

AG

Z0

80

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z0

90

E5

44

(1

38

2)

25

9 (

65

8)

AG

Z1

00

E5

16

(1

31

1)

23

1 (

58

7)

CO

NN

EC

TIO

N

SIZ

E

IN

30

(7

6)

EV

AP

D

IME

NS

ION

S

IN (

MM

)U

NIT

MO

DE

L

XY

Z

AG

Z0

75

E4

53

(1

15

1)

38

6 (

98

0)

56

2 (

14

27

)

AG

Z0

80

E4

42

(1

12

2)

39

2 (

99

5)

56

5 (

14

35

)

AG

Z0

90

E4

42

(1

12

2)

39

2 (

99

5)

55

0 (

13

97

)

AG

Z1

00

E4

36

(1

10

8)

38

9 (

98

8)

55

7 (

14

15

)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

AG

Z075E

4388 (

1990)

4451 (

2019)

1341 (

608)

1420 (

644)

790 (

358)

837 (

380)

1173 (

532)

1242 (

563)

989 (

449)

1047 (

475)

AG

Z080E

4510 (

2046)

4579 (

2077)

1407 (

638)

1418 (

643)

840 (

381)

846 (

384)

1232 (

559)

1241 (

563)

1049 (

476)

1057 (

479)

AG

Z090E

4540 (

2059)

4609 (

2091)

1456 (

660)

1466 (

665)

806 (

366)

812 (

368)

1276 (

579)

1285 (

583)

1020 (

463)

1028 (

466)

AG

Z100E

4696 (

2130)

4780 (

2168)

1505 (

683)

1480 (

671)

863 (

391)

848 (

385)

1322 (

600)

1299 (

589)

1089 (

494)

1070 (

485)

UN

IT M

OD

EL

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 31: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 31 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 31 AGZ110E - AGZ130E

51

20

80

31

30

51

20

12

75

0

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

NT

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

Z

Y

X

L3

WA

TE

R

FIE

LD

IN

ST

AL

LE

D

EV

AP

L

1 -

L4

L1

EV

AP

OP

TIO

N)

OU

TL

ET

L4

LIF

TIN

GL

OC

AT

ION

S

WA

TE

RL

2

INL

ET

WY

E-S

TR

AIN

ER

RE

QU

IRE

D(F

AC

TO

RY

OR

11

42

90

37

15

60

92

40

48

79

19

21

99

63

92

15

36

08

58

33

8

33

45

47

12

1

AG

Z-E

8 F

AN

S

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R I

NC

LU

DE

D

SH

IPP

ING

AN

D O

PE

RA

TIN

G W

EIG

HT

S D

O N

OT

IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

CO

NT

RO

LB

OX

[22

] 87

5 P

OW

ER

EN

TR

YK

NO

CK

OU

TS

FR

ON

T O

R R

IGH

T S

IDE

21

38

4

88

02

23

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

EL

IFT

ING

BR

AC

KE

TS65

17

56

9

29

2

25

16

5

64

64

11

5

25

98

62

50

6

92

72

35

52

2 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L2

M4

L4

M6

CO

MP

R

CIR

1

M1

- M

6

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

M3

L3

L1

M5

CIR

2

M2

CO

MP

R

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

RE

MO

VE

D

24

33

44

0

14

99

59

09

58

24

8

2052

19 75

0

63

0

QT

Y 6

52

A

20

12

43

15

11

18

B

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z110E

5437 (

2466)

5528 (

2508)

1762 (

799)

1769 (

802)

951 (

431)

955 (

433)

1424 (

646)

1430 (

649)

845 (

383)

849 (

385)

489 (

222)

491 (

223)

AG

Z120E

5696 (

2584)

5796 (

2629)

1907 (

865)

1915 (

869)

935 (

424)

939 (

426)

1548 (

702)

1555 (

705)

878 (

398)

882 (

400)

465 (

211)

467 (

212)

AG

Z130E

5792 (

2627)

5903 (

2678)

1941 (

880)

1863 (

845)

1015 (

460)

974 (

442)

1575 (

714)

1511 (

685)

920 (

417)

883 (

401)

517 (

235)

496 (

225)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

Z

AG

Z1

10

E4

41

(1

12

0)

42

1 (

10

69

)6

90

(1

75

3)

AG

Z1

20

E4

41

(1

12

0)

43

3 (

11

00

)6

64

(1

68

7)

AG

Z1

30

E4

31

(1

09

5)

41

0 (

10

41

)6

83

(1

73

5)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)

AB

AG

Z110E

955

(2426)

691

(1755)

AG

Z120E

939

(2385)

675

(1715)

AG

Z130E

920

(2337)

655

(1664)

EV

AP

D

IME

NS

ION

S

IN (

MM

)C

ON

NE

CT

ION

SIZ

E

IN

30

(76)

UN

IT

MO

DE

L

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 32: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 32 wwwDaikinAppliedcom

dImensIons and WeIghTs - paCkaged unITs

Figure 32 AGZ140E - AGZ150E

X

Y

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

65

16

5

DIM

EN

SIO

N D

OE

S N

OT

IN

CL

UD

E

22

35

LIF

TIN

G B

RA

CK

ET

S

29

2

64

25

64

11

5

25

98

62

50

6

23

55

88

0

92

7

84

21

3

69

17

5

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

L4

M6

TO

P V

IEW

WIT

HC

OIL

S A

ND

FA

NS

M1

- M

4 IS

OL

AT

OR

MO

UN

TIN

G H

OL

E L

OC

AT

ION

S O

N B

OT

TO

M S

UR

FA

CE

OF

UN

IT B

AS

E

M1

L1

M3

L3

M5

L2

RE

MO

VE

D

CIR

1

M2

M4

CO

MP

R

CO

MP

R

CIR

2

17

11

67

4

75

0

15

64

61

6

A

19

QT

Y 6

52

B

202052

12

43

15

95

82

43

3

11

18

44

0

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T IN

CL

UD

E T

HE

WE

IGH

TS

OF

AN

Y O

PT

ION

S O

R A

CC

ES

SO

RIE

S

33

45

47

131

AG

Z-E

10F

AN

S

LO

CA

TIO

NS

INS

TA

LL

ED

OP

TIO

N)

L3

WA

TE

R

WA

TE

R

L1

L4

INL

ET

EV

AP

L1

- L

4

EV

AP

(FA

CT

OR

Y O

R F

IEL

D

L2

LIF

TIN

GO

UT

LE

TW

YE

-ST

RA

INE

RR

EQ

UIR

ED

60

92

40

19

19

75

5

60

25

23

72

29

01

14

21

08

3

1537

85

83

38

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z140E

6555 (

2973)

6674 (

3027)

1862 (

845)

1868 (

847)

1410 (

640)

1415 (

642)

1411 (

640)

1416 (

642)

1070 (

485)

1074 (

487)

850 (

386)

853 (

387)

AG

Z150E

6617 (

3001)

6745 (

3059)

1888 (

856)

1881 (

853)

1426 (

647)

1421 (

645)

1433 (

650)

1428 (

648)

1085 (

492)

1081 (

490)

861 (

391)

858 (

389)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

XY

ZA

B

AG

Z140E

441

(1120)

426

(1083)

833

(2117)

1221

(3102)

675

1 (

1715)

AG

Z150E

439

(1116)

424

(1077)

833

(2115)

1205

(3062)

659

(1674)

UN

IT

MO

DE

L

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 33: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

dImensIons and WeIghTs - paCkaged unITs

wwwDaikinAppliedcom 33 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 33 AGZ160E - AGZ180E

22 8

75

KN

OC

KO

UT

SP

OW

ER

EN

TR

Y K

NO

CK

OU

TS

AR

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E C

ON

TR

OL

BO

X

51

20 8

03

1

30

51

20

12

75

0

Z

X

Y

NO

TE

L

IFT

ING

WE

IGH

TS

AR

E B

AS

ED

ON

UN

IT S

HIP

PIN

G W

EIG

HT

S

MO

UN

TIN

G W

EIG

HT

S A

RE

BA

SE

D O

N U

NIT

OP

ER

AT

ING

WE

IGH

T W

ITH

EV

AP

OR

AT

OR

WA

TE

R IN

CL

UD

ED

S

HIP

PIN

G A

ND

OP

ER

AT

ING

WE

IGH

TS

DO

NO

T I

NC

LU

DE

TH

E W

EIG

HT

S O

F A

NY

OP

TIO

NS

OR

AC

CE

SS

OR

IES

33

45

47

13

1

EV

AP

L1

- L

4

L2

LIF

TIN

GL

OC

AT

ION

S

WA

TE

R

INL

ET

OU

TL

ET

L3

L4

(FA

CT

OR

Y O

R F

IEL

DIN

ST

AL

LE

D O

PT

ION

)

