8 PHOENIX CONTACT

Building and industrial installations in different parts of the world have different requirements for lightning and surge protection in the power supply unit. High-capacity type 1 + type 2 lightning arrester combinations provide the initial basis for the power supply. TRABTECH implements a complete three-stage protection concept with user-friendly and ready-to-install solutions, from type 2 surge arresters in sub-distribution boards through to type 3 protection for termination devices.

Surge protection for the power supply unit

IEC/EN

Main range 10

Features 12

Selection guide 14

Type 1 lightning arresters

FLASHTRAB compact PLUS 16

FLASHTRAB PLUS 19

FLASHTRAB 22

POWERTRAB 24

VALVETRAB-MS T1/T2 26

Type 1 + 2 lightning/surge arrester combination

FLASHTRAB compact 28

Type 2 surge arresters

VALVETRAB compact 32

VALVETRAB-MS 36

VALVETRAB compact combined with... 48

Special systems, type 1 and type 2

For industry solutions 46

For 690 V and 960 V power supply systems 47

Type 3 device protection

DIN rail modules 52

For flush-type sockets 55

For cable ducts 55

Socket strips 57

Device protection adapters 57

Accessories 58

Basic solutions

For building installation 61

For photovoltaic systems 62

Applications 66

NEMA

Main range 70

Selection guide 72

VAL-SQ SE 74

VAL-SQ SP 76

VAL-SQ SI 78

Applications 80

9PHOENIX CONTACT

10 PHOENIX CONTACT

High-capacity varistors as surge arresters

Mechanical keying

Labeling options

Encapsulated and low-line-follow-current spark gaps

Double terminal points up to 35 mm2

Compact installation blocks

FLASHTRAB compact/VALVETRAB compact

Surge protection for IEC/EN power supply unit

Main range

11PHOENIX CONTACT

Perfect pluggability

Universal pluggability ensures a high degree of comfort, e.g., for insulation measurements in the system. Instead of accessing the installation, just unplug the connector.

The symmetrical connector design facilitates plugging in both directions within the base element. These protective devices can be installed in any control cabinet environment thanks to this flexible installation direction.

The complete system

The protective devices in the "compact" range offer a seamless installation concept. Uniform and high-capacity modules are available for virtually all power supply systems. Whether a lightning arrester, surge arrester or a combination of the two, this concept offers consistent and seamless application features that are universal.

Worldwide use

The voltage fluctuations in power supplies vary from country to country. The surge protection also has to deal with these short-term (temporary) voltage fluctuations. Due to the high rated voltage of 350 V AC, arresters in the "compact" range have no limitations and can be used in 230/400 V systems.

Innovative technology

The high breaking capacity of the innovative spark gaps also enables their use in low-voltage high-current installations with short-circuit currents of up to 50 kA. The encapsulated lightning arresters are designed to ensure a low amount of line follow current, so that even small backup fuses remain unaffected.

Status at a glance

The mechanical status indicator provides information locally at a glance.

Remote signaling

A common floating remote indication contact enables remote signaling without taking up extra space.

Designation structure

FLT - CP - 3 S - 350

VAL - CP - 3 S - 350

Product range:FLASHTRAB/VALVETRAB

compact

No. of phase conductorsS - Separate PE + NC - Combined PEN

Maximum continuous voltage UC

Surge protection for IEC/EN power supply unit

Main range

Surge protection for IEC/EN power supply unit

Features

POWERTRAB

12 PHOENIX CONTACT

Labeling options

Plug-in surge arrester

Optional floating remote indication contact

Compact installation blocks

Mechanical keying

17.5 mm design width

Terminal points up to 25 mm2

including protective guide

Plug-in surge arrester

12 mm design width

VALVETRAB

Protective conductor connection

Labeling option

Remote indication contact

Connection for module mounting

LED indicator

Remote indication circuit power supply

Double terminal point

Rugged aluminum die-cast housing

Surge protection for IEC/EN power supply unit

Features

Optical status indication

Uninterruptible and impedance-neutral insertion and removal

Floating remote indication contact

Keying for circuit type and voltage levels

Surge-current-resistant contact with DIN rail

Labeling possible on input and output side

Barcode for CHECKMASTER

17.5 mm design width

Optional integrated signal interface protection, such as TV-SAT, ISDN, etc.

Recessed ON/OFF switch

Operating indicator

1.8 m connecting cable

Country-specific versions

Increased touch-proof protection

Operating indicator

PLUGTRAB

COMBITRAB/MAINTRAB

13PHOENIX CONTACT

The selection matrix makes it easy to select suitable surge protection for the desired application.

The first column (Network type) divides the selection according to the number of phases of the power supply system, and the second column (Description) contains the corresponding power supply system. Subsequent columns provide information about the properties of the surge protective devices. The corresponding order numbers are then listed. Product-specific information can be found on the corresponding pages.

Special solutions for the IT power supply system can be found on page 47 onwards.

3-ph

ase

pow

er s

uppl

y

TN-S

/TT

3-phase power supply unit

Separate N and PE

TN-C 3-phase power supply unit

Common PEN

2-ph

ase

pow

er s

uppl

y

TN-S

/TT

2-phase power supply unit

Separate N and PE

TN-C 2-phase power supply unit

Common PEN

Sing

le-p

hase

pow

er s

uppl

y

TN-S

/TT

Single-phase power supply unit

Separate N and PE

TN-C Single-phase power supply unit

Common N and PE

Term

inat

ion

devi

ce p

ower

sup

ply

TN-S

/TT

3-phase power supply unit on the termination device

Separate N and PE

TN-S

/TT

Single-phase power supply unit on the termination device

L1

L2

L3

N

PE

PEN

L1

L2

L3

N

PE

L1

L2

PEN

L1

L2

N

PE

L1

PEN

L1

L1

L2

L3

N

PE

N

PE

L1

Net

work

typ

e

Des

crip

tion

NoteProducts bearing this stamp

(connector elements) can be tested with the CHECKMASTER.

Surge protection for IEC/EN power supply unit

Selection guide

14 PHOENIX CONTACT

FLT-CP-PLUS-3S-350 2882640 16

FLT-CP-3S-350 2859712 28

VAL-CP-3S-350 2859521 32

VAL-MS-320/3+1-FM 2859181 36

FLT-CP-PLUS-3C-350 2882653 16

FLT-CP-3C-350 2859725 28

VAL-CP-3C-350 2859547 32

VAL-MS-320/3+0-FM 2920243 37

FLT-CP-PLUS-2S-350 2882666 17

FLT-CP-2S-350 2859767 29

VAL-CP-2S-350 2859505 33

FLT-CP-PLUS-2C-350 2882679 17

FLT-CP-2C-350 2859770 29

VAL-CP-2C-350 2859589 33

FLT-CP-PLUS-1S-350 2882682 17

FLT-CP-1S-350 2859738 29

VAL-CP-1S-350 2859563 33

FLT-CP-PLUS-1C-350 2882695 18

FLT-CP-1C-350 2859741 30

PT 4-PE/S-230AC 2882459 52

PT 2-PE/S-230AC 2858357 52

MNT-1D1) 2882200 57

CBT-SCHUKO1) 2857280 57

BT-SKT-230ACBT-1S-230AC/A

28593432803409

55 55

1) Protection for power supply units is available in corresponding country-specific versions. Surge protective devices are also available with signal interface protection.

Type

3 de

vice

pro

tect

ion

Type

1 lig

htnin

g ar

rest

er

Type

2 su

rge

arre

ster

12 m

m d

esig

n wid

th p

er cha

nnel

17.5

mm

des

ign

wid

th p

er cha

nnel

Can

be

plugg

ed in

and

tes

ted

Statu

s in

dica

tor +

rem

ote

indi

cation

conta

ct

DIN

-rai

l moun

tabl

e

Ada

pter

Mul

ti-p

osition

sock

et str

ip

Socket

inst

alla

tion

Surge

pro

tect

ive

device

Ord

er N

o.

Page

Surge protection for IEC/EN power supply unit

Selection guide

15PHOENIX CONTACT

Total width 142.8 mm Total width 106.9 mm

Technical data Technical dataElectrical dataIEC category / EN type I / T1 I / T1Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / 350 V AC / - - / - / 350 V ACLightning test curr. Iimp (10/350) s

Peak value 100 kA 75 kACharge 50 As 37.5 As

Specific energy 2.50 MJ/ 1.40 MJ/Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 25 kA / 100 kA / - - / - / 75 kA (3L-PEN)Follow current quenching capacity Ifi

L-N / N-PE / L-PEN 50 kA (264 V AC) / 100 A / - - / - / 50 kA (264 V AC)Protection level UP

L-N / N-PE / L-PEN 1.5 kV / 1.5 kV / - - / - / 1.5 kVResponse time tA

L-N / N-PE / L-PEN 100 ns / 100 ns / - - / - / 100 nsMax. backup fuse according to IEC 315 A (gL/gG) 315 A (gL/gG)Immunity to short-circuiting (with max. backup fuse) IP 50 kA 50 kA

General dataConnection data solid / stranded / AWG 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 /

EN 61643-11/A11 EN 61643-11/A11Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC / 200 mA DC 1 A AC / 200 mA DC

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

FLASHTRAB compact PLUSFLT-CP-PLUS-3S-350 2882640 1 FLT-CP-PLUS-3C-350 2882653 1

Accessories AccessoriesReplacement connector

L-N / L-PEN FLT-CP-PLUS-350-ST 2859913 10 FLT-CP-PLUS-350-ST 2859913 10N-PE FLT-CP-N/PE-350-ST 2859686 10

Labeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

16 PHOENIX CONTACT

N

PE L2L1 L3

12 14

11 FM

PEN

L1 L3L2

12 14

11 FM

– Seamless pluggability (even for N/PE spark gap)

– Thermal disconnect device for each individual connector

– Optical, mechanical status indication for the individual arresters

– With floating remote indication contact– Connectors can be checked with

CHECKMASTER– High continuous voltage of 350 V AC for

230/400 V AC networks with high voltage fluctuations

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

FLASHTRAB compact PLUS

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

5-conductor system; L1, L2, L3, N, PE 4-conductor system; L1, L2, L3, PEN

For additional information, visit www.phoenixcontact.net/catalog

Total width 106.9 mm Total width 71.6 mm Total width 71.6 mm

Technical data Technical data Technical data

I / T1 I / T1 I / T1240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)

350 V AC / 350 V AC / - - / - / 350 V AC 350 V AC / 350 V AC / -

75 kA 50 kA 50 kA37.5 As 25 As 25 As1.40 MJ/ 625.00 kJ/ 625.00 kJ/

25 kA / 100 kA / - - / - / 25 kA 25 kA / 100 kA / -

50 kA (264 V AC) / 100 A / - - / - / 50 kA (264 V AC) 50 kA (264 V AC) / 100 A / -

1.5 kV / 1.5 kV / - - / - / 1.5 kV 1.5 kV / 1.5 kV / -

100 ns / 100 ns / - - / - / 100 ns 100 ns / 100 ns / -315 A (gL/gG) 315 A (gL/gG) 315 A (gL/gG)50 kA 50 kA 50 kA

2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2-40°C ... 80°C -40°C ... 80°C -40°C ... 80°CV0 V0 V0IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 /EN 61643-11/A11 EN 61643-11/A11 EN 61643-11/A11PDT contact PDT contact PDT contact0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 125 V DC 250 V AC / 125 V DC 250 V AC / 125 V DC1 A AC / 200 mA DC 1 A AC / 200 mA DC 1 A AC / 200 mA DC

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

FLT-CP-PLUS-2S-350 2882666 1 FLT-CP-PLUS-2C-350 2882679 1 FLT-CP-PLUS-1S-350 2882682 1

Accessories Accessories Accessories

FLT-CP-PLUS-350-ST 2859913 10 FLT-CP-PLUS-350-ST 2859913 10 FLT-CP-PLUS-350-ST 2859913 10FLT-CP-N/PE-350-ST 2859686 10 FLT-CP-N/PE-350-ST 2859686 10

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

17PHOENIX CONTACT

N

PE L2L1

12 14

11 FM

PEN

L1 L2

12 14

11 FM

N

PE L1

12 14

11 FM

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

4-conductor system; L1, L2, N, PE 3-conductor system; L1, L2, PEN 3-conductor system; L, N, PE

Total width 35.8 mm Total width 35.8 mm

Technical data Technical dataElectrical dataIEC category / EN type I / T1 I / T1Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (N-PE)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / - / 350 V AC - / 350 V AC / -Lightning test curr. Iimp (10/350) s

Peak value 25 kA 100 kACharge 12.5 As 50 As

Specific energy 160.00 kJ/ 2.50 MJ/Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 25 kA / - / 25 kA - / 100 kA / -Follow current quenching capacity Ifi

L-N / N-PE / L-PEN 50 kA (264 V AC) / - / 50 kA (264 V AC) - / 100 A / -Protection level UP

L-N / N-PE / L-PEN 1.5 kV / - / 1.5 kV - / 1.5 kV / -Response time tA

L-N / N-PE / L-PEN - / - / 100 ns - / 100 ns / -Max. backup fuse according to IEC 315 A (gL/gG) -Immunity to short-circuiting (with max. backup fuse) IP 50 kA 25 kA

General dataConnection data solid / stranded / AWG 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 / UL 1449 IEC 61643-1 / EN 61643-11 / EN 61643-11/A11 /

UL 1449Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC / 200 mA DC 1 A AC / 200 mA DC

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

FLASHTRAB compact PLUSFLT-CP-PLUS-1C-350 2882695 1

FLASHTRAB compactFLT-CP-N/PE-350 2859754 1

Accessories AccessoriesReplacement connector

L-N / L-PEN FLT-CP-PLUS-350-ST 2859913 10N-PE FLT-CP-N/PE-350-ST 2859686 10

Labeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

18 PHOENIX CONTACT

– Seamless pluggability (even for N/PE spark gap)

– Thermal disconnect device for each individual connector

– Optical, mechanical status indication for the individual arresters

– With floating remote indication contact– Connectors can be checked with

CHECKMASTER– High continuous voltage of 350 V AC for

230/400 V AC networks with high voltage fluctuations

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

FLASHTRAB compact PLUS

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

PEN

L1

12 14

11 FM

N

PE

12 14

11 FM

2-conductor system; L, PEN N-PE spark gap, for Lightning Protection Level 1

For additional information, visit www.phoenixcontact.net/catalog

Total width 35.5 mm Total width 35.5 mm

Technical data Technical dataElectrical dataIEC category / EN type I / T1 I / T1 I / T1Nominal voltage UN 230 V AC (400 V AC) 230 V AC (400 V AC) 230 V AC (400 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / - / 350 V AC 440 V AC / - / 440 V AC 440 V AC / - / 440 V ACLightning test curr. Iimp (10/350) s

Peak value 50 kA 50 kA -Charge 25 As 25 As -

Specific energy 625.00 kJ/ 625.00 kJ/ -Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 50 kA / - / 50 kA 50 kA / - / 50 kA 50 kA / - / -Protection level UP

L-N / N-PE / L-PEN 1.5 kV / - / 1.5 kV 2.5 kV / - / 2.5 kV 3 kV / - / 3 kVResponse time tA

L-N / N-PE / L-PEN 100 ns / - / 100 ns 100 ns / - / 100 ns 100 ns / - / 100 nsMax. backup fuse according to IEC 500 A (gL) 500 A (NH-gL)Immunity to short-circuiting (with max. backup fuse) IP 50 kA 25 kA (440 V AC)

General dataConnection data solid / stranded / AWG 10 ... 50 mm² / 16 ... 35 mm² / 6 - 1 10 ... 50 mm² / 16 ... 35 mm² / 6 - 1Temperature range -40°C ... 85°C -40°C ... 85°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11 IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

FLASHTRAB PLUS CTRLWithout status indicator FLT-PLUS CTRL-1.5 2800119 1 FLT-PLUS CTRL-2.5 2800121 1

FLT-PLUS CTRL-3.0 2800168 1FLASHTRAB PLUS CTRLWith status indicator FLT-PLUS CTRL-1.5/I 2800120 1 FLT-PLUS CTRL-2.5/I 2800122 1

FLT-PLUS CTRL-3.0/I 2800170 1

Accessories AccessoriesLabeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59Wiring bridge MPB ..., see page 58 MPB ..., see page 58

19PHOENIX CONTACT

– Single-channel– Triggered– High discharge capacity– Good follow current quenching capacity

with higher rated voltage– Direct parallel connection with type 2

arresters supported

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

FLASHTRAB PLUS CTRL

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

L / N ( ) L / N ( ) L / N ( ) L / N ( )

1.5 kV protection level 2.5 kV/3 kV protection level

Total width 70.4 mm

Technical dataElectrical dataIEC category / EN type I / T1Nominal voltage UN 230 V AC (400 V AC)Maximum continuous operating voltage UC

L-N / N-PE 260 V AC / 260 V ACLightning test curr. Iimp (10/350) s

Peak value 35 kA (L-N)Charge 17.5 As

Specific energy 306.00 kJ/ (L-N)Nominal discharge surge current In (8/20) μs

L-N / N-PE 35 kA / 50 kAFollow current quenching capacity Ifi

L-N / N-PE 3 kA / 100 AProtection level UP

L-N / N-PE 2 kV / 2 kVResponse time tA

L-N / N-PE 100 ns / 100 nsMax. backup fuse according to IEC 400 A (NH-gL)Immunity to short-circuiting (with max. backup fuse) IP 25 kA

General dataConnection data solid / stranded / AWG 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2Temperature range -40°C ... 85°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11

Ordering data

Description Type Order No. Pcs. / Pkt.

