Source-changeover systems

Catalogue

Compact, Interpactand Masterpact

2004

312E0100_Ver1.0.fm Page 4 Vendredi, 2. juillet 2004 11:08 11

Page 2: Catalogue - ATS Part1

0

The Guiding System, the new way to create your electrical installations

A comprehensive offer of products with consistent design

The Guiding System is first and foremost a Merlin Gerin product offer covering all electrical distribution needs. However, what makes all the difference is that these products have been designed to operate togheter: mechanical and electrical compatibility, interoperability, modularity, communication.Thus the electrical installation is both optimised and more efficient: better continuity of supply, enhanced safety for people and equipment, guaranteed upgradeability, effective monitoring and control.

Tools to simplify design and implementation

With the Guiding System, you have a comprehensive range of tools - the Guiding Tools - that will help you increase your product knowledge and product utilisation. Of course this is in compliance with current standards and procedures.These tools include technical booklets and guides, design aid software, training courses, etc. and are regularly updated.

For a genuine partnership with you

Because each electrical installation is unique, there is no standard solution. With the Guiding System, the variety of combinations allows for genuine customisation solutions. You can create and implement electrical installations to meet your creative requirements and design knowledge. You and Merlin Gerin’s Guiding System form a genuine partnership.

For more details on the Guiding System,consult www.merlin-gerin.com

Copie de 180E1000.fm Page 0 Mardi, 19. octobre 2004 11:23 11

Page 3: Catalogue - ATS Part1

1

0

A consistent design of offers from Medium Voltage to Ultra terminal

All Merlin Gerin offers are designed according to electrical, mechanical and communication consistency rules.The products express this consistency by their overall design and shared ergonomics.

Electrical consistency:

Each product complies with or enhances system performance at co-ordination level: breaking capacity, Isc, temperature rise, etc. for more safety, continuity of supply (discrimination) or economic optimisation (cascading).The leading edge technologies employed in Merlin Gerin’s Guiding System ensure high performance levels in discrimination and cascading of protection devices, electrodynamic withstand of switches and current distributors, heat loss of devices, distribution blocks and enclosures.Likewise, inter-product ElectroMagnetic Compatibilty (EMC) is guaranteed.

Discrimination guarantees co-ordination between the operating characteristics of serial-connected circuit-breakers. Should a fault occurs downstream, only the circuit-breaker placed immediately upstream from the fault will trip.

Mechanical consistency:

Each product adopts dimensional standards simplifying and optimising its use within the system.It shares the same accessories and auxiliaries and complies with global ergonomic choices (utilisation mode, operating mode, setting and configuration devices, tools, etc.) making its installation and operation within the system a simpler process.

Prefabricated and tested solutions, upstream and downstream from the device complying with the IEC 60439-1 switchboard standard.

Communication consistency:

Each product complies with global choices in terms of communication protocols (Modbus, Ethernet, etc.) for simplified integration in the management, supervision and monitoring systems.

Thanks to the use of standard Web technologies, you can offer your customers intelligent Merlin Gerin switchboards allowing easy access to information: follow-up of currents, voltages, powers, consumption history, etc.

Guiding Tools for more efficient design and implementation of your installations.

Copie de 180E1000.fm Page 1 Mardi, 19. octobre 2004 11:23 11

Page 4: Catalogue - ATS Part1

2

0

SM6

Medium voltage switchboard system from 1 to 36 kV

Sepam

Protection relays

Masterpact

Protection switchgear from 100 to 6300 A

TrihalMV/LV dry cast resin transformer from 160 to 5000 kVA

EvolisMV vacuum switchgear and components from 1 to 24 kV.

The Technical guide

These technical guides help you comply with installation standards and rules i.e.:The electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high-performance electrical installations.For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

CAD software and tools

The CAD software and tools enhance productivity and safety.They help you create your installations by simplifying product choice through easy browsing in the Guiding System offers.Last but not least, they optimise use of our products while also complying with standards and proper procedures.

Copie de 180E1000.fm Page 2 Mardi, 19. octobre 2004 11:23 11

Page 5: Catalogue - ATS Part1

3

0

Compact

Protection switchgear system from 100 to 630 A

Multi 9

Modular protection switchgear system up to 125 A

Prisma Plus

Functional system for electrical distribution switchboards up to 3200 A

Pragma CanalisEnclosures for distribution switchboards up to 160 A

Prefabricated Busbar Trunking from 25 to 4000 A

PowerLogicPowermanagement

Training

Training allows you to acquire the Merlin Gerin expertise (installation design, work with power on, etc.) for increased efficiency and a guarantee of improved customer service.The training catalogue includes beginner’s courses in electrical distribution, knowledge of MV and LV switchgear, operation and maintenance of installations, design of LV installations to give but a few examples.

Copie de 180E1000.fm Page 3 Mardi, 19. octobre 2004 11:23 11

Page 6: Catalogue - ATS Part1

4

PB

1008

39

To ensure a continuous supply of electrical power, certain installations are connected to two sources:b a normal source Nb a replacement source R used to supply the installation when the normal source is unavailable.

A source-changeover system switches the load between these two sources. It can be automated to manage transfers according to external conditions. A source-changeover system includes two or three circuit breakers or switch-disconnectors.

With Interpact INS, Compact NS and Masterpact NT and NW, new installation solutions are available to optimise the size of the switchboard and simplify installation.

Interlocking of two Interpact switch-disconnectors via rotary handles.

PB

1008

40

Complete source-changeover assembly with two Interpact switch-disconnectors.

PB

1009

30-6

8

Interlocking of two Compact NS circuit breakers on a base plate.

PB

1008

42

Interlocking of two Masterpact NT and NW circuit breakers using cables.

312E0100_Ver1.0.fm Page 5 Jeudi, 1. juillet 2004 2:16 14

Page 7: Catalogue - ATS Part1

5

Source-changeover systems

General content 0

Presentation 6

Functions and characteristics 11

Dimensions 41

Electrical diagrams 63

Catalogue numbers and order forms 99

Page 8: Catalogue - ATS Part1

6

Presentation For maximum continuity of service ... 0

PB

1008

43

Manual source-changeover systemThis is the most simple type. It is controlled manually by an operator and consequently the time required to switch from the normal to the replacement source can vary.A manual source-changeover system is made up of two or three mechanically interlocked manually-operated circuit breakers or switch-disconnectors.

Remote-operated source-changeover systemThis is the most commonly employed system for devices with high ratings (above 400 A). No human intervention is required. Transfer from the normal to the replacement source is controlled electrically.A remote-controlled source-changeover system is made up of two or three circuit breakers or switch-disconnectors linked by an electrical interlocking system that may have different configurations. In addition, a mechanical interlocking system protects against electrical malfunctions or incorrect manual operations.

Automatic source-changeover systemsAn automatic controller may be added to a remote-operated source-changeover system for automatic source control according to programmable operating modes.This solution ensures optimum energy management:b transfer to a replacement source according to external requirementsb management of power sourcesb regulationb emergency source replacement, etc.The automatic controller may be fitted with an option for communication with a supervisor.

PB

1008

44

Commercial and service sector:b operating rooms in hospitalsb safety systems for tall buildingsb computer rooms (banks, insurance companies, etc.)b lighting systems in shopping centres…

PB

1008

45

Industry:b assembly linesb engine rooms on shipsb critical auxiliaries in thermal power stations…

PB

1008

46P

B10

0847

Infrastructures:b port and railway installationsb runway lighting systemsb control systems on military sites…

Page 9: Catalogue - ATS Part1

7

Presentation ... in a wide range of applications 0

PB

1008

39

PB

1008

42Interlocking of two Interpact switch-disconnectors via rotary handles.

PB

1008

40

Interlocking of two Masterpact NT and NW circuit breakers using cables.

PB

1008

49

PB

1008

50

Complete source-changeover assembly with two Interpact switch-disconnectors.

PB

1009

57-6

2

Interlocking of two Compact NS circuit breakers on a base plate.

Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

Interlocking of three Masterpact NW circuit breakers using cables.

Other source-changeover systems: Telemecanique products

PB

1008

48

PB

1008

51

See LC2-D series.

See LC2-F series.

Page 10: Catalogue - ATS Part1

8

Presentation For maximum continuity of service... 0

Incoming feeders and main LV switchboards

PB

1008

53

DB

1015

43

CurrentsFrom 630 to 6300 A.

Power distribution

PB

1008

52

CurrentsFrom 250 to 3200 A.

