Condensing UnitsCBX Series

CBX030 thru CBX3602.5 TR thru 30 TR9 kW thru 105 kW

R-134a

Page 2: CBX series

Company BusinessZamil Air Conditioners was founded in 1974 as one of the first air conditioning business to be established in Saudi Arabiaand today is a leading international manufacturer of air conditioning systems and is No. 1 in the Middle East.

Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55countries in the Middle East, Europe, Africa and Asia.

The company’s operations are structured into four Strategic Business Units (SBUs) supporting five in-house product andservice brands as well as a number of international brands under the OEM sales.

The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.

The four SBUs are:1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.2. Unitary & Applied Business Unit supporting Classic, Cooline, GE and OEM brands for commercial and industrial

customers.3. Zamil CoolCare providing engineering & project management services, HVAC maintenance, retrofit services and parts.4. Geoclima srl is an independent business supporting other SBUs for their requirement of Chillers & Double skin AHU’s.

The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare Service direct their businessoperations from the corporate headquarters at Dammam, Saudi Arabia.

Geoclima has its engineering & production departments located at Monfalcone, Italy and has a design center in Austria.

All the four SBUs, while operating independently, supplement each other’s activities in a way that makes synergy work atits best and achieve the corporate goals of maximizing customer satisfaction.

Factories and ProductionsZamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one speciality production facilityin Italy operated by Geoclima.

The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central AirConditioning systems per year.

Quality & Product CertificatesThe Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification.

Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabia’s Standard Organization)Certificate for Room Air Conditioners. ZAC's products are also certified with:1. CE (Council of European Community)2. UL (Underwriters Laboratory)3. Eurovent4. DEMKO5. ETL

Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammedbin Fahd Al Saud Award for Factory Safety.

Our ProductsIn addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditionersmanufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the Con-cealed Units up to 5 tons, the Ducted Splits up to 30 tons, the Packaged Units up to 90 tons, the Single and Double SkinAir Handling Units up to 70,630 CFM and the Water Chillers up to 660 tons cooling capacity.

Page 3: CBX series

Contents Page

Model decoding ........................................................................................................................................ 2

Unit features & options .......................................................................................................................... 2-3

Physical data ......................................................................................................................................... 4-5

Selection procedure ................................................................................................................................. 6

Performance data .................................................................................................................................. 6-8

Electrical data ...................................................................................................................................... 9-10

Dimensions ....................................................................................................................................... 11-15

Typical schematic wiring diagram...................................................................................................... 16-17

Typical unit installation ........................................................................................................................... 18

Electrical ................................................................................................................................................. 19

System design ........................................................................................................................................ 19

INDEX

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1

Page 4: CBX series

MODEL DECODING1, 2 & 3BASIC

4, 5 & 6NOMINALCOOLINGCAPACITY

(MBH)

8REFRIGERA-TION CIRCUIT

7ELECTRICAL

SUPPLY( V-Ph-Hz )

10CONDENSER

MOTOR

12ACCESSORIES

CBXCONDENSING

UNIT(R-134a)

030

036

042

048

060

075

090

100

120

150

180

220

240

300

360

S : SINGLEH : 208/230-3-60

M : 380-3-60* (4 WIRE)

F : 460-3-60

N : STANDARD

L : LOWAMBIENT

N : STD. UNIT

F : STD. UNIT WITHFILTER DRYER& SIGHT GLASS

P : PDS

S : STD. UNIT WITHPDS, FILTERDRYER &SIGHT GLASS

9MODE

C : COOL ONLY

14MATCHING

11CONDENSER

COIL

A : ALUMINUM FIN

B : COATEDALUMINUMFIN

C : COPPER FIN

13OPTIONS

N :STD. UNIT(MATCHINGWITH BYSERIES)

K :MATCHINGWITH DOUBLESKIN AHU

D : DUAL

UNIT FEATURES & OPTIONSA. GENERALThe Zamil Condensing units are environment friendly units that use refrigerant R-134a and incorporate the latest innovativetechnology to provide quiet, reliable performance. The wrap-around coil not only adds to the aesthetical appeal, it also givesoptimum heat transfer efficiency. The access panels provide access to the compressor, fan motor and to the electricalcontrol box.

These condensing units can be combined with a wide variety of evaporator coils and blower packages to provide quietand dependable comfort. These units can be installed on a roof or at ground level.

B. UNIT ENCLOSUREAll panels are of heavy gauge (G-90) galvanized steel sheet and completely weatherized for outdoor installation. Steelsheet panels are zinc coated and galvanized by the hot dip process of lock-forming quality conforming to ASTM A 653commercial weight G-90, followed by baked on electrostatic polyester dry powder coat.

C. COMPRESSORHermetic scroll compressors are used as standard as shown in the physical data. They are provided with all the standardcontrols necessary for proper and safe operation. These compressors have a self-regulating crankcase heater, improvedinternal pressure relief valve which provides high pressure protection to the refrigerant system and vibration isolators forquiet and efficient operation.

D. AIR COOLED CONDENSER1. The large wrap-around condenser coil is of corrugated fin & tube type, constructed of enhanced copper tubes and

mechanically bonded to aluminum fins. As an option to aluminum fins, coated aluminum fins or corrugated copper finsmay be provided. Tube support sheets are of galvanized steel, formed to provide structural strength. Tubes are cir-cuited to ensure minimum pressure drop and maximum heat transfer. Each coil is completely dehydrated, charged andsealed at the factory upon completion of pressure tests.

2. The fans are propeller type and direct-driven, upward discharge provided with fan grille.

3. Units are equipped with totally enclosed fan motors for greater reliability and dependable performance for many years.Inherent thermal protection is automatic reset type.

N : NO OPTION

U : UVM

V : VOLT FREECONTACTS

C : U & V

* Presently not available for models CBX042, CBX048, CBX090 & CBX100 (under development).

