chapter 49

8
1 Chapter 49 Chapter 49 Cooling Towers and Cooling Towers and Pumps Pumps Cooling Tower Function Cooling Tower Function Rejects heat absorbed by the chiller to the atmosphere. Water is moved by a pump from the condenser to the cooling tower and back to the condenser. Cooling Tower Function Cooling Tower Function Compression System Example: 1. The cooling tower must reject more heat than the chiller can absorbs. 2. Heat of compression is added to the heat absorbed by the chiller. 3. The compressor adds approximately 25% additional heat 4. If a chiller absorbs 1,000 tons of heat, the cooling tower would reject about 1,250 tons of heat Cooling Tower Function Cooling Tower Function Design Temperature of water leaving the cooling tower is 85*F. The tower can cool the water down to within 7*F of the wet bulb temperature of the ambient air. Just because the pump is running doesn’t mean the fan is running. Cools the water by evaporation 1. As air passed over the water, some of it evaporates 2. This evaporating water cools the remaining water Types Of Cooling Towers Types Of Cooling Towers Natural Draft Towers Forced / Induced Draft Tower Closed Loop Hybrid Towers Dry / Wet Mode Adiabatic Mode Dry Mode Natural Draft Towers Natural Draft Towers 1. Rely on prevailing winds 2. Cool the water better when the winds are stronger 3. Operate with an approach temperature of about 10*F. 4. Spray ponds can be located at ground level or on a rooftop. 5. Rooftop spray ponds help to cool the roof and reduce the air-conditioning load 6. Use pumps to atomize the water into droplets 7. Spray nozzles must be kept clean.

Upload: prasanna-kumar-subudhi

Post on 21-Nov-2015

3 views

Category:

Documents


0 download

DESCRIPTION

ytwryw45wy4ywerqyt

TRANSCRIPT

  • 1Chapter 49Chapter 49

    Cooling Towers and Cooling Towers and PumpsPumps

    Cooling Tower FunctionCooling Tower Function

    Rejects heat absorbed by the chiller to the atmosphere.

    Water is moved by a pump from the condenser to the cooling tower and back to the condenser.

    Cooling Tower FunctionCooling Tower Function

    Compression System Example:1. The cooling tower must reject more heat

    than the chiller can absorbs.2. Heat of compression is added to the heat

    absorbed by the chiller.3. The compressor adds approximately

    25% additional heat4. If a chiller absorbs 1,000 tons of heat,

    the cooling tower would reject about 1,250 tons of heat

    Cooling Tower FunctionCooling Tower Function Design Temperature of water leaving the cooling tower

    is 85*F. The tower can cool the water down to within 7*F of the

    wet bulb temperature of the ambient air. Just because the pump is running doesnt mean the

    fan is running. Cools the water by evaporation1. As air passed over the water, some of it evaporates2. This evaporating water cools the remaining water

    Types Of Cooling TowersTypes Of Cooling Towers

    Natural Draft Towers Forced / Induced Draft Tower Closed Loop Hybrid Towers Dry / Wet Mode Adiabatic Mode Dry Mode

    Natural Draft TowersNatural Draft Towers1. Rely on prevailing winds2. Cool the water better when the winds are stronger3. Operate with an approach temperature of about

    10*F.4. Spray ponds can be located at ground level or on

    a rooftop.5. Rooftop spray ponds help to cool the roof and

    reduce the air-conditioning load6. Use pumps to atomize the water into droplets7. Spray nozzles must be kept clean.

  • 2 Mechanical draft Cooling Towers have long piping runs that spray the water downward. Large fans pull air across the dropping water toremove the heat. As the water drops downward onto the "fill" or slats in the cooling tower, the drops break up into a finer spray. On colder days, tall plumes of condensation can be seen. On warmer days, only small condensation plumes will be seen.

    This photo shows a single natural draft cooling tower as used at a European plant. Natural draft towers are typically about 400 ft (120 m) high, depending on the differential pressure between the cold outside air and the hot humid air on the inside of the tower as the driving force. No fans are used. Whether the natural or mechanical drafttowers are used depends on climatic and operating requirement conditions.

    The green flow paths show how the water is taken from a river (yellow) to an intake supply basin (green) that the Circ Water Pumps take a suction from. The water is then pumped to the Condenser where the water is heated. The water is then sent to an exit distribution basin where the water then can be returned to the river and/or pumped by the Cooling Tower Pumps to the Cooling Towers then the water returned to the intake supply basin where the water can be reused.

    The green flow paths show how the warm water leaves the plant proper, is pumped to the natural draft cooling tower and is distributed. The cooled water, including makeup from the lake to account for evaporation losses to the atmosphere, is returned to the condenser.

    Forced / Induced Draft TowerForced / Induced Draft Tower

    1. Use a fan to move air through the tower.

    2. Majority use centrifugal fans3. Can be located indoors or outdoors4. Indoor installations require

    ductwork and centrifugal blowers.