Loads

PB

1008

54

CurrentsFrom 40 to 400 A.

Page 11: Catalogue - ATS Part1

9

Presentation ... in a wide range of applications 0

1 normal source 1 replacement source

2 sources with coupler on busbars

2 normal sources1 replacement source

DB

1015

38

DB

1015

39

DB

1015

40

QN QR QS1 QC QS2 QN1 QN2 QR0 0 0 0 0 0 0 01 0 1 0 1 1 1 0

0 1 1 1 0 0 0 10 1 1 1 0 01 0 0 (1) 0 1 0

0 0 1 (1)

(1) possible by forcing operation.

Generator or permanent source

DB

1015

41

QN QR Typical applications:b continuous production processesb operating roomsb computer rooms...

0 0

1 00 1

Generator or permanent source

Generator or permanent source

DB

1015

41

DB

1015

44

QN QR Typical applicationsb large electrical installations (e.g. airports)b refrigeration unitsb special electricity tariffsb pumping stations...

0 01 0

0 1

Page 12: Catalogue - ATS Part1

10

Page 13: Catalogue - ATS Part1

11

Source-changeover systems

Functions and characteristics

Presentation 6

Overview of solutionsManual source-changeover systems Interpact INS and Compact NS 40 A to 630 A 12

Overview of solutionsManual source-changeover systems Compact NS andMasterpact NT/NW 630 A to 6300 A 13

Overview of solutionsRemote-operated source-changeover systems Compact NS100/1600 100 A to 1600 A 14

Overview of solutionsRemote-operated source-changeover systemsMasterpact NT/NW 630 A to 6300 A 15

Manual source-changeover systems 16Possible combinations 16

Remote-operated source-changeover systems 20Mechanical interlocking 20General characteristics 22Mechanical and electrical durability 24

Connection and insulation accessories for Compact NS and INS y 630 A 25Electrical interlocking 26Standard configurations 27

Associated controllers 28Controller selection 28Controller installation 29BA controller 30BA controller 31Operating sequences 31

Associated controllers 32UA controller 32UA controller 33Operating sequences 33

Operating sequences 36

COM communications option 38

Dimensions 41Electrical diagrams 63Catalogue numbers and order forms 99

Page 14: Catalogue - ATS Part1

12

Functions and characteristics

Overview of solutionsManual source-changeover systems Interpact INS and Compact NS 40 A to 630 A 0

Range Interpact CompactModels INS40 to INS80

NS100 to INS160INS250 to INS630INV250 to INV630

NS100 to NS250NS400 to NS630

Rating (A) 40 to 160 100 to 630 100 to 630Type of device Switch-disconnectors with

extended handlesSwitch-disconnectors N/H/L circuit breakers

NA switch-disconnectors

Manual source-changeover systemsInterlocking via toggles

DB

1017

68

DB

1015

45

2 devices side-by-side 3 devices side-by-side

Interlocking via rotary handles

DB

1017

69

DB

1015

46

DB

1015

47

DB

1015

48

2 devices side-by-side

Interlocking via keylocks with captive keys

DB

1017

70

DB

1015

49

DB

1015

50

A number of different devices

Interlocking on a base plate

DB

1017

71

DB

1015

51

2 devices side-by-side

Complete source-changeover assemblies

DB

1017

72

DB

1015

52

2 devices side-by-side

N

2.4

ONI

OOFF

ONI

OOFF

Page 15: Catalogue - ATS Part1

13

Functions and characteristics

Overview of solutionsManual source-changeover systems Compact NS andMasterpact NT/NW 630 A to 6300 A 0

Range Compact MasterpactModels NS630b to NS1600 NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 630 to 1600 800 to 6300 Type of device N/H/L circuit breakers

NA switch-disconnectorsH1/L1 circuit breakersHA switch-disconnectors

N1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

Manual source-changeover systemsInterlocking via extended rotary handles

DB

1017

69

DB

1015

53

2 devices side-by-side

Interlocking via keylocks with captive keys

DB

1017

70

DB

1015

54

DB

1015

55

DB

1015

56

A number of different devices

Mechanical interlocking using connecting rods

DB

1017

73

DB

1015

57

DB

1015

58

DB

1015

59

2 devices one above the other

(1)

Mechanical interlocking using cables

DB

1017

74

DB

1015

60

DB

1015

61

DB

1015

62

2 or 3 devices one above the other

DB

1017

75

(1)

(2)2 or 3 devices side-by-side

For this case and other cases, please consult us

DB

1019

16

(1) Implemented with NS630b to NS1600 electrically-operated devices only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page 23.

Opush OFF

Ipush ON

O OFF

discharged

Opush OFF

Ipush ON

O OFF

discharged

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

Page 16: Catalogue - ATS Part1

14

Functions and characteristics

Overview of solutionsRemote-operated source-changeover systems Compact NS100/1600 100 A to 1600 A 0

Range CompactModels NS100 to NS630 NS630b to NS1600Rating (A) 100 to 630 630 to 1600Type of device N/H/L circuit breakers

NA switch-disconnectorsN/H/L circuit breakersNA switch-disconnectors

Remote-operated source-changeover systemMechanical interlocking on base plate + electrical interlocking

DB

1017

71

DB

1015

63

2 electrically-operated devices side-by-side combined with an electrical interlocking system

Mechanical interlocking using connecting rods + electrical interlocking

DB

1017

73

DB

1015

57

2 electrically-operated devices one above the other combined with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking

DB

1017

77

DB

1015

60

2 electrically-operated devices one above the other combined with an electrical interlocking system

DB

1017

76

2 electrically-operated devices side-by-side combined with an electrical interlocking system

(2)

Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

DB

1017

77

The automatic controller operates the devices depending on external parameters.

BA: Simple controller that manages the changeover function.

UA: Controller that also manages engine generator sets.

UA150: UA controller with a communication option.

DB

1015

64

BA controller

DB

1017

76

DB

1015

65

UA and UA150 controller

(2) For source-changeover systems using cables, always respect the installation conditions specified on page 23.

OpushOFF

IpushON

OOFF

discharged

OpushOFF

IpushON

OOFF

discharged

Page 17: Catalogue - ATS Part1

15

Functions and characteristics

Overview of solutionsRemote-operated source-changeover systemsMasterpact NT/NW 630 A to 6300 A 0

Range MasterpactModels NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 800 to 6300 Type of device H1/L1 circuit breakers

HA switch-disconnectorsN1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

Remote-operated source-changeover systemMechanical interlocking using connecting rods + electrical interlocking

DB

1017

73

DB

1015

58

DB

1015

59

2 electrically-operated devices side-by-side combined with an electrical interlocking system

Mechanical interlocking using cables + electrical interlocking

DB

1017

74

DB

1015

61

DB

1015

62

2 or 3 electrically-operated devices one above the other combined with an electrical interlocking system (1)

DB

1017

75

2 or 3 electrically-operated devices side-by-side combined with an electrical interlocking system (1)

(2)

Automatic source-changeover systemsRemote-operated source-changeover system combined with an automatic-control system

DB

1017

77

The automatic controller operates the devices depending on external parameters.

BA: Simple controller that manages the changeover function.

UA: Controller that also manages engine generator sets.

UA150: UA controller with a communication option.

DB

1015

64

BA controller

DB

1017

76

DB

1015

65

UA and UA150 controller

(1) Three devices with Masterpact NW only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page 23.For other cases, please consult us.

Page 18: Catalogue - ATS Part1

16

Functions and characteristics

Manual source-changeover systems 0

Possible combinations

A manual source-changeover system can be installed on two or three manually-operated and mechanically interlocked circuit breakers or switch-disconnectors.Interlocks prevent connection to both sources at the same time, even momentarily.

All possibilities for manual source-changeover systems

Type of device Type of interlocking for two devicesComplete assembly

Keylock Direct rotary handle

Extended rotary handle

Interpact switch-disconnectors

INS40 to INS160 b

INS250-100 to INS630 b b b r b r

INV100 to 630 b b r b r r

INS/INV630b to 2500 bLegend:r Possible but visible break function disabled.r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Type of device Type of interlocking for two devicesToggle Keylock Direct rotary

handleExtended rotary handle

On base plate (toggle or direct extended rotary control)

On base plate(motor mechanism)

Compact fixed or withdrawable circuit breakers

NS100 to 250 b b b b p b b b b b b b b b b

NS400 to NS630 b b b b p b b b b b b b b b b

NS100 to 630 b b p b b p b b p b b b p b b b p

NS630b to 1600 with rotary handle

b b p b b b b

Legend:b Fixed devices only.b Fixed or withdrawable devices.b Devices must be either both fixed or both withdrawable.p With NS400/630 rotary handle interlocking system.p Possible with NS400/630 base plate + NS100-250 adaptation kit.p Devices equipped with rotary handles.