2

Page 5: CBX series

E. SERVICE VALVESBoth suction and liquid service valves are back seating type. Valves are externally located so refrigerant tube connectionscan be made quickly and easily. Each valve has a gauge pressure port for ease of checking refrigerant operating pres-sures.

F. CONTROL PANELThe control panel design is equivalent to NEMA construction for easy access ensuring dust and weather proof construc-tion. Internal power and control wiring is neatly routed, properly anchored and all wires identified with cable markers asper NEC standard applicable to HVAC units. The electrical controls used in the control panel are UL approved, which arereliable in operation at high ambient conditions for a long period.

The electrical circuit has been carefully designed with all necessary protection and circuit elements for safe operation ofthe unit.

G. LOW PRESSURE SWITCHAuto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure falls below10 PSIG. Also provides additional protection against evaporator freeze up due to loss of indoor airflow.

H. HIGH PRESSURE SWITCHAuto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure risesabove 350 PSIG. Also provides additional protection against compressor damage due to loss of outdoor airflow.

I. LOW AMBIENT (OPTIONAL)Low ambient operation down to 450F using fan cycling switch.

J.PUMP DOWN SOLENOID VALVE (AVAILABLE AS OPTION for CBX075 & above)Pump down solenoid valve keeps the evaporator coil dry of liquid refrigerant.

3

Page 6: CBX series

MODEL NUMBER CBX030 CBX036 CBX042 CBX048 CBX060 CBX075 CBX090 CBX100

NUMBER OF REFRIGERATION CIRCUIT Single Single Single Single Single Single Dual Dual

NOMINAL CAPACITY (TONS)* 2.5 3 3.5 4 5 6 7.5 8.5

COMPRESSOR Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Quantity 1 1 1 1 1 1 2 2

Oil (oz) 40 42 62 56 81 106 62x2 56x2

Refrigerant R–134a

Charge per system (oz)+ 98 99 110 155 161 189 134x2 144x2

CONDENSER FAN Type Propeller

Qty. – Diameter (inch) 1 – 18 1 – 18 1 – 24 1 – 24 1 – 24 2 – 24 2 – 24 2 – 24

Nominal CFM 2300 2300 3650 3650 3650 7150 7150 7150

Motor HP – RPM 1/4–1100 1/4–1100 1/3–1100 1/3–1100 1/3–1100 1/3–1075 1/3–1075 1/3–1075

CONDENSER COIL Type Corrugated fin & tube

Tube Dia.- Rows - Fins Per Inch 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16 3/8-2-16

Total face area, Sq. ft. 10 10 16 16 16 21 21 24

HIGH PRESSURE SWITCH Open (PSIG) 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10

Close (PSIG) 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10

LOW PRESSURE SWITCH Open (PSIG) 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5

Close (PSIG) 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5

REFRIGERANT LINES** Suction line size (OD) - inch 3/4 7/8 7/8 7/8 7/8 1-1/8 7/8 (2) 7/8 (2)

Liquid line size (OD) - inch 3/8 3/8 3/8 1/2 1/2 5/8 1/2 (2) 1/2 (2)

SHIPPING WEIGHT Kg. 78 81 106 118 132 222 246 242

PHYSICAL DATA

* Refer to performance data for exact rating values.

** Pipe sizes are for runs up to 25 feet to indoor unit. For refrigerant lines longer than 25 feet, use next larger size.+ Operating system charge is applicable when matched with BY series air handling units & connected by 25 feet of refrigerant piping.

4

Page 7: CBX series

MODEL NUMBER CBX120 CBX150 CBX180 CBX220 CBX240 CBX300 CBX360

NUMBER OF REFRIGERATION CIRCUIT Dual Dual Dual Dual Dual Dual Dual

NOMINAL CAPACITY (TONS)* 10 12 15 18 20 25 30

COMPRESSOR Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Quantity 2 2 2 2 2 2 2

Oil per system (oz) 81x2 106x2 106x2 11 0x2 110x2 110 & 148 148 & 200

Refrigerant R–134a

Charge per system (oz)+ 150x2 152x2 238x2 242x2 349x2 430x2 536x2

CONDENSER FAN Type Propeller

Qty. – Diameter (inch) 2 – 24 2 – 26 2 – 26 2 – 26 2 – 30 2 – 30 3 – 30

Nominal CFM 7150 10000 12500 12500 15200 15000 22800

Motor HP – RPM 1/3 – 1075 1/3 – 850 3/4 – 1140 3/4 – 1140 1.5 – 1140 1.5 – 1140 1.5 – 1140

CONDENSER COIL Type Corrugated fin & tube

Tube Dia.– Rows – Fins per inch 3/8–2–16 3/8–2–16 3/8–2–16 3/8–2–16 3/8–4–14 3/8–5–14 3/8–4–14

Total face area, Sq. ft. 24 38 38 38 28 28 47

HIGH PRESSURE SWITCH Open (PSIG) 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10 350 ± 10

Close (PSIG) 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10 300 ± 10

LOW PRESSURE SWITCH Open (PSIG) 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5 10 ± 5

Close (PSIG) 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5 30 ± 5

REFRIGERANT LINES** Suction line size (OD), inch 7/8 (2) 7/8 (2) 1-3/8 (2) 1-3/8 (2) 1-3/8 (2) 1-3/8 (2) 1-5/8 (2)

Liquid line size (OD), inch 1/2 (2) 1/2 (2) 5/8 (2) 5/8 (2) 5/8 (2) 5/8 (2) 7/8 (2)

SHIPPING WEIGHT Kg. 282 460 544 605 762 924 1010

PHYSICAL DATA

* Refer to performance data for exact rating values.

** Pipe sizes are for runs up to 50 feet to indoor unit. For refrigerant lines longer than 50 feet, use next larger size.+ Operating system charge is applicable when matched with BY series air handling units & connected by 25 feet of refrigerant piping.