L1

WA

TE

R

EV

AP

WY

E-S

TR

AIN

ER

RE

QU

IRE

D1

537

83

21

0

11

42

90

60

92

40

19

19

75

5

60

25

23

72

85

83

38

CO

NT

RO

LB

OX

[22

] 87

5

PO

WE

R E

NT

RY

KN

OC

KO

UT

S F

RO

NT

O

R R

IGH

T S

IDE

2564

64

25

25

06

98

6

23

55

92

7

21

38

4

17

56

9

16

56

5

22

35

88

0D

IME

NS

ION

DO

ES

NO

T I

NC

LU

DE

LIF

TIN

G B

RA

CK

ET

S

29

21

15

22 87

5 K

NO

CK

OU

TS

FIE

LD

CO

NT

RO

LC

ON

NE

CT

ION

SQ

TY

3

CO

MP

R

M1

- M

4

ISO

LA

TO

R M

OU

NT

ING

HO

LE

LO

CA

TIO

NS

ON

BO

TT

OM

SU

RF

AC

E O

F U

NIT

BA

SE

M1

L1

M3

L3

M5

M2

L2

M4

L4

M6

RE

MO

VE

DC

IR

2T

OP

VIE

W W

ITH

CO

ILS

AN

D F

AN

S

CO

MP

R

CIR

1

2052

B

2052

19

A

75

0Q

TY

6

31

51

24

24

33

95

81

56

46

16

17

11

67

4

11

18

44

0

SH

IPP

ING

WE

IGH

TO

PE

RA

TIN

G W

EIG

HT

LB

S (

KG

)L

BS

(K

G)

L1

L2

L3

L4

M1

M2

M3

M4

M5

M6

AG

Z160E

6937 (

3147)

7065 (

3205)

1941 (

880)

1947 (

883)

1522 (

690)

1527 (

693)

1466 (

665)

1471 (

667)

1136 (

515)

1140 (

517)

924 (

419)

927 (

420)

AG

Z170E

7170 (

3252)

7307 (

3314)

2072 (

940)

1995 (

905)

1581 (

717)

1522 (

690)

1571 (

713)

1512 (

686)

1197 (

543)

1152 (

523)

956 (

434)

920 (

417)

AG

Z180E

7412 (

3362)

7560 (

3429)

2121 (

962)

2127 (

965)

1580 (

717)

1584 (

718)

1613 (

732)

1617 (

733)

1210 (

549)

1214 (

551)

951 (

431)

954 (

433)

MO

UN

TIN

G (

OP

ER

AT

ING

) W

EIG

HT

L

BS

(K

G)

UN

IT

MO

DE

L

LIF

TIN

G (

SH

IPP

ING

) W

EIG

HT

BY

CO

RN

ER

L

BS

(K

G)

XY

ZA

B

AG

Z160E

441

(1119)

414

(1051)

845

(2147)

1205

(3062)

659

(1674)

AG

Z170E

432

(1096)

404

(1025)

836

(2123)

119 (

3022)

643

(1634)

AG

Z180E

441

(1119)

394

(1000)

828

(2103)

117 (

2971)

624

(1584)

UN

IT M

OD

EL

CG

LO

CA

TIO

N

IN (

MM

)E

VA

P

DIM

EN

SIO

NS

IN

(M

M)

CO

NN

EC

TIO

N

SIZ

E

IN

40

(102)

$=()$16

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 34: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 34 wwwDaikinAppliedcom

IsolaTors

Figure 34 Spring Isolator

Figure 35 Rubber-in-Shear (RIS) Isolator

Transfer the unit as indicated in the current AGZ-E Installation and Operation Manual which can be found on wwwDaikinAppliedcom In all cases set the unit in place and level When spring isolators are required install springs running under the main unit supports

QVWDOODWLRQRIVSULQJLVRODWRUVUHTXLUHVAgraveH[LEOHSLSLQJFRQQHFWLRQVDQGDWOHDVWWKUHHIHHWRIAgraveH[LEOHHOHFWULFDOFRQGXLWto avoid straining the piping and transmitting vibration and noise

Mounting locations for each model can be found in the ldquoDimensions - Packaged Unitsrdquo section of this document starting on page 28

925[2350]

105[2667]

56[143]

775[1969]

3

[762]62[158]

625

[1270]

FREEHT

5X[1270]

OPERHT

5[127]DIA

POSITIONING

PIN

25[64]ELASTOMERICPAD

ADJBOLT

ELASTOMERIC

SNUBBER

625

[159]25TO5GAP

[64to127]

IsolaTors

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 35: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

eleCTrICal daTa

wwwDaikinAppliedcom 35 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Electrical Data NotesElectrical Data Single and Multi-Point

1 Unit wire size ampacity (MCA) is equal to 125 of the largest compressor-motor RLA plus 100 of RLA of all other loads in the circuit

2 The control transformer is furnished and no separate 115V power is required For both single and multi-point power connections the control transformer is in circuit 1 with control power wired from there to circuit 2 In multi-point power disconnecting power to circuit 1 disconnects control power to the unit

3 Wire sizing amps is 15 amps if a separate 115V power supply is used for the control circuit

4 Recommended power lead wire sizes for 3 conductors per conduit are based on 100 conductor ampacity in accordance with NEC Voltage drop has not been included It is recommended that power leads be kept short All terminal block connections must be made with copper (type THW) wire or aluminum wire

5 5HFRPPHQGHG)XVH6L]HVDUHVHOHFWHGDWDSSUR[LPDWHORIWKHODUJHVWFRPSUHVVRU5$SOXVRIDOOother loads in the circuit

6 0D[LPXP)XVHRUEUHDNHUVL]HLVHTXDOWRRIWKHlargest compressor RLA plus 100 of all other loads

The recommended power wire sizes are based on an ambient temperature of 86degF (30degC) Ampacity correction factors must be applied for other ambient temperatures Refer to the NEC Handbook

8 Must be electrically grounded according to national and local electrical codes

Wiring Data1 Single-point power supply requires a single disconnect

to supply electrical power to the unit This power supply must either be fused or use a circuit breaker

2 Power wiring connections to the chiller may be done with either copper or aluminum wiring Wire should be sized per NEC andor local codes Wire sizing and wire count PXVWiquestWLQWKHSRZHUFRQQHFWLRQOXJVL]LQJVKRZQLQWKHElectrical Data tables starting on page 38

3 $OOiquestHOGZLUHVL]HYDOXHVJLYHQLQWKH(OHFWULFDODWDtables starting on page 38DSSOWRampUDWHGZLUHSHUNEC

Circuit Breakers Factory installed compressor circuit breakers are standard on units with single point power supply only This option provides compressor short circuit protection and makes servicing easier

Voltage Limitations1 Within 10 percent of nameplate rating

2 9ROWDJHXQEDODQFHQRWWRH[FHHGZLWKDUHVXOWDQWcurrent unbalance of 6 to 10 times the voltage unbalance

per NEMA MG-1 2009 Standard Rev 1-2010

Table 22 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electrical Control CenterOperating and equipment protection controls and motor starting components are separately housed in a centrally located weather resistant control panel with hinged and tool-locked doors In addition to the MicroTechreg III controller GHVFULEHGLQWKHQH[WVHFWLRQVWKHIROORZLQJFRPSRQHQWVDUHhoused in the panel

bull Power terminal blocks multi-point connection standardbull Control input and output terminal blockbull Control transformerbull Optional disconnect switch (through-the-door handle)bull Compressor motor inherent thermal and overload

protection is standard bull Optional phase voltage monitor with underover voltage

and phase reversal protectionbull Fan contactors with short circuit protective devicesbull Optional ground fault protectionbull FanTroltrade fan staging head pressure control systembull Power connections are per Table 23