Type of device Type of interlocking for either all fixed or all withdrawable devicesKeylock Cable-type,

2 devices side-by-side

Cable-type,3 devices side-by-side

Cable-type,2 devices one above the other

Cable-type,3 devices one above another

Rod-type,3 devices one above another

Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism NS630b to 1600 b b b bMasterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism

NT06 to 16 b b b b

NW08 to 63 b b b b b b

NT06 to NW63 b b b

Page 19: Catalogue - ATS Part1

17

Functions and characteristics

Manual source-changeover systems 0

Possible combinations

All possibilities for manual source-changeover systems

DB

1015

71

Complete source-changeover assembly for two switch-disconnectorsThese assemblies provide an easy way to implement source changeover functions with:b a single 3-position rotary handle that controls the two switch-disconnectors (Normal source ON, OFF, Replacement source ON)b a smaller size, taking up less room in the switchboard.A complete source changeover assembly can be ordered with a single catalogue number.

Complete source-changeover assembly for two Interpact INS switch-disconnectors.

"Normal N" "Replacement" RINS250-100 INS250-160 INS200-200 INS250-250 INS320 INS400 INS500 INS630

INS250-100Ratings 100 A bINS250-160Ratings 160 A bINS200-200Ratings 200 A bINS250-250Ratings 250 A bINS320Ratings 320 A bINS400Ratings 400 A bINS500Ratings 500 A bINS630Ratings 630 A b

Possible combinations of “Normal” and “Replacement” source circuit breakers

DB

1015

66

Interlocking of two or three toggle-controlled devicesTwo devices can be interlocked using this system. Two identical interlocking systems can be used to interlock three devices installed side by side, in which case one device is in the ON position and the two others are in the OFF position. Devices must all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout.The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).Two interlocking system models are available for:b Compact NS100 to 250b Compact NS400 to 630.

"Normal N" "Replacement" RInterlocking of two toggle-controlled devices. NS100 NS160 NS250 NS400 NS630

NS100Ratings 16... 100 A b b b b bNS160Ratings 80...160 A b b b b bNS250Ratings 125...250 A b b b b bNS400Ratings 150... 400 A b b b b bNS630Ratings 630 A b b b b b

Page 20: Catalogue - ATS Part1

18

Functions and characteristics

Manual source-changeover systems 0

Possible combinations

Combination of “Normal” and “Replacement” devices

All Interpact, Compact and Masterpact circuit breakers and switch-disconnectors from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.

DB

1015

69

Interlocking of a number of devices using keylocks (captive keys)Interlocking is based on two identical keylocks with a single key and a keylock adapter (different for each device). This solution enables interlocking between two devices that are physically distant or that have very different characteristics, for example between a low and a medium-voltage device, or between Compact NS circuit breakers and switch-disconnectors.A system of wall-mounted captive key boxes makes possible a large number of combinations between many devices.

Keylock-type interlocking of two circuit breakers with rotary handles or motor mechanisms.

Possible combinations of “Normal” and “Replacement” source circuit breakers

DB

1015

68

Interlocking of two devices with rotary handlesThe direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.(1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking system.

"Normal N" "Replacement" RCompact NS100/630 (1) NS100 NS160 NS250 NS400 NS630

NS100Ratings 16... 100 A b b b v v

Interlocking of two Compact NS circuit breakers with rotary handles.

NS160Ratings 80...160 A b b b v vNS250Ratings 125...250 A b b b v vNS400Ratings 160... 400 A v v v b bNS630Ratings 630 A v v v b bv 250 A and 630 A ratings can be mixed by using NS400/630 rotary handle interlocking system.

"Normal N" "Replacement" RCompact NS630/1600(1) NS630b NS800 NS1000 NS1200 NS1600

NS630bRatings 250... 630 A b b b b bNS800Ratings 320... 800 A b b b b bNS1000Ratings 400... 1000 A b b b b bNS1200Ratings 480... 1200 A b b b b bNS1600Ratings 640... 1600 A b b b b b

(1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking system.

ONI

OOFF

ONI

OOFF

Page 21: Catalogue - ATS Part1

19

Functions and characteristics

Manual source-changeover systems 0

Possible combinations

Possible combinations of “Normal” and “Replacement” source switch-disconnectors

DB

1015

67

Interlocking of two devices with rotary handlesThe direct or extended rotary handles are padlocked with the devices in the OFF position. The mechanism prevents simultaneous closing of the devices, but allows them to be opened.

"Normal N" "Replacement" RInterpact INS (1) INS40 INS63 INS80 INS100 INS125 INS160INS40Ratings 40 A b b b b b bINS63Ratings 63 A b b b b b bINS80Ratings 80 A b b b b b b

Interlocking of two Interpact switch-disconnectors with direct rotary handles.

INS100Ratings 100 A b b b b b bINS125

(1) With extended rotary handles only.(2) Possible with INV, but visible-break function is significantly impaired.

Ratings 125 A b b b b b bINS160Ratings 160 A b b b b b b

"Normal N" "Replacement" RInterpact INS /INV (2) INS250-100/

INV100INS250-160/INV160

INS250-200/INV200

INS250-250/INV250

INS320/INV320

INS400/INV400

INS500/INV500

INS630/INV630

INS250-100/INV100Ratings 100 A b b b b v v vINS250-160/INV160Ratings 160 A b b b bINS250-200/INV200Ratings 200 A b b b bINS250-250/INV250Ratings 250 A b b b b v vINS320/INV320Ratings 320 A v v b b b bINS400/INV400Ratings 400 A b b b bINS500/INV500Ratings 500 A b b b bINS630/INV630Ratings 630 A v v b b b bv 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Possible combinations of Compact “Normal” and “Replacement” source circuit breakers

DB

1015

70

Interlocking of two devices on a base plateA base plate is available for mechanical interlocking of two manually-operated Compact circuit breakers or switch-disconnectors."Normal N" "Replacement" R

NS100 NS160 NS250 NS400 NS630NS100Ratings 16... 100 A b b b b bNS160Ratings 80... 160 A b b b b bNS250Ratings 125... 250 A b b b b bNS400Ratings 150... 400 A b b b b b

Interlocking of two manually-operated Compact NS devices on a base plate.

NS630Ratings 630 A b b b b b

Combination of Masterpact devices

DB

1019

03

Interlocking of a number of devices using keylocks (captive keys)Interlocking uses two identical keylocks with a single key. This solution enables interlocking between two devices that are physically distant or that have significantly different characteristics.

pushto

trip

pushto

trip

Page 22: Catalogue - ATS Part1

20

Functionsand characteristics

Remote-operated source-changeover systems 0

Mechanical interlocking

Electrical interlocking of two or three devices is used to create a remote-operated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation.

Interlocking of two Compact NS100 to 630 devices using a base plateA base plate designed for two Compact circuit breakers can be installed horizontally or vertically on a mounting rail. Interlocking is carried out on the base plate by a mechanism located behind the breakers. Access to the circuit breaker controls and trip units is conserved. Circuit breakers must be fixed or plug-in versions, with or without earth-leakage protection or measurement modules. The base plate and the circuit breakers are supplied separately.b base plate for Compact NS100 to 250 devicesThis base plate is intended for two Compact NS100 to 250 devices.b base plate for Compact NS400 to 630 devicesThis base plate is intended for two Compact NS400 to 630 devices. It may also be used, without any modifications, to interlock a fixed Compact NS100 to 250 with a Compact NS400 or 630 device.An adapter kit is required for plug-in versions of the Compact NS100 to 250 devices.Compact NS100 to 250 devices, in both fixed and plug-in versions, may be equipped with spreaders.

PB

1009

30-6

7

Possible combinations of “Normal” and “Replacement” Compact source circuit breakers

"Normal N" "Replacement" RNS100 NS160 NS250 NS400 NS630

NS100Interlocking of two electrically-operated Compact NS circuit breakers using a base plate.

Ratings 12,5... 100 A b b b b bNS160Ratings 12,5...160 A b b b b bNS250Ratings 12,5...250 A b b b b bNS400Ratings 160... 400 A b b b b bNS630Ratings 250... 630 A b b b b b

DB

1015

72

Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rodsThe two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices).Combinations are possible between Compact NS630b to NS1600 devices and between Masterpact NT and Masterpact NW devices.