5

Page 8: CBX series

ALTITUDE (FEET) 2000 4000 6000 8000 10000

Condensing Unit Cooling Capacity .99 .98 .96 .95 .94

Condensing Unit & Evaporator .98 .96 .93 .90 .88FACTOR

SELECTION PROCEDURE1. Enter performance tables at specified SST and desired ambient conditions.

2. HEAT REJECTION:Calculate condenser Total Heat Rejection Capacity as follows:HR = Unit cooling capacity + (3.41 x Total Unit Power Input, Watts).

3. HEAD PRESSURE:To determine head pressure (psig) use the following conversion table:

LEGEND: SST - Saturated Suction Temperature; TC - Total Capacity (1000 Btuh) Gross; CT - Condensing Temperature (0F); kW - Total unit power input

Condensing Temp. - 0F. 100 110 120 130 140 150 160

(R-134a) Head Pressure - PSIG. 124.1 146.4 171.1 198.7 229.2 262.8 299.9

MODEL No.: CBX030

MODEL No.: CBX042

MODEL No.: CBX036

MODEL No.: CBX048

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

75 85 95 105 115 12528.8 26.3 23.6 21.1 18.6 16.297 106 117 126 134 1412.5 2.56 2.68 2.75 2.82 2.932.2 29.8 27.1 24.4 21.6 1999 110 120 128 136 143

2.55 2.72 2.81 2.9 3 3.137.1 33.4 30.4 27.3 24.5 21.6102 114 123 131 140 1462.7 2.87 3 3.1 3.24 3.3540.1 37.1 33.7 30.6 27.3 24.2106 116 125 134 141 1482.82 2.97 3.13 3.26 3.4 3.5744.1 40.5 37.3 33.8 30.4 27.1108 119 127 136 144 1502.94 3.13 3.3 3.45 3.66 3.848 44.1 40.4 37.2 33.1 29.4112 120 130 138 146 1523.14 3.31 3.51 3.73 3.93 4.1

SST(0F)

AMBIENT TEMPERATURE - 0F

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 12536.5 33.7 30.6 28.1 25.5 22.4102 111 121 129 138 1443.5 3.61 3.79 3.92 4.09 4.240.8 37.7 34.2 31.2 28 25.2105 115 124 132 141 1493.68 3.81 3.9 4.1 4.3 4.544.9 41.8 38.2 35.1 31.6 28.5111 118 128 136 145 1523.9 4.1 4.3 4.48 4.65 4.949.5 45.9 42.3 38.7 35.2 31.6114 121 130 138 146 1544.1 4.3 4.5 4.7 4.95 5.1554.1 50 45.4 41.6 38 34.2117 125 133 141 149 1554.37 4.55 4.72 4.95 5.2 5.458.7 54.6 50.6 46.2 42 38.3118 126 135 142 151 1574.55 4.82 5.12 5.34 5.55 5.9

75 85 95 105 115 12539.3 36.4 32.9 29.8 27.3 23.598 106 113 121 131 1403.4 3.51 3.68 3.77 4.1 4.1444.3 41.1 37.2 33.7 30.2 26.9100 108 117 126 134 1423.55 3.7 3.86 3.98 4.14 4.349.1 45.9 41.8 38.1 34.3 30.6103 111 121 129 137 1443.73 3.9 4.1 4.27 4.42 4.5154.2 50.5 46.4 42.3 38.3 34.4105 114 122 129 139 1474.04 4.15 4.31 4.51 4.69 4.8859.4 55.4 51 46.5 42.4 38107 116 124 131 140 1494.17 4.39 4.55 4.71 5 5.264.5 60.2 55.4 50.9 46.3 41.8109 118 126 133 142 1504.38 4.63 4.84 5.1 5.3 5.55

75 85 95 105 115 12543.9 40.6 36.7 33.2 30.7 2697 106 114 121 131 140

3.86 3.92 4 4.09 4.2 4.349.8 46 41.7 37.8 33.7 30.1101 109 118 126 135 1423.95 4.1 4.25 4.4 4.5 4.755.3 51.6 47 42.6 38.5 34.2103 111 120 128 137 1454.15 4.3 4.5 4.65 4.8 561 56.6 52 47.5 42.8 38.9

105 114 123 131 139 1484.29 4.55 4.74 4.95 5.1 5.366.3 62.2 57.1 52 47.6 43.2108 116 125 134 142 1504.48 4.65 5 5.1 5.42 5.671.9 67.3 61.7 57.2 52 46.9110 118 127 136 145 1524.65 4.9 5.25 5.48 5.76 6.1

PERFORMANCE DATA

4. CORRECTION FACTORS FOR ALTITUDE:

6

Page 9: CBX series

PERFORMANCE DATAMODEL No.: CBX060

MODEL No.: CBX090

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 12553.5 50 46 43 38.7 35100 107 117 124 133 1424.62 4.72 4.9 4.98 5.12 5.3859.2 55.4 51.6 47.1 43.2 39101 109 118 126 135 1454.65 4.81 5.0 5.2 5.45 5.6765.4 61 57 52.4 48.1 43.9104 112 120 129 138 1484.79 5.12 5.25 5.55 5.7 671.2 67 61.8 57.4 53 48.2107 115 123 132 141 1504.98 5.3 5.55 5.7 6.0 6.477 72 67.2 62.6 57.5 53109 118 127 135 144 1525.2 5.5 5.85 6.2 6.5 6.983 77.1 72.6 67.8 62.2 57.4112 120 128 137 145 1545.45 5.8 6.2 6.5 7.0 7.25