FLASHTRAB installation blockWith status indicator FLT 35/3+1 CTRL-2.0/I 2800125 1FLASHTRABIimp: 50 kA (10/350) μs

AccessoriesLabeling material ZBN 18 ..., see page 59Wiring bridge MPB ..., see page 58

20 PHOENIX CONTACT

L1 L2 L3

N

FLASHTRAB

– Encapsulated and triggered– With ignition electronics– Direct parallel connection with type 2

arresters supported

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

5-conductor system; L1, L2, L3, N, PE, pre-assembled installation block

For additional information, visit www.phoenixcontact.net/catalog

Total width 17.6 mm Total width 35.8 mm

Technical data Technical data

I / T1 I / T1230 V AC (400 V AC) 230 V AC (N-PE)

- / 260 V AC - / 260 V AC

50 kA 100 kA25 As 50 As625.00 kJ/ (N-PE) 2.50 MJ/ (N-PE)

- / 50 kA - / 100 kA

- / 100 A - / 100 A

- / 2 kV - / 1.5 kV

- / 100 ns - / 100 ns- -- -

0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2-40°C ... 85°C -40°C ... 80°CV0 V0IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11 IEC 61643-1 / EN 61643-11 / EN 61643-11/A11

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

FLT 50 N/PE CTRL-2.0 2800109 1FLT 100 N/PE-1.5 2800303 1

Accessories AccessoriesZBN 18 ..., see page 59 ZBN 18 ..., see page 59MPB ..., see page 58 MPB ..., see page 58

21PHOENIX CONTACT

L / N ( ) L / N ( )

L/N ( ) L/N ( )

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

N-PE spark gap, single-channel N-PE spark gap, single-channel, plug-in

Total width 17.6 mm Total width 17.6 mm

Technical data Technical dataElectrical dataIEC category / EN type I / T1 I / T1Nominal voltage UN 230 V AC (400 V AC) 230 V AC (400 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / - / 350 V AC 440 V AC / - / 440 V ACLightning test curr. Iimp (10/350) s

Peak value 35 kA 25 kACharge 17.5 As 12.5 As

Specific energy 306.00 kJ/ 156.00 kJ/Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 35 kA / - / 35 kA 25 kA / - / 25 kAFollow current quenching capacity Ifi

L-N / N-PE / L-PEN 1.5 kA / - / 1.5 kA 2.5 kA / - / 2.5 kAProtection level UP

L-N / N-PE / L-PEN 5 kV / - / 5 kV 5 kV / - / 5 kVResponse time tA

L-N / N-PE / L-PEN 100 ns / - / 100 ns 100 ns / - / 100 nsMax. backup fuse according to IEC 400 A (gL) 250 A (gL)Immunity to short-circuiting (with max. backup fuse) IP 25 kA 25 kA

General dataConnection data solid / stranded / AWG 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2Temperature range -40°C ... 85°C -40°C ... 85°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

FLASHTRABFLT 35-260 2800110 10 FLT 25-400 2800106 1

Accessories AccessoriesLabeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59Wiring bridge MPB ..., see page 58 MPB ..., see page 58

22 PHOENIX CONTACT

L/N ( ) L/N ( )L/N ( ) L/N ( )

– Single-channel– High discharge capacity

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

FLASHTRAB

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

Encapsulated, 35 kA lightning test current 25 kA lightning test current

For additional information, visit www.phoenixcontact.net/catalog

Total width 35.5 mm Total width 35.5 mm Total width 35.8 mm

Technical data Technical data Technical data

I / T1 I / T1 I / T1230 V AC (400 V AC) 230 V AC (400 V AC) 230 V AC (400 V AC)

400 V / - / 400 V 440 V AC / - / 440 V AC - / 260 V AC / -

60 kA 50 kA 100 kA30 As 25 As 50 As900.00 kJ/ 625.00 kJ/ 2.50 MJ/

60 kA / - / 60 kA 50 kA / - / 50 kA - / 100 kA / -

2.5 kA / - / 2.5 kA 25 kA / - / 25 kA - / 100 A / -

5 kV / - / 5 kV 5 kV / - / 5 kV - / 4 kV / -

100 ns / - / 100 ns 100 ns / - / 100 ns - / 100 ns / -500 A (gL) 500 A (NH-gL) -25 kA 25 kA (440 V AC) -

10 ... 50 mm² / 16 ... 35 mm² / 6 - 1 10 ... 50 mm² / 16 ... 35 mm² / 6 - 1 10 ... 50 mm² / 16 ... 35 mm² / 6 - 1-40°C ... 85°C -40°C ... 85°C -40°C ... 85°CV0 V0 V0IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

FLT 60-400 2800107 1 FLT-PLUS 2800116 1 FLT 100-260 2838160 1

Accessories Accessories AccessoriesZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59MPB ..., see page 58 MPB ..., see page 58 MPB ..., see page 58

23PHOENIX CONTACT

L/N ( ) L/N ( ) L/N ( ) L/N ( )N ( ) N ( )

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

60 kA lightning test current 50 kA lightning test current Single-channel, encapsulated, N-PE spark gap, 100 kA lightning test current, for

Lightning Protection Level 1

Total width 56 mm

Technical dataElectrical dataIEC category I, II / T1, T2Nominal voltage UN 690 V ACMaximum continuous operating voltage UC 800 V ACTOV behavior at UT 1500 V AC (5 sec.)Nominal load current IL 150 A (serial through wiring with 50 mm2)Nominal discharge surge current In (8/20) μs 35 kAMax. discharge surge current Imax (8/20) s 100 kALightning test current (10/350) s

Peak value Iimp 35 kAProtection level UP 4.5 kVMax. required backup fuse with branch wiring 400 A (gL/gG; 2 x 50 mm2)

Max. required backup fuse with V-type through wiring 125 A (gL/gG; 35 mm2)

Short-circuit resistance IP with max. backup fuse (effective) 50 kA (400 A gL/gG)

General dataAmbient temperature (operation) -40°C ... 80°CDegree of protection according to IEC 60529/EN 60529 IP20Housing material PA/PCInflammability class according to UL 94 V2Test standards IEC 61643-1 2005 / IEC 61643-11 Ed.1 FDIS 2010 /

EN 61643-11/A11 2007

ConductorConnection name Double terminal pointConnection method Screw connectionScrew thread M6Connection data solid / stranded / AWG 16 ... 50 mm² / 16 ... 50 mm² / 6 - 0Protective conductor connectionConnection name PE conductor connectionConnection method Ring cable lugScrew thread M10Connection data solid / stranded / AWG 16 ... 95 mm² / 16 ... 95 mm² / 6 - 0Remote indication contact Single-pos. N/C contactConnection data solid / stranded / AWG 0.2 ... 2.5 mm² / 0.2 ... 2.5 mm² / 24 - 12Max. operating voltage 30 V AC / 30 V DCMax. operating current 1.5 A AC / 1.5 A DC

Ordering data

Description Type Order No. Pcs. / Pkt.

POWERTRABPWT 35-800AC-FM 2800419 1

Mounting set, comprising: 1 x PE aluminum rail(147.5 x 30 x 3 mm), 3 x M10x20 hexagon head screw,3 x M10 hexagonal nut, 3 x M10 washer, 3 x M10 spring washer,1 x Installation instructions

24 PHOENIX CONTACT

12

11 FM21

22

PE / PEN /

POWERTRAB

– Type 1 arrester based on a varistor– Meets Lightning Protection Level I– Universal solution for various network

types:500 ... 690 V AC IT systems554/960 V AC TN-C systems400/690 V AC TN-C systems

– Multi-stage status monitoring via remote indication contact

– Local optical status indication– Encapsulated, non-extinguishing– Free of leakage current/no line follow

current– Very high TOV resistance– Meets installation requirements according

to CLC/TS 50539-22– Use in harsh industrial environments

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

Single-channel

For additional information, visit www.phoenixcontact.net/catalog

Total width 176 mm

Technical data

I, II / T1, T2690 V AC800 V AC1500 V AC (5 sec.)150 A (serial through wiring with 50 mm2)35 kA (per position)100 kA

35 kA (per position) 4.5 kV

400 A (gL/gG; 2 x 50 mm2)

125 A (gL/gG; 35 mm2)

50 kA (400 A gL/gG)

-40°C ... 80°CIP20PA/PCV2IEC 61643-1 2005 / IEC 61643-11 Ed.1 FDIS 2010 / EN 61643-11/A11 2007

Double terminal pointScrew connectionM616 ... 50 mm² / 16 ... 50 mm² / 6 - 0

PE conductor connectionRing cable lugM1016 ... 95 mm² / 16 ... 95 mm² / 6 - 0Single-pos. N/C contact0.2 ... 2.5 mm² / 0.2 ... 2.5 mm² / 24 - 1230 V AC / 30 V DC1.5 A AC / 1.5 A DC

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

PWT 100-800AC-FM 2800531 1

PWT CCT-SET 2800532 1

25PHOENIX CONTACT

PE / PEN /

12

11 FM21

22L1 L2 L3

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

4-conductor system; L1, L2, L3, PE/PEN Mounting set

Total width 71.2 mm

Technical dataElectrical data ...335 ...175IEC category / EN type I, II / T1, T2 I, II / T1, T2Nominal voltage UN 240 V AC (230/400 V AC ...

240/415 V AC)120 V AC

Maximum continuous operating voltage UCL-N / L-PE / N-PE / L-PEN 335 V AC / - / 264 V AC / - 175 V AC / - / 264 V AC / -

Lightning test curr. Iimp (10/350) sPeak value 50 kA 50 kA

Charge 25 As 25 AsSpecific energy 625.00 kJ/ 625.00 kJ/

Follow current quenching capacity IfiL-N / L-PE / N-PE / L-PEN - / - / 100 A (264 V AC) / - - / - / 100 A (264 V AC) / -

Nominal discharge surge current In (8/20) μsL-N / L-PE / N-PE / L-PEN 12.5 kA / - / 50 kA / - 12.5 kA / - / 50 kA / -

Max. discharge surge current Imax. (8/20) μsL-N / L-PE / N-PE / L-PEN 50 kA / - / 50 kA / - 50 kA / - / 50 kA / -

Protection level UPL-N / L-PE / N-PE / L-PEN 1.2 kV / 2 kV / 1.7 kV / - 0.8 kV / 2 kV / 1.7 kV / -

Max. backup fuse according to IEC 160 A (gL/gG) 160 A (gL/gG)General dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2Temperature range -40°C ... 80°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / EN 61643-11/A11Remote indication contact Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V ACMax. operating current 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

Ordering data

Description UC Type Order No. Pcs. / Pkt.

VALVETRAB-MS, varistor-based lightning arrester

With remote indication contact 335 V AC VAL-MS-T1/T2 335/12.5/3+1-FM 2800183 1Without remote indication contact 335 V AC VAL-MS-T1/T2 335/12.5/3+1 2800184 1VALVETRAB-MS, varistor-based lightning arrester

With remote indication contact 175 V AC VAL-MS-T1/T2 175/12.5/3+1-FM 2800670 1Without remote indication contact 175 V AC VAL-MS-T1/T2 175/12.5/3+1 2800671 1

AccessoriesReplacement connector

L-N / L-PEN VAL-MS-T1/T2 335/12.5 ST 2800190 10L-N / L-PEN VAL-MS-T1/T2 175/12.5 ST 2800676 10

N-PE F-MS-T1/T2 50 ST 2800191 10

Labeling material ZBN 18 ..., see page 59

26 PHOENIX CONTACT

12 14

11 FM

NL1 L2 L3

VAL-MS-T1/T2.../12.5...

– Seamless pluggability (even for N/PE spark gap)

– Secure hold of connectors in the event of high lightning current loads and strong vibration thanks to new latching

– Thermal disconnect device for each individual connector

– Optical, mechanical status indication for the individual arresters

– With or without floating remote indication contact

– Mechanical keying of all slots– Connectors can be checked with

CHECKMASTER

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

5-conductor system; L1, L2, L3, N, PE (3+1 circuit)

For additional information, visit www.phoenixcontact.net/catalog

Total width 71.2 mm Total width 53.4 mm Total width 35.6 mm

Technical data Technical data Technical data...335 ...175 ...335 ...175

I, II / T1, T2 I, II / T1, T2 I, II / T1, T2 I, II / T1, T2 I, II / T1, T2240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC

(230/400 V AC ... 240/415 V AC)120 V AC 240 V AC

(230 V AC ... 240 V AC)120 V AC

- / 335 V AC / 335 V AC / - - / - / - / 335 V AC - / - / - / 175 V AC 335 V AC / - / 264 V AC / - 175 V AC / - / 264 V AC / -

50 kA 37.5 kA 37.5 kA 25 kA 25 kA25 As 18.75 As 18.75 As 12.5 As 12.5 As625.00 kJ/ 352.00 kJ/ 352.00 kJ/ 160.00 kJ/ 160.00 kJ/

- / - / - / - - / - / - / - - / - / - / - - / - / 100 A (264 V AC) / - - / - / 100 A (264 V AC) / -

- / 37.5 kA (3 x L) / 12.5 kA / - - / - / - / 37.5 kA (3 x L) - / - / - / 37.5 kA (3 x L) 12.5 kA / - / 50 kA / - 12.5 kA / - / 50 kA / -

- / 150 kA (3 x L) / 50 kA / - - / - / - / 150 kA (3 x L) - / - / - / 150 kA (3 x L) 50 kA / - / 50 kA / - 50 kA / - / 50 kA / -

- / 1.2 kV / 1.2 kV / - - / - / - / 1.2 kV - / - / - / 0.7 kV 1.2 kV / 2 kV / 1.7 kV / - 0.8 kV / 2 kV / 1.7 kV / -160 A (gL/gG) 160 A (gL/gG) 160 A (gL/gG) 160 A (gL/gG) 160 A (gL/gG)

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2-40°C ... 80°C -40°C ... 80°C -40°C ... 80°CV0 V0 V0IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11Single-pos. PDT Single-pos. PDT Single-pos. PDT0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC 250 V AC 250 V AC1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-MS-T1/T2 335/12.5/4+0-FM 2800644 1 VAL-MS-T1/T2 335/12.5/3+0-FM 2800188 1 VAL-MS-T1/T2 335/12.5/1+1-FM 2800186 1VAL-MS-T1/T2 335/12.5/4+0 2800645 1 VAL-MS-T1/T2 335/12.5/3+0 2800189 1 VAL-MS-T1/T2 335/12.5/1+1 2800187 1

VAL-MS-T1/T2 175/12.5/3+0-FM 2800672 1 VAL-MS-T1/T2 175/12.5/1+1-FM 2800674 1VAL-MS-T1/T2 175/12.5/3+0 2800673 1 VAL-MS-T1/T2 175/12.5/1+1 2800675 1

Accessories Accessories Accessories

VAL-MS-T1/T2 335/12.5 ST 2800190 10 VAL-MS-T1/T2 335/12.5 ST 2800190 10 VAL-MS-T1/T2 335/12.5 ST 2800190 10VAL-MS-T1/T2 175/12.5 ST 2800676 10 VAL-MS-T1/T2 175/12.5 ST 2800676 10

F-MS-T1/T2 50 ST 2800191 10

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

27PHOENIX CONTACT

12 14

11 FM

NL1 L2 L3

PENPEN

L1 L2 L3

12 14

11 FM

12 14

11 FM

NL

Surge protection for the IEC/EN power supply unit

Type 1 lightning arrester

5-conductor system; L1, L2, L3, N, PE (4+0 circuit)

4-conductor system; L1, L2, L3, PEN 3-conductor system; L, N, PE

Total width 142.8 mm Total width 106.9 mm

Technical data Technical dataElectrical dataIEC category / EN type I + II / T1 + T2 I + II / T1 + T2Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / 350 V AC / - - / - / 350 V ACLightning test curr. Iimp (10/350) s

Peak value 100 kA 75 kA (3-pos.)Charge 50 As 37.5 As

Specific energy 2.50 MJ/ 1.40 MJ/Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 25 kA / 100 kA / - - / - / 75 kA (all channels)Follow current quenching capacity Ifi

L-N / N-PE / L-PEN 25 kA (264 V AC) / 100 A / - - / - / 25 kA (264 V AC)Protection level UP

L-N / N-PE / L-PEN 1.5 kV / 1.5 kV / - - / - / 1.5 kVResponse time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / - - / - / 25 nsMax. backup fuse according to IEC 315 A (gL/gG) 315 A (gL / gG)Immunity to short-circuiting (with max. backup fuse) IP 25 kA 25 kA

General dataConnection data solid / stranded / AWG 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 / UL 1449 IEC 61643-1 / EN 61643-11 / UL 1449Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC / 200 mA DC 1 A AC / 200 mA DC

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

FLASHTRAB compactFLT-CP-3S-350 2859712 1 FLT-CP-3C-350 2859725 1

Accessories AccessoriesReplacement connector

L-N / L-PEN FLT-CP-350-ST 2881887 10 FLT-CP-350-ST 2881887 10N-PE FLT-CP-N/PE-350-ST 2859686 10

L-N / L-PEN VAL-CP-350-ST 2859602 10 VAL-CP-350-ST 2859602 10

Labeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

28 PHOENIX CONTACT

N

PE L2L1 L3

12 14

11 FM

PEN

L1 L2 L3

12 14

11 FM

– Seamless pluggability (even for N/PE spark gap)

– Thermal disconnect device for each individual connector

– Optical, mechanical status indication for the individual arresters

– With floating remote indication contact– Connectors can be checked with

CHECKMASTER– High continuous voltage of 350 V AC for

230/400 V AC networks with high voltage fluctuations

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

FLASHTRAB compact

Surge protection for the IEC/EN power supply unit

Type 1 + 2 lightning/surge arrester combinations

5-conductor system; L1, L2, L3, N, PE 4-conductor system; L1, L2, L3, PEN

For additional information, visit www.phoenixcontact.net/catalog

Total width 106.9 mm Total width 71.6 mm Total width 71.6 mm

Technical data Technical data Technical data

I + II / T1 + T2 I + II / T1 + T2 I + II / T1 + T2240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230 V AC ... 240 V AC)

350 V AC / 350 V AC / - - / - / 350 V AC 350 V AC / 350 V AC / -

75 kA 50 kA (2-pos.) 50 kA37.5 As 25 As 25 As1.40 MJ/ 625.00 kJ/ 625.00 kJ/

25 kA / 100 kA / - - / - / 50 kA (all channels) 25 kA / 100 kA / -

25 kA (264 V AC) / 100 A / - - / - / 25 kA (264 V AC) 25 kA (264 V AC) / 100 A / -

1.5 kV / 1.5 kV / - - / - / 1.5 kV 1.5 kV / 1.5 kV / -

25 ns / 100 ns / - - / - / 25 ns 25 ns / 100 ns / -315 A (gL/gG) 315 A (gL / gG) 315 A (gL/gG)25 kA 25 kA 25 kA

2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2-40°C ... 80°C -40°C ... 80°C -40°C ... 80°CV0 V0 V0IEC 61643-1 / EN 61643-11 / UL 1449 IEC 61643-1 / EN 61643-11 / UL 1449 IEC 61643-1 / EN 61643-11 / UL 1449PDT contact PDT contact PDT contact0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 125 V DC 250 V AC / 125 V DC 250 V AC / 125 V DC1 A AC / 200 mA DC 1 A AC / 200 mA DC 1 A AC / 200 mA DC

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

FLT-CP-2S-350 2859767 1 FLT-CP-2C-350 2859770 1 FLT-CP-1S-350 2859738 1

Accessories Accessories Accessories

FLT-CP-350-ST 2881887 10 FLT-CP-350-ST 2881887 10 FLT-CP-350-ST 2881887 10FLT-CP-N/PE-350-ST 2859686 10 FLT-CP-N/PE-350-ST 2859686 10VAL-CP-350-ST 2859602 10 VAL-CP-350-ST 2859602 10 VAL-CP-350-ST 2859602 10

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

29PHOENIX CONTACT

N

PE L1 L2

12 14

11 FM

PEN

L1 L2

12 14

11 FM

N

PE L1

12 14

11 FM

Surge protection for the IEC/EN power supply unit

Type 1 + 2 lightning/surge arrester combinations

4-conductor system; L1, L2, N, PE 3-conductor system; L1, L2, PEN 3-conductor system; L, N, PE

Total width 35.8 mm

Technical dataElectrical dataIEC category / EN type I + II / T1 + T2Nominal voltage UN 240 V AC (230 V AC ... 240 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / - / 350 V ACLightning test curr. Iimp (10/350) s

Peak value 25 kACharge 12.5 As

Specific energy 160.00 kJ/Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 25 kA / - / 25 kAFollow current quenching capacity Ifi

L-N / N-PE / L-PEN 25 kA (264 V AC) / - / 25 kA (264 V AC)Protection level UP

L-N / N-PE / L-PEN 1.5 kV / - / 1.5 kVResponse time tA

L-N / N-PE / L-PEN 25 ns / - / 25 nsMax. backup fuse according to IEC 315 A (gL / gG)Immunity to short-circuiting (with max. backup fuse) IP 25 kA

General dataConnection data solid / stranded / AWG 2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2Temperature range -40°C ... 80°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / EN 61643-11 / UL 1449

Remote indication contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DCMax. operating current 1 A AC / 200 mA DC

Ordering data

Description Type Order No. Pcs. / Pkt.

