chapter02 transients

Upload: muhammad-abuzar

Post on 14-Apr-2018

276 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/27/2019 Chapter02 Transients

    1/26

    Chapter 2

    Theoretical principle concern

    2.1 Transient Overvoltage in Power System2.1.1 Characteristic of Overvoltage in Power System

    Electromagnetic transient overvoltage is voltage stresses which directly

    effective to equipment in power system and especially to insulation. It is severe to the

    system in case of stored energy in the line such as trapped charge in capacitor. The

    overvoltage can be classified into two groups; the first group is external overvoltage

    such as lightning. This causes from natural events. The second group is internal

    overvoltage due to switching and temporary overvoltage as show in table: 2.1[4], [5].

    Table: 2.1 Cases and shapes of overvoltage Standard voltage shapes and

    standard withstand tests [16].

  • 7/27/2019 Chapter02 Transients

    2/26

    12

    2.1.2 Switching Overvoltage in Power System

    Switching overvoltage is one of the internal overvoltages which generate

    many changes in the operating conditions of network. There are a great variety of

    events that would initiate a switching surge in a power network, whenever a switch in

    an electric circuit is opened or closed; this is true for transmission as well as

    distribution circuits. The interruption by switching operations of a circuit having

    inductance and capacitance may result in transient oscillations that can cause

    overvoltage on the systems. The switching operations of greatest relevance to

    insulation design can be classified as following: [4], [5], [16]

    Line energization Line re-energization Switching off of small capacitive currents Switching off of small inductive currents Fault initiation Fault clearing

    As can be seen in table: 2.2, there are different ranges of switching overvoltage

    classified by causes of overvoltages for EHV system.

    Table: 2.2 Cases of switching overvoltage without protective device [6].

    p.u on phase-to-ground base

    Cause of overvoltages Value of maximum SOV (p u)

    Closing ( line energization) 2.4 2.8

    Re- Closing ( Re- energization ) 3.5 4.0

    Single phase to ground 1.5 1.7

    Double phase to ground 1.5 1.7

    Fault clearing 1.4 1.8

  • 7/27/2019 Chapter02 Transients

    3/26

    13

    2.1.2.1 Line Energization Overvoltage in Power System

    ( )c

    V tsin[ ( )]SV t T +

    Figure 2.1 Diagram of line energization switching transient [16].

    In the Figure 2.1 the inductance L represents the leakage inductance of

    transformer, and the inductance of line. The resistance R includes all series resistance

    of the line and transformer. The voltage across the capacitor C represents the voltage

    at the open circuit end of the line which is included in the scope of study.

    The circuit performance after switch on can be expressed as:

    ( ) 1( ) . ( ) ( )

    S

    di tV t R i t L i t dt

    dt C= + + , (2.1)

    The apply voltage ( )S

    V t beyond the switching instant is:

    ( ) sin( )S S

    V t V t T = + , (2.2)

    The expression for voltage across the line capacitance is:

    1( ) sin( ) sin( )t

    C CV t V t T Ae t

    = + + , (2.3)

    Where:

    2 2( . 1/ . )

    SC

    VV

    C R L C =

    + , (2.4)

    tan. 1/ .

    t R

    L C

    =

    , (2.5)

    0

    1

    LC = , (2.6)

    2 2

    1 0 12 .f = + = , (2.7)

  • 7/27/2019 Chapter02 Transients

    4/26

    14

    2

    R

    L= , (2.8)

    1 1 sin( )tancos( ) sin( )

    T

    T T

    = +

    . (2.9)

    As we can see from above expression the voltage across at opened end ( )C

    V t is

    oscillation wave form with damped-decay. However the maximum value is the most

    interesting value for design and safe operation [17].

    2.1.2.2 Switching Overvoltage with Capacitive and Inductive Currents

    1) Switching of capacitive currents: This includes capacitor banks,

    unloaded overhead lines and cables. It involves interruption of small capacitive

    currents at peak voltage. The recovery overvoltage may reach 1.5 p.u. across the

    contacts of the circuit breaker. Half a cycle later, when the voltage of the feeding side

    attains its maximum, a voltage of 2.5 p.u. is then established across the circuit breaker

    contacts which may lead to restrike of the circuit breaker [28].

