central community college center for health … addendum 3_pdfccc.pdf1742 ccc center for health and...

24
1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 1 Central Community College CENTER FOR HEALTH AND TECHNICAL SCIENCES PHASE 1 REMODEL Addendum 3 Grand Island, Nebraska 1742 Wilkins Architecture Design Planning 2908 West 39 th Street, Suite A Kearney, Nebraska 68845 Date Issued: March 26, 2017 308-237-5787 Bid Date: March 29, 2017 TO ALL BID DOCUMENT HOLDERS OF RECORD: Acknowledge receipt of this addendum by inserting its number in the space provided on the BID FORM. Failure to do so may subject Bidder to disqualification. This Addendum forms a part of the BIDDING DOCUMENTS and modifies them as follows. - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Addendum 3 1 ADDENDUM 2 Item 2: 08 8113 GLASS MARKER BOARDS The following manufacturers have been approved for the listed items. All items shall meet the requirements of the construction documents, specifications and are subject for review during shop drawing submittal: Specialty Glass Products, Grand Rapids, MI, (616) 784-5500, www.specialtyglass.biz GlassArt Design, Minneapolis, MN, (612) 870-0247, www.glassartdesign.com Addendum 3 2 SPECIFICATION SECTION 01 2100 ALLOWANCES At paragraph 1.5, Item B. Interior Room Sign allowance, change allowance sum to amount $18,239.90 in lieu of $0.00. Add attached equipment list in its entirety. Addendum 3 2 Specification Section 233113 Metal Ducts and Accessories Add fire dampers to the specification section. Add the following subsection 2.1.6: 1. Fire and Smoke Dampers a. Air Balance b. American Warming c. Carnes d. Cesco e. Greenheck f. Louvers and Dampers, Inc. g. Nailor h. Penn i. Pottorff j. Prefco k. Ruskin l. Vent Products Add the following subsection 2.13: 2.13 FIRE DAMPERS A. General: Labeled to UL 555 6. 1-1/2 hour fire rating with 165ºF fusible link unless otherwise indicated. Where wall or ceiling rating requires longer more than 1-1/2 hour rating, provide appropriate rated dampers. Where application requires higher temperature rating, use appropriate temperature rating.

Upload: ngocong

Post on 08-May-2018

222 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 1

Central Community College CENTER FOR HEALTH AND TECHNICAL SCIENCES

PHASE 1 REMODEL Addendum 3

Grand Island, Nebraska

1742 Wilkins Architecture Design Planning 2908 West 39th Street, Suite A Kearney, Nebraska 68845 Date Issued: March 26, 2017 308-237-5787 Bid Date: March 29, 2017 TO ALL BID DOCUMENT HOLDERS OF RECORD:

Acknowledge receipt of this addendum by inserting its number in the space provided on the BID FORM. Failure to do so may subject Bidder to disqualification. This Addendum forms a part of the BIDDING DOCUMENTS and modifies them as follows.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Addendum 3 – 1 ADDENDUM 2 – Item 2: 08 8113 GLASS MARKER BOARDS The following manufacturers have been approved for the listed items. All items shall

meet the requirements of the construction documents, specifications and are subject for review during shop drawing submittal: Specialty Glass Products, Grand Rapids, MI, (616) 784-5500, www.specialtyglass.biz

GlassArt Design, Minneapolis, MN, (612) 870-0247, www.glassartdesign.com Addendum 3 – 2 SPECIFICATION SECTION 01 2100 – ALLOWANCES At paragraph 1.5, Item B. Interior Room Sign allowance, change allowance sum to

amount $18,239.90 in lieu of $0.00. Add attached equipment list in its entirety. Addendum 3 – 2 Specification Section 233113 Metal Ducts and Accessories Add fire dampers to the specification section.

Add the following subsection 2.1.6:

1. Fire and Smoke Dampers a. Air Balance b. American Warming c. Carnes d. Cesco e. Greenheck f. Louvers and Dampers, Inc. g. Nailor h. Penn i. Pottorff j. Prefco k. Ruskin l. Vent Products

Add the following subsection 2.13:

2.13 FIRE DAMPERS A. General: Labeled to UL 555

6. 1-1/2 hour fire rating with 165ºF fusible link unless otherwise indicated. Where wall or ceiling rating requires longer more than 1-1/2 hour rating, provide appropriate rated dampers. Where application requires higher temperature rating, use appropriate temperature rating.

Page 2: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2

7. All fire dampers located in ducted supply or return ductwork shall be rated for dynamic closure unless otherwise noted.

8. Dynamic fire dampers shall be rated for minimum velocity of 2000 fpm. When duct velocity exceeds 2000 fpm, use appropriate velocity rating.

9. Static rated dampers may be used only where HVAC systems are automatically shut down in the event of a fire or for transfer duct openings in walls or partitions.

B. Frame: SMACNA Type A with blades in airstream; fabricated with roll-formed, 0.034-inch- thick galvanized steel; with mitered and interlocking corners. Allowed only if duct free area loss is less than 5%.

C. Frame: SMACNA Type B with blades out of airstream; fabricated with roll-formed, 0.034-inch- thick galvanized steel; with mitered and interlocking corners.

D. Mounting Sleeve: Factory- or field-installed galvanized, sheet steel. 1. Minimum Thickness: 0.052 inch or 0.138 inch thick as indicated, and

length to suit application. 2. Exceptions: Omit sleeve where damper frame width permits direct

attachment of perimeter mounting angles on each side of wall or floor, and thickness of damper frame complies with sleeve requirements.