FLASHTRAB compactSingle-pos. FLT-CP-1C-350 2859741 1

AccessoriesReplacement connector

L-N / L-PEN FLT-CP-350-ST 2881887 10N-PE

L-N / L-PEN VAL-CP-350-ST 2859602 10

Labeling material ZBN 18 ..., see page 59

30 PHOENIX CONTACT

PEN

L1

12 14

11 FM

FLASHTRAB compact

– Seamless pluggability (even for N/PE spark gap)

– Thermal disconnect device for each individual connector

– Optical, mechanical status indication for the individual arresters

– With floating remote indication contact– Connectors can be checked with

CHECKMASTER– High continuous voltage of 350 V AC for

230/400 V AC networks with high voltage fluctuations

Surge protection for the IEC/EN power supply unit

Type 1 + 2 lightning/surge arrester combinations

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

2-conductor system; L, PEN

For additional information, visit www.phoenixcontact.net/catalog

Total width 35.8 mm

Technical data

I / T1240 V AC (N-PE)

- / 350 V AC / -

100 kA50 As2.50 MJ/

- / 100 kA / -

- / 100 A / -

- / 1.5 kV / -

- / 100 ns / --25 kA

2.5 ... 35 mm² / 2.5 ... 25 mm² / 13 - 2-40°C ... 80°CV0IEC 61643-1 / EN 61643-11 / EN 61643-11/A11 /UL 1449PDT contact0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 125 V DC1 A AC / 200 mA DC

Ordering data

Type Order No. Pcs. / Pkt.

FLT-CP-N/PE-350 2859754 1

Accessories

FLT-CP-N/PE-350-ST 2859686 10

ZBN 18 ..., see page 59

31PHOENIX CONTACT

N

PE

12 14

11 FM

Surge protection for the IEC/EN power supply unit

Type 1 + 2 lightning/surge arrester combinations

N-PE spark gap, for Lightning Protection Level 1

Total width 49.2 mm Total width 37.25 mm

Technical data Technical dataElectrical data ... 350 ... 175 ... 350 ... 175IEC category / EN type II / T2 II / T2 II / T2 II / T2Nominal voltage UN 240 V AC (230/400 V AC ...

240/415 V AC)120 V AC 240 V AC (230/400 V AC ...

240/415 V AC)120 V AC (3P/PEN)

Maximum continuous operating voltage UCL-N / N-PE / L-PEN 350 V AC / 264 V AC / - 175 V AC / 150 V AC / - - / - / 350 V AC - / - / 175 V AC

Nominal discharge surge current In (8/20) μsL-N / N-PE / L-PEN 60 kA (all channels) / 20 kA / - 60 kA (all channels) / 20 kA / - - / - / 60 kA (all channels) - / - / 60 kA (all channels)

Max. discharge surge current Imax. (8/20) μsL-N / N-PE / L-PEN 120 kA (all channels) / 40 kA / - 120 kA (all channels) / 40 kA / - - / - / 120 kA (all channels) - / - / 120 kA (all channels)

Residual voltage at 5 kA L-N / N-PE / L-PEN 1.1 kV / 0.25 kV / - 600 V / 200 V / - - / - / 1.1 kV - / - / 600 VProtection level UP

L-N / N-PE / L-PEN 1.4 kV / 1.5 kV / - 850 V / 950 V / - - / - / 1.4 kV - / - / 850 V (at In)Response time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / - 25 ns / 100 ns / - - / - / 25 ns - / - / 25 nsMax. backup fuse according to IEC 125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG)General dataConnection data solid / stranded / AWG 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 /

IEEE C62.1 / IEEE C62.45 / IEEE C62.34 IEEE C62.1 / IEEE C62.34 / IEEE C62.45Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC (ohmic) / 200 mA DC (ohmic) 1 A AC (ohmic) / 200 mA DC (ohmic)

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB compactWith remote indication contact VAL-CP-3S-350 2859521 1 VAL-CP-3C-350 2859547 1Without remote indication contact VAL-CP-3S-350/O 2881010 1 VAL-CP-3C-350/O 2881023 1With remote indication contact VAL-CP-3S-175 2859453 1 VAL-CP-3C-175 2859466 1Bridge set, for bridging VALVETRAB compact to the r.c.c.b.

MPB SET VAL-CP-3S 2880684 1

Accessories AccessoriesReplacement connector

L-N / L-PEN VAL-CP-350-ST 2859602 10 VAL-CP-350-ST 2859602 10N-PE VAL-CP-N/PE-350-ST 2859699 10

L-N / L-PEN VAL-CP-175-ST 2859628 10 VAL-CP-175-ST 2859628 10

Labeling material ZBFM 5 ..., see page 59 ZBFM 5 ..., see page 59

32 PHOENIX CONTACT

12 14

11 FM

N

PE L1 L2 L3

12 14

11 FM

PEN

L1 L2 L3

– Type 2 seamless plug-in surge arrester– Disconnect device on each individual

connector– Optical, mechanical status indication for

the individual arresters– With or without floating remote

indication contact– Mechanical keying of all slots– Modular arrester blocks with ultra-slim

design– Use of varistors that are free of leakage

current– Connectors can be checked with

CHECKMASTER– High continuous voltage of 350 V AC for

230/400 V AC networks with high voltage fluctuations

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

VALVETRAB compact

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

5-conductor system; L1, L2, L3, N, PE 4-conductor system; L1, L2, L3, PEN

For additional information, visit www.phoenixcontact.net/catalog

Total width 37.25 mm Total width 25.3 mm Total width 25.3 mm

Technical data Technical data Technical data... 350 ... 175 ... 350 ... 175 ... 350 ... 175II / T2 II / T2 II / T2 II / T2 II / T2 II / T2240 V AC (230/400 V AC ... 240/415 V AC)

120 V AC 240 V AC (230/400 V AC ... 240/415 V AC)

120 V AC (2P/PEN) 240 V AC (230/400 V AC ... 240/415 V AC)

120 V AC

350 V AC / 264 V AC / - 175 V AC / 150 V AC / - - / - / 350 V AC - / - / 175 V AC 350 V AC / 264 V AC / - 175 V AC / 150 V AC / -

40 kA (all channels) / 20 kA / - 40 kA (all channels) / 20 kA / - - / - / 40 kA (all channels) - / - / 40 kA (all channels) 20 kA / 20 kA / - 20 kA / 20 kA / -

80 kA (all channels) / 40 kA / - 80 kA (all channels) / 40 kA / - - / - / 80 kA (all channels) - / - / 80 kA (all channels) 40 kA / 40 kA / - 40 kA / 40 kA / - 1.1 kV / 0.25 kV / - 600 V / 200 V / - - / - / 1.1 kV - / - / 600 V 1.1 kV / 0.25 kV / - 600 V / 200 V / -

1.4 kV / 1.5 kV / - 850 V / 950 V / - - / - / 1.4 kV - / - / 850 V (at In) 1.4 kV / 1.5 kV / - 850 V / 950 V / -

25 ns / 100 ns / - 25 ns / 100 ns / - - / - / 25 ns - / - / 25 ns 25 ns / 100 ns / - 25 ns / 100 ns / -125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG)

2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4-40°C ... 80°C -40°C ... 80°C -40°C ... 80°C

V0 V0 V0IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 /

IEEE C62.1 / IEEE C62.45 / IEEE C62.34 IEEE C62.1 / IEEE C62.34 / IEEE C62.45 IEEE C62.1 / IEEE C62.45 / IEEE C62.34PDT contact PDT contact PDT contact

0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 125 V DC 250 V AC / 125 V DC 250 V AC / 125 V DC

1 A AC (ohmic) / 200 mA DC (ohmic) 1 A AC (ohmic) / 200 mA DC (ohmic) 1 A AC (ohmic) / 200 mA DC (ohmic)

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-CP-2S-350 2859505 1 VAL-CP-2C-350 2859589 1 VAL-CP-1S-350 2859563 1VAL-CP-2S-350/O 2881049 1 VAL-CP-2C-350/O 2881052 1 VAL-CP-1S-350/O 2881036 1VAL-CP-2S-175 2859495 1 VAL-CP-2C-175 2859482 1 VAL-CP-1S-175 2859479 1

Accessories Accessories Accessories

VAL-CP-350-ST 2859602 10 VAL-CP-350-ST 2859602 10 VAL-CP-350-ST 2859602 10VAL-CP-N/PE-350-ST 2859699 10 VAL-CP-N/PE-350-ST 2859699 10VAL-CP-175-ST 2859628 10 VAL-CP-175-ST 2859628 10 VAL-CP-175-ST 2859628 10

ZBFM 5 ..., see page 59 ZBFM 5 ..., see page 59 ZBFM 5 ..., see page 59

33PHOENIX CONTACT

12 14

11 FM

N

PE L1 L2

12 14

11 FM

PEN

L1 L2

12 14

11 FM

N

PE L1

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

4-conductor system; L1, L2, N, PE 3-conductor system; L1, L2, PEN 3-conductor system; L, N, PE

Total width 49.2 mm Total width 37.25 mm

Technical data Technical dataElectrical dataIEC category / EN type II / T2 II / T2Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / 264 V AC / - - / - / 350 V ACNominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 30 kA (all channels) / 20 kA / - - / - / 30 kA (all channels)Max. discharge surge current Imax. (8/20) μs

L-N / N-PE / L-PEN 60 kA (all channels) / 40 kA / - - / - / 60 kA (all channels)Residual voltage at 5 kA L-N / N-PE / L-PEN 1 kV / 0.25 kV / - - / - / 1 kVProtection level UP

L-N / N-PE / L-PEN 1.5 kV / 1.5 kV / - - / - / 1.5 kVResponse time tA

L-N / N-PE / L-PEN 100 ns / 100 ns / - - / - / 100 nsMax. backup fuse according to IEC 125 A (gL/gG) 125 A (gL/gG)General dataConnection data solid / stranded / AWG 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 /

IEEE C62.1 / IEEE C62.34 / IEEE C62.45 IEEE C62.1 / IEEE C62.34 / IEEE C62.45Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC (ohmic) / 200 mA DC (ohmic) 1 A AC (ohmic) / 200 mA DC (ohmic)

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB compactVAL-CP-3S-350VF 2859518 1 VAL-CP-3C-350 VF 2859534 1

Accessories AccessoriesReplacement connector

L-N / L-PEN VAL-CP-350 VF-ST 2859615 10 VAL-CP-350 VF-ST 2859615 10N-PE VAL-CP-N/PE-350-ST 2859699 10

Labeling material ZBFM 5 ..., see page 59 ZBFM 5 ..., see page 59

34 PHOENIX CONTACT

12 14

11 FM

N

PE L1 L2 L3

12 14

11 FM

PEN

L1 L2 L3

– Type 2 seamless plug-in surge arrester– Versions free of leakage current through

series connection of varistor and surge arrester

– Disconnect device on each individual connector

– Optical, mechanical status indication for the individual arresters

– With floating remote indication contact– Mechanical keying of all slots– Modular arrester blocks with ultra-slim

design– High continuous voltage of 350 V AC for

230/400 V AC networks with high voltage fluctuations

Further versions on request.

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

VALVETRAB compact, free of leakage current

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

5-conductor system; L1, L2, L3, N, PE 4-conductor system; L1, L2, L3, PEN

For additional information, visit www.phoenixcontact.net/catalog

Total width 37.25 mm Total width 25.3 mm Total width 25.3 mm

Technical data Technical data Technical data

II / T2 II / T2 II / T2240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)

350 V AC / 264 V AC / - - / - / 350 V AC 350 V AC / 264 V AC / -

20 kA (all channels) / 20 kA / - - / - / 10 kA (1 channel) 10 kA / 20 kA / -

40 kA (all channels) / 40 kA / - - / - / 40 kA (all channels) 20 kA / 40 kA / - 1 kV / 0.25 kV / - - / - / 1 kV 1 kV / 0.25 kV / -

1.5 kV / 1.5 kV / - - / - / 1.5 kV 1.5 kV / 1.5 kV / -

100 ns / 100 ns / - - / - / 100 ns 100 ns / 100 ns / -125 A (gL/gG) 125 A (gL/gG) 125 A (gL/gG)

2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4-40°C ... 80°C -40°C ... 80°C -40°C ... 80°CV0 V0 V0IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 / IEC 61643-1 / EN 61643-11 / UL 1449 /IEEE C62.1 / IEEE C62.34 / IEEE C62.45 IEEE C62.1 / IEEE C62.34 / IEEE C62.45 IEEE C62.1 / IEEE C62.34 / IEEE C62.45PDT contact PDT contact PDT contact0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 125 V DC 250 V AC / 125 V DC 250 V AC / 125 V DC1 A AC (ohmic) / 200 mA DC (ohmic) 1 A AC (ohmic) / 200 mA DC (ohmic) 1 A AC (ohmic) / 200 mA DC (ohmic)

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-CP-2S-350 VF 2859592 1 VAL-CP-2C-350 VF 2859576 1 VAL-CP-1S-350 VF 2859550 1

Accessories Accessories Accessories

VAL-CP-350 VF-ST 2859615 10 VAL-CP-350 VF-ST 2859615 10 VAL-CP-350 VF-ST 2859615 10VAL-CP-N/PE-350-ST 2859699 10 VAL-CP-N/PE-350-ST 2859699 10

ZBFM 5 ..., see page 59 ZBFM 5 ..., see page 59 ZBFM 5 ..., see page 59

35PHOENIX CONTACT

12 14

11 FM

N

PE L1 L2

12 14

11 FM

PEN

L1 L2

12 14

11 FM

N

PE L1

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

4-conductor system; L1, L2, N, PE 3-conductor system; L1, L2, PEN 3-conductor system; L, N, PE

Total width 70.8 mm Total width 70.8 mm

Technical data Technical dataElectrical data VAL-MS 230 VAL-MS 320 VAL-MS 120 VAL-MS 320IEC category / EN type II / T2 II / T2 II / T2 II / T2Nominal voltage UN 230 V AC (400 V AC) 230 V AC (400 V AC) 120 V AC (208 V AC) 230 V AC (400 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 275 V AC / 260 V AC / - 335 V AC / 260 V AC / - 150 V AC / 260 V AC / - 335 V AC / 260 V AC / -Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 20 kA / 20 kA / - 20 kA / 20 kA / - 20 kA / 20 kA / - 20 kA / 20 kA / -Max. discharge surge current Imax. (8/20) μs

L-N / N-PE / L-PEN 40 kA / 40 kA / - 40 kA / 40 kA / - 40 kA / 40 kA / - 40 kA / 40 kA / -Residual voltage at 5 kA L-N / N-PE / L-PEN 1.1 kV / 0.15 kV / - 1.25 kV / 0.15 kV / - 0.7 kV / 0.15 kV / - 1.25 kV / 0.15 kV / -Protection level UP

L-N / N-PE / L-PEN 1.35 kV / 1.5 kV / - 1.6 kV / 1.5 kV / - 0.85 kV / 1.5 kV / - 1.6 kV / 1.5 kV / -Response time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / - 25 ns / 100 ns / - 25 ns / 100 ns / - 25 ns / 100 ns / -Max. backup fuse according to IEC 125 A (gL) 125 A (gL)Immunity to short-circuiting (with max. backup fuse) IP 25 kA 25 kA

General dataConnection data solid / stranded / AWG 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 30 V DC 250 V AC / 30 V DCMax. operating current 0.75 A AC (250 V AC) / 3 A AC (125 V AC) 0.75 A AC (250 V AC) / 3 A AC (125 V AC)

Ordering data Ordering data

Description Imax UC Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB, multi-position surge arrester combination

With remote indication contact 40 kA 150 V AC VAL-MS 120/3+1/FM-UD 2856692 1Without remote indication contact 40 kA 275 V AC VAL-MS 230/3+1 2838209 1With remote indication contact 40 kA 275 V AC VAL-MS 230/3+1 FM 2838199 1Without remote indication contact 40 kA 335 V AC VAL-MS 320/3+1 2859178 1With remote indication contact 40 kA 335 V AC VAL-MS 320/3+1/FM 2859181 1 VAL-MS 320/3+1/FM-UD 2856689 1VALVETRAB MSWithout remote indication contact 30 kA 580 V ACWith remote indication contact 30 kA 580 V AC

Accessories AccessoriesReplacement connector120 V AC 1L-N/PE VAL-MS 120-UD ST 2858292 10230 V AC 1L-N/PE VAL-MS 230 ST 2798844 10230 V AC 1L-N/PE VAL-MS 320 ST 2838843 10 VAL-MS 320-UD ST 2858315 10400 V AC 1L-N/PE230 V AC N-PE F-MS 12 ST 2817990 10 F-MS 12 ST 2817990 10

Labeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

36 PHOENIX CONTACT

12 14

11 FM

NL1 L2 L3 1214

11FM

N L1 L2 L3

– Multi-channel type 2 arrester– Type 2 seamless plug-in surge arrester– Disconnect device on each individual

connector– Optical, mechanical status indication for

the individual arresters– With or without floating remote

indication contact– Mechanical keying of all slots

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

VALVETRAB MS30/40 kA performance class

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

5-conductor system; L1, L2, L3, N, PE, supply line supply from below

5-conductor system; L1, L2, L3, N, PE, supply line supply from above

For additional information, visit www.phoenixcontact.net/catalog

Total width 53.4 mm Total width 35.6 mm Total width 35.6 mm

Technical data Technical data Technical dataVAL-MS 320 VAL-MS 580 VAL-MS 230 VAL-MS 320II / T2 II / T2 II / T2 II / T2 II / T2230 V AC (max. 240/415 V AC) 400 V AC (400/690 V AC TN-C) 230 V AC 230 V AC 230 V AC (400 V AC)

- / - / 335 V AC - / - / 580 V AC 275 V AC / 260 V AC / - 335 V AC / 260 V AC / - - / - / 275 V AC

- / - / 60 kA (all channels) - / - / 45 kA (all channels) 20 kA / 20 kA / - 20 kA / 20 kA / - - / - / 40 kA (all channels)

- / - / 120 kA (all channels) - / - / 90 kA (all channels) 40 kA / 40 kA / - 40 kA / 40 kA / - - / - / 80 kA (all channels)- / - / 1.2 kV - / - / 2.1 kV 1.1 kV / 150 V / - - 1.2 kV / 150 V / - - / - / 1.1 kV

- / - / 1.5 kV - / - / 2.5 kV 1.35 kV / 1.5 kV / - 1.5 kV / 1.5 kV / - - / - / 1.35 kV

- / - / 25 ns - / - / 25 ns 25 ns / 100 ns / - 25 ns / 100 ns / - - / - / 25 ns125 A (gL / gG) 125 A (gL/gG) 125 A (gL/gG)

25 kA 25 kA 25 kA

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2-40°C ... 80°C -40°C ... 80°C -40°C ... 80°C

V0 V0 V0IEC 61643-1 / EN 61643-11 IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

PDT contact Single-pos. PDT Single-pos. PDT0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16

250 V AC / 30 V DC 250 V AC / 30 V DC 250 V AC / 30 V DC1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-MS 230/1+1 2804429 1 VAL-MS 230/2+0 2800103 1VAL-MS 230/1+1-FM 2804432 1 VAL-MS 230/2+0-FM 2800102 1

VAL-MS 320/3+0 2920230 1 VAL-MS 320/1+1 2804380 1VAL-MS 320/3+0-FM 2920243 1 VAL-MS 320/1+1-FM 2804393 1

VAL-MS 580/3+0 2920450 1VAL-MS 580/3+0-FM 2920447 1

Accessories Accessories Accessories

VAL-MS 230 ST 2798844 10 VAL-MS 230 ST 2798844 10VAL-MS 320 ST 2838843 10 VAL-MS 320 ST 2838843 10VAL-MS 580-ST 2920434 10

F-MS 12 ST 2817990 10

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

37PHOENIX CONTACT

PENPEN

L1 L2 L3

12 14

11 FM

12 14

11 FM

NL1

12 14

11 FMPEN

L1 L2

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

4-conductor system; L1, L2, L3, PEN 3-conductor system; L, N, PE 3-conductor system; L1, L2, PEN

Total width 17.7 mm Total width 17.7 mm

Technical data Technical dataElectrical data ... 60AC ... 230ACIEC category / EN type II / T2 II / T2 II / T2Nominal voltage UN 60 V AC/DC 230 V AC 230 V ACMaximum continuous operating voltage UC

L-N / N-PE / L-PEN 75 V AC / - / 75 V AC 275 V AC / - / 275 V AC - / 260 V AC / -

Nominal discharge surge current In (8/20) μsL-N / N-PE / L-PEN 15 kA / - / - 20 kA / - / 20 kA - / 20 kA / -

Max. discharge surge current Imax. (8/20) μsL-N / N-PE / L-PEN 40 kA / - / 40 kA 40 kA / - / 40 kA - / 40 kA / -

Residual voltage at 5 kA L-N / N-PE / L-PEN 325 V / - / 325 V 1 kV / - / 1 kV - / 150 V / -Protection level UP

L-N / N-PE / L-PEN 500 V / - / 500 V 1.35 kV / - / 1.35 kV - / 1.5 kV / -Response time tA

L-N / N-PE / L-PEN 25 ns / - / 25 ns 25 ns / - / 25 ns - / 100 ns / -Max. backup fuse according to IEC 0.125 A AC (gL/gG) -General dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

Remote indication contact Single-pos. PDT PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC / 200 mA DC 1 A AC / 200 mA DC

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB MSWith remote indication contact VAL-MS 60/FM 2868033 1 F-MS 12/FM 2817974 1Without remote indication contact VAL-MS 60 2868020 1 F-MS 12 2817987 1With remote indication contact VAL-MS 230/FM 2839130 1Without remote indication contact VAL-MS 230 2839127 1VALVETRAB surge protection plug120 V AC230 V AC IT230 V AC400 V AC500 V AC400 V AC554 V AC

Accessories AccessoriesReplacement connector60 V AC 1L-N/PE VAL-MS 60 ST 2807573 10 F-MS 12 ST 2817990 10230 V AC 1L-N/PE VAL-MS 230 ST 2798844 10

Labeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

38 PHOENIX CONTACT

12 14

11 FM

N / PEN

L 12 14

11 FM

N

– Single-channel, DIN-rail mountable protective devices

– Comprising base element and connector– Base element with/without floating

remote indication contact– Disconnect device on each individual

connector– Optical, mechanical status indication for

the individual arresters– Mechanical keying of all slots

VALVETRAB MS

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

2-conductor system; L, N/PEN Spark gap, N-PE

For additional information, visit www.phoenixcontact.net/catalog

Total width 17.7 mm Total width 17.7 mm Total width 17.7 mm

Technical data Technical data Technical data... 120 ST ... 230 IT ST ... 320 ST ... 400 ST ... 500 ST ... 580 ST ... 750/30 ST

II / T2 II / T2 II / T2 II / T2 II / T2 II / T2 II / T2 II / T2230 V AC 120 V AC 230 V AC 230 V AC 400 V AC 500 V AC 400 V AC 554 V AC

350 V AC / - / 350 V AC 150 V AC / 200 V DC

385 V AC / 500 V DC

335 V AC / 420 V DC 440 V AC / 585 V DC

600 V AC / 600 V DC

580 V AC / - 750 V AC / -

10 kA / - / 10 kA 20 kA 20 kA 20 kA 20 kA 15 kA 15 kA 15 kA

20 kA / - / 20 kA 40 kA 40 kA 40 kA 40 kA 30 kA 30 kA 30 kA 1 kV / - / 1 kV 550 V 1.35 kV 1.2 kV 1.5 kV 2.3 kV 2.1 kV 2.4 kV

1.5 kV / - / 1.5 kV 800 V 1.8 kV 1.5 kV 2.2 kV 2.7 kV 2.5 kV 2.7 kV

100 ns / - / 100 ns 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns125 A (gL) 125 A (gL) 125 A (gL)

0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2 - --40°C ... 80°C -40°C ... 80°C -40°C ... 80°C- V0 V0IEC 61643-1 / EN 61643-11/A11 / NF C61-740 / IEC 61643-1 / EN 61643-11/A11 / UL 1449 / IEC 61643-1 / EN 61643-11/A11 / UL 1449 /UL 1449 IEEE C62.1 / C62.34 / C62.45 IEEE C62.1 / C62.34 / C62.45PDT contact - -0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 - -250 V AC / 125 V DC - -1 A AC / 200 mA DC - -

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-MS 350 VF/FM 2856579 1VAL-MS 350VF 2856582 1

VAL-MS 120 ST 2807586 10VAL-MS 230 IT ST 2807599 10VAL-MS 320 ST 2838843 10

VAL-MS 400 ST 2816399 10VAL-MS 500 ST 2807609 10VAL-MS 580-ST 2920434 10VAL-MS 750/30-ST 2920256 10

Accessories Accessories Accessories

VAL-MS 350 VF ST 2856595 10

ZBN 18 ..., see page 59

39PHOENIX CONTACT

12 14

11 FM

L

N / PEN

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

2-conductor system; L, N/PEN Connector for VAL-MS base element Connector for VAL-MS base element

Total width 71.2 mm

Technical dataElectrical data ... 350/10 ... 350/20IEC category / EN type II / T2 II / T2Nominal voltage UN 230 V AC (400 V AC) 230 V AC (400 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / 260 V AC / - 350 V AC / 260 V AC / -Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 15 kA (all channels) / 20 kA / - 30 kA (all channels) / 20 kA / -Max. discharge surge current Imax. (8/20) μs

L-N / N-PE / L-PEN 30 kA (all channels) / 30 kA / - 60 kA (all channels) / 30 kA / -Residual voltage at 5 kA L-N / N-PE / L-PEN 1.2 kV / 150 V / - 1.2 kV / 150 V / -Protection level UP

L-N / N-PE / L-PEN 1.2 kV / 1.5 kV / - 1.4 kV / 1.5 kV / -Response time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / - 25 ns / 100 ns / -Max. backup fuse according to IEC 125 A (gL/gG)Immunity to short-circuiting (with max. backup fuse) IP 25 kA

General dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2Temperature range -40°C ... 80°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / EN 61643-11/A11Remote indication contact Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V ACMax. operating current 0.75 A AC (250 V AC) / 3 A (125 V AC)Min. operating current 5 mA (5 V)

Ordering data

Description Imax UC Type Order No. Pcs. / Pkt.

VALVETRAB MSWithout remote indication contact 10 kA 350 V AC VAL-MS 350/10/3+1 2803593 1With remote indication contact 10 kA 350 V AC VAL-MS 350/10/3+1-FM 2803603 1VALVETRAB MSWithout remote indication contact 20 kA 350 V AC VAL-MS 350/20/3+1 2803548 1With remote indication contact 20 kA 350 V AC VAL-MS 350/20/3+1-FM 2803551 1

AccessoriesReplacement connector350 V AC 1L-N/PE VAL-MS 350/10 ST 2803564 1350 V AC 1L-N/PE VAL-MS 350/20 ST 2803506 1260 V AC N-PE F-MS 30 ST 2803519 1Base element, for individual assembly with protective connectors

Without remote indication contact VAL-MS/3+1-BE 2838885 1With remote indication contact VAL-MS/3+1-BE/FM 2838898 1

Labeling material ZBN 18 ..., see page 59

40 PHOENIX CONTACT

12 14

11 FM

NL1 L2 L3

VALVETRAB MS10/20 kA performance class

– Multi-channel type 2 arrester– Type 2 seamless plug-in surge arrester– Disconnect device on each individual

connector– Optical, mechanical status indication for

the individual arresters– With or without floating remote

indication contact– Mechanical keying of all slots– Solutions for the low performance class

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

5-conductor system; L1, L2, L3, N, PE

For additional information, visit www.phoenixcontact.net/catalog

Total width 53.4 mm Total width 35.6 mm

Technical data Technical data... 350/10 ... 350/20 ... 350/10 ... 350/20II / T2 II / T2 II / T2 II / T2230 V AC (400 V AC) 230 V AC (400 V AC) 230 V AC (400 V AC) 230 V AC (400 V AC)

- / - / 350 V AC - / - / 350 V AC 350 V AC / 260 V AC / - 350 V AC / 260 V AC / -

- / - / 15 kA (all channels) - / - / 30 kA (all channels) 5 kA / 20 kA / - 10 kA / 20 kA / -

- / - / 30 kA (all channels) - / - / 60 kA (all channels) 10 kA / 30 kA / - 20 kA / 30 kA / -- / - / 1.2 kV - / - / 1.2 kV 1.2 kV / 150 V / - 1.2 kV / 150 V / -

- / - / 1.2 kV - / - / 1.4 kV 1.2 kV / 1.5 kV / - 1.4 kV / 1.5 kV / -

- / - / 25 ns - / - / 25 ns 25 ns / 100 ns / - 25 ns / 100 ns / -125 A (gL/gG) 125 A (gL/gG)

25 kA 25 kA

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2-40°C ... 80°C -40°C ... 80°C

V0 V0IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

Single-pos. PDT Single-pos. PDT0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16

250 V AC 250 V AC1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

5 mA (5 V) 5 mA (5 V)

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VAL-MS 350/10/3+0 2803577 1 VAL-MS 350/10/1+1 2803632 1VAL-MS 350/10/3+0-FM 2803580 1 VAL-MS 350/10/1+1-FM 2803645 1

VAL-MS 350/20/3+0 2803522 1 VAL-MS 350/20/1+1 2803616 1VAL-MS 350/20/3+0-FM 2803535 1 VAL-MS 350/20/1+1-FM 2803629 1

Accessories Accessories

VAL-MS 350/10 ST 2803564 1 VAL-MS 350/10 ST 2803564 1VAL-MS 350/20 ST 2803506 1 VAL-MS 350/20 ST 2803506 1

F-MS 30 ST 2803519 1

VAL-MS/3+0-BE 2881816 1 VAL-MS/1+1-BE 2920528 1VAL-MS/3+0-BE/FM 2881803 1 VAL-MS/1+1-BE/FM 2920531 1

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

41PHOENIX CONTACT

PENPEN

L1 L2 L3

12 14

11 FM

12 14

11 FM

NL

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

4-conductor system; L1, L2, L3, PEN 3-conductor system; L, N, PE

Total width 71.2 mm

Technical dataElectrical data .. 385/65 .. 385/80IEC category / EN type II / T2 II / T2Nominal voltage UN 240 V AC (230/400 V AC ...

240/415 V AC)240 V AC (230/400 V AC ... 240/415 V AC)

Maximum continuous operating voltage UCL-N / N-PE / L-PEN 385 V AC / 264 V AC / - 385 V AC / 264 V AC / -

Nominal discharge surge current In (8/20) μsL-N / N-PE / L-PEN 30 kA / 40 kA / - 40 kA / 40 kA / -

Max. discharge surge current Imax. (8/20) μsL-N / N-PE / L-PEN 65 kA / 80 kA / - 80 kA / 80 kA / -

Residual voltage at 5 kA L-N / N-PE / L-PEN 1 kV / 0.5 kV / - 1 kV / 0.5 kV / -Protection level UP

L-N / N-PE / L-PEN 1.8 kV / 1.7 kV / - 1.8 kV / 1.7 kV / -Response time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / - 25 ns / 100 ns / -Max. backup fuse according to IEC 250 A (gL/gG)Immunity to short-circuiting (with max. backup fuse) IP 25 kA

General dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2Temperature range -40°C ... 80°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / DIN EN 61643-11Remote indication contact Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V ACMax. operating current 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)Min. operating current 5 mA (5 V)

Ordering data

Description Imax UC Type Order No. Pcs. / Pkt.

VALVETRAB MSWith remote indication contact 65 kA 385 V AC VAL-MS 385/65/3+1-FM 2920887 1Without remote indication contact 65 kA 385 V AC VAL-MS 385/65/3+1 2920890 1VALVETRAB MSWith remote indication contact 80 kA 385 V AC VAL-MS 385/80/3+1-FM 2920968 1Without remote indication contact 80 kA 385 V AC VAL-MS 385/80/3+1 2920971 1

AccessoriesReplacement connectorFor VAL-MS 385/65... 1L-N/PE VAL-MS 385/65 ST 2920308 10For VAL-MS 385/80... 1L-N/PE VAL-MS 385/80 ST 2920353 10

N-PE F-MS 80 ST 2921307 10Base element, for individual assembly with protective connectors

Without remote indication contact VAL-MS/3+1-BE 2838885 1With remote indication contact VAL-MS/3+1-BE/FM 2838898 1

Labeling material ZBN 18 ..., see page 59

42 PHOENIX CONTACT

12 14

11 FM

NL1 L2 L3

/ PE / PE

VALVETRAB MS65/80 kA performance class

– Multi-channel type 2 arrester– Type 2 seamless plug-in surge arrester– Secure hold of connectors in the event of

high lightning current loads and strong vibration thanks to new latching

– Disconnect device on each individual connector

– Optical, mechanical status indication for the individual arresters

– With or without floating remote indication contact

– Mechanical keying of all slots– Connectors can be checked with

CHECKMASTER

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

5-conductor system; L1, L2, L3, N, PE

For additional information, visit www.phoenixcontact.net/catalog

Total width 53.4 mm Total width 35.6 mm

Technical data Technical data.. 385/65 .. 385/80 .. 385/65 .. 385/80II / T2 II / T2 II / T2 II / T2240 V AC (230/400 V AC ... 240/415 V AC)

240 V AC (230/400 V AC ... 240/415 V AC)

240 V AC (230 V AC ... 240 V AC)

240 V AC (230 V AC ... 240 V AC)

- / - / 385 V AC - / - / 385 V AC 385 V AC / 264 V AC / - 385 V AC / 264 V AC / -

- / - / 90 kA (all channels) - / - / 120 kA (all channels) 30 kA / 40 kA / - 40 kA / 40 kA / -

- / - / 150 kA (all channels) - / - / 200 kA (all channels) 65 kA / 80 kA / - 80 kA / 80 kA / -- / - / 1 kV - / - / 1 kV 1 kV / 0.5 kV / - 1 kV / 0.5 kV / -

- / - / 1.8 kV - / - / 1.8 kV 1.8 kV / 1.7 kV / - 1.8 kV / 1.7 kV / -

- / - / 25 ns - / - / 25 ns 25 ns / 100 ns / - 25 ns / 100 ns / -250 A (gL/gG) 250 A (gL/gG)

25 kA 25 kA

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2-40°C ... 80°C -40°C ... 80°C

V0 V0IEC 61643-1 / DIN EN 61643-11 IEC 61643-1 / DIN EN 61643-11

Single-pos. PDT Single-pos. PDT0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16

250 V AC 250 V AC1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

5 mA (5 V) 5 mA (5 V)

