centerline 2100 motor control centers mains and incoming
TRANSCRIPT
Technical DataOriginal Instructions
CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension ReferenceBulletin Numbers 2191M, 2192M, 2193M
Topic PageSummary of Changes 2Application Notes 3Catalog Numbers 3Main Incoming Lines 4Main Fusible Disconnects 12Main Circuit Breakers 28Conduit Entry - Top 38Conduit Entry - Bottom 43Additional Resources 49
CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.
Topic PageAdded dimensions for conduit entry for 100 ms ArcShield motor control centers. 38 and 39
2 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Application Notes
This guide contains cabling dimensions for main incoming line compartments, fusible disconnect switch mains, and circuit breaker mains in Bulletin 2100 CENTERLINE® motor control centers. Lug pad dimensions are included for main incoming line compartments. The fusible disconnect and circuit breaker mains drawing include dimensions for standard lugs, and optional lugs (if specified).
Catalog Numbers
Every CENTERLINE motor control center unit is defined by a catalog number. For mains, these catalog numbers are of the following form:
The catalog numbers appear on the unit label, located on the unit bottom plate. For assembled motor control centers, catalog numbers for each unit are also listed on the Job-specific Drawings (Form 385) that ship with the order.
IMPORTANT Although this guide is accurate at the time of printing, there are differences between these drawings and the actual product, due to recent design enhancements. Always refer to the Job-specific Drawings (Form 385) for the most accurate drawings and dimensions.
IMPORTANT Dimensions are shown in inches and (millimeters). Reference dimensions include a tolerance of ±1/8 inches (±3.2 millimeters).
Catalog Number Example
Type of Main Catalog Bulletin Number Catalog Number ExampleIncoming Line 2191M 2191MT-CAC-54Fusible Disconnect 2192M 2192MB-GAC-29RCircuit Breaker 2193M 2193MT-FJC-54WT-83C500
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 3
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Main Incoming Lines(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 1 - 300 A Incoming Line Compartment, Top Entry, 1.0 Space Factor(a)
Figure 2 - 300 A Incoming Line Compartment, Bottom Entry, 1.0 Space Factor(a)
Figure 3 - 600 A Incoming Line Compartment, Top Entry, 1.0 Space Factor(a)
Figure 4 - 600 A Incoming Line Compartment, Bottom Entry, 1.0 Space Factor(a)
4 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 5 - 800 A Incoming Compartment Top Entry, 1.5 Space Factor(a)
Figure 6 - 800 A Incoming Compartment Bottom Entry, 1.5 Space Factor(a)
Figure 7 - 800 A Incoming Compartment Top Entry in Horizontal Wireway (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
Figure 8 - 800…1200 A Incoming Compartment Top Entry 1.0 Space Factor (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 5
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 9 - 800 A Incoming Line Compartment Top Entry, 1.5 Space Factor(a)
Figure 10 - 800 A Incoming Line Compartment Bottom Entry, 1.5 Space Factor(a)
Figure 11 - 800…1200 A Incoming Line Compartment Top Entry, 2.0 Space Factor(a)
Figure 12 - 800…1200 A Incoming Line Compartment Bottom Entry, 2.0 Space Factor(a)
6 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 12 - 600…1600 A Incoming Line Section Top Entry, 6.0 Space Factor(a)
Figure 13 - 600…1600 A Incoming Line Section Bottom Entry, 6.0 Space Factor(a)
Figure 14 - 2000 A Incoming Line Section Top Entry, 6.0 Space Factor(a)
Figure 15 - 2000 A Incoming Line Section Bottom Entry, 6.0 Space Factor(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 7
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 17- 600…1200 A Corner Incoming Line Section Top Entry, 6.0 Space Factor(a)