E. Mounting Orientation: Vertical or horizontal as indicated. F. Blades: Roll-formed, interlocking, 0.034-inch- thick, galvanized, sheet steel. In

place of interlocking blades, use full-length, 0.034-inch- thick, galvanized steel blade connectors.

G. Horizontal Dampers: Include a blade lock and stainless-steel negator closure spring.

Add the following subsection 3.2.M: M. Fire-Rated Partition Penetrations: Where ducts pass through interior partitions

and exterior walls, install appropriately rated fire damper, sleeve, and fire-stopping sealant. Contractor shall be responsible to coordinate appropriately rated fire damper with supplier and engineer. All fire dampers shall be dynamically rated unless otherwise approved by Engineer and Authority Having Jurisdiction.

Addendum 3 – 4 Sheet C3.0 Grading Plan Delete note 8 - “All areas not built upon shall be seeded in accordance with

specifications.” College personnel will seed disturbed areas after construction is complete.

Addendum 3 – 4 Sheet A1.0 Floor Plan – Ground Floor See attached sketch ASK-02 CONCRETE PATCHING for extents of new concrete to

coordinate with new plumbing work. Addendum 3 – 5 Sheet S1.1 Structural Notes & Design Data At DESIGN LOADS: ROOF: modify Flat Roof Snow to be 30 psf Addendum 3 – 6 Sheet S1.1 Structural Notes & Design Data At DESIGN LOADS: WIND LOADS: modify Wind Speed to be 120 MPH Addendum 3 – 7 Sheet S1.1 Structural Notes & Design Data At CONTINUOUS FOOTING SCHEDULE: modify depth of CF1 to 3’-4 in lieu of current

3’-0 Addendum 3 – 8 Sheet S1.1 Structural Notes & Design Data At PAD FOORING SCHEDULE: modify Pad footing schedule to attached sketch (SK-1) Addendum 3 – 9 Sheet MD1.1 Mechanical Demolition Plan Revise note 11 to include capping existing sanitary piping and abandonment of unused

sanitary below grade. See MSK-4. Addendum 3 – 10 Sheet M1.1 HVAC Plan Add fire dampers at duct penetrations of Storage / 980 wall. See MSK-5.

Page 3: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 3

Addendum 3 – 11 Sheet M2.1 Mechanical Piping and Plumbing Plan Add cap at existing sanitary piping. See MSK-6. Addendum 3 – 12 Sheet E2.1 Power Plan Delete card reader in Corridor 970. Addendum 3 – 13 Sheet E3.1 Special Systems Plan Delete card reader in Corridor 970.

Page 4: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Customer #: C01033

5849 Peachtree RoadAtlanta, GA 30341

P (800) 445-4796; P (770) 921-5566F (770) 279-1327

Made in the USA Veteran Owned

Message Schedule Project Number: F43305Mar. 21, 2018

CCC- GI CIT RenovationUnless otherwise noted, the specifications below will be used for this project.

Frame Color:

Shape:

Insert color:

Typestyle:

Letter Color:

#08 - Black

Square/No Perimeter Stripe

#08 - Black

Arial

W - White/U&L

Incomplete Items - 18

RC Typestyle: Arial

CENTRAL COMMUNITY COLLEGE

Version: 3

RC Letter Color: B - Black

Message Special InstructionsLocation DescriptionModuleQty

1 Dimensional LetterGEM

Drafting & DesignTechnology

Arial Typestyle6" Cast Aluminum DimensionalLetters. Stud Mounted withSpacing Template Included.

1

$2,280.00Quantity: @1 $2,280.00

2 Dimensional LetterGEM

Electrical Technology Arial Typestyle6" Cast Aluminum DimensionalLetters. Stud Mounted withSpacing Template Included.

1

$1,812.50Quantity: @1 $1,812.50

3 5.5-ID 954 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

Original: 02/28/2018 Revised: 03/09/2018 Page: 1

Page 5: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Message Special InstructionsLocation DescriptionModuleQty

5.5/A Faculty SuiteLettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

$128.50Quantity: @1 $128.50

4 Dimensional LetterGEM

Faculty Suite Arial Typestyle6" Cast Aluminum DimensionalLetters. Stud Mounted withSpacing Template Included.

1

$1,095.00Quantity: @1 $1,095.00

5 10.1-ID 954 Sign Type FInnerDot Frame with BrailleTranslation Modified withOversized Backplate andBrushed Aluminum Accents.Made to Hold (1) CustomHeader and (4) Custom Strips

1

10.1-ID Raised Character(s)3

Custom Faculty SuiteLettered Header1

Custom (Message to BeDetermined)

Lettered Strip1

Custom (Message to BeDetermined)

Lettered Strip1

Custom (Message to BeDetermined)

Lettered Strip1

Custom (Message to BeDetermined)

Lettered Strip1

10.1 Made for 14-3/4" x11-3/4" OversizedBackplate

Backplate/Glass1

$379.00Quantity: @1 $379.00

6 Custom ID 955 Sign Type G4" X 18" InnerDot Frame withBraille Translation with BrushedAluminum Laminate Accent onLeft and Holds (1) CustomInsert

1

Custom ID Raised Character(s)3

Custom Conference RoomLettered Insert for 4" x 18"Frame

1

Custom For 4" x 18" FrameBackplate/Glass1

$144.00Quantity: @1 $144.00

7 Custom ID 956 Sign Type G4" X 18" InnerDot Frame withBraille Translation with BrushedAluminum Laminate Accent onLeft and Holds (1) CustomInsert

1

Original: 02/28/2018 Revised: 03/09/2018 Page: 2

Page 6: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Message Special InstructionsLocation DescriptionModuleQty

