chapter 9.simulation control

Upload: audrey-patrick-kalla

Post on 03-Apr-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 Chapter 9.Simulation Control

    1/24

    Dynamic Behavior of

    Closed-Loop Control

    Systems

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    2/24

    Control System Instrumentation

    Figure 9.3 A typical process transducer.

    Transducers and Transmitters

    Figure 9.3 illustrates the general configuration of a measurement

    transducer; it typically consists of a sensing element combined

    with a driving element (transmitter).

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    3/24

    Since about 1960, electronic instrumentation has come into

    widespread use.

    Sensors

    The book briefly discusses commonly used sensors for the most

    important process variables. (See text.)

    Transmitters

    A transmitter usually converts the sensor output to a signal level

    appropriate for input to a controller, such as 4 to 20 mA.

    Transmitters are generally designed to be direct acting.

    In addition, most commercial transmitters have an adjustableinput range (or span).

    For example, a temperature transmitter might be adjusted so that

    the input range of a platinum resistance element (the sensor) is

    50 to 150 C.

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    4/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    5/24

    Chapter9

    Instrument Selection Criteria

    solid/gas/liquid, corrosive fluidnature of signal, speed of responseaccuracy, measurement rangecostsprevious plant practiceavailable spacemaintenance, reliabilitymaterials of constructioninvasive/non-invasive

    environmental/safety (enclosures, fugitive emissions)

  • 7/28/2019 Chapter 9.Simulation Control

    6/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    7/24

    Transmitter/Controller

    Chapter9

    May need additional transducers for Gm if its output is in

    mA or psi. In the above case, Gc is dimensionless (volts/volts).

  • 7/28/2019 Chapter 9.Simulation Control

    8/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    9/24

    Figure 9.15 Nonideal instrument behavior: (a) hysteresis,

    (b) deadband.

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    10/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    11/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    12/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    13/24

    Measurement / Transmission Lags

    Temperature sensor

    make as small as possible (location, materials forthermowell)

    Pneumatic transmission lines

    usually pure time delay, measure experimentally (no

    time delays for electronic lines); less common today

    compared to electronic transmissions.

    ss

    ssM

    AU

    Cm=

    1+s

    1

    )s(T

    )s(T

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    14/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    15/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    16/24

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    17/24

    Chapter9

    from Riggs, J.B., Chemical Process Control

    Numbers in table above correspond to Cvf(l), dp in psi, q in gal/min, andgs is

    specific gravity:

  • 7/28/2019 Chapter 9.Simulation Control

    18/24

    Three valve characteristics determined by plug shape:

    (1) Quick Opening (square root trim)

    (2) Linear Trim

    (3) Equal Percentage

    must take other flow obstructions into account for actual valve

    performance

    1)s(0valvetheofopenfractions sf

    sf

    50-20f~slope1 sf

    Chapter9

  • 7/28/2019 Chapter 9.Simulation Control

    19/24

    Chapt

    er9

    See Example 9.2

  • 7/28/2019 Chapter 9.Simulation Control

    20/24

    Suppose valve has linear trim and flow must be

    changed. Ifp through exchanger does not change,

    valve would behave linearly (true for low flow rates),since it takes most ofp . For lower flow rates, p

    through exchanger will be reduced, changing effective

    valve characteristics (valve must close more than

    expected

    nonlinear behavior).

    Equal % in this case behaves more like linear valve.

    Size pvalve = 25% total p , at s=50% (p$)

    valves need to operate between 5% and 95%,

    valveP~flow

    Chapt

    er9

  • 7/28/2019 Chapter 9.Simulation Control

    21/24

    Chapt

    er9

  • 7/28/2019 Chapter 9.Simulation Control

    22/24

    Chapt

    er9

  • 7/28/2019 Chapter 9.Simulation Control

    23/24

    Pneumatic control valves are to be specified for the

    applications listed below. State whether an A-O or A-C

    valve should be specified for the following manipulatedvariables:

    (a) Steam pressure in a reactor heating coil.

    (b) Flow rate of reactants into a polymerization reactor.(c) Flow of effluent from a wastewater treatment

    holding tank into a river.

    (d) Flow of cooling water to a distillation condenser.

    Failure philosophy: Keep process pressure low,

    protect environment (equipment and engineers)

    A-O F / C

    A-C F / O

    Chapt

    er9

  • 7/28/2019 Chapter 9.Simulation Control

    24/24

    Chapt

    er9

    Previous chapter Next chapter

    http://www.che.utexas.edu/course/che360/ch8.htmhttp://www.che.utexas.edu/course/che360/ch10.htmhttp://www.che.utexas.edu/course/che360/ch10.htmhttp://www.che.utexas.edu/course/che360/index.htmlhttp://www.che.utexas.edu/course/che360/ch8.htm