    2) Switching of inductive current: When interrupting the small

    inductive currents of unloaded transformers and shunt reactors, current shopping may

    occur with the current forced to zero before natural current zero. The high di/dt

    associated with current shopping results in high induced voltage in the inductive

    circuit. This type of operation produces overvoltages of 2 to 3 p.u. in modern

    transformer; however, with transformers loaded with shunt reactors, value up to 5 p.u.

    may be reached which necessitates the use of surge arresters for protection [17].

    2.1.2.3 Switching Overvoltage with Fault Initiation and Clearing

    Initiation and closing of system faults: the most frequent fault on

    power systems is the short circuit phase to earth which is often accompanied by anincrease of neutral potential. If the fault occurs at peak voltage, then up to 2.7 p.u

    overvoltages can be generated. Reducing of ratio ( X0/X1 ), however, will

    significantly limit the overvoltage: e.g. for a configuration having a ratio equal to 1,

    no overvoltage has been observed. The single phase fault which causes an asymmetry

    is therefore the most dangerous fault. The clearing of a fault by circuit breakers, in

    particular a three phases fault, will also generate crest overvoltages of up to 3 p.u. as

    shown in Figure 2.2 [17].

  • 7/27/2019 Chapter02 Transients

    5/26

    15

    CV C

    CBL

    cosm

    SourceV V t =

    Fault

    Fault

    CB

    Figure 2.2 Equivalent circuit of transient recovery voltage when a circuit

    breaker clears a fault [18].

    The simplest circuit that can be chosen to illustrate this phenomenon is that

    shown in Figure 2.2. It is assumed that load being fed through the circuit breaker is

    suddenly isolated by the occurrence of a fault and that fault is a dead short circuit.

    Where:

    L is all the inductance limiting the current to the point of fault.

    Cis the natural capacitance of the adjacent to the circuit breaker.

    In the circuit of Figure 2.2 the current is assumed to be symmetrical and will be

    completely reactive since it is limited entirely by inductance. This means that at the

    instant of current zero, the circuit voltage will be at a maximum value, but the voltage

    at the switch contacts, and therefore across the capacitor C, will be arc voltage. The

    relative importance of the arc voltage varies.In this analysis, time will be measured from the instant of interruption when the

    fault current has just come to zero. Sine the source voltage is a sinusoidally varying

    quantity and is at its peak at the moment, it is expressed as cosm

    V t . The circuit

    equation is therefore

    cosc m

    dIL V V t

    dt+ = , (2.10)

    There are two unknowns, I and VC , so another relationship between them is

    required. This is

  • 7/27/2019 Chapter02 Transients

    6/26

    16

    cdV

    I Cdt

    = , (2.11)

    after the switch has cleared, the only path for current is into the capacitor. The

    combination of these equations gives

    2cos

    2c c m

    d V V V t

    LC LCdt+ = , (2.12)

    Let2

    01/LC = , and transform Equation 2.12:

    2 ' 2 2

    0 0

    2 2

    ( ) (0) (0) ( )c c c c m

    ss v s sV V v s V

    s

    + =

    +,

    or

    '2

    0 2 2 2 2 2 2 2 2

    0 0 0

    (0)( ) (0)

    ( )( )

    cc m c

    Vs sv t V V

    s s s s

    = + +

    + + + + (2.13)

    If we neglect are voltage the second term on the right is zero. The third term is also

    zero because, from Equation 2.11, '(0)

    (0) 0c

    IV

    C= = ,

    Therefore only the first term remains. Now

    2 2 2 2 2 2 2 2 2 2

    0 0 0

    1( )

    ( )( )

    s s s

    s s s s =

    + + + +,

    Therefore

    2

    0

    2 2 2 2 2 2

    0 0

    ( ) ( )c ms s

    v s Vs s

    =

    + +,

    and

    2

    0

    02 20

    ( ) (cos cos )c m

    V t V t t

    =

    , (2.14)

    Equation 2.13 is the voltage appearing across the switch contacts after current

    zero. It is the classical transient recovery voltage described by Park and Skeats [18].