Custom ID Raised Character(s)3

Custom Conference RoomLettered Insert for 4" x 18"Frame

1

Custom For 4" x 18" FrameBackplate/Glass1

$144.00Quantity: @1 $144.00

8 5.5-ID 957 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A Break AreaLettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

$128.50Quantity: @1 $128.50

9 Custom ID 958 Sign Type G4" X 18" InnerDot Frame withBraille Translation with BrushedAluminum Laminate Accent onLeft and Holds (1) CustomInsert

1

Custom ID Raised Character(s)3

Custom Interview RoomLettered Insert for 4" x 18"Frame

1

Custom For 4" x 18" FrameBackplate/Glass1

$144.00Quantity: @1 $144.00

10 5.5-ID 959 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A Human ServicesLettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

Original: 02/28/2018 Revised: 03/09/2018 Page: 3

Page 7: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Message Special InstructionsLocation DescriptionModuleQty

$128.50Quantity: @1 $128.50

11 Dimensional LetterGEM

Human Services Arial Typestyle6" Cast Aluminum DimensionalLetters. Stud Mounted withSpacing Template Included.

1

$1,186.25Quantity: @1 $1,186.25

12 Custom ID 960 Sign Type G4" X 18" InnerDot Frame withBraille Translation with BrushedAluminum Laminate Accent onLeft and Holds (1) CustomInsert

1

Custom ID Raised Character(s)3

Custom Interview RoomLettered Insert for 4" x 18"Frame

1

Custom For 4" x 18" FrameBackplate/Glass1

$144.00Quantity: @1 $144.00

13 5.5-ID 961 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A Drafting & DesignTechnology

Lettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

$128.50Quantity: @1 $128.50

14 5.5-ID 962 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A Drafting & DesignTechnology

Lettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

Original: 02/28/2018 Revised: 03/09/2018 Page: 4

Page 8: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Message Special InstructionsLocation DescriptionModuleQty

$128.50Quantity: @1 $128.50

15 5.5-ID 963 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A Health InformationManagementServices

Lettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

$128.50Quantity: @1 $128.50

16 Dimensional LetterGEM

Health InformationManagement Services

Arial Typestyle6" Cast Aluminum DimensionalLetters. Stud Mounted withSpacing Template Included.

1

$3,177.50Quantity: @1 $3,177.50

17 5.5-ID 965 Sign Type A.Modified withOversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A ClassroomLettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

$128.50Quantity: @1 $128.50

18 8.11 Sign Type E.Top Loading Frame.

Frame1

Other Thumb Notch in Backplate1

8.11 Backplate/Glass1

$81.50Quantity: @1 $81.50

19 5.5-ID 966 Sign Type A.Modified with

InnerDot Frame with BrailleTranslation

1

Original: 02/28/2018 Revised: 03/09/2018 Page: 5

Page 9: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Message Special InstructionsLocation DescriptionModuleQty

Oversized Backplatewith 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

5.5-ID Raised Character(s)3

5.5/A Electrical TechnologyLab

Lettered Insert1

5.5 Made for 7-1/2" x8-3/4" OversizedBackplate

Backplate/Glass1

$128.50Quantity: @1 $128.50

20 5.5-ID 968InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A StorageLettered Insert1

$68.75Quantity: @1 $68.75

22 5.5-ID 969InnerDot Frame with BrailleTranslation

1

5.5-ID Raised Character(s)3

5.5/A Tool RoomLettered Insert1

$68.75Quantity: @1 $68.75

23 33.5SD (Message to BeDetermined)

2" Brushed AluminumVinyl Accent at Bottom

Double-Sided Ceiling Mount11-1/2" x 36" x 1-3/4"

1

33.5SD (Message to BeDetermined)

2" Brushed AluminumVinyl Accent at Bottom

Double-Sided Ceiling Mount11-1/2" x 36" x 1-3/4"

Other Vinyl Arrow1

Other Vinyl Symbol1

Other Additional Copy1

$657.50Quantity: @1 $657.50

24 15.0 Frame Modified withOversized Backplateand 2" BrushedAluminum Top Accentand 1" BrushedAluminum BottomAccent

Frame1

15.0/A (Message to BeDetermined)

Lettered Header1

15.0/B TBD Lettered Strip1

Original: 02/28/2018 Revised: 03/09/2018 Page: 6

Page 10: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Message Special InstructionsLocation DescriptionModuleQty

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/B TBDLettered Strip1

15.0/C (Message to BeDetermined)

Lettered Base1

$805.75Quantity: @1 $805.75

Original: 02/28/2018 Revised: 03/09/2018 Page: 7

Page 11: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

Terms:

UNLESS OTHERWISE SPECIFIED,ALL QUOTATIONS ARE SUBJECTTO STANDARD TERMS ANDCONDITIONS

Interior Signage Total

INTERIOR PROJECT TOTAL

$660.82

$13,216.50

$462.58

Net 10 Days

[Does not include sales tax]

$150.00Film Set-Up Fee

Installation includes one trip only, no removal, no patch, no paint. If additional trip is needed to complete install due towall(s)/building not ready to receive signage additional fees willapply for additional trip(s) to complete install.

$3,750.00

FREIGHT COSTS ARE PREPAID ANDADDED AT TIME OF INVOICING.

Delivery/Freight

SubTotal $14,489.90INNERFACE COMPLIES WITH CURRENTADA STANDARDS

Freight is billed as shown unlessNext Day Air is requested. Next Dayfreight is billed as charged by thecarrier.

