Efficiency data FHQ + RZQSG 71C + 71L3V1 100C + 100L9V1125C +
125L9V1140C +
140L9V1100C +
100L8Y1125C +
125L8Y1 140C + 140LY1
Cooling capacity Nom. kW 6.8 9.5 12.0 13.4 9.5 12.0 13.4Heating capacity Nom. kW 7.5 10.8 13.5 15.5 10.8 13.5 15.5Power input Cooling Nom. kW 1.97 2.96 4.15 4.45 2.96 4.15 4.45
Heating Nom. kW 1.88 2.99 3.73 4.54 2.99 3.73 4.54Seasonal efficiency (according to EN14825)
Cooling Energy label A+ - A+ -Pdesign kW 6.80 9.50 12.00 - 9.5 12 -SEER 5.61 - 5.61 -Annual energy consumption kWh 424 593 749 - 593 749 -
Heating (Average climate)
Energy label A A+ - A A+ -Pdesign kW 7.60 - 7.6 -SCOP 3.90 3.91 4.01 - 3.91 4.01 -Annual energy consumption kWh 2,727 2,722 2,654 - 2,722 2,654 -
Nominal efficiency EER 3.46 3.21 2.89 3.01 3.21 2.89 3.01COP 4.00 3.61 3.62 3.41 3.61 3.62 3.41Annual energy consumption kWh 985 1,480 2,075 - 1,480 2,075 2,225Energy label Cooling/Heating A/A C/A - A/A C/A -
Indoor unit FHQ 71C 100C 125C 140C 100C 125C 140CDimensions Unit HeightxWidthxDepth mm 235x1,270x690 235x1,590x690Weight Unit kg 32 38Air filter Type Resin net with mold resistanceFan - Air flow rate Cooling High/Nom./Low m³/min 20.5/17/14 28/24/20 31/27/23 34/29/24 28/24/20 31/27/23 34/29/24
Heating High/Nom./Low m³/min 20.5/17/14 28/24/20 31/27/23 34/29/24 28/24/20 31/27/23 34/29/24Sound power level Cooling dBA 55 60 62 64 60 62 64
Heating dBA 55 60 62 64 60 62 64Sound pressure level Cooling High/Nom./Low dBA 38/36/34 42/38/34 44/41/37 46/42/38 42/38/34 44/41/37 46/42/38
Heating High/Nom./Low dBA 38/36/34 42/38/34 44/41/37 46/42/38 42/38/34 44/41/37 46/42/38Control systems Infrared remote control BRC7G53
Wired remote control BRC1D52 / BRC1E52A/BPower supply Phase / Frequency / Voltage Hz / V 1~ / 50/60 / 220-240/220
Outdoor unit RZQSG 71L3V1 100L9V1 125L9V1 140L9V1 100L8Y1 125L8Y1 140LY1Dimensions Unit HeightxWidthxDepth mm 770x900x320 990x940x320 1,430x940x320 990x940x320 1,430x940x320Weight Unit kg 67 72 74 95 82 101Sound power level Cooling dBA 65 70 69 70 69Sound pressure level Cooling Nom./Silent operation dBA 49/47 53/- 54/- 53/- 54/- 53/-
Heating Nom. dBA 51 57 58 54 57 58 54Night quiet mode Level 1 dBA - 49
Operation range Cooling Ambient Min.~Max. °CDB -15~46Heating Ambient Min.~Max. °CWB -15~15.5
Refrigerant Type/Charge kg-TCO²Eq/GWP R-410A/2.75/5.7/2,087.5 R-410A/2.9/6.1/2,087.5 R-410A/4.0/8.4/2,087.5 R-410A/2.9/6.1/2,087.5 R-410A/4.0/8.4/2,087.5Piping connections Liquid OD mm 9.52
Gas OD mm 15.9Piping length OU - IU Max. m 50
System Equivalent m 70Chargeless m 30
Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 15 30.0
Power supply Phase / Frequency / Voltage Hz / V 1~ / 50 / 220-240 3N~ / 50 / 380-415Current - 50Hz Maximum fuse amps (MFA) A 20 32 16 20(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more detailed information on each combination, please refer to the electrical data drawing.
