chapter 1 rc ii columns design notes
TRANSCRIPT
-
8/10/2019 Chapter 1 RC II Columns design Notes
1/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
1
Chapter 1 DESIGN OF COLUMNS
Columns are the members that take axial compressive load and bending moments. The bending
effect may be due to the lateral loads, end moments, and/or due to eccentricity of the axial loads.
Reinforced concrete columns are classified in EBCS 2, as un-braced (sway) or braced (non-sway), based on how the horizontal loads are transmitted by the super structure to the foundation.
Un-braced Columns (in sway frames): An un-braced structure is one in which frame action is
used to resist horizontal loads (lateral loads due to wind or earthquake). In such structure, beam
and column members may be designed to act together as a rigid frame in transmitting the lateral
forces down to the foundations through bending action in the beams and columns. In such an
instance the columns are said to be un-braced and must be designed to carry both the vertical
(compressive) and lateral (bending) loads. Moments in the columns can substantially reduce the
vertical load carrying capacity. The frame as a whole may exhibit significant lateral
displacement. The bending moment can increase due to second order effect.
Braced columns (in non-sway frames): If the lateral loads in a frame are transmitted to the
foundation through a system of bracing or shear walls, the column member in such a frame is
said to be braced column and consequently carry only vertical loads. In such a case, second
order effect will be negligible.
a). Braced columns in a non sway b). Unbraced columns in Sway type
Second order effect or P- effect: Consider a slender column subjected only to equal and
opposite end moment,M, as shown in figure. The column is bent into a single curvature with a
maximum deflection at the mid height as shown. If the axial compression is applied at the ends
of the column now, additional bending moment is caused due to the axial load acting on the
deformed shape. This additional bending moment causes additional deflection and so on, until
the final maximum deflection is reached at the stage of equilibrium under combined axial force
and bending moments. This is referred to asP- effects. It should be observed that due to P-
effects the maximum moment in the column is larger than the externally applied end moment M.
-
8/10/2019 Chapter 1 RC II Columns design Notes
2/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
2
If the column is short, P- effect is negligible. If the column is slender, P- effect is to be
considered.
(Section 4.4.4.4 of EBCS 2) Isolated columns: Columns may be considered as isolatedcolumns when they are isolated compression members (such as individual isolated columns and
columns with articulations in a non-sway structure), or compression members which are integral
parts of a structure but which are considered to be isolated for design purposes (such as slender
bracing elements considered as isolated columns, and columns with restrained ends in a non-
sway structure).
(Section 4.4.5 of EBCS 2) Slenderness ratio:
On the basis of the slenderness ratio columns may be classified as short or long (slender).
- For isolated columns, the slenderness ratio is defined by
WhereLeis the effective buckling length
i is the minimum radius of gyration of the concrete section only.
(Section 4.4.6 of EBCS 2) Limits of slenderness ratio:
Generally, the slenderness ratio of concrete columns shall not exceed 140.
Second-order effects in compressive members need not be taken into account in the following
cases:
(a).
For sway frames, the greater of the two
d
15
25
(b).For nonsway frames
2
12550M
M
WhereM1andM2are the first-order (calculated) moments at the ends, M2being always positive
and greater in magnitude than M1, and M1being positive if member is bent in single curvatureand negative if bent in double curvature.
i
Le
M
M
M
M
P
P
Max. Moment = M + PMax. Moment = M
A
Ii
-
8/10/2019 Chapter 1 RC II Columns design Notes
3/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
3
loadaxialdesignNAf
Nsd
ccd
sdd
Effective length of compression membersThe effective height (length) of a column is the distance between the two consecutive points of
contra flexure or zero bending moments. The figure shown below may serve this purpose.
In accordance with EBCS-2, 1995, the effective lengthLefor an RC Column is given as,
a. Non-sway mode 7.08.0
4.0
m
me
L
L
b. Sway mode
15.15.7
6.145.7
21
2121
L
Le
Or Conservatively .15.18.01 me
L
L
For the theoretical model shown below:
2
21
2221
22
1211
11
m
c
c
KK
KK
KK
KK
where K1 and K2 are column stiffness coefficients (EI/L) for the lower and the upper column
respectively.Kcis the stiffness coefficient (EI/L) of the column being designed.
Kijis the effective beam stiffness coefficient (EI/L)
= 1.0 (EI/L) for opposite end elastically or rigidly restrained.
= 0.5 (EI/L) for opposite end free to rotate.