Figure 18 - 600…1200 A Corner Incoming Line Section Bottom Entry, 6.0 Space Factor(a)
Figure 19 - 1600 A Corner Incoming Line Section Top Entry, 6 Space Factor(a)
Figure 20 - 1600 A Corner Incoming Line Section Bottom Entry, 6 Space Factor(a)
8 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 21 - 600…1200 A, 10 in. Wide Incoming Line Section Top Entry, 6.0 Space Factor (left-hand version shown)(a)
Figure 22 - 600…1200 A, 10 in. Wide Incoming Line Section Bottom Entry, 6.0 Space Factor (left-hand version shown)(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 9
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
3.00(76.2)
2.562(65.1)
3.310(84.07) 0.75 ± 0.010
(19.10 ± 0.25)
1.875 ± 0.010(47.63 ± 0.25)
5.687 ± 0 .031(144.45 ±0.79)
Figure 23 - #6-350 kcmil, One Cable Mechanical Lug Figure 24 - #6-350 kcmil, Two Cable Mechanical Lug
Figure 25 - 350…800 kcmil, One Cable Mechanical Lug
Figure 26 - #4/0-600 kcmil, One Cable Mechanical Lug Figure 27 - #4/0-600 kcmil, Two Cable Mechanical Lug
Figure 28 - #4/0-600 kcmil, Two Cable Mechanical Lug
10 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 29 - 250 kcmil Panduit Crimp Lug Figure 30 - 250 kcmil Burndy Crimp Lug
Figure 31 - 350 kcmil Panduit Crimp Lug Figure 32 - 350 kcmil Burndy Crimp Lug
Figure 33 - 500 kcmil Panduit Crimp Lug Figure 34 - 500 kcmil Burndy Crimp Lug
Figure 35 - 750 kcmil Panduit Crimp Lug Figure 36 - 750 kcmil Burndy Crimp Lug
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 11
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Main Fusible Disconnects(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 37 - 30 A Main Fusible Disconnect Top Entry, 1.5 Space Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(a)
Figure 38 - 30 A Main Fusible Disconnect Bottom Entry, 1.5 Space Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(a)
Figure 39 - 60 A Main Fusible Disconnect Top Entry, 1.5 Space Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(a)
Figure 40 - 60 A Main Fusible Disconnect Bottom Entry, 1.5 Space Factor with #14…#8 AWG Mechanical Lugs, 1 per Phase(a)
12 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 41 - 100 A Main Fusible Disconnect Top Entry, 1.5 Space Factor with #8…1/0 AWG Mechanical Lugs, 1 per Phase(a)
Figure 42 - 100 A Main Fusible Disconnect Bottom Entry, 1.5 Space Factor with #8…1/0 AWG Mechanical Lugs, 1 per Phase(a)
Figure 43 - 200 A Main Fusible Disconnect Top Entry, 2.0 Space Factor with #6…4/0 AWG or #6…250 kcmil Mechanical Lugs, 1 per Phase(a)
Figure 44 - 200 A Main Fusible Disconnect Bottom Entry, 2.0 Space Factor with #6…4/0 AWG or #6…250 kcmil Mechanical Lugs, 1 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 13
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 45 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor with Two Cable 1/0…250 kcmil Mechanical Lugs, 1 per Phase(a)
Figure 46 - 400 A Main Fusible Disconnect Bottom Entry, 2.5 Space Factor with Two Cable 1/0…250 kcmil Mechanical Lugs, 1 per Phase(a)
Figure 47 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor with 250 kcmil Panduit Crimp Lugs, 2 per Phase(a)
Figure 48 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 1 per Phase (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
14 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 49 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor with 250 kcmil Burndy Crimp Lugs, 2 per Phase(a)
Figure 50 - 400 A Main Fusible Disconnect Top Entry, 2.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 1 per Phase (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
Figure 51 - 600 A Main Fusible Disconnect Top Entry, 3.5 Space Factor with #2…600 kcmil Mechanical Lugs, 2 per Phase(a)
Figure 52 - 600 A Main Fusible Disconnect Bottom Entry, 3.5 Space Factor with #2…600 kcmil Mechanical Lugs, 2 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 15