Ceiling suspended unit
For wide rooms with no false ceilings nor free floor space
Combination with Seasonal Classic ensures good value for money for all types of commercial applications › Ideal for comfortable air flow in wide rooms thanks to Coanda effect: up to 100° discharge angle
› Even rooms with ceilings up to 3.8m can be heated up or cooled down very easily without capacity loss
› Can easily be mounted in corners and narrow spaces, as it only needs 30mm lateral service space
30 or more 30 or more(Service space) (Service space) Obstruction
Air inlet
Air outlet
FHQ-C + RZQSG-L3/9V1/L(8)Y1
› Reduced energy consumption thanks to specially developed DC fan motor and drain pump
› Stylish unit blends easily with any interior. The flaps close entirely when the unit is not operating and there are no air intake grilles visible
› No optional adapter needed for DIII-connection, link your unit into the wider building management system.
› Drain pump kit available as accessory › Fresh air intake integrated in the same system thus reducing installation cost as no additional ventilation device is required
70
-
Efficiency data FHQ + RZQG 71C + 71L9V1100C +
100L9V1125C +
125L9V1140C +
140L9V171C +
71L8Y1100C +
100L8Y1125C +
125L8Y1140C + 140LY1
Cooling capacity Nom. kW 6.8 9.5 12.0 13.4 6.8 9.5 12.0 13.4Heating capacity Nom. kW 7.5 10.8 13.5 15.5 7.5 10.8 13.5 15.5Power input Cooling Nom. kW 1.78 2.49 3.58 4.05 1.78 2.49 3.58 4.05
Heating Nom. kW 1.82 2.60 3.48 4.27 1.82 2.60 3.48 4.27Seasonal efficiency (according to EN14825)
Cooling Energy label A++ A+ - A++ A+ -Pdesign kW 6.80 9.50 12.00 - 6.8 9.5 12 -SEER 6.95 6.11 6.01 - 6.95 6.11 6.01 -Annual energy consumption kWh 343 545 699 - 343 545 699 -
Heating (Average climate)
Energy label A+ A++ A+ - A+ A++ A+ -Pdesign kW 7.60 11.30 14.13 - 7.6 11.3 14.13 -SCOP 4.32 4.61 4.23 - 4.32 4.61 4.23 -Annual energy consumption kWh 2,463 3,432 4,677 - 2,463 3,432 4,677 -
Nominal efficiency EER 3.82 3.81 3.35 3.31 3.82 3.81 3.35 3.31COP 4.13 4.15 3.89 3.63 4.13 4.15 3.89 3.63Annual energy consumption kWh 890 1,245 1,790 - 890 1,245 1,790 -Energy label Cooling/Heating A/A - A/A -
Indoor unit FHQ 71C 100C 125C 140C 71C 100C 125C 140CDimensions Unit HeightxWidthxDepth mm 235x1,270x690 235x1,590x690 235x1,270x690 235x1,590x690Weight Unit kg 32 38 32 38Air filter Type Resin net with mold resistanceFan - Air flow rate Cooling High/Nom./Low m³/min 20.5/17/14 28/24/20 31/27/23 34/29/24 20.5/17/14 28/24/20 31/27/23 34/29/24
Heating High/Nom./Low m³/min 20.5/17/14 28/24/20 31/27/23 34/29/24 20.5/17/14 28/24/20 31/27/23 34/29/24Sound power level Cooling dBA 55 60 62 64 55 60 62 64
Heating dBA 55 60 62 64 55 60 62 64Sound pressure level Cooling High/Nom./Low dBA 38/36/34 42/38/34 44/41/37 46/42/38 38/36/34 42/38/34 44/41/37 46/42/38
