chapter02 transients
TRANSCRIPT
-
7/27/2019 Chapter02 Transients
1/26
Chapter 2
Theoretical principle concern
2.1 Transient Overvoltage in Power System2.1.1 Characteristic of Overvoltage in Power System
Electromagnetic transient overvoltage is voltage stresses which directly
effective to equipment in power system and especially to insulation. It is severe to the
system in case of stored energy in the line such as trapped charge in capacitor. The
overvoltage can be classified into two groups; the first group is external overvoltage
such as lightning. This causes from natural events. The second group is internal
overvoltage due to switching and temporary overvoltage as show in table: 2.1[4], [5].
Table: 2.1 Cases and shapes of overvoltage Standard voltage shapes and
standard withstand tests [16].
-
7/27/2019 Chapter02 Transients
2/26
12
2.1.2 Switching Overvoltage in Power System
Switching overvoltage is one of the internal overvoltages which generate
many changes in the operating conditions of network. There are a great variety of
events that would initiate a switching surge in a power network, whenever a switch in
an electric circuit is opened or closed; this is true for transmission as well as
distribution circuits. The interruption by switching operations of a circuit having
inductance and capacitance may result in transient oscillations that can cause
overvoltage on the systems. The switching operations of greatest relevance to
insulation design can be classified as following: [4], [5], [16]
Line energization Line re-energization Switching off of small capacitive currents Switching off of small inductive currents Fault initiation Fault clearing
As can be seen in table: 2.2, there are different ranges of switching overvoltage
classified by causes of overvoltages for EHV system.
Table: 2.2 Cases of switching overvoltage without protective device [6].
p.u on phase-to-ground base
Cause of overvoltages Value of maximum SOV (p u)
Closing ( line energization) 2.4 2.8
Re- Closing ( Re- energization ) 3.5 4.0
Single phase to ground 1.5 1.7
Double phase to ground 1.5 1.7
Fault clearing 1.4 1.8
-
7/27/2019 Chapter02 Transients
3/26
13
2.1.2.1 Line Energization Overvoltage in Power System
( )c
V tsin[ ( )]SV t T +
Figure 2.1 Diagram of line energization switching transient [16].
In the Figure 2.1 the inductance L represents the leakage inductance of
transformer, and the inductance of line. The resistance R includes all series resistance
of the line and transformer. The voltage across the capacitor C represents the voltage
at the open circuit end of the line which is included in the scope of study.
The circuit performance after switch on can be expressed as:
( ) 1( ) . ( ) ( )
S
di tV t R i t L i t dt
dt C= + + , (2.1)
The apply voltage ( )S
V t beyond the switching instant is:
( ) sin( )S S
V t V t T = + , (2.2)
The expression for voltage across the line capacitance is:
1( ) sin( ) sin( )t
C CV t V t T Ae t
= + + , (2.3)
Where:
2 2( . 1/ . )
SC
VV
C R L C =
+ , (2.4)
tan. 1/ .
t R
L C
=
, (2.5)
0
1
LC = , (2.6)
2 2
1 0 12 .f = + = , (2.7)
-
7/27/2019 Chapter02 Transients
4/26
14
2
R
L= , (2.8)
1 1 sin( )tancos( ) sin( )
T
T T
= +
. (2.9)
As we can see from above expression the voltage across at opened end ( )C
V t is
oscillation wave form with damped-decay. However the maximum value is the most
interesting value for design and safe operation [17].
2.1.2.2 Switching Overvoltage with Capacitive and Inductive Currents
1) Switching of capacitive currents: This includes capacitor banks,
unloaded overhead lines and cables. It involves interruption of small capacitive
currents at peak voltage. The recovery overvoltage may reach 1.5 p.u. across the
contacts of the circuit breaker. Half a cycle later, when the voltage of the feeding side
attains its maximum, a voltage of 2.5 p.u. is then established across the circuit breaker
contacts which may lead to restrike of the circuit breaker [28].