75 85 95 105 115 12583.8 76.6 71.1 64.4 57.2 51.598 107 116 125 133 1426.8 7.2 7.42 7.77 7.98 8.3593.3 86.8 81 73.5 68 58.4102 110 118 127 136 1447.18 7.66 7.91 8.24 8.57 8.95103.1 95.7 88.6 81.4 74 66.8104 113 121 130 138 1467.5 7.84 8.3 8.65 8.98 9.3113 105.5 98 90.4 83.6 75107 115 124 132 140 1487.8 8.16 8.72 9.15 9.42 9.91124 116.4 107 100 92.6 83.5109 118 127 134 143 1508.29 8.76 9.22 9.68 10.1 10.47133.9 125.1 115.6 107.9 99 91.2111 120 129 136 145 1528.65 9.26 9.8 10.12 10.67 11.0

MODEL No.: CBX120

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

75 85 95 105 115 125103.4 95.2 89 82 73.6 68103 112 118 125 137 1459.79 10.15 10.55 10.78 11.5 11.85113.4 106.5 99 92 83.4 77106 115 120 128 139 148

10.18 10.61 11.05 11.6 12.1 12.48125 117.6 110 101.8 93 82.6109 118 123 131 142 15110.6 11.15 11.8 12.22 12.69 13.2137 129 120.4 112 101.6 94.3111 120 125 134 145 15211.2 11.7 12.4 12.9 13.65 14.26149 141 129.8 122 112.5 102.6113 122 127 136 148 15411.5 12.25 13.3 13.7 14.5 15.2159 148 138.5 130 119 110115 124 130 139 149 15612.2 12.8 13.71 14.5 15.22 16.0

SST(0F)

AMBIENT TEMPERATURE - 0F

MODEL No.: CBX075

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 12564 60 56.1 52.3 48 4595 104 113 121 130 139

5.95 6.2 6.3 6.7 7.2 7.472 67 64 59 56 5297 106 115 123 133 141

6.16 6.48 6.8 7.2 7.6 7.978.4 75 70 66 62 58100 109 118 126 135 1436.5 6.82 7.14 7.6 8.1 8.2586.1 82.3 77.1 71.9 68.4 63.7102 111 120 129 138 1456.7 6.95 7.6 7.9 8.3 8.6594 88.5 83.3 79.1 73.1 70.4104 113 122 131 140 1486.95 7.3 7.72 8.25 8.6 9.23101.2 95.8 90.7 85.2 80.1 76.8106 115 124 133 141 1507.22 7.61 8.05 8.39 8.64 9.4

MODEL No.: CBX100

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 12590.3 82.4 75.6 67.3 60.2 52.799 108 114 124 132 142

8.35 8.51 8.7 8.88 9.12 9.28101 92.5 84 77.3 69.4 61102 110 116 126 135 1448.62 8.95 9.2 9.45 9.68 9.97113 104 95 86.1 78.2 69.9105 113 119 129 138 1478.92 9.27 9.66 10.05 10.4 10.75124 114 105 97 87.6 78.1108 116 122 131 141 1499.4 9.85 10.1 10.65 11.1 11.5135 125 115 106 96.8 86.9110 119 125 134 143 1519.85 10.4 10.9 11.4 11.9 12.3145 135 125 115 105 95112 122 127 136 146 15310.3 10.85 11.5 12.1 12.6 13.0

MODEL No.: CBX150

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

75 85 95 105 115 125124 117 110 102 94 8796 105 114 124 134 141

11.71 12.45 13.12 13.85 14.72 15.46138 130 122 113 104 9799 106 116 126 136 143

12.25 12.9 13.72 14.63 15.4 16.1152 144 134 125 115 106101 109 119 129 139 146

12.74 13.6 14.4 15.65 16.1 16.9166 157.4 148 136 128 117102 111 121 130 141 14813.1 14 14.9 15.8 16.7 17.6178 171.5 160 148.7 138 127104 113 123 132 142 14913.6 14.5 15.4 16.5 17.6 18.5196 184 172 161 148 136105 115 124 134 143 15114.2 15.3 16.2 17.2 18.15 19.0

SST(0F)

AMBIENT TEMPERATURE - 0F

LEGEND: SST - Saturated Suction Temperature; TC - Total Capacity (1000 Btuh) Gross; CT - Condensing Temperature (0F); kW - Total unit power input

7

Page 10: CBX series

PERFORMANCE DATAMODEL No.: CBX180

MODEL No.: CBX240

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 125161 152 143.5 136 127.8 12098 105 115 125 135 144

12.8 13.1 13.4 13.8 14.2 14.5176 168 159 151 143 135100 108 118 127 136 14714.1 14.7 15.1 15.5 15.9 16.2194 184 173 165 155 146101 111 120 130 138 14816 16.2 16.6 16.9 17.3 17.7211 201 191 174 172 161103 112 121 131 140 14917.6 17.9 18.3 18.7 18.9 19.1231 220 208 197 186 175105 114 123 132 141 15119.2 19.6 19.9 20.1 20.3 20.65245 235 222 211 199 188106 116 126 134 144 15220.9 21.2 21.6 21.9 22.1 212.5

75 85 95 105 115 125225 214 201 191 180 16698 108 116 126 137 146

18.2 19.9 22.1 23.7 26.3 28.2246 234 221 210 198 184101 109 118 127 138 14718.6 20.2 22.4 24.5 26.6 28.6268 255 242 228 216 202102 111 121 130 140 14919 20.7 23.1 24.8 27 29

290 276 262 249 235 220105 113 123 131 141 15019.4 21.1 23.5 25.1 27.2 29.4311 297 283 268 253 239106 116 125 134 144 15219.7 21.9 24 25.5 27.6 29.6333 318 303 287 272 257108 118 127 136 146 15320 22.2 24.5 26.2 28 29.7