Power Connections

Table 23 Power Connection Availability

Power Connection Power Block

Disc Swt

Comp Circuit

Breakers

Panel High Short Circuit

Current Rating

Optional Single Point Std Opt Std Opt

Standard Multi-Point Std Opt Not Avail Opt

HiquestQLWLRQV1 Power Block$QHOHFWULFDOGHYLFHWRGLUHFWODFFHSWiquestHOG

wiring without any disconnecting means

2 Disconnect Switch A molded case switch that accepts iquestHOGZLULQJDQGGLVFRQQHFWVPDLQSRZHUWRWKHHQWLUHunit or each main power supply if the multi-point power supply option is selected This option does not provide overcurrent protection

3 Compressor Circuit Breakers A manually reset circuit breaker for each compressor providing compressor only short circuit protection and located ahead of the contactor

4 Control Panel High Short Circuit Current Rating (Previously known as ldquowithstand ratingrdquo) The entire control panel is designed for short circuit current rating as shown in Table 22 on page 35 In the event of a short circuit the damage is contained within the control panel enclosure

eleCTrICal daTa

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 36: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 36 wwwDaikinAppliedcom

eleCTrICal daTa

Figure 36 Typical Field Wiring Diagram (Single-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7$

72amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

817$$50

9$amp7

7

7

7

7

7

$

$$50(23721

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

$IRU9$$IRU9$lt27+(56

1RWHV

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

)(51$5$07+0amp527(amp+amp21752(5

$$50(5($lt9$amp$030$

($57+5281

$5

1313

1313

1313

9$amp$030$

1313

1313

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

1

7

7

7

3$1(

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 37: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

eleCTrICal daTa

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Figure 37 Typical Field Wiring Diagram (Multi-Point Connection)

12amp20

(

0$)25(0$107lt27+(56

0$)25(9$375(6(7lt27+(56

28(6(7321702(67amp+

lt27+(56

70(amp2amp

2))

0$18$

21

$872

)5(027(6723amp21752686(5(029(($)5207(50

7727

70(amp2amp2))

0$18$

21

$872

7

7

7

7

7

7

72amp5amp87amp2035(66256$1)$1027256

$$50(5($lt

9$amp

)8

7

)8amp21752amp5amp87

)86(6((127(

)8

5(027(672367amp+lt27+(56

7

7

$$50(23721

7

7

7

7

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56

7

7

(7(51$$$50(9(17

6amp211(amp7lt27+(56

1

9$amp

23721$)(6833(amp2175232(5)8

72amp5amp87amp2035(66256$1)$1027256

3+$6(32(56285amp(

6amp211(amp767amp+25

32(52amp

amp5amp875($(5lt27+(56 $IRU9$

$IRU9$lt27+(56

$

$

$5

$

)(7(51$$$50(9(17686(

5(029(($$)5207(50

7727

1

9$amp

9$amp7

7

$

$$50(23721 $$50(5($lt

9$amp$030$

)(51$5$07+0amp527(amp+amp21752(5

($57+5281

$5

1313

1313

1313

1313

1313

$)(5172(167$($61(ampamp$66516lt67(07+amp218amp7255$7(9276))(6833(amp2175232(586(508675(029()8$15(180(56$16(amp217523$1(1313 86(5ltamp217$amp7621lt21276833lt)(32(5729$amp259$ampamp21752amp5amp876

1RWHV

9$amp$030$

1313

amp+)267amp+0$1$725ltlt27+(56

12523(13803$8amp217$amp7623721$

7

7

1313

1313

1

9$amp7

7

amp+53803125($ltlt27+(56

9$amp$030$

amp+53803125($ltlt27+(56

9$amp$030$

1

9$amp7

7

3

B

B

7

7

7

7

7

7

1

3$1(

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 38: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 38 wwwDaikinAppliedcom

eleCTrICal daTa

Table 24 Electrical Data - Single Point (6050Hz) Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

030E

208V60 149 (1) 2-600MCM (1) 6-350MCM

230V60 149 (1) 2-600MCM (1) 6-350MCM

380V60 100 100 (1) 2-600MCM (1) 12-10

460V60 80 80 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 90 90 (1) 14-20 (1) 12-10

035E

208V60 163 (1) 2-600MCM (1) 6-350MCM

230V60 163 (1) 2-600MCM (1) 6-350MCM

380V60 96 110 110 (1) 2-600MCM (1) 4-300MCM

460V60 90 90 (1) 14-20 (1) 12-10

575V60 64 (1) 14-20 (1) 12-10

400V50 80 90 90 (1) 14-20 (1) 12-10

040E

208V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

230V60 168 200 200 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 80 90 90 (1) 14-20 (1) 12-10

575V60 80 80 (1) 14-20 (1) 12-10

400V50 83 100 100 (1) 14-20 (1) 12-10

045E

208V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

230V60 228 250 250 (1) 2-600MCM (1) 6-350MCM

380V60 125 125 (1) 2-600MCM (1) 4-300MCM

460V60 90 100 100 (1) 2-600MCM (1) 12-10

575V60 90 90 (1) 14-20 (1) 12-10

400V50 94 110 110 (1) 2-600MCM (1) 4-300MCM

050E

208V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 241 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 131 150 150 (1) 2-600MCM (1) 4-300MCM

460V60 109 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 110 110 (1) 2-600MCM (1) 4-300MCM

400V50 125 125 (1) 2-600MCM (1) 4-300MCM

055E

208V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 251 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 (1) 2-600MCM (1) 6-350MCM

460V60 118 125 125 (1) 2-600MCM (1) 4-300MCM

575V60 105 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 119 125 125 (1) 2-600MCM (1) 4-300MCM

060E

208V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 260 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 126 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

065E

208V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

230V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

380V60 161 (1) 2-600MCM (1) 6-350MCM

460V60 129 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 113 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 129 150 150 (1) 2-600MCM (1) 4-300MCM

070E

208V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 306 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 164 200 200 (1) 2-600MCM (1) 6-350MCM

460V60 138 150 150 (1) 2-600MCM (1) 4-300MCM

575V60 125 125 (1) 2-600MCM (1) 4-300MCM

400V50 138 150 150 (1) 2-600MCM (1) 4-300MCM

075E

208V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 338 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 200 200 (1) 14-20 (1) 6-350MCM

460V60 149 (1) 14-20 (1) 6-350MCM

575V60 125 150 150 (1) 14-20 (1) 4-300MCM

400V50 149 (1) 14-20 (1) 6-350MCM

080E

208V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

230V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 2-600MCM (1) 6-350MCM

460V60 153 (1) 14-20 (1) 6-350MCM

575V60 126 150 150 (1) 14-20 (1) 4-300MCM

400V50 153 (1) 14-20 (1) 6-350MCM

090E

208V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 384 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 218 250 250 (1) 2-600MCM (1) 6-350MCM

460V60 168 200 200 (1) 14-20 (1) 6-350MCM

575V60 (1) 14-20 (1) 6-350MCM

400V50 168 200 200 (1) 14-20 (1) 6-350MCM

100E

208V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 268 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 203 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 184 225 225 (1) 2-600MCM (1) 6-350MCM

400V50 203 250 250 (1) 2-600MCM (1) 6-350MCM

110E

208V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 490 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 294 350 350 (1) 2-600MCM (2) 30-500MCM

460V60 250 250 (1) 2-600MCM (1) 6-350MCM

575V60 204 250 250 (1) 2-600MCM (1) 6-350MCM

400V50 250 250 (1) 2-600MCM (1) 6-350MCM

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 39: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

eleCTrICal daTa

wwwDaikinAppliedcom 39 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 24 continued Electrical Data - Single Point (6050Hz)

Model Size

Voltage Freq

Single Point Field Data

Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch

120E

208V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

230V60 534 600 600 (2) 6-500MCM (2) 30-500MCM

380V60 330 400 400 (1) 2-600MCM (2) 30-500MCM

460V60 261 300 300 (1) 2-600MCM (2) 30-500MCM

575V60 234 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 261 300 300 (1) 2-600MCM (2) 30-500MCM

130E

208V60 569 (2) 6-500MCM (3) 20-400MCM

230V60 569 (2) 6-500MCM (3) 20-400MCM

380V60 358 400 450 (1) 2-600MCM (2) 30-500MCM

460V60 284 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 239 250 250 (1) 2-600MCM (2) 30-500MCM