2) Switching of inductive current: When interrupting the small
inductive currents of unloaded transformers and shunt reactors, current shopping may
occur with the current forced to zero before natural current zero. The high di/dt
associated with current shopping results in high induced voltage in the inductive
circuit. This type of operation produces overvoltages of 2 to 3 p.u. in modern
transformer; however, with transformers loaded with shunt reactors, value up to 5 p.u.
may be reached which necessitates the use of surge arresters for protection [17].
2.1.2.3 Switching Overvoltage with Fault Initiation and Clearing
Initiation and closing of system faults: the most frequent fault on
power systems is the short circuit phase to earth which is often accompanied by anincrease of neutral potential. If the fault occurs at peak voltage, then up to 2.7 p.u
overvoltages can be generated. Reducing of ratio ( X0/X1 ), however, will
significantly limit the overvoltage: e.g. for a configuration having a ratio equal to 1,
no overvoltage has been observed. The single phase fault which causes an asymmetry
is therefore the most dangerous fault. The clearing of a fault by circuit breakers, in
particular a three phases fault, will also generate crest overvoltages of up to 3 p.u. as
shown in Figure 2.2 [17].
-
7/27/2019 Chapter02 Transients
5/26
15
CV C
CBL
cosm
SourceV V t =
Fault
Fault
CB
Figure 2.2 Equivalent circuit of transient recovery voltage when a circuit
breaker clears a fault [18].
The simplest circuit that can be chosen to illustrate this phenomenon is that
shown in Figure 2.2. It is assumed that load being fed through the circuit breaker is
suddenly isolated by the occurrence of a fault and that fault is a dead short circuit.
Where:
L is all the inductance limiting the current to the point of fault.
Cis the natural capacitance of the adjacent to the circuit breaker.
In the circuit of Figure 2.2 the current is assumed to be symmetrical and will be
completely reactive since it is limited entirely by inductance. This means that at the
instant of current zero, the circuit voltage will be at a maximum value, but the voltage
at the switch contacts, and therefore across the capacitor C, will be arc voltage. The
relative importance of the arc voltage varies.In this analysis, time will be measured from the instant of interruption when the
fault current has just come to zero. Sine the source voltage is a sinusoidally varying
quantity and is at its peak at the moment, it is expressed as cosm
V t . The circuit
equation is therefore
cosc m
dIL V V t
dt+ = , (2.10)
There are two unknowns, I and VC , so another relationship between them is
required. This is
-
7/27/2019 Chapter02 Transients
6/26
16
cdV
I Cdt
= , (2.11)
after the switch has cleared, the only path for current is into the capacitor. The
combination of these equations gives
2cos
2c c m
d V V V t
LC LCdt+ = , (2.12)
Let2
01/LC = , and transform Equation 2.12:
2 ' 2 2
0 0
2 2
( ) (0) (0) ( )c c c c m
ss v s sV V v s V
s
+ =
+,
or
'2
0 2 2 2 2 2 2 2 2
0 0 0
(0)( ) (0)
( )( )
cc m c
Vs sv t V V
s s s s
= + +
+ + + + (2.13)
If we neglect are voltage the second term on the right is zero. The third term is also
zero because, from Equation 2.11, '(0)
(0) 0c
IV
C= = ,
Therefore only the first term remains. Now
2 2 2 2 2 2 2 2 2 2
0 0 0
1( )
( )( )
s s s
s s s s =
+ + + +,
Therefore
2
0
2 2 2 2 2 2
0 0
( ) ( )c ms s
v s Vs s
=
+ +,
and
2
0
02 20
( ) (cos cos )c m
V t V t t
=
, (2.14)
Equation 2.13 is the voltage appearing across the switch contacts after current
zero. It is the classical transient recovery voltage described by Park and Skeats [18].
Almost invariably 0 >>, so that2 2 2
0 0/ ( ) 1 . Thus to a very close
approximation,
0( ) (cos cos )c mV t V t t = , (2.15)
Indeed, it often happens that over the period of interest (the time for switch the
-
7/27/2019 Chapter02 Transients
7/26
17
natural frequency oscillation persists), there is little change in the power frequency
term. In this case equation 2.14 can be further reduced to give
0( ) [1 cos ]c mV t V t = . (2.16)
This is very evident from Figure 2.3 which shown as oscillogram of the current
interruption period. In this case the transient recovery voltage oscillation (lower trace)
lasts for about 600 s . The decline of the current to zero can be seen in the upper
trace. It will be noted that transient recovery voltage begins with a small excursion of
the opposite polarity to the instantaneous system voltage. This indicates some current
chopping [18].