MODEL No.: CBX360

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

75 85 95 105 115 125324 308 291 276 259 24397 107 116 125 136 145

26.76 30.3 33.2 36 39.7 42.8358 341 322 306 288 270100 109 118 127 137 14727.4 30.7 33.7 37.1 40.6 44392 374 354 336 316 297102 111 120 129 139 14828.7 31.6 34.8 37.6 41.1 44.5427 406 385 366 344 323104 112 122 131 140 15029.4 32.1 35.5 38.9 42 45.2461 438 417 395 373 350105 114 124 133 142 15229.6 32.8 36.1 39.4 42.7 45.8495 471 448 425 401 378107 116 125 135 144 15430.5 33.4 36.9 39.9 43.3 46.5

SST(0F)

AMBIENT TEMPERATURE - 0F

MODEL No.: CBX220

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 125187 179 168 159 148 13899 109 118 128 138 149

14.9 17 19.2 21.3 23.5 25.5205 195 184.5 174 163 154102 112 121 131 141 15015.7 17.9 17.8 21.8 23.9 25.7224.5 213 201 190 179 167105 114 124 134 142 15116.5 18.3 20.3 22.6 24.3 26.3241 229 219.5 207 194 184108 118 126 136 144 15317.1 19.2 20.9 23.2 24.7 26.8261 248 237 221 211 197110 120 129 139 146 15517.4 19.7 21.4 23.7 25.1 27.1278 267 254 239 227 212113 122 129 140 147 15617.9 20.2 21.6 24 25.9 27.4

MODEL No.: CBX300

TC30 CT

kWTC

35 CTkWTC

40 CTkWTC

45 CTkWTC

50 CTkWTC

55 CTkW

SST(0F)

AMBIENT TEMPERATURE - 0F

75 85 95 105 115 125282 268 254 240 225 21299 111 121 132 142 152

24.4 27.4 29.9 32.8 35.6 38.2310 295 281 265 250 236102 113 122 134 144 15425.2 28.1 30.6 33.7 36.3 38.9338 321 305 291 274 258104 115 125 136 146 15526.1 28.8 31.3 34.4 37 39.4365 348 332 314 298 281106 117 127 138 148 15626.6 29.4 32.1 35 37.5 40.1392 375 357 339 321 303108 118 130 140 150 15827.4 29.9 33 35.4 38 40.6420 401 383 364 345 326110 120 131 141 152 15928.1 30.7 33.6 35.9 38.8 41.3

LEGEND:

SST - Saturated Suction Temperature

TC - Total Capacity (1000 Btuh) Gross

CT - Condensing Temperature (0F)

kW - Total unit power input

8

Page 11: CBX series

ELECTRICAL DATA

MCA MOCPCOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX036

380-3-60(4 WIRE)

Single compressor units

MIN. MAX. RLA LRA

208/230-3-60 187 253 16 97 1.4 21.4 35

342 418 8.5 52 1.4 12 20

460-3-60 414 506 8.2 50 0.7 10.9 15

MODEL No.: CBX060

MODEL No.: CBX090

MOCP

MIN. MAX. RLA LRA

208/230-3-60 187 253 20.7 128 2.3 28.3 45

460-3-60 414 506 10 63 1.3 13.8 20

MOCP

MIN. MAX. RLA LRA

208/230-3-60 187 253 33.6 231 2.3 46.6 80

342 418 18.6 140 2.3 27.9 45

460-3-60 414 506 17.3 114 1.3 24.2 40

MCACOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX042

MCACOMPRESSORVOLTAGE

RANGEPOWERSUPPLY(V-Ph-Hz)

MODEL No.: CBX075

380-3-60(4 WIRE)

MODEL No.: CBX100

MCA MOCPCOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX030

380-3-60(4 WIRE)

MIN. MAX. RLA LRA

208/230-3-60 187 253 13.1 80 1.4 17.8 30

342 418 6.0 44 1.4 8.9 15

460-3-60 414 506 5.9 42 0.7 8.1 15

NOTE: Refer to page 10 for legend & notes.

MODEL No.: CBX048

*FAN

MOTORFLA

(each)

Dual compressor units

MOCP

MIN. MAX. RLA LRA

208/230-3-60 187 253 32.1 203 2.3 42.4 60

342 418 16.7 123 2.3 23.2 35

460-3-60 414 506 16.4 95 1.3 21.8 35

MCACOMPRESSORVOLTAGE

RANGEPOWERSUPPLY(V-Ph-Hz)

380-3-60(4 WIRE)

*FAN

MOTORFLA

(each)

MOCP

MIN. MAX. RLA LRA

208/230-3-60 187 253 20.7 156 2.3 28.2 45

460-3-60 414 506 10 75 1.3 13.8 20

MCACOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MOCP

MIN. MAX. RLA LRA

208/230-3-60 187 253 20.7 128 2.3 51.2 70

460-3-60 414 506 10 63 1.3 25.1 35

MCACOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MOCP

MIN. MAX. RLA LRA

208/230-3-60 187 253 20.7 156 2.3 51.2 70

460-3-60 414 506 10 75 1.3 25.1 35

MCACOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

9

Page 12: CBX series

MCA MOCPCOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX120

380-3-60(4 WIRE)

MIN. MAX. RLA LRA

208/230-3-60 187 253 32.1 203 2.3 76.9 100

342 418 16.7 123 2.3 42.2 50

460-3-60 414 506 16.4 95 1.3 39.5 50

ELECTRICAL DATA Dual compressor units

MIN. MAX. RLA LRA

208/230-3-60 187 253 33.6/42 231/239 2.5 91.1 125

342 418 18.6/23.5 140/145 2.5 52.9 70

460-3-60 414 506 17.3/19.2 114/125 1.3 73.9 60

MCA MOCPCOMPRESSOR *

FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX150

380-3-60(4 WIRE)

(each)(each)

