certificate of approval no cf 821... · this certificate is the property of warrington...
TRANSCRIPT
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
Signed and sealed for and on behalf of CERTIFIRE
Sir Ken Knight Paul Duggan Chairman Certification Manager
WCL Impartiality Committee Warrington Certification Ltd
CERTIFICATE OF APPROVAL No CF 821
Issued: 9th December 2010
Revised: 4th December 2015
Valid to: 30th June 2019
Page 1 of 16
This is to certify that, in accordance with
TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of
SIKA DEUTSCHLAND GMBH
Kornwestheimer Strasse 103-107, D-70439 Stuttgart,Germany
Tel: 0049 7042 109 259 Fax: 0049 7042 109 261 www.protectivecoatings.de
Have been assessed against the requirements of the Technical Schedule(s)
denoted below and are approved for use subject to the conditions appended hereto:
______________________________________________________________________________
CERTIFIED PRODUCT TECHNICAL SCHEDULE
Sika® Unitherm® Platinum TS15 Intumescent Coatings for Steelwork
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 2 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
Sika® Unitherm® Platinum 1. This approval relates to the use of Sika
® Unitherm
® Platinum for the fire protection of
I-shaped steel sections as well as circular hollow sections. The precise scope is given in Tables 1 to 14 which show the total dry film thickness of Sika
® Unitherm
® Platinum
(excluding primer and top sealer) required to provide fire resistance periods in accordance with BS476: Part 21: 1987 of 15 minutes up to 90 minutes for differing sections and section factors.
2. This certification is designed to demonstrate compliance of the product or system
specifically with Approved Document B (England and Wales), Section 2 of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to be taken into account.’
3. The products are approved on the basis of:
i) Initial type testing. ii) A design appraisal against TS15. iii) Certification of quality management system to ISO 9001: 2008
iv) Inspection and surveillance of factory production control v) Audit testing
4. The data shown is applicable to steel sections galvanised or blast cleaned to Swedish
Standard SA2.5 or equivalent and primed with a suitable and compatible primer. The data shown is also applicable to steel sections blast cleaned to Swedish Standard SA2.5 or equivalent followed by direct application of Sika® Unitherm® Platinum. Specifications of surface preparations, primers and top sealers is available from Sika Deutschland GmbH whose responsibility is to ensure that Sika® Unitherm® Platinum is compatible for use in respect of both ambient and fire conditions. The total dry film thickness of primer and top sealer together may not exceed the maximum tested thickness.
5. The data shown is applicable to Sika
® Unitherm
® Platinum applied by spray to horizontal,
vertical, flexural and compression members supporting loads up to the maximum design loads specified in BS449: Part 2 as indicated in Tables 5 and 7. For other design temperatures it should be confirmed it is acceptable to utilise these temperatures prior to using the data for approval purposes.
6. The approval relates to on going production. Product and/or its immediate packaging is
identified with the manufacturers’ name, the product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate.
7. The data shown in the tables is based on assessments which comply with the criteria for