Figure 2.3 Characteristic of restriking voltage [18].
2.1.3 Temporary Overvoltage in Power System
Temporary overvoltage is characterized by amplitude and durations,
typically from a few cycles to a few seconds. These overvoltages differ from transient
switching overvoltages in that they last longer. They take the form of undamed or
slightly damped oscillation at a frequency equal or close to the power frequency. The
classification of temporary overvoltages as distinct from transient switchingovervoltages is due mainly to the fact that responses of the power network insulation
and surge arresters to their shapes are different. Some of the most important events
leading to the generation of temporary overvoltages are discussed briefly as
following: [4], [5], [17]
Ferranti effect ( Long line effect ) Load rejection
Transformer energization Ground faults
-
7/27/2019 Chapter02 Transients
8/26
18
2.1.3.1 Ferranti Effect Overvoltage in Power System
ES
XS R
X 0S
U
RU
( )xU
E
l
Figure 2.4 Equivalent of the Ferranti effect rise voltage at opened line [17].
From Figure 2.4 the Ferranti effect of an uncompensated transmission line is
given by
cosh sinhS R R C
U U l I Z l = + , (2.17)
sinh coshRS RC
UI l I lZ = + , (2.18)
No load in line 0R
I =
coshS
R
Ul
U= , (2.19)
where:
RU and
SU are the receiving end and the sending end voltages,
respectively; cZ is impedance of line and lis line length in km.
is the phase shift constant of the line per unit length. It is equal to the
imaginary part of 1/2( )YZ , where Z and Y are impedance and admittance
of the line per unit length.
Obviously for uncompensated transmission line the highest overvoltage will
appear at the receiving end.
For a losses line:
LC = , (2.20)
-
7/27/2019 Chapter02 Transients
9/26
19
where:
Land Care inductance and capacitance of the line per unit length.
has a value of about 6per 100 km at the normal power frequency.
When the impedance of sourceEbe consider and the shunt reactor was installed
at the receiving end of the line [17].
The voltage rise at the receiving end is:
cos . cos
cos( )
RU
E l
=
+ +, (2.21)
Where:
RX the reactance of shunt reactor,
SX is the transient reactance of
generator in series with the transformer reactance and lis line length in km.
tan SX
Z= , (2.22)
tanR
Z
X= . (2.23)
2.1.3.2 Load Rejection Overvoltage in Power System
E
X
CX V
Figure 2.5 Equivalent circuits during load rejection [17].
From Figure 2.5 when the transmission line or large inductive load that is fed
from power station is suddenly switched off, the generator will speed up and busbar
voltage will rise.
The amplitude of the overvoltage can be evaluated approximately by
C
C
XV E
X X=
. (2.24)
where:
-
7/27/2019 Chapter02 Transients
10/26
20
E is voltage behind the transient reactance, which is assumed to be
constant over the subtransient reactance of the generator in series with the
transformer reactance [17].
X is the transient reactance of generator in series with the transformer
reactance
CX is the equivalent capacitive input reactance of the system.
2.1.3.3 Inrush Transient by Switching on Transformer
Transformer energization creates transient inrush currents, when the
transformers core becomes over fluxed or saturation. Transformer inrush currents can
have a high magnitude containing a significant harmonic content. The harmonic rich
transformer inrush currents interact with harmonic resonances of power system.
The inrush is most severe when the transformer is switched on the instant the
voltage goes through zero with such polarity that flux increases in the direction of
residual flux is shown in Figure 2.6 [18].
Figure 2.6 Equivalent circuit of a transformer.
For condition above, we may write:
2 sin dd
v V t N s s dt dt
= = = , (2.25)
The value of the flux is then found by integration:
0
2sin (0)
t
sV tdtN
= + , (2.26)
-
7/27/2019 Chapter02 Transients
11/26
21
where 0(0) = is the residual flux, thus
0 02 (1 cos ) coss mV t tN
= + = + +
, (2.27)
Representing winding and core losses, the periodic component 0m + , is
obtained as a constant quantity. However, due to these losses, the aperiodic term
decays very slowly according to the large time constant of magnetizing circuit.