400V50 284 350 350 (1) 2-600MCM (2) 30-500MCM

140E

208V60 612 (2) 6-500MCM (3) 20-400MCM

230V60 612 (2) 6-500MCM (3) 20-400MCM

380V60 388 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 248 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 309 350 350 (1) 2-600MCM (2) 30-500MCM

150E

208V60 640 (2) 6-500MCM (3) 20-400MCM

230V60 640 (2) 6-500MCM (3) 20-400MCM

380V60 410 500 500 (1) 2-600MCM (2) 30-500MCM

460V60 328 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 252 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 328 400 400 (1) 2-600MCM (2) 30-500MCM

160E

208V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

230V60 688 800 800 (2) 6-500MCM (3) 20-400MCM

380V60 406 450 450 (1) 2-600MCM (2) 30-500MCM

460V60 316 350 350 (1) 2-600MCM (2) 30-500MCM

575V60 280 300 300 (1) 2-600MCM (2) 30-500MCM

400V50 316 350 350 (1) 2-600MCM (2) 30-500MCM

170E

208V60 800 800 (2) 6-500MCM (4) 40-500MCM

230V60 800 800 (2) 6-500MCM (4) 40-500MCM

380V60 442 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 355 400 400 (1) 2-600MCM (2) 30-500MCM

575V60 309 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 355 400 400 (1) 2-600MCM (2) 30-500MCM

180E

208V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

230V60 1000 1000 (4) 2-600MCM (4) 40-500MCM

380V60 500 500 (2) 6-500MCM (2) 30-500MCM

460V60 394 450 450 (1) 2-600MCM (2) 30-500MCM

575V60 339 350 350 (1) 2-600MCM (2) 30-500MCM

400V50 394 450 450 (1) 2-600MCM (2) 30-500MCM

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 40: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 40 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

030E

208V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

230V60 100 100 (1) 14-20 (1) 12-10 100 100 (1) 14-20 (1) 4-300MCM

380V60 46 60 60 (1) 14-20 (1) 12-10 46 60 60 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

575V60 34 40 45 (1) 14-20 (1) 12-10 34 40 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 40 50 50 (1) 14-20 (1) 12-10

035E

208V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 82 100 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 44 60 60 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 39 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 32 40 40 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 40 50 50 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

040E

208V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

230V60 88 110 110 (1) 14-20 (1) 4-300MCM 88 110 110 (1) 14-20 (1) 4-300MCM

380V60 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

460V60 42 50 50 (1) 14-20 (1) 12-10 42 50 50 (1) 14-20 (1) 12-10

575V60 35 45 45 (1) 14-20 (1) 12-10 35 45 45 (1) 14-20 (1) 12-10

400V50 44 60 60 (1) 14-20 (1) 12-10 44 60 60 (1) 14-20 (1) 12-10

045E

208V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

230V60 120 150 150 (1) 14-20 (1) 4-300MCM 120 150 150 (1) 14-20 (1) 6-350MCM

380V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

460V60 48 60 60 (1) 14-20 (1) 12-10 48 60 60 (1) 14-20 (1) 12-10

575V60 39 50 50 (1) 14-20 (1) 12-10 39 50 50 (1) 14-20 (1) 12-10

400V50 49 60 60 (1) 14-20 (1) 12-10 49 60 60 (1) 14-20 (1) 12-10

050E

208V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM 150 (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 69 90 90 (1) 14-20 (1) 12-10

460V60 58 80 (1) 14-20 (1) 12-10 58 80 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 51 60 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 56 (1) 14-20 (1) 12-10

055E

208V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 150 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 69 90 90 (1) 14-20 (1) 12-10 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 58 80 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 51 60 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 56 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

060E

208V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

230V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 41: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

eleCTrICal daTa

wwwDaikinAppliedcom 41 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Table 25 continued Electrical Data - Multiple Point (6050 Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

065E

208V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

230V60 141 (1) 14-20 (1) 6-350MCM 141 (1) 14-20 (1) 6-350MCM

380V60 85 110 110 (1) 14-20 (1) 4-300MCM 85 110 110 (1) 14-20 (1) 4-300MCM

460V60 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

575V60 59 80 (1) 14-20 (1) 12-10 59 80 (1) 14-20 (1) 12-10

400V50 68 80 90 (1) 14-20 (1) 12-10 68 80 90 (1) 14-20 (1) 12-10

070E

208V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

230V60 162 200 225 (1) 2-600MCM (1) 6-350MCM 162 200 225 (1) 2-600MCM (1) 6-350MCM

380V60 86 110 110 (1) 14-20 (1) 4-300MCM 86 110 110 (1) 14-20 (1) 4-300MCM

460V60 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

575V60 62 80 80 (1) 14-20 (1) 12-10 62 80 80 (1) 14-20 (1) 12-10

400V50 90 100 (1) 14-20 (1) 12-10 90 100 (1) 14-20 (1) 4-300MCM

075E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 225 225 (1) 14-20 (1) 6-350MCM

380V60 92 110 125 (1) 14-20 (1) 4-300MCM 91 110 125 (1) 14-20 (1) 4-300MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 65 80 90 (1) 14-20 (1) 12-10

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 100 100 (1) 14-20 (1) 4-300MCM

080E

208V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

230V60 186 225 250 (1) 2-600MCM (1) 6-350MCM 186 225 250 (1) 2-600MCM (2) 30-500MCM

380V60 98 125 125 (1) 14-20 (1) 4-300MCM 98 125 125 (1) 14-20 (1) 6-350MCM

460V60 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

575V60 66 80 90 (1) 14-20 (1) 12-10 66 80 90 (1) 14-20 (1) 4-300MCM

400V50 80 100 110 (1) 14-20 (1) 4-300MCM 80 100 110 (1) 14-20 (1) 4-300MCM

090E

208V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

230V60 203 250 250 (1) 2-600MCM (1) 6-350MCM 203 250 250 (1) 2-600MCM (2) 30-500MCM

380V60 115 150 150 (1) 14-20 (1) 4-300MCM 115 150 150 (1) 14-20 (1) 6-350MCM

460V60 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

575V60 100 110 (1) 14-20 (1) 4-300MCM 100 110 (1) 14-20 (1) 4-300MCM

400V50 89 110 125 (1) 14-20 (1) 4-300MCM 89 110 125 (1) 14-20 (1) 4-300MCM

100E

208V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

230V60 215 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 350 (1) 2-600MCM (2) 30-500MCM

380V60 129 (1) 14-20 (1) 6-350MCM 152 200 200 (1) 14-20 (2) 30-500MCM

460V60 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

575V60 110 110 (1) 14-20 (1) 4-300MCM 105 150 150 (1) 14-20 (1) 6-350MCM

400V50 96 125 125 (1) 14-20 (1) 4-300MCM 150 150 (1) 14-20 (1) 6-350MCM

110E

208V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 259 350 350 (1) 2-600MCM (2) 30-500MCM 259 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 156 200 225 (1) 14-20 (1) 6-350MCM 156 200 225 (1) 14-20 (2) 30-500MCM

460V60 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

575V60 108 150 150 (1) 14-20 (1) 4-300MCM 108 150 150 (1) 14-20 (1) 6-350MCM

400V50 120 150 (1) 14-20 (1) 6-350MCM 120 150 (1) 14-20 (1) 6-350MCM

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 42: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 42 wwwDaikinAppliedcom

eleCTrICal daTa

Table 25 continued Electrical Data - Multiple Point (6050Hz)

NOTE 0amp$ 0LQLPXPampXUUHQW$PSDFLW5)6 5HFRPPHQGHG)XVH6L]H0)6 0D[LPXP)XVH6L]H For RFS use the given values for intended standard ambient operation If the operating ambient is intended to be above 105degF MFS must be used

Model Size

Voltage )UHTXHQF

Multiple Point Field Data - Circuit 1 Multiple Point Field Data - Circuit 2

Ratings Lug Range Ratings Lug Range

MCA RFS MFS Power Block Disconnect Switch MCA RFS MFS Power Block Disconnect

Switch

120E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 281 350 350 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 225 225 (1) 14-20 (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 123 150 150 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM (1) 14-20 (1) 6-350MCM

130E

208V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 281 350 350 (1) 2-600MCM (2) 30-500MCM 316 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 225 225 (1) 14-20 (1) 6-350MCM 201 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