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VAL-MS 385/65/3+0-FM 2921006 1 VAL-MS 385/65/1+1-FM 2921242 1VAL-MS 385/65/3+0 2921019 1 VAL-MS 385/65/1+1 2921255 1

VAL-MS 385/80/3+0-FM 2921080 1 VAL-MS 385/80/1+1-FM 2921284 1VAL-MS 385/80/3+0 2921093 1 VAL-MS 385/80/1+1 2921297 1

Accessories Accessories

VAL-MS 385/65 ST 2920308 10 VAL-MS 385/65 ST 2920308 10VAL-MS 385/80 ST 2920353 10 VAL-MS 385/80 ST 2920353 10

F-MS 80 ST 2921307 10

VAL-MS/3+0-BE 2881816 1 VAL-MS/1+1-BE 2920528 1VAL-MS/3+0-BE/FM 2881803 1 VAL-MS/1+1-BE/FM 2920531 1

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

43PHOENIX CONTACT

PENPEN

L1 L2 L3

12 14

11 FM

12 14

11 FM

NL1

/ PE / PE

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

4-conductor system; L1, L2, L3, PEN 3-conductor system; L, N, PE

Total width 70.8 mm Total width 53.4 mm

Technical data Technical dataElectrical dataNominal voltage UN - 400 V AC (690 V AC)Max. backup fuse according to IEC 125 A (gL / gG) 200 A (gL / gG)General dataConnection data solid / stranded / AWG 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

Remote indication contact Single-pos. PDT Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 30 V DC 250 V AC / 30 V DCMax. operating current 0.75 A AC (250 V AC) / 2 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB, base elementWith remote indication contact VAL-MS/3+1-BE/FM 2838898 1 VAL-MS/3+0-BE/FM 2881803 1Without remote indication contact VAL-MS/3+1-BE 2838885 1 VAL-MS/3+0-BE 2881816 1

Accessories AccessoriesLabeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

44 PHOENIX CONTACT

PE

L1 L2 L3 N

12 14

11 FM

PEN

L1 L2 L3

12 14

11 FM

– Single/multi-pos. design for accommodating protective connectors

– Versions with and without floating remote indication contact

– Keying when protective connector is inserted for the first time

– DIN rail module

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

Not to be used with VAL-MS-T1/T2....ST, VAL-MS...65...ST, and VAL-MS...80...ST

VALVETRAB MS base elements

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

5-conductor system; L1, L2, L3, N, PE 4-conductor system; L1, L2, L3, PEN

For additional information, visit www.phoenixcontact.net/catalog

Total width 36.2 mm Total width 35.6 mm Total width 17.7 mm

Technical data Technical data Technical data

240 V AC (415 V AC) 240 V AC (1P/N/PE) 240 V AC200 A (gL / gG) 200 A (gL/gG) 125 A (gL/gG)

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 0.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2-40°C ... 80°C -40°C ... 80°C -40°C ... 80°CV0 V0 V0IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

Single-pos. PDT Single-pos. PDT PDT contact0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 30 V DC 250 V AC / 30 V DC 250 V AC / 125 V DC1 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1 A AC (ohmic) / 200 mA DC (ohmic)

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-MS/2+0-BE/FM 2805321 1 VAL-MS/1+1-BE/FM 2920531 1 VAL-MS BE/FM 2817738 10VAL-MS/2+0-BE 2804584 1 VAL-MS/1+1-BE 2920528 1 VAL-MS BE 2817741 10

Accessories Accessories AccessoriesZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

45PHOENIX CONTACT

PEN

L1 L2

12 14

11FM

PE

L1 N

12 14

11 FM

12 14

11 FM

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester

3-conductor system; L1, L2, PEN 3-conductor system; L, N, PE Single-position base element for use in single and multi-phase networks

Total width 35.6 mm Total width 35.6 mm

Technical data Technical dataElectrical data Base element PlugIEC category / EN type II / T2 - / - II / T2Nominal voltage UN 690 V AC 240 V AC (415 V AC) 48 V AC (5 V...48 V AC)Maximum continuous operating voltage UC

L-PE 800 V AC - 75 V ACNominal discharge surge current In (8/20) μs

L-PE 15 kA - 10 kAMax. discharge surge current Imax. (8/20) μs

L-PE 30 kA - 20 kAResidual voltage at 5 kA

L-PE 2.4 kV (at 5 kA) - 350 V (at 5 kA)Protection level UP

L-PE 5 kV - 1.4 kVResponse time tA

L-PE 100 ns - 100 nsMax. backup fuse according to IEC 100 A (gL / gG) 63 A (gL / gG) 63 A (gL / gG) 63 A (gL / gG)General dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1 ... 35 mm² / 1 ... 25 mm² / 18 - 2Temperature range -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11 IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11Remote indication contact Single-pos. PDT Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC 250 VMax. operating current 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB MS, with protective connectors connected in series

With remote indication contact VAL-MS 800/30 VF/FM 2805402 1

Accessories AccessoriesProtective connector, for inserting in base element

554 V AC 1L-N/PE VAL-MS 750/30-ST 2920256 10 VAL-MS 75 VF ST 2805318 10230 V AC N-PE F-MS 2200/30 ST 2805392 10 F-MS 12 ST 2817990 10Base element, for individual assembly with protective connectors

With remote indication contact VAL-MS 1+1-BE/FM/HD/S1A 2800257 1 VAL-MS/2+0-BE/FM/S2 2800246 1

Labeling material ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

46 PHOENIX CONTACT

– Type 2 seamless plug-in surge arrester– Also suitable for industry solutions, e.g.,

in the wind industry– Disconnect device on each individual

connector– Optical, mechanical status indication for

the individual arresters– With or without floating remote

indication contact– Mechanical keying of all slots

Type 2 surge arrester

Surge protection for the IEC/EN power supply unit

Special systems

12 14

11 FM

L

12 14

11 FM

1 2

Free of leakage current, for nominal voltages up to 690 V AC, e.g., rotor protection for wind

power plants

Free of leakage current, for nominal voltages up to 48 V AC

For additional information, visit www.phoenixcontact.net/catalog

Total width 142 mm Total width 53.4 mm

Technical data Technical dataElectrical data ... T1 ... T2IEC category / EN type I / T1 II / T2 II / T2Nominal voltage UN 400 V AC (690 V AC) 400 V AC (690 V AC) 554 V AC (554/960 V AC TN-C)Maximum continuous operating voltage UC

L-PEN 440 V AC 600 V AC 750 V ACLightning test curr. Iimp (10/350) s

Peak value 50 kA (per channel) - -Charge 25 As - -

Specific energy 625.00 kJ/ - -Nominal discharge surge current In (8/20) μs

L-PEN 150 kA (all channels) 45 kA (all channels) 45 kA (all channels)Follow current quenching capacity Ifi

L-PEN 25 kA (440 V AC) - -Protection level UP

L-PEN 3 kV 2.7 kV 2.7 kVResponse time tA

L-PEN 100 ns 25 ns 25 nsGeneral dataConnection data solid / stranded / AWG 10 ... 50 mm² /

16 ... 35 mm² / 6- 10.5 ... 35 mm² / 0.5 ... 25 mm² / 20 - 2

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2

Temperature range -40°C ... 85°C -40°C ... 80°C -40°C ... 80°CInflammability class according to UL 94 V0 V0 V0Test standards IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / DIN EN 61643-11 /

DIN EN 61643-11/A11IEC 61643-1 / DIN EN 61643-11 / DIN EN 61643-11/A11

Remote indication contact - PDT contact PDT contactConnection data solid / stranded / AWG - 1.5 ... 0.14 mm² /

1.5 ... 0.14 mm² / 28 - 160.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16

Max. operating voltage - 250 V AC 250 V ACMax. operating current - 1 A AC (inductive) 1.5 A AC (250 V AC) / 1.5 A DC (30 V DC)

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

SYS-SET, multi-position lightning arrester combination

Type 1 SYS-SET/3/T1/690 2800126 1Surge protection combinationType 2 SYS-SET/3/T2/690 2880341 1VALVETRAB MSWith remote indication contact VAL-MS 750/30/3+0-FM 2920272 1Without remote indication contact VAL-MS 750/30/3+0 2920269 1VALVETRAB surge protection plug500 V AC VAL-MS 500 ST 2807609 10554 V AC VAL-MS 750/30-ST 2920256 10

47PHOENIX CONTACT

Surge protection for the IEC/EN power supply unit

Special systems

4-conductor system; L1, L2, L3, PEN (400/690 V TN-C system)

4-conductor system; L1, L2, L3, PEN (554/960 V TN-C system)

– For power supplies with higher supply voltages

– Use in powerful industrial networks and wind turbines

– Other solutions for power supplies UN ≥ 400 V available on request

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

Surge protection for 690 V AC and 960 V AC power supply systems

Total width 121 mm Total width 121 mm

Technical data Technical dataElectrical dataIEC category / EN type II / T2 II / T2Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)Maximum continuous operating voltage UC

L-N / N-PE 350 V AC / 264 V AC 350 V AC / 264 V ACNominal discharge surge current In (8/20) μs

L-N / N-PE 60 kA (all channels) / 20 kA 60 kA (all channels) / 20 kAMax. discharge surge current Imax. (8/20) μs

L-N / N-PE 90 kA (all channels) / 30 kA 90 kA (all channels) / 30 kAResidual voltage at 5 kA L-N / N-PE 1.2 kV / 0.3 kV 1.2 kV / 0.3 kVProtection level UP

L-N / N-PE 2 kV / 2 kV 2 kV / 2 kVResponse time tA

L-N / N-PE 25 ns / 100 ns 25 ns / 100 nsGeneral dataConnection data solid / stranded / AWG 4 ... 16 mm² / 4 ... 16 mm² / 12 - 4 4 ... 16 mm² / 4 ... 16 mm² / 12 - 4Temperature range -25°C ... 40°C -25°C ... 40°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 / IEC 61008-1 / IEC 61643-1 / EN 61643-11 / IEC 61008-1 /

IEC 61008-2-1 / IEC 60947-3 IEC 61008-2-1 / IEC 60947-3RCD dataClass A selective ANominal load current IL 40 A 40 ARated residual current 300 mA 30 mARated making and breaking capacity Im 630 A 1.5 kARated residual making and breaking capacity I m 630 A 2.5 kASurge withstand capability 6 kV (1.2/50 μs) 6 kV (1.2/50 μs)Immunity to short-circuiting Inc 10 kA backup fuse: 63 A 10 kA backup fuse: 63 ATripping time for I n 300 ms 300 msTripping time for 5xI n 40 ms 40 msCycles, max. 20000 20000Utilization category AC 23 A AC 23 A

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB compact with RCDVAL-CP-RCD-3S/40/0.3/SEL 2808001 1

VAL-CP-RCD-3S/40/0.03 2882802 1

Accessories AccessoriesReplacement connector

L-N / L-PEN VAL-CP-350-ST-GY 2882718 10 VAL-CP-350-ST-GY 2882718 10N-PE VAL-CP-N/PE-350-ST-GY 2882734 10 VAL-CP-N/PE-350-ST-GY 2882734 10

48 PHOENIX CONTACT

– For 5-conductor systems; L1, L2, L3, N, PE

– Combination of type 2 surge arrester and RCD residual current circuit breaker

– Personal protection and device protection in a single device

– Type 2 seamless plug-in surge arrester– Disconnect device on each individual

connector– Optical, mechanical status indication for

all protective connectors– Residual current circuit breaker is not

triggered by magnetic influences caused by discharge currents in the type 2 arrester

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

Combi RCDVAL-CP-RCD...

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester with RCD

PEN

N

T

1

2

3

4

5

6

PEN

N

T

1

2

3

4

5

6

With selective RCD residual current circuit breaker, 300 mA

With selective RCD residual current circuit breaker, 30 mA

For additional information, visit www.phoenixcontact.net/catalog

Total width 54 mm Total width 54 mm

Technical data Technical dataElectrical dataIEC category / EN type II / T2 II / T2Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / 264 V AC / - - / - / 350 V ACNominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 60 kA (all channels) / 20 kA / - - / - / 60 kA (all channels)Max. discharge surge current Imax. (8/20) μs

L-N / N-PE / L-PEN 75 kA (all channels) / 40 kA / - - / - / 75 kA (all channels)Residual voltage at 5 kA L-N / N-PE / L-PEN 1.8 kV / 0.25 kV / - - / - / 1.8 kVProtection level UP

L-N / N-PE / L-PEN 2.5 kV / 1.5 kV / - - / - / 2.5 kVResponse time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / - - / - / 25 nsMax. backup fuse according to IEC (Not required) (Not required)Immunity to short-circuiting (with max. backup fuse) IP 25 kA 25 kA

Rated surge current resistance Ipk 52 kA 52 kAGeneral dataConnection data solid / stranded / AWG 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4Temperature range -25°C ... 60°C -25°C ... 60°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11 IEC 61643-1 / EN 61643-11/A11Remote indication contact PDT contact PDT contactConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 125 V DC 250 V AC / 125 V DCMax. operating current 1 A AC (ohmic) / 0.2 A DC (ohmic) 1 A AC (ohmic) / 0.2 A DC (ohmic)

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VALVETRAB compactVAL-CP-MOSO 60-3S-FM 2804403 1 VAL-CP-MOSO 60-3C-FM 2804416 1

Accessories AccessoriesReplacement connector

L-N / L-PEN VAL-CP-350-ST-GY 2882718 10 VAL-CP-350-ST-GY 2882718 10N-PE VAL-CP-N/PE-350-ST-GY 2882734 10

Labeling material ZBF 12 ..., see page 59 ZBF 12 ..., see page 59

49PHOENIX CONTACT

– Multi-channel type 2 surge arresters and integrated arrester backup fuses

– For 60 mm system technology– Tool-free mounting on 5 and 10 mm

busbars– Signaling to monitoring systems via

remote indication contact in the event of an error

– Surge-proof arrester backup fuse tailored to type 2 arresters

– Type 2 seamless plug-in surge arrester– Disconnect device on each individual

connector– Optical, mechanical status indication for

the individual arresters– Connectors can be checked with

CHECKMASTER

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

Combi MCBVAL-CP-MOSO...

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester for 60 mm system technology

12 14

11 FM

L1 L2 L3

N

PE

12 14

11 FM

L1 L2 L3

PEN

5-conductor system; L1, L2, L3, N, PE 4-conductor system; L1, L2, L3, PEN

Total width 131.5 mm

Technical dataElectrical dataIEC category / EN type II / T2Nominal voltage UN 240 V AC (230/400 V AC ... 240/415 V AC)Maximum continuous operating voltage UC

L-N / N-PE / L-PEN 350 V AC / 264 V AC / -Nominal discharge surge current In (8/20) μs

L-N / N-PE / L-PEN 60 kA (all channels) / 20 kA / -Max. discharge surge current Imax. (8/20) μs

L-N / N-PE / L-PEN 90 kA (all channels) / 30 kA / -Residual voltage at 5 kA L-N / N-PE / L-PEN 1.3 kV / 0.5 kV / -Protection level UP

L-N / N-PE / L-PEN 2.5 kV / 1.7 kV / -Response time tA

L-N / N-PE / L-PEN 25 ns / 100 ns / -Max. backup fuse according to IEC (Not required)Immunity to short-circuiting (with max. backup fuse) IP 25 kA

General dataConnection data solid / stranded / AWG 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4Temperature range -25°C ... 60°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / EN 61643-11 / IEC 60364-4-443 /

IEC 60364-5-534Remote indication contact Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V AC / 250 V DCMax. operating current 2 A AC / 50 mA DC

Ordering data

Description Type Order No. Pcs. / Pkt.

VALVETRAB compact, with an arrester backup fuse

VAL-CP-MCB-3S-350/40/FM 2882750 1

AccessoriesReplacement connector

L-N / L-PEN VAL-CP-350-ST-GY 2882718 10N-PE VAL-CP-N/PE-350-ST-GY 2882734 10

50 PHOENIX CONTACT

IN

L1 L2 L3N

PE

14 12

11 FM

Combi MCBVAL-CP-MCB...

