chapter 10 the asce 7-10 design provisions for seismically...
TRANSCRIPT
![Page 1: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/1.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Chapter 10 The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
1
![Page 2: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/2.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
CONTENT 1. Introduction 2. Design Methods 3. Design Based on Static Analysis 4. Design Based on Dynamic Analysis 5. Adequacy Assessment of Bearings 6. Design Review and Testing 7. Design Example 8. Project Example
2
![Page 3: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/3.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Major References • ASCE 7-10 Standard
– Chapter 17
3
![Page 4: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/4.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
1. Introduction • Early versions of seismic provisions for seismically
isolated structures: – Emphasized simple, statically equivalent method of design – Displacements concentrated at isolation level – Superstructure assumed to moves as a rigid body – Design based on single mode of vibration – Design forces for superstructure computed from isolator
forces at design displacement • Recent versions of seismic provisions:
– Increased situations for dynamic analysis – Incentives to encourage dynamic analysis
4
![Page 5: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/5.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
2. Design Methods • For all seismic isolation designs, necessary to first perform static analysis • Static Analysis establishes minimum level for design displacements and
forces • Static analysis (or equivalent lateral force procedure) can be used as only
design method if all following conditions are met: – Design spectral acceleration at a period of 1 second is less than or equal to 0.6 g. – Structure is located on soil type A, B, C, or D. – Structure above isolation interface not more than four stories or 20 m in height. – Isolated period of structure at design displacement less than or equal to 3
seconds. – Isolated period of structure at design displacement greater than three times the
elastic fixed-based period of the structure (i.e. ε < 1/9 ) – Structure is regular. – The isolation system does not limit MCE displacement to less than the total
maximum displacement.
5
![Page 6: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/6.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• For all seismic isolation designs, necessary to first perform static analysis • Static Analysis establishes minimum level for design displacements and
forces • Static analysis (or equivalent lateral force procedure) can be used as only
design method if all following conditions are met: – Effective stiffness of the isolation system at design displacement greater than 1/3
of effective stiffness at 20% of design displacement.
2. Design Methods
6
![Page 7: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/7.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• For all seismic isolation designs, necessary to first perform static analysis. • Static Analysis establishes minimum level for design displacements and
forces. • Static analysis (or equivalent lateral force procedure) can be used as only
design method if all following conditions are met: – The isolation system configured to produce a restoring force such that the lateral
force at the total design displacement is at least 0.025W greater than the lateral force at 50 percent of the total design displacement.
2. Design Methods
7
![Page 8: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/8.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
– All other cases, dynamic analysis is required. – Response spectrum analysis can be used in following cases:
• Structure located on soil type A, B, C, or D. • Effective stiffness of the isolation system at design displacement greater
than 1/3 of effective stiffness at 20% of design displacement. • The isolation system configured to produce a restoring force such that the
lateral force at the total design displacement is at least 0.025W greater than the lateral force at 50 percent of the total design displacement.
• The isolation system does not limit MCE displacement to less than the total maximum displacement.
– For all other cases, time-history dynamic analysis required.
2. Design Methods
8
![Page 9: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/9.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
9
![Page 10: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/10.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
10
![Page 11: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/11.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
11
![Page 12: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/12.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
12
![Page 13: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/13.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
13
![Page 14: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/14.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• After preliminary design completed, prototype isolators constructed and tested.
• Values of kDmin and kDmax obtained from test results. • Results of prototype tests also used to refine
preliminary design, and when dynamic analysis used, needed to establish bounds on design quantities.
• Because effective stiffness and the effective damping dependent on displacement, the process of computing TD and BD is iterative.
3. Design Based on Static Analysis
14
![Page 15: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/15.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• Preliminary Design Flowchart Assume a design displacement, DD
Determine the minimum lateral siffness of isolators , kDmin, at displacement DD.
Calculate effective isolated period, TD, at displacement DD:
Calculate equivalent viscous damping, ζ, and the reduction factor BD.
Calculate an updated design displacement, DD∗ :
?DD ≈ DD*
YesNo Preliminary design completedDD = DD *
*
3. Design Based on Static Analysis
15
![Page 16: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/16.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
16
![Page 17: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/17.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
ASCE 7-10 standard specifications
3. Design Based on Static Analysis
17
![Page 18: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/18.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
18
![Page 19: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/19.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
19
![Page 20: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/20.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
20
![Page 21: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/21.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
3. Design Based on Static Analysis
21
![Page 22: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/22.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• RI factor for base isolated structure much lower than R factor for equivalent fixed base structure.
• In fixed-base design, several factors lead to values of R: – Period shift: as structure yields, period lengthens and force demand reduces. – Damping increase because of yielding of structural elements.
• For isolated structure, only overstrength and redundancy are applicable. – Period shift in superstructure counters effectiveness of isolation system.
• Decreases the separation between fixed base period and the isolated period. • Could attract larger forces and more participation from higher modes.
– Damping in isolated structure less than in fixed base structure.
3. Design Based on Static Analysis
22
![Page 23: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/23.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• Vertical distribution of inertia forces:
3. Design Based on Static Analysis
23
![Page 24: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/24.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• Incentives to use dynamic analysis:
4. Design Based on Dynamic Analysis
24
![Page 25: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/25.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• Reduction in displacements to account for superstructure flexibility:
4. Design Based on Dynamic Analysis
25
![Page 26: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/26.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
• Selection of Design Ground Motions: – Pairs of horizontal components from at least three recorded seismic events
necessary for time-history analysis. – Events must be representative of site, soil, and source characteristics and have
durations consistent with DBE or MCE. – Time- histories site within 15 km from major active fault requires near-fault
characteristics. – Ground motions scaling:
• For each ground motion pair, SRSS of 5% damped spectrum computed • Motions scaled so that average SRSS spectrum not below target spectrum for the MCE in the
period range 0.5TD to 1.25TD. – Calculation of design values:
• If three time-histories used: – Design based on maximum response quantities from three time-history analyses.
• If seven time-histories used: – Design based on mean response quantities from seven time-history analyses.
4. Design Based on Dynamic Analysis
26
![Page 27: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/27.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
5. Adequacy Assessment of Bearings • Adequacy Assessment of Bearings
– See Chapter 9
http://mceer.buffalo.edu/publications/catalog/reports/LRFD-Based-Analysis-and-Design-Procedures-for-Bridge-Bearings-and-Seismic-Isolators-MCEER-11-0004.html
27
![Page 28: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/28.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Peer Review Composition:
Must be conducted by an independent team of professionals familiar with seismic isolation technology (seer ASCE 7-10, Section 17.7).
Responsibilities: 1. Review of design criteria specific to the site including:
Development of site specific design response spectra. Development of site specific design ground motion time-histories. All other design criteria developed specifically for the project.
2. Review of preliminary design including: Determination of total design displacement, DTD. Determination of maximum total design displacement, DTM. Determination of design forces.
3. Review and observation of prototype testing. 4. Review of the final design of the entire structure, the SFRS and the isolation system. 5. Review of the quality control criteria and procedures of the testing program.
6. Design Review and Testing
28
![Page 29: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/29.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Testing Requirements To verify the deformation and damping characteristics of the isolation system. Testing of two full-scale prototype specimens of each type of isolators used in
the project including wind locking mechanisms. Prototype specimens not be used in construction. Cyclic testing on each specimen under a vertical load equal to the average of the
service dead load plus half of the service live load. If the properties of the isolator depends on the rate of loading, dynamic tests
must be conducted at a frequency equal to the inverse of the effective isolation period at the design displacement, 1/TD.
6. Design Review and Testing
29
![Page 30: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/30.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Testing Protocol: 1. Twenty load-controlled reversed cycles corresponding to the
design wind load. 2. Three displacement-controlled reversed cycles for each of the
following displacement increments: 0.25DD, 0.5DD, 1.0DD, et 1.0DM.
3. Three displacement-controlled reversed cycles corresponding to the maximum total design displacement, 1.0DTM.
4. 30SD1/SDSBD ≥ 10 cycles displacement-controlled reversed cycles corresponding to the total design displacement, , 1.0DTD.
6. Design Review and Testing
30
![Page 31: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/31.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
Concrete frame
Reaction Wall
Removable steel cross-beam and tie-down rods
Bearing specimen
Moveable platen
Horizontal actuators
Stabilizing hydrostatic slide bearing-actuators on platen’s outrigger arms
Hydrostatic slide bearing-actuators beneath platen
Concrete frame
Reaction Wall
Removable steel cross-beam and tie-down rods
Bearing specimen
Moveable platen
Horizontal actuators
Stabilizing hydrostatic slide bearing-actuators on platen’s outrigger arms
Hydrostatic slide bearing-actuators beneath platen
6. Design Review and Testing
31
![Page 32: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/32.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego Spécifications
Vertical Longitudinal Transverse Force 53,400 kN
(12,000 kips) 8,900 kN
(2,000 kips) 4,450 kN
(1,000 kips) Displacement ± 0.127 m
(5 in.) ± 1.22 m (48 in.)
± 0.61 m (24 in.)