acceptability now incorporated within the CERTIFIRE scheme.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 3 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
110 0.457 75 0.876 50 0.950
115 0.468 80 0.907 55 1.134
120 0.479 85 0.938 60 1.318
125 0.490 90 0.969 65 1.503
130 0.501 95 1.000 70 1.668
135 0.512 100 1.031 75 1.757
140 0.523 105 1.062 80 1.846
145 0.534 110 1.092 85 1.935
150 0.545 115 1.123 90 2.025
155 0.556 120 1.154 95 2.114
160 0.567 125 1.185 100 2.203
165 0.578 130 1.216 105 2.292
170 0.590 135 1.247 110 2.381
175 0.601 140 1.278 115 2.471
180 0.612 145 1.309 120 2.560
185 0.623 150 1.340 125 2.649
190 0.634 155 1.371
195 0.645 160 1.402
200 0.656 165 1.433
205 0.667 170 1.464
210 0.678 175 1.495
215 0.689 180 1.526
220 0.700 185 1.557
225 0.711 190 1.588
230 0.722 195 1.619
235 0.733 200 1.650
240 0.744 205 1.685
245 0.755 210 1.720
250 0.766 215 1.755
255 0.778 220 1.790
260 0.789 225 1.826
265 0.800 230 1.861
270 0.811 235 1.896
275 0.822 240 1.931
280 0.833 245 1.966
285 0.844 250 2.001
290 0.855 255 2.036
295 0.866 260 2.071
300 0.877 265 2.106
305 0.888 270 2.141
310 0.899 275 2.177
315 0.910 280 2.212
320 0.921 285 2.247
325 0.932 290 2.282
330 0.943 295 2.317
335 0.954 300 2.352
340 0.965 305 2.387
310 2.422
315 2.457
320 2.493
325 2.528
330 2.563
335 2.598
340 2.633
I' or 'H' Shaped Sections: 350oC
15 minutes 30 minutes 45 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 1
Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 4 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
150 0.457 40 0.457 55 0.996 30 1.019
155 0.465 45 0.469 60 1.076 35 1.134
160 0.471 50 0.504 65 1.157 40 1.249
165 0.477 55 0.539 70 1.237 45 1.364
170 0.484 60 0.573 75 1.318 50 1.479
175 0.490 65 0.608 80 1.398 55 1.594
180 0.496 70 0.643 85 1.479 60 1.709
185 0.503 75 0.678 90 1.559 65 1.824
190 0.509 80 0.712 95 1.640 70 1.939
195 0.515 85 0.747 100 1.691 75 2.054
200 0.522 90 0.782 105 1.742 80 2.169
205 0.528 95 0.817 110 1.792 85 2.284
210 0.534 100 0.851 115 1.843 90 2.399
215 0.541 105 0.886 120 1.894 95 2.514
220 0.547 110 0.921 125 1.945
225 0.553 115 0.956 130 1.995
230 0.560 120 0.990 135 2.046
235 0.566 125 1.025 140 2.097
240 0.572 130 1.060 145 2.148
245 0.579 135 1.079 150 2.198
250 0.585 140 1.097 155 2.249
255 0.591 145 1.116 160 2.300
260 0.598 150 1.134 165 2.351
265 0.604 155 1.153 170 2.401
270 0.610 160 1.172 175 2.452
275 0.617 165 1.190 180 2.503
280 0.623 170 1.209 185 2.554
285 0.629 175 1.227 190 2.604
290 0.636 180 1.246 195 2.655
295 0.642 185 1.264 200 2.706
300 0.648 190 1.283 205 2.757
305 0.655 195 1.302 210 2.807
310 0.661 200 1.320 215 2.858
315 0.667 205 1.339 220 2.909
320 0.674 210 1.357 225 2.960
325 0.680 215 1.376 230 3.010
330 0.686 220 1.395 235 3.061
335 0.693 225 1.413 240 3.112
340 0.699 230 1.432 245 3.163
235 1.450 250 3.213
240 1.469
245 1.488
250 1.506
255 1.525
260 1.543
265 1.562
270 1.581
275 1.599
280 1.618
285 1.636
290 1.664
295 1.694
300 1.725
305 1.755
310 1.785
315 1.816
320 1.846
325 1.876
330 1.906
335 1.937
340 1.967
I' or 'H' Shaped Sections: 400oC
15 minutes 30 minutes 45 minutes 60 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 2
Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 5 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
250 0.478 85 0.457 40 0.816 45 1.020
255 0.483 90 0.481 45 0.849 50 1.120
260 0.487 95 0.505 50 0.882 55 1.220
265 0.491 100 0.530 55 0.915 60 1.320
270 0.496 105 0.554 60 0.948 65 1.420
275 0.500 110 0.579 65 0.981 70 1.520
280 0.505 115 0.603 70 1.014 75 1.610
285 0.509 120 0.628 75 1.047 80 1.684