575V60 123 150 150 (1) 14-20 (1) 4-300MCM 128 (1) 14-20 (1) 6-350MCM

400V50 (1) 14-20 (1) 6-350MCM 160 200 225 (1) 14-20 (2) 30-500MCM

140E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 324 400 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 206 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 131 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 164 200 225 (1) 14-20 (2) 30-500MCM

150E

208V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 324 400 450 (1) 2-600MCM (2) 30-500MCM 351 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 206 250 250 (1) 2-600MCM (1) 6-350MCM 228 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

575V60 131 (1) 14-20 (1) 6-350MCM 134 (1) 14-20 (1) 6-350MCM

400V50 164 200 225 (1) 14-20 (1) 6-350MCM 182 225 250 (1) 2-600MCM (2) 30-500MCM

160E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 358 450 450 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 212 250 250 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 146 (1) 14-20 (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 165 200 200 (1) 14-20 (2) 30-500MCM

170E

208V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

230V60 358 450 450 (1) 2-600MCM (2) 30-500MCM 405 500 500 (1) 2-600MCM (2) 30-500MCM

380V60 212 250 250 (1) 2-600MCM (1) 6-350MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 146 (1) 14-20 (1) 6-350MCM 200 225 (1) 2-600MCM (1) 6-350MCM

400V50 165 200 200 (1) 14-20 (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

180E

208V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

230V60 453 500 500 (2) 6-500MCM (2) 30-500MCM 453 500 500 (2) 6-500MCM (2) 30-500MCM

380V60 248 300 300 (1) 2-600MCM (2) 30-500MCM 248 300 300 (1) 2-600MCM (2) 30-500MCM

460V60 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

575V60 200 225 (1) 2-600MCM (1) 6-350MCM 200 225 (1) 2-600MCM (2) 30-500MCM

400V50 204 250 250 (1) 2-600MCM (1) 6-350MCM 204 250 250 (1) 2-600MCM (2) 30-500MCM

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 43: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

opTIons and aCCessorIes

wwwDaikinAppliedcom 43 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Controls Options amp Accessories RapidRestorereg and Fast LoadingAllows the unit to restart and to reach full load more quickly than standard in case of a power interruption After a power loss duration of up to 180 seconds once power is restored the time for a Trailblazertrade chiller to restart is less than 125 seconds with the chiller reaching full load within 220 seconds from power restoration

Fast Loading Stand-By ChillerGives the system greater response time by starting a stand-by chiller and reaching full load capacity in 115 seconds (assumes conditions require full load capacity)

Hot Gas Bypass (Factory Installed) Hot gas bypass permits unit operation down to 10 of full load capacity This option includes a factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve PRGHOVRQOIRUHDFKFLUFXLW

Low Ambient Control (Factory Installed)Optional fan VFD control allows unit operation down to -10degF (-23degC) Not available on 380 volt (60 Hz) units

High Ambient Control PanelQFOXGHVDQH[KDXVWIDQZLWKUDLQKRRGWZRLQOHWVFUHHQVZLWKiquestOWHUVQHFHVVDUFRQWUROVDQGZLULQJ5HTXLUHGIRURSHUDWLRQfrom 105degF to 125degF (40degC to 52degC) ambient temperature This panel is included on units with Low Ambient Control regardless of ambient temperature to dissipate additional VFD heat

Water Flow Switch (Field Installed) $WKHUPDOGLVSHUVLRQZDWHUAgraveRZVZLWFKLVDYDLODEOHIRUiquestHOGinstallation in the chilled water piping to avoid evaporator IUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV7HUPLQDOVDUHSURYLGHGLQWKHXQLWFRQWUROFHQWHUIRUiquestHOGKRRNXSRIWKHZDWHUAgraveRZVZLWFKIWKLVRSWLRQLVQRWRUGHUHGZLWKWKHXQLWWKHQDiquestHOGVXSSOLHGZDWHUAgraveRZVZLWFKPXVWEHLQVWDOOHG

Water Flow Switch (Factory Installed)$IDFWRUPRXQWHGDQGZLUHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFKWRDYRLGHYDSRUDWRUIUHH]HXSXQGHUORZRUQRAgraveRZFRQGLWLRQV

Alarm Bell (Field Installed)Field installed and wired to the control panel to provide remote indication of unit alarm condition

Remote Operator Interface Panel (Field Installed)$UHPRWHLQWHUIDFHSDQHOiquestHOGZLUHGWRWKHXQLWSURYLGLQJall the data viewable on the unitrsquos controller including alarm clearing and setpoint change capability See ldquoOptional Remote Interface Panelrdquo on page 6 for details

BAS Interface - Open Choicestrade (Field Installed)7KHSUHIHUUHGPRGXOHLVVKLSSHGORRVHIRUiquestHOGLQVWDOODWLRQon the Microtechreg III controller to provide the interface to the following standard protocols

bull BACnetregIPbull Modbusreg

bull BACnetreg Ethernetbull LonMarkreg

Electrical Options and AccessoriesSingle-Point Electrical Connection Provides a single power connection to the unit power block with compressor circuit breakers or to a disconnect switch with compressor circuit breakers

Either option also available without circuit breakers

Multi-Point with Disconnect Switch Provides a disconnect switch mounted inside the power VHFWLRQRIWKHFRQWUROER[ZLWKDWKURXJKWKHGRRUKDQGOHIRUHDFKFLUFXLWDQGQRFRPSUHVVRUFLUFXLWEUHDNHUV5HTXLUHViquestHOGinstalled circuit protection

Phase LossVoltage ProtectionPhase loss with underover voltage protection and multiple LED indication of fault type is available as a factory installed option to guard against compressor motor burnout

Convenience Outlet 100 amp 115 volt Ground Fault Circuit Interruption (GFCI) outlet in control panel for servicing unit

Ground Fault Protection Protects equipment from damage from line-to-ground fault currents less than those required for conductor protection

High Short Circuit Current Rating (HSCCR) with Single-Point Disconnect Breaker SwitchProvides control panel with high short circuit current rating

Table 26 Standard and HSCCR Panel Ratings

3DQHO7SH 208V 230V 380V 400V 460V 575V

Standard 5kA 5kA 5kA

HSCCR 65kA 65kA 25kA

Electronic Expansion Valve$QHOHFWURQLFH[SDQVLRQYDOYHLVRSWLRQDORQPRGHOVZKLFKKDYHWKHUPDOH[SDQVLRQYDOYHVDVVWDQGDUG

opTIons and aCCessorIes

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 44: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 44 wwwDaikinAppliedcom

opTIons and aCCessorIes

8QLW2SWLRQVDQG$FFHVVRULHVRemote Evaporators Trailblazertrade models have an evaporator shipped separately IRUiquestHOGLQVWDOODWLRQDQGSLSLQJWRWKHRXWGRRUXQLW$YDLODEOHIRUPRGHOV$=(WKDWKDYHFRQGHQVLQJXQLWVEXLOWZLWKWXEHDQGiquestQFRLOVQIRUPDWLRQRQPRGHOVZLWKUHPRWHevaporators can be found in the current product Installation and Operation Manual available at wwwDaikinAppliedcom

Pump PackagesSee page 6 for general information and refer to the current product Installation and Operation Manual available on wwwDaikinAppliedcom for detailed information

amp26+36HLVPLFampHUWLiquestFDWLRQDLNLQPRGHOV$=(KDYHEHHQWHVWHGDQGFHUWLiquestHGEDQLQGHSHQGHQWDJHQFsup2H[SHUWVLQVHLVPLFDQDOVLVDQGdesign mdash to meet IBC seismic and OSHPD pre-approval with SDS (design spectral response acceleration at short period) HTXDOWRDWOHDVWJZKHQWKHVHLVPLFIDFWRURSWLRQRUiquestHOGaccessory is selected and the chiller is installed with either the optional seismic rated springs or the optional neoprene pads Find more information about seismic requirements and HVAC systems at wwwDaikinAppliedcom

Vibration Isolators (Field Installed)Spring or neoprene-in-shear vibration isolators are available for iquestHOGLQVWDOODWLRQWRUHGXFHYLEUDWLRQWUDQVPLVVLRQWKURXJKWKHunit base Seismic rated spring isolators are available for units UHTXLULQJVHLPLFFHUWLiquestFDWLRQ