    Almost invariably 0 >>, so that2 2 2

    0 0/ ( ) 1 . Thus to a very close

    approximation,

    0( ) (cos cos )c mV t V t t = , (2.15)

    Indeed, it often happens that over the period of interest (the time for switch the

  • 7/27/2019 Chapter02 Transients

    7/26

    17

    natural frequency oscillation persists), there is little change in the power frequency

    term. In this case equation 2.14 can be further reduced to give

    0( ) [1 cos ]c mV t V t = . (2.16)

    This is very evident from Figure 2.3 which shown as oscillogram of the current

    interruption period. In this case the transient recovery voltage oscillation (lower trace)

    lasts for about 600 s . The decline of the current to zero can be seen in the upper

    trace. It will be noted that transient recovery voltage begins with a small excursion of

    the opposite polarity to the instantaneous system voltage. This indicates some current

    chopping [18].

    Figure 2.3 Characteristic of restriking voltage [18].

    2.1.3 Temporary Overvoltage in Power System

    Temporary overvoltage is characterized by amplitude and durations,

    typically from a few cycles to a few seconds. These overvoltages differ from transient

    switching overvoltages in that they last longer. They take the form of undamed or

    slightly damped oscillation at a frequency equal or close to the power frequency. The

    classification of temporary overvoltages as distinct from transient switchingovervoltages is due mainly to the fact that responses of the power network insulation

    and surge arresters to their shapes are different. Some of the most important events

    leading to the generation of temporary overvoltages are discussed briefly as

    following: [4], [5], [17]

    Ferranti effect ( Long line effect ) Load rejection

    Transformer energization Ground faults

  • 7/27/2019 Chapter02 Transients

    8/26

    18

    2.1.3.1 Ferranti Effect Overvoltage in Power System

    ES

    XS R

    X 0S

    U

    RU

    ( )xU

    E

    l

    Figure 2.4 Equivalent of the Ferranti effect rise voltage at opened line [17].

    From Figure 2.4 the Ferranti effect of an uncompensated transmission line is

    given by

    cosh sinhS R R C

    U U l I Z l = + , (2.17)

    sinh coshRS RC

    UI l I lZ = + , (2.18)

    No load in line 0R

    I =

    coshS

    R

    Ul

    U= , (2.19)

    where:

    RU and

    SU are the receiving end and the sending end voltages,

    respectively; cZ is impedance of line and lis line length in km.

    is the phase shift constant of the line per unit length. It is equal to the

    imaginary part of 1/2( )YZ , where Z and Y are impedance and admittance

    of the line per unit length.

    Obviously for uncompensated transmission line the highest overvoltage will

    appear at the receiving end.

    For a losses line:

    LC = , (2.20)

  • 7/27/2019 Chapter02 Transients

    9/26

    19

    where:

    Land Care inductance and capacitance of the line per unit length.

    has a value of about 6per 100 km at the normal power frequency.

    When the impedance of sourceEbe consider and the shunt reactor was installed

    at the receiving end of the line [17].

    The voltage rise at the receiving end is:

    cos . cos

    cos( )

    RU

    E l

    =

    + +, (2.21)

    Where:

    RX the reactance of shunt reactor,

    SX is the transient reactance of

    generator in series with the transformer reactance and lis line length in km.

    tan SX

    Z= , (2.22)

    tanR

    Z

    X= . (2.23)

    2.1.3.2 Load Rejection Overvoltage in Power System

    E

    X

    CX V

    Figure 2.5 Equivalent circuits during load rejection [17].

    From Figure 2.5 when the transmission line or large inductive load that is fed

    from power station is suddenly switched off, the generator will speed up and busbar

    voltage will rise.

    The amplitude of the overvoltage can be evaluated approximately by

    C

    C

    XV E

    X X=

    . (2.24)

    where:

  • 7/27/2019 Chapter02 Transients

    10/26

    20

    E is voltage behind the transient reactance, which is assumed to be

    constant over the subtransient reactance of the generator in series with the

    transformer reactance [17].

    X is the transient reactance of generator in series with the transformer

    reactance

    CX is the equivalent capacitive input reactance of the system.

    2.1.3.3 Inrush Transient by Switching on Transformer

    Transformer energization creates transient inrush currents, when the

    transformers core becomes over fluxed or saturation. Transformer inrush currents can

    have a high magnitude containing a significant harmonic content. The harmonic rich

    transformer inrush currents interact with harmonic resonances of power system.

    The inrush is most severe when the transformer is switched on the instant the

    voltage goes through zero with such polarity that flux increases in the direction of

    residual flux is shown in Figure 2.6 [18].