Velocity ± 254 mm/s (10 in./s)
± 1778 mm/s (70 in./sec)
± 762 mm/s (30 in./sec)
Clearance Up to 1.52 m (5 ft)
~ 4 m (13 ft)
Relative rotation
± 2° ± 2° ± 2°
6. Design Review and Testing
32
![Page 33: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/33.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
High Bay Physics and SRMD Test Facility
LC Building
Low Bay PortionHigh Bay Portion Control Room
Pipe Trench
AccumulatorBuilding
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
6. Design Review and Testing
33
![Page 34: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/34.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Slide BearingActuator Steel Bearing Plate
10.4 m(34 ft)
Corner Fixture
18.3 m (60 ft)
Platen
HorizontalActuator
Plan View of Test System
Outrigger Arm
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
6. Design Review and Testing
34
![Page 35: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/35.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Prestressing System
Lab Floor
Slide BearingActuators
4.1 m(13.5 ft)
3.5 m(11.5 ft)
0.6 m(2 ft) 18.3 m (60 ft)
1.8 m(6 ft)
ReactionWall
Tie-Down Systemand Steel Cross Frame
Corner Fixture
PipingSystem
Longitudinal Section View of Test System
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
6. Design Review and Testing
35
![Page 36: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/36.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
0.9 m (3 ft)
Cross Section View
Platen assembly
36
![Page 37: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/37.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Schematic of Self-Reacting Frames / Foundation
Post-tensioned concrete beam across bottom of concrete frame.
Steel cross-beam and post-tensioned steel tie-rods.
Horizontal forces (red) are reacted by the horizontal self-reacting concrete frame and the steel
cross-beam above.
Vertical forces (blue) are reacted by the
vertical self-reacting concrete and steel
frame.
6. Design Review and Testing
37
![Page 38: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/38.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Horizontal actuators
Quantity 4Capacity (tension) 4,500 kN (1,000 kips)Capacity (compr.) 7,000 kN (1,600 kips)Stroke 2.5 m (100 in)Rod diameter 0.3 m (12 in)Bore 0.5 m (20 in)Max velocity 1.8 m/s (70 in/s)Swivels ± 10°
Servovalves 19.3 m3/min (5,000 gpm)Pressure 35 MPa (5,000 psi)Weight (each) 13 ton (28 kips)
38
![Page 39: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/39.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Vertical actuators Quantity 4Capacity (tension) NACapacity (compr.) 18,000 kN (4,000 kips)Stroke 0.25 m (10 in)Rod diameter NABore 0.81 m (32 in)Max velocity 0.4 m/s (15 in/s)Swivels ± 2°
Servovalves 11 m3/min (3,000 gpm)Pressure 35 MPa (5,000 psi)Weight (each) 4.4 ton (9.7 kips)
39
![Page 40: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/40.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Outrigger stabilizing actuators
Quantity 4Capacity (tension) NACapacity (compr.) 534 kN (120 kips)Stroke 0.5 m (20 in)Rod diameter NABore 0.19 m (7.5 in)Max velocity 0.5 m/s (18 in/s)Swivels ± 2°
Servovalves 0.7 m3/min (180 gpm)Pressure 21 MPa (3,000 psi)Weight (each) 0.4 ton (1 kips)
40
![Page 41: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/41.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Control Room
Hydraulic Pump
Pipe Trench
10 Accumulator Racks (10 Bottles per Rack)
Surge Tank
Accumulator Building and Control Room
41
![Page 42: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/42.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
6. Design Review and Testing
42
![Page 43: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/43.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
DIS LR Bearing, Vertical Load = 558 kips, Displacement = 22 in, velocity = 60 in/s
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
6. Design Review and Testing
43
![Page 44: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/44.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
DIS LR Bearing, 400% strain
SRMD (Seismic Response Modification Device) Testing Facility , UC-San Diego
6. Design Review and Testing
44
![Page 45: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/45.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
7. Design Example
Design of a 4-story seismically isolated building and verification of the equivalent
static force method of ASCE 7-10.
45
![Page 46: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/46.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Four-story regular steel building part of a hospital. No in-plane or elevation irregularity. Ie = 1.5
Plan dimensions : 73.2 m x 45.75 m Total height: 19.52 m (4.88 m per story) Seismic weight above the isolation plane: 107 MN. SFRS composed of peripheral special concentrically
braced steel frames (per ASCE 7-10) R = 6
Eccentricity of 600 mm in each principal direction between the center of mass (CM) of the building above the isolation plane and the shear center (SC) of the isolation system
Design seismic parameters (per ASCE 7-10): Soil type D
SDS = 0.83 and SD1 =0.58 (DE) SMS = 1.25 and SM1 =0.87 (MCE)
Building Description
Isolation plane
4 @
4.8
8 m
e = 600 mm
CM (building)
73.2 m
45.7
5 m
SC (isolation)
e = 600 mm
46
![Page 47: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/47.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Two types of isolation bearings with the force-displacement envelopes shown from prototype testing. 20 bearings of Type 1 34 bearings of Type 2
Linear viscous dampers in parallel with the isolation system: Provide a supplemental damping
ratio of 9.4% of critical.
Seismic Isolation System
50 mm
50 mm
0.92 kN/mm
0.77 kN/mm
2.51 kN/mm
2.09 kN/mm
1.31 kN/mm
1.10 kN/mm
2.84 kN/mm
2.37 kN/mm
Type 1
Type 2
47
![Page 48: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/48.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
1. Determine the total design displacement, DTD , and the total maximum displacement, DTM , of the bearings using the equivalent static force procedure.
2. Determine the minimum design force under and over the isolation plane. It is assumed that wind loads are not critical.
3. Verify that the equivalent static force procedure is applicable for this building.
Design Requirements
48
![Page 49: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/49.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Design displacement at the center of rigidity of the bearings:
Equivalent viscous damping ratio and damping
reduction factor:
1. Determination of DTD and DTM for the bearings
SD1 =0.58
+ 0.094
49
![Page 50: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/50.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Effective isolated period at the design displacement:
W = 107 MN
2Typemin1 Typeminmin 3420 DDD kkk +=
50
1. Determination of DTD and DTM for the bearings
![Page 51: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/51.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings 51
Assume a design displacement, DD
Determine the minimum lateral siffness of isolators , kDmin, at displacement DD.
Calculate effective isolated period, TD, at displacement DD:
Calculate equivalent viscous damping, ζ, and the reduction factor BD.
Calculate an updated design displacement, DD∗ :
?DD ≈ DD*
YesNo Preliminary design completedDD = DD *
*
1. Determination of DTD and DTM for the bearings
![Page 52: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/52.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings 52
4-Story Isolated Building Example
![Page 53: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/53.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
DD = 311.6 mm; kDmax =76.39 kN/mm, TD = 2.59 s
DTD = 389.8 mm
53
1. Determination of DTD and DTM for the bearings
e = 600 mm CM (isolation)
73.2 m
45.7
5 m
CM (building)
e = 600 mm
![Page 54: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/54.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Maximum displacement at the center of rigidity of the bearings:
Equivalent viscous damping ratio and damping
reduction factor:
SM1 =0.87
+ 0.094
54
1. Determination of DTD and DTM for the bearings
![Page 55: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/55.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Effective isolated period at maximum displacement:
W = 107 MN
2Typemin1 Typeminmin 3420 MMM kkk +=
55
1. Determination of DTD and DTM for the bearings
![Page 56: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/56.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assume a maximum displacement, DM
Determine minimum effective stiffness of the bearings, kMmin, at a displacement DM.
Calculate the effective isolated period, TM, at a displacement DM:
Calculate the equivalent viscous damping ratio, ζ, and the damping reduction factor BD.
Calculate an updated maximum displacement, DM∗ :
? DM ≈ DM*
Yes No Preliminary design completed DM = DM *
*
56
![Page 57: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/57.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings 57
4-Story Isolated Building Example
![Page 58: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/58.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
DM = 485.3 mm; kMmax =71.68 kN/mm, TM = 2.68 s
DTM = 607.2 mm
58
1. Determination of DTD and DTM for the bearings
e = 600 mm CM (isolation)
73.2 m
45.75 m CM (building)
e = 600 mm
![Page 59: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/59.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Minimum design force under the isolation plane:
Minimum design force over the isolation plane:
( )( ) MN23.80mm311.6kN/mm76.39 ==bV
( ) 2226.2683
831 =→≤===≤ II RRR
( )( ) MN11.902
mm311.6kN/mm76.39==sV
59
2. Determination of minimum design force under and over the isolation plane
![Page 60: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/60.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Vs cannot be less than: I. The design force on the structure with the same seismic
weight W on a rigid base according to the equivalent lateral force procedure of ASCE 7-10 but with an effective period TD.
II. The lateral force required to activate the isolation
system multiplied by 1.5. III. The design wind load according to ASCE 7-10. This verification is not made here.
( )
( )
DSs s
e
D1
e
SV C W with : CR I
ST R I
= =
≤( ) ( ) ( ) OKMN90.11MN99.5MN1075.1659.2
58.011 =<=== s
eD
D VWIRT
SV
( ) ( ) ( )( )( )OKMN90.11MN01.11
mm50kN/mm84.234kN/mm51.2205.134205.1
2
max,2max,1max,2
=<=
+=+=
s
yee
VVDkkV
60
2. Determination of minimum design force under and over the isolation plane
![Page 61: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/61.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Design spectral acceleration at a period of 1 second is less than or equal to 0.6 g. SD1 =0.58
Structure is located on soil type A, B, C, or D. Soil type D
Structure above isolation interface not more than four stories or 20 m in height. Total height of the building = 19.52 m
Isolated period of structure at design displacement less than or equal to 3 seconds. TD = 2.59 s
61
3. Verification of applicability of equivalent static force procedure
![Page 62: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/62.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Isolated period of structure at design displacement greater than three times the elastic fixed-based period of the structure. Use the empirical formula of ASCE 7-10 for the fundamental period of
concentrically braced frame: Ta = 0.0488 hn0.75 where hn is the total height
of the building in meters.