Protective Base Guards Optional factory-installed vinyl-coated welded-wire base guards provide around lower section protection on ground level installations

Figure 38 Unit with Base Guards

Louvers (Base andor Coil)Available for the upper portion or both the upper and lower portions of unit (upper not required on Models 030 and 035) Selecting both will completely enclose the unit with louvers The louvers protect the coils from hail damage

Figure 39 Unit with Louvered Panels

Copper TubeAluminum Fin Condenser Coils$OXPLQXPiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeCopper Fin Condenser CoilsampRSSHUiquestQFRQGHQVHUFRLOVDUHDQRSWLRQRQDOOPRGHOV

Copper TubeBlackFintrade Coils$OXPLQXPiquestQVWRFNSUHFRDWHGZLWKDSKHQROLFFRDWLQJZLWKKRXUVDOWVSUDUHVLVWDQFH$670

Coated FinsampRSSHURUDOXPLQXPiquestQVFRDWHGZLWK(OHFWUR)LQregEDNHGHSR[protective coating with 5000-hour salt spray resistance (ASTM

Evaporator InsulationDouble insulation thickness (total of 1frac12 inch) for high humidity DUHDVRUORZAgraveXLGWHPSHUDWXUHV

Sound Reduction Acoustical blankets are factory-installed on each compressor 7KHDUHDOVRDYDLODEOHIRUUHWURiquestWiquestHOGLQVWDOODWLRQ

Shut-off Valves Suction valves (one per circuit) liquid line shutoff valves and discharge shutoff valves can be factory mounted

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 45: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

opTIons and aCCessorIes

wwwDaikinAppliedcom 45 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

Chicago Code Relief Valves Unit will be provided with factory-mounted relief valves to meet Chicago code requirements

Evaporator Inlet StrainerEvaporator water strainer kit consisting of Y-type strainer EORZGRZQYDOYHSLSHH[WHQVLRQZLWKWZR6FKUDGHUiquestWWLQJVDQGWZRJURRYHGFRXSOLQJViquestHOGLQVWDOOHGHWDLOVRQpage 12

Replaceable Core Filter-Drier)DFWRULQVWDOOHGiquestOWHUGULHUZLWKDUHSODFHDEOHFRUHDOORZVIRUIDVWUHSODFHPHQWRIiquestOWHUHOHPHQWDQGHDVLHUVHUYLFHDELOLW

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 46: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 46 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

TRAILBLAZERtrade AIR-COOLED SCROLL COMPRESSOR CHILLERS

PART 1 - GENERAL

6800$5ltA Section includes design performance criteria

refrigerants controls and installation requirements for air-cooled scroll compressor chillers

102 REFERENCESA Comply with applicable StandardsCodes of AHRI

550590-2003 ANSIASHRAE 15 ETL cETL NEC and OSHA as adopted by the State

B gt3DFNDJHGampKLOOHUV2QO8QLWVVKDOOPHHWWKHHIiquestFLHQFstandards of ASHRAE Standard 901 2010]

68077$6A Submit shop drawings and product data in accordance

ZLWKWKHVSHFLiquestFDWLRQV

B Submittals shall include the following

1 Dimensioned plan and elevation view drawings UHTXLUHGFOHDUDQFHVDQGORFDWLRQRIDOOiquestHOGconnections

2 6LQJOHOLQHVFKHPDWLFGUDZLQJRIWKHSRZHUiquestHOGhookup requirements indicating all items that are furnished

3 Schematic diagram of control system indicating points IRUiquestHOGLQWHUIDFHFRQQHFWLRQ

4 LDJUDPVKDOOIXOOGHOLQHDWHiquestHOGDQGIDFWRUZLULQJ

5 ampHUWLiquestFDWLRQRIIDFWRUUXQWHVWRIFKLOOHUXQLWVLJQHGEFRPSDQRIiquestFHU

6 Installation manuals

48$7lt$6685$1amp(A 4XDOLiquestFDWLRQV(TXLSPHQWPDQXIDFWXUHUPXVWVSHFLDOL]H

LQWKHPDQXIDFWXUHRIWKHSURGXFWVVSHFLiquestHGDQGKDYHiquestYHHDUVH[SHULHQFHZLWKWKHWSHRIHTXLSPHQWDQGrefrigerant offered

B Regulatory Requirements Comply with the codes and VWDQGDUGVVSHFLiquestHG

C Chiller manufacturerrsquos plant must be ISO registered

(9(5lt$1+$11A [Packaged Chillers Only Chiller shall be delivered

to the job site completely assembled and charged with refrigerant and oil by the manufacturer] [Remote Evaporator Option The outdoor unit shall be delivered to the job site with condensing section completely assembled and a holding charge of nitrogen]

B Comply with the manufacturerrsquos instructions for rigging and handling equipment

$55$17ltA The refrigeration equipment manufacturerrsquos guarantee

shall be for a period of one year from date of equipment start-up but not more than 18 months from shipment The guarantee shall provide for repair or replacement due to failure by material and workmanship that prove defective ZLWKLQWKHDERYHSHULRGH[FOXGLQJUHIULJHUDQW

107 MAINTENANCEA Maintenance of the chillers shall be the responsibility

of the owner and performed in accordance with the manufacturerrsquos instructions

3$573528amp76

$ampamp(37$(0$18)$amp785(56A Daikin Applied

B (Approved Equal)

817(6amp53721A [Factory-charged Packaged Provide and install as

shown on the plans factory-assembled air-cooled scroll compressor chiller with remote evaporator in the quantity VSHFLiquestHG(DFKRXWGRRUVHFWLRQVKDOOFRQVLVWRIKHUPHWLFWDQGHPRUWULRVFUROOFRPSUHVVRUVHWVWRWDORIIRXURUVL[compressors depending on chiller model) air-cooled condenser section microprocessor-based control system and all components necessary for controlled unit operation] OR [Remote Evaporator Option A PXOWLFLUFXLWGLUHFWH[SDQVLRQEUD]HGSODWHLQVXODWHGevaporator shall be provided for remote location to be installed and piped to the outdoor unit by the installing contractor]

B Each chiller shall be factory run-tested to verify operation Operating controls and refrigerant charge shall be checked for proper operation and optimum performance

(615(485(0(176A General[Packaged Chillers Provide a complete scroll

FRPSUHVVRUSDFNDJHGFKLOOHUDVVSHFLiquestHGKHUHLQDQGDVshown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect] [Remote Evaporator Option Provide a complete scroll compressor chiller system consisting of an outdoor compressor-condenser section DQGDUHPRWHLQGRRUHYDSRUDWRUDVVSHFLiquestHGKHUHLQand as shown on the drawings The unit shall be in accordance with the standards referenced in section 102 and any local codes in effect]

B Performance Refer to the schedule of performance on the drawings The chiller shall be capable of stable

engIneerIng guIde speCIfICaTIons

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 47: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

engIneerIng guIde speCIfICaTIons

ZZZDLNLQ$SSOLHGFRP CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

operation to a minimum percentage of full load (without hot gas bypass) of 25 Performance shall be in accordance with AHRI Standard 550590

C Flow Range The chiller shall have the ability to support YDULDEOHAgraveRZUDQJHGRZQWRRIQRPLQDOGHVLJQ(based on AHRI conditions)

D Operating Range The chiller shall have the ability to

FRQWUROOHDYLQJFKLOOHGAgraveXLGWHPSHUDWXUHIURP)WR65degF

E Acoustics Sound pressure levels for the unit shall not H[FHHGWKHIROORZLQJVSHFLiquestHGOHYHOV7KHPDQXIDFWXUHUshall provide the necessary sound treatment to meet these levels if required Sound data shall be provided with the quotation Test shall be in accordance with AHRI 6WDQGDUG

204 CHILLER COMPONENTSA Compressors

1 The compressors shall be sealed hermetic scroll type with crankcase oil heater and suction strainer The compressor motor shall be refrigerant gas cooled high torque hermetic induction type two-pole with inherent thermal protection on all three phases and shall be mounted on RIS vibration isolator pads The compressors shall be equipped with an internal module providing compressor protection and communication capability

B Evaporators

1 7KHHYDSRUDWRUVKDOOEHDFRPSDFWKLJKHIiquestFLHQFGXDOFLUFXLWEUD]HGSODWHWRSODWHWSHKHDWH[FKDQJHUconsisting of parallel stainless steel plates