    Figure 2.6 Equivalent circuit of a transformer.

    For condition above, we may write:

    2 sin dd

    v V t N s s dt dt

    = = = , (2.25)

    The value of the flux is then found by integration:

    0

    2sin (0)

    t

    sV tdtN

    = + , (2.26)

  • 7/27/2019 Chapter02 Transients

    11/26

    21

    where 0(0) = is the residual flux, thus

    0 02 (1 cos ) coss mV t tN

    = + = + +

    , (2.27)

    Representing winding and core losses, the periodic component 0m + , is

    obtained as a constant quantity. However, due to these losses, the aperiodic term

    decays very slowly according to the large time constant of magnetizing circuit.

    Then, at t = ( a period after switching) the instantaneous flux will be

    max 02 m = + , (2.28)

    The magnetic flux density under steady-state conditions is 1.3mB T . If

    0 is assumed to 0.6 m , then the maximal flux density, which in a transformer

    is directly proportional to the flux, will be

    max (2 0.6)1.3 3.4B T T= + . (2.29)

    The typical curve of an inrush current for a transformer switched at zero

    instantaneous voltage is shown in Figure 2.7 [19].

    Since a magnetic flux density is the ratio of magnetic flux to a given area with

    passes through equation 2.28 can be recast of following:

    max 0(2 )c mA B B = + , (2.30)

    Bm and BO are the peak steady state and residual magnetic flux density

    magnitudes, and Ac is sectional area of the transformer core. Equation 2.30 assumes

    that the flux lines are perpendicular toAc.

    Using Amperes Law, wherea

    H dl iN= and a aB H= , we can compute the

    inrush current magnitude as follow:

    0(2 ),a c

    inrush m Sat

    a

    H l A lI B B B

    N NA= = + + (2.31)

    where lis the mean length of the transformer leg and winding, Nis the number of the

    turns in winding and is the flux linkages. It should be noted that the inrush current

    magnitude estimate is the maximum theoretical value as shown in Figure 2.7.

  • 7/27/2019 Chapter02 Transients

    12/26

    22

    Figure 2.7 (A) Magnetizing curve, (B) Inrush current of transformer [18].

    2.2. Determination of Transient Overvoltages

    At present, computer is an important equipment used for analyzing the

    overvoltage in power system because of its high accuracy, speed and convenient to

    change the parameters. There are four main methods for analyzing the

    electromagnetic transient overvoltage in the transmission line which are Lattice

    Diagram, Fourier Transform, Transient Network Analysis (TNA) and

    Electromagnetic Transient Program (EMTP). The detail of each method could be

    explained as follows:

    2.2.1 Lattice Diagram Method

    Lattice Diagram is an excellent method of keeping track of the various

    reflections as they occurred. By applied reflection theory the voltage at the receiving

    end can be plotted. But the method is not suitable for actual system, because there are

    many transmission lines connect together. For study of transient in single line this

    method is rather suitable [20].

    (A)

    (B)

  • 7/27/2019 Chapter02 Transients

    13/26

    23

    2.2.2 Fourier Transform Method

    This method is applies in the frequency domain analysis and convert in the

    time domain in final state. The output results are more accurate than Lattice Diagram

    method. But the Fourier Transform is not convenient for complicated or network

    systems [21].

    2.2.3 Transient Network Analysis (TNA) Method

    This method is simulator device for power system or substation. The

    Transient Network Analysis can be used to study transient switching surge level that

    take place at the substation. It is suitable for specified model with all equipments are

    not change, because must re-arrange modeling which take the time and cost. The

    results may be used to determine and coordinate proper impulse insulation and

    switching surge strength required in substation apparatus [21].

    2.2.4 Electromagnetic Transient Program (EMTP) Method

    Generally in electromagnetic transient simulations, there are two main

    ways to represent transmission lines. The most familiar method is Pi sections model.

    The other method is a distributed transmission line, which is most suited for transient

    line response modeling using digital computer [22].

    Using transient studies in the Electromagnetic Transient Program is very popular

    in the world. This simulator not only can simulate the transient in power systems, but

    also simulate steady state solutions and Transient Analysis of Control Systems

    (TACS). If there is any change in equipment, it is very easy to modify the model and

    re-simulate as user requirement [20], [23].

