chapter-4
TRANSCRIPT
![Page 1: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/1.jpg)
CHAPTER-4
DESIGN OF POWER SYSTEM
The proposed system is composed of a 100 MVA, 20KV conventional power
plant, composed of 3-phase synchronous machine, connected by 200 km long 154 KV
distributed-parameters transmission line through a step-up transformer of
20/154KV( TR1). At the substation (TR2), the voltage is stepped down to 22.9 kV from
154KV. High power industrial loads of 6MW and 330MVAR loads are connected to the
conventional source. The 10 MVA wind farms is composed of three fixed-speed
induction-type wind turbines each having a rating of 3.33MVA. The wind farm is
operating at 20KV, and is this voltage is stepped up to branch network voltages of
22.9KV through a 20KV/22.9KV transformer (TR3). The wind farm directly connects
with the branch network (B1) through a transformer (TR3) and is providing power to the
domestic loads. The 10MVA wind farm supplied to the customer loads at 400V, through
distribution transformers of 22.9KV/400V. Three domestically loads are separated by
each 5KM transmission line and at each end of 5KM transmission line a domestically
load is connected through a distribution transformer, as shown in Fig.1. The most severe
fault in the power system is three phase to ground fault, it results in very high current in
the system. The designed fault current limiter is in such a way that it should reduce the
fault current due to three phase to ground fault, then it can successfully reduces the fault
current in micro grids for all remaining faults. Artificial faults are marked as Fault 1,
Fault 2 and Fault 3, which represent three-phase-to-ground faults in distribution grid,
customer grid and transmission line respectively as shown in the Fig.1.and for each and
every fault the wind farm fault current observed. To reduce this wind farm fault current
the designed superconducting fault current limiter is placed at three scenarios for three
different faults in the power system. First, we assumed that single SFCL was located at
Location 1 (Substation). Second, single SFCL was located at Location 2 (Branch
Network). Third, single SFCL was located at Location 3 (Wind farm integration point
with the grid). Finally, in order to clarify the usefulness of dual SFCL installed together
for different locations, SFCLs were located at Location 1 (Substation) and Location 4
(Wind Farm) respectively.
![Page 2: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/2.jpg)
Superconducting fault current limiter
Superconducting Fault Current Limiter (SFCL) is innovative electric equipment
which has the capability to reduce the fault current level within the first cycle of fault
current [11]. The first-cycle suppression of fault current by a SFCL results in an
increased transient stability of the power system carrying higher power with greater
stability. The concept of using the superconductors to carry electric power and to limit
peak currents has been around since the discovery of superconductors and the realization
that they possess highly non-linear properties. More specifically, the current limiting
behavior depends on their nonlinear response to temperature, current and magnetic field
variations. Increasing any of these three parameters can cause a transition between the
superconducting and the normal conducting regime. The current increase can cause a
![Page 3: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/3.jpg)
section of superconductor to become so resistive that the heat generated cannot be
removed locally. This excess heat is transferred along the conductor, causing the
temperature of adjacent sections to increase. The combined current and temperature can
cause these regions to become normal and also generate heat. The term “quench” is
commonly used to describe the propagation of the normal zone through a superconductor.
Once initiated, the quench process is often rapid and uncontrolled. Though once initiated
the quench process is uncontrolled, the extent of the normal region and the temperature
rise in the materials can be predicted.
. SFCL performance evaluation graph indicating the relationship between SFCL impedance and reduction in fault current
![Page 4: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/4.jpg)
Simulation Model of SFCL
The resistive type SFCL was modeled considering four fundamental parameters
of a resistive type SFCL. These parameters and their selected values are: 1) Transition or
response time = 2m.sec 2) Minimum impedance = 0.01Ω. Maximum impedance = 20Ω
3) Triggering current and =550 A 4) Recovery time. = 10 msec. The SFCL working
voltage is 22.9kV. The maximum impedance value can be varied from 20 ohms to 27
ohms. The SFCL model developed in Simulink/SimPower System is shown in Fig.3.1.
The SFCL model works as follows. First, SFCL model calculates the RMS value of the
passing current and then compares it with the characteristic table. Second, if a passing
current is larger than the triggering current level, SFCL‟s resistance increases to
maximum impedance level in a pre-defined response time. Finally, when the current level
falls below the triggering current level the system waitsuntil the Recovery time and then
goes into normal state. The SFCL characteristic table shown in Fig.3.1 plays a main role
which consists of standard parameter values of SFCL.
The current limiting resistance value is calculated and this value is implemented
in the simulation model. The important parameter to be given in SFCL is the current
limiting resistance value. It is stored in the SFCL characteristic table. In order to avoid
harmonics caused by transients, filter is used. The SFCL model developed is tested in
both single phase and three phase test systems and the current waveforms are recorded
with the presence and absence of SFCL. The simulation model of a single phase test
system with and without SFCL is shown in Fig.3.2 and Fig.3.3 respectively and the
current waveforms are recorded. The fault current is induced in the source directly in
order to reduce the complexity of the simulation model.
Fault in the Distribution Grid (Fault 1)
Comparison between fault current from the wind farm (measured at output of TR3
in Fig. 1) for different SFCL locations in the case when a three-phase-to-ground fault was
initiated in the distribution grid (Fault 1 in Fig. 1).