Handling

$18,239.90

Original: 02/28/2018 Revised: 03/09/2018 Page: 8

Page 12: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

TERMS AND CONDITIONS: 1. This quotation is subject to 30 day acceptance and delivery within 180 days of date shown on quotation unlessotherwise indicated. Price and delivery after expiration date are subject to Factory approval. 2. Delivery Schedule is estimated and is calculated from date of receipt of approval from customer of all shopdrawings, submittals, samples, etc., and subject to production schedule at the time of manufacture. Production time isestimated at time of quotation and may be amended upon order entry based upon workload at the time. 3. Prices are based on the use of INNERFACE standard letter styles, spacing, layouts, colors, finishes, materials, etc.,unless otherwise indicated. 4. This quotation is referred to and made an integral part of any contract between the Customer and INNERFACEArchitectural Signage, Inc. Terms contradictory to this quotation must be made in writing and signed by an officer ofINNERFACE Architectural Signage, Inc. and Customer. 5. Cost of licenses, permits, or fees not specifically noted in proposal are not included. 6. This quotation does not include mounting fasteners and hardware unless so stated. 7. Sizes and quantities are determined from bid documents provided INNERFACE Architectural Signage, Inc.INNERFACE Architectural Signage, Inc. does not guarantee the correctness of sizes or quantities, if those items areshown in this quotation. If requirements vary from those shown, this quotation is subject to revision to conform to thefinal requirements. 8. Quotations offered on products manufactured by companies other than INNERFACE Architectural Signage, Inc.(where INNERFACE Architectural Signage, Inc. is acting as Supplier), are not valid, except as Estimates, until suchquotation is accepted and confirmed by respective manufacturer. This applies only to products not manufactured byINNERFACE Architectural Signage, Inc. 9. Estimates are for reference and/or budget purposes only and are not binding in any way whatsoever.10. INNERFACE Architectural Signage, Inc. reserves the right to file property liens on any projects resulting from thisQuotation, provided that all necessary Notices of Liens are filed by INNERFACE Architectural Signage, Inc.11. State and Local Taxes are not included unless specifically shown, but may be added to final invoice unless a bonafide certificate of exemption is submitted.12. If payment within terms is not met, the customer shall be responsible for interest charges of 1/2 percent per monthand any collection and/or reasonable attorney's fees incurred in obtaining full payment. INNERFACE reserves the rightto withhold processing orders for any account for which past due balances exist.13. In no case shall the total liability of INNERFACE Architectural Signage, Inc. or its affiliates for any design andplanning errors or omissions exceed the value of the contract covered by this Quotation.14. Order acknowledgment or INNERFACE order forms will be deemed by customer and by INNERFACE ArchitecturalSignage, Inc. as final expression of their agreement and will be deemed the exclusive statement of the terms thereof,unless notified by INNERFACE Architectural Signage, Inc. in writing.15. INNERFACE Officers, staff, representatives and/or consultations assume no legal responsibility for interpretationsof The Americans with Disabilities Act (ADA). Neither is liability assumed for the outcome of decisions, contracts,commitments or obligation made on the basis of interpretation of ADA.

Notes: Revisions to the Message Schedule and/or Quotation may require pricing changes. Final Message Schedule andQuotation must be approved by client prior to order entry. Unless specifically stated, prices quoted are for INNERFACEstandard colors, sizes, formats, typestyles, fabrication and mounting methods.

INNERFACE REPRESENTATIVE: QUOTATION ACCEPTED BY:

Project Manager: Megan Dolan Authorized Signature

Printed or Typed Name

QUOTATION IS SUBJECT TO 30 DAY ACCEPTANCE

C01033

Mar. 21, 2018 - 8:53:13 AM

Message Schedule

If you have questions regarding this message schedule, contact Innerface Customer Service at 800-445-4796

CENTRAL COMMUNITY COLLEGE - Project: F43305

CCC- GI CIT Renovation

INTERIOR PROJECT TOTAL $18,239.90

Page 13: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

SECTION 23 3113

METAL DUCTS AND ACCESSORIES

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Condi-tions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes metal ducts and accessories for heating, ventilating, and air-conditioning systems, diffusers, registers and grilles, and gas vents.

1.3 DEFINITIONS

A. Pressure Classification for Ductwork: As defined by to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible” and applicable codes. 1. Low Pressure: Maximum 2500 fpm velocity; maximum 2.0” WG positive or –2.0” WG

negative static pressure class.

1.4 SUBMITTALS

A. Product data including product construction, installation instructions and performance data for the following: 1. Sealing materials. 2. Backdraft dampers. 3. Manual-volume dampers. 4. Fire and smoke dampers. 5. Duct-mounted access doors and panels. 6. Flexible ducts 7. Diffuser’s Registers & Grilles 8. Hangers and Supports

B. No requirement for shop drawings if after examining the contract documents and actual condi-tions, contractor agrees system can be installed as shown.

C. Record Drawings: Indicate actual routing, fitting details, reinforcement, support, and installed accessories and devices.

D. See “Submittal Schedule” located at the end of Section 23 0100 – General Requirements for Mechanical Systems.

1.5 QUALITY ASSURANCE

A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," unless oth-erwise indicated.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the fol-lowing: 1. Backdraft and Volume Dampers

a. Greenheck b. Air Balance c. American Warming d. Cesco e. Louvers and Dampers, Inc. f. Penn g. Prefco h. Carnes i. Ruskin j. Vent Products

Page 14: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

2. Flexible Ducts a. Flexible Air Products b. Flexmaster c. Thermaflex d. Certainteed e. Wiremold f. General Flex Corp g. H.K. Porter

3. Duct Access Doors a. Air Balance b. American Warming c. Cesco d. Ventfrabrics e. Penn f. Prefco g. Carnes h. Ruskin i. Kees j. United McGill k. Nailor Industries