The structure is regular: by assumption The isolation system does not limit MCE displacement to less than the
total maximum displacement. To insure during the design of the bearings.
( )( ) s59.2s35.1s45.03= 3
s45.0m52.190488.0 0.0488 = 75.0750
=<===
Da
.na
TThT
62
3. Verification of applicability of equivalent static force procedure
![Page 63: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/63.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
( )
( ) ( )
( )( ) ( )
kN/mm85.031kN/mm56.1
mm6.311kN31.487
kN31.487mm50mm6.311kN/mm32.1mm50kN/mm84.2
kN/mm85.0mm32.623kN26.158
31
kN26.158mm50mm32.62kN/mm32.1mm50kN/mm84.2:2 Type Bearings
mm32.62mm6.3112.02.0
20
=>==
=−+=
==
=−+=
==
DD
D
D
D
DD
D
D
D.
D
kk
F
k
F
D
50 mm
0.92 kN/mm
0.77 kN/mm
2.51 kN/mm
2.09 kN/mm
Type 1
50 mm
1.31 kN/mm
1.10 kN/mm
2.84 kN/mm
2.37 kN/mm
Type 2
( )
( ) ( )
( )( ) ( )
kN/mm73.031kN/mm18.1
mm6.311kN17.366
kN17.366mm50mm6.311kN/mm92.0mm50kN/mm51.2
kN/mm73.0mm32.623kN83.136
31
kN83.136mm50mm32.62kN/mm92.0mm50kN/mm51.2:1 Type Bearings
mm32.62mm6.3112.020
20
=>==
=−+=
==
=−+=
==
DD
D
D
D
DD
D
D
D.
D
kk
F
k
F
D.
63
3. Verification of applicability of equivalent static force procedure
Effective stiffness of the isolation system at design displacement greater than 1/3 of effective stiffness at 20% of design displacement.
Same conclusion if minimum stiffness values are used.
![Page 64: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/64.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
The isolation system configured to produce a restoring force such that the lateral
force at the total design displacement is at least 0.025W greater than the lateral force at 50 percent of the total design displacement.
Same conclusion if minimum stiffness values are used.
50 mm
0.92 kN/mm
0.77 kN/mm
2.51 kN/mm
2.09 kN/mm
Type 1
50 mm
1.31 kN/mm
1.10 kN/mm
2.84 kN/mm
2.37 kN/mm
Type 2
( )
( ) ( )( ) ( )
( ) ( )( ) ( ) kN14.587mm50mm8.389kN/mm31.1mm50kN/mm84.2
kN82.331mm50mm9.194kN/mm31.1mm50kN/mm84.2:2 Type Bearings
kN12.438mm50mm8.389kN/mm92.0mm50kN/mm51.2
kN81.258mm50mm9.194kN/mm92.0mm50kN/mm51.2:1 Type Bearings
mm9.194mm8.3895.05.0
50
50
=−+=
=−+=
=−+=
=−+=
==
TD
TD
TD
TD
D
D.
D
D.
TD
F
F
F
F
DDTD0.5DTD
Force
Déplacement
TDDF
TDDF
5.0
WFFTDTD DD
025.05.0
+≥
( ) ( )( ) ( )
( ) MN14.19MN1070.025MN46.16025.0MN73.28
MN46.16kN82.33134kN81.25820
MN73.28kN14.58734kN12.43820:System Isolation Complete
50
50
=+=+≥=
=+=
=+=
WFF
F
F
TDTD
TD
TD
D.D
D.
D
64
3. Verification of applicability of equivalent static force procedure
![Page 65: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/65.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
8. Project Example Design of a Base Isolated Building per
ASCE 7-10 Standard
Contributor: Jorge Mario Cueto Baiz
65
![Page 66: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/66.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
General Description of the Building • Use
– Residential • Plan Dimensions
– 20 m x 20 m • Floor Area
– 340 m2
(Residential) – 430 m2
(Basement)
66
![Page 67: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/67.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
General Description of the Building • # of Floors
– 10 + 2 Basements
• Story Height – 2.40m
67
![Page 68: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/68.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
General Description of the Building • Structural System
– This building has two different structural systems.
– Residential Floors (Upper System) • Reinforced Concrete (RC) Bearing Walls with flat RC slab. • Walls Thickness: 0.12m • Slabs Thickness: 0.10m
– Basement Floors (Lower System)
• RC Structural Walls with ribbed slab • Walls Thickness: 0.40m
68
![Page 69: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/69.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
General Description of the Building • Comments on the Structural System (Why two?)
– Big cities have one common problem: lack of space. – Bearing Walls is a cheap and fast way to construct residential
buildings. – Walls systems are not good to provide space for parking lots,
therefore, frame systems must be used for basements. – This means that the systems must be combined, however:
• The design must meet a significant number of requirements imposed by codes.
• The behavior of the overall building is driven by the interface between both systems.
• That interface is subjected to a high demands from the upper level which might leads to a non-ductile behavior. That is undesirable.
69
![Page 70: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/70.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
General Description of the Building • Base Isolation as a Solution
– Instead of combining the systems, let’s divide them using an adequate interface called: The Isolation Level.
– Two reasons why this building is expected to be a good candidate: • Look at the overall dimensions of the upper system: 20 x 20 x 25 m, is almost a cube! • The upper system has several walls. This means that its behavior will be close to a rigid
body. Keep in mind that not all the walls have to be structural.
– However, there are issues to be aware of: • Accommodate the displacement in the interface. Stairs, elevators, ducts, access ramps, etc.
This is the most critical one but is a reminder that the success of these kind of projects relies on the interaction of all the professional involved: architect, electrical, structural, geotechnical, etc.
• The elements that will support the isolators could end up being so massive that the parking space is significantly reduced.
70
![Page 71: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/71.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Analysis • Dead Load (DL)
– Self Weight • A preliminary model could be built in order to have a sense of
the self-weight of the structural elements.
• SW Upper Level: 28470kN
• SW Lower Level: 7900 kN
71
![Page 72: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/72.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Analysis • Dead Load (DL)
– External • This load will depend on several aspects such as:
– Use of the building (Luxurious condos and rental apartments will have different type of finishing).
– Materials to be use in the nonstructural walls. – Non structural components different than the walls (ceilings, ducts, etc.). – The finishing and the nonstructural components are different in the
residential floors, in the basements levels and in the roofs.
• For this particular case, the external dead loads are: Upper Level: 2.0 kN/m2 x (340 m2 x 10 + 430 m2 x 1 ) = 7660 kN Lower Level: 1.2 kN/m2 x (430 m2 x 1 ) = 516 kN
72
![Page 73: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/73.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Analysis • Live Load (LL)
– Using the ASCE 7-10; Table 4-1.
• For this case in particular the live loads are: Upper Level: 7030 kN Lower Level: 830 kN
73
![Page 74: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/74.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Analysis • Summary
DL (SW + Ext) LL(kN) (kN)
36130 7030
8416 830ISOLATION LEVEL
SEISMIC WEIGHT TO ISOLATE
74
![Page 75: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/75.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Specific Location
– The project is assumed to be located in: Palos Verdes, California, 90274(USA).
75
![Page 76: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/76.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Risk Category and Importance Factor. ASCE 7-
10
–For seismically isolated buildings, Table 1.5-2 DOES NOT APPLY, instead:
RESIDENTIAL
I ASCE 7-10, Table 1.5-11 ASCE 7-10, 17.2.1
USERISK CATEGORY
Importance Factor
76
![Page 77: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/77.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– Site Class: the geotechnical report for this project specifies the soil parameters and classifies it as a soft rock. According to ASCE 7-10, Table 20.3-1 the Site class is:
77
![Page 78: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/78.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– Spectral Response Acceleration Parameters: The USGS US Seismic Design Map Web Application is used to obtain the basic parameters to build up both spectra, DE and MCE. The input data is:
78
![Page 79: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/79.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– Spectral Response Acceleration Parameters: The output provided by the USGS US Seismic Design Map Web Application is:
79
![Page 80: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/80.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– Site Coefficients: With the basic parameters from USGS application output, ASCE 7-10, Table 11.4-1 and -2 are used to compute Fa and Fv.
80
![Page 81: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/81.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– MCE and Design Spectral Acceleration Parameters: As per ASCE 7-10, 11.4.3 and 11.4.4:
SMS=FaSs = 1.0x1.498 =1.498
SM1=FvS1 = 1.3x0.574 = 0.746
SDS=2/3SMS = 0.67x1.498 = 0.999
SD1=2/3SM1 = 0.67x0.746 = 0.497 81
![Page 82: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/82.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– MCE and Design Response Spectra: Following the steps in ASCE 7-10, 11.4.5, the spectral information and graphs is as follows:
SITE CLASS C SMS (g) 1.498 To (s) 0.100SS (g) 1.498 SM1 (g) 0.746 Ts (s) 0.498S1 (g) 0.574 SDS (g) 0.999 TL (s) 8.00
FA 1.00 SD1 (g) 0.497FV 1.30
ASCE 7-10, Fig. 22-12
82
![Page 83: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/83.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Location and Seismic Hazard Information • Seismic Hazard Information
– Seismic Design Category (SDC) As per ASCE 7-10, 11.6.
Risk Cat. IS1 < 0.75 YES
SDC - SDS D SDC Due to SDS, Table 11.6-1SDC - SD1 D SDC Due to SD1, Table 11.6-2
SDC D
83
![Page 84: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/84.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis • Modeling
– SAP2000 is used to model the structure.