In the case of SFCL located at Location 1 (Substation) or Location 2 (Branch Network),
![Page 5: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/5.jpg)
fault current contribution from the wind farm was increased and the magnitude of fault current is
higher than ‘No FCL’ situation. These critical observations imply that the installation of SFCL in
Location 1 and Location 2, instead of reducing, has increased the DG fault current. This sudden
increase of fault current from the wind farm is caused by the abrupt change of power system’s
impedance. The SFCL at these locations (Location 1 or Location 2) entered into cur-rent limiting
mode and reduced fault current coming from the conventional power plant due to rapid increase
in its resistance. Therefore, wind farm which is the other power source and also closer to the
Fault 1 is now forced to supply larger fault current to fault point (Fault 1).
In the case when SFCL is installed at the integration point of wind farm with the grid, marked
as Location 3 in Fig. 1, the
Comparison of the wind farm fault currents for four SFCL locations in case of fault in customer grid (Fault 2).
wind farm fault current has been successfully reduced. SFCL gives 68% reduction
of fault current from wind farm and also reduce the fault current coming from
conventional power plant because SFCL is located in the direct path of any fault current
flowing towards Fault 1.
![Page 6: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/6.jpg)
With dual SFCL installed at Location 1 and Location 4, 45% reduction in fault
current is also observed. However, even though two SFCLs were installed, wind farm
fault current reduction is lower than what was achieved by the single SFCL installed at
Location 3. From the simulation results, it was known that the installation of two SFCLs
(Location 1 and Location 4) is economically and technically not feasible.
B. Fault in Customer Grid (Fault 2)
Fig. 5 shows a comparison between fault current from the wind farm (measured at
output of TR3 in Fig. 1) for different SFCL locations in the case when a three-phase-to-
ground fault was initiated in the customer grid (Fault 2 in Fig. 1). Fault 2 is
comparatively a small fault as it occurred in low voltage customer side distribution
network. The results obtained are similar to what were observed in the case of
distribution grid (Fault 1) as explained in Section III-A.
Once again the best results are obtained when a single SFCL is located at
Location 3, which is the integration point of the wind farm with the distribution grid.
Comparison of the wind farm fault currents for four SFCL locations in case of fault in customer grid (Fault 2).
![Page 7: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/7.jpg)
Comparison of the wind farm fault currents for four SFCL locations in case of fault in transmission line (Fault 3).
The resistive type SFCL was modeled considering four fundamental parameters of a
resistive type SFCL. These parameters and their selected values are: 1) Transition or response
time = 2m.sec 2) Minimum impedance = 0.01Ω. Maximum impedance = 20Ω 3) Triggering
current and =550 A 4) Recovery time. = 10 msec. The SFCL working voltage is 22.9kV. The
maximum impedance value can be varied from 20 ohms to 27 ohms. The SFCL model developed
in Simulink/SimPower System is shown in Fig.3.1. The SFCL model works as follows. First,
SFCL model calculates the RMS value of the passing current and then compares it with the
characteristic table. Second, if a passing current is larger than the triggering current level,
SFCL‟s resistance increases to maximum impedance level in a pre-defined response time.
Finally, when the current level falls below the triggering current level the system waits until the
Recovery time and then goes into normal state. The SFCL characteristic table shown in Fig.3.1
plays a main role which consists of standard parameter values of SFCL.
![Page 8: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/8.jpg)
The current limiting resistance value is calculated and this value is implemented in the
simulation model. The important parameter to be given in SFCL is the current limiting resistance
value. It is stored in the SFCL characteristic table. In order to avoid harmonics caused by
transients, filter is used. The SFCL model developed is tested in both single phase and three
phase test systems and the current waveforms are recorded with the presence and absence of
SFCL. The simulation model of a single phase test system with and without SFCL is shown in
Fig.3.2 and Fig.3.3 respectively and the current waveforms are recorded. The fault current is
induced in the source directly in order to reduce the complexity of the simulation model.
Simulation model of single phase system with SFCL
The type of the fault induced in the model is single phase to ground fault where it is induced
through the AC voltage source. An RMS block is needed in order to calculate the RMS value of
the incoming current signal and to increase the impedance value according to the limited fault
current value specified in the SFCL characteristic table.
![Page 9: chapter-4](https://reader038.vdocument.in/reader038/viewer/2022100504/577cc9d11a28aba711a4b2b3/html5/thumbnails/9.jpg)
The SFCL subsystem can be implemented in various types of single phase test systems and the
operation can be tested. The performance of the SFCL can also be tested in a power system
generation and distribution systems using three phase SFCL for controlling the fault current for
each phase. The subsystem specified in Fig.3.2 is the SFCL model designed for single phase
system which is shown in Fig.3.3. Harmonics filtration is used in order to reduce the harmonics
caused due to the abnormal fault current. A normal first order filter is used for reducing the
harmonics. The type of the filter can be changed depending upon the application of the system. A
controlled voltage source is connected in order to compensate the voltage sag caused due to the
induced fault current which is caused due to both internal and external causes.