= 0.0 (EI/L) for a cantilever beam.
For a nonsway frame 1.0cr
sd
N
N
Where: Nsdthe design value of the total vertical load.Ncrcritical vertical load for failure in a sway mode given as
Lc2
Lc
Lc1
Ib11Ib12
Ib22 Ib21
Ic
Ic1
Le 5.1
0.7L 1.2L
Le
L0.5L
Le 65.0 Le 8.0 Le 2.1
0.8L
Le 8.0
Ic2
-
8/10/2019 Chapter 1 RC II Columns design Notes
4/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
4
2
2
e
ecr
L
EIN
EIe= 0.2EcIc+ EsIs (or conservatively EIe= ccbal
bal IEr
M4.0
1 )
Ec 310511100 dr
Curvaturefbal
cd
I c= Moment of inertia of the concrete sections of the substitute column w.r.to centre
Is = Moment of inertia of reinforcement sections of the conc. section
A frame may be classified as braced if its sway resistance is supplied by a bracing system which
is sufficiently stiff to assume that all horizontal loads are resisted by the bracing system. (Not
more than 10% of the horizontal loads are attracted by the frame)
Reinforcement arrangement & Minimum Code Requirements
Functions of Lateral Rein forcement
Rules for the arrangement:
- Diameter of ties, t t 6mm or 4
- C/C spacing
mm
ensionlateralleastb
barsallongitudinofdiameterimumml
300
dim
)(min12
- Pitch of spiral 100mm
- Ties shall be arranged such that every bar or group of bars placed in a corner and
alternate longitudinal bar shall have lateral support provided by the corner of a tie
with an included angle of not more than 135oand no bar shall be farther than
150mm clear on each side along the tie from such a laterally supported bar.
Main or Longitudinal rein forcement
- Area of longitudinal reinforcement, As.
l
15t 300mm
At center
Equal or less
than 150mm
May be greater than 150mm
No intermediate tie is required
At center
135
15t
3
00mm
t
l = longitudinal bars
t = main ties
-
8/10/2019 Chapter 1 RC II Columns design Notes
5/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
5
0.008AcAs0.08Ac or 0.008 08.0c
s
A
A
- Min. # of bars
.6
tan4
tarrangemenCircularin
tarrangemengularrecin
- The diameter of longitudinal bars, .12mml
- The minimum lateral dimension of a column shall be at least 150mm- The Min. cover to reinforcement should never be less than
(a) ormmor n ),40(
(b) .3255 mmdifmmOrmm gn
n = ,55mmn n= no. of bars having the same diameter
dgthe largest nominal maximum aggregate size.
Minimum reinforcements are provided:
Example 4.1. (Classif ication of columns)
The frame shown in figure below is composed of members with rectangular cross sections. All
members are constructed of the same strength concrete (E is the same for both beams and
columns). Considering bending in the plane of the frame only, classify column EF as long or
short if the frame is braced. All girders are 300 x 600 mm.
Solution:
Moments of inertia
Girders: 483
105412
600300mmx
xIg
Columns: 483
1016
12
400300mmx
xIDE
.1071875.1012
350300 483
mmxx
IEF
F
E
I
H
G
E
D
C
B
A
M2= 45 KNm
M1= 30 KNm
7.5 m9 m
3.80 m
3.80 m
400
600
600
350
300 x 400
300 x 350
525 KNF
300300
-
8/10/2019 Chapter 1 RC II Columns design Notes
6/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
6
Stiffness Coefficients:
.102.77500
1054
.1069000
1054
:5
8
58
ExxE
KK
ExxE
KK
L
EIKGirders
FIEH
cFBE
g
g
g
Columns:
Exx
EK
Exx
xEK
L
EIK
EF
DE
c
cc
5
3
8
5
3
8
1082.2108.3
1071875.10
1021.4108.3
1016
The column being considered is column EF.
Rotational stiffnesses at joints E and F.
effgf
col
effgf
col
LI
LI
LEI
LEI
/
/
/
/
Joint E: 53.0102.7106
1082.21021.455
55
xx
xx
KK
KK
EHBE
DEEFE
Joint F: 21.0102.7106
1082.255
5
xx
x
KK
K
FICF
EFF
37.02
21.053.0
2 FEm
For a braced column (Non sway structure ) for design
7.066.08.037.0
4.037.0
8.0
4.0
m
me
L
L
Le= (0.7) (3.8) = 2.66m = 2660mm
The slenderness ratio: 3503001071875.10
2660
8 xxAI
L
I
L ee
.