MIN. MAX. RLA LRA

208/230-3-60 187 253 47.1 273 3.7 113.4 150

342 418 24.4 145 1.7 58.3 80

460-3-60 414 506 19.6 125 1.8 47.7 60

MCA MOCP

COMPRESSOR FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX180

380-3-60(4 WIRE)

(each)

(each)MIN. MAX. RLA LRA

208/230-3-60 187 253 30 195 3.7 74.9 100

342 418 27.2 167 1.7 64.6 90

460-3-60 414 506 19.3 125 1.8 47 60

MCA MOCP

COMPRESSOR FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX220

380-3-60(4 WIRE)

(each)

(each)

MCA MOCPCOMPRESSOR FAN

MOTORFLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX240

380-3-60(4 WIRE)

MIN. MAX. RLA LRA

208/230-3-60 187 253 37.1 239 5 93.5 125

342 418 32.1 198 2.7 77.6 100

460-3-60 414 506 25.7 148 2.5 62.8 80

MCA MOCP

COMPRESSOR FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX300

380-3-60(4 WIRE)

MIN. MAX. RLA LRA

208/230-3-60 187 253 37.1/81.4 239/505 5 148.9 225

342 418 32.1/42.1 198/280 2.7 90.1 125

460-3-60 414 506 25.7/37.9 148/225 2.5 78.1 110

(each)

(each)(each)

(each)

MCA MOCP

COMPRESSOR FANMOTOR

FLA

VOLTAGERANGEPOWER

SUPPLY(V-Ph-Hz)

MODEL No.: CBX360

380-3-60(4 WIRE)

MIN. MAX. RLA LRA

208/230-3-60 187 253 81.4/87.9 505/500 5 206.3 250

342 418 62.1/61.4 280/305 2.7 147.1 200

460-3-60 414 506 37.9/48.6 225/250 2.5 106.2 150

(each)

(each)

* Single phase motors (208/230V-1Ph-60Hz for 208/230V-3Ph-60Hz & 380V-3Ph-60Hz power supply. 460V-1Ph-60Hz for 460V-3Ph-60Hz power supply).

LEGEND:

FLA – Full Load Amps

LRA – Locked Rotor Amps

RLA – Rated Load Amps

MOCP – Maximum Over Current Protection

MCA – Minimum Circuit Amps

NOTE:If other than 900C copper wire is used, size can be determined from unit ampacity given in above table and applicable table of NEC.Wire size selected must have current capacity not less than that of copper wire specified and voltage drop should not exceed 2% ofrated voltage. Must use copper wire from disconnect switch to the unit.

10

Page 13: CBX series

DIMENSIONSCBX030 - CBX060

MODEL NUMBER A B C D E F G H

CBX030 - CBX036 711 610 708 596 440 175 86 57

CBX042 - CBX060 889 813 806 695 538 216 99 72

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2.Allow 32" (812mm) clearance to service end of the

unit, 12" (305mm) on remaining sides and 24"(610mm) between units for proper airflow.

11

Page 14: CBX series

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units for

proper airflow.

DIMENSIONSCBX075 - CBX120

12

Page 15: CBX series

DIMENSIONSCBX150 - CBX220

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

13

Page 16: CBX series

DIMENSIONSCBX240 - CBX300

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

14

Page 17: CBX series

943[37.13"]

943[37.13"]

2032[80.0"]

73 [2.88"]

2197[86.50"]

2121[83.50"]

1550

[61.

0"]

203

[8.0

"]DIMENSIONS

CBX360

NOTES:1. All dimensions are in mm, (dimensions in brackets are in inches).2. Allow 48" (1219 mm) clearance on all sides for proper airflow.

15

Page 18: CBX series

USE FOR OPTION-3B ONLY

UNITS 24V CIRCUITTO BY & FMX *

5

4

3

41A

22ALPS [AI]

SEE NOTE 6

*25A 26AJP12 CC

ATB1

2

11615 CB

TRANS

L1

[UVM] [SD] JP11JP124 VAC

1

L2

JP21A

17

1B 17

SEE HPS OPTION BELOW

HPS

NAME

LPS

SET POINTS

300 ± 10

CLOSE (PSIG)

30 ± 5

OPEN (PSIG)

350 ± 1010 ± 5

CRANKCASE HTR CONNECTION

LUG

36B

FM2

35A

COMP

T2A

T1A

CAP1

T3A

FM1

37A36A

CAP235B

CC

37B

COMP L1 C.HTR

HVTB

L2

L3

L1

L2

OF A.H.U ACCORDINGLY.

NOTE: ATB# 1,4 & 5 OF COND. UNIT TO BE CONNECTED TO ATB# 1,4 & 5

CONTROL & INTERCONN. DETAILS FOR FMX AHU W/O SYSTEMIZER

FCS 125 ± 10 225 ± 15

B. COMP ON/OFF & TRIP & [UNIT] TRIP INDICATION OPTION

1. UVM OPTION

A. UNIT ON & OFF INDICATION

3. VOLT FREE CONTACT OPTIONS

OPTIONS4. HPS OPTION

TOLPS

23A 25AHPS

FOR BY & FMX UNITS

AR1

46

UNIT ON

45 AR1-1

ATB115

UNIT OFF

AR1-1 47

ATB217

CC

A-2

B

COMP-TRIPCOMP-OFF

COMP-ON

55 56 57 58

FR-2

CC

A-2A

FR-2

54

UNIT/COMP-TRIP

43 FR-15 41AATB1

FR44

ATB217

2. SMOKE DETECTOR OPTION

1B

ATB2

1A

ATB2

REMOVE JP2

VFC-FROM CUSTOMER'SSMOKE DETECTOR

L3

UVM

L2L1

TO ATBTO ATB

(REMOVE JP1)