290 0.514 125 0.652 80 1.080 85 1.759
295 0.518 130 0.677 85 1.113 90 1.833
300 0.522 135 0.702 90 1.146 95 1.908
305 0.527 140 0.726 95 1.178 100 1.982
310 0.531 145 0.751 100 1.211 105 2.057
315 0.536 150 0.775 105 1.244 110 2.131
320 0.540 155 0.800 110 1.277 115 2.206
325 0.544 160 0.824 115 1.310 120 2.280
330 0.549 165 0.849 120 1.343 125 2.355
335 0.553 170 0.873 125 1.376 130 2.429
340 0.558 175 0.898 130 1.409
180 0.923 135 1.442
185 0.947 140 1.475
190 0.972 145 1.508
195 0.996 150 1.541
200 1.021 155 1.573
205 1.045 160 1.611
210 1.068 165 1.650
215 1.089 170 1.689
220 1.110 175 1.728
225 1.131 180 1.766
230 1.152 185 1.805
235 1.172 190 1.844
240 1.193 195 1.883
245 1.214 200 1.922
250 1.235 205 1.961
255 1.256 210 1.999
260 1.276 215 2.038
265 1.297 220 2.077
270 1.318 225 2.116
275 1.339 230 2.155
280 1.360 235 2.194
285 1.380 240 2.232
290 1.401 245 2.271
295 1.422 250 2.310
300 1.443 255 2.349
305 1.464 260 2.388
310 1.484 265 2.426
315 1.505 270 2.465
320 1.526 275 2.504
325 1.547 280 2.543
330 1.568 285 2.582
335 1.588 290 2.621
340 1.609 295 2.659
300 2.698
305 2.737
310 2.776
315 2.815
320 2.854
325 2.892
330 2.931
335 2.970
340 3.009
I' or 'H' Shaped Sections: 450oC
15 minutes 30 minutes 45 minutes 60 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 3
Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 6 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
340 0.457 100 0.457 90 1.035 50 1.007
105 0.463 95 1.055 55 1.065
110 0.480 100 1.076 60 1.123
115 0.497 105 1.096 65 1.182
120 0.513 110 1.116 70 1.240
125 0.530 115 1.136 75 1.298
130 0.547 120 1.157 80 1.357
135 0.564 125 1.177 85 1.415
140 0.581 130 1.197 90 1.473
145 0.598 135 1.217 95 1.532
150 0.615 140 1.238 100 1.590
155 0.631 145 1.258 105 1.634
160 0.648 150 1.278 110 1.678
165 0.665 155 1.298 115 1.722
170 0.682 160 1.319 120 1.766
175 0.699 165 1.339 125 1.810
180 0.716 170 1.359 130 1.854
185 0.733 175 1.379 135 1.898
190 0.749 180 1.400 140 1.942
195 0.766 185 1.420 145 1.986
200 0.783 190 1.440 150 2.030
205 0.800 195 1.460 155 2.074
210 0.817 200 1.481 160 2.118
215 0.834 205 1.501 165 2.162
220 0.851 210 1.521 170 2.206
225 0.867 215 1.541 175 2.250
230 0.884 220 1.562 180 2.294
235 0.901 225 1.582 185 2.338
240 0.918 230 1.609 190 2.382
245 0.935 235 1.640 195 2.426
250 0.952 240 1.671 200 2.470
255 0.969 245 1.702 205 2.514
260 0.985 250 1.733
265 1.002 255 1.764
270 1.019 260 1.795
275 1.036 265 1.827
280 1.053 270 1.858
285 1.070 275 1.889
290 1.087 280 1.920
295 1.105 285 1.951
300 1.128 290 1.982
305 1.151 295 2.013
310 1.174 300 2.045
315 1.197 305 2.076
320 1.220 310 2.107
325 1.243 315 2.138
330 1.266 320 2.169
335 1.290 325 2.200
340 1.313 330 2.231
335 2.262
340 2.294
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
15 minutes 30 minutes 45 minutes 60 minutes
I-Sections: 500oC
Sika® Unitherm® Platinum
Table 4 Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 7 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
340 0.457 120 0.457 45 0.457 50 1.006 75 2.192
125 0.466 50 0.485 55 1.031 80 2.338
130 0.479 55 0.514 60 1.055 85 2.484
135 0.491 60 0.543 65 1.080 90 2.630
140 0.503 65 0.572 70 1.105 95 2.776
145 0.515 70 0.601 75 1.130
150 0.527 75 0.630 80 1.154
155 0.539 80 0.659 85 1.179
160 0.551 85 0.688 90 1.204
165 0.563 90 0.717 95 1.229
170 0.575 95 0.746 100 1.253
175 0.588 100 0.775 105 1.278
180 0.600 105 0.804 110 1.303
185 0.612 110 0.833 115 1.328
190 0.624 115 0.862 120 1.352
195 0.636 120 0.891 125 1.377
200 0.648 125 0.920 130 1.402
205 0.660 130 0.949 135 1.427