Heating High/Nom./Low dBA 38/36/34 42/38/34 44/41/37 46/42/38 38/36/34 42/38/34 44/41/37 46/42/38Control systems Infrared remote control BRC7G53
Wired remote control BRC1D52 / BRC1E52A/BPower supply Phase / Frequency / Voltage Hz / V 1~ / 50/60 / 220-240/220
Outdoor unit RZQG 71L9V1 100L9V1 125L9V1 140L9V1 71L8Y1 100L8Y1 125L8Y1 140LY1Dimensions Unit HeightxWidthxDepth mm 990x940x320 1,430x940x320 990x940x320 1,430x940x320Weight Unit kg 69 95 80 101Sound power level Cooling dBA 64 66 67 69 64 66 67 69Sound pressure level Cooling Nom. dBA 48 50 51 52 48 50 51 52
Heating Nom. dBA 50 52 53 50 52 53Night quiet mode Level 1 dBA 43 45 43 45
Operation range Cooling Ambient Min.~Max. °CDB -15~50Heating Ambient Min.~Max. °CWB -20~15.5
Refrigerant Type/Charge kg-TCO²Eq/GWP R-410A/2.9/6.1/2,087.5 R-410A/4.0/8.4/2,087.5 R-410A/2.9/6.1/2,087.5 R-410A/4.0/8.4/2,087.5Piping connections Liquid OD mm 9.52
Gas OD mm 15.9Piping length OU - IU Max. m 50 75 50 75
System Equivalent m 70 90 70 90Chargeless m 30
Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 30.0
Power supply Phase / Frequency / Voltage Hz / V 1~ / 50 / 220-240 3N~ / 50 / 380-415Current - 50Hz Maximum fuse amps (MFA) A 20 32 20 32
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
Ceiling suspended unit
For wide rooms with no false ceilings nor free floor space
For combination with Seasonal Smart ensures best in class quality, highest efficiency and performance
FHQ-C + RZQG-L9V1/L(8)Y1
71
BRC1E52A-B, BRC7G53RZQG100-125-140L9V1/L(8)Y1
FHQ60-71C Indo
or u
nits
-
Detailed technical drawings
FHQ35C
FHQ50C
72
Find all technical drawings on our business portal http://my.daikin.eu
https://my.daikin.eu/content/denv/en_US/home/applications/product-finder/FHQ-C.html
-
Detailed technical drawings
FHQ60C
FHQ71C
73
Indo
or u
nits
-
Detailed technical drawings
FHQ100-140C
74
-
Efficiency data AHQ + AZQS 71C + 71BV1 100C + 100B8V1125C +
125B8V1140C +
140B8V1 100C + 100BY1 125C + 125BY1 140C + 140BY1
Cooling capacity Nom. kW 6.8 9.5 12.1 13.0 9.5 12.1 13.0Heating capacity Nom. kW 7.5 10.8 13.5 15.5 10.8 13.5 15.5Power input Cooling Nom. kW 2.24 3.62 4.60 4.32 3.62 4.60 4.32
Heating Nom. kW 2.46 3.17 3.74 4.55 3.17 3.74 4.55Seasonal efficiency (according to EN14825)
Cooling Energy label B - B -Pdesign kW 6.80 9.50 - 9.50 -SEER 4.65 4.60 - 4.60 -Annual energy consumption kWh 511.85 723 - 723 -
Heating (Average climate)
Energy label A - A -Pdesign kW 6.33 7.60 - 7.60 -SCOP 3.80 - 3.80 -Annual energy consumption kWh 2,332.26 2,800 - 2,800 -
Nominal efficiency EER 3.03 2.62 2.63 3.01 2.62 2.63 3.01COP 3.05 3.41 3.61 3.41 3.61 3.41Annual energy consumption kWh 1,120 1,810 2,300 - 1,810 2,300 -Energy label Cooling/Heating B/D D/B D/A - D/B D/A -