InstallationThis function requires:b an adaptation fixture on the right side of each circuit breaker or switch-disconnectorb a set of connecting rods with no-slip adjustments.The adaptation fixtures, connecting rods and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.The maximum vertical distance between the fixing planes is 900 mm.

Possible combinations of “Normal” and “Replacement” source circuit breakers

"Normal N" "Replacement" RNS630b to NS1600

NT06 to NT16 NW08 to NW40

NW40b to NW63

NS630b to NS1600Ratings 250... 1600 A b

Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

NT06 to NT16Ratings 250... 1600 A b b bNW08 to NW40Ratings 320... 4000 A b b bNW40b to NW63Ratings 4000... 6300 A b b b

Page 23: Catalogue - ATS Part1

21

Functions and characteristics

Remote-operated source-changeover systems 0

Mechanical interlocking

PB

1008

42

Interlocking of two Compact NS630b to 1600 or two Masterpact NT/NW or up to three Masterpact NW devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other or side-by-side.The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes.Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW)This function requires:b an adaptation fixture on the right side of each deviceb a set of cables with no-slip adjustments.The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.

Interlocking between three devices (Masterpact NW only)This function requires:b a specific adaptation fixture for each type of interlocking, installed on the right side of each deviceb two or three sets of cables with no-slip adjustments.The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm.

InstallationThe adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.

Installation conditions for cable interlocking systems:b cable length: 2.5 mb radius of curvature: 100 mb maximum number of curves: 3.

Interlocking of two Masterpact circuit breakers using cables.

Possible combinations of “Normal” and “Replacement” source circuit breakers

"Normal N" "Replacement" RNS630b to NS1600

NT06 to NT16 NW08 to NW40

NW40b to NW63

NS630b to NS1600Ratings 250... 1600 A bNT06 to NT16Ratings 250... 1600 A b b bNW08 to NW40Ratings 320... 4000 A b b bNW40b to NW63Ratings 4000... 6300 A b b b

It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW) devices.All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.

Possible combinations of three device

NS630b to NS1600

NT06 to NT16 NW08 to NW40

NW40b to NW63

NS630b to NS1600Ratings 250... 1600 A

NT06 to NT16Ratings 250... 1600 ANW08 to NW40Ratings 320... 4000 A b bNW40b to NW63Ratings 4000... 6300 A b b

Only Masterpact NW may be used for three-device combinations.

Types of mechanical interlocking and combinationsSee page 14 to page 19.

Page 24: Catalogue - ATS Part1

22

Functions and characteristics

Remote-operated source-changeover systems 0

General characteristics

Range Compact Types of devices NS100 to NS250 NS400 to NS630Types of circuit breakers N / H / L N / H / LSwitch-disconnector version NA NAMixing possibilities all devices all devices

NS100 to NS250 NS100 to NS630N/H/L/NA N/H/L/NA fixed or plug-in fixed or plug-in

Electrical characteristicsRating 15 to 250 A 15 to 630 AInsulating voltage Ui (V AC) 750 750 Positive break indication b bNumber of poles(N and R devices must have the same number of poles)

3, 4

Electrical durability See page 24Operating temperature –25 °C to +70 °C (50 °C for 440 V - 60 Hz)Control characteristics

Control voltage AC 48 to 415 V - 50/60 Hz 440 V - 60 Hz

DC 24-250 VMaximum consumption AC 500 VA 500 VA

DC 500 W 500 WMinimum switching time 800 ms 800 msInterlocking

Mechanical (see page ...)Electrical by diagram (without IVE) b b

with IVE unit b bauxiliary contacts used by circuit breaker 1 OF + 1 SDE 1 OF + 1 SDE

Protection and measurementOverload protection long time b bShort-circuit protection short time b b

instantaneous b bEarth-fault protection bZone selective interlocking (ZSI) bEarth-leakage protection by Vigi module b b

by control unitby add-on Vigirex relay b b

Current measurementsVoltage, frequency, power measurements, etc.Indication and control auxiliaries

Available auxiliary indication contacts OF + SD (+ SDV) 2 OF + SD (+ SDV)Voltage releases MX shunt b b

MN undervoltage b bVoltage presence indicator b bVoltage transformer b bAmmeter module b bInsulation monitoring module b bSource-changeover controller

With permanent replacement source b BA controllerWith standby generator set b UA controllerRemote communication via bus

Device status indications b bDevice remote controlTransmission of settingsIndication and identification of protection status and alarmsTransmission of measurementsInstallation and connection

Fixed front connectedFixed rear connected b (long rear connections) b (long rear connections)Withdrawable, plug-in or drawout b (plug-in on base) b (plug-in on base)Installation and connection accessories

Downstream coupling accessory b bBare-cable connectors b bTerminal extensions b bTerminal shields and inter-phase barriers bLocking by padlock b b

by keylock b bFront panel escutcheons b b

Page 25: Catalogue - ATS Part1

23

Functions and characteristics

Remote-operated source-changeover systems 0

General characteristics

MasterpactNS630b to NS1600 NT06 to 16 NW08 to 63N / H / L N1 / H1 / H2 / H3 / L1 N1 / H1 / H2 / H3 / L1NA NA / HA / HF NA / HA / HFall devices all mixing possibilities all mixing possibilitiesNS630b to 1600 (fixed, drawout or fixed + drawout) (fixed, drawout or fixed + drawout) N/H/L/NA N1/H1/H2/H3/L1/NA/HA/HF N1/H1/H2/H3/L1/NA/HA/HFfixed or plug-in

250 to 1600 A 600 to 1600 A 800 to 6300 A750 1000 1000b b b

3, 4

See page 24–25 °C to +70 °C (50 °C for 440 V - 60 Hz)

48 to 415 V - 50/60 Hz 440 V - 60 Hz24-250 V

180 VA 180 VA 180 VA180 W 180 W 180 W800 ms 800 ms 800 ms

b b bb only with UA or BA only with UA or BA1 OF + 1 CE (+ SDE) 1 OF + 1 CE + 1 PF 1 OF + 1 CE + 1 PF

b b bb b bb b bb b bb b b

b b bb b bb b b

b b

2 OF + SD 2 OF + SD 2 OF + SDb b bb b b

b bb bb bb b

b BA controllerb UA controller

b b b

b b bb b bb b b

b (vertical or horizontal) b (vertical or horizontal) b (vertical or horizontal)b (drawout) b (drawout) b (drawout)

b

bb b bb b bb b b

Page 26: Catalogue - ATS Part1

24

Functions and characteristics

Remote-operated source-changeover systems 0

Mechanical and electrical durability

Interpact INS switch-disconnectorsINS250-100 INS250-160 INS250-200 INS250

Number of poles 3, 4 3, 4 3, 4 3, 4Conventional thermal current (A) lth At 60 °C 100 160 200 250

Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A440-480 V 100 100 160 160 200 200 250 250660-690 V 100 100 160 160 200 200 250 250

Durability (category A) (ON-CR-OR-CN cycles)

Mechanical 15000 15000 15000 15000Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A440-480 V 1500 1500 1500 1500 1500 1500 1500 1500

660-690 V 1500 1500 1500 1500 1500 1500 1500 1500

INS320 INS400 INS500 INS630Number of poles 3, 4 3, 4 3, 4 3, 4Conventional thermal current (A) lth at 60 °C 320 400 500 630Rated operational current (A) Ie Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A

440-480 V 320 320 400 400 500 500 630 630660-690 V 320 320 400 400 500 500 630 630

Durability (category A) (ON-CR-OR-CN cycles)

Mechanical 10000 10000 10000 10000

Electrical AC, 50/60 Hz AC22A AC23A AC22A AC23A AC22A AC23A AC22A AC23A440-480 V 1500 1500 1500 1500 1500 1500 1500 1500660-690 V 1500 1500 1500 1500 1500 1500 1500 1500

Compact NS100-NS1600NS100-250 NS400-630 NS630b-

NS1600Number of poles 3, 4 3, 4 3, 4Rated current In (A) 100 to 250 400 to 630 630 to 1600

Mechanical durability(ON-CR-OR-CN cycles)

10000 8000 8000

Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2)

10000 3000 2000

Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2)

1500 1500 1500

Masterpact NT06-NT16/NW08-NW63 (1)

