Circuit breakers time-current characteristic curve could be shaped to allow adjustment of individual circuit breakers for proper coordination between upstream and downstream protective devices.

Time-Current Characteristics

The basic adjustable functions are:

Continuous Current (Ir)

Page 2: DocumentCB

Continuous Current

This is the magnitude of current that a circuit breaker can carry without tripping. Ir is a percentage of the circuit breaker nominal rating (In).Adjustment of this setting will vary the continuous current from about 20% to 100% of the circuit breaker nominal rating (In).Example:In = 1000AAdjusting the setting to 60% will make the maximum continuous current rating of the circuit breaker to= (60% x 1000) = 600 A

Long Time Delay

Page 3: DocumentCB

Long Time Delay

Long-time delay causes the breaker to wait a certain amount of time to allow temporary inrush currents, such as starting a motor, to flow without tripping.Usually, the time adjustment is on a multiple of the continuous current rating (Ir). A common multiple is 6xIr as most motors draw current six (6) times its full load current during starting. The setting depends on the motor driven load. The unit adjustment for this setting is seconds. The long-time delay effects the position of an I2t slope which means that lower levels of contiuous current setting will allow the circuit breaker to remain online for longer periods of time.

Page 4: DocumentCB

Short Time Pickup

Short Time Pickup

Short-time pickup is used for discrimination or selective tripping. The short-time pickup function determines the amount of current the circuit breaker will carry for a short period of time, allowing downstream protective devices to clear short-circuits without tripping the upstream device.This setting could be adjustable from 1.5 to 10 times the trip unit continuous current setting (Ir). For example, a 1000 ampere frame can be adjusted to trip anywhere from 1500 to 10,000 amps.

Page 5: DocumentCB

If this function is set to “OFF†� position, the short-time pickup and short-time delay will be disabled.

Short Time Delay

Short Time Delay

Short-time delay, used in conjunction with short-time pickup, controls the time duration before a short-time pickup trip.There are two modes:

Fixed timeA fixed instantaneous trip point, trips the breaker automatically and overrides any pre-programmed settings.

I2t rampThe I2t ramp mode is adjustable providing a short inverse

Page 6: DocumentCB

time ramp. This allows better coordination with downstream thermal-magnetic circuit breakers and fuses.

Instantaneous Pickup

Instantaneous Pickup

Instantaneous Pickup is used to trip the circuit breaker with no intentional delay at any current between 2 and 40 times the breaker’s continuous ampere setting (Ir).Example:Continuous Current Setting (Ir) = 60% x In = 600 AInstantaneous pickup = 10 x Ir = 10 x 600 = 6000 AA setting higher than the fixed instantaneous override will automatically trips the breaker at the fixed instantaneous override regardless of the instantaneous pickup setting