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 53 - 600 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(a)
Figure 54 - 600 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(a)
Figure 55 - 600 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(a)
Figure 56 - 600 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(a)
16 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 57 - 600 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with #2…600 kcmil Mechincal Lugs, 2 per Phase(a)
Figure 58 - 600 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with #2…600 kcmil Mechincal Lugs, 2 per Phase(a)
Figure 59 - 600 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(a)
Figure 60 - 600 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 2 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 17
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 61 - 600 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(a)
Figure 62 - 600 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 2 per Phase(a)
Figure 63 - 800 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(a)
Figure 64 - 800 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(a)
18 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 65 - 800 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(a)
Figure 66 - 800 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(a)
Figure 67 - 800 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(a)
Figure 68 - 800 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 19
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 69 - 800 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(a)
Figure 70 - 800 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 3 per Phase(a)
Figure 71 - 800 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(a)
Figure 72 - 800 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 3 per Phase(a)
20 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 73 - 800 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(a)
Figure 74 - 800 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 3 per Phase(a)
Figure 75 - 1200 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(a)
Figure 76 - 1200 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 21
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 77 - 1200 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(a)
Figure 78 - 1200 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(a)
Figure 79 - 1200 A Main Fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(a)
Figure 80 - 1200 A Main Fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(a)
22 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 81 - 1200 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(a)
Figure 82 - 1200 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with #6…350 kcmil Mechanical Lugs, 4 per Phase(a)
Figure 83 - 1200 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(a)
Figure 84 - 1200 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Panduit Crimp Lugs, 4 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 23
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 85 - 1200 A Main Non-fusible Disconnect, Top Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(a)
Figure 86 - 1200 A Main Non-fusible Disconnect, Bottom Entry, 3.5 Space Factor with 500 kcmil Burndy Crimp Lugs, 4 per Phase(a)
Figure 87 - 1600 A Main Fusible or Non-fusible Disconnect, Top Entry, 6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 4 per Phase(a)
Figure 88 - 1600 A Main Fusible or Non-fusible Disconnect, Bottom Entry, 6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 4 per Phase(a)
24 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 89 - 1600 A Main Fusible or Non-fusible Disconnect, Top Entry, 6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 5 per Phase(a)