NT06-NT10

NT12-NT16

NW08-NW16

NW20 NW25-NW40

NW50-NW63

Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4 3, 4Rated current In (A) 630 to

16001250 to 1600

800 to 1600

2000 2500 to 4000

5000 to 6300

Mechanical durability(ON-CR-OR-CN cycles)

8000 8000 10000 10000 10000 5000

Electrical durability at In (ON-CR-OR-CN cycles) for y 440 V and 480 V NEMA (2)

6000 6000NT16: 3000

10000 8000 5000 1500

Electrical durability at In (ON-CR-OR-CN cycles) for U = 500 V to 690 V (2)

3000 2000NT16: 1000

10000 6000 2500 1500

(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.Note: ON: opening of Normal sourceCR: closing of Replacement sourceOR: opening of Replacement sourceCN: closing of Normal source

Page 27: Catalogue - ATS Part1

25

Functions and characteristics

Connection and insulation accessories for Compact NS and INS y 630 A 0

DB

1016

05

Downstream coupling accessoryThis accessory simplifies connection to bars and cables with lugs.It may be used to couple two circuit breakers (Compact NS100 to 630) or switch-disconnectors (Interpact INS/INV100 to 630) of the same size.Pitch between outgoing terminals:b Interpact INS250 and INV100 to 250: 35 mmb Interpact INS/INV320 to 630: 52.5 mmb Compact NS100 to 250: 35 mmb Compact NS400 to 630: 52.5 mm.

Connection and insulation accessoriesThe coupling accessory can be fitted with the same connection and insulation accessories as the circuit breakers and switch-disconnectors.

Possible uses Downstream couplingPossible Outgoing pitch

(mm)

Manual source-changeover systemsINS250 (100 to 250 A) with rotary handle b 35

NS100/250 with rotary handle b 35NS100/250 on base plate with toggle control b 35INS400/630 (320 to 630 A) with rotary handle b 52.5

NS400/630 with rotary handle b 52.5NS400/630 on base plate with toggle control b 52.5

Complete source-changeover assemblyINS250 (100 to 250 A) b 35INS400/630 (320 to 630 A) b 52.5

Remote-operated source-changeover systemsNS100/250 b 35

NS400/630 b 52.5

Page 28: Catalogue - ATS Part1

26

Functions and characteristics

Remote-operated source-changeover systems 0

Electrical interlocking

Electrical interlocking is used with the mechanical interlocking system. It electrically interlocks the two circuit breakers and implements the time delays required for proper operation of the system.An automatic controller may be added to take into account information from the distribution system.

Electrical interlocking is carried out by an electrical control device.For Compact NS up to 630 A, electrical interlocking is implemented by the IVE unit integrating control circuits and an external terminal block. The integrated control circuits implement the time delays required for correct source transfer.For Compact NS630b to 1600 and Masterpact, this function can be implemented in one of two ways:b using the IVE unitb by an electrician based on the diagrams presented in the “Electrical diagrams” part of this catalogue.

Characteristics of the IVE unitb external connection terminal block:v inputs: circuit breaker control signalsv outputs: status of the SDE contacts on the “Normal” and “Replacement” source circuit breakersb 2 connectors for the two “Normal” and “Replacement” source circuit breakers:v inputs:- status of the OF contacts on each circuit breaker (ON or OFF)- status of the SDE contacts on the “Normal” and “Replacement” source circuit breakersv outputs: power supply for operating mechanismsb control voltage:v 24 to 250 V DCv 48 to 415 V 50/60 Hz - 440 V 60 Hz.The IVE unit control voltage must be same as that of the circuit breaker operating mechanisms.

DB

1015

73

IVE unit.

Necessary equipmentFor Compact NS100 to 630, each circuit breaker must be equipped with:b a motor mechanismb an OF contactb an SDE contact.The components are supplied ready for assembly and the circuit breakers prewired. The prewiring must not be modified.

For Compact NS630b to 1600, each circuit breaker must be equipped with:b a motor mechanismb an available OF contactb a CE connected-position contact (carriage switch) on withdrawable circuit breakersb an SDE contact.

For Masterpact NT and NW, each circuit breaker must be equipped with:b a remote-operation system made up of:v MCH gear motorv MX or MN opening releasev XF closing releasev PF “ready to close” contactb an available OF contactb one to three CE connected-position contacts (carriage switches) on drawout circuit breakers (depending on the installation).

Page 29: Catalogue - ATS Part1

27

Functions and characteristics

Remote-operated source-changeover systems 0

Standard configurations

Compact NS, Masterpact NT and NW Types of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.2 devices

DB

1015

74

QN QR Compact NS100 to 630:0 0 b electrical interlocking without emergency

power off (EPO) auxiliaries: 512011771 0v with EPO by MN 512011780 1v with EPO by MX 51201179Compact NS630b to 1600:b electrical interlocking with lockout after fault:v permanent replacement source (without IVE) 51201180v with EPO by MX (without IVE) 51201181v with EPO by MN (without IVE) 51201182v permanent replacement source (with IVE) 51201183v with EPO by MX (with IVE) 51201184v with EPO by MN (with IVE) 51201185b automatic control without lockout after fault:v permanent replacement source (without IVE) 51201186v engine generator set (without IVE) 51201187Masterpact NT and NW:b electrical interlocking with lockout after fault:

v permanent replacement source (without IVE) 51201139v with EPO by MX (without IVE) 51201140v with EPO by MN (without IVE) 51201141v permanent replacement source (with IVE) 51201142v with EPO by MX (with IVE) 51201143v with EPO by MN (with IVE) 51201144b automatic control without lockout after fault:v permanent replacement source (without IVE) 51156226v engine generator set (without IVE) 51156227b automatic control with lockout after fault:v permanent replacement source (with IVE) 51156904v engine generator set (with IVE) 51156905b BA/UA controller (with IVE) 51156903

Masterpact NW onlyTypes of mechanical interlocking Possible combinations Typical electrical diagrams Diagram no.3 devices: 2 “Normal” sources and 1 “Replacement” source

DB

1015

75

QN1 QN2 QR b electrical interlocking:

0 0 0 v without lockout after fault 511569061 1 0 v with lockout after fault 511569070 0 1

3 devices: 2 “Normal” sources and 1 “Replacement” source with source selection

DB

1015

76

QN1 QN2 QR b automatic control with engine generator set:0 0 0 v without lockout after fault (with MN) 511569081 0 0 v with lockout after fault (with MN) 511569090 0 11 1 00 1 0

3 devices: 3 sources, only one device

DB

1015

77

QS1 QS2 QS3 b electrical interlocking:

0 0 0 v without lockout after fault 511569101 0 0 v with lockout after fault 511569110 1 0

0 0 1

3 devices: 2 sources + 1 coupling

DB

1015

78

QS1 QC QS2 b electrical interlocking:0 0 0 v without lockout after fault 511569121 0 1 v with lockout after fault 511569131 1 0 b automatic control with lockout after fault 511569140 1 11 0 0 (1)

0 0 1 (1)

(1) possible by forcing operation

“Lockout after fault” option. This option makes it necessary to manually reset the device following fault tripping.

Page 30: Catalogue - ATS Part1

28

Functions and characteristics

Associated controllers 0

Controller selection

By combining a remote-operated source-changeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences.These controllers can be used on source-changeover systems comprising 2 circuit breakers.For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the “electrical diagrams” section of this catalogue.