    Induced draft cooling towers, illustrated in Figure 11, are constructed such that the incoming circulating water is dispersed throughout the cooling towervia a spray header. The spray is directed down over baffles

    that are designed to maximize the contact between water and air. The air is drawn through the baffled area by large circulating fans and causes the evaporation and

    the cooling of the water

  • 3 The most economical and most common style air cooler GEA Rainey Corporation builds, the forced draft ACHE, uses axial fans to force air across the fin tube bundle. The fans are positioned below the bundle thus not exposing the mechanical sections to the hot exhaust airflow.

    The forced draft aircooler also simplifies future plant expansion by providing direct access to bundle for replacement. Structural disassembly is not required

    Closed Loop Hybrid TowerClosed Loop Hybrid Tower

    1. Equipped with a finned coil, prime surface coil, and a wet deck surface.

    2. Three modes: Dry / Wet Mode, Adiabatic mode, and Dry Mode

    Approach Temperatures in Cooling Approach Temperatures in Cooling TowersTowers

    Approach is the difference between the leaving water (where does it pump from) and the wet bulb temperature of the cooling towers entering air.

    (Talk About ) The lowest the water from the cooling tower can be is

    the wet bulb temperature of the entering air.

    Stop

    Dry / Wet ModeDry / Wet Mode

    1. Fluid to be cooled is fed first to the dry finned coil.

    2. Fluid then fed to the prime surface coil.3. Fluid then leaves the tower4. Water in the tower flows over the prime

    surface coil and wet deck surface.5. Air is drawn through the prime surface

    coil and wet deck surface.

  • 4Adiabatic TowerAdiabatic Tower1. Condenser water is cooled by evaporating tower

    water.2. No heat is added to or removed during the process3. Fluid to be cooled passes only through the finned

    coil.4. Spray water is used to help cool the air passing

    through the tower.5. Plume is the saturated discharge air.

    Dry ModeDry Mode

    1. Fluid to be cooled passes through the finned coil and the prime surface coil.

    2. No spray water is used.3. No plume results.4. Fluid is cooled by air passing over

    the coil.

    Fire ProtectionFire Protection The off season can create a fire hazard. Tower components may be flammable. A tower wetting system may be required

    1. Usually consists of sprinkler heads2. Water is sprayed over the tower periodically

    during the off season Some towers are kept wet whenever the

    temperature is above freezing

    Fill MaterialsFill Materials Designed to slow the flow of trickling water through

    the tower Splash method

    1. Uses wood slats, PVC pipe, or FRP plastic.2. Both have a slow burn rate.3. Tower has a framework to support slats at the correct

    angle. Film or wetted surface

    1. Fill is usually plastic or fiberglass2. The water is spread out over the fill as air passes over it.

    Flow PatternsFlow Patterns Crossflow

    1. Air enters from the side and is discharged from the top or the other side

    2. Tower water must be contained since the chemicals can be corrosive

    Counterflow1. Air enters from the bottom and is exhausted at the top.2. The water flows down as the air moves up

    Water that is blown out of the tower is called drift Eliminators reduce the amount of drift.

  • 5Tower MaterialsTower Materials Must withstand the environment Must withstand fan and drive mechanism vibrations Usually made of galvanized steel, fiberglass, or FRP Larger towers may have a concrete base The sides of the tower can be made of wood,

    fiberglass, corrugated FRP, or corrugated asbestos-cement panels

    (older towers) Fiberglass is the preferred material for safety reasons

    because they arent susceptible to fires like the wood towers.

    Fan SectionFan Section Belt-driven fan

    1. Primarily found on small towers2. Requires a great deal of maintenance

    Gear box transmissions1. Motors are usually mounted at a 90-degree angle to the

    fan2. Mat be designed to reduce the fan speed3. Motor, gear box, and bearings must be accessible for

    servicing

    Fan blade is located in a housing

    Tower AccessTower Access Tower fill must be accessible for cleaning or

    replacement Sludge needs to be cleaned from the tower basin Garbage, bird feathers, and other pollutants

    accumulate in the sump There is a strainer to prevent this garbage from

    entering the pump and water circuit Stairs or ladders provide access to fans and drive

    mechanisms on all towers

    Tower SumpTower Sump Area where tower water collects Sump water must not freeze

    1. Thermostatically-controlled heater2. Larger units may use a hot-water coil or low-pressure

    steam3. Antifreeze can be added to the water

    May be installed underground1. Will not freeze in southern climates2. Must be protected from freezing in northern climates

    Should be accessible for cleaning Is usually equipped with a strainer to protect the

    pump

    MakeMake--up Waterup Water Water continuously evaporates from the system Fresh (normal )water must be supplied to the

    system as needed Float valve

    1. As the water level drops, the float ball drops2. The valve will open and supply water

    Solenoid controlled valve1. Solenoid valve operation controlled by a float switch2. When float switch falls, the valve is energized