84
![Page 85: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/85.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis • Periods and Mode Shapes
– MODE 1 • T1 = 0.81s • Main Direction: Rotational
85
![Page 86: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/86.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis • Periods and Mode Shapes
– MODE 2 • T2 = 0.58s • Main Direction: Y
86
![Page 87: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/87.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis • Periods and Mode Shapes
– MODE 3 • T3 = 0.52s • Main Direction: X
87
![Page 88: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/88.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis – Period Determination. ASCE 7-10; 12.8.2
• T < Cu x Ta , where Ta is from eq 12.8-7 and Cu is from Table 12.8-1.
– Ta = Ct x hnX
– Tmax = Cu x Ta
– T from model THEREFORE:
hn (m) 25Ct 0.049x 0.75
Ta (s) 0.55
SD1 0.497Cu 1.40 Table 12.8-1
Tmax (s) 0.77
Mode T UpFixed (s) Direction1 0.810 Rotational2 0.580 Y3 0.516 X
Tx (S) 0.52Ty (S) 0.58
Definite Fundamental Periods
88
![Page 89: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/89.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis – Irregularities. ASCE 7-10; Table 12.3-1 & Table 12.3-2 – 1aH and 1bH Torsional and Extreme Torsional
10 0.0648 0.0452 0.0085 0.0086 0.0100 OK NA NA 1.009 0.0563 0.0393 0.0085 0.0086 0.0101 OK NA NA 1.008 0.0478 0.0335 0.0085 0.0086 0.0100 OK NA NA 1.007 0.0393 0.0276 0.0082 0.0084 0.0097 OK NA NA 1.006 0.0311 0.0219 0.0078 0.0079 0.0092 OK NA NA 1.005 0.0233 0.0165 0.0071 0.0073 0.0085 OK NA NA 1.004 0.0162 0.0115 0.0062 0.0063 0.0074 OK NA NA 1.003 0.0100 0.0072 0.0050 0.0051 0.0060 OK NA NA 1.002 0.0050 0.0036 0.0035 0.0036 0.0042 OK NA NA 1.001 0.0015 0.0011 0.0015 0.0016 0.0019 OK NA NA 1.00
TSLAB 0.0000 0.0000 0.0000 0.0000 0.0000 Apply Ax 0 0 #¡DIV/0!
10 0.0695 0.064203 0.0092 0.0105 0.0123 OK NA NA 1.009 0.0602 0.055869 0.0092 0.0106 0.0123 OK NA NA 1.008 0.0510 0.047493 0.0091 0.0105 0.0122 OK NA NA 1.007 0.0418 0.039162 0.0089 0.0102 0.0119 OK NA NA 1.006 0.0330 0.031031 0.0084 0.0097 0.0113 OK NA NA 1.005 0.0246 0.023296 0.0076 0.0088 0.0103 OK NA NA 1.004 0.0170 0.016194 0.0066 0.0077 0.0090 OK NA NA 1.003 0.0104 0.009991 0.0053 0.0062 0.0072 OK NA NA 1.002 0.0051 0.004987 0.0036 0.0043 0.0050 OK NA NA 1.001 0.0015 0.001502 0.0015 0.0018 0.0021 OK NA NA 1.00
TSLAB 0.0000 0 0.0000 0.0000 0.0000 Apply Ax 0 0 #¡DIV/0!
Level δ X1 (m) δ X2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
Level δ Y1 (m) δ Y2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
δX1
δX2
δY1 δY
2
89
![Page 90: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/90.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Fixed-Base Seismic Analysis – Irregularities. ASCE 7-10; Table 12.3-1 & Table 12.3-2 – Diaphragm Irregularities
– CLASSIFICATION OF THE STRUCTURE:
3H. Diaphragm Discontinuity Irregularity
Open Area 9.1 m2.Diaph Area 337 m2.
Open Area < 0.50xDiaph Area - OK!
4H to 5H: NOT APPLICABLE
1V to 5V: NOT APPLICABLE
2H. Reentrant Corner Irregularity NOT APPLICABLE
REGULAR90
![Page 91: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/91.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Codes and References
– For the design example, reference will be made to the following documents:
1. ASCE Standard (ASCE/SEI 7-10), Minimum Design Loads for Buildings and Other Structures, American Society of Civil Engineers, Reston, Virginia.
2. C. Christopoulos and A. Filiatrault, Principles of Passive Supplemental Damping and Seismic Isolation, IUSS Press, Pavia, Italy, 2006.
3. Constantinou, M.C, Kalpakidis, I., Filiatrault, A., Ecker R.A., LRFD-Based Analysis and Design Procedures for Bridge Bearings and Seismic Isolators, MCEER Report 11-0004, September 26, 2011.
4. Constantinou, M.C, Whittaker, A.S., Kalpakidis, Y., Fenz, D.M and Warn G.P., Performance of Seismic Isolation Hardware under Service and Seismic Loading, MCEER Report 07-0012, August 27, 2007.
91
![Page 92: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/92.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Why preliminary? • The design of isolators is highly sensitive to geometry and material. • The capacity of the isolator depends on the displacement they are subjected to. This means that the
displacement has to be known (or assumed) to find out the properties. • The preliminary design then, is used to start with some initial values of the isolators and then iterate up to the
point where the displacement assumed is equal to the displacement from the spectra. Also, project requirements must be satisfied, i.e. minimum overlap factor, limits on the shape factor and maximum displacement. Then, with the values of load and maximum displacements, adequacy assessment of the stability and strength of isolators must be performed.
– Type of isolator. • The selection of the type of isolator hardware (TFP, Lead-Rubber, among others) depends on many reasons.
For this project, the isolator to be used is Lead-Rubber. – Recommended Procedure for Preliminary Design .
• There is an 8-steps procedure recommended to perform the Preliminary Design.
92
![Page 93: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/93.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Preliminary Design of Isolators – Step 1 – Geometric Properties
• Ref. 3 recommends the following as a starting point:
Do ≈ 3Di to 6Di Tr ≥ Di
Where: –Do: Diameter of rubber –Di: Diameter of the lead plug. –Tr: Total thickness of rubber.
93
![Page 94: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/94.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Step 2 – Material Properties • The properties of the material depends on fabricator, however, the
rubber and lead can be typically found with the following values:
Where: –Geff: Effective Shear Modulus of Rubber. –K: Compression modulus (or Bulk Modulus). –GLEAD: Shear Modulus of Lead. −τpy: Shear Lead Strength. –Lower and Upper Bound Values are according to recommendations of Ref. 3 and fabricator.
Average Lower Bound Upper BoundValues Values Values
Geff (MPa) 0.7 0.595 0.805K (MPa) 2000 2000 2000
GLEAD (MPa) 150 127.5 172.5
τpy (MPa) 10 8.5 11.5
MATERIAL PROPERTIES
94
![Page 95: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/95.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Step 3 – Hysteresis Information for One Isolator • The hysteresis loop can be characterized with the following
parameters:
Where: –Qd: Characteristic Strength (kN). –AL: Lead Plug Area (mm2). –Arubber: Bonded Rubber Area (mm2). –Kd: Post-elastic Stiffness (kN/mm). –Y = 25 mm as recommended in Ref. 2.
95
![Page 96: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/96.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Step 4 – Weight to Isolate and Number of Isolators
• The number of isolators is selected depending upon the requirements for the project. For this example, the
isolators are located on top of the walls of the lower system.
NUMBER OF ISOLATORS : 28
96
![Page 97: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/97.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Preliminary Design of Isolators – Step 5 – Properties of the System of Isolators
• With the number of isolators, the characteristics parameters for the hysteresis loop of all the isolators can be computed:
• Where N Is the number of isolators.
97
![Page 98: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/98.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Preliminary Design of Isolators – Step 6 – Assumption of Displacement Xb and
Computation of Dynamic Properties:
98
![Page 99: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/99.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Step 7 – Computation of Design Displacement (Sd) and Verification of Xb
• With the damping of the system and the information of the response acceleration spectra given, the design displacement can be computed.
• To do so, a damping modification factor B must be computed, according to Ref. 3:
• With the period Teff and the displacement reduced response spectra, Sd can be read and iteration on Xb must be performed until Xb=Sd.
99
![Page 100: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/100.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Step 8 – Preliminary Checking • Some limits are checked in order to have preliminary results on
parameters that might changes assumptions done at the beginning. These are:
– Project Requirement Checking:
» Maximum Displacement. For this project, the maximum displacement allowed due to issues with the ducts is 250mm.
Xb ≤ 250mm
– Overlapping Area Factor (Ar /A ) and Shape Factor (S) Checking: » This initial checking estimates buckling and shear strain issues.
100
![Page 101: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/101.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Preliminary Design of Isolators
– Summary Flow Chart for Preliminary Design
101
![Page 102: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/102.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Results from Preliminary Analysis – Once the iterative process is done for both, lower bound
(LB) and Upper Bound (UB) properties, two targets are sought:
1. Dynamic Properties of the System:
DE MCE DE MCEβEFF 0.208 0.161 0.223 0.18
Teff (s) 1.72 1.88 1.41 1.57Sd (mm) 137 230 110 189
LOWER BOUND UPPER BOUND
102
![Page 103: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/103.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Results from Preliminary Analysis
2. Material Properties for Modeling: 2.1 Lateral Properties
Keff is the only one that changes because is the only one dependent on the displacement.