Controller BA UACompatible circuit breakers All Compact NS and

Masterpact circuit breakers

4-position switchAutomatic operation b bForced operation on “Normal” source b bForced operation on “Replacement” source b bStop (both “Normal” and “Replacement” sources off) b bAutomatic operation

Monitoring of the “Normal” source and automatic transfer b bGenerator set startup control bDelayed shutdown (adjustable) of generator set bLoad shedding and reconnection of non-priority circuits bTransfer to the “Replacement” source if one of the phases of the “Normal” phase is absent

b

TestBy opening the P25M circuit breaker supplying the controller b

PB

1008

55

By pressing the test button on the front of the controller bIndications

Circuit breaker status indication on the front of the controller: on, off, fault trip

b b

Automatic mode indicating contact b bOther functions

Selection of type of “Normal” source (single-phase or three-phase) (1)

b

Voluntary transfer to “Replacement” source (e.g. energy management commands)

b b

During peak-tariff periods (energy management commands) forced operation on “Normal” sourceif “Replacement” source not operational

b

Additional contact (not part of controller). Transfer to “Replacement” source only if contact is closed. (e.g. used to test the frequency of UR).

b b

BA controller. Setting of maximum startup time for the replacement source bOptions

PB

1008

56

Communication option

Power supplyControl voltages (2) 110 V b b

220 to 240 V 50/60 Hz b b380 to 415 V 50/60 Hz and 440 V 60 Hz

b b

Operating thresholdsUndervoltage 0.35 Un y voltage y 0.7 Un b bPhase failure 0.5 Un y voltage y 0.7 Un bVoltage presence voltage u 0.85 Un b bIP degree of protection (EN 60529) and IK degree of protection against external mechanical impacts (EN 50102)

Front IP40 b bSide IP30 b bConnectors IP20 b b

UA controller. Front IK07 b bCharacteristics of output contacts (dry, volt-free contacts)

Rated thermal current (A) 8Minimum load 10 mA at 12 VOutput contacts:Position of the Auto/Stop switch b bLoad shedding and reconnection order bGenerator set start order. b

AC DCUtilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13Operational current (A) 24 V 8 7 5 5 8 2

48 V 8 7 5 5 2 -110 V 8 6 4 4 0.6 -220/240 V 8 6 4 3 - -250 V - - - - 0.4 -380/415 V 5 - - - - -440 V 4 - - - - -660/690 V - - - - - -

(1) For example, 220 V single-phase or 220 V three-phase.(2) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this voltage is the same as the source voltage, then the “Normal” and “Replacement” sources can be used directly for the power supply. If not, an isolation transformer must be used.

Page 31: Catalogue - ATS Part1

29

Functions and characteristics

Associated controllers 0

Controller installation

PB

1008

57

ACP auxiliaries control plateThe auxiliaries control plate provides in a single unit:b protection for the BA or UA controller with two highly limiting P25M circuit breakers (infinite breaking capacity) for power drawn from the AC sourceb control of circuit-breaker ON and OFF functions via two relay contactorsb connection of the circuit breakers to the BA or UA controller via a built-in terminal block.

Control voltagesb 110 V 50/60 Hzb 220 to 240 V 50/60 Hzb 380 to 415 V 50/60 Hz and 440 V 60 Hz.The same voltage must be used for the ACP plate, the controller and the circuit-breaker operating mechanisms.

InstallationConnection between the ACP auxiliaries control plate and the IVE electrical-interlocking unit may use:b wiring done by the installerb prefabricated wiring (optional).

Installation of the BA and UA controllersThe BA and UA controllers may be installed in one of two manners:b directly mounted on the ACP auxiliaries control plateb mounted on the front panel of the switchboard.The length of the connection between the ACP plate and the controller must not exceed two metres. Wiring is done by the installer.ACP auxiliaries control plate.

DB

1015

79

Mounting on the ACP plate.

DB

1015

80

Mounting on the front panel of the switchboard.

Page 32: Catalogue - ATS Part1

30

Functions and characteristics

Associated controllers 0

BA controller

The BA controller is used to create simple source-changeover systems that switch from one source to another depending on the presence of voltage UN on the “Normal” source.It is generally used to manage two permanent sources and can control Compact NS and Masterpact NT/NW circuit breakers and switch-disconnectors.

Operating modesA four-position switch may be used to select:b automatic operationb forced operation on the “Normal” sourceb forced operation on the “Replacement” sourceb stop (both “Normal” and “Replacement” sources off).

Setting the time delaysTime delays are set on the front of the controller.t1. delay between detection that the “Normal” source has failed and the transmission of the order to open the “Normal” source circuit breaker (adjustable from 0.1 to 30 seconds).t2. delay between detection that the “Normal” source has returned and the transmission of the order to open the “Replacement” source circuit breaker (adjustable from 0.1 to 240 seconds).

Circuit breaker commands and status indicationsThe status of the circuit breakers is indicated on the front of the controller.b ON, OFF, fault.A built-in terminal block may be used to connect the following input/output signals:b inputs:v voluntary order to transfer to source R (e.g. for special tariffs, etc.)v additional control contact (not part of the controller). Transfer to the “Replacement” source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.)b outputs:indication of operation in automatic or stop mode via changeover contacts.

TestIt is possible to test the operation of the BA controller by turning OFF (opening) the P25M circuit breaker for the “Normal” source and thus simulating a failure of voltage UN.

PB

1008

58D

B10

1779

Front of the BA controller.

Page 33: Catalogue - ATS Part1

31

Functions and characteristics

Associated controllers 0

BA controllerOperating sequences

Switch set to Auto (automatic operation and special-tariff mode) Switch set to the “N” position (forced operation on the “Normal” source)

DB

1015

82

DB

1015

84

Switch set to the “R” position (forced operation on the “Replacement” source)

Switch set to the “Stop” position

DB

1015

86

DB

1015

88

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breaker

WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

The number sends to the indicated step when the condition is true.

1

Page 34: Catalogue - ATS Part1

32

Functions and characteristics

Associated controllers 0

UA controller

The UA controller is used to create a source-changeover system integrating the following automatic functions:b transfer from one source to another depending on the presence of voltage UN on the “Normal” sourceb startup of an engine generator setb shedding and reconnection of non-priority circuitsb transfer to the “Replacement” source if one of the phases on the “Normal” source fails.The UA controller can control Compact NS and Masterpact NT/NW devices.

Operating modesA four-position switch may be used to select:b automatic operationb forced operation on the “Normal” sourceb forced operation on the “Replacement” sourceb stop (both “Normal” and “Replacement” sources off, then manual operation).

Setting the time delaysTime delays are set on the front of the controller.t1. delay between detection that the “Normal” source has failed and the transmission of the order to open the “Normal” source circuit breaker (adjustable from 0.1 to 30 seconds).t2. delay between detection that the “Normal” source has returned and the transmission of the order to open the “Replacement” source circuit breaker (adjustable from 0.1 to 240 seconds).t3. delay following opening of QN with load shedding and before closing of QR (adjustable from 0.5 to 30 seconds).t4. delay following opening of QR with load reconnection and before closing of QN (adjustable from 0.5 to 30 seconds).t5. delay for confirmation that UN is present before shutting down the engine generator set (adjustable from 60 to 600 seconds).t6. delay before startup of the engine generator set (120 or 180 seconds).

Commands and indicationsCircuit breaker status indications on the front of the controller:b ON, OFF, fault.A built-in terminal block may be used to connect the following input/output signals:b inputs:v voluntary order to transfer to source R (e.g. for special tariffs, etc.)v additional control contact (not part of the controller). Transfer to the “Replacement” source takes place only if the contact is closed (e.g. used to test the frequency of UR, etc.)b outputs:v control of an engine generator set (ON / OFF)v shedding of non-priority circuitsv indication of operation in automatic mode via changeover contacts.

Distribution-system settingsThree switches are used to:b select the type of “Normal” source, whether single-phase or three-phase (e.g. 240 V single-phase or 240 V three-phase)b select whether to remain (or not) on the “Normal” source if the “Replacement” source is not operational during operation on special tariffsb select the maximum permissible startup time for the engine generator set during operation on special tariffs (120 or 180 seconds).

TestA pushbutton on the front of the controller may be used to test transfer from the “Normal” source to the “Replacement” source, then the return to the “Normal” source. The test lasts approximately three minutes.

COM communications optionUsing the internal bus protocol, this option may be used to remote the following information:b circuit breaker status (ON, OFF, fault trip)b presence of the “Normal” and “Replacement” voltagesb presence of an order for forced operation (e.g. special tariffs)b settings and configuration informationb status of non-priority circuits (loads shed or not)b position of the switch (stop, auto, forced operation on the “Normal” source, forced operation on the “Replacement” source).

PB

1008

58D

B10

1778

Front of the UA controller.

Page 35: Catalogue - ATS Part1

33

Functions and characteristics

Associated controllers 0

UA controllerOperating sequences

Switch set to the “R” position (forced operation on the “Replacement” source) Switch set to the “N” position (forced operation on the “Normal” source)

DB

1015

90

DB

1015

92

Switch set to the “Stop” position

DB

1015

94

WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

When the UA controller is not energised, the output for generator set startup is activated).

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breaker

Page 36: Catalogue - ATS Part1

34

Functions and characteristics

Associated controllers 0

UA controllerOperating sequences

Switch set to the “Auto” position (special-tariff mode)

DB

1015

96 WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

When the UA controller is not energised, the output for generator set startup is activated).