Figure 90 - 1600 A Main Fusible or Non-fusible Disconnect, Bottom Entry, 6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 5 per Phase(a)
Figure 91 - 1600 A Main Fusible or Non-fusible Disconnect, Top Entry, 6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 5 per Phase(a)
Figure 92 - 1600 A Main Fusible or Non-fusible Disconnect, Bottom Entry, 6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 5 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 25
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 93 - 2000 A Main Fusible or Non-fusible Disconnect, Top Entry, 6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 6 per Phase(a)
Figure 94 - 2000 A Main Fusible or Non-fusible Disconnect, Bottom Entry, 6.0 Space Factor with #2…600 kcmil Mechanical Lugs, 6 per Phase(a)
Figure 95 - 2000 A Main Fusible or Non-fusible Disconnect, Top Entry, 6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 6 per Phase(a)
Figure 96 - 2000 A Main Fusible or Non-fusible Disconnect, Bottom Entry, 6.0 Space Factor with 500 kcmil Panduit Crimp Lugs, 6 per Phase(a)
26 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 97 - 2000 A Main Fusible or Non-fusible Disconnect, Top Entry, 6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 6 per Phase(a)
Figure 98 - 2000 A Main Fusible or Non-fusible Disconnect, Bottom Entry, 6.0 Space Factor with 500 kcmil Burndy Crimp Lugs, 6 per Phase(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 27
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Main Circuit Breakers(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
11.13(283) 7.28
(185)
7.28(185)
5.16(131)
7.24(184)
7.24(184)
5.05(128)
10.57(268.5)
Figure 99 - 150 A Main Circuit Breaker, Top Entry, 1.5 Space Factor, with #14…#1/0 AWG Mechanical Lugs, 1 per Phase, 15…125 A Trips(a)
Figure 100 - 150 A Main Circuit Breaker, Bottom Entry, 1.5 Space Factor, with #14…#1/0 AWG Mechanical Lugs, 1 per Phase, 15…125 A Trips(a)
Figure 101 - 250 A Main Circuit Breaker, Top Entry, 1.5 Space Factor, with #10…250 kcmil Mechanical Lugs, 1 per Phase, 70…250 A Trips(a)
Figure 102 - 250 A Main Circuit Breaker, Bottom Entry, 1.5 Space Factor, with #4…250 kcmil Mechanical Lugs, 1 per Phase, 70…250 A Trips(a)
28 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
16.88(428.75) 6.90
(175.25)
6.90(175.25)
11.38(289)
6.15(156.2)
6.15(156.2)
6.96(177)
6.96(177)
15.94(405)
11.38(289)
Figure 103 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 250…500 kcmil Mechanical Lugs, 1 per Phase, 300 A(a)
Figure 104 - 400 A Main Circuit Breaker, Bottom Entry, 2.0 Space Factor, with 250…500 kcmil Mechanical Lugs, 1 per Phase, 300 A Trip(a)
Figure 105 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 2/0…250 kcmil Mechanical Lugs, 2 per Phase, 400 A Trip(a)
Figure 106 - 400 A Main Circuit Breaker, Bottom Entry, 2.0 Space Factor,with 2/0…250 kcmil Mechanical Lugs, 2 per Phase, 400 A Trip(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 29
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
11.16(283.5)
7.64(194)
6.12(155.4)
11.68(296.7)
7.64(194)
6.12(155.4)
11.61(283.5)
6.46(164.1)
10.94(278)
6.4(162.6)
Figure 107 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 250 kcmil Panduit Crimp Lugs, 2 per Phase, 300…400 A Trips (optional Pull Box provides an additional 12 in. of bending space)(a)
Figure 108 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 250 kcmil Burndy Crimp Lugs, 2 per Phase, 300…400 A Trips (optional Pull Box provides an additional 12 in. of bending space)(a)
Figure 109 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 500 kcmil Panduit Crimp Lugs, 1 per Phase, 300 A Trips (optional Pull Box provides an additional 12 in. of bending space)(a)