– Combinations of type 2 arresters with integrated arrester backup fuse

– Overload of the surge protection results in all-pole disconnection from the mains

– Signaling to monitoring systems via remote indication contact in the event of an error

– Type 2 seamless plug-in surge arrester– Surge-proof arrester backup fuse– Optical, mechanical status indication for

the individual arresters– Connectors can be checked with

CHECKMASTER

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester with integrated backup fuse

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

5-conductor system; L1, L2, L3, N, PE

For additional information, visit www.phoenixcontact.net/catalog

Total width 114 mm Total width 72 mm

Technical data Technical data

II / T2 II / T2240 V AC (230/400 V AC ... 240/415 V AC) 240 V AC (230/400 V AC ... 240/415 V AC)

- / - / 350 V AC 350 V AC / 264 V AC / -

- / - / 60 kA (all channels) 20 kA / 20 kA / -

- / - / 90 kA (all channels) 30 kA / 30 kA / -- / - / 1.3 kV 1.3 kV / 0.5 kV / -

- / - / 2.5 kV 2.5 kV / 1.7 kV / -

- / - / 25 ns 25 ns / 100 ns / -(Not required) (Not required)25 kA 25 kA

2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4 2.5 ... 25 mm² / 2.5 ... 16 mm² / 12 - 4-25°C ... 60°C -25°C ... 60°CV0 V0IEC 61643-1 / EN 61643-11 / IEC 60364-4-443 / IEC 61643-1 / EN 61643-11 / IEC 60364-4-443 /IEC 60364-5-534 IEC 60364-5-534Single-pos. PDT Single-pos. PDT0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC / 250 V DC 250 V AC / 250 V DC2 A AC / 50 mA DC 2 A AC / 50 mA DC

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VAL-CP-MCB-3C-350/40/FM 2882776 1 VAL-CP-MCB-1S-350/40/FM 2882763 1

Accessories Accessories

VAL-CP-350-ST-GY 2882718 10 VAL-CP-350-ST-GY 2882718 10VAL-CP-N/PE-350-ST-GY 2882734 10

51PHOENIX CONTACT

IN

L1 L2 L3

PE

14 12

11 FM

IN

L1N

PE

14 12

11 FM

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester with integrated backup fuse

4-conductor system; L1, L2, L3, PEN 3-conductor system; L, N, PE

Total width 35.4 mm Total width 17.7 mm

Technical data Technical dataElectrical data ... 24AC ... 120AC ... 230ACIEC category / EN type III / T3 III / T3 III / T3 III / T3Nominal voltage UN 230 V AC (max. 240/415 V AC) 24 V AC/DC 120 V AC 230 V ACMaximum continuous operating voltage UC AC/DC 335 V AC (255 V AC / N-PE) / - 34 V AC /

44 V DC150 V AC / - 253 V AC / -

Nominal load current IL 26 A (30°C) 26 A (30°C) 26 A (30°C) 26 A (30°C)Nominal discharge surge current In (8/20) μs 1.5 kA (per channel) 1 kA 2.5 kA 3 kAMax. discharge surge current Imax. (8/20) μs 10 kA (N-PE) -Combined surge UOC 4 kV 2 kV 6 kV 6 kVResidual voltage at In L-N / L-PE - / - 180 V /

550 V / - 1.1 kV / 600 V

Protection level UP L-N / L(N)-PE 1.2 kV / 1.5 kV 180 V / - 620 V / 850 V

1.1 kV / 1.5 kV

Response time tA L-N / L(N)-PE 25 ns / 100 ns 25 ns / 100 ns

25 ns / 100 ns

25 ns / 100 ns

Max. backup fuse according to IEC 25 A (gL) 25 A (gL)General dataConnection data solid / stranded / AWG 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12Temperature range -40°C ... 85°C -40°C ... 85°CInflammability class according to UL 94 V0 V0Test standards IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11 / UL 1449Remote indication contact N/C contact N/C contactConnection data solid / stranded / AWG 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12Max. operating voltage 250 V 250 VMax. operating current 3 A AC 3 A AC

Ordering data Ordering data

Description Voltage UN Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

MAINS-PLUGTRAB, comprising connector and base element

24 V AC/DC PT 2-PE/S-24AC/FM 2800457 1120 V AC PT 2-PE/S-120AC/FM 2856812 1230 V AC PT 4-PE/S-230AC/FM 2882459 5 PT 2-PE/S-230AC/FM 2858357 1

48 V DCMAINS-PLUGTRAB connector

24 V AC PT 2-PE/S- 24AC-ST 2839318 1060 V AC

120 V AC PT 2-PE/S-120AC-ST 2839334 10230 V AC PT 4-PE/S-230AC-ST 2882462 5 PT 2-PE/S-230AC-ST 2839347 10

48 V DC

Accessories AccessoriesBase element

PT-BE/FM 2839282 10Grounding plug

PT MAIN-EST 2880736 10

Labeling material ZBF ..., see page 125 ZBF ..., see page 125

52 PHOENIX CONTACT

IN OUT

12

6L

2N

10L

L

L

LN

11

8L

4

1

3

5

7

9

1

2

3

3

2

1

IN OUT

5 6

3 4

1 2

11

12�

N

L

PEPE

N

L

– For single and multi-phase power supply units

– DIN rail module– Comprising base element and connector– With floating remote indication contact– Optical signaling of disconnection via LED– Tool-free connector replacement– Connectors can be checked with

CHECKMASTER

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

MAINS-PLUGTRAB

Surge protection for the IEC/EN power supply unit

Type 3 device protection

5-conductor system; L1, L2, L3, N, PE 3-conductor system; L, N, PE

For additional information, visit www.phoenixcontact.net/catalog

Total width 17.7 mm Total width 17.7 mm Total width 17.7 mm

Technical data Technical data Technical data... 24AC ... 60AC ... 120AC ... 230ACIII / T3 III / T3 III / T3 III / T3 III / T3 III / T324 V AC 60 V AC 120 V AC 230 V AC 230 V AC 48 V DC34 V AC / 44 V DC

100 V AC / 95 V DC

150 V AC / - 253 V AC / - 275 V AC / - - / 60 V DC

26 A (30°C) 26 A (30°C) 26 A (30°C) 26 A (30°C) 26 A (30°C) -1 kA 2.5 kA 2.5 kA 3 kA 3 kA 500 A

8 kA 500 A2 kV 4 kV 6 kV 6 kV 6 kV 6 kV (for 12 )

180 V / 120 V

420 V / 250 V

620 V / 330 V

1.1 kV / 600 V

- / - - / -

180 V / 550 V

400 V / 700 V

620 V / 850 V

1.1 kV / 1.5 kV

1.2 kV / 1.5 kV 120 V / 120 V

25 ns / 100 ns

25 ns / 100 ns

25 ns / 100 ns

25 ns / 100 ns

25 ns / 100 ns 1 ns / 1 ns

25 A (gL) 25 A (gL/C) 25 A (gL)

- ... - / - ... - / - 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12-40°C ... 85°C -40°C ... 75°C -40°C ... 85°C

V0 V0 V0IEC 61643-1 / EN 61643-11/A11 / UL 1449 IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11

- N/C contact N/C contact- ... - / - ... - / - 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12

- 250 V 250 V- 3 A AC/DC 3 A AC

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

PT 2-IT-230AC/FM 2805130 1PT 2+1-S-48DC/FM 2817958 10

PT 2-PE/S- 24AC-ST 2839318 10PT 2-PE/S- 60AC-ST 2839321 10PT 2-PE/S-120AC-ST 2839334 10PT 2-PE/S-230AC-ST 2839347 10 PT 2-IT-230AC-ST 2805127 10

PT 2+1-S-48DC-ST 2839648 10

Accessories Accessories Accessories

PT-BE/FM 2839282 10 PT-BE/FM 2839282 10 PT-BE/FM 2839282 10

PT MAIN-EST 2880736 10 PT MAIN-EST 2880736 10

ZBF ..., see page 125 ZBF ..., see page 125 ZBF ..., see page 125

53PHOENIX CONTACT

IN OUT

5 6

3 4

1 2

11

12�

N

L

PEPE

N

L

IN OUT

5 6

3 4

1 2

11

12

PEPE

IN OUT

1 2

3 4

5 6

12

11

+

-��

(+)

(-)

Surge protection for the IEC/EN power supply unit

Type 3 device protection

Replacement connector for 3-conductor system; L, N, PE

3-conductor system; L, N, PE/L, L, PE (IT system)

3-conductor system, for single-phase DC power supply units

Total width 22.5 mm

Technical dataElectrical dataIEC category / EN type III / T3Nominal voltage UN 240 V ACMaximum continuous operating voltage UC L-N / L-PE 275 V AC / 440 V AC (4-conductor IT system)Nominal load current IL 16 A (30°C)Nominal discharge surge current In (8/20) μs 3 kAMax. discharge surge current Imax. (8/20) μs L-N / L-PE 8 kA (> 100x 1 kA) / -Combined surge UOC 6 kVResidual voltage at In L-N / L-PE - / -Protection level UP L-N / L(N)-PE 1.3 kV / -Response time tA L-N / L(N)-PE 25 ns (L-N) / 100 ns (L, N-PE)Max. backup fuse according to IEC 16 A (gL/C/B)General dataConnection data solid / stranded / AWG 0.2 ... 2.5 mm² / 0.2 ... 2.5 mm² / 24 - 14Temperature range -30°C ... 75°CInflammability class according to UL 94 V0Test standards IEC 61643-1 / EN 61643-11/A11Remote indication contact -Connection data solid / stranded / AWG -Max. operating voltage -Max. operating current -

Ordering data

Description Voltage UN Type Order No. Pcs. / Pkt.

BLOCKTRAB, for universal mounting240 V AC BT-1S-230AC/O 2800625 1

SOCKETTRAB, device protection for installation socket inserts

230 V ACMAINS-PRINTRAB, device protection connector with temperature monitoring and visual fault warning, plus remote indication contact

120 V AC230 V AC

MAINS-PRINTRAB, device protection connector with temperature monitoring, visual and acoustic fault warning, plus remote indication contact

120 V AC230 V AC

MAINS-PRINTRAB, flush-type base for installation in cable ducts and flush-type boxes

230 V AC

AccessoriesCover frameCentral plate

54 PHOENIX CONTACT

PE

!

230 V

BLOCKTRAB and PRINTRAB

BT-1S-230AC/... is used as device protection in deep installation boxes (according to DIN 49073), cable ducts, underfloor systems, and termination devices.– With double spring-cage terminal blocks

for tool-free conductor connection– Side latches for easy fixing– Optical/acoustic signaling of

disconnection

BT-SKT 230/A is device protection for flush-type sockets.– Independent of the switch range and pin

arrangement– Mounted on the socket insert– For installation boxes according to

DIN 49073– Bridges provided for multiple

combinations– Subsequent on-site installation possible– Thermally monitored protective circuit– Acoustic signaling of disconnection– Signal deactivation by pulling the link

under the socket cover

MAINS-PRINTRAB is device protection for installation in cable ducts and installation boxes.– Two-piece design, comprising

PRT-S-230/FM protective connector and PRT-CD-AD1 flush-type base

– Optical and acoustic signaling of disconnection

– With floating remote indication contact– Installation in range of switches with the

appropriate central plate possible– Tool-free connector replacement

Surge protection for the IEC/EN power supply unit

Type 3 device protection

For universal mounting, optical signaling

For additional information, visit www.phoenixcontact.net/catalog

Total width 22.5 mm Total width 31.5 mm

Technical data Technical data Technical data... 120AC ... 230AC

III / T3 III / T3 III / T3 III / T3240 V AC 230 V AC 120 V AC 230 V AC275 V AC / 440 V AC (4-conductor IT system) 335 V AC / - 150 V AC / 150 V AC 253 V AC / 253 V AC16 A (30°C) 16 A (30°C) 10 A (CSA) 16 A (45°C)3 kA - 1.5 kA 1.5 kA8 kA (> 100x 1 kA) / - 4.5 kA / 4.5 kA 4.5 kA / 4.5 kA 4.5 kA / 4.5 kA6 kV 4 kV 4 kV 4 kV- / - - / - 610 V / 330 V 1.2 kV / 650 V

1.3 kV / - 1.3 kV / 1.5 kV 600 V / 800 V 1.3 kV / 1.5 kV (At UOC) 25 ns (L-N) / 100 ns (L, N-PE) 25 ns / 100 ns 25 ns / 100 ns 25 ns / 100 ns

16 A (gL/C/B) 16 A (gL / B) 16 A (gL/C)

0.2 ... 2.5 mm² / 0.2 ... 2.5 mm² / 24 - 14 - ... - / - ... 1.5 mm² / - 0.2 ... 4 mm² / 0.2 ... 2.5 mm² / 24 - 12-25°C ... 75°C -25°C ... 75°C -25°C ... 75°CV0 V0 V0IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11- - N/C contact- 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 26 - 16- - 250 V AC- - 3 A

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

BT-1S-230AC/A 2803409 10

BT-SKT 230/A 2859343 1

PRT-S-120/FM 2830618 10PRT-S-230/FM 2749686 10

PRT-S/A-120/FM 2830605 1PRT-S/A-230/FM 2830621 10

PRT-CD-AD1 2749673 25

Accessories Accessories AccessoriesAR-J/ST550 WH 2830359 1ZP-J/TAE/ST550 WH 2830362 10

55PHOENIX CONTACT

PE

!

230 V

N

L

PE

L

PE

N

FM

!

Surge protection for the IEC/EN power supply unit

Type 3 device protection

For universal mounting, acoustic signaling For mounting in flush-type sockets For mounting in cable ducts and installation boxes

Electrical dataIEC category / EN typeNominal voltage UNMaximum continuous operating voltage UC

L-N / L-PENominal load current ILNominal discharge surge current In (8/20) μs

L-N / L-PECombined surge UOCProtection level UP

L-N / N-PE / L-PEResponse time tA

L-N / L-PEGeneral dataTemperature rangeInflammability class according to UL 94Test standards

Description For country-specific use in

COMBITRAB, socket strip with surge protection

Black D, A, NL, E, PMAINTRAB, attachment plug with signal lamp for inserting in a socket, for device protection

Black D, A, NLWhite D, A, NLBlack B, F, CZ, SVK, PLBlack E, PWhite S, FIN, NBlack CHMAINTRAB-POWERLINE, attachment plug with signal lamp for use in Powerline transmission systems

Black D, A, NL, E, P

56 PHOENIX CONTACT

COMBITRAB– For several termination devices– With 1.8 m connecting cable– Recessed ON/OFF switch to prevent

unintentional actuation– Optical signaling of the surge voltage

function via LED

MAINTRAB– Attachment plug– For individual termination devices– With increased touch-proof protection– Optical signaling of the surge voltage

function via LED

MNT-POWERLINE– For POWERLINE transmission systems– With adapted protective circuit– Optimized attenuation behavior– Optical signaling of the surge voltage

function via LED

Note: Other versions of CBT-? socket strips and MNT attachment plugs with combined protection for the power supply and data/IT interfaces are provided from page 153.

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

COMBITRAB and MAINTRAB

Surge protection for the IEC/EN power supply unit

Type 3 device protection

For additional information, visit www.phoenixcontact.net/catalog

Total width 81 mm Total width 63 mm Total width 63 mm

Technical data Technical data Technical data

III / T3 III / T3 III / T3230 V AC 230 V AC 230 V AC

260 V AC / 260 V AC 275 V AC / 360 V AC 260 V AC / 260 V AC16 A (30°C) 16 A (30°C) 16 A (30°C)

1.5 kA / 1.5 kA 3 kA / 3 kA 3 kA / 3 kA4 kV 4 kV 6 kV

1.3 kV / 1.5 kV / 1.5 kV 1.2 kV / 1.5 kV / 1.5 kV 1.1 kV / 1.5 kV / 1.5 kV

25 ns / 100 ns (and N-PE) 25 ns / 100 ns - / 100 ns

-20°C ... 75°C -25°C ... 75°C -25°C ... 75°CV0 V0/HB V0/HBIEC 61643-1 / EN 61643-11/A11 IEC 61643-1 / EN 61643-11/A11 / VDE 0620-1 / IEC 61643-1 / EN 61643-11/A11 / IEC 60884-1 /

IEC 60884-1 / NEK-HD 195 S6 DIN VDE 0620-1

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

CBT-SCHUKO 2857280 1

MNT-1 D 2882200 1MNT-1 D/WH 2882213 1MNT-NET B/F 2882226 1MNT-1 E 2882239 1MNT-1 S/WH 2880862 1MNT-1 CH II 2882255 1

MNT-POWERLINE 2858001 1

57PHOENIX CONTACT

IN OUT

LL

NN

NPE L NPE L

Surge protection for the IEC/EN power supply unit

Type 3 device protection

Socket strip, with 1.8 m connecting cable Attachment plug Attachment plug for Powerline transmission

Ordering data

Description Nominal current IN Type Order No. Pcs. / Pkt.

Wiring bridge, for modules with 17.5 mm connecting pitch, single-phase2-pos. 100 A MPB 18/1- 2 2809209 103-pos. 100 A MPB 18/1- 3 2809212 104-pos. 100 A MPB 18/1- 4 2809225 105-pos. 100 A MPB 18/1- 5 2817864 106-pos. 100 A MPB 18/1- 6 2748564 107-pos. 100 A MPB 18/1- 7 BU 2856278 108-pos. 100 A MPB 18/1- 8 BU 2858470 108-pos. 100 A MPB 18/1- 8 2748577 109-pos. 100 A MPB 18/1- 9 2748580 1012-pos. 100 A MPB 18/1-12 2748593 1057-pos. 100 A MPB 18/1-57 2809238 1Wiring bridge, for modules with 17.5 mm connecting pitch, 3-phase6-pos. 80 A MPB 18/3- 6 2809241 109-pos. 80 A MPB 18/3- 9 2809254 10Wiring bridge, for modules with 17.5 mm connecting pitch,4-phase8-pos. 80 A MPB 18/4- 8 2809283 1012-pos. 80 A MPB 18/4-12 2809296 10Wiring bridge, flexible, 16 mm² diameter, fork-type cable lug at one end200 mm 100 A (30°C) MPB F200X16/ 1GS 2818339 1400 mm 100 A (30°C) MPB F400X16/ 1GS 2818342 1600 mm 100 A (30°C) MPB F600X16/ 1GS 2818355 1

58 PHOENIX CONTACT

– For combinations of lightning and surge arresters

– In combination with other devices in the installation distributor, such as residual current circuit breakers and miniature circuit breakers

– Practical wiring of all common applications

– Single, three or four-phase versions with various numbers of positions

– The rated cross section of the MPB bridge metals is 16 mm2 per phase

– End covers are used to terminate and insulate individually cut bridges

TRABTECH wiring bridges

Surge protection for the IEC/EN power supply unit

Wiring bridges

For additional information, visit www.phoenixcontact.net/catalog

Ordering data

Description Type Order No. Pcs. / Pkt.

Marking labelsCan be labeled acc. to customer specifications ZBN 18 CUS 0825059 1Unprinted ZBN 18:UNBEDRUCKT 2809128 10L1, L2, L3, N, ZBN 18,LGS:L1-N,ERDE 2749576 10

, , , , ZBN 18,LGS:ERDE 2749589 10Zack marker sheet, flat, 120-section, can be separated

Can be labeled acc. to customer specifications ZBFM 5 CUS 0825037 1Unprinted ZBFM 5/WH:UNBEDRUCKT 0803595 10Zack marker strip, flat, 5-section, unprinted5-section ZBF 12:UNBEDRUCKT 0809735 10

59PHOENIX CONTACT

– Flat zack marker strips– Comprising five individual labels with

17.5 mm pitch.– Can be labeled with CMS computer

marking system or by hand using B-STIFT

Labeling material

Surge protection for the IEC/EN power supply unit

Labeling material

Technical dataElectrical dataMaximum continuous operating voltage UC 500 V AC/DCNominal current IN 125 A (30°C)Lightning test curr. Iimp (10/350) s

Peak value 100 kAGeneral dataConnection data solid / stranded / AWG 35 ... 0.5 mm² / 0.5 ... 25 mm² / 20 - 2Temperature range -40°C ... 85°CInflammability class according to UL 94 V0Test standards IEC 60947-7-1 / IEC 60947-7-1 / IEC 60947-7-1

Ordering data

Description Type Order No. Pcs. / Pkt.

Feed-through terminal blockDK-BIC-35 2749880 1

AccessoriesLabeling material ZBN 18 ..., see page 59

– Biconnect feed-through terminal block– For wiring mixed combinations of

lightning and surge arresters– As a system extension for FLASHTRAB

and VALVETRAB applications

Feed-through terminal block

Surge protection for the IEC/EN power supply unit

Accessories

Feed-through terminal block

Ordering data

Description Type Order No. Pcs. / Pkt.