L3L2L1

LEGEND

AHU AIR HANDLING UNITAI ANTI ICE THERMOSTATAR AUXILIARY RELAYATB AUXILIARY TERMINAL BLOCKCAP CAPACITORCC COMPRESSOR CONTACTORCB CIRCUIT BREAKERC. HTR CRANKCASE HEATERCOMP COMPRESSORFM FAN MOTOR (CONDENSER)FMC FAN MOTOR CONTACTORFR FAULT RELAYHPS HIGH PRESSURE SWITCHHVTB HIGH VOLTAGE TERMINAL BLOCKJP JUMPERL1 LINE 1L2 LINE 2L3 LINE 3LPS LOW PRESSURE SWITCHLUG LUG GROUNDN NEUTRALNTB NEUTRAL TERMINAL BLOCKSD SMOKE DETECTORTRANS TRANSFORMERT'STAT THERMOSTATUVM UNDER VOLTAGE MONITORVFC VOLT FREE CONTACT

FIELD WIRINGDISCONNECT TAB - 1/4"SPLICE-CLOSED END

TYPICAL SCHEMATIC WIRING DIAGRAM

_ _ _+

N (SEE NOTE -7)

REFER TO UNITNAMEPLATE FORPOWER SUPPLY

NOTES1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.

2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.

3. POWER MUST BE SUPPLIED TO CRANKCASEHEATER FOR MINIMUM OF 12 HOURS PRIOR TOSYSTEM START UP.

IF POWER IS OFF 6 HOURS OR MORE, CRANKCASEHEATER MUST BE ON FOR 12 HOURS BEFOREOPERATING THE SYSTEM.

FAILURE TO FOLLOW THESE INSTRUCTIONS MAYRESULT IN COMPRESSOR DAMAGE.

4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKERTO BE PROVIDED BY END USER WITH RATING ASRECOMMENDED BY ZAMIL.

5. * ATB 3 IS APPLICABLE FOR PDS OPTION UNITSONLY.

6. REMOVE JUMPER FOR AI OPTION. ROUTE AIWIRES FROM AHU.

7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60HzPOWER SUPPLY ONLY.

Single compressor units - Cool only

16

Page 19: CBX series

TO CC2T2B

35B

T1A

FCS1

TO CC1AMBIENT OPTION- 460VAC UNITS ONLYCONNECTION APPLICABLE FOR LOW -

AMBIENT OPTION 230VAC UNITS ONLYCONNECTION APPLICABLE FOR LOW

[SD]

5AHU

22B

7

8

6

USE FOR OPTION-3-B ONLY

LPS2

41A

41B

JP5

[AI2]25B 26B

22A

TO

1

3

4

2

ATB

15

HVTB

LUG

L2

L3

L1

CRANKCASE HTR CONNECTION

SEE HPS OPTION BELOW

SEE HPS OPTION BELOW

LPS1

CB 16

24VAC

TRANSL1

36A

T3A

T2A

T1A

35A

COMP2

COMP1

L2

L1

T1B

37A

T2B

T3B

JP1

[UVM]

SEE NOTE-7

[AI1]25A

L2

JP2

26A

1A

C.HTR1

C.HTR2

37B

35B

36B

35A

L3

L2

15

CAP1

36A

CC1

TO CC1

39A

FM1

36ACC2

35A

CAP1

T1A

36B

LS37

AH

S38

A

CAP2

FCS1

T2A

C2-CONTACTORCC2

TO CC2

C1-CONTACTORCC1

1B JP11 17

FCS

C2

17FCSC1

FCSC213A

12A

FM1

HS

LS38

A37

A

T2A

FCS

C1

39A

FCS215

13B

FM2

12B

T2B

37B

LS38

B

T3B

FCSC4

FCSC317

FCS

C4

39B

FCSC

3H

S

CAP2

35B

36B

1PH FAN MOTOR ONLYCONNECTION APPLICABLE FOR

36A

CAP1

35A

HS

38B

FM2

LS37

B

FCS2

T3B

39B

37A

FM1

36A

TO CC1T2AT1A

37B

FM2

36B

TO CC2T3BT2B

3. VOLT FREE CONTACT OPTIONS

ATB(7)

C1-OFFC1-ON

B. COMP ON, OFF & TRIP [&] UNIT TRIP INDICATION OPTION

2. SMOKE DETECTOR OPTION

VFC-FROM CUSTOMER'S

REMOVE JP2

SMOKE DETECTOR

1A 1B

1. UVM OPTION

A. UNIT ON & OFF INDICATION

UNIT ON

AR1-145

15 AR1 41A

UNIT OFF

AR1-146

55

47

17

OPTIONS

TOLPS2

LPS1TO

C2-ON

C1-TRIP C2-TRIP

C2-OFF

41B

FR2-1

ATB(8)

UNIT-TRIP

17

FR1-2

CC

1A-2

A

56

FR1-2

CC

1A-2

B

57

54

FR1

43

58 60

FR1-1 44A

COMP1

59

62

FR2-2

61

FR2-2

CC

2A-2

A

CC

2A-2

B

44

FR2

63

COMP2

23B HPS2 25B

23A

4. HPS OPTION

HPS1 25A

(REMOVE JP1)

TO ATBTO ATB

L1 L2 L3

UVM

LEGEND

AHU AIR HANDLING UNITAI ANTI ICE THERMOSTATAR AUXILIARY RELAYATB AUXILIARY TERMINAL BLOCKCAP CAPACITORCC COMPRESSOR CONTACTORCB CIRCUIT BREAKERC. HTR CRANKCASE HEATERCOMP COMPRESSORFM FAN MOTOR (CONDENSER)FMC FAN MOTOR CONTACTORFR FAULT RELAYHPS HIGH PRESSURE SWITCHHVTB HIGH VOLTAGE TERMINAL BLOCKJP JUMPERL1 LINE 1L2 LINE 2L3 LINE 3LPS LOW PRESSURE SWITCHLUG LUG GROUNDN NEUTRALNTB NEUTRAL TERMINAL BLOCKRR RESET RELAYSD SMOKE DETECTORTRANS TRANSFORMERT'STAT THERMOSTATUVM UNDER VOLTAGE MONITORVFC VOLT FREE CONTACT

FIELD WIRINGDISCONNECT TAB - 1/4"SPLICE-CLOSED END

TYPICAL SCHEMATIC WIRING DIAGRAM

_ _ _+

N (SEE NOTE -8)

REFER TO UNITNAMEPLATE FORPOWER SUPPLY

NOTES1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.