210 0.672 135 0.978 140 1.451
215 0.684 140 1.007 145 1.476
220 0.697 145 1.036 150 1.501
225 0.709 150 1.065 155 1.525
230 0.721 155 1.094 160 1.550
235 0.733 160 1.118 165 1.579
240 0.745 165 1.140 170 1.621
245 0.757 170 1.161 175 1.664
250 0.769 175 1.183 180 1.706
255 0.781 180 1.205 185 1.749
260 0.793 185 1.227 190 1.791
265 0.806 190 1.249 195 1.834
270 0.818 195 1.271 200 1.876
275 0.830 200 1.293 205 1.919
280 0.842 205 1.315 210 1.961
285 0.854 210 1.337 215 2.004
290 0.866 215 1.359 220 2.046
295 0.878 220 1.381 225 2.089
300 0.890 225 1.403 230 2.131
305 0.903 230 1.425 235 2.174
310 0.915 235 1.447 240 2.216
315 0.927 240 1.469 245 2.259
320 0.939 245 1.491 250 2.301
325 0.951 250 1.513 255 2.344
330 0.963 255 1.535 260 2.386
335 0.975 260 1.557 265 2.429
340 0.987 265 1.581 270 2.471
270 1.609 275 2.514
275 1.637 280 2.556
280 1.665 285 2.599
285 1.693 290 2.641
290 1.720 295 2.684
295 1.748 300 2.726
300 1.776 305 2.769
305 1.804 310 2.811
310 1.832 315 2.854
315 1.860 320 2.896
320 1.888 325 2.939
325 1.916 330 2.981
330 1.943 335 3.024
335 1.971 340 3.066
340 1.999
I' or 'H' Shaped Sections: 550oC
30 minutes 45 minutes 60 minutes 90 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
15 minutes
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 5
Thickness is intumescent only. Table applies to 3 or 4 sided protection. Table also applies to 4 Sided protection to columns when subject to the maximum design loads in accordance with BS 449: Part 2.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 8 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
340 0.457 125 0.457 75 0.457 60 1.017 85 2.270
130 0.463 80 0.471 65 1.035 90 2.404
135 0.473 85 0.494 70 1.053 95 2.537
140 0.484 90 0.517 75 1.071
145 0.494 95 0.540 80 1.089
150 0.504 100 0.563 85 1.107
155 0.515 105 0.586 90 1.125
160 0.525 110 0.609 95 1.143
165 0.536 115 0.632 100 1.161
170 0.546 120 0.655 105 1.180
175 0.557 125 0.678 110 1.198
180 0.567 130 0.701 115 1.216
185 0.578 135 0.724 120 1.234
190 0.588 140 0.747 125 1.252
195 0.599 145 0.770 130 1.270
200 0.609 150 0.792 135 1.288
205 0.619 155 0.815 140 1.306
210 0.630 160 0.838 145 1.324
215 0.640 165 0.861 150 1.342
220 0.651 170 0.884 155 1.360
225 0.661 175 0.907 160 1.378
230 0.672 180 0.930 165 1.396
235 0.682 185 0.953 170 1.415
240 0.693 190 0.976 175 1.433
245 0.703 195 0.999 180 1.451
250 0.713 200 1.022 185 1.469
255 0.724 205 1.045 190 1.487
260 0.734 210 1.068 195 1.505
265 0.745 215 1.091 200 1.523
270 0.755 220 1.113 205 1.541
275 0.766 225 1.135 210 1.559
280 0.776 230 1.158 215 1.586
285 0.787 235 1.180 220 1.624
290 0.797 240 1.202 225 1.663
295 0.807 245 1.224 230 1.702
300 0.818 250 1.246 235 1.741
305 0.828 255 1.268 240 1.780
310 0.839 260 1.291 245 1.819
315 0.849 265 1.313 250 1.858
320 0.860 270 1.335 255 1.897
325 0.870 275 1.357 260 1.936
330 0.881 280 1.379 265 1.974
335 0.891 285 1.402 270 2.013
340 0.901 290 1.424 275 2.052
295 1.446 280 2.091
300 1.468 285 2.130
305 1.490 290 2.169
310 1.512 295 2.208
315 1.535 300 2.247
320 1.557 305 2.286
325 1.588 310 2.324
330 1.634 315 2.363
335 1.679 320 2.402
340 1.725 325 2.441
330 2.480
335 2.519
340 2.558
30 minutes 45 minutes 60 minutes 90 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
I' or 'H' Shaped Sections: 600oC
15 minutes
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 6
Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 9 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
340 0.457 180 0.546 75 0.457 30 0.445 30 1.479
185 0.555 80 0.464 35 0.485 35 1.542