    2.2.4.1 Equipment Modeling

    There are many types of equipment models in the PSCAD/EMTDC program library. This thesis used the equipment models for the 500 kV

    transmission line Nam Theun 2 Roi Et 2 from program library as shown in table 2.3.

  • 7/27/2019 Chapter02 Transients

    14/26

    24

    Table: 2.3 Equipments modeling of 500 kV transmission system [20], [23].

    List

    Transmission

    line / Equipment Modeling of equipment

    1 Transmission line Traveling wave parameter frequency dependent model

    2 Transformer Lumped linear elements, Type short circuit impedance

    3 Generator Non-linear elements, Type three phase (X)-matrix

    4 Surge Arrester Non-linear elements, Type metal oxide arrester

    5 Circuit Breaker Lumped linear elements for pre-insert resistor, Ordinary switches

    6 Shunt Reactor Lumped linear elements

    7 Load Lumped linear elements

    2.2.4.2 Transmission Line

    There are three basic transmission line modeling techniques in

    PSCAD/EMTDC: Pi section model, the Bergeron model, and the frequency

    dependent line models. The requirements for this research will determine which one

    of three models will be suitable [22].

    2.2.4.2.1 The Pi Section Model

    Equivalent Pi section is shown in Figure 2.8. There are

    two Pi line section components: normal Pi line model and coupled Pi line model. One

    Pi section is equal 15 km of transmission line length. If the line is longer than 15 km,

    then two or more Pi sections should be cascaded in series, a maximum of 10 Pi

    sections for a long line is adequate. This model is usually quite short line and it is use

    at power frequency, where R, L and C is resistance, inductance and capacitance of

    line per unit length [22-24].

    1[C]

    2

    1[ ]

    2C

    Figure 2.8 The transmission line model Pi-circuit [25].

  • 7/27/2019 Chapter02 Transients

    15/26

    25

    2.2.2.4.2 The Bergeron Model

    The Bergeron model is based on a distributed LC

    parameter traveling wave line model with lumped resistance. It should generally be

    chosen over a Pi model, lines over 15 km could be represented by Bergeron model.

    The model produces a constant surge impedance and is essentially a single frequency

    model, it is roughly equivalent to using an infinite number like of Pi Section except

    that resistance is lumped by inserting R/2 in the middle of line and R/4 at each end

    of the line. The Bergeron model can be used for any general fundamental frequency

    impedance studies, such as relay testing or matching load-flow result.

    A line model will be represented as shown in Figure 2.9 (A) and (B) with 0Z for

    the characteristic or surge impedance [] and for travel time of the line [s]. The

    travel time of the line and the characteristic impedance 0Z can be related to

    inductance and capacitance of the transmission line [22-24].

    1

    4

    R 1

    4

    R1

    2

    R

    (B)

    Figure 2.9 (A) Lossless line [6], (B) Equivalent impedance network [22].

    2.2.2.4.3. The Frequency Dependent Line Model

    The frequency dependent line model represents the

    frequency dependence of all parameters R, L and C. This model should be used for all

    k m

    ( )kV t ( )mV t 0

    Z 0Z

    ( )kI t

    ( )mI t

    ,k mi

    ,m ki mk

    (A)

  • 7/27/2019 Chapter02 Transients

    16/26

    26

    studies that require frequency other than the fundamental to be represented accurately

    such as transient overvoltage, harmonic analysis etc. There are two models: the

    frequency dependent phase model is the most accurate, as it presents the frequency

    dependence of internal transformation matrices, whereas the frequency dependent

    mode model assumes a constant transformation. The line is divided into two sections,

    each section of transmission line has characteristic impedance. The voltages and

    currents at one end of the line at the time ( t ) may be represented in terms of the

    voltage and current at the other end at the time ( t- ), and related in terms of sources

    ( )kb t and ( )mb t . The Bergeron model and frequency dependent model are basically

    distributed parameters traveling wave models. This model can be solved using the

    more advantage phase domain techniques. The thesis is used this model for

    representing equipment models for transmission line, because it is more accurate and

    suitable for analysis of switching and temporary overvoltage. The frequency

    dependent line model is shown in Figure 2.10 [6], [22-23].

    Figure 2.10 Traveling wave frequency dependent line model (Matrix) [6], [9].

    2.2.4.3 Transformer

    Transformer is device that transfers energy from one circuit to

    another by means of a common magnetic field. In all cases except autotransformers,

    there is no direct connection from one circuit to the other.