2. ANY WIRE REPLACEMENT SHOULD BE OF THE 900COR ITS EQUIVALENT.USE COPPER CONDUCTOR WIRES ONLY.

3. POWER MUST BE SUPPLIED TO CRANKCASEHEATER FOR MINIMUM OF 12 HOURS PRIOR TOSYSTEM START UP.

IF POWER IS OFF 6 HOURS OR MORE, CRANKCASEHEATER MUST BE ON FOR 12 HOURS BEFOREOPERATING THE SYSTEM.

FAILURE TO FOLLOW THESE INSTRUCTIONS MAYRESULT IN COMPRESSOR DAMAGE.

4. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKERTO BE PROVIDED BY END USER WITH RATING ASRECOMMENDED BY ZAMIL.

5. * ATB 3 & 5 IS APPLICABLE FOR PDS OPTION UNITSONLY.

6. USE DISCONNECT TAB OR SPLICE ONLY WHEREEVER REQUIRED FOR EXTENSION OF ORIGINALWIRE.

7. REMOVE JUMPER FOR AI OPTION. ROUTE AIWIRES FROM AHU.

8. NEUTRAL LINE REQUIRED ON 380V-3Ph-60HzPOWER SUPPLY ONLY.

Dual compressor units - Cool only

17

Page 20: CBX series

INSTALLATION & START-UP INSTRUCTIONSSAFETY CONSIDERATIONSImproper installation, service, maintenance or use can cause explosion, fire, electrical shock or other conditions whichmay cause personal injury or property damage. Check with your nearest Zamil dealer/sales office for information orassistance.

WarningBefore installation or servicing the system, always turn off main power supply. Electrical shock can cause personal injuryor death.

INSTALLATIONSTEP-1:Check equipment and job siteUnpack unit and move to final location taking care not to damage the unit. Remove screws holding the unit to woodenpallet and after removing wooden pallet, refix the screws.

STEP- 2:Installation on a solid, level mounting padFor proper drainage, the condensing unit must be raised off the mounting pad. If conditions require the unit be attached tothe pad, tie down bolts should be used.

When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping and service. Double the serviceaccess when multiple units are installed at one location.

On rooftop applications, locate unit at least 6" (152 mm) above roof surface. Place unit above a load-bearing wall, isolateunit and piping set from structure.Arrange supporting members to adequately support unit and minimize transmission of vibration to building.

STEP-3:Piping connectionsOutdoor units should be connected to indoor units using field-supplied piping of refrigerant grade and correct size. Theliquid and suction line diameters can be determined from the physical data table. For piping requirements beyond 25 ft(7.62m), obtain information from your nearest Zamil dealer/sales office.If either refrigerant piping or indoor coil is exposed to atmospheric conditions, it must be dehydrated to 500 microns toeliminate moisture contamination in the system.It is advisable to size piping according to recommended ASHRAE methods. Install piping according to refrigerationstandard practice. Run refrigerant pipes as directly as possible, avoiding unnecessary turns and bends. Install refrigerantpipes carefully to prevent damaging the suction pipe insulation and vibration transmission to the structure.

Outdoor unit connected to factory matched indoor unitOutdoor unit contains correct system refrigerant charge for operation with matched indoor unit as given on cooling capac-ity table and when connected with up to 25 ft (7.62 m) of field-supplied piping. Check refrigerant charge for maximumefficiency.

Sweat connectionUse refrigerant grade piping. Service valves are closed from factory when shipped and ready for brazing. After wrappingthe service valve with a wet cloth, the piping set can be brazed to service valve using either silver rod or silfos rod brazingmaterial. When brazing completed, refrigerant piping and indoor coil are now ready for leak testing. This check shouldalso include all field and factory brazed joints.

18

Page 21: CBX series

ELECTRICALSTEP 1: INSTALLATIONA) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.

Caution: Operation of the unit on improper power supply will result in damage to the unit.Note: Use copper wires of proper rating for all field wiring.

Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than onedisconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.

B) Ground & power wiresConnect power wires to terminal block per wiring diagram.Connect ground wire to the ground lug inside the control box.

C) Control wiring between outdoor & indoor unitUse 16 gauge color-coded wire between the indoor and outdoor units (control wiring).

STEP 2: START-UP1) Energize crankcase heater for a minimum of 12 hours prior to the system start-up. To energize crankcase heater only,

set thermostat to "off" position and close electrical disconnect switch to the outdoor unit.2) Fully open liquid/suction service valves.3) Close electrical disconnect switch to energize the system.4) Set room thermostat to desired temperature.

SYSTEM DESIGNTHE ZAMIL CONDENSING UNIT SYSTEM HAS BEEN DESIGNED BASED ON THE FOLLOWING:

• Intended for outdoor installation with free air intake and discharge.

• Minimum outdoor operating air temperature during cooling without low ambient operation option is 550F.

• Maximum outdoor operating air temperature during cooling is 1300F.

• For reliable operation, unit should be level on horizontal plane.

• Maximum elevation of indoor unit above or below the outdoor unit is: indoor unit above = 50 feet, indoor unit below =150 feet.

• For interconnecting refrigerant pipe lengths greater than 25 feet, check with your local Zamil sales office.

• Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type ofconnector provided.

19