190 0.564 85 0.483 40 0.526 40 1.605
195 0.573 90 0.501 45 0.566 45 1.668
200 0.582 95 0.520 50 0.607 50 1.732
205 0.591 100 0.539 55 0.647 55 1.795
210 0.599 105 0.557 60 0.688 60 1.858
215 0.608 110 0.576 65 0.728 65 1.921
220 0.617 115 0.595 70 0.768 70 1.984
225 0.626 120 0.614 75 0.809 75 2.047
230 0.635 125 0.632 80 0.849 80 2.111
235 0.643 130 0.651 85 0.890 85 2.174
240 0.652 135 0.670 90 0.930 90 2.237
245 0.661 140 0.688 95 0.971 95 2.300
250 0.670 145 0.707 100 1.011 100 2.363
255 0.679 150 0.726 105 1.051 105 2.426
260 0.687 155 0.745 110 1.092 110 2.489
265 0.696 160 0.763 115 1.113
270 0.705 165 0.782 120 1.128
275 0.714 170 0.801 125 1.144
280 0.723 175 0.819 130 1.160
285 0.731 180 0.838 135 1.176
290 0.740 185 0.857 140 1.192
295 0.749 190 0.876 145 1.207
300 0.758 195 0.894 150 1.223
305 0.767 200 0.913 155 1.239
310 0.775 205 0.932 160 1.255
315 0.784 210 0.950 165 1.271
320 0.793 215 0.969 170 1.286
325 0.802 220 0.988 175 1.302
330 0.811 225 1.006 180 1.318
335 0.819 230 1.025 185 1.334
340 0.828 235 1.044 190 1.349
240 1.063 195 1.365
245 1.081 200 1.381
250 1.100 205 1.397
255 1.129 210 1.413
260 1.158 215 1.428
265 1.187 220 1.444
270 1.216 225 1.460
275 1.245 230 1.476
280 1.273 235 1.492
285 1.302 240 1.507
290 1.331 245 1.523
295 1.360 250 1.539
300 1.389 255 1.555
305 1.418 260 1.571
310 1.447 265 1.604
315 1.476 270 1.664
320 1.505 275 1.724
325 1.534 280 1.784
330 1.563 285 1.844
335 1.594 290 1.904
340 1.629 295 1.964
300 2.024
305 2.084
310 2.144
315 2.204
320 2.264
325 2.324
330 2.384
335 2.444
340 2.504
15 minutes
Section
factor up to
m-1
Thckness mm
I' or 'H' Shaped Sections: 620oC
30 minutes 45 minutes 60 minutes 90 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 7 Thickness is intumescent only. Table applies to 3 or 4 sided protection. Table also applies to 3 sided protection to beams with concrete slabs when subject to the maximum design loads in accordance with BS 449: Part 2.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 10 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
340 0.457 180 0.528 80 0.457 30 0.457 30 1.413
185 0.537 85 0.487 35 0.472 35 1.475
190 0.546 90 0.503 40 0.509 40 1.538
195 0.554 95 0.519 45 0.547 45 1.600
200 0.563 100 0.535 50 0.585 50 1.663
205 0.572 105 0.551 55 0.623 55 1.725
210 0.580 110 0.567 60 0.661 60 1.788
215 0.589 115 0.583 65 0.699 65 1.850
220 0.598 120 0.599 70 0.737 70 1.913
225 0.607 125 0.615 75 0.774 75 1.975
230 0.615 130 0.631 80 0.812 80 2.038
235 0.624 135 0.647 85 0.850 85 2.100
240 0.633 140 0.663 90 0.888 90 2.163
245 0.641 145 0.679 95 0.926 95 2.225
250 0.650 150 0.695 100 0.964 100 2.288
255 0.659 155 0.711 105 1.002 105 2.350
260 0.667 160 0.727 110 1.039 110 2.413
265 0.676 165 0.743 115 1.077 115 2.475
270 0.685 170 0.759 120 1.106 120 2.538
275 0.693 175 0.775 125 1.122 125 2.600
280 0.702 180 0.791 130 1.138
285 0.711 185 0.807 135 1.153
290 0.720 190 0.823 140 1.169
295 0.728 195 0.839 145 1.184
300 0.737 200 0.855 150 1.200
305 0.746 205 0.871 155 1.216
310 0.754 210 0.887 160 1.231
315 0.763 215 0.903 165 1.247
320 0.772 220 0.919 170 1.263
325 0.780 225 0.935 175 1.278
330 0.789 230 0.951 180 1.294
335 0.798 235 0.967 185 1.309
340 0.807 240 0.983 190 1.325
245 0.999 195 1.341
250 1.015 200 1.356
255 1.031 205 1.372
260 1.047 210 1.388
265 1.063 215 1.403
270 1.079 220 1.419
275 1.095 225 1.434
280 1.111 230 1.450
285 1.127 235 1.466
290 1.152 240 1.481
295 1.180 245 1.497
300 1.208 250 1.513
305 1.236 255 1.528
310 1.264 260 1.544
315 1.292 265 1.559
