ce-p - controlin › wp-content › uploads › ce-p-aees-en-ds-20… · battery test the test...
TRANSCRIPT
-
CE-PDC Energy - Rectifier
Quick installation in electrical panels.
Designed for heavy environments (Genset)
A universal reference (battery or sealed lead-opened or manual, single or dual voltage).
DIN rail mounting (included).
Plug-in connectors (Easy wiring).
Built in incoming / outgoing fuses (time/ space savings).
Fully protected (short circuits - reverse polarity - coding connectors).
Complies to NFC 58-311 (Gas emissions secured).
Designed for heavy environments (Genset)
Exceptional input voltage (305 Vac).
Wide temperature operating range.
Screws fixing (different mountings possible).
Many safety features built in (reliability).
Functions improving battery life time.
Clear signalling (easy maintenance).
One single product for both 12V and 24V, or 30V and 48V.
CE-P chargers are designed to charge 12 V to 48 Vdc / 7 to 150 Ah battery or maintain larger battery used forGenset starter.
They can also be integrated on a support plate, in box or in electrical panels to provide power supplies with backup for process control systems, or to LV/MV switchgears. They can be also easily used as a 12, 24, 30 or 48 Vdc power supply, with an Benefits adjustable output voltage.
Pour plus de détails.
Consultez les documentations techniques disponibles sur le site www.aees.fr
Controlin BV - +31 (0)180 33 05 22 - [email protected] - www.controlin.nl
-
Emerson Network Power IS SAS30 avenue Montgolfier / BP90 69684 Chassieu Cedex FranceT +33 (0) 4 72 47 63 77 / F +33 (0) 4 78 40 13 [email protected] / www.Aees.frEmersonNetworkPower.com
Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. All the other marks are the property of their respective owners. ©2015 Emerson Electric Co.PDS.EL-AT0-FR
CE-PDC Energy - Rectifier
Em Er so n . Co n si D Er it so lVED ™.
Les
info
rmat
ions
con
tenu
es d
ans
ce d
ocum
ent s
ont f
ourn
ies
à ti
tre
indi
cati
f et n
e pe
uven
t êtr
e ut
ilisé
es c
ontr
actu
elle
men
t. N
otre
soc
iété
a u
ne p
olit
ique
de
déve
lopp
emen
t et d
’am
élio
rati
on c
onti
nue
de s
es p
rodu
its,
et p
ar c
onsé
quen
t se
rése
rve
le d
roit
de
mod
ifier
tout
e in
form
atio
n sa
ns p
réav
is. C
rédi
ts P
hoto
s : G
eorg
es R
ival
ain,
iSto
ckPh
oto,
Fot
olia
.
Functions
Boost
For vented lead and Ni-Cd batteries starting-up and equalizing, it is useful to set the voltage at a higher level for several hours. The boost device rises the charging voltage by 3.8%.This function is activated by strapping connector terminals. The voltage automatically returns to the initial tension after 12 hours in boost (manual return on 6011054).
Battery testThe test allows to prevent back up interruption due to a wire or a battery link cut or defective battery. The test can be performed automatically or manually from free volt contact control. Function not available 6011054.
Signalling
The charger status is indicated by a Led• Charger Ok: Led lighted up• No input sector fuse and mains fault: LED offAdditionally (not available 6011054): contact signals synthesis fault• Low battery voltage: Led flashes (quick)• High charger voltage: Led flashes (quick)Charger shuts down in case of regulation lost to protect all the connected equipments• Battery test (on a battery fault): Led flashes (quick)• Overload or battery discharged (current limit): the LED flashes intermittently; no fault report.
CF Option Available in cabinet IP31 with visualisation : 300 x 333 x 203 mm (HWD)
General dataInput voltage 187 to 305 VAC - 47 to 63 Hz
Static regulation ±1% for cumulative parameters
Output current ± 5%
Ambient operating storage temperature -20 to +50°C / - 45 to +85°C
Relative humidity < 95% to 20°C - Cooling: Natural convection
Isolation Classe I
Protection IP 20
Weight 0.5 kg
Dimension 155 x 112 x 65 mm
Code ReferenceVoltages Current
Output (A)Signalling
Input (Vac) Output (Vdc) Status Led Relay 58 3116011054 CE-P 2.5 12
187 to 305 V
50/60 Hz
12 V (10-15) 2.5 A 2 No No6011060 CE-P 08 12 12 V (10-15) 8 A 4 Yes Yes
6007024 CE-P 05 12/2412 V (10-15)
5 A 4 Yes Yes24 V (24-30)
6011062 CE-P 2.5 30/4830 V (30-38)
2.5 A 4 Yes Yes48 V (48-60)
Standards
Compliance
Product: NF C 58-311 / NF EN 61204 (except 6011054)ECM n°2004/108/CENF EN 61000-6-2 / NF EN 61000-6-4Complies to (LV Safety Compliance) n°2006/95/CENF EN 50178 - complies to SELVTransformers comply to NF EN 61558-2-17