Equipotential busbarPAS-1 2765615 1

60 PHOENIX CONTACT

Notes:

Dimensional drawings starting on page 240

– Equipotential bonding strip for main equipotential bonding according to DIN VDE 0100

– As well as for lightning protection equipotential bonding according to DIN EN 62305

– Has a comb-shaped contact bar

Equipotential bonding

Equipotential busbar

For additional information, visit www.phoenixcontact.net/catalog

Ordering data

Description Type Order No. Pcs. / Pkt.

TRABTECH housing, for the isolated mounting of surge arresters

TG 40 2788896 1

Notes:

Dimensional drawings starting on page 240

– For separate installation of surge protective devices

– Use in harsh environmental conditions at the installation location

– Installation outdoors or indoors possible– Aluminum housing equipped with two

cable glands– Supplied as standard: an NS 35/7.5 DIN

rail– The DIN rail requires five part width

sections of 17.5 mm each

TRABTECH housing

Surge protection for the IEC/EN power supply unit

Accessories/set solution

IP65 protection class

Ordering data

Description Type Order No. Pcs. / Pkt.

Building set, consisting of:1 x VAL-CP-3S-350/O (surge arrester)2 x MNT-1D (equipment protection adapter)1 x MNT-ISDN D (equipment and ISDN protection adapter)1 x MNT-TV-SAT D (equipment and TV-SAT protective adapter)2 x Adapter for F to TV (IEC) connector1 x MPB-SET (4 flexible bridges)1 x KBL TV-SAT/150, 1 x KBL TV/150, 1 x KBL ISDN/150 (connecting cable)

GEB-SET-CP ISDN/TV-SAT 2856943 1Building set, consisting of:1 x VAL-CP-3S-350/O (surge arrester)2 x MNT-1D (equipment protection adapter)1 x MNT-TAE D (equipment and TAE protection adapter)1 x MNT-TV-SAT D (equipment and TV-SAT protective adapter)2 x Adapter for F to TV (IEC) connector1 x MPB-SET (4 flexible bridges)1 x KBL TV-SAT/150, 1 x KBL TV/150, 1 x KBL TAE/150 (connecting cable)

GEB-SET-CP TAE/TV-SAT 2856964 1

61PHOENIX CONTACT

Notes:

Approvals starting on page 252

– Basic equipment for surge protection for the office, surgery, legal office or home, for example

– VALVETRAB compact (type 2) for installation in sub-distribution boards

– MAINTRAB (type 3) device protection adapters, two of which are combined adapters

– Combined adapters protect the power supply and the data/signal interfaces

– Cables, bridges, and adapters are supplied as standard

Set solutions for building installationsGEB-SET-CP

Package solution with surge protection

Total width 53.4 mm

Technical dataElectrical dataIEC category / EN type II / T2Max. non-load voltage UOC 1000 V DCMaximum continuous operating voltage UC

(L+) - (L-) / (L+/L-) - PE 1000 V DCMax. short-circuit current ISC max 80 A DCNominal discharge surge current In (8/20) μs 15 kAMax. discharge surge current Imax. (8/20) μs 30 kAProtection level UP

(L+) - (L-) / (L+/L-) - PE 5 kV / 3 kVResponse time tA

(L+) - (L-) / (L+/L-) - PE 25 ns / 100 nsGeneral dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2Temperature range -40°C ... 80°CDegree of protection according to IEC 60529/EN 60529 IP20Housing material PBT/PAInflammability class according to UL 94 V0Test standards DIN EN 61643-11 / IEC 61643-1 / IEC 60364-7-712Remote indication contact Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V ACMax. operating AC current 1.5 A AC (250 V AC)Connection method Screw connection

Ordering data

Description Type Order No. Pcs. / Pkt.

VALVETRAB-MSWith remote indication contact (L+)-PE & (L-)-PE & (L+)-(L-) VAL-MS 1000DC/2+F-FM 2800176 1

Without remote indication contact (L+)-PE & (L-)-PE & (L+)-(L-) VAL-MS 1000DC/2+F 2800177 1

With remote indication contact (L+)-(L-)Without remote indication contact (L+)-(L-/PE)

AccessoriesReplacement connector1000 V DC 1L-N/PE VAL-MS 1000PV ST 2805185 1600 V DC 1L-N/PE1000 V DC N-PE F-MS 1100/30 ST 2800178 1

Labeling material ZBN 18 ..., see page 59

62 PHOENIX CONTACT

1412

11FM

L+ L–

Type 2 surge arrester for PV systems

– Type 2 seamless plug-in surge arrester– Optical, mechanical status indication for

the individual arresters– With or without floating remote

indication contact– Mechanical keying of all slots– Connectors can be checked with

CHECKMASTER

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester and sets for photovoltaic systems

Notes:

Dimensional drawings starting on page 240

Approvals starting on page 252

Insulated PV applicationsup to 1000 V DC, free of leakage current

For additional information, visit www.phoenixcontact.net/catalog

Total width 53.4 mm Total width 53.4 mm Total width 35.6 mm

Technical data Technical data Technical data

II / T2 II / T2 II / T2 1000 V DC 600 V DC 1000 V DC

1000 V DC 600 V DC 1000 V DC 80 A DC 80 A DC 80 A DC

15 kA 15 kA 15 kA30 kA 40 kA 30 kA

5 kV / 5 kV 3 kV / 3 kV 5 kV / -

25 ns / 25 ns 25 ns / 25 ns 25 ns / 25 ns

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2-40°C ... 80°C -40°C ... 80°C -40°C ... 80°CIP20 IP20 IP20PBT/PA PBT/PA PBT/PAV0 V0 V0DIN EN 61643-11 / IEC 61643-1 / IEC 60364-7-712 DIN EN 61643-11 / IEC 61643-1 / IEC 60364-7-712 DIN EN 61643-11 / IEC 61643-1 / IEC 60364-7-712Single-pos. PDT Single-pos. PDT Single-pos. PDT0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16250 V AC 250 V AC 250 V AC1.5 A AC (250 V AC) 1.5 A AC (250 V AC) 1.5 A AC (250 V AC)Screw connection Screw connection Screw connection

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-MS 1000DC/2+V-FM 2920502 1 VAL-MS 600DC/2+V-FM 2800195 1

VAL-MS 1000DC/2+V 2805091 1 VAL-MS 600DC/2+V 2805457 1

VAL-MS 1000DC/1+V-FM 2804490 1VAL-MS 1000DC/1+V 2804542 1

Accessories Accessories Accessories

VAL-MS 1000PV ST 2805185 1 VAL-MS 1000PV ST 2805185 1VAL-MS 600PV ST 2805431 1

ZBN 18 ..., see page 59 ZBN 18 ..., see page 59 ZBN 18 ..., see page 59

63PHOENIX CONTACT

12 14

11 FM

L–L+

12 14

11 FM

L–L+

12 14

11 FM

L– /L+

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester and sets for photovoltaic systems

Insulated or grounded PV applications up to 1000 V DC

Insulated or grounded PV applications up to 600 V DC

Fuse-free grounded PV applications up to 1000 V DC

Total width 200 mm

Technical dataElectrical data DC side AC sideIEC category / EN type II / T2 II / T2Max. non-load voltage UOC 1000 V DC 230 V AC (UN)Maximum continuous operating voltage UC

(L+) - (L-) / (L+/L-) - PE 1000 V DC -Max. short-circuit current ISC max 80 A DC -Nominal discharge surge current In (8/20) μs 15 kA 20 kAMax. discharge surge current Imax. (8/20) μs 30 kA 40 kAProtection level UP

(L+) - (L-) / (L+/L-) - PE 5 kV / 5 kV 1.5 kV / 1.2 kVResponse time tA 25 ns -General dataConnection data solid / stranded / AWG 1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2Temperature range -25°C ... 70°CDegree of protection according to IEC 60529/EN 60529 IP65Housing material Polycarbonate fiber reinforcedInflammability class according to UL 94 V2Test standards IEC 61643-1 / DIN EN 61643-11 / IEC 60364-7-712

Remote indication contact Single-pos. PDTConnection data solid / stranded / AWG 0.14 ... 1.5 mm² / 0.14 ... 1.5 mm² / 28 - 16Max. operating voltage 250 V ACMax. operating AC current 1.5 A AC (at 250 V)Connection method Screw terminal blocks

Ordering data

Description Type Order No. Pcs. / Pkt.

PV-SET 1000 DC/ACDC: (L+)-PE & (L-)-PE & (L+)-(L-) / AC: L-N & N-PE PV-SET 1000 DC/AC 2804458 1

PV-SET 1000DC(L+)-PE & (L-)-PE & (L+)-(L-)

PV-SET 5ST/600DC(L+)-PE & (L-)-PE & (L+)-(L-)

AccessoriesReplacement connector1000 V DC 1L-N/PE VAL-MS 1000PV ST 2805185 1230 V AC 1L-N/PE VAL-MS 320 ST 2838843 10230 V AC 1L-N/PE

64 PHOENIX CONTACT

IN OUT

L+

L1

L+ N

L–L–

DC AC

Surge protection for photovoltaic systems

– For insulated or grounded PV applications up to 1000 V DC

– Pre-assembled protection solutions– Suitable for DC applications such as PV

systems– Type 2 seamless plug-in surge arrester– Optical, mechanical status indication for

the individual arresters– With or without floating remote

indication contact– Mechanical keying of all slots– Connectors can be checked with

CHECKMASTER

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester and sets for photovoltaic systems

Up to 1000 V DC/230 V AC

For additional information, visit www.phoenixcontact.net/catalog

Total width 125 mm Total width 300 mm

Technical data Technical data

II / T2 II / T2 1000 V DC 600 V DC

1000 V DC 600 V DC 40 A DC 30 A

15 kA (DC) 20 kA30 kA 40 kA

5 kV / 5 kV - / - 25 ns -

1.5 ... 35 mm² / 1.5 ... 25 mm² / 15 - 2 0.2 ... 16 mm² / 0.2 ... 10 mm² / --30°C ... 80°C -25°C ... 60°CIP65 IP65Polycarbonate, glass-fiber-reinforced Polycarbonate fiber reinforcedV2 (housing/cover) V2IEC 61643-1 / DIN EN 61643-11 / IEC 60364-7-712 / IEC 61643-1 / EN 61643-11/A11 / IEC 60364-7-712EN 60439-1- -- -- -- -SUNCLIX PV connector Screw terminal blocks

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

PV-SET 1000 DC 2804445 1

PV-SET 5ST/600DC 2920780 1

Accessories Accessories

VAL-MS 1000PV ST 2805185 1

VAL-MS 600PV-UD ST 2805198 1

65PHOENIX CONTACT

IN OUT

L+L+

L–L–

IN OUT

L+

L+

L–L–

Surge protection for the IEC/EN power supply unit

Type 2 surge arrester and sets for photovoltaic systems

For insulated or grounded PV applications up to 1000 V DC, with SUNCLIX

For up to five solar strings, including a generator disconnect

66 PHOENIX CONTACT

Network type Application

TT system

230/400 V AC240/415 V AC

L1L2L3NPE

Type 1 FLT-CP-PLUS-3S-350

Type 1 + 2 FLT-CP-3S-350

Type 2 VAL-CP-3S-350

L2

L3L2

L1

L3

F1

N

L3

L1

L1 L2

N

N

PE

F2

6

6

FLASHTRAB compact

FLASHTRABcompact

FLASHTRAB

FLT-CP-N/PE-350-ST

28 59 68 6

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FM

L2

L3L2

L1

L3

F1

N

L3

L1

L1 L2

N

N

PE

F2

6

6

FLASHTRAB compact

FLASHTRABcompact

FLASHTRAB

FLT-CP-N/PE-350-ST

28 59 68 6

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

FM

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

Branch wiring V-type through wiring

The values for backup fuses F1 and F2 can be found in the relevant installation instructions. Separate backup fuses (F2) are not required when supplying up to 315 A.

The values for backup fuse F1 can be found in the relevant installation instructions.This connection is particularly suitable for reducing additional voltages (caused by surge currents) on cables.

L2

L3L2

L1

L3

F1

N

L3

L1

L1 L2

N

N

PE

F2

6

6

FLASHTRAB compact

FLASHTRABcompact

FLASHTRAB

FLT-CP-N/PE-350-ST

28 59 68 6

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FM

L2

L3L2

L1

L3

F1

N

L3

L1

L1 L2

N

N

PE

6

6

FLASHTRAB compact

FLASHTRABcompact

FLASHTRAB

FLT-CP-N/PE-350-ST

28 59 68 6

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FM

L2

L2

L1

L3

F1

N

L1

L1 L2

N

N

PE

F2

VALVETRAB compact

VALVETRABcompact

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FM

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

L3

L3

6

6

Surge protection for the power supply unit

Applications

67PHOENIX CONTACT

Network type Application

TN-S system

230/400 V AC240/415 V AC

TN-C system

230/400 V AC240/415 V AC

L1L2L3NPE

L1L2L3

PEN

L2

L3L2

L1

L3

F1

N

L3

L1

L1 L2

N

N

PE

F2

6

6

FLASHTRAB compact

FLASHTRABcompact

FLASHTRAB

FLT-CP-N/PE-350-ST

28 59 68 6

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FM

Type 1 + 2 FLT-CP-3S-350

L2

L3L2

L1

L3

F1

N

L3

L1

L1 L2

N

N

PE

F2

6

6

FLASHTRAB compact

FLASHTRABcompact

FLASHTRAB

FLT-CP-N/PE-350-ST

28 59 68 6

FM

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

Type 1 FLT-CP-PLUS-3S-350

L2

L3L2

L1

L3

F1

L3

L1

L1 L2

PEN

PEN

PEN

F2

FLASHTRAB compact

FLASHTRABcompact

FM

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

FLASHTRAB

FLT-CP-PLUS-350-ST

28 59 91 3

Type 1 FLT-CP-PLUS-3C-350

L2

L3L2

L1

L3

F1

L3

L1

L1 L2

PEN

PEN

PEN

F2

FLASHTRAB compact

FLASHTRABcompact

FM

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

L2

L2

L1

L3

F1

N

L1

L1 L2

N

N

PE

F2

VALVETRAB compact

VALVETRABcompact

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FM

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

L3

L3

6

6

Type 2 VAL-CP-3S-350

L2

L2

L1

L3

F1

L1

L1 L2

PEN

PEN

F2

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FM

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

L3

L3

PEN

Type 2 VAL-CP-3C-350

Type 1 + 2 FLT-CP-3C-350

Surge protection for the power supply unit

Applications

68 PHOENIX CONTACT

Network type Application

TN-S system

230/400 V AC240/415 V AC

IT system

230 V AC

IT system

500 V AC

L1L2L3NPE

PE

LL

L1L2L3PE

Type 2 VAL-MS-320/3+1-FMwith residual current circuit breaker

Type 1 + 2 FLT-CP-2C-350 Type 2 VAL-CP-2C-350

Type 2 VAL-MS 580/3+0-FM

L

LL

LF1

LL

6

6

PE

F2

FLASHTRAB compact

FLASHTRABcompact

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FLASHTRAB

FLT-CP-350-ST

28 59 66 0

FM

L

LL

LF1

LL

6

6

PE

F2

VALVETRAB

VAL-CP-350-ST

28 59 61 5

VALVETRAB

VAL-CP-350-ST

28 59 61 5

FM

VALVETRAB

VAL-MS

580 ST

U :580VACC

I : 15 kA

29 20 43 4

n

VALVETRAB VALVETRAB

L3L2L1

11 1214

VAL-MS

580 ST

U :580VAC

I : 15 kA

29 20 43 4

C

n

VAL-MS

580 ST

U :580VAC

I : 15 kA

29 20 43 4

C

n

L1L2L3

PE

F2

FM

PE

PE

F1

VALVETRAB

VAL-MS

320 ST

U 335 Vr

I 15 kA

28 38 84 3

n

VALVETRAB VALVETRAB

N

6

6

VALVETRAB

L3L2L1

11 1214

VAL-MS

320 ST

U 335 Vr

I 15 kA

28 38 84 3

n

VAL-MS

320 ST

U 335 Vr

I 15 kA

28 38 84 3

n

F-MS

12 ST

U 260 VC

I 20 kA

28 17 99 0

n

L1L2L3NPE

L1´L2´L3´N´

PE

F2

MPB 18/4-8

FM

Surge protection for the power supply unit

Applications

69PHOENIX CONTACT

Network type Application

IT system

690 V AC

TN-C system

400/690 V AC

TN-C system

554/960 V AC

L1L2L3PE

L1L2L3

PEN

L1L2L3

PEN

Type 2 VAL-MS 750/30/3+0/FM

Type 2 SYS-SET/3/T2/690

Type 2 VAL-MS 750/30/3+0/FM

VALVETRAB

VAL-MS

750 ST

U :750VACC

I : 15 kA

29 20 25 6

n

VALVETRAB VALVETRAB

L3L2L1

11 1214

VAL-MS

750 ST

U :750VAC

I : 15 kA

29 20 25 6

C

n

VAL-MS

750 ST

U :750VAC

I : 15 kA

29 20 25 6

C

n

L1L2L3

PE

F2

FM

PE

PE

F1

VALVETRAB

VAL-MS

500 ST

U :600VACC

I : 15 kAn

28 07 60 9

VALVETRAB VALVETRAB

L3L2L1

11 1214

VAL-MS

500 ST

U :600VAC

I : 15 kA

28 07 60 9

C

n

VAL-MS

500 ST

U :600VAC

I : 15 kA

28 07 60 9

C

n

L1L2L3

PEN

F2

FM

PEN

PEN

F1

VALVETRAB

VAL-MS

750 ST

U :750VACC

I : 15 kAn

29 20 25 6

VALVETRAB VALVETRAB

L3L2L1

11 1214

VAL-MS

750 ST

U :750VAC

I : 15 kA

29 20 25 6

C

n

VAL-MS

750 ST

U :750VAC

I : 15 kA

29 20 25 6

C

n

L1L2L3

PEN

F2

FM

PEN

PEN

F1

L1L2L3

PE

F2

F1

Type 1 PWT 100-800AC-FM

L1L2L3

PEN

F2

F1

Type 1 PWT 100-800AC-FM

L1L2L3

PEN

F2

F1

Type 1 PWT 100-800AC-FM

Surge protection for the power supply unit

Applications

VALVETRAB-SQ ...