    Electrodes1. Uses to sense the water level2. Valves open and close to maintain proper water level

    Blow downBlow down Process of bleeding off a portion of the system water This water is replaced with fresh water Designed to reduce the amount of solid materials in the water

    1. As the water evaporates, it leaves solids behind2. Over time, the amount of solids increases3. Solids form a cement like substance4. Can act as an insulator in the condenser

    Blow down allows the dilution of solids in the water circuit Without blow down

    1. High head pressure2. High approach temperatures3. Condenser would need to be cleaned

    Must be done correctly1. Excessive amounts of water can be lost2. Excessive amounts of water treatment chemicals can be lost

  • 6Balancing the Water Flow for a TowerBalancing the Water Flow for a Tower

    Water flow to each of the tower cells must be equal

    Distribution pans1. Receives water returning from the

    condenser2. Have calibrated holes to distribute water3. Holes must be clean

    Balancing valves must be adjusted properly

    Water PumpsWater Pumps Responsible for moving water

    through the condenser and cooling tower circuit

    Usually a centrifugal pump Made from cast iron a majority of

    the time Close coupled pump

    1. Impeller is mounted to the motor shaft2. Used in small applications3. Shaft seal prevents water leakage

    Base Mounted PumpBase Mounted Pump Motor and pump are connected by a

    flexible coupling Can have a single or double sided

    impeller Motor and pump are mounted on a

    steel or cast iron base Base is usually cemented to the floor Motor and pump are factory aligned

    Water PumpsWater Pumps Double Inlet Impeller

    1. Allows water to enter the pump from both sides2. Can be disassembled from the ends or from the top

    Pump must have a shaft seal1. Stuffing box

    a. Packing gland type sealb. Must be tightened with a wrenchc. Used on pumps with pressure up to 150 psig

    2. Mechanicala. Used on higher pressures up to about 300 psigb. Uses a carbon ring, O-ring, and a ceramic ring

    Water PumpsWater Pumps Can be used in a vertical position Most pumps are made of cast iron Most centrifugal pump impeller are

    made of bronze The eye of the impeller must be

    under water during startup1. They cannot pump air to pull water into the impeller2. A free flow of water from the sump to the pump is

    desired

    Water PumpsWater Pumps If the pump is located higher than

    the sump, the pump must be filled with water before starting

    1. Water hose can be used2. A foot or check valve is used to keep water from flowing

    back to the sump during shutdown Whirlpool action in the pump is called vortexing

    1. Introduces air into the system2. Can be caused by poor design or installation3. Can be eliminated by cross shaped device

  • 7VortexingVortexing A whirlpool action in the sump or tower basin of a cooling tower. Vortexing is caused by insufficient surface tension on the

    liquid Symptoms 1. Pump makes a growling sound 2. Whirlpool usually visible on liquid surface 3. Loss of Flow Causes 1. There is not enough liquid height above the suction line

    entrance 2. The velocity at the suction line entrance is too high Remedy Decrease liquid velocity and/or increase submergence in

    accordance with the following table

    Water PumpsWater Pumps Strainers are located between the

    sump and the pump1. Prevents trash from entering the pump2. A coarse strainer is located at the outlet of the tower to

    the sump3. A finer strainer is usually located at the inlet to the pump4. A blocked strainer at the pump inlet will cause a

    pressure drop and may cause cavitation

    Water PumpsWater Pumps Tower Bypass Valve1. Helps to maintain correct water pressure during

    startup and low ambient conditions2. Water from the pump outlet is re-circulating to the

    pump inlet3. Prevents cold water from the condenser4. Effects of cold water entering the condenser

    a. Reduced head pressureb. Evaporator can starvec. Can cause oil migrationd. Can cause salt crystallization (absorption

    systems)

    Water PumpsWater Pumps Mixing Valve

    1. Has 2 inlets and 1 outlet2. Located in the pumps inlet line

    Diverting Valve1. Has one inlet and 2 outlets2. Usually located at the condenser outlet (return line

    to the tower)3. Water can be piped to either the tower or the pump

    inlet

    Water PumpsWater Pumps Pump motor and pumps are joined

    together by a flexible coupling in most cases.

    Pumps can have sleeve bearings or ball bearings

    1. Sleeve bearings are used in small pumps2. Ball bearings are used in larger pumps

    Pumps and shafts must be properly aligned

    Centrifugal Water PumpsCentrifugal Water Pumps Use 2 types of seals:

    1. Stuffing box2. Mechanical types

  • 8Cooling Towers Cooling Towers

    No matter the design all cooling towers need routine maintenance.

    Angular & Parallel AlignmentAngular & Parallel Alignment

    When installing or changing a pump it must be aligned to operate properly.

    Angular alignment ensures that both shafts are aligned with each other and are mounted on the same angle

    Parallel alignment ensure that the shafts are end to end.

    Dial indicators are used to ensure proper aligment.