2 The evaporator shall be protected with an electric resistance heater (heat trace tape) and insulated with 34rdquo (19 mm) thick closed-cell polyurethane insulation This combination shall provide freeze protection down to 20degF (-29degC) ambient air temperature

3 The water-side working pressure shall be a minimum of 653 psig (4502 kPa) Vent and drain connections shall be provided in the inlet and outlet chilled water piping by the installing contractor Evaporators shall be designed and constructed according to and listed by Underwriters Laboratories (UL)

C Condenser

1 Condenser fans shall be propeller type arranged for vertical air discharge and individually driven by direct-drive fan motors The fans shall be equipped with a heavy-gauge vinyl-coated fan guard Fan motors shall be TEAO type with permanently lubricated ball bearings inherent overload protection three-phase direct-drive 1140 rpm Each fan section shall be partitioned to avoid cross circulation

2 Coil Options

a [Standard Microchannel] Coil shall be all aluminum

alloy microchannel design and shall have a series RIAgraveDWWXEHVFRQWDLQLQJPXOWLSOHSDUDOOHOAgraveRZmicrochannels layered between the refrigerant manifolds Coils shall consist of a two-pass arrangement Each condenser coil shall be factory leak tested with high-pressure air under water

bull [Standard Micro-Channel Coil] Coils shall ZLWKVWDQGKRXUDFLGLiquestHGVQWKHWLFVHDwater fog (SWAAT) test (ASTM G85-02) at )ampZLWKiquestQORVVDQGGHYHORSQRleaks

bull [ElectroFinreg Micro-Channel Option] Condenser coils shall include ElectroFinreg EDNHGHSR[FRDWLQJSURYLGLQJKRXUVDOWVSUDUHVLVWDQFH$670DSSOLHGWRboth the coil and the coil frames

b [CuAl Coils] The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral part of the main condenser coil

bull [Black-Fin CuAl Option] Condenser coils VKDOOLQFOXGHDOXPLQXPiquestQVSUHFRDWHGZLWKDSKHQROLFHSR[FRDWLQJZLWKKRXUVDOWVSUDUDWLQJ$670

bull [ElectroFinreg CuAl Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

c [Copper-Copper Coils] - The condenser coils shall consist of 38 inch (10 mm) seamless copper tubes PHFKDQLFDOOERQGHGLQWRSODWHWSHiquestQV7KHiquestQVshall have full drawn collars to completely cover the tubes A subcooling coil shall be an integral

Sound Pressure (at 30 feet)63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

Sound Power63 Hz

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

Overall dBA

RDG dBA

50 Load dBA

25 Load dBA

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 48: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 48 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

part of the main condenser coil Condenser coils VKDOOLQFOXGHFRSSHUiquestQV

bull [ElectroFinreg CuCu Option] Condenser coils shall include ElectroFinregEDNHGHSR[FRDWLQJproviding 5000+ hour salt spray resistance $670DSSOLHGWRERWKWKHFRLODQGthe coil frames

D Refrigerant Circuit

1 Each of the two refrigerant circuits shall include DUHIULJHUDQWiquestOWHUGULHUVLJKWJODVVZLWKPRLVWXUHLQGLFDWRUOLTXLGOLQHVROHQRLGYDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGVXFWLRQOLQH

2 [Optional] Each of the two refrigerant circuits shall LQFOXGHDUHSODFHDEOHFRUHUHIULJHUDQWiquestOWHUGULHUsight glass with moisture indicator liquid line solenoid YDOYHQRH[FHSWLRQVH[SDQVLRQYDOYHDQGLQVXODWHGsuction line

E Construction

1 Unit casing and all structural members and rails shall be fabricated of pre-painted or galvanized steel to PHHW$670KRXUVDOWVSUDWHVW

2 OPTIONS

a Painted steel wraps enclosing the coil end sections and piping

b Protective 12 GA PVC-coated wire coil guards for the vertical upper coil section of the unit

c Protective 12 GA PVC-coated wire base guards for the lower section of the unit

d Protective and decorative louvers for upper section of the unit covering the coils and unit end

e Protective and decorative louvers for lower section of the unit

F Control System

1 A centrally located weatherproof control panel shall FRQWDLQWKHiquestHOGSRZHUFRQQHFWLRQSRLQWVFRQWUROinterlock terminals and control system Power and starting components shall include factory circuit breaker for fan motors and control circuit individual contactors for each fan motor solid-state compressor three-phase motor overload protection inherent fan motor overload protection and two power blocks (one per circuit) for connection to remote contractor supplied disconnect switches Hinged access doors shall be lockable Barrier panels or separate enclosures are required to protect against accidental contact with line voltage when accessing the control system

2 OPTIONS

a [Shall include standard multi-point power blocks ]

b [Shall include single-point power connection to power block with compressor circuit breakers (Customer-supplied disconnect required)]

c [Shall include single-point connection to a non-fused disconnect switch with through-the-door handle and compressor circuit breakers ]

d [Shall include multi-point disconnect switches (one per circuit)]

e [Shall include high short circuit current rating RIDPSVDPSVDW9ROWZLWKsingle-point disconnect switch][Shall include multi-point disconnect switches (one per circuit)]

G An advanced DDC microprocessor unit controller with a 5-line by 22-character liquid crystal display provides the operating and protection functions The controller shall take preemptive limiting action in case of high discharge pressure or low evaporator pressure The controller shall contain the following features as a minimum

1 Equipment Protection

a The unit shall be protected in two ways (1) by alarms that shut the unit down and require manual reset to restore unit operation and (2) by limit alarms that reduce unit operation in response to some out-of-limit condition Shut down alarms shall activate an alarm signal

b Shutdown Alarms

bull 1RHYDSRUDWRUZDWHUAgraveRZbull Sensor failures

bull Low evaporator pressure

bull Evaporator freeze protection

bull High condenser pressure

bull Outside ambient temperature (auto-restart)

bull Motor protection system

bull Phase voltage protection (Optional)c Limit Alarms

bull Condenser pressure stage down unloads unit at high discharge pressures

bull Low ambient lockout shuts off unit at low ambient temperatures

bull Low evaporator pressure hold holds stage 1 until pressure rises

bull Low evaporator pressure unload shuts off one compressor

d Unit Enable Selection

bull Enables unit operation from either local keypad digital input or BAS

e Unit Mode Selection

bull Selects standard cooling ice glycol or test operation mode

f Analog Inputs

bull Reset of leaving water temperature 4-20 mA

bull Current Limit

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 49: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

engIneerIng guIde speCIfICaTIons

wwwDaikinAppliedcom 49 CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS

g Digital Inputs

bull Unit off switch

bull Remote startstop

bull Flow switch

bull Ice mode switch converts operation and setpoints for ice production

bull Motor protectionh Digital Outputs

bull 6KXWGRZQDODUPiquestHOGZLUHGDFWLYDWHVRQDQalarm condition off when alarm is cleared

bull (YDSRUDWRUSXPSiquestHOGZLUHGVWDUWVSXPSwhen unit is set to start

i Condenser Fan Control

bull The unit controller shall provide control of condenser fans based on compressor discharge pressure

j Building Automation System (BAS) Interface

bull Factory mounted DDC controller(s) shall support operation on a BACnetreg Modbusreg or LonMarkreg network via one of the data link SKVLFDOODHUVOLVWHGEHORZDVVSHFLiquestHGEWKHsuccessful Building Automation System (BAS) supplier

ndash BACnetreg MSTP master (Clause 9)

ndash BACnetreg3$QQH[- ndash BACnetreg ISO 8802-3 (Ethernet)

ndash LonMarkreg FTT-10A The unit controller shall be LonMarkregFHUWLiquestHG

bull The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring control and alarm QRWLiquestFDWLRQDVVSHFLiquestHGLQWKHXQLWVHTXHQFHRIoperation and the unit points list

bull For chillers communicating over a LonMarkreg network the corresponding LonMarkreg ([WHUQDOQWHUIDFH)LOH)VKDOOEHSURYLGHGwith the chiller submittal data

bull All communication from the chiller unit FRQWUROOHUDVVSHFLiquestHGLQWKHSRLQWVOLVWVKDOObe via standard BACnetreg objects Proprietary BACnetreg objects shall not be allowed BACnetreg communications shall conform to the BACnetreg protocol (ANSIASHRAE135-2001) A BACnetreg Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal

205 OPTIONS AND ACCESSORIESA The following optional items shall be furnished

1 RapidRestorereg and Fast Loading The chiller shall be equipped with the capability to restart and to reach full load more quickly than standard in case of a power interruption The chiller shall be capable of rapidly restarting after power loss duration of up to 180 seconds The time to restart the chiller shall be DPD[LPXPRIVHFRQGVDQGIXOOORDGVKDOOEHachieved in 220 seconds from power restoration

2 Fast Loading Stand-By Chiller The chiller shall be equipped with the capability to start and to reach full load more quickly than standard in the event that the primary chiller system is disabled The chiller shall be capable of rapidly achieving full capacity The time to full load shall be achieved in 115 seconds

3 6HLVPLFampHUWLiquestFDWLRQ2SWLRQDOampVHLVPLFDQGOSHPD pre-approval shall meet a minimum seismic design spectral response acceleration SDS of 20g and be so labeled The chiller must be mounted on optional seismic rated spring isolators or neoprene ZDIAgraveHYLEUDWLRQSDGV

4 Hot Gas Bypass allows unit operation to 10 percent of full load Includes factory-mounted hot gas bypass valve solenoid valve and manual shutoff valve for HDFKFLUFXLW6KDOOEHUHDGIRUiquestHOGSLSLQJDFFRUGLQJto manufacturer instructions

5 Low Ambient Control Fan VFD allows unit operation from 32degF (0degC) down to -10degF (-23degC)

6 +LJKDPELHQWFRQWUROER[IRURSHUDWLRQLQDPELHQWtemperatures from 105degF (40degC) to 125degF (52degC)

Ground Fault Protection Factory installed circuit breaker to protect equipment from damage from line-to-ground fault currents less than those required for conductor protection

8 Phase loss with underover voltage protection and with LED indication of the fault type to guard against compressor motor burnout

9 )DFWRUPRXQWHGWKHUPDOGLVSHUVLRQAgraveRZVZLWFK

10 )LHOGPRXQWHGSDGGOHWSHFKLOOHGZDWHUAgraveRZVZLWFKiquestHOGZLUHGWRWKHFRQWUROSDQHO

11 (YDSRUDWRULQOHWVWUDLQHUPHVKZLWKH[WHQVLRQSLSHDQGJURRYHGFRXSOLQJVIDFWRUPRXQWHGRUiquestHOGinstalled)

12 6SULQJYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

13 5XEEHULQVKHDUYLEUDWLRQLVRODWRUViquestHOGLQVWDOOHG

14 6HLVPLFUDWHGVSULQJLVRODWRUViquestHOGLQVWDOOHG

15 Compressor sound reduction package

16 5HPRWHRSHUDWRULQWHUIDFHSDQHOiquestHOGZLUHG

115V GFI convenience outlet

18 BAS interface module factory mounted

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 50: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 bull TRAILBLAZERtrade MODEL AGZ CHILLERS 50 wwwDaikinAppliedcom

engIneerIng guIde speCIfICaTIons

23721$)$amp725lt167$( 38033$amp$(

A The pump package shall be factory mounted and wired on the chiller The chiller controller shall provide a pump startstop signal when operation is required On dual pump systems the chiller shall also provide automatic alternating of pump starts and dutystandby functionality The package shall be equipped with

1 Single Pump Model 4380 single spring inside-seal vertical in-line radially split-case pump serviceable without breaking pipe connections The motor and pump rotating assembly shall be serviceable without removing the pump casing from the line or

2 Dual Pumps in a Single Casting Model 4392 single-spring inside-seal vertical in-line radially split-case pumps mounted in a common casing with a common inlet connection and outlet connection and including DAgraveDSSHUYDOYHWRSUHYHQWUHFLUFXODWLRQZKHQRQOone pump is operating An isolation valve shall be included to allow one pump to operate when the other is removed The pumps shall be designed for dutystandby not parallel operation

B Pump package shall also be equipped with

1 ldquoYrdquo type inlet strainer

2 Combination triple-duty outlet valve having a drip-tight discharge shutoff valve non-slam check valve and AgraveRZWKURWWOLQJYDOYH

3 ampRPELQDWLRQVXFWLRQJXLGHZLWKAgraveRZVWDELOL]LQJRXWOHWvanes and stainless steel strainer with a disposable iquestQHPHVKVWUDLQHUIRUVWDUWXS

4 Factory power and control wiring from the AGZ chiller to the pump package control panel

5 Flow switch mounted and wired

6 Interconnecting schedule 40 piping with grooved couplings

Insulation of all cold surfaces

C Pump Package Options

1 Water pressure gauges on the pump suction and discharge

2 ([SDQVLRQWDQNZLWKVL]HLQFUHPHQWVIURPWRJDOORQViquestHOGLQVWDOOHGVPDOOVL]HVFDQEHIDFWRUmounted)

3 $LUVHSDUDWRUZLWKDLUYHQWiquestHOGLQVWDOOHG

4 Storage tanks vertical insulated 150 300 600 JDOORQVL]HVZLWKRSWLRQDOLPPHUVLRQKHDWHUiquestHOGinstalled

5 3XPS9)IRUYDULDEOHFKLOOHGZDWHUAgraveRZFDSDELOLW

a The VFD shall be completely sensorless requiring QRiquestHOGLQVWDOODWLRQRUZLULQJRIVHQVRUV7KHdrive shall incorporate an integrated graphical user interface that shall provide running and diagnostic information and identify faults and status in clear English language Faults shall be logged recorded for interrogation at a later date The keypad shall incorporate Hand-Off-Auto push buttons to enable switching between auto control modes and manual control The drive shall incorporate a USB port for direct connection to a PC and an RS485 connection with Modbusreg RTU protocol The built-in BAS mode shall be equipped with the same protocol as the chiller

b Control software shall provide automatic speed control in variable volume systems without the QHHGIRUSXPSPRXQWHGLQWHUQDOH[WHUQDORUremotely mounted differential pressure system feedback sensor Control mode setting and PLQLPXPPD[LPXPKHDGDQGAgraveRZVHWSRLQWVVKDOObe set at the factory and be user adjustable via the built-in programming interface

3$57((amp8721

301 INSTALLATION A Install in strict accordance with manufacturerrsquos

requirements shop drawings and contract documents

B Adjust and level chiller in alignment on supports

C Coordinate electrical installation with electrical contractor

D Coordinate controls with control contractor

E QVWDOODFOHDQDEOHiquestHOGVXSSOLHGPHVKVWUDLQHULQWKHchilled water return line at the evaporator inlet

67$5783A Provide testing and starting of machine and instruct the

Owner in its proper operation and maintenance

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW

Page 51: Catalog 624-4 Trailblazer Air-Cooled Scroll Compressor · PDF fileCatalog 624-4 Trailblazer™ Air-Cooled Scroll Compressor Chillers Model AGZ, E Vintage 030 to 180 Tons (100 to 630

CAT 624-4 (0115) copy2015 Daikin Applied | (800) 432ndash1342 | wwwDaikinAppliedcom

Daikin Applied Training and Development

1RZWKDWRXKDYHPDGHDQLQYHVWPHQWLQPRGHUQHIiquestFLHQWDLNLQ$SSOLHGHTXLSPHQWLWVFDUHVKRXOGbe a high priority For training information on all Daikin Applied HVAC products please visit us at wwwDaikinAppliedcom and click on Training or call 540-248-9646 and ask for the Training Department

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale including LPLWHG3URGXFWDUUDQWampRQVXOWRXUORFDODLNLQ$SSOLHGUHSUHVHQWDWLYHIRUZDUUDQWGHWDLOV7RiquestQGyour local Daikin Applied representative go to wwwDaikinAppliedcom

Aftermarket Services

7R iquestQG RXU ORFDO SDUWV RIiquestFH YLVLWwwwDaikinAppliedcom RU FDOO 3$576 7RiquestQGRXUORFDOVHUYLFHRIiquestFHYLVLWwwwDaikinAppliedcom or call 800-432-1342

This document contains the most current product information as of this printing For the most up-to-date product information please go to wwwDaikinAppliedcom

3URGXFWVPDQXIDFWXUHGLQDQ62ampHUWLiquestHG)DFLOLW