Figure 110 - 400 A Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 500 kcmil Burndy Crimp Lugs, 1 per Phase, 300 A Trips (optional Pull Box provides an additional 12 in of bending space)(a)
30 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
6.90(175.26)
14.36(364.7) 5.15
(130.8)
14.44(366.8)
5.15(130.8)6.90(175.26)
6.90(175.26)
5.15(130.8)
14.44(366.8)
5.15(130.8)6.90(175.26)
14.36(364.7)
Figure 111 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 3/0…350 kcmil Mechanical Lugs, 2 per Phase, 600 A Trips(a)
Figure 112 - 800 A Frame Main Circuit Breaker, Bottom Entry, 2.0 Space Factor, with 3/0…350 kcmil Mechanical Lugs, 2 per Phase, 600 A Trips(a)
Figure 113 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 250…500 kcmil Mechanical Lugs, 2 per Phase, 600 A Trips(a)
Figure 114 - 800 A Frame Main Circuit Breaker, Bottom Entry, 2.0 Space Factor, with 250…500 kcmil Mechanical Lugs, 2 per Phase, 600 A Trips(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 31
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 115 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 500 kcmil Panduit Crimp Lugs, 2 per Phase, 600 A Trips (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
Figure 116 - 800 A Frame Main Circuit Breaker, Top Entry, 2.0 Space Factor, with 500 kcmil Burndy Crimp Lugs, 2 per Phase, 600 A Trips (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
32 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
16.90(430)
5.62(143)
4.93(125)
17.40(442)
5.81(148)
5.06(129)
Figure 117 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor, with #2/0…250 kcmil Mechanical Lugs, 3 per Phase, 800 A Trips(a)
Figure 118 - 800 A Main Circuit Breaker, Bottom Entry, 2.5 Space Factor, with #2/0...350 kcmil Mechanical Lugs, 3 per Phase, 800 A Trips(a)
16.90(430)
6.12(156)5.43(138)
4.81(123)
17.40(442)
4.81(123)
5.43(138)6.12(156)
Figure 119 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor, with #2/0 - 400 kcmil Mechanical Lugs, 3 per Phase, 800 A Trips(a)
Figure 120 - 800 A Main Circuit Breaker, Bottom Entry, 2.5 Space Factor, with #2/0 - 400 kcmil Mechanical Lugs, 3 per Phase, 800 A Trips(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 33
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
4.18(107)
7.62(194)6.00(153)4.53(115)
3.94(100)
7.62(194)6.00(153)4.53(115)
Figure 121 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor, with 500 kcmil Panduit Crimp Lugs, 3 per Phase, 800 A Trips (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
Figure 122 - 800 A Main Circuit Breaker, Top Entry, 2.5 Space Factor, with 500 kcmil Burndy Crimp Lugs, 3 per Phase, 800 A Trips (additional 12 in. Pull Box required to meet NEC wire bending requirements)(a)
Figure 123 - 1200 A Main Circuit Breaker, Top Entry, 3.5 Space Factor, with #4/0 - 500 kcmil Mechanical Lugs, 4 per Phase, 400…1200 Trips(a)
Figure 124 - 1200 A Main Circuit Breaker, Bottom Entry, 3.5 Space Factor, with #4/0 - 500 kcmil Mechanical Lugs, 4 per Phase, 400…1200 Trips(a)
34 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
16.20(412)
9.23(235)
7.73(197)6.30(160)
4.80(122)
16.34(415)
4.80(122)6.30(160)7.73(197)
9.23(235)
15.54(395)
9.23(235)
7.73(197)6.30(160)
4.80(122)
15.68(398)
4.80(122)6.30(160)7.73(122)
9.23(235)
Figure 125 - 1200 A Main Circuit Breaker, Top Entry, 3.5 Space Factor, with 500 kcmil Panduit Crimp Lugs, 3 or 4 per Phase, 400…1200 Trips(a)
Figure 126 - 1200 A Main Circuit Breaker, Bottom Entry, 3.5 Space Factor, with 500 kcmil Panduit Crimp Lugs, 3 or 4 per Phase, 400…1200 Trips(a)
Figure 127 - 1200 A Main Circuit Breaker, Top Entry, 3.5 Space Factor, with 500 kcmil Burndy Crimp Lugs, 4 per Phase, 600…1200 Trips(a)
Figure 128 - 1200 A Main Circuit Breaker, Bottom Entry, 3.5 Space Factor, with 500 kcmil Burndy Crimp Lugs, 4 per Phase, 600…1200 Trips(a)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 35