    Transformer model in Electromagnetic Transient Program is presented through

    one of two fundamental methods. Simulation of transformers requires an

    understanding of some of their basic properties involving both core and winding

    configuration. This is complicated by the fact that the core of the transformer is prone

  • 7/27/2019 Chapter02 Transients

    17/26

    27

    to saturation leading to the phenomena of the inrush current, remanence geomagnetic

    current effect and Ferro resonance. The two mutually couple winding is shown in

    Figure 2.11.

    Figure 2.11 Two mutually couple winding.

    Where:

    11L : Self inductance of winding 1

    12L : Mutual inductance between winding 1 and 2

    22L : Self inductance of winding 2

    The voltage across the first winding is 1Vand the voltage across the second

    winding is 2V . The following equation describes the voltage and current relationship

    for two coupled coil [22].

    1

    2

    V

    V

    =11

    12

    L

    L

    12

    22

    L

    L

    .1

    2

    Id

    Idt

    . (2.32)

    2.2.4.4 Generator

    In electricity generation, an electrical generator is a device that

    converts mechanical energy to electrical energy, generally using electromagnetic

    induction. The reverse conversion of electrical energy into mechanical energy is done

    by a motor, and motors and generators have many similarities. A generator forces

    electric charges to move through an external electrical circuit, but it does not create

    electricity or charge, which is presented already in the wire of its windings.

    Synchronous machines are simply represented as voltage sources. Switches arenot needed for the connection of these sources since they are connected to the network

  • 7/27/2019 Chapter02 Transients

    18/26

    28

    at all times. However, sources parameters ( StartT and StopT ) are employed to model the

    period during which the source is in effect. Therefore, the source functions are zero

    between 0 < t Stop

    T . The source functions are evaluated at discrete

    time step t t= , 2 t ,. only. Linear interpolation is assumed by the program to be

    in-between. The following option is adopted for the sinusoidal function

    representation:

    max 0( ) cos( ( ) )startv t V t T = + , (2.33)

    wheremaxV , 0 ( in degrees), startT ( in second ) must be supplied. The value 0startT < is

    used to get AC steady state solution. Before entering the transient solution, negative

    value ofstart

    T are set to zero and treated as zero in the equation 2.33 [26].

    2.2.4.5 Surge Arrester

    The arrester equipments used in the transmission line are Metal-

    Oxide and Zinc-Oxide. The resistance property of arrester equipment is non-linear, it

    is normal practice in the 500 kV transmission line between Nam Theun 2 and Roi Et 2

    to install surge arresters to protect transmission system equipments from the damage

    by lightning. A bank of surge arrester is connected to one end of a three phases

    distributed parameter transmission line. The non-linear current voltage characteristic

    of a metal oxide arrester ( MOA) is shown in equation 2.34.

    / .k k

    I V C

    = (sign of kV ) , k= 1,2,,m, (2.34)

    where m = 3 for three phase

    = is constant.

    C = difference voltage.

    These equations are solved simultaneously with the rest of the network, which is

    represented by the three phase Thevenin equivalent circuit

    [ ] [ ] [ ][ ]open THEV

    V V R i= . (2.35)

    In each time step. Since the equations are nonlinear, a solution can only be

    obtained iteratively. Newtons method is used to solve these equations for the voltage.

    The accuracy of the convergence is determined according to a predefined tolerance

    V . It is shown in Figure 2.12 [26].

  • 7/27/2019 Chapter02 Transients

    19/26

    29

    1k 2k 3k

    1m 2m 3m

    Figure 2.12 Equivalent circuit of surge arrester [6].

    2.2.4.6 Circuit Breaker

    In general, there are five basic switch types in electromagnetic

    transient program which are modeled as ideal switches. In this thesis the time

    controlled switch is used for modeling transmission line circuit breakers, as well as

    for fault representation. The switch is originally open, and close atclose

    T . It opens

    again afteropen

    T ( if maxopenT Tp ), where maxT is the maximum time for the transient

    simulation, either as soon as the absolute value of the switch current falls below a user

    defined current margin, or as soon as the current goes through zero. 0close

    T p signal to

    the program that switch is normally closed. The switching operation due to fault

    inception and/or fault clearing is modeled as shown in Figure 2.13 [26].