!66.6645
302550
.327.26
shortiscolumThe
ok
-
8/10/2019 Chapter 1 RC II Columns design Notes
7/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
7
Design of short Columns subjected to Axial compression
The ultimate capacity of an axially loaded short column can be determined by
Pdu = fcd(Ag - As) + fydAst, = fcdAg (1) + Agfyd
Where, =g
st
A
Aor Ast = Ag
Pdu = Ag [fcd(1) +fyd]
Ag= Gross concrete area; Ast = Area of main reinforcement
A column may be classified as long when the slenderness factor is defined as
;12b
Le
For long (Slender) columns a load reduction factor Cr is introduced in such a way that theconcrete concentric design axial load capacity can be given by
Pduc= CrPduWhere Cr= 1.25Le/48b
Le= Effective height; b= least lateral dimension
Example: A column resting on an independent footing supports a flat slab. The super imposed
factored load transferred from the slab is 1000 kN. Design the column assuming a gross steel
ratio of (a) 0.01 (b) 0.02. Use concrete C30, steel S300 and class I works. Assume column
height h = 4 m.
Solution: fcd = 13.6 MPa; fyd = 260.87 MPa
Pdu = Ag [fcd(1) +fyd]
(a)For = 0.01 and Pd = 1000 kN,
])1([ ydcd
dg
ff
PA
S2=)87.260(01.0)01.01(6.13
10*1000 3
S = 249 mm
Use 250 mm 250 mm cross section
Ast =Ag = 0.01 (250)2= 625 mm2
Use 4 numbers of 16 mm dia rods; Astprovided = 804 mm2
Ties: d 6 mm (or) S 12* dia of main bar = 192 mm
Dia of main bar/4 = 16/4 = 4 mm Least lateral dimension = 250 mm
300 mm
Therefore, use 6 mm dia rods at 190 mm center to center
(b)For = 0.02 and Pd = 1000 kN,
-
8/10/2019 Chapter 1 RC II Columns design Notes
8/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
8
])1([ ydcd
dg
ff
PA
S2=)87.260(02.0)02.01(6.13
10*1000 3
S = 232 mm
Use 240 mm 240 mm cross section
Ast =Ag = 0.02 (240)2= 1125 mm2
Use 4 numbers of 20 mm dia rods; Astprovided = 1256 mm2
Ties: d 6 mm (or) S 12* dia of main bar = 240 mm
Dia of main bar/4 = 20/4 = 5 mm Least lateral dimension = 240 mm
300 mm
Therefore, use 6 mm dia rods at 240 mm center to center
Design of Columns with moments (eccentrically Loaded Columns)When a member is subjected to combined axial load and bending moment it is more convenient
to replace the axial load and moment with an equivalent load applied at an eccentricity e.
I nteraction diagram:It is a plot of axial load capacity of a column against the bending moment
it sustains. To illustrate conceptually the interaction between axial load and moment in a
column, an idealized, homogeneous and linearly elastic column with compressive strength fcu
equal to its tensile strengthftuis considered. This type of column fails in compression when
max=fcu.
;cufI
My
A
P or 1
If
My
Af
P
cucu
-------------------------(1)
ButPmax= fcuA & Mmax=y
Ifcu
Equation (1) becomes, 1ma xma x
MM
PP ; This equation is called interaction equation.
Pd
Md
e
Pd
-
8/10/2019 Chapter 1 RC II Columns design Notes
9/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
9
It shows the interaction of (or) relationship between P and M at failure.
Reinforced concrete is not elastic, and it hasft
-
8/10/2019 Chapter 1 RC II Columns design Notes
10/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
10
Where ee=equivalent constant first-order eccentricity of the design axial load.
ea = additional eccentricity in account of geometric imperfections.
ea= mmLe 20300
ee = eo,for eoequal at both ends of a column
For first order moments varying linearly along the length, the equivalent eccentricity is the higherof the following two values. eo1and eo2are first order eccentricities at the ends with eo2being positive and greater in
magnitude than eo1and eo1 is the smaller and positive for single curvature and negative for
double curvature.
e2 = Second-order eccentricity and is ignored if column is short.
For nonsway frames, e2 = 10
121 rLK e
.350.1
351575.020
1
1
forK
forK
3
2 105
sec1
dK
tioncriticaltheatCurvaturer
Where d = the Column dimension in the buckling plane less the cover to the center of the
longitudinal reinforcement.