VAL-SQ SE Universal mounting option

Optical diagnostics and status indication per phase

Pulse counter

Remote indication contact

NEMA 3R/12 metal housing

VAL-SQ SP

Universal mounting option

NEMA 4X non-metal housing

Acoustic alarm

Remote indication contact

VAL-SQ SI

NEMA 4X housing

Optical diagnostics and status indication per phase

Compact design

70 PHOENIX CONTACT

Surge protection for NEMA power supply unit

Main range and features

Integral protection

Cascaded (graduated) use of VAL-SQ protective devices in building installation ensures the efficient protection of electrical systems.

VALVETRAB-SQ … The VALVETRAB-SQ product range has

been specially developed to meet North American installation requirements (NEMA).

Protection for all installation locations:– VAL-SQ SE (Service Entrance - for the

main supply)– VAL-SQ SP (Sub-Panel - for the sub-

distribution)– VAL-SQ SI (Small Installation - for the

equipment)The common use of protective devices

offers complete protection against harmful surge voltages.

Mounting next to the control cabinet or directly on electrical devices is supported.

The devices have a protective circuit with high discharge capacity for rated surge currents up to 400 kA (8/20) s per phase. The individual fuse for each protective path, which is integrated in the design, provides additional safety for the products.

The entire product range is approved according to UL 1449 3rd Edition.

71PHOENIX CONTACT

Service entrance Sub-panel Control cabinet or direct to equipment

VAL-SQ SE VAL-SQ SP VAL-SQ SI

Features – Display with pulse counter indicates the

number of power pulse currents safely discharged to ground

– Acoustic status alarm for the protective device in the event of damage for VAL-SQ SE and VAL-SQ SP products

– LEDs in all VAL-SQ products for continuous status monitoring of each individual phase

VAL-SQ SE VAL-SQ SP VAL-SQ SI

Max. surge current capacity (8/20) s (UL 1449 3rd Edition)

180, 200, 300, and 400 kA 50 and 100 kA 36, 40, 80, 100, and 120 kA

Nominal current In 20 kA 20 kA 20 kA

Status LEDs

Acoustic alarm -

Remote indication contact -

Pulse counter - -

Degree of protection NEMA 3R/12 NEMA 4X NEMA 4X

Short-circuit current rating (SCCR) 200 kA 200 kA 25 and 200 kA

Filtering -30 dB -30 dB -

Surge protection for NEMA power supply unit

Main range and features

VA

L-S

Q S

E

Main

su

pp

ly Ideal protection for the main distribution

Multi-phase surge protection with remote indication contact, status LED, interference filter, and pulse counter

VA

L-S

Q S

P

Su

b-d

istr

ibu

tio

n

Ideal protection for the sub-distribution

Multi-phase surge protection with remote indication contact and interference filter in compact housing

VA

L-S

Q S

I

Eq

uip

me

nt

Ideal protection for small systems and equipment with limited space

Multi-phase surge protection in compact housing

The selection matrix makes it easy to select suitable surge protection for the desired application.

Inst

alla

tion lo

cation

Des

crip

tion

72 PHOENIX CONTACT

Designation structure

VAL - SQ - SE 200 - 277/480Y / TS

Product range:VALVETRAB

SQ

Product group:SE - Main supplySP - Sub-distributionSI - Equipment

Max. rated surge current

Voltage system/network type

SelectionD - Disconnect switchTS - Protection of all 10 paths

Surge protection for NEMA power supply unit

Selection guide

2 3R/12 400 kA

200 kA

74

2 3R/12 300 kA 74

2 3R/12 200 kA 74

2 3R/12 180 kA 74

2 4X50 kA

100 kA200 kA 76

1 4X

120 kA 25 kA

78

100 kA 25 kA

80 kA 25 kA

50 kA 25 kA

40 kA 200 kA

36 kA 25 kA

Max

. sur

ge cur

rent

cap

acity

(8/2

0 μs

)

UL t

ype

NEM

A cla

ss

SCCR

LED sta

tus in

dicat

or

Aco

ustic al

arm

Rem

ote in

dicat

ion c

onta

ct

Pulse

coun

ter

Gro

undin

g

Filter

Prote

ctio

n of a

ll 10

pat

hs

73PHOENIX CONTACT

Disco

nnec

t sw

itch

Page

Surge protection for NEMA power supply unit

Selection guide

Technical data Technical data120/240S 120/208Y 120/240 HLD

MCOV 150 V 150 V 150 VNominal discharge current In 20 kA 20 kAEMI/RFI filtering -30 dB @ 100 kHz -30 dB @ 100 kHzVoltage Protection Rating (VPR)

L-N / L-PE 700 V / 700 V 700 V / 700 V 700 V / 1200 VN-PE / L-L 700 V / 1200 V 700 V / 1200 V 700 V / 1500 V

HL-L / HL-N - / - - / - 300 V / 150 VHL-PE - - 150 V

Short-circuit current rating (SCCR) 200 kA 200 kAUL type Type 2 Type 2Degree of protection NEMA 3R/12 NEMA 3R/12Error/status indicator Phase LEDs / Acoustic alarm / Remote indication contact Phase LEDs / Acoustic alarm / Remote indication contactTemperature range -20°C ... 65°C -20°C ... 65°CDimensions W / H / D 418.00 mm / 562.00 mm / 222.00 mm 418.00 mm / 562.00 mm / 222.00 mmTest standards UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

Service entrance surge protection with disconnect option

200 kA VAL-SQ SE 200-120/240S /D 2800395 1400 kA VAL-SQ SE 400-120/240S /D 2800397 1Service entrance surge protection with disconnect option

200 kA VAL-SQ SE 200-120/208Y /D 2800383 1400 kA VAL-SQ SE 400-120/208Y /D 2800385 1200 kA VAL-SQ SE 200-120/240HLD /D 2800388 1400 kA VAL-SQ SE 400-120/240HLD /D 2800391 1Service entrance surge protection with disconnect option

200 kA400 kA200 kA400 kAService entrance surge protection with disconnect option

200 kAService entrance surge protection for sensitive electronics

180 kA ten-mode300 kA ten-mode180 kA ten-mode300 kA ten-mode

74 PHOENIX CONTACT

L1 L2 N GND

� �� � �

C NC NO L1 L2 L3 N GND C NC NO

� � �� � � �

VAL-SQ SE products provide maximum surge protection for the service entrance.– Available with up to 400 kA surge current

rating per phase– Sine wave tracking filter– Optional disconnect switch– Optional ten-mode protection for

sensitive electronics– UL 1449 3rd edition listed

NOTE: The dimensions of 400 kA housing are 519 mm x 664 mm x 222 mm (W x H x D).

Notes:

The products are only available for export outside the EU and the European Economic Area.

Device protection for the service entrance

Surge protection for NEMA power supply unit

Surge protective devices

Arrester for 120/240 V single/split-phase systems

Arrester for 120/208 V wye and 120/240 V HLD systems

For additional information, visit www.phoenixcontact.net/catalog

Technical data Technical data Technical data277/480Y 347/600Y 277/480Y 120/208Y 277/480Y

320 V 420 V 550 V 150 V 320 V20 kA 20 kA 20 kA

-30 dB @ 100 kHz -30 dB @ 100 kHz -30 dB @ 100 kHz

2000 V / 1200 V 2500 V / 1500 V 2000 V / - 1000 V / 700 V 1800 V / 1200 V1200 V / 2000 V 1500 V / 2500 V - / 2000 V 600 V / 1000 V 1000 V / 1800 V- / - - / - - / - - / - - / -- - - - -

200 kA 200 kA 200 kAType 2 Type 2 Type 2

NEMA 3R/12 NEMA 3R/12 NEMA 3R/12Phase LEDs / Acoustic alarm / Remote indication contact Phase LEDs / Acoustic alarm / Remote indication contact Phase LEDs / Acoustic alarm / Remote indication contact

-20°C ... 65°C -20°C ... 65°C -20°C ... 65°C418.00 mm / 562.00 mm / 222.00 mm 418.00 mm / 562.00 mm / 222.00 mm 411.00 mm / 550.00 mm / 159.00 mm

UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 /IEEE C62.45 IEEE C62.45 IEEE C62.45

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-SQ SE 200-277/480Y /D 2800400 1VAL-SQ SE 400-277/480Y /D 2800403 1VAL-SQ SE 200-347/600Y /D 2800409 1VAL-SQ SE 400-347/600Y /D 2800411 1

VAL-SQ SE 200-277/480Y-H /D 2800406 1

VAL-SQ SE 180-120/208Y /TS 2800373 1VAL-SQ SE 300-120/208Y /TS 2800375 1VAL-SQ SE 180-277/480Y /TS 2800378 1VAL-SQ SE 300-277/480Y /TS 2800380 1

75PHOENIX CONTACT

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 N GNDL2 L3

� � � � � � � � � �

Surge protection for NEMA power supply unit

Surge protective devices

Arrester for 277/480 V and 347/600 V wye systems

Arrester for 277/480 V wye high-resistance ground systems

Arrester for 120/208 V and 277/480 V wye systems

Technical data Technical data120/240S 120/208Y

MCOV 150 V 150 V Voltage Protection Rating (VPR)

L-N / L-PE 900 V / 1200 V 900 V / 1200 VN-PE / L-L 700 V / 1500 V 700 V / 1500 V

Short-circuit current rating (SCCR) 200 kA 200 kANominal discharge current In 20 kA 20 kAEMI/RFI filtering -30 dB @ 100 kHz -30 dB @ 100 kHzUL type Type 2 Type 2Connection data

Power (AWG / length) 10 AWG / 61 cm 10 AWG / 61 cmRemote indication contact #24 AWG/0.205 mm² wires (24 in./61 cm long) #24 AWG/0.205 mm² wires (24 in./61 cm long)

Degree of protection NEMA 4X NEMA 4XError/status indicator Phase LEDs / Acoustic alarm / Remote indication contact Phase LEDs / Acoustic alarm / Remote indication contact

Temperature range -40°C ... 71°C -40°C ... 71°CDimensions W / H / D 250.00 mm / 122.00 mm / 79.00 mm 250.00 mm / 122.00 mm / 79.00 mmTest standards UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

Sub-panel surge protection50 kA VAL-SQ SP 50-120/240S 2800495 1100 kA VAL-SQ SP 100-120/240S 2800463 1Sub-panel surge protection50 kA VAL-SQ SP 50-120/208Y 2800493 1100 kA VAL-SQ SP 100-120/208Y 2800461 1Sub-panel surge protection50 kA100 kA50 kA100 kASub-panel surge protection50 kA100 kASub-panel surge protection50 kA100 kA50 kA100 kA50 kA100 kA

76 PHOENIX CONTACT

L1 L2 N GND

� �� � �

C NC NO L1 L2 L3 N GND C NC NO

� � �� � � �

VAL-SQ SP products provide a surge current rating of 50 or 100 kA per phase in compact NEMA 4X housing.– Sine wave tracking circuitry that provides

up to -30 dB of noise attenuation– Each surge protection mode is individually

fused– LEDs provide continuous feedback on the

status of each phase– Dry contacts allow connection to a

remote monitoring system– UL 1449 3rd edition listed

Notes:

The products are only available for export outside the EU and the European Economic Area.

Device protection for the sub-panel

Surge protection for NEMA power supply unit

Surge protective devices

Arrester for 120/240 V single/split-phase systems

Arrester for 120/208 V wye systems

For additional information, visit www.phoenixcontact.net/catalog

Technical data Technical data Technical data277/480Y 347/600Y 120/240 HLD 240D 480D/ 600D

320 V 320 V 150 V 300 V 300 V

2500 V / 1200 V 2500 V / 1200 V 1500 V / 1000 V 1500 V / - 1500 V / -1000 V / 2500 V 1000 V / 2500 V 700 V / 1500 V - / 1500 V - / 1500 V200 kA 200 kA 200 kA 200 kA 200 kA

20 kA 20 kA 20 kA-30 dB @ 100 kHz -30 dB @ 100 kHz -30 dB @ 100 kHz

Type 2 Type 2 Type 2

10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm 10 AWG / 61 cm#24 AWG/0.205 mm² wires (24 in./61 cm long)

#24 AWG/0.205 mm² wires (24 in./61 cm long)

#24 AWG/0.205 mm² wires (24 in./61 cm long) #24 AWG/0.205 mm² wires (24 in./61 cm long)

#24 AWG/0.205 mm² wires(24 in./61 cm long)

NEMA 4X NEMA 4X NEMA 4XPhase LEDs / Acoustic alarm / Remote indication contact Phase LEDs / Acoustic alarm / Remote indication contact Phase LEDs / Acoustic alarm / Remote indication contact

-40°C ... 71°C -40°C ... 71°C -40°C ... 71°C250.00 mm / 122.00 mm / 79.00 mm 250.00 mm / 122.00 mm / 79.00 mm 250.00 mm / 122.00 mm / 79.00 mm

UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 /IEEE C62.45 IEEE C62.45 IEEE C62.45

Ordering data Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt. Type Order No. Pcs. / Pkt.

VAL-SQ SP 50-277/480Y 2800497 1VAL-SQ SP 100-277/480Y 2800465 1VAL-SQ SP 50-347/600Y 2800498 1VAL-SQ SP 100-347/600Y 2800466 1

VAL-SQ SP 50-120/240HLD 2800494 1VAL-SQ SP 100-120/240HLD 2800462 1

VAL-SQ SP 50-240D 2800496 1VAL-SQ SP 100-240D 2800464 1VAL-SQ SP 50-480D 2800500 1VAL-SQ SP 100-480D 2800467 1VAL-SQ SP 50-600D 2800513 1VAL-SQ SP 100-600D 2800514 1

77PHOENIX CONTACT

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 L2 L3 N GND C NC NO

� � �� � � �

L1 L2 L3 C NC NO

� � �

Surge protection for NEMA power supply unit

Surge protective devices

Arrester for 277/480 V and 347/600 V wye systems

Arrester for 120/240-208 V high-leg delta systems

Arrester for delta systems

Technical data Technical data36-2C-120 50-120/240S 80-120/240S

MCOV 150 V 150 V 150 V Voltage Protection Rating (VPR)

L-N / L-PE 700 V / - 700 V / 800 V 700 V / 800 VN-PE / L-L - / 1200 V - / 1200 V - / 1200 V

Short-circuit current rating (SCCR) 25 kA 25 kA 25 kANominal discharge current In 10 kA 10 kAUL type Type 1 Type 1Connection data

Power (AWG / length) 14 AWG / 61 cm 12 AWG / 61 cmDegree of protection NEMA 4X NEMA 4XHousing material Non-metal Non-metalError/status indicator Optical Optical Temperature range -40°C ... 70°C -40°C ... 70°CDimensions W / H / D 57.00 mm / 57.00 mm / 49.00 mm 76.00 mm / 91.00 mm / 68.00 mmTest standards UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

Ordering data Ordering data

Description Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

Component surge protection36 kA, 120 V, 2-phase with common GND-N VAL-SQ SI 36-2C-120 2800003 1

Component surge protection50 kA, 120/240 V, 2-phase with separate GND-N VAL-SQ SI 50-120/240S 2800323 1

80 kA, 120/240 V, 2-phase with separate GND-N VAL-SQ SI 80-120/240S 2800324 1

100 kA, 120/240 V, 2-phase with separate GND-N

120 kA, 120/240 V, 2-phase with separate GND-N

Component surge protection40 kA, up to 600 V, 3-phase with common GND-N

78 PHOENIX CONTACT

L1 L2 PE/N

� �

L1 L2 GND N

� � �

VAL-SQ SI products provide an inexpensive means of protecting electronic equipment in light commercial, light industrial, and residential environments.– Compact NEMA 4X housing– Each surge suppression mode is

individually fused– LEDs provide continuous feedback on the

status of each phase– UL 1449 3rd edition listed

Notes:

The products are only available for export outside the EU and the European Economic Area.

Device protection for control cabinets and small installations

Surge protection for NEMA power supply unit

Surge protective devices

Arrester, 36 kA, 2-phase Arrester for 120/240 V single/split-phase systems

For additional information, visit www.phoenixcontact.net/catalog

Technical data Technical data100-120/240S 120-120/240S 40-3C-600

150 V 150 V 750 V

1200 V / 700 V 1200 V / 700 V 4000 V / 2500 V- / 1200 V - / 1200 V - / 4000 V25 kA 25 kA 25 kA

10 kA 10 kAType 1 Type 1

12 AWG / 61 cm 12 AWG / 61 cmNEMA 4X NEMA 4XNon-metal Non-metal

Optical Optical -40°C ... 70°C -40°C ... 70°C

76.00 mm / 91.00 mm / 68.00 mm 92.00 mm / 76.00 mm / 64.00 mmUL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 / UL 1449 3rd edition, Sept. 2009 / UL 1283 / IEEE C62.41 /

IEEE C62.45 IEEE C62.45

Ordering data Ordering data

Type Order No. Pcs. / Pkt. Type Order No. Pcs. /

Pkt.

VAL-SQ SI 100-120/240S 2800325 1

VAL-SQ SI 120-120/240S 2800326 1

VAL-SQ SI 40-3C-600 2800007 1

79PHOENIX CONTACT

L1 L2 GND N

� � �

L1 L2 L3 PE/N

� � �

Surge protection for NEMA power supply unit

Surge protective devices

Arrester for 120/240 V single/split-phase systems

Arrester, 40 kA, 3-phase

Network type Application

Split/single-phase

120/240 V

Three-phase high-leg delta

120/240 - 208 V

v

L

N

L

L

LLN

L

L

LPEN

A

N

C

CN

A B

B

C

AN

1 32 34

B

C

A

N

CN

A B

80 PHOENIX CONTACT

VAL-SQ SP

VAL-SQ SE

VAL-SQ SE VAL-SQ SI

L

PEN

L

L

NL

A

N

C

1233

VAL-SQ SP

VAL-SQ SI VAL-SQ SI1 Green Earth ground

2 White Neutral

3 Black Phase

1 Green Earth ground

2 White Neutral

3 Black Phase

4 Orange High-leg phase

Surge protection for NEMA power supply unit

Applications

Network type Application

Three-phase deltaFloating or

corner ground

240 V480 V600 V

Three-phase wye

120/208 V277/480 V347/600 V

L

L

L

L

N

L

L

L

PENL

L

L

L

L

B

N

C

A

12333

A

N

B

C

CN

A B

B

C

A

CN

A B

B

CA

333

81PHOENIX CONTACT

VAL-SQ SE VAL-SQ SP

VAL-SQ SPVAL-SQ SE

VAL-SQ SI

VAL-SQ SI

1 Green Earth ground

2 White Neutral

3 Black Phase

3 Black Phase

Surge protection for NEMA power supply unit

Applications