    R

    2

    switch R

    2

    switch

    Figure 2.13 Equivalent of circuit breaker.

    2.2.4.7 Shunt Reactor

    Shunt reactor has been employed on power to partially compensate

    the capacitive charging currents of long high voltage AC overhead lines or high

    voltage cable systems. The technical advantages they provide include:

    - Control of voltage rise at the ends of long high voltage lines at periods of high

    load or following load rejection.

    - Prevention of self-excitation of generators on leading power factor load.

  • 7/27/2019 Chapter02 Transients

    20/26

    30

    - Reduction of overvoltage due to line to ground fault.

    - Reduction of switching overvoltage due to the initial charging of lines.

    Shunt reactor compensation has a two fold effect when situated at the

    transmission line receiving end, both respects of which contribute to a reduction in the

    severity of the transient overvoltages. The reactor reduces the magnitude of the

    Ferranti rise long line by negating the effect of portion of the line shunt capacitance

    and presents a line termination other than an open circuit to any traveling waves from

    the transmission line sending end as shown in Figure 2.14 [27].

    Neutral reactors is compensated in additional to ensuring that the design of the

    main reactors will satisfactory for single phase recloser, it is necessary to eliminate

    the risk of an arc being maintained by capacitance coupling after this phase on with

    the fault occurred has been disconnected by circuit breaker operation. This can be

    achieved by connection a neutral reactor between the star point of the phase reactor

    and earth [20].

    , ( )k mi t t

    2LR

    t=

    ( )k

    V t ( )m

    V t

    , ( )k mi t

    Figure 2.14 Equivalent circuit shunt reactor using lumped elements [22].

    2.3 Control Transient Overvoltages in Power System

    The adverse effects of overvoltages on power networks can be reduced in two

    ways: by using protective devices such as surge arrester or by reducing their

    magnitudes wherever the surge originates. The latter way is commonly known

    overvoltage control. The techniques employed to control switching surges and

    temporary overvoltages are outlined briefly below.

  • 7/27/2019 Chapter02 Transients

    21/26

    31

    2.3.1 Pre-Insertion Resistor in Circuit Breaker Devices

    This is one of the most common methods for reducing energization

    overvoltages. It is effected by initially applying the voltage to the line, normally

    between one-third or one- half of a cycle, the pre-insertion is short circuit, allowing

    the full apply voltage to be applied to the line. The initial amplitude of the

    energization surge when the pre-insertion resistor of value R is used would be only

    0 0/( )Z R Z+ of reached in the absence of the resistor. It is shown in Figure 2.15,

    where 0Z is surge impedance of the line. When the resistor is short at the end of the

    pre-insertion period, another surge will develop. If R is too small, control of the first

    surge become ineffective; if it is too large, the second surge become dangerous. An

    optimal value of T would normally be a fraction of 0Z , and depend on transmission

    line length [16].

    Figure 2.15 Diagram of circuit breaker with pre-inserted resistor.

    ( R Pre-inserted resistor, 1K - Arcing contract and 2K - Main contract )

    It is effected by initially applying the apply voltage to the line through a resistor.

    By the end of the pre-insertion period, the magnitude of the energization surge is

    usually is much reduced by the effect of the system damping.

    2.3.2 Use of Shunt Reactor

    Shunt reactors are used on many high voltage transmission lines as a

    means of shunt compensation to improve the performance of the line, which would

    otherwise draw large capacitive currents from the supply. The additional advantage of

    shunt reactor is to decrease the transient surge magnitudes. This is accomplished

    mainly by reduction in temporary overvoltages, as will be seen in the next section.

    R 1

    K

    2K

  • 7/27/2019 Chapter02 Transients

    22/26

    32

    The shunt reactors can effectively control the temporary particularly the Ferranti

    voltage rise.

    2.3.3 Use of Surge Arrester

    Surge arresters are used to control transient overvoltages effect on power

    system, particularly the Zinc Oxide arrester, as shown in Figure 2.16.

    Figure 2.16 Typical voltage-current characteristic of surge arrester [24].

    Surge arresters are used of protective of power system equipment against surge

    ovevoltages because they offer low protection levels and permit the decreasing of

    insulation levels, which has a substantial effect on the cost of high voltage equipment.