4. Diffusers, Registers, Grilles a. Carnes b. Krueger c. Price d. Tuttle and Bailey e. Metal-Aire f. Titus g. Hart and Cooly h. Anemostat i. Nailor Industies

5. Duct Hangers & Supports: a. Ductmate Industries, Inc. b. Duro Dyne c. Eberl Iron Works, Inc. d. Gripple e. Miro Industries, Inc. f. The Pate Company g. PHP Systems / Design

6. Fire and Smoke Dampers a. Air Balance b. American Warming c. Carnes d. Cesco e. Greenheck f. Louvers and Dampers, Inc. g. Nailor h. Penn i. Pottorff j. Prefco k. Ruskin l. Vent Products

2.2 SHEET METAL MATERIALS

A. Galvanized, Sheet Steel: Lock-forming quality; ASTM A 653/A 653M, G90 coating designation; mill-phosphatized finish for surfaces of ducts exposed to view.

Page 15: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

B. Reinforcement Shapes and Plates: Galvanized steel reinforcement where installed on galva-nized, sheet metal ducts; compatible materials for aluminum and stainless-steel ducts.

C. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for 36-inch length or less; 3/8-inch minimum diameter for lengths longer than 36 inches.

2.3 SEALANT MATERIALS

A. Duct Sealant: UL classified, non-combustible, flame spread 25 or less, smoke developed rating of 540 or less, resistant to water, pressure rupture rating of 16” WG minimum, suitable for use alone or with tape, application an operational temperature ranges appropriate for usage.

2.4 MANUFACTURED DUCT JOINTS

A. Manufactured duct joining system to consistent of roll formed angles, corner pieces, metal cleats and gasket material. Construct and join ductwork in accordance with the latest SMACNA test data and joint reinforcement schedule corresponding to duct gauge used. Corners to be down set design, no bolt design except bolting is required for medium pressure applications. Reinforcements requirement for sheet metal to comply with latest SMACNA for manufactured duct Joining technique appropriate to get to pressure class.

2.5 MANUAL-VOLUME DAMPERS

A. Fabricate in accordance with latest edition of SMACNA HVAC Duct Construction Standards – Metal and Flexible and as indicated.

B. Fabricate single blade dampers for duct sizes 9 ½: high x 30” width maximum. Single blade dampers to have spring end bearing regulator. Provide end brace for static pressure greater than 2.0” WG. Provide end brace for static pressure greater than 2.0”.

C. Fabricate multi-blade damper of opposed blade pattern using minimum 16 gauge steel with maximum blade sizes 6” x 48”. Where width exceeds 48”, provide regulator at both ends. As-semble center and edge crimped blades in 16 gauge channel frame with suitable hardware. Blades and frame to be galvanized or prime coated steel except where indicated for special ap-plication.

D. Provide end bearings with end seals for pressure class required except in round duct 12” in di-ameter and smaller.

2.6 TURNING VANES

A. Fabricate to comply with SMACNA's "HVAC Duct Construction Standards--Metal and Flexible."

B. Manufactured Turning Vanes: Fabricate of 1-1/2-inch- wide, curved blades set 3/4 inch o.c.; support with bars perpendicular to blades set 2 inches on center; and set into side strips suita-ble for mounting in ducts.

2.7 DUCT-MOUNTED ACCESS DOORS AND PANELS

A. General: Fabricate doors and panels airtight and suitable for duct pressure class.

B. Frame: Galvanized, sheet steel, with bend-over tabs and foam gaskets.

C. Door: Double-wall, galvanized, sheet metal construction with insulation fill and thickness, and number of hinges and locks as indicated for duct pressure class. Include vision panel where indicated. Include 1-by-1-inch butt or piano hinge and cam latches.

D. Seal around frame attachment to duct and door to frame with neoprene or foam rubber.

E. Insulation: 1-inch- thick, fibrous-glass or polystyrene-foam board.

F. Label: Label access doors at fire and smoke damper locations per NFPA 90A.

2.8 FLEXIBLE CONNECTORS

A. General: Flame-retarded or noncombustible fabrics, coatings, and adhesives complying with UL 181, Class 1.

B. Neoprene double-coated woven glass fibber fabric in accordance with NFPA 90A, suitable for temperatures and pressures of application, approximately 6” wide, crimped into metal edge strip.

Page 16: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

2.9 FLEXIBLE DUCTS

A. General: Comply with UL 181, Class 1.

B. Factory-fabricated, insulated, round duct, with an outer jacket enclosing glass-fiber insulation around a continuous inner liner. 1. Reinforcement: Steel-wire helix encapsulated in inner liner. 2. Outer Jacket: Polyethylene film or Glass-reinforced, silver Mylar with a continuous hang-

ing tab, integral fibrous-glass tape, and nylon hanging cord. 3. Inner Liner: Polyethylene film.

C. Pressure Rating: 4-inch wg positive, 3/4-inch wg negative.

D. Minimum R-value: R-5 for ducts inside building envelope. R-8 for ducts in unconditioned spaces.

2.10 DIFFUSER, REGISTERS AND GRILLES

A. General: Sizes, types and capacities as indicated. Verify ceiling and wall frame types and di-mensions from architectural drawings. Factory baked enamel finish with color selected by Ar-chitect unless otherwise indicated.

B. Diffusers: Circular, square, or rectangular air distribution outlet comprised of deflecting mem-bers discharging supply air in various directions and planes and arranged to promote mixing of primary air with secondary room air. Opposed blade dampers.

C. Grilles: Streamlined blades, single or double deflection as indicated.

D. Registers: Combination grille and opposed damper assembly.

2.11 ACCESSORY HARDWARE

A. Flexible Duct Clamps: Stainless-steel band with cadmium-plated hex screw to tighten band with a worm-gear action, in sizes 3 to 18 inches to suit duct size.