320 1.320 270 1.575
325 1.348 275 1.591
330 1.376 280 1.627
335 1.404 285 1.695
340 1.432 290 1.764
295 1.832
300 1.900
305 1.968
310 2.036
315 2.105
320 2.173
325 2.241
330 2.309
335 2.377
340 2.445
I' or 'H' Shaped Sections: 650oC
30 minutes 45 minutes 60 minutes 90 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
15 minutes
Section
factor up to
m-1
Thckness mm
Sika® Unitherm® Platinum
Table 8 Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 11 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
340 0.457 200 0.543 100 0.530 30 0.457 30 1.364
205 0.549 105 0.542 35 0.479 35 1.418
210 0.555 110 0.554 40 0.502 40 1.471
215 0.562 115 0.566 45 0.525 45 1.524
220 0.568 120 0.578 50 0.548 50 1.578
225 0.574 125 0.590 55 0.570 55 1.631
230 0.580 130 0.602 60 0.593 60 1.685
235 0.586 135 0.614 65 0.616 65 1.738
240 0.592 140 0.626 70 0.639 70 1.792
245 0.599 145 0.638 75 0.670 75 1.845
250 0.605 150 0.650 80 0.691 80 1.899
255 0.611 155 0.662 85 0.712 85 1.952
260 0.617 160 0.674 90 0.733 90 2.006
265 0.623 165 0.686 95 0.754 95 2.059
270 0.630 170 0.698 100 0.775 100 2.113
275 0.636 175 0.710 105 0.796 105 2.166
280 0.642 180 0.723 110 0.817 110 2.220
285 0.648 185 0.735 115 0.838 115 2.273
290 0.654 190 0.747 120 0.859 120 2.327
295 0.660 195 0.759 125 0.880 125 2.380
300 0.667 200 0.771 130 0.901 130 2.433
305 0.673 205 0.783 135 0.922 135 2.487
310 0.679 210 0.795 140 0.943 140 2.540
315 0.685 215 0.807 145 0.964
320 0.691 220 0.819 150 0.985
325 0.697 225 0.831 155 1.006
330 0.704 230 0.843 160 1.027
335 0.710 235 0.855 165 1.048
340 0.716 240 0.867 170 1.070
245 0.879 175 1.091
250 0.891 180 1.112
255 0.903 185 1.132
260 0.915 190 1.152
265 0.927 195 1.173
270 0.939 200 1.193
275 0.951 205 1.213
280 0.963 210 1.233
285 0.975 215 1.254
290 0.988 220 1.274
295 1.000 225 1.294
300 1.012 230 1.314
305 1.024 235 1.335
310 1.036 240 1.355
315 1.048 245 1.375
320 1.060 250 1.395
325 1.072 255 1.416
330 1.084 260 1.436
335 1.096 265 1.456
340 1.108 270 1.476
275 1.497
280 1.517
285 1.537
290 1.557
295 1.578
300 1.598
305 1.633
310 1.690
315 1.748
320 1.805
325 1.863
330 1.920
335 1.978
340 2.035
30 minutes 45 minutes 60 minutes 90 minutes
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
Thckness mm
Section
factor up to
m-1
I' or 'H' Shaped Sections: 700oC
15 minutes
Section
factor up to
m-1
Thckness mm Thckness mm
Sika® Unitherm® Platinum
Table 9
Thickness is intumescent only. Table applies to 3 or 4 sided protection.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 12 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
Sika® Unitherm® Platinum
Table 10
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
330 0.877 120 0.877 50 0.877 50 1.605
125 0.935 55 0.997 55 1.818
130 1.031 60 1.130 60 2.030
135 1.127 65 1.264 65 2.259
140 1.223 70 1.398 70 2.555
145 1.318 75 1.531 75 2.850
150 1.414 80 1.665 80 3.145
155 1.510 85 1.799 85 3.441
160 1.606 90 1.933 90 3.576
165 1.702 95 2.066 95 3.671
170 1.798 100 2.200 100 3.767
175 1.893 105 2.316 105 3.862
180 1.989 110 2.432 110 3.957
185 2.085 115 2.548 115 4.052
190 2.181 120 2.664 120 4.148
195 2.266 125 2.780 125 4.243
200 2.348 130 2.896 130 4.338
205 2.430 135 3.013 135 4.433
210 2.513 140 3.129 140 4.529
215 2.595 145 3.245 145 4.624
220 2.677 150 3.361 150 4.719
225 2.759 155 3.477 155 4.814
230 2.842 160 3.529 160 4.910
235 2.924 165 3.566
240 3.006 170 3.603
245 3.089 175 3.640
250 3.171 180 3.677
255 3.253 185 3.713
260 3.335 190 3.750
265 3.418 195 3.787
270 3.500 200 3.824
275 3.521 205 3.861