KeyUN : “Normal” source voltageUR : “Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breakerB : Penalties accepted (N ON), i.e. B = 1

The number sends to the indicated step when the condition is true.

1

Page 37: Catalogue - ATS Part1

35

Functions and characteristics

Associated controllers 0

UA controllerOperating sequences

Switch set to the “Auto” position (automatic operation and test mode).

DB

1015

98

WAITING The system exits this mode when the operating mode is modified or when an external event occurs (e.g. failure or return of UN).

When the UA controller is not energised, the output for generator set startup is activated).

KeyUN : “Normal” source voltageUR : "Replacement” source voltageN : “Normal” source circuit breakerR : “Replacement” source circuit breaker B : Penalties accepted (N ON), i.e. B = 1(*) The test lasts 180 seconds.

The number sends to the indicated step when the condition is true.

1

Page 38: Catalogue - ATS Part1

36

Functions and characteristics

Operating sequences 0

IVE unit

DB

1016

00

SymbolsQN : “Normal” Compact C circuit breaker equipped

for remote operation (motor mechanism)QR : “Replacement” Compact C circuit breaker

equipped for remote operation (motormechanism)

ON : Circuit breaker QN opening orderOR : Circuit breaker QR opening orderIN : Circuit breaker QN closing orderIR : Circuit breaker QR closing orderL1 : Faulty “Normal” indication LEDL2 : Faulty “Replacement” indication LED

KeyO: OFF (circuit open)I: ON (circuit closed

: either ON or OFF.

Note: Following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on the front of the motor mechanism is required.

Page 39: Catalogue - ATS Part1

37

Functions and characteristics

Operating sequences 0

BA controller

DB

1016

02

InputsUN : “Normal” source voltageUR : “Replacement” source voltageKT : order for forced-operation on RKR : additional check before transfer

OutputsQN : “Normal” source circuit breakerQR : “Replacement” source circuit breaker

UA controller

DB

1016

04

InputsUN : “Normal” source voltageUR : “Replacement” source voltageKT : order for forced-operation on RKR : additional check before transfer

OutputsKG : order to the gensetSH : load-shedding orderQN : “Normal” source circuit breakerQR : “Replacement” source circuit breaker

KeyO: OFF (circuit open)I: ON (circuit closed

: either ON or OFF.

ImportantIf UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is carried out later when KR status becomes I.

Page 40: Catalogue - ATS Part1

38

Functions and characteristics

COM communications option 0

DB

1019

28

Communications option for Compact NS and Masterpact NT/NWThe COM communications option is compatible with all the source-changeover systems for Compact NS100 to 1600 and Masterpact NT/NW circuit breakers and switch-disconnectors.It can be used to remote status information. It may not be used to operate the circuit breakers (only possible locally on the front of the UA150 controller).Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors are compatible with the Modbus ECO COM option.Depending on the trip units or control units used, the COM option may also be used to analyse distribution-system parameters required for the operating and maintenance assistance.

Circuit breaker communicationSwitch-disconnector

Circuit breaker

Compact NS100/1600 status indicationsON / OFF b bFault trip bConnected / disconnected position b b

Masterpact NT/NW status indicationsON / OFF b bFault trip bConnected / disconnected position b b

Operating and maintenance assistanceSTR53UE trip unit for Compact NS400/630

Current readingsPhase and neutral rms currents b

Current on the most heavily loaded phase bAlarm readingsOverload bTripping cause (overload, short-circuit, etc.) bPositions of setting dials b

Operating and maintenance aids Digipact ModbusMeasurementCurrent A P H A P HVoltages, frequency, power, etc. P H P HPower quality: fundamental, harmonics H

Programming of demand metering P HFault readingsType of fault A P H

Interrupted current P HWaveform captureOn faults H

On demand or programmed HHistories and logsTrip history P H

Alarm history P HEvent logs P HIndicatorsCounter operation A P H A P HContact wear P HMaintenance register P H

Note: see the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators.

Page 41: Catalogue - ATS Part1

39

Functions and characteristics

COM communications option 0

Automatic source-changeover controllerUA150

Status indications“Normal” sourceON / OFF bCircuit breaker ON bFault trip (SDE) bVoltage presence b“Replacement” sourceCircuit breaker ON bFault trip (SDE) bVoltage presence bStatus of R voltage contact bControllerAutomatic mode b“Normal” mode b“Replacement” mode bStop mode bTesting b“Replacement” engine generator setGenset failure bGenset OFF bGenset ON bShedding of non-priority circuits bReconnection of non-priority circuits b

Settings

Time delay t1 for validation of UN absence b

Time delay t2 for validation of UN return bTime delay t3 for wait between opening of N and closing of R bTime delay t4 for wait between opening of R and closing of N bTime delay t5 for wait between return of UN and order for genset shutdown bTime delay t6 for wait before declaring genset failure bPenalties accepted to avoid special tariff transfer b

Page 42: Catalogue - ATS Part1

40

Page 43: Catalogue - ATS Part1

41

Source-changeover systems

Dimensions

Presentation 6Functions and characteristics 11

Source-changeover systems 42Interlocking depending on the type of device 42

Manual source-changeover systems 43Interlocking of direct rotary handles 43Interlocking of extended rotary handles 44Interlocking of toggles 46Complete source-changeover assembly 47Downstream coupling accessory 48

Remote-operated source-changeover systems 50Interlocking on a base plate 50Interlocking using connecting rods 54Interlocking using cables 56IVE electrical-interlocking unitBA and UA automatic controllers 61

Electrical diagrams 63Catalogue numbers and order forms 99

Page 44: Catalogue - ATS Part1

42

Dimensions Source-changeover systems 0

Interlocking depending on the type of device

Page 45: Catalogue - ATS Part1

43

Dimensions Manual source-changeover systems 0

Interlocking of direct rotary handles

Compact NS100 to 1600Dimensions Front-panel cut-out

DB

1016

06

DB

1016

07

DB

1016

08

Dimensions (mm) Type A B C D F G H J K L M N P

NS100/160/250N/H/L 325 90 87.5 175 156 133 9.25 9 295 75.5 150 75 155

NS400/630N/H/L 416 115 100 200 210 157 5 24.6 386 100 175 74.5 179

Interpact INS/INV250 100 to 250 A / Interpact INS/INV320/400/500/630Dimensions Front-panel cut-out

DB

1016

09

DB

1016

10

DB

1016

11

Dimensions (mm) Type A B C D F G H K L M N P

INS/INV250 100/160/250 A 325 90 87.5 175 156 106 17.5 295 75.5 150 75 131

INS/INV320/400/500/630 416 115 100 200 210 130 22.5 386 100 175 74.5 160.4Note: X et Y are the symmetry planes for a 3-pole device.

Page 46: Catalogue - ATS Part1

44

Dimensions Manual source-changeover systems 0

Interlocking of extended rotary handles

Compact NS100 to 630Dimensions Front-panel cut-out

DB

1016

12

DB

1016

07

DB

1016

13

Dimensions (mm) Type A B C D F G min G max H J P Q

NS100/160/250N/H/L 325 90 87.5 175 156 185 600 9.25 9 25.5 25.5

NS400/630N/H/L 416 115 100 200 210 204 600 5 24.6 30.8 30.8

Interpact INS40/63/80/100/125/160 / Interpact INS/INV250 100 to 250 A / Interpact INS/INV320/400/500/630Dimensions Front-panel cut-out

DB

1016

14

DB

1016

15

DB

1016

16

Dimensions (mm) Type A B C D F G min G max H P Q

INS40/63/80 325 90 87.5 175 156 155 396 0 25.5 25.5INS100/125/160 325 90 87.5 175 156 200 441 0 25.5 25.5

INS/INV250 100/160/250 A 325 90 87.5 175 156 185 600 17.5 25.5 25.5INS320/400/500/630 416 115 100 200 210 204 600 22.5 30.8 30.8