B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline and grease.

2.12 HANGERS AND SUPPORTS

A. Building Attachments: Concrete inserts, powder-actuated fasteners, or structural-steel fasten-ers appropriate for building materials.

B. Hanger Rods for Noncorrosive Environments: Cadmium-plated steel rods and nuts.

C. Hanger Rods for Corrosive Environments: Electrogalvanized, all-thread rods or galvanized rods with threads painted with zinc-chromate primer after installation.

D. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 5-1, "Rectangular Duct Hangers Minimum Size," and Table 5-2, "Minimum Hanger Sizes for Round Duct."

E. Steel Cables for Galvanized-Steel Ducts: Galvanized steel complying with ASTM A 603.

F. Steel Cable End Connections: Cadmium-plated steel assemblies with brackets, swivel, and bolts designed for duct hanger service; with an automatic-locking and clamping device.

G. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible with duct materials.

H. Trapeze and Riser Supports: 1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates. 2. Supports for Stainless-Steel Ducts: Stainless-steel shapes and plates. 3. Supports for Aluminum Ducts: Aluminum or galvanized steel coated with zinc chromate.

2.13 FIRE DAMPERS

A. General: Labeled to UL 555 1. 1-1/2 hour fire rating with 165ºF fusible link unless otherwise indicated. Where wall or

ceiling rating requires longer more than 1-1/2 hour rating, provide appropriate rated dampers. Where application requires higher temperature rating, use appropriate temper-ature rating.

Page 17: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

2. All fire dampers located in ducted supply or return ductwork shall be rated for dynamic closure unless otherwise noted.

3. Dynamic fire dampers shall be rated for minimum velocity of 2000 fpm. When duct veloc-ity exceeds 2000 fpm, use appropriate velocity rating.

4. Static rated dampers may be used only where HVAC systems are automatically shut down in the event of a fire or for transfer duct openings in walls or partitions.

B. Frame: SMACNA Type A with blades in airstream; fabricated with roll-formed, 0.034-inch- thick galvanized steel; with mitered and interlocking corners. Allowed only if duct free area loss is less than 5%.

C. Frame: SMACNA Type B with blades out of airstream; fabricated with roll-formed, 0.034-inch- thick galvanized steel; with mitered and interlocking corners.

D. Mounting Sleeve: Factory- or field-installed galvanized, sheet steel. 1. Minimum Thickness: 0.052 inch or 0.138 inch thick as indicated, and length to suit appli-

cation. 2. Exceptions: Omit sleeve where damper frame width permits direct attachment of perime-

ter mounting angles on each side of wall or floor, and thickness of damper frame com-plies with sleeve requirements.

E. Mounting Orientation: Vertical or horizontal as indicated. F. Blades: Roll-formed, interlocking, 0.034-inch- thick, galvanized, sheet steel. In place of inter-

locking blades, use full-length, 0.034-inch- thick, galvanized steel blade connectors. G. Horizontal Dampers: Include a blade lock and stainless-steel negator closure spring.

PART 3 - EXECUTION

3.1 DUCT FABRICATION

A. General: Fabricate ducts, elbows, transitions, offsets, branch connections, and other construc-tion with galvanized, sheet steel, according to SMACNA's "HVAC Duct Construction Standards--Metal and Flexible." Comply with requirements for metal thickness, reinforcing types and in-tervals, tie-rod applications, and joint types and intervals.

B. Low Pressure duct 1. Seams and Joints (Rectangular Ducts): Longitudinal seams shall be Pittsburg lock,

grooved seams or button punch snap lock. Transverse joints shall be drive slip. Joints 36” and larger shall be manufactured duct joining system with downset corners, or SMACNA T-25 formed on flanges with corner and cleat. Contractor option on smaller sizes

2. Seams and Joints (Concealed Round Duct): Transverse joints in low velocity concealed round ducts shall be slip type secured with sheet metal screws equally spaced on 6” cen-ters maximum with a minimum of three screws per joint. Joints shall be sealed with mas-tic during joining. Exposed inside edge of duct at joint shall point in direction of airflow. All duct joints exposed to weather shall be caulked weathertight.

3. Seams and joints (Exposed Round Duct): Longitudinal seams shall be lock type spiral or grooved seams rolled spirally. Transverse joints shall be slip type up to 36” in diameter and shall be sealed with mastic during joining. Flanged and gasketed joints shall be used on size larger than 36” diameter.

C. Rectangular fittings: Construct tees, bends and elbows with centerline radius of 1-1/2 times width of duct.

D. Round Elbows: Fabricate in die-formed, gored, pleated, or mitered construction. Fabricate bend radius of die-formed, gored, and pleated elbows one and one-half times elbow diameter. Unless elbow construction type is indicated, fabricate elbows as follows:

E. Static-Pressure Classifications: Unless otherwise indicated, construct ducts to low pressure standards.

F. Cross Breaking or Cross Beading: Cross break or cross bead duct sides 19 inches and larger and 0.0359 inch thick or less, with more than 10 sq. ft. of unbraced panel area, unless ducts are lined.

G. Sizes shown on plans are inside clear dimensions. Ductwork utilizing duct liner shall be in-creased in size to accommodate the duct liner thickness.

Page 18: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

3.2 DUCT INSTALLATION

A. Drawings indicate general arrangement of ducts, fittings, and accessories. Minor modifications to route, size and shape of duct may be required to meet structural and other interference. Changes which could affect system performance shall be reviewed by Architect/Engineer prior to fabrication or installation of duct.