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
10.10(256.5)
11.75(298.5)
13.40(340.4)
15.05(382.3)
24.82(630.4)
24.82(630.4)
10.10(256.5)
11.75(298.5)
13.40(340.4)
15.05(382.3)
25.81(655.6)
24.72(627.9)
25.71(653.0)
10.10(256.5)
11.75(298.5)
13.40(340.4)
15.05(382.3)
24.72(627.9)
10.10(256.5)
11.75(298.5)
13.40(340.4)
15.05(382.3)
Figure 129 - 3000 A R-frame Main Circuit Breaker, Top Entry, 8 Cables per Phase
Figure 130 - 3000 A R-frame Main Circuit Breaker, Bottom Entry, 8 Cables per Phase
Figure 131 - 2500 A R-frame Main Circuit Breaker, Top Entry, 100%, 7 Cables per Phase
Figure 132 - 2500 A R-frame Main Circuit Breaker, Bottom Entry, 100%, 7 Cables per Phase
36 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
24.86(631.4)
25.85(656.6)
4.61(117.1)
5.77(146.6)
8.47(215.1)
24.82(630.4)
25.81(655.6)
4.61(117.1)5.77(146.6)
8.47(215.1)
24.82(630.4)
4.61(117.1)
5.77(146.6)
24.86(631.4)
4.61(117.1)
5.77(146.6)
Figure 135 - 2000 A and Less R-frame, Top Entry, 6 Cables per Phase
Figure 136 - 2000 A and Less R-frame, Bottom Entry, 6 Cables per Phase
Figure 133 - 2500 A R-frame, Top Entry, 80% 7 Cables per Phase
Figure 134 - 2500 A R-frame, Bottom Entry, 80% 7 Cables per Phase
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 37
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Conduit Entry - TopFigure 137 - Top View, 20 in. Wide Cabinet, NEMA Type 1 or 12
1.14 17.72
20.00
14.48(367.80)
17.97 (456.44)
20.00 (508.00)
6.63 (168.4)
7.44 (189)
.25 (6.35)
11.09 (281.70)
Load and
Control Wiring
Incoming Line Cables
4.00 (101.60)Wide Internal
VerticalWireway
Front of Cabinet
and Vertical BaffleOptional Horizontal Ground Bus
Note:
Note:Vertical WirewayUsed WhereApplicable
Figure 138 - Top View, 25 in. Wide Cabinet, 100 ms ArcShield
1.14(29.00)
22.72(577.09)
25.00(635.00)
20.00 (508.00)
6.63 (168.40)
0.25 (6.35)
7.44 (189.00)Incoming Line,
Load, and
Control Wiring
and Vertical BaffleHorizontal Ground Bus
Note:
Front of Cabinet
Lift Angle
Pressure Relief Vent
38 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Figure 139 - Top View, 30 in. Wide Cabinet, 100 ms ArcShield
20.00 (508.00)
1.14(29.00)
30.00(762.00)27.72
(704.09)
7.44 (189.00)
0.25 (6.35)
6.63 (168.40) Incoming Line,Load, and
Control Wiring
and Verticle BaffleHorizontal Ground Bus
Note:
Front of Cabinet
Lift Aangle
Pressure Relief Vent
Figure 140 - Top View, 35 in. Wide Cabinet, 100 ms ArcShield
7.44 (189.00)
0.25 (6.35)
6.63 (168.40)
35.00(889.00)
32.72(803.09)
1.14(29.00)
20.00 (508.00)
Incoming Line,Load, and
Control Wiring
and Vertical BaffleGround BusHorizontal
Note:
Front of Cabinet
Lift Aangle
Pressure Relief Vent
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 39
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 141 - Top Horizontal Ground Bus Location Front View(a)
Figure 142 - Standard and Incoming Line Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Single Section, Top View(a)
Dimensions are shown as in. (mm)
Dimension15” Deep 20” Deep
20” Wide
25” Wide
30” Wide
35” Wide
20” Wide
25” Wide
30” Wide
35” Wide
‘A’ 20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
‘B’ 15.00 (381)
15.00 (381)
15.00 (381)
15.00 (381)
20.00 (508)
20.00 (508)
20.00 (508)
20.00 (508)
‘C’ 17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
‘D’ 4.38 (111)
9.38 (238) — — 4.38
(111)9.38 (238) — —
‘E’ 7.00 (178)
7.00 (178) — — 7.00
(178)7.00 (178) — —
‘F’ 12.97 (329)
12.97 (329)
12.97 (329)
12.97 (329)
17.97 (456)
17.97 (456)
17.97 (456)
17.97 (456)
40 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 143 - Standard and Incoming Line Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Back-to-Back Construction, Top View(a)
Figure 144 - Standard and Incoming Line Corner Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Top View