280 3.542 210 3.898
285 3.562 215 3.934
290 3.583 220 3.971
295 3.604 225 4.008
300 3.625 230 4.045
305 3.645 235 4.082
310 3.666 240 4.118
315 3.687 245 4.155
320 3.708 250 4.192
325 3.728 255 4.229
330 3.749 260 4.266
265 4.302
270 4.339
275 4.376
280 4.413
285 4.450
290 4.487
295 4.523
300 4.560
305 4.597
310 4.634
315 4.671
320 4.707
325 4.744
330 4.781
60 minutes
Circular Hollow Columns: 500oC
15 minutes 30 minutes 45 minutes
Thickness is intumescent only.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 13 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
Sika® Unitherm® Platinum
Table 11
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
330 0.877 125 0.877 50 0.877 50 1.494
130 0.922 55 0.903 55 1.701
135 1.013 60 1.026 60 1.909
140 1.105 65 1.148 65 2.117
145 1.196 70 1.270 70 2.344
150 1.287 75 1.393 75 2.585
155 1.379 80 1.515 80 2.826
160 1.470 85 1.637 85 3.067
165 1.561 90 1.760 90 3.307
170 1.652 95 1.882 95 3.518
175 1.744 100 2.004 100 3.607
180 1.835 105 2.127 105 3.697
185 1.926 110 2.244 110 3.787
190 2.017 115 2.354 115 3.876
195 2.109 120 2.464 120 3.966
200 2.200 125 2.575 125 4.055
205 2.269 130 2.685 130 4.145
210 2.338 135 2.795 135 4.234
215 2.407 140 2.905 140 4.324
220 2.477 145 3.015 145 4.413
225 2.546 150 3.125 150 4.503
230 2.615 155 3.236 155 4.593
235 2.684 160 3.346 160 4.682
240 2.753 165 3.456 165 4.772
245 2.822 170 3.522 170 4.861
250 2.891 175 3.558 175 4.951
255 2.961 180 3.594
260 3.030 185 3.630
265 3.099 190 3.666
270 3.168 195 3.702
275 3.237 200 3.739
280 3.306 205 3.775
285 3.376 210 3.811
290 3.445 215 3.847
295 3.504 220 3.883
300 3.524 225 3.919
305 3.545 230 3.955
310 3.565 235 3.992
315 3.586 240 4.028
320 3.606 245 4.064
325 3.627 250 4.100
330 3.647 255 4.136
260 4.172
265 4.208
270 4.245
275 4.281
280 4.317
285 4.353
290 4.389
295 4.425
300 4.461
305 4.498
310 4.534
315 4.570
320 4.606
325 4.642
330 4.678
15 minutes 30 minutes 45 minutes 60 minutes
Circular Hollow Columns: 520oC
Thickness is intumescent only.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 14 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
Sika® Unitherm® Platinum
Table 12
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
330 0.877 135 0.877 60 0.877 50 1.341
140 0.954 65 0.986 55 1.536
145 1.034 70 1.093 60 1.731
150 1.114 75 1.199 65 1.927
155 1.194 80 1.306 70 2.122
160 1.274 85 1.412 75 2.308
165 1.353 90 1.519 80 2.489
170 1.433 95 1.625 85 2.669
175 1.513 100 1.731 90 2.850
180 1.593 105 1.838 95 3.031
185 1.673 110 1.944 100 3.211
190 1.753 115 2.051 105 3.392
195 1.833 120 2.157 110 3.530
200 1.913 125 2.260 115 3.604
205 1.992 130 2.360 120 3.678
210 2.072 135 2.460 125 3.752
215 2.152 140 2.560 130 3.826
220 2.229 145 2.660 135 3.900
225 2.302 150 2.760 140 3.974
230 2.375 155 2.860 145 4.048
235 2.448 160 2.960 150 4.122
240 2.521 165 3.060 155 4.196
245 2.594 170 3.160 160 4.270
250 2.667 175 3.260 165 4.344
255 2.740 180 3.360 170 4.419
260 2.813 185 3.460 175 4.493
265 2.887 190 3.521 180 4.567
270 2.960 195 3.555 185 4.641
275 3.033 200 3.589 190 4.715
280 3.106 205 3.623 195 4.789
285 3.179 210 3.658 200 4.863
290 3.252 215 3.692 205 4.937
295 3.325 220 3.726
300 3.398 225 3.761
305 3.471 230 3.795
310 3.511 235 3.829
315 3.530 240 3.863
320 3.549 245 3.898
325 3.568 250 3.932
330 3.587 255 3.966
260 4.001
265 4.035
270 4.069
275 4.103
280 4.138
285 4.172
290 4.206
295 4.241
300 4.275
305 4.309
310 4.343
315 4.378
320 4.412
325 4.446
330 4.481
30 minutes 45 minutes 60 minutes15 minutes
Circular Hollow Columns: 550oC
