chapter 9.simulation control
TRANSCRIPT
-
7/28/2019 Chapter 9.Simulation Control
1/24
Dynamic Behavior of
Closed-Loop Control
Systems
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
2/24
Control System Instrumentation
Figure 9.3 A typical process transducer.
Transducers and Transmitters
Figure 9.3 illustrates the general configuration of a measurement
transducer; it typically consists of a sensing element combined
with a driving element (transmitter).
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
3/24
Since about 1960, electronic instrumentation has come into
widespread use.
Sensors
The book briefly discusses commonly used sensors for the most
important process variables. (See text.)
Transmitters
A transmitter usually converts the sensor output to a signal level
appropriate for input to a controller, such as 4 to 20 mA.
Transmitters are generally designed to be direct acting.
In addition, most commercial transmitters have an adjustableinput range (or span).
For example, a temperature transmitter might be adjusted so that
the input range of a platinum resistance element (the sensor) is
50 to 150 C.
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
4/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
5/24
Chapter9
Instrument Selection Criteria
solid/gas/liquid, corrosive fluidnature of signal, speed of responseaccuracy, measurement rangecostsprevious plant practiceavailable spacemaintenance, reliabilitymaterials of constructioninvasive/non-invasive
environmental/safety (enclosures, fugitive emissions)
-
7/28/2019 Chapter 9.Simulation Control
6/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
7/24
Transmitter/Controller
Chapter9
May need additional transducers for Gm if its output is in
mA or psi. In the above case, Gc is dimensionless (volts/volts).
-
7/28/2019 Chapter 9.Simulation Control
8/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
9/24
Figure 9.15 Nonideal instrument behavior: (a) hysteresis,
(b) deadband.
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
10/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
11/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
12/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
13/24
Measurement / Transmission Lags
Temperature sensor
make as small as possible (location, materials forthermowell)
Pneumatic transmission lines
usually pure time delay, measure experimentally (no
time delays for electronic lines); less common today
compared to electronic transmissions.
ss
ssM
AU
Cm=
1+s
1
)s(T
)s(T
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
14/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
15/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
16/24
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
17/24
Chapter9
from Riggs, J.B., Chemical Process Control
Numbers in table above correspond to Cvf(l), dp in psi, q in gal/min, andgs is
specific gravity:
-
7/28/2019 Chapter 9.Simulation Control
18/24
Three valve characteristics determined by plug shape:
(1) Quick Opening (square root trim)
(2) Linear Trim
(3) Equal Percentage
must take other flow obstructions into account for actual valve
performance
1)s(0valvetheofopenfractions sf
sf
50-20f~slope1 sf
Chapter9
-
7/28/2019 Chapter 9.Simulation Control
19/24
Chapt
er9
See Example 9.2
-
7/28/2019 Chapter 9.Simulation Control
20/24
Suppose valve has linear trim and flow must be
changed. Ifp through exchanger does not change,
valve would behave linearly (true for low flow rates),since it takes most ofp . For lower flow rates, p
through exchanger will be reduced, changing effective
valve characteristics (valve must close more than
expected
nonlinear behavior).
Equal % in this case behaves more like linear valve.
Size pvalve = 25% total p , at s=50% (p$)
valves need to operate between 5% and 95%,
valveP~flow
Chapt
er9
-
7/28/2019 Chapter 9.Simulation Control
21/24
Chapt
er9
-
7/28/2019 Chapter 9.Simulation Control
22/24
Chapt
er9
-
7/28/2019 Chapter 9.Simulation Control
23/24
Pneumatic control valves are to be specified for the
applications listed below. State whether an A-O or A-C
valve should be specified for the following manipulatedvariables:
(a) Steam pressure in a reactor heating coil.
(b) Flow rate of reactants into a polymerization reactor.(c) Flow of effluent from a wastewater treatment
holding tank into a river.
(d) Flow of cooling water to a distillation condenser.
Failure philosophy: Keep process pressure low,
protect environment (equipment and engineers)
A-O F / C
A-C F / O
Chapt
er9
-
7/28/2019 Chapter 9.Simulation Control
24/24
Chapt
er9
Previous chapter Next chapter
http://www.che.utexas.edu/course/che360/ch8.htmhttp://www.che.utexas.edu/course/che360/ch10.htmhttp://www.che.utexas.edu/course/che360/ch10.htmhttp://www.che.utexas.edu/course/che360/index.htmlhttp://www.che.utexas.edu/course/che360/ch8.htm