K2=bal
sd
bal
sd
MM
Msd = design moment at the critical section including second-order effects.
Mbal = balanced moment capacity of the column.
Design of columns for uni-axial bending
A column is said to be bending uniaxially if it is loaded with a bending moment only in one
direction, in addition to axial force. For the design of such a column interaction charts are
prepared using non-dimensional parameters, and , in which,bhf
N
cd
sd and2bhf
M
cd
sd
A chart showing the interaction diagrams are prepared (and compiled in EBCS 2 - part 2) for
different values of d' and h as given in the sample chart. Ascan be calculated by the formula,
yd
cdcs
f
fAA
In using these charts for design, the following procedure may be adopted.Given: axial load and bending moment, (BM = axial load total eccentricity)
* Assume the cross section dimensions band h.
-
8/10/2019 Chapter 1 RC II Columns design Notes
11/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
11
* Assume d' and evaluate d'/hto choose appropriate chart number
* Calculate and ,
* The coordinate (,) gives the value of from the appropriate chart chosen
* Determineyd
cdcs
f
fAA
Sample design chart
-
8/10/2019 Chapter 1 RC II Columns design Notes
12/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
12
Example 1
Design a slender braced (non-sway) column subjected to uniaxail bending.
Given:- factored load=1650KN
-factored 1storder equivalent constant
Moment=130KNm
-Geometric length: L=7m and Le=0.7L
-Material data; C-30, S-460 class I work-Assume Column size
b = 400mm; h = 400mm;
Required: - quantity of reinforcement.
Solution
Assume cover = 20mm; long = 20mm and lat. = 10mm
400
40'
h
d= 0.1 and d = 400-40 = 360mm
ea>=300
eL=
3007000*7.0
= 16.33 or 20mm
Therefore; ea=20mm
Check for second order effect
- =
A
I
Le =
12
400
4900
2= 42.4
- max = 50-25( 21
M
M) ; here first order moment is constant throughout the column.
Therefore; max= 50-25=25
As > max, second order effect has to be considered
Msd = etot*Nsd=(ee+ea) Nsd=ee* Nsd+ ea* Nsd=first order moment + moment due to ea
= 130+ (1650*0.02) =163kNm
For C-30 concrete; fck= 24; fcd=s
ckf
85.0
=5.1
24*85.0
= 13.6MPa
fyd =s
ykf
=15.1
460
= 400MPa
sd =cdc
sd
fA
N
=6.13*400
10*16502
3
= 0.76
hfA
M
cdc
sdsd =
400*6.13*400
10*1632
6
=0.187
Using chart no- 2; forsd = 0.76 and sd = 0.187; = 0.32; bal = 0.25
-
8/10/2019 Chapter 1 RC II Columns design Notes
13/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
13
K2 =bal
sd
=25.0
187.0= 0.75,
r
1
= K2(
d
5) 10-3 = 0.75( 310*
360
5
= 10.42*10-6
e2 = (10
2
1LeK
r
1) here K1= 1 for > 35
= )10*42.10(10
)4900(1 62
= 25mm
e tot = ee+ ea+e2 = mm8.12325201650
10*130 3
Msd = 1650*1000
8.123= 204.3kNm ,
6.13*400
10*3.2043
3
= 0.236 implies =0.45
Recalculating k2, bal=0.3
k2=
3.0
235.0= 0.78 ,
r
1
= 0.78( 310*)
360
5 = 10.8*10-6
e2= 26mm
etot = 124.8
Msd = 1650*1000
8.124
= 205.09 kNm ,
hfA
M
cdc
sdsd =
400*6.13*400
10*1.2052
6
= 0.236
= 0.45
Interaction can be stopped.
400
6.13*400*45.0 2stA= 2448mm2
Use 8 number of 20mm diameter rods.