Thickness is intumescent only.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 15 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
Sika® Unitherm® Platinum
Table 13
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
330 0.877 145 0.877 65 0.877 50 1.210
150 0.942 70 0.955 55 1.375
155 1.009 75 1.034 60 1.540
160 1.077 80 1.113 65 1.705
165 1.145 85 1.192 70 1.870
170 1.212 90 1.271 75 2.035
175 1.280 95 1.349 80 2.200
180 1.348 100 1.428 85 2.335
185 1.415 105 1.507 90 2.471
190 1.483 110 1.586 95 2.606
195 1.551 115 1.664 100 2.742
200 1.618 120 1.743 105 2.877
205 1.686 125 1.822 110 3.013
210 1.754 130 1.901 115 3.148
215 1.821 135 1.979 120 3.283
220 1.889 140 2.058 125 3.419
225 1.956 145 2.137 130 3.522
230 2.024 150 2.220 135 3.579
235 2.092 155 2.320 140 3.635
240 2.159 160 2.420 145 3.691
245 2.222 165 2.520 150 3.747
250 2.278 170 2.620 155 3.803
255 2.333 175 2.720 160 3.859
260 2.389 180 2.820 165 3.915
265 2.444 185 2.920 170 3.971
270 2.500 190 3.020 175 4.027
275 2.556 195 3.120 180 4.083
280 2.611 200 3.220 185 4.139
285 2.667 205 3.320 190 4.195
290 2.722 210 3.420 195 4.251
295 2.778 215 3.507 200 4.307
300 2.833 220 3.539 205 4.364
305 2.889 225 3.572 210 4.420
310 2.944 230 3.605 215 4.476
315 3.000 235 3.638 220 4.532
320 3.056 240 3.670 225 4.588
325 3.111 245 3.703 230 4.644
330 3.167 250 3.736 235 4.700
255 3.769 240 4.756
260 3.802 245 4.812
265 3.834 250 4.868
270 3.867 255 4.924
275 3.900
280 3.933
285 3.966
290 3.998
295 4.031
300 4.064
305 4.097
310 4.130
315 4.162
320 4.195
325 4.228
330 4.261
15 minutes 30 minutes 45 minutes
Circular Hollow Columns: 590oC
60 minutes
Thickness is intumescent only.
This certificate is the property of Warrington Certification Limited, Holmesfield Road, Warrington, Cheshire WA1 2DS, UK. Registered company No. 02250182.
CERTIFICATE No CF 821 SIKA DEUTSCHLAND GMBH
Page 16 of 16 Signed C/012
Issued: 9th
December 2010 Revised: 4
th December 2015
Valid to: 30th
June 2019
Sika® Unitherm® Platinum
Table 14
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
Section
Factor up to
m-1
Thickness
mm
330 0.877 150 0.877 75 0.877 50 1.173
155 0.930 80 1.050 55 1.339
160 0.997 85 1.124 60 1.504
165 1.063 90 1.197 65 1.670
170 1.130 95 1.271 70 1.836
175 1.197 100 1.345 75 2.001
180 1.264 105 1.419 80 2.167
185 1.331 110 1.492 85 2.300
190 1.398 115 1.566 90 2.425
195 1.465 120 1.640 95 2.550
200 1.531 125 1.713 100 2.675
205 1.598 130 1.787 105 2.800
210 1.665 135 1.861 110 2.925
215 1.732 140 1.935 115 3.050
220 1.799 145 2.008 120 3.175
225 1.866 150 2.082 125 3.300
230 1.933 155 2.156 130 3.425
235 1.999 160 2.243 135 3.521
240 2.066 165 2.349 140 3.572
245 2.133 170 2.456 145 3.623
250 2.200 175 2.562 150 3.674
255 2.254 180 2.669 155 3.726
260 2.308 185 2.775 160 3.777
265 2.363 190 2.882 165 3.828
270 2.417 195 2.989 170 3.879
275 2.471 200 3.095 175 3.931
280 2.525 205 3.202 180 3.982
285 2.579 210 3.308 185 4.033
290 2.633 215 3.415 190 4.085
295 2.688 220 3.506 195 4.136
300 2.742 225 3.538 200 4.187
305 2.796 230 3.570 205 4.238
310 2.850 235 3.602 210 4.290
315 2.904 240 3.634 215 4.341
320 2.958 245 3.666 220 4.392
325 3.013 250 3.698 225 4.444
330 3.067 255 3.730 230 4.495
260 3.762 235 4.546
265 3.794 240 4.597
270 3.826 245 4.649
275 3.857 250 4.700
280 3.889 255 4.751
285 3.921 260 4.803
290 3.953 265 4.854
295 3.985 270 4.905
300 4.017 275 4.956
305 4.049
310 4.081
315 4.113
320 4.145
325 4.177
330 4.209
30 minutes 45 minutes 60 minutes
Circular Hollow Columns: 600oC
15 minutes
Thickness is intumescent only.