Dimensions are shown as in. (mm)
Dimension15” Deep 20” Deep
20” Wide
25” Wide
30” Wide
35” Wide
20” Wide
25” Wide
30” Wide
35” Wide
‘A’ 20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
‘B’ 29.78 (756)
29.78 (756)
29.78 (756)
29.78 (756)
39.78 (1010)
39.78 (1010)
39.78 (1010)
39.78 (1010)
‘C’ 17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
‘D’ 4.38 (111)
9.38 (238) — — 4.38
(111)9.38 (238) — —
‘E’ 7.00 (178)
7.00 (178) — — 7.00
(178)7.00 (178) — —
‘F’ 12.97 (329)
12.97 (329)
12.97 (329)
12.97 (329)
17.97 (456)
17.97 (456)
17.97 (456)
17.97 (456)
DimensionSection Depth15”
Wide20”
Wide
‘A’ 25.12 (638)
30.12 (765)
‘B’ 22.75 (578)
27.75 (705)
‘C’ 15.00 (381)
20.00 (508)
‘D’ 7.34 (186)
12.34 (313)
‘E’ 7.41 (188)
12.41 (315)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 41
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 145 - 10 in. Wide Incoming Line Section, Top Entry, NEMA Type 1, 1 (with gasket), or 12, Top View
DimensionSection Depth15”
Wide20”
Wide
‘A’ 14.86 (377)
19.86 (504)
‘B’ 12.71 (323)
17.71 (450)
42 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Conduit Entry - Bottom(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 146 - Bottom Horizontal Ground Bus Location, Front View(a)
Figure 147 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, Single Section, Top View(a)
Dimensions are shown as in. (mm)
Dimension15” Deep 20” Deep
20” Wide
25” Wide
30” Wide
35” Wide
20” Wide
25” Wide
30” Wide
35” Wide
‘A’ 20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
‘B’ 15.00 (381)
15.00 (381)
15.00 (381)
15.00 (381)
20.00 (508)
20.00 (508)
20.00 (508)
20.00 (508)
‘C’ 17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
‘D’ 10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
‘E’ 4.38 (111)
4.38 (111) — — 4.38
(111)4.38 (111) — —
‘F’ 7.00 (178)
7.00 (178) — — 7.00
(178)7.00 (178) — —
‘G’ 11.56 (294)
11.56 (294)
11.56 (294)
11.56 (294)
16.56 (421)
16.56 (421)
16.56 (421)
16.56 (421)
‘H’ 9.13 (232)
9.13 (232)
9.13 (232)
9.13 (232)
14.13 (359)
14.13 (359)
14.13 (359)
14.13 (359)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 43
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 148 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, Back-to-Back Construction, Top View(a)
Figure 149 - Standard and Incoming Line Corner Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, Top View
Dimensions are shown as in. (mm)
Dimension15” Deep 20” Deep
20” Wide
25” Wide
30” Wide
35” Wide
20” Wide
25” Wide
30” Wide
35” Wide
‘A’ 20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
‘B’ 29.78 (756)
29.78 (756)
29.78 (756)
29.78 (756)
39.78 (1010)
39.78 (1010)
39.78 (1010)
39.78 (1010)
‘C’ 17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
‘D’ 10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
‘E’ 4.38 (111)
4.38 (111) — — 4.38
(111)4.38 (111) — —
‘F’ 7.00 (178)
7.00 (178) — — 7.00
(178)7.00 (178) — —
‘G’ 11.56 (294)
11.56 (294)
11.56 (294)
11.56 (294)
16.56 (421)
16.56 (421)
16.56 (421)
16.56 (421)
‘H’ 9.13 (232)
9.13 (232)
9.13 (232)
9.13 (232)
14.13 (359)
14.13 (359)
14.13 (359)
14.13 (359)
DimensionSection Depth15”
Wide20”
Wide
‘A’ 25.12 (638)
30.12 (765)
‘B’ 21.35 (578)
26.35 (705)
‘C’ 15.00 (381)
20.00 (508)
‘D’ 12.65 (321)
15.15 (385)
‘E’ 7.41 (188)
12.41 (315)
44 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Figure 150 - 10 in. Wide Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12 Top View
DimensionSection Depth15”
Wide20”
Wide
‘A’ 14.86 (377)
19.86 (504)
‘B’ 12.71 (323)
17.71 (450)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 45
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
(a)
(a) Optional ground bus location. The front face of the 1/4 in. ground bus is located 7.41 in. (188 mm) from the cabinet front. Incoming cable pull is not correctly represented in the diagram.