2.2 Vertical Stiffness
All these values are for the system, therefore, have to be divided by 28.
DE MCE DE MCEK1 SYSTEM (kN/mm) 120 120 163 163
Fy SYSTEM (kN) 3006 3006 4067 4067
Qd SYSTEM (kN) 2692 2692 3642 3642Kd SYSTEM (kN/mm) 29.4 29.4 39.8 39.8
KEFF (kN/mm) 49.1 41.1 72.9 59.1
LOWER BOUND UPPER BOUND
For Non linear Analysis Cases
For Linear Analysis Cases
LB UBKvγ (kN/m) 1962261 2654824
KvV (kN/m) 3392920 3392920
KVERTICAL (kN/m) 1243244 1489416
103
![Page 104: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/104.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Selection of analysis Procedure. ASCE 7-10, 17.4
– Seven criteria must be evaluated to know which procedure is applicable. This selection is only for Equivalent Lateral Force (ELF) or Modal Response Spectrum Analysis (MRSA). Time-History Analysis (THA) is always permitted
LOWER BOUND
1. S1 (g) 0.574 OK!
2. SITE CLASS C OK! (ELF and MRSA)
3. Height Above Isol (m) 24 ELF IS NA!!3. # of Floors 10 ELF IS NA!!
4. TM (s) 1.88 Tm < 3.0 s; OK!
Tx FIXED-BASE (s) 0.52
Ty FIXED-BASE (s) 0.58
3 x TMAX FIXED-BASE (s) 1.74
5. TD (s) 1.72 Td < 3Tfix; ELF IS NA!!
6. REGULAR? REGULAR OK!
7a Effective Stiffness Keff at Xb (kN/mm) 49.1
Keff at 0.2Xb (kN/mm) 128 OK! (ELF and MRSA)7b Restoring Force Xb (mm) 137
F at Xb (kN) 6303
0.5Xb (mm) 69
F at 0.5Xb (kN) 4286 OK! (ELF and MRSA)
104
![Page 105: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/105.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Selection of analysis Procedure. ASCE 7-10, 17.4 UPPER BOUND
1. S1 (g) 0.574 OK!
2. SITE CLASS C OK! (ELF and MRSA)
3. Height Above Isol (m) 24 ELF IS NA!!3. # of Floors 10 ELF IS NA!!
4. TM (s) 1.57 Tm < 3.0 s; OK!
Tx FIXED-BASE (s) 0.52
Ty FIXED-BASE (s) 0.58
3 x TMAX FIXED-BASE (s) 1.74
5. TD (s) 1.41 Td < 3Tfix ELF IS NA!!
6. REGULAR? REGULAR OK!
7a Effective Stiffness Keff at Xb (kN/mm) 72.9
Keff at 0.2Xb (kN/mm) 205 OK! (ELF and MRSA)7b Restoring Force Xb (mm) 110
F at Xb (kN) 7452
0.5Xb (mm) 55
F at 0.5Xb (kN) 5262 OK! (ELF and MRSA)
USE: MRSA 105
![Page 106: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/106.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis
– Objectives: • # of modes to use. • Determine isolated and non-isolated modes and periods. • Verify mass participation > 90%. • Build up the “Reduced Spectra”. • Must be done for Lower and Upper Bound and DE and MCE. • Check seismic design requirement as per ASCE 7-10.
– Number of Modes to Use: • It is recommended to use:
– (Number of DOF x 3) + (Number of Isolators x 3 ). – 14* x 3 + 28 x 3 = 126 modes.
» * 14 = 10 residential floors + 2 machinery and elevators roofs + 2 basements.
106
![Page 107: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/107.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis
– Isolated and Non-Isolated Modes. • This is done in order to identify the periods of vibration that
will be reduced by the new damping introduced by the isolator. • In this example, the first three modes were clearly isolated. • ISOLATED MODES:
• NON-ISOLATED FIRST THREE MODES:
Mode 1 Mode 2 Mode 3
Mode 4 Mode 5 Mode 6
107
![Page 108: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/108.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis. (LB – DE)
– Isolated Periods and Mass Verification.
TABLE: Modal Participating Mass RatiosOutputCase StepType StepNum Period UX UY UZ SumUX SumUY SumUZ
Text Text Unitless Sec Unitless Unitless Unitless Unitless Unitless UnitlessMODAL Mode 1 1.805304 0.00176 0.83951 2.41E-09 0.00176 0.83951 2.41E-09MODAL Mode 2 1.792631 0.84255 0.00193 3.059E-07 0.84431 0.84144 3.083E-07MODAL Mode 3 1.519694 0.00133 0.00277 2.126E-08 0.84565 0.8442 3.295E-07MODAL Mode 4 0.543093 2.252E-07 0.00172 3.795E-07 0.84565 0.84592 7.09E-07MODAL Mode 5 0.413024 7.226E-06 0.00338 4.397E-07 0.84565 0.8493 1.149E-06MODAL Mode 6 0.40044 0.0035 6.197E-06 0.00003517 0.84915 0.84931 0.00003632
MODAL Mode 66 0.01282 2.887E-06 0.00047 0.00135 0.98762 0.99247 0.90003MODAL Mode 67 0.012592 0.0000222 0.00094 0.00147 0.98764 0.99341 0.9015MODAL Mode 68 0.011889 0.00003171 0.00035 0.00088 0.98767 0.99376 0.90237MODAL Mode 69 0.011391 2.767E-06 0.0011 0.00022 0.98767 0.99486 0.90259MODAL Mode 70 0.011 0.00008376 4.638E-06 0.0005 0.98776 0.99487 0.9031
108
![Page 109: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/109.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis. (LB – MCE)
– Isolated Periods and Mass Verification.
TABLE: Modal Participating Mass RatiosOutputCase StepType StepNum Period UX UY UZ SumUX SumUY SumUZ
Text Text Unitless Sec Unitless Unitless Unitless Unitless Unitless UnitlessMODAL Mode 1 1.959463 0.00094 0.84343 1.128E-09 0.00094 0.84343 1.128E-09MODAL Mode 2 1.948408 0.84453 0.00101 2.169E-07 0.84547 0.84445 2.18E-07MODAL Mode 3 1.630073 0.00117 0.00114 1.617E-08 0.84663 0.84559 2.342E-07MODAL Mode 4 0.554051 1.826E-07 0.00124 3.975E-07 0.84663 0.84683 6.317E-07MODAL Mode 5 0.415845 0.00000469 0.00239 4.267E-07 0.84664 0.84922 1.058E-06MODAL Mode 6 0.403004 0.00246 4.096E-06 0.00003569 0.8491 0.84922 0.00003675
MODAL Mode 67 0.012607 0.00002566 0.00096 0.00158 0.98762 0.99405 0.90155MODAL Mode 68 0.011882 0.00002191 0.00036 0.00085 0.98764 0.99442 0.9024MODAL Mode 69 0.011397 5.029E-07 0.00126 0.00023 0.98764 0.99568 0.90263MODAL Mode 70 0.010996 0.00008992 4.101E-07 0.00048 0.98773 0.99568 0.90312MODAL Mode 71 0.009875 0.0002 0.00051 0.00002329 0.98793 0.99619 0.90314
109
![Page 110: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/110.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis. (UB – DE)
– Isolated Periods and Mass Verification.
TABLE: Modal Participating Mass RatiosOutputCase StepType StepNum Period UX UY UZ SumUX SumUY SumUZ
Text Text Unitless Sec Unitless Unitless Unitless Unitless Unitless UnitlessMODAL Mode 1 1.520651 0.00372 0.82 9.972E-09 0.00372 0.82 9.972E-09MODAL Mode 2 1.502621 0.83607 0.0044 6.376E-07 0.83979 0.8244 6.475E-07MODAL Mode 3 1.321077 0.00206 0.01467 3.431E-08 0.84184 0.83908 6.819E-07MODAL Mode 4 0.51306 2.35E-07 0.00342 3.261E-07 0.84185 0.8425 1.008E-06MODAL Mode 5 0.404853 0.00001963 0.00703 4.831E-07 0.84186 0.84953 1.491E-06MODAL Mode 6 0.39304 0.00746 0.00001599 0.00003358 0.84933 0.84955 0.00003507
MODAL Mode 67 0.012489 0.00001133 0.00072 0.00058 0.98769 0.99104 0.90138MODAL Mode 68 0.011918 0.00004821 0.00029 0.00097 0.98774 0.99133 0.90236MODAL Mode 69 0.011396 0.00001479 0.00055 0.00016 0.98775 0.99187 0.90252MODAL Mode 70 0.01101 0.00007117 0.00004731 0.00055 0.98783 0.99192 0.90307MODAL Mode 71 0.009766 0.00035 0.00073 0.0000236 0.98818 0.99265 0.9031
110
![Page 111: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/111.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis. (UB – MCE)
– Isolated Periods and Mass Verification.