B. Construct and install each duct system for the specific duct pressure classification indicated.

C. Install ducts with fewest possible joints.

D. Install fabricated fittings for changes in directions, changes in size and shape, and connections.

E. Install couplings tight to duct wall surface with a minimum of projections into duct.

F. Install ducts, unless otherwise indicated, vertically and horizontally, parallel and perpendicular to building lines; avoid diagonal runs.

G. Install ducts close to walls, overhead construction, columns, and other structural and perma-nent enclosure elements of building.

H. Install ducts with a clearance of 1 inch, plus allowance for insulation thickness.

I. Conceal ducts from view in finished spaces. Do not encase horizontal runs in solid partitions, unless specifically indicated.

J. Coordinate layout with suspended ceiling, fire- and smoke-control dampers, lighting layouts, and similar finished work.

K. Electrical Equipment Spaces: Route ductwork to avoid passing through transformer vaults and electrical equipment spaces and enclosures.

L. Non-Fire-Rated Partition Penetrations: Where ducts pass through interior partitions and exteri-or walls, and are exposed to view, conceal space between construction opening and duct or duct insulation with sheet metal flanges of same metal thickness as duct. Overlap opening on four sides by at least 1-1/2 inches.

M. Fire-Rated Partition Penetrations: Where ducts pass through interior partitions and exterior walls, install appropriately rated fire damper, sleeve, and fire-stopping sealant. Contractor shall be responsible to coordinate appropriately rated fire damper with supplier and engineer. All fire dampers shall be dynamically rated unless otherwise approved by Engineer and Authority Hav-ing Jurisdiction.

3.3 HANGER AND SUPPORT INSTALLATION

A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 5, "Hangers and Supports."

B. Building Attachments: Concrete inserts, powder-actuated fasteners, or structural-steel fasteners appropriate for construction materials to which hangers are being attached. 1. Where practical, install concrete inserts before placing concrete. 2. Install powder-actuated concrete fasteners after concrete is placed and completely cured. 3. Use powder-actuated concrete fasteners for standard-weight aggregate concretes or for

slabs more than 4 inches thick. 4. Do not use powder-actuated concrete fasteners for lightweight-aggregate concretes or for

slabs less than 4 inches thick. 5. Do not use powder-actuated concrete fasteners for seismic restraints.

C. Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 5-1, "Rectangular Duct Hangers Minimum Size," and Table 5-2, "Minimum Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports with-in 24 inches of each elbow and within 48 inches of each branch intersection.

D. Hangers Exposed to View: Threaded rod and angle or channel supports.

E. Install upper attachments to structures. Select and size upper attachments with pull-out, ten-sion, and shear capacities appropriate for supported loads and building materials where used.

3.4 PROTECTION OF DUCTWORK ON SITE

Page 19: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

METAL DUCTS AND ACCESSORIES 3/18 Wilkins Architecture Design Planning, L.L.C. WilkinsADP 1742

A. Ductwork stored on site as well as installed ductwork that is left open to construction activities shall be covered. Provide protective coverings on open ends of ductwork to prevent excessive accumulation of dust and debris on interior surfaces. Protection and storage of ductwork shall be in accordance to SMACNA's 'Duct Cleanliness for New Construction'.

3.5 SEAM AND JOINT SEALING

A. Low Pressure Ductwork: Seal per SMACNA Seal Class “C”. Sealant material shall be installed per manufacturer’s recommendations.

B. Seal externally insulated ducts before insulation installation.

3.6 HANGING AND SUPPORTING

A. Install rigid round, rectangular, and flat-oval metal duct with support systems indicated in SMACNA's "HVAC Duct Construction Standards--Metal and Flexible."

B. Support horizontal ducts within 24 inches of each elbow and within 48 inches of each branch in-tersection.

C. Support vertical ducts at a maximum interval of 16 feet and at each floor.

3.7 DUCT ACCESSORY INSTALLATION

A. Install duct accessories according to applicable details shown in SMACNA's "HVAC Duct Con-struction Standards--Metal and Flexible" for metal ducts.

B. Install volume dampers at locations indicated and at all branch take-offs to air outlets and inlets.

C. Provide fire and smoke dampers at locations indicated and where required by applicable codes. Install fire and smoke dampers according to manufacturer's UL-approved written instructions.

D. Provide turning vanes in all mitered elbows and duct turns.

E. Install duct access panels for access to inlet side of coils, equipment, control dampers, fire dampers, and smoke dampers.

F. Final connections to air outlets and terminal units may be made with flexible duct. Install flexi-ble ducts with metal collars or sleeves with draw bands. Length of flexible duct shall not ex-ceed 24”. Change of direction is not allowed with flexible ductwork.

G. Provide flexible connections to motor driven equipment. Secure fabric to duct or fan collar with 3/16” rivets space not more than 5” on center. Provide thrust restraints so that connections are not in tension with equipment in operation.

H. Install diffusers, registers, and grilles level and plumb, according to manufacturer's written in-structions, Coordination Drawings, original design, and referenced standards. Examine areas where diffusers, registers, and grilles are to be installed for compliance with requirements for installation tolerances and other conditions affecting performance of equipment. Do not pro-ceed with installation until unsatisfactory conditions have been corrected.

I. Install gas vents, chimneys, and stacks according to manufacturer's written instructions and NFPA 54. Locate to comply with minimum clearances from combustibles.

3.8 ADJUSTING

A. Adjust volume-control dampers in ducts, outlets, and inlets to achieve design airflow. Refer to Division 230593 Section "Testing, Adjusting, and Balancing" for detailed procedures.