Asprovided = 2512, compare the result with minimum and maximum code requirements
>0.008*4002=1280
-
8/10/2019 Chapter 1 RC II Columns design Notes
14/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
14
Soln: Assume d= 40mm;h
d' =
400
40= 0.1 use uniaxail chart no-2
ee 0.6eo2+0.4eo1 or 0.4eo2
eo2= 1000*1280
155=121.1mm
eo1= 1000*1280
82=-64.1mm
ea
300
le=
300
7500*75.0=18.75mm or 20mm; use ea =20mm
Check for e2; =
12
400
7500*75.02
=48.7 ; max=50-25(155
82)=63.2
< max; therefore; neglect second order eccentricity
etot=eo2+ea =121.1+20=141.1mm
Msd= Nsd*etot=1280*1000
1.141=180.6kNm; fcd= 13.6 ; fyd=347.8
=400*300*6.13
10*1280 3
bhf
N
cd
sd =0.78 and =2
6
2 400*300*6.13
10*61.180
bhf
M
cd
sd =0.28
implis =0.6
As=
yd
cdc
f
fA **=
8.347
6.13*300*400*6.0= 2815.4mm; use 822mm bar
Aspov= 8*4
*22 2 =3041mm2
< Asmax= 0.08*Ag=9600mm2
>Asmin=0.008Ag=960mm2
Lateral reinforcement
6 or 22/4 S12* 22 =264 or 300
Use 6mm ties at 260mm spacing.
-
8/10/2019 Chapter 1 RC II Columns design Notes
15/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
15
Design of columns for biaxial bending
A column may receive moments from beams and grade framing to it, in addition to the axial
loads. This situation of a biaxial loaded rectangular section is shown below with the
corresponding interaction curves.
Uniaxial loading about y-y.
Uniaxil loading about X-X
Biaxial loading about a diagonal axis x-x where: r=arc tandy
dx
e
e=arc tan
dxM
Mdy
Three-dimensional interaction diagramInteraction surface
Any combination of Pdn, Mdx,and Mdylying inside the surface can be applied safety.
Any point lying outside the surface would represent failure.
Due to the mathematical complication arising from the construction of interaction surface,
in practice a simpler approximation methods are used of which the one developed by
Bresler is satisfactory.
-
8/10/2019 Chapter 1 RC II Columns design Notes
16/17
School of Civil & Urban Eng., IOTec. Hawassa University
___________________________________________________________________________
RC II (CEng 3111) Chapter 1
16
It is given as reciprocal load equation.
dodnydnxdn PPPP
1111 , which simplifies to
dnydnxdnydnxdo
dnydnxdo
dn
PPPPP
PPPP
)(
Where: Pdnis the desing axial load capacity when applid at edxand edy
simultaneously.(biaxial bending ).
Pdnxand Pdny- design axial load capacity when edx and edy are only acting ( case of
uniaxal loading).
PdoDesign axial force capacity for concentric load case.
However, in EBCS 1995, interaction charts are prepared for this purpose and they can be easly
used for actual design where the following procedures need be followed. Given : Pd; Mband Mh
Assume a cross section and evaluateh
h
b
b ',
Calculate b , h, and
ccd
d
Af
N ,
bAf
M
ccd
bb and
bAf
M
ccd
hh
Select suitable chart, which nearly satisfy the calculatedh
h
b
b ', and
Enter the chart for suitable value of ( 0.0,0.2,0.41.4)
Note: - > 1.4 shows very small concrete cross section
For intermediate value of ,use interpolation
Select corresponding to,b , h
Compute As, totyd
cd
f
bhf
Check minimum and maximum requirements.
Example 1
Design a column to sustain a factored design axial load of 900KN and biaxial moments of
Mdx=270KNM and Mdy=180KNm including all other effects. Use C-30, S-300 class I works.
Soln: fck= 24MPa ;fcd=13.6MPa; fyd=260.87MPa
Assume b*h = 400*600mm andb
b' =
h
h'=0.1, Nsd= 900kN
Mh=Mdx=270kNm
Mb=Mdy=180kNm
= 600*400*6.13
10*900 3
=0.28(between0.2 and0.4)
-
8/10/2019 Chapter 1 RC II Columns design Notes
17/17
School of Civil & Urban Eng., IOTec. Hawassa University
17
bAf
M
ccd
bb = 2
6
400*600*6.13
10*180=0.14 and
hAf
M
ccd
hh = 2
6
600*400*6.13
10*270=0.14
Using biaxial chart no- 9 thus:
for =0.2; h =0.14 , b =0.14; =0.4
for =0.4; h =0.14, b =0.14; =0.4
By interpolation for =0.28; =0.4
As=yd
cdc
f
fA **=
87.260
6.13*600*400*4.0=5005mm2
< Asmax= 0.08*Ag=19200mm2
>Asmin=0.008Ag=1920mm2
use 830mm bar
Lateral reinforcement
6 or 30/4
{
Use 8mm ties at 300mm spacing.