TABLE: Modal Participating Mass RatiosOutputCase StepType StepNum Period UX UY UZ SumUX SumUY SumUZ
Text Text Unitless Sec Unitless Unitless Unitless Unitless Unitless UnitlessMODAL Mode 1 1.664335 0.00268 0.83306 4.79E-09 0.00268 0.83306 4.79E-09MODAL Mode 2 1.649563 0.83996 0.00301 4.32E-07 0.84263 0.83607 4.37E-07MODAL Mode 3 1.420457 0.00159 0.00618 2.72E-08 0.84422 0.84225 4.64E-07MODAL Mode 4 0.530193 2.54E-07 0.00238 3.57E-07 0.84422 0.84463 8.21E-07MODAL Mode 5 0.409602 0.00001137 0.00477 4.57E-07 0.84423 0.8494 1.278E-06MODAL Mode 6 0.397337 0.00499 0.00000955 0.00003452 0.84923 0.84941 0.0000358
MODAL Mode 66 0.01281 3.85E-07 0.00053 0.0006 0.98764 0.9916 0.90025MODAL Mode 67 0.012563 0.0000182 0.00088 0.0012 0.98766 0.99248 0.90145MODAL Mode 68 0.011899 0.00004062 0.00033 0.00091 0.9877 0.99282 0.90236MODAL Mode 69 0.011388 6.987E-06 0.00088 0.0002 0.98771 0.99369 0.90256MODAL Mode 70 0.011004 0.00007795 0.00001739 0.00053 0.98779 0.99371 0.90308
111
![Page 112: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/112.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Modal Response Spectrum Analysis.
– Comments on the Isolated Periods and Mass Verification. • The following table shows the periods computed previously in the
Preliminary Analysis and the extracted from the Modeling process.
• Isolated translational modes (T1 and T2) vs Teff… Why the difference?
– Influence of the translational natural modes of the building. Suggesting that the “Rigid Body” is, as expected, not that rigid. – Influence of the base of the isolators which is not fixed but is an structural system with its own stiffness.
• Isolated rotational mode (T3) vs T1 and T2 … Why the difference? – Strong Influence of the rotational natural mode of the building. Somehow expected because in the fixed-base structure, the
fundamental mode is rotational and is 40% bigger than translational fixed-base.
DE MCE DE MCEPreliminary Analysis Teff (s) 1.72 1.88 1.41 1.57
T1 (s) 1.81 1.96 1.52 1.66
T2 (s) 1.79 1.95 1.50 1.65
T3 (s) 1.52 1.63 1.32 1.42
Modelling
LOWER BOUND UPPER BOUND
112
![Page 113: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/113.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Effective Damping and Reduced Spectra
– Once the analysis is done, the reduced spectra can be build by applying the reduction due to the damping for the isolated modes and keeping in 5% the damping for the rest of the spectrum.
– LB - DE
1 1.812 1.793 1.52
ISOLATED MODES
DAMPING and REDUCTION FACTOR
β system 0.208B 1.53
β < 30%, ASCE 7-10; 17.6.3.3
113
![Page 114: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/114.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Effective Damping and Reduced Spectra
– LB - MCE
1 1.962 1.953 1.63
ISOLATED MODES
DAMPING and REDUCTION FACTOR
β system 0.161B 1.42
β < 30%, ASCE 7-10; 17.6.3.3
114
![Page 115: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/115.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Effective Damping and Reduced Spectra – UB - DE
1 1.522 1.503 1.32
ISOLATED MODES
DAMPING and REDUCTION FACTOR
β system 0.223B 1.57
β < 30%, ASCE 7-10; 17.6.3.3
115
![Page 116: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/116.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Effective Damping and Reduced Spectra
– UB – MCE
• Note: These spectra are already affected by the damping provided by the isolator system. Therefore, the function damping ratio and the modal damping specified in the program shall be zero!
1 1.662 1.653 1.42
ISOLATED MODES
DAMPING and REDUCTION FACTOR
β system 0.180B 1.47
β < 30%, ASCE 7-10; 17.6.3.3
116
![Page 117: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/117.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Seismic Design Requirements – For the dynamic analysis, the ASCE 7- Chapter 17,
specifies four criteria to be met: 1. Minimum Lateral Force – ASCE 7-10, 17.6.4.1 & 17.6.4.2 2. Minimum Displacement for the Isolation System – ASCE 7-
10, 17.6.4.1 3. Scaling Design Values of Combined Response – ASCE 7-10,
17.6.4.3 4. Checking Minimum Design Shear Stories – ASCE 7-10,
17.6.3.3
117
![Page 118: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/118.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Minimum Lateral Force. • Design Displacement (DD) and MCE Displacement (DM) must
be computed according to 17.5.3.1 and 17.5.3.3 • Iterative process must be conducted and is shown
simultaneously for DD and DM
DD O (mm) 139 DM O (mm) 252
K D MIN (kN/mm) 49 K M MIN (kN/mm) 40
Effective Period, eq) 17.5-2TD (s) 1.73 TM (s) 1.90
Displacement - Initial ValueDisplacement - Initial Value Displacement - Initial Value
Effective Stiffness Effective Stiffness
Computation of DD and DM
Effective Period, eq) 17.5-4
Effective Stiffness
118
![Page 119: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/119.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Minimum Lateral Force. • Design Displacement (DD) and MCE Displacement (DM) must
be computed according to 17.5.3.1 and 17.5.3.3
Effective DampingβDamper 0.000 βDamper 0.000
β Isol 0.207 β Isol 0.153
β system 0.207 β system 0.153
Damping Coefficient*BD. = (βsystem/0.05)^0.3 1.53 BM. = (βsystem/0.05)^0.3 1.40
BD. = 4/(1-ln βsystem) 1.55 BM. = 4/(1-ln βsystem) 1.39*Two formulas are presented for comparison purposes only *Two formulas are presented for comparison purposes only
Damping Coefficient*
Effective Damping
(ASCE 7-10; Table 17.5-1)βD or βM (%) BD or BM.
< = 2 0.85 1
10 1.220 1.530 1.740 1.9
> = 50 2
119
![Page 120: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/120.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Seismic Design Requirements – Minimum Lateral Force.
• Design Displacement (DD) and MCE Displacement (DM) must be computed according to 17.5.3.1 and 17.5.3.3
SD1 (g) 0.497 SM1 (g) 0.746
DD (mm) eq) 17.5-1 139 DM (mm) eq) 17.5-3 252
DD O (mm) 139 Ok DM O (mm) 252 Ok
Checking Assumption of DD.
Ground Motion InfoGround Motion Info Ground Motion Info
Checking Assumption of DD.
120
![Page 121: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/121.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Seismic Design Requirements – Minimum Lateral Force.
• Minimum Seismic Force for Isolation System and Below (Vb) and Minimum Seismic Force for Elements Above (Vs) must be computed according to 17.5.4.1 and 17.5.4.2
• Computation of Vb
Base Shear (VB) for Isolator and Structure Below - 17.5.4.1
DD (mm) 139
KD MAX (kN/mm) 66
VB eq. 17.5-7 (kN) 9195
VB MIN (kN) Eq. 17.5-7
121
![Page 122: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/122.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Seismic Design Requirements – Minimum Lateral Force.
• Computation of Vs
Base Shear (VS) for Structure Above Isolator - 17.6.4.2
SMRF Table 12.2-1: A.2
Description: Spetial RC Shear Wall
R 5Ωo 2.5
Cdi 1.9 ASCE 7-10; 17.6.4.4
SDC D
Max. Height (m) 48.0 Ok; h = 24.0m < 48.0mRi = 3/8 R 1.88 OK; 1.0 < Ri < 2.0
VS MIN (kN) 4904
VS MIN Eq. 17.5-8
122
![Page 123: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/123.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Minimum Lateral Force. • Computation of Vs
SDS (g) 0.999
SD1 (g) 0.497
TL (s) 8.0
Ie (Table 1.5-2) 1
CS eq) 12.8-2 0.20
TD (s) 1.73
CS UP LIMIT eq) 12.8-3 or- 4 0.058CS MIN eq) 12.8-5 0.044
CS MIN S1 > 0.6g eq) 12.8-6 0.00
CS DEFINITE 0.058
VS MIN 1 (Cs) (kN) 2082
VS MIN 2 (Wind) (kN) 0VS MIN 3 (Fully Active) (kN) 0
VS MIN (kN) 2082
VS eq. 17.5-8 (kN) 4904
VS MIN 17.5.4.3
123
![Page 124: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/124.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Minimum Lateral Force. • For the Isolation System and the structure below, the minimum
base shear can be reduced by 10% with respect to the static analysis base shear.
• The latter is also applied to the elements above the isolation system but the reduction is of 20% if the structure is regular and 10% if is irregular.
VB eq. 17.5-7 (kN) 9195
VB MIN (kN) 8276
Structure Above: REGULARVS eq. 17.5-8 (kN) 4904
Reduction Factor 0.80VS MIN (kN) 3923
Isolation and Structure Below
Structure Above
124
![Page 125: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/125.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Minimum Displacements. • For the dynamic analysis, the total displacements can be affected by the ratio of the period of
the fixed-base structure (TFIXED) over the design period of isolated building (TD) as specified in eqs. 17.6-1 and -2. Also reduction factor of 0.8 for DE displacement and 0.9 for MCE is applicable.
b (m) 18.68 b (m) 18.68d (m) 19.16 d (m) 19.16
emax (m) 0.958 emax (m) 0.958
ymax (m) 9.58 ymax (m) 9.58
TD ISOL (s) 1.73 TM ISOL (s) 1.90
TFIXED (s) 0.52 TFIXED (s) 0.52
DD (mm) 139 DM (mm) 252
D'D (mm) 133 D'M (mm) 244
DTD (mm) 154 DTM (mm) 281Reduction Factor 0.90 Reduction Factor 0.80
D TD MIN (mm) 139 D TM MIN (mm) 225
Min. Design Displacement Min. MCE Displacement
125
![Page 126: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/126.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Seismic Design Requirements – Scaling Design Values of Combined Response
• A scale factor (SF) is computed in order for the base shear to use in the MRSA be at least the 80% (for regular structures) of the base shear (VS) from eq. 17.5-8. i.e., the minimum base shear (VS MIN)
LB – DE LB - MCE
UB – DE UB - MCE
VSPEC-D (kN) VS MIN (kN) SFX DIRECTION 3466 3923 1.13Y DIRECTION 3429 3923 1.14
VSPEC-D (kN) VS MIN (kN) SFX DIRECTION 4888 3923 1.00Y DIRECTION 4853 3923 1.00
VSPEC-D (kN) VS MIN (kN) SFX DIRECTION 4119 3923 1.00Y DIRECTION 3995 3923 1.00
VSPEC-D (kN) VS MIN (kN) SFX DIRECTION 5642 3923 1.00Y DIRECTION 5545 3923 1.00
126
![Page 127: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/127.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building
• Seismic Design Requirements – Modification Factor (MF) due to story shear distribution
• The design shear force in each story must not be smaller than the story shear using the ELF distribution and using as a base shear (Vs) the base shear that comes from the MRSA.