Indoor unit AHQ 71C 100C 125C 140C 100C 125C 140CDimensions Unit HeightxWidthxDepth mm 260x1,320x634 260x1,538x634 260x1,786x634 285x1,902x680 260x1,538x634 260x1,786x634 285x1,902x680Weight Unit kg 38 45 54 70 45 54 70Air filter Type Removable / washableFan - Air flow rate Cooling High/Nom./Low m³/min 23.8/21.3/18.9 31.1/27.8/24.8 34.4/30.6/27.2 43.9/39.1/28.3 31.1/27.8/24.8 34.4/30.6/27.2 43.9/39.1/28.3
Heating High/Nom./Low m³/min 23.8/21.3/18.9 31.1/27.8/24.8 34.4/30.6/27.2 43.9/39.1/28.3 31.1/27.8/24.8 34.4/30.6/27.2 43.9/39.1/28.3Sound power level Cooling dBA 59 64 69 70 64 69 70
Heating dBA 62 64 69 70 64 69 70Sound pressure level Cooling High/Nom./Low dBA 49/48/46 52/47/46 52/50/49 56/53/46 52/47/46 52/50/49 56/53/46
Heating High/Nom./Low dBA 49/48/46 52/47/46 52/50/49 56/53/46 52/47/46 52/50/49 56/53/46Control systems Infrared remote control ARCWLA
Wired remote control ARCWBPower supply Phase / Frequency / Voltage Hz / V 1~ / 50 / 220-240
Outdoor unit AZQS 71BV1 100B8V1 125B8V1 140B8V1 100BY1 125BY1 140BY1Dimensions Unit HeightxWidthxDepth mm 770x900x320 990x940x320 1,430x940x320 990x940x320 1,430x940x320Weight Unit kg 67 72.8 74.3 94.9 82 101Sound power level Cooling dBA 64 70 71 70 71 70Sound pressure level Cooling Nom. dBA 48 53 54 53 54 53
Heating Nom. dBA 50 57 58 54 57 58 54Night quiet mode Level 1 dBA 43 49
Operation range Cooling Ambient Min.~Max. °CDB -5~46Heating Ambient Min.~Max. °CWB -15~15.5
Refrigerant Type/Charge kg-TCO²Eq/GWP R-410A/2.75/5.7/2,087.5 R-410A/2.9/6.1/2,087.5 R-410A/4.0/8.4/2,087.5 R-410A/2.9/6.1/2,087.5 R-410A/4.0/8.4/2,087.5Piping connections Liquid OD mm 9.52
Gas OD mm 15.9Piping length OU - IU Max. m 50
System Equivalent m 70Chargeless m 30
Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 30.0
Power supply Phase / Frequency / Voltage Hz / V 1~ / 50 / 220-240 3N~ / 50 / 380-415Current - 50Hz Maximum fuse amps (MFA) A 20 32 16 20
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing.
Ceiling suspended unit
For wide rooms with no false ceilings nor free floor space
› Ideal solution for commercial spaces with no or narrow false ceilings
› Exclusively offered for pair applications › Can easily be installed in both new and refurbishment projects › Air filter removes airborne dust particles to ensure a steady supply of clean air
› Decrease of temperature variation by automatic fan speed selection or freely selectable 3-step fan speed.
› Easy installation and maintenance
AHQ-C + AZQS-B(8)V1/BY1
75
ARCWLAAZQS71BV1
AHQ71C Indo
or u
nits
-
Detailed technical drawings
AHQ71-125C
AHQ140C
• Indoor Unit • AHQ-C
4
• Split - Sky Air • AHQ-C6
4 Dimensional drawings
• Indoor Unit • AHQ-C
4
• Split - Sky Air • AHQ-C6
4 Dimensional drawings
76
Find all technical drawings on our business portal http://my.daikin.eu
https://my.daikin.eu/content/denv/en_US/home/applications/product-finder/AHQ-C.html