    2.4 Statistical Switching Studies

    Circuit breaker closing in power systems can produce transient overvoltages

    whose maximum peaks depend on several factors such as network configuration on

    the source side of the circuit breaker and the amount of trapped charge in reclosing

    operations of transmission lines. Therefore, statistical switching studies are used to

    determine the maximum switching overvoltages along the transmission line [28].

    Current ( A)

    Voltage in (p.u) of rate voltage ( Crest value )

  • 7/27/2019 Chapter02 Transients

    23/26

    33

    Since all switching surges are products of circuit breaker actions, the random

    variation in switching surges is attributed primarily to the performance of these

    devises, as well as the network circumstances at the time of switching. Random

    angles of switching are mainly responsible for this variation. The following factors

    contribute to the randomness in switching angle:- The mechanical movement of circuit breaker contacts produces fluctuations

    about the aiming angle of interruption or closure.

    - Circuit closure may be prematurely effected following a breakdown betweenthe breakers contacts.

    - Arc interruption, whose timing is relevant to the production of recoverytransient voltages, involves a number of physical processes, many of which

    are inherently random.

    In Figure 2.17 shows the closing and the delay times of circuit breaker. When

    the operator closes the circuit breaker at time = t. Each phase of the circuit breaker

    does not close immediately since the delay time of mechanical equipment. Normally,

    each phase does not close at the same time. Therefore, in this work, it should be

    assumed that circuit breaker phases a, b and c are closed at t+ta, t+tb and t+tc

    respectively [16], [28], [29].

    Figure 2.17 Circuit breaker closing and delay times [6].

    The closing angles of the three breaker poles are the phase angles of the source

    side voltages at the instant of electrical closure of the contract. The angles have a

    strong influence on the line closing and reclosing overvoltages as they determine the

    initial conditions for the transients. For transients, when they are not controlled,

    undesired closing instants of the three poles many occur, but only within the limits of

  • 7/27/2019 Chapter02 Transients

    24/26

    34

    the circuit breakers pole span. The pole span is the time between the first and the last

    pole to close. When all the three breaker poles close simultaneously, the overvoltages

    are smaller than those of random closing.

    If pre-insertion resistors are used to mitigate switching overvoltages, the closing

    times of both main and auxiliary contacts are statistically determined. The closing

    times can be determined assuming that main contacts aim at the same closing time

    and both switches have a normal distribution. If statistical switches are used to normal

    present a circuit breaker with pre-insertion resistors, the closing time of the auxiliary

    contact is determined as follow [28]:

    ( ) ( )close slave close master off set T T T= + , (2.36)

    whereoffset

    T is now a constant value.

    Therefore, the transient overvoltages depend upon the instant on the voltage

    waveform at which the circuit breaker contacts close electrically. A statistical

    switching case study typically consists of 100 or more separate simulations, each

    using different set of circuit breaker closing times shown in Figure 2.18. The statistic

    can be used to process the peak overvoltages from all the simulations. Normally, the

    2% value on the cumulative frequency distribution curve is used to design

    overvoltages. This thesis selects a numerically 200 times closing poles of circuit

    breaker [6], [16], [28].

  • 7/27/2019 Chapter02 Transients

    25/26

    35

    -3

    T

    T

    3

    T

    +

    2

    T

    +

    T

    +-

    2

    T

    -

    T

    6

    Figure 2.18 Breaker pole random closing orders for the simulation of SOV during

    line energization and reclosing [16].

    In the transient overvoltage study, the breaker trip order is given at a precisetime during the simulation since the system separation time has a minor impact on the

    near steady state overvoltage. During line energizing or single phase reclosing tests,

    the breaker pole closing orders are generated as follows [16]:

    - The _

    T angle is first randomly selected recording to an even distribution

    between 0and 360of period of the fundamental frequency.

    - Afterwards, the closing time of the three breaker poles auxiliary contacts is

    selected according to normal distribution around point _T truncated at

    3 (3 2 )ms = . The operation simulates breaker three poles closing time

    dispersion.

    - Finally, the closing time of the breaker three main interrupting heads is

    delayed by 10 ms with respect to point _

    T with a standard deviation of

    2 ms normally distribute around this point (3 2 )ms= . The operation is to

    simulate the insertion time of the reclosing resistors. This procedure is

    illustrated in the following Figure2.18 [4], [16].

  • 7/27/2019 Chapter02 Transients

    26/26

    36