Figure 151 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional External Mounting Channels, Single Section, Top View(a)
Figure 152 - Standard and Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional External Mounting Channels, Back-to-Back Construction, Top View(a)
Dimensions are shown as in. (mm)
Dimension15” Deep 20” Deep
20” Wide
25” Wide
30” Wide
35” Wide
20” Wide
25” Wide
30” Wide
35” Wide
‘A’ 20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
‘B’ 15.00 (381)
15.00 (381)
15.00 (381)
15.00 (381)
20.00 (508)
20.00 (508)
20.00 (508)
20.00 (508)
‘C’ 17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
‘D’ 10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
‘E’ 4.38 (111)
4.38 (111) — — 4.38
(111)4.38 (111) — —
‘F’ 7.00 (178)
7.00 (178) — — 7.00
(178)7.00 (178) — —
‘G’ 11.56 (294)
11.56 (294)
11.56 (294)
11.56 (294)
16.56 (421)
16.56 (421)
16.56 (421)
16.56 (421)
‘H’ 8.46 (215)
8.46 (215)
8.46 (215)
8.46 (215)
13.46 (342)
13.46 (342)
13.46 (342)
13.46 (342)
Dimensions are shown as in. (mm)
Dimension15” Deep 20” Deep
20” Wide
25” Wide
30” Wide
35” Wide
20” Wide
25” Wide
30” Wide
35” Wide
‘A’ 20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
20.00 (508)
25.00 (635)
30.00 (762)
35.00 (889)
‘B’ 29.78 (756)
29.78 (756)
29.78 (756)
29.78 (756)
39.78 (1010)
39.78 (1010)
39.78 (1010)
39.78 (1010)
‘C’ 17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
17.72 (450)
22.72 (577)
27.72 (704)
32.72 (831)
‘D’ 10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
10.00 (254)
12.50 (318)
15.00 (381)
17.50 (445)
‘E’ 4.38 (111)
4.38 (111) — — 4.38
(111)4.38 (111) — —
‘F’ 7.00 (178)
7.00 (178) — — 7.00
(178)7.00 (178) — —
‘G’ 11.56 (294)
11.56 (294)
11.56 (294)
11.56 (294)
16.56 (421)
16.56 (421)
16.56 (421)
16.56 (421)
‘H’ 8.46 (215)
8.46 (215)
8.46 (215)
8.46 (215)
13.46 (342)
13.46 (342)
13.46 (342)
13.46 (342)
46 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Figure 153 - Standard and Incoming Line Corner Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional External Mounting Channels, Top View
Figure 154 - 10 in. Wide Incoming Line Section, Bottom Entry, NEMA Type 1, 1 (with gasket), or 12, with Optional External Mounting Channels, Top View
DimensionSection Depth15”
Wide20”
Wide
‘A’ 25.12 (638)
30.12 (765)
‘B’ 20.98 (533)
25.98 (660)
‘C’ 15.00 (381)
20.00 (508)
‘D’ 12.65 (321)
15.15 (385)
‘E’ 7.41 (188)
12.41 (315)
DimensionSection Depth15”
Wide20”
Wide
‘A’ 14.86 (377)
19.86 (504)
‘B’ 8.59 (218)
13.59 (345)
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 47
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Notes:
48 Rockwell Automation Publication 2100-TD018C-EN-P - April 2020
Rockwell Automation Publication 2100-TD018C-EN-P - April 2020 49
Bulletin 2100 CENTERLINE 2100 Motor Control Centers Mains and Incoming Lines Dimension Reference Technical Data
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at rok.auto/literature.
Resource DescriptionForm 385 - Motor Control Center Layout and Specification Specific drawings and dimensions for your MCC.Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.
Publication 2100-TD018C-EN-P - April 2020Supersedes Publication 2100-TD018B-EN-P - March 2015 Copyright © 2020 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Use these resources to access support information.
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.
Technical Support Center Find help with how-to videos, FAQs, chat, user forums, and product notification updates. rok.auto/support
Knowledgebase Access Knowledgebase articles. rok.auto/knowledgebase
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware. rok.auto/pcdc
Rockwell Automation maintains current product environmental information on its website at rok.auto/pec.
Allen-Bradley, CENTERLINE, expanding human possibility, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenkÖy, İstanbul, Tel: +90 (216) 5698400 EEE YÖnetmeliğine Uygundur