LB-DE
127
![Page 128: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/128.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Modification Factor (MF) due to story shear distribution LB –MCE
UB –DE
128
![Page 129: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/129.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Seismic Design Requirements
– Modification Factor (MF) due to story shear distribution
UB –MCE
– Comments on Modal Spectral Analysis:
•No advantage except for the 20% reduction in the static design base shear. •Nonlinear time-history analysis should be considered as an alternative.
129
![Page 130: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/130.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Load Combinations
– Due to the different types of structural system that are present in the project, multiple combinations are arranged for different purposes:
SDS 1.00ρ 1.30Ri 1.88Cdi 1.88Ωo 2.5Ie 1.00
Service LoadsFactored LoadsDispl, Forces and TensionDesign Upper SystemDesign TSLAB ElementsDesign Lower System
COMBINATIONS
Factored Loads
General Parameters
GROUPS
ASCE 12.4.2.3 - Combinations 5 and 6 using ρ & Ri = 1.0 ASCE 12.4.2.3 - Combinations 5 and 6 using Ωo ASCE 12.4.2.3 - Combinations 5 and 6 using ρ ASCE 12.4.2.3 - Combinations 5 and 6 with ± 0.2SDS with ρ =1.0 and using Cdi for displacements
Dead plus Live
130
![Page 131: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/131.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Seismic Analysis of Base Isolated Building • Load Combinations
– Due to the different types of structural system that are present in the project, multiple combinations are arranged for different purposes:
D L Design SPECX Design SPECY What For:D 1.0 0.0 0.0 0.0 ServiceD+L 1.0 1.0 0.0 0.0 Service1.4D 1.4 0.0 0.0 0.0 Ultimate Gravity Design Upper, Tslab and Lower1.2D+ 1.6L 1.2 1.6 0.0 0.0 Ultimate Gravity Design Upper, Tslab and LowerCOMB1 1.40 1.0 1.88 0.56 Displ. and Max. Compression Force in IsolatorsCOMB2 1.40 1.0 0.56 1.88 Displ. and Max. Compression Force in IsolatorsCOMB3 0.70 0.0 1.88 0.56 Displ. and Max. Tension Force in IsolatorsCOMB4 0.70 0.0 0.56 1.88 Displ. and Max. Tension Force in IsolatorsCOMB5 1.40 1.0 1.30 0.4 Design Upper SystemCOMB6 1.40 1.0 0.39 1.3 Design Upper SystemCOMB7 0.70 0.0 1.30 0.4 Design Upper SystemCOMB8 0.70 0.0 0.39 1.3 Design Upper SystemCOMB9 1.40 1.0 2.50 0.8 Design TSLAB ElementsCOMB10 1.40 1.0 0.75 2.5 Design TSLAB ElementsCOMB11 0.70 0.0 2.50 0.8 Design TSLAB ElementsCOMB12 0.70 0.0 0.75 2.5 Design TSLAB ElementsCOMB13 1.40 1.0 2.44 0.7 Design Lower SystemCOMB14 1.40 1.0 0.73 2.4 Design Lower SystemCOMB15 0.70 0.0 2.44 0.7 Design Lower SystemCOMB16 0.70 0.0 0.7 2.4 Design Lower System
COMBINATIONS
131
![Page 132: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/132.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Combinations Combinations for the calculations of the displacements and
compression/tension forces on the isolators.
QEX and QEY are the effects of the design seismic forces in the X and Y directions, respectively.
132
Seismic Analysis of Base Isolated Building
![Page 133: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/133.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Combinations Combinations for the calculations of the structural
elements above the isolators.
QEX and QEY are the effects of the design seismic forces
in the X and Y directions, respectively.
133
Seismic Analysis of Base Isolated Building
![Page 134: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/134.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Combinations Combinations for the calculations of the elements of
the transition slab.
QEX and QEY are the effects of the design seismic forces
in the X and Y directions, respectively.
134
Seismic Analysis of Base Isolated Building
![Page 135: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/135.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Load Combinations Combinations for the calculations of the structural
elements below the isolators.
QEX ou QEY est l'effet des forces sismiques de calcula
dans les directions X et Y, respectivement.
135
Seismic Analysis of Base Isolated Building
![Page 136: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/136.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Displacements and Tension Forces in Isolators • Isolation Level Displacements
– Following are presented the min. and max. values of total displacement throughout the 28 isolators. The total displacement is computed as the SRSS of the X and Y displacements for each isolator, for each type of analysis (LB, UB – DE, MCE) and for the appropriate combinations.
As expected, the displacements for UB are smaller than the ones from LB analysis given that the latter ones
have the lowest isolator stiffness.
LB-DE COMB 1 COMB 2δ TMIN (m) 0.186 0.200δ TMAX (m) 0.204 0.208
LB-MCE COMB 1 COMB 2δ TMIN (m) 0.230 0.237δ TMAX (m) 0.252 0.241
UB-DE COMB 1 COMB 2δ TMIN (m) 0.114 0.110δ TMAX (m) 0.126 0.126
UB-MCE COMB 1 COMB 2δ TMIN (m) 0.188 0.187δ TMAX (m) 0.207 0.203
136
![Page 137: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/137.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Displacements and Tension Forces in Isolators • Isolation Level Torsional Irregularity Factor
– The same concept applied for the non-isolated buildings, is applied it here in order to detect whether excessive rotation is occurring at the isolation level.
Torsional Irregularity if
Extreme Torsional Irregularity if
∆ MAX T =
∆ MAX E =
COMPUTATION OF ISOLATION LEVEL TORSIONAL IRREGULARITIES
δX1
δX2
δY1 δY
2
137
![Page 138: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/138.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Displacements and Tension Forces in Isolators • Isolation Level Torsional Irregularity Factor
LOWER BOUND - DE
COMB1 0.174 0.188 0.1879 0.2170 0.2532 OK NA NA 1.00
COMB2 0.196 0.189 0.1955 0.2309 0.2694 OK NA NA 1.00
OBSERV δ MAX (m) δ PROM (m) A X
OBSERV δ MAX (m) δ PROM (m) A X
COMB δ Y1 (m) δ Y2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m)
COMB δ X1 (m) δ X2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m)
LOWER BOUND - MCE
COMB1 0.218 0.235 0.2350 0.2718 0.3171 OK NA NA 1.00
COMB2 0.226 0.196 0.2262 0.2533 0.2955 OK NA NA 1.00
COMB δ X1 (m) δ X2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
COMB δ Y1 (m) δ Y2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
138
![Page 139: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/139.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Displacements and Tension Forces in Isolators • Isolation Level Torsional Irregularity Factor
UPPER BOUND - DE
COMB1 0.107 0.116 0.1165 0.1341 0.1564 OK NA NA 1.00
COMB2 0.115 0.101 0.1146 0.1296 0.1512 OK NA NA 1.00
COMB δ X1 (m) δ X2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
COMB δ Y1 (m) δ Y2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
UPPER BOUND - MCE
COMB1 0.177 0.193 0.1925 0.2216 0.2585 OK NA NA 1.00
COMB2 0.188 0.175 0.1876 0.2175 0.2537 OK NA NA 1.00
COMB δ X1 (m) δ X2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) A X
COMB δ Y1 (m) δ Y2 (m) ∆1 (m) ∆ MAX T (m) ∆ MAX E (m) OBSERV δ MAX (m) δ PROM (m) A X
OBSERV δ MAX (m) δ PROM (m)
139
![Page 140: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/140.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Displacements and Tension Forces in Isolators • Tension forces in isolators
– The type of isolators used in this project are bolted isolators. Therefore, tension forces could be developed. Ref. 4 provides a recommendation in which the maximum tension force must be limited to the cavitation force which is equal to PCAV = 3GeffA.
PCAV (kN)LB 485UB 656
COMB3 COMB4LB - DE 219 310 OK
LB - MCE 228 298 OKUB - DE 196 199 OK
UB - MCE 322 414 OK
COMPUTATION OF TENSION REACTIONS
TMAX (kN)OBSERV
140
![Page 141: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/141.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assessment of Adequacy of Isolators • General Procedure
– As the final step before designing the elements of the building, the adequacy of the lead-rubber bearings must be checked. For this, three general steps must be followed:
• Geometric and Material Properties. The properties established in the preliminary design are about to become the final design, therefore another parameters such as, rubber layers, shims layers and end plates must be included.
• Maximum Vertical Loads on Isolators. From the MRSA, the information of the forces, displacements and rotations are gathered. The displacements to be used must be bigger than the DTMIN computed previously.