Page 47: Catalogue - ATS Part1

45

Dimensions Manual source-changeover systems 0

Interlocking of extended rotary handles

Compact NS630b to 1600Dimensions

DB

1016

17

DB

1016

18

Front-panel cut-out

DB

1016

19

Dimensions (mm) Type A B C D F G min G max H J P Q R

NS630b/800/1000/1200/1600 411 63.5 98 175 280 218 605 25 24 25.5 25.5 64

Page 48: Catalogue - ATS Part1

46

Dimensions Manual source-changeover systems 0

Interlocking of toggles

Compact NS100 to 630Dimensions 3 poles 4 poles

DB

1016

20

DB

1016

21

DB

1016

22

Front-panel cut-out 3 poles on left 4 poles on left

DB

1016

23

DB

1016

24

Dimensions (mm) Type C2 C3 L L16 L17 L18 R2 R18 R19 P5 P

NS100/160/250N/H/L 54 108 52.5 140 245 280 54 89 140 83 115NS400/630N/H/L 92.5 184 70 185 325 370 71.5 116.5 185 107 144

Page 49: Catalogue - ATS Part1

47

Dimensions Manual source-changeover systems 0

Complete source-changeover assembly

Assembly for INS250 100 to 250 A / Assembly for INS320/400/500/630Dimensions

DB

1016

25

DB

1016

26

Front-panel cut-out

DB

1016

27

Dimensions (mm) Type A B C D E F G H I J K L M N

INS250 60.4 130.4 296 68 136 131 61.8 279.3 42 84 156 186.5 5.5 50INS320/630 82.5 175 395 102.5 205 155 87 383.7 64 128 210 213 8 50

Dimensions of the complete source-changeover assembly with an extended handle

DB

1016

50

DB

1016

51

DB

1016

52

Dimensions (mm) Type A B C E K L M N

INS250INV100/250

60.4 130.4 295 136 156 138.5 631 50

INS320/630INV320/630

82.5 175 395 205 210 162.5 658 75

Dimensions (mm) Type P Mmax Mmin Q

INS250INV100/250

100 567.5 195 64

INS320/630INV320/630

150 593 220.5 64

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector. Reference plane Z corresponds to the back of the switch-disconnector.

Page 50: Catalogue - ATS Part1

48

Dimensions Manual source-changeover systems 0

Downstream coupling accessory

Compact NS100 to NS630Dimensions

DB

1016

28

DB

1016

29

Dimensions Connection

DB

1016

30

DB

1016

31

Dimensions (mm) Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16

NS100/160/250 118 181.5 238 96 140 156 35 35 51 156 70 170 8NS400/630 165.9 265.7 339.5 143.5 188.5 227.5 45 52.5 75 210 113.5 250.7 3.75

Dimensions (mm) Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 ØT

NS100/160/250 320 99.5 300 89.5 1 123 139.5 74.5 19.5 87.5 9.5 140 6NS400/630 420 127.5 400 117.5 11.2 187.5 - 96.5 26 115 22.5 210 6

Page 51: Catalogue - ATS Part1

49

Dimensions Manual source-changeover systems 0

Downstream coupling accessory

Interpact INS250 100 to 250 A / Interpact INS320/400/500/630Dimensions

DB

1016

32

DB

1016

33

Dimensions Connection

DB

1019

01

DB

1019

02

Dimensions (mm) Type G2 G3 G28 G29 G30 G52 K1 K2 K3 K4 K8 K9 K16

INS250-100/160/200/250 105.5 169 225.5 83.5 127.5 143.5 35 35 51 156 57.5 157.5 25.5NS320/400/500/630 141 240.7 315 119 163.5 202.5 45 52.5 75 210 88.5 225.7 26.25

Dimensions (mm) Type L28 L29 L30 L31 L32 L33 L34 L35 L36 L37 L39 L40 ØT

INS250-100/160/200/250 320 82 300 72 16.5 123 139.5 74.5 21.5 70 8.5 140 6NS320/400/500/630 420 105 400 95 11.2 187.5 - 98.5 26 92.5 0 210 6

Page 52: Catalogue - ATS Part1

50

Dimensions Remote-operated source-changeover systems 0

Interlocking on a base plate

Compact NS100 to 250Dimensions, 3 or 4 poles Fixed device

DB

1016

34

DB

1016

35

(*) Short terminal shields are mandatory.

Withdrawable deviceD

B10

1636

DimensionsVertical mounting Horizontal mounting

DB

1016

37

DB

1016

38

Dimensions (mm) Type G50 G51 H20 H21 H22 H23 H42 H43 H44 H45 H46 K25 K35 K36

NS100/160/250N/H/L 137.5 285 62.5 97 45.5 73 60 120 144.5 300 37 156 210.5 300NS400/630N/H/L 180 360 100 152 83 123 60 120 189 378 77 210 282.5 400

Dimensions (mm) Type L31 L32 P7 P8 P9 P32 P33 P50 P52 P54 ØT9 ØT10 U

NS100/160/250N/H/L 110.5 354 25 45 75 178 143 25 99.5 21 9 6 y 32NS400/630N/H/L 150.5 466 25 45 100 250 215 25 123 21 9 6 y 32

Page 53: Catalogue - ATS Part1

51

Dimensions Remote-operated source-changeover systems 0

Interlocking on a base plate

Compact NS400 to 630Dimensions, 3 or 4 poles Fixed device

DB

1016

39

DB

1016

40

(*) Short terminal shields are mandatory. Withdrawable device

DB

1016

41

DimensionsVertical mounting Horizontal mounting

DB

1016

37

DB

1016

38

Note: Dimensions see page 50.

Page 54: Catalogue - ATS Part1

52

Dimensions Remote-operated source-changeover systems 0

Interlocking on a base plate

“Normal” and “Replacement” source devices: NS100 to NS250Dimensions Front-panel cut-out

DB

1016

42

DB

1016

48

“Normal” and “Replacement” source devices: NS400 to NS630 Dimensions Front-panel cut-out

DB

1016

44

DB

1016

49

Note for Compact NS:For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.

Page 55: Catalogue - ATS Part1

53

Dimensions Remote-operated source-changeover systems 0

Interlocking on a base plate

NS400 to NS630 as the “Normal” device, NS100 to NS250 as the “Replacement” deviceDimensions Front-panel cut-out

DB

1016

46

DB

1016

53

Page 56: Catalogue - ATS Part1

54

Dimensions Remote-operated source-changeover systems 0

Interlocking using connecting rods

Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices

DB

1016

54

DB

1016

55

Two Masterpact NT devices one above the other Fixed devices Withdrawable devices

DB

1016

56

DB

1016

55

Page 57: Catalogue - ATS Part1

55

Dimensions Remote-operated source-changeover systems 0

Interlocking using connecting rods

Two Masterpact NW devices one above the otherFixed devices Withdrawable devices

DB

1016

57

DB

1016

58

Page 58: Catalogue - ATS Part1

56

Dimensions Remote-operated source-changeover systems 0

Interlocking using cables

Two Compact NS630b to NS1600 devices side-by-sideFixed devices Withdrawable devices

DB

1016

61

DB

1016

62

Two Masterpact NT devices side-by-side Fixed devices Drawout devices

DB

1016

63

DB

1016

62

Two Masterpact NT and NW devices side-by-side Fixed devices Drawout devices

DB

1016

64

DB

1016

65

Page 59: Catalogue - ATS Part1

57

Dimensions Remote-operated source-changeover systems 0

Interlocking using cables

Two Masterpact NW devices side-by-sideFixed devices Drawout devices

DB

1016

66

DB

1016

67

Three Masterpact NW devices side-by-side Fixed devices

DB

1016

68

Drawout devices

DB

1016

69

Page 60: Catalogue - ATS Part1

58

Dimensions Remote-operated source-changeover systems 0

Interlocking using cables

Two Compact NS630b to NS1600 devices one above the otherFixed devices Withdrawable devices

DB

1016

70

DB

1016

71

Two Masterpact NT devices one above the other Fixed devices Drawout devices

DB

1016

72

DB

1016

71

Page 61: Catalogue - ATS Part1

59

Dimensions Remote-operated source-changeover systems 0

Interlocking using cables

Two Masterpact NW devices one above the otherFixed devices Drawout devices

DB

1016

74

DB

1016

75

Two Masterpact NT and NW devices one above the otherFixed devices Drawout devices

DB

1016

73

DB

1016

75

Page 62: Catalogue - ATS Part1

60

Dimensions Remote-operated source-changeover systems 0

Interlocking using cables

Three Masterpact NW devices one above the otherFixed devices Drawout devices

DB

1016

77

DB

1016

76

Page 63: Catalogue - ATS Part1

61

Dimensions Remote-operated source-changeover systems 0

IVE electrical-interlocking unitBA and UA automatic controllers

IVE electrical-interlocking unit

DB

1016

79

DB

1016

78

ACP auxiliaries control plate and BA/UA controller Door cut-out for BA/UA controllers

DB

1016

80

DB

1016

81

DB

1016

82

DB

1016

83

(1) Cut-out according DIN 43700 standard.