B. Adjust duct accessories for proper settings and actions.

3.9 CLEANING

A. After completing system installation, inspect the system. Vacuum ducts before final acceptance to remove dust and debris.

B. After installation of diffusers, registers, and grilles, inspect exposed finish. Clean exposed sur-faces to remove burrs, dirt, and smudges. Replace diffusers, registers, and grilles that have damaged finishes.

C. Clean exposed ductwork surfaces to remove burrs, dirt, and smudges. Repair dented or dam-aged exposed ductwork and touch up paint defects or damage.

kaylee.troyer
Snapshot
Page 20: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

11 1613 14 15

G G

D

C

B

12 17 18 19 20

E

F

H H

J J

15'14'11.3 12.5 13.8 14.8

H.9H.9

H.10 H.10

10.9

ELECTRICAL

TECHNOLOGY

LAB

966

STORAGE

980

CLASSROOM

965

CORRIDOR

952

BREAK AREA

957

FACULTY

SUITE

954HUMAN

SERVICES

959

INTERVIEW

ROOM

958

INTERVIEW

ROOM

960

DRAFTING

LAB

961

CORRIDOR

951

CORRIDOR

950

MECH

953

CORRIDOR

970

CLASSROOM

E976

CLASSROOM

E979

RESTROOM

E975B

WELDING/INDUSTRIAL

ACADEMY

E975

WATER MAIN

967

CONFERENCE

956

CONFERENCE

955

HEALTH

INFORMATION

MANAGEMENT

SERVICES

963

DRAFTING

LECTURE

962

WORK ROOM

964

STORAGE

968

TOOL ROOM

969

83' - 3 3/4"

19' - 1

1/2

"

25' -

0"

4' - 5 3/4"

1' -

11"

4' -

0"

4' - 0"

1' - 11"

4' -

5 3

/4"

52' - 7 7/8"

3' -

10"

6' -

0"

Sketch Number:

Copyright © 2018

WILKINS Architecture|Design|Planning L.L.C.

Project Number:

Sketch Date:Central Community College - Grand IslandCENTER FOR HEALTH & TECHNICAL SCIENCES -PHASE 1 REMODEL

1742

March 26, 2018

ASK-02CONCRETE PATCHING

Addendum No. 3

Sheet Ref: 1/A1.0

SCALE:N 1/16" = 1'-0"ASK-02

1 FLOOR PLAN - GROUND FLOOR

Page 21: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

MARK PLAN SIZE REINFORCINGDEPTH

F1 3'-4

PAD FOOTING SCHEDULE

3'-0 x 3'-0 5- #5 EACH WAY, TOP & BOTTOM

F2 3'-44'-0 x 4'-0 6- #5 EACH WAY, TOP & BOTTOM

Date Sheet No.

SK-103/26/18REVISED PAD FTG

Central Community College -

Grand IslandWILKINS ADP

Page 22: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

11 REMOVE EXISTING FLOOR DRAIN, CLEANOUT, AND CAP THE ABANDONEDSANITARY PIPING BACK AT THE MAIN. ABANDON REMAINING SANITARYPIPING THAT WILL NOT BE IN SERVICE. PATCH FLOOR TO MATCHADJACENT CONSTRUCTION. CAMERA EXISTING SANITARY MAIN TO FIELDVERIFY EXACT LOCATION AND DEPTH.

13 14 15

F

15'14'13.8 14.8

26x1

6 S

A (

E)

3

RL

/ RS

(E

)

GAS (E)

4" W

(E

)

D (E)

CO (E) 1111

Sketch Number:

L.L.C. Copyright © 2018 Project Number: Sketch Date:

Central Community College - Grand Island

CENTER FOR HEALTH & TECHNICAL SCIENCES -PHASE 1 REMODEL

1742

MSK-4MD1.1 MECHANICAL DEMOLITION PLAN

Addendum 3

03/26/18

Page 23: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

T

TT

T

T

FD FD

1615 17

H

15'14'

H.10

-

---

CLASSROOM

965

STORAGE

980

CORRIDOR

952

2

AIR COMPRESSOR (R)

1 (TYP)

GFUH (R)

F-950

225

10"Ø D-1

(4 TYP)

14x12 RA

16x12 RA

14x12 SA

100

6"Ø

D-1

G-1

900

RTU-965

4

FURNACE, SEE DETAIL

9

2

M3.1

10

ELECTRIC UNIT HEATER, SEE ELECTRICAL PLANS

11

12

14

Sketch Number:

L.L.C. Copyright © 2018 Project Number: Sketch Date:

Central Community College - Grand Island

CENTER FOR HEALTH & TECHNICAL SCIENCES -PHASE 1 REMODEL

1742

MSK-5M1.1 - HVAC PLAN

Addendum 3

03/26/18

Page 24: Central Community College CENTER FOR HEALTH … Addendum 3_pdfCCC.pdf1742 CCC Center for Health and Technical Sciences Phase 1 Remodel Addendum 3 2 7. All fire dampers located in ducted

14 15

F

15'14'13.8 14.8

HEALTH

INFORMATION

MANAGEMENT

SERVICES

963

2" CW (E)

N / E1" CW

NEW TO EXISTING CONNECTION (TYPICAL)

S-3

4" W (E)

WORK ROOM

964

1/2" CW

1/2" CW

3/4" CWN / E

CAP

Sketch Number:

L.L.C. Copyright © 2018 Project Number: Sketch Date:

Central Community College - Grand Island

CENTER FOR HEALTH & TECHNICAL SCIENCES -PHASE 1 REMODEL

1742

MSK-6M2.1 MECHANICAL PIPING ANDPLUMBING PLAN

Addendum 3

03/26/18