Certificate subject: Wind tunnel measurements wind forces on Multimount with Performa mesh trays or conduits date: June 17 th , 2020 reference: MvU/W 15390-3-NO-001 from: ir. G.M. van Uffelen, Peutz bv By order of Schneider Electric Sverige AB, Sweden, and PVX Multimount of Gorinchem, The Netherlands, boundary layer wind tunnel measurements have been undertaken into the wind loading on the Schneider Electric Performa, or Performa Palt, Mesh tray or conduits with PVX Multimount flat roof installation system and the weight that is needed to prevent this system from shifting, lifting or overturning. We have elaborated the results of our wind tunnel studies in a calculation tool. The application of our results by Schneider Electric and PVX Multimount has been checked thoroughly and matches the assumptions and findings as laid down in our report W 15390-1E-RA of June 17 th , 2020. Conformity: CUR Recommendation 103: 2005 NEN 7250: 2014 NEN-EN 1990: 2011 NEN-EN 1991-1-4: 2011 Mook, peutz bv, postbus 66, 6585 zh mook, +31 85 822 86 00, [email protected], www.peutz.nl kvk 12028033, conditions in accordance with DNR 2011, member NLingenieurs, btw NL.004933837B01, ISO-9001:2008 W 15390-3-NO-001 1

Upload: others

Post on 11-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Certificate · 2020-06-21 · Certificate subject: Wind tunnel measurements wind forces on Multimount with Performa mesh trays or conduits date: June 17th, 2020 reference: MvU/W 15390-3-NO-001

Certificates u b j e c t : Wind tunnel measurements wind forces on Multimount with Performa mesh trays or

conduitsd a t e : June 17th, 2020

r e f e r e n c e : MvU/ W 15390-3-NO-001

f r o m : ir. G.M. van Uffelen, Peutz bv

By order of Schneider Electric Sverige AB, Sweden, and PVX Multimount of Gorinchem, TheNetherlands, boundary layer wind tunnel measurements have been undertaken into the windloading on the Schneider Electric Performa, or Performa Palt, Mesh tray or conduits with PVXMultimount flat roof installation system and the weight that is needed to prevent this systemfrom shifting, lifting or overturning. We have elaborated the results of our wind tunnel studiesin a calculation tool. The application of our results by Schneider Electric and PVX Multimounthas been checked thoroughly and matches the assumptions and findings as laid down in ourreport W 15390-1E-RA of June 17th, 2020.

Conformity: CUR Recommendation 103: 2005NEN 7250: 2014NEN-EN 1990: 2011NEN-EN 1991-1-4: 2011

Mook,

peutz bv, postbus 66, 6585 zh mook, +31 85 822 86 00, [email protected], www.peutz.nl kvk 12028033, conditions in

accordance with DNR 2011, member NLingenieurs, btw NL.004933837B01, ISO-9001:2008W 15390-3-NO-001 1