• Strain, buckling and shims thickness checking. These revisions must be done for three different state of loads, i.e., Factored Vertical Load, LB-DE and LB-MCE. UB is not necessary because the max. displacements occur for LB.
141
![Page 142: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/142.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assessment of Adequacy of Isolators • Geometric and Material Properties
– For the vertical factored load (Static) it is recommended to use 80% of the nominal values. – Hysteresis loop info and vertical stiffness for the nominal values are presented in order to be compared with
the data from the fabricator.
Do (mm) 600 DYNAMICTr (mm) 160 Lower BoundDi (mm) 120 Geff (MPa) 0.7 0.56 0.595tr (mm) 8.00 K (MPa) 2000 2000 2000
Rubber Layers 20.0 GLEAD (MPa) 150 120 128
Shims 19.0 τpy (MPa) 10.0 8.0 8.5
t shims (mm) 4.76 (3/16")Fy shims (MPa) 420 Qd (kN) 113.10
End Plates (mm) 50 (2 x 1") Kd (kN/mm) 1.237Y (mm) 25
h ISOL (mm) 250 Fy (kN) 126.3
h ISOL+PLATES (mm) 300
S 18.00 KVγ (kN/m) 2308543
KVV (kN/m) 3392920
KVERTICAL (kN/m) 1373806
GEOMETRIC PROPERTIES
NOMINAL STATIC
MATERIAL PROPERTIES
HYSTERESIS LOOP INFO
VERTICAL STIFFNESS
142
![Page 143: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/143.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assessment of Adequacy of Isolators
• Maximum Loads and Displacements – From the MRSA, the loads and displacements are:
Type P (kN) D (mm) θ (rad)Factored Vertical 3350 0 0.01
LB - DE 4190 208 0.01LB - MCE 4210 252 0.01
143
![Page 144: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/144.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assessment of Adequacy of Isolators • Service Loads Checking
– Initial Data – Strain Checking – Buckling Checking – Minimum Thickness of Shims
Lat. Displ.K/G S f1 (T 5-1) γu
C-S OBSERV. γuS-S K/G S f2 (T 5-8) γu
r-S
3571 18.0 1.17 1.43 < 3.5; OK! 0.00 3571 18.0 0.32 0.900 2.33 < 6.0; OK!
COMPRESSION ROTATION OBSERV.Σ γu
C-S + γuS-S+ γu
r-S
P (kN) D (mm) θ (rad) δ. Ao Ar Ar / Ao3350 0 0.01 3.14 271434 271434 1.000
Factor Pcr (kN) P'cr (kN) Pu (kN) P'cr / Pu OBSERV.0.738 9128 9128 3350 2.72 > 2.0; OK
α. ts MIN 1 (mm) ts MIN 2 (mm) ts MIN (mm) ts (mm) OBSERV.1.65 0.38 1.9 1.90 4.76 > ts min; OK
144
![Page 145: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/145.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assessment of Adequacy of Isolators • DE Checking
– Initial Data
– Strain Checking – Minimum Thickness of Shims
P (kN) D (mm) θ (rad) δ. Ao Ar Ar / Ao4190 208 0.01 2.43 271434 154071 0.568
Lat. Displ.K/G S f1 (T 5-1) γu
C OBSERV. γuS K/G S f2 (T 5-8) γu
r
3361 18.0 1.18 3.00 < 3.5; OK! 1.30 3361 18.0 0.32 0.900 5.20 < 6.0; OK!
COMPRESSION ROTATION OBSERV.Σ γu
C + γuS+ γu
r
α. ts MIN 1 (mm) ts MIN 2 (mm) ts MIN (mm) ts (mm) OBSERV.1.65 0.90 1.9 1.90 4.76 > ts min; OK
< 7.0 OK!
Note: No buckling check required for DE.
145
![Page 146: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/146.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Assessment of Adequacy of Isolators • MCE Checking
– Initial Data – Strain Checking – Buckling Checking – Minimum Thickness of Shims
P (kN) D (mm) θ (rad) δ. Ao Ar Ar / Ao4210 252 0.01 2.27 271434 130670 0.481
Lat. Displ.K/G S f1 (T 5-1) γu
C OBSERV. γuS K/G S f2 (T 5-8) γu
r
3361 18.0 1.18 3.55 NA 1.58 3361 18.0 0.32 0.900 6.02 < 9.0; OK!
OBSERV.Σ γu
C + γuS+ γu
r
COMPRESSION ROTATION
Factor Pcr (kN) P'cr (kN) Pu (kN) P'cr / Pu OBSERV.0.738 9698 4669 4210 1.11 > 1.1; OK
α. ts MIN 1 (mm) ts MIN 2 (mm) ts MIN (mm) ts (mm) OBSERV.1.65 1.09 1.9 1.90 4.76 > ts min; OK
146
![Page 147: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/147.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Drifts and Acceleration Results • Drifts
– ASCE 7-10, 17.6.4.4 requires that for MRSA, the maximum drift shall not be higher than 1.5% the height of the floor.
– Results of drifts from previous analysis done for the building without isolators are shown.
147
![Page 148: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/148.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Drifts and Acceleration Results • Accelerations
– There is not a clear specification on the limits for the acceleration. The limits are highly dependent on the type of non-structural component within the building.
– Results of drifts from previous analysis done for the building without isolators are shown.
148
![Page 149: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/149.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Design Forces in Selected Walls • Selected Walls
149
![Page 150: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/150.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Design Forces in Selected Walls • Results of Walls in X Direction
TABLE: Section Cut Forces - SectionCut OutputCase P VX MX P VX MX
Text Text KN KN KN-m KN KN KN-mMX1A DESIGNSPECX -1551 -698 -1278 -420 -183 -356MX1A 1.4D -1054 2.0 97.8 -947 222.5 450.7MX1A 1.2D + 1.6L -1147 4.5 109.4 -1041 238.3 484.2MX1A COMB5 -2098 -369 -583 -1401 2 48MX1A COMB6 -2359 -356 -580 -1400 -161 -209MX1A COMB7 -1540 -372 -637 -920 -107 -174MX1A COMB8 -1801 -359 -634 -919 -270 -431
MX3A DESIGNSPECX -3492 -506 -15963 -776 -180 -5103MX3A 1.4D -2114 -249.4 27.2 -2341 -707.3 -1361.5MX3A 1.2D + 1.6L -2243 -273.6 -0.5 -2486 -789.8 -1577.7MX3A COMB5 -4766 -591 -7414 -3741 -960 -5393MX3A COMB6 -6194 -696 -4549 -5065 -1021 -3699MX3A COMB7 -3682 -458 -7410 -2605 -592 -4650MX3A COMB8 -5110 -562 -4545 -3929 -654 -2956
ISOLATED - Upper BoundORIGINAL
150
![Page 151: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/151.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Design Forces in Selected Walls • Results of Walls in Y Direction
TABLE: Section Cut Forces SectionCut OutputCase P VY MY P VY MY
Text Text KN KN KN-m KN KN KN-mMY1A DESIGNSPECY -2333 -1210 20881 -487 -203 7288MY1A 1.4D -2006 -1111.4 -3689.7 -2180 -767.8 -2415.6MY1A 1.2D + 1.6L -2152 -1195.9 -3985.5 -2356 -834.7 -2636.2MY1A COMB5 -4057 -1893 37 -3353 -1090 -390MY1A COMB6 -3616 -1867 5140 -2943 -1032 2661MY1A COMB7 -3013 -1312 1974 -2270 -705 826MY1A COMB8 -2571 -1286 7077 -1860 -647 3878
MY1B DESIGNSPECY -2541 -1274 27988 -746 -80 2136MY1B 1.4D -2292 1221.7 3974.5 -2691 432.8 1135.6MY1B 1.2D + 1.6L -2461 1301.8 4238.9 -2899 456.8 1194.4MY1B COMB5 -4572 419 9507 -4050 162 2727MY1B COMB6 -4066 560 16460 -3694 317 3000MY1B COMB7 -3378 -211 7453 -2719 -46 2183MY1B COMB8 -2871 -70 14407 -2363 109 2456
ISOLATED - Upper BoundORIGINAL
151
![Page 152: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/152.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
Design Forces in Selected Walls • Comments on the results (For this Project)
– Three groups were shown, why? • DesignSpec: In order to see the difference from the spectrum analysis only
without vertical loads and directional effects. In this one, it can be seen that isolating the building gives a reduction of 75% (avg) of the forces.
• 1.4D and 1.2D+1.6L: This combination is shown in order to realize that the
fact of having isolators makes that the upper system is supported in “point supports” instead of the continuous walls like in the original building. This means that the vertical displacement of the slab above the isolators, plays a significant role in the moments of the walls, and shall not be discarded when designing isolated buildings.
• COMBS 5 to 8: This is the final combination to design. In general, it can be seen that the reduction in design forces due to the isolation system is about 40%.
152
![Page 153: Chapter 10 The ASCE 7-10 Design Provisions for Seismically ...sharif.ir/~ahmadizadeh/courses/strcontrol/CIE626-Chapter-10-The... · Project Example 2 . ... Must be conducted by an](https://reader034.vdocument.in/reader034/viewer/2022051011/5aed67dc7f8b9ad73f910679/html5/thumbnails/153.jpg)
Supplemental Damping and Seismic Isolation Chapter 10 – Seismic Isolation Systems
CIE 626 - Structural Control Chapter 10 – The ASCE 7-10 Design Provisions for
Seismically Isolated Buildings
153
Questions/Discussions