Then, at t = ( a period after switching) the instantaneous flux will be
max 02 m = + , (2.28)
The magnetic flux density under steady-state conditions is 1.3mB T . If
0 is assumed to 0.6 m , then the maximal flux density, which in a transformer
is directly proportional to the flux, will be
max (2 0.6)1.3 3.4B T T= + . (2.29)
The typical curve of an inrush current for a transformer switched at zero
instantaneous voltage is shown in Figure 2.7 [19].
Since a magnetic flux density is the ratio of magnetic flux to a given area with
passes through equation 2.28 can be recast of following:
max 0(2 )c mA B B = + , (2.30)
Bm and BO are the peak steady state and residual magnetic flux density
magnitudes, and Ac is sectional area of the transformer core. Equation 2.30 assumes
that the flux lines are perpendicular toAc.
Using Amperes Law, wherea
H dl iN= and a aB H= , we can compute the
inrush current magnitude as follow:
0(2 ),a c
inrush m Sat
a
H l A lI B B B
N NA= = + + (2.31)
where lis the mean length of the transformer leg and winding, Nis the number of the
turns in winding and is the flux linkages. It should be noted that the inrush current
magnitude estimate is the maximum theoretical value as shown in Figure 2.7.
-
7/27/2019 Chapter02 Transients
12/26
22
Figure 2.7 (A) Magnetizing curve, (B) Inrush current of transformer [18].
2.2. Determination of Transient Overvoltages
At present, computer is an important equipment used for analyzing the
overvoltage in power system because of its high accuracy, speed and convenient to
change the parameters. There are four main methods for analyzing the
electromagnetic transient overvoltage in the transmission line which are Lattice
Diagram, Fourier Transform, Transient Network Analysis (TNA) and
Electromagnetic Transient Program (EMTP). The detail of each method could be
explained as follows:
2.2.1 Lattice Diagram Method
Lattice Diagram is an excellent method of keeping track of the various
reflections as they occurred. By applied reflection theory the voltage at the receiving
end can be plotted. But the method is not suitable for actual system, because there are
many transmission lines connect together. For study of transient in single line this
method is rather suitable [20].
(A)
(B)
-
7/27/2019 Chapter02 Transients
13/26
23
2.2.2 Fourier Transform Method
This method is applies in the frequency domain analysis and convert in the
time domain in final state. The output results are more accurate than Lattice Diagram
method. But the Fourier Transform is not convenient for complicated or network
systems [21].
2.2.3 Transient Network Analysis (TNA) Method
This method is simulator device for power system or substation. The
Transient Network Analysis can be used to study transient switching surge level that
take place at the substation. It is suitable for specified model with all equipments are
not change, because must re-arrange modeling which take the time and cost. The
results may be used to determine and coordinate proper impulse insulation and
switching surge strength required in substation apparatus [21].
2.2.4 Electromagnetic Transient Program (EMTP) Method
Generally in electromagnetic transient simulations, there are two main
ways to represent transmission lines. The most familiar method is Pi sections model.
The other method is a distributed transmission line, which is most suited for transient
line response modeling using digital computer [22].
Using transient studies in the Electromagnetic Transient Program is very popular
in the world. This simulator not only can simulate the transient in power systems, but
also simulate steady state solutions and Transient Analysis of Control Systems
(TACS). If there is any change in equipment, it is very easy to modify the model and
re-simulate as user requirement [20], [23].
2.2.4.1 Equipment Modeling
There are many types of equipment models in the PSCAD/EMTDC program library. This thesis used the equipment models for the 500 kV
transmission line Nam Theun 2 Roi Et 2 from program library as shown in table 2.3.
-
7/27/2019 Chapter02 Transients
14/26
24
Table: 2.3 Equipments modeling of 500 kV transmission system [20], [23].
List
Transmission
line / Equipment Modeling of equipment
1 Transmission line Traveling wave parameter frequency dependent model
2 Transformer Lumped linear elements, Type short circuit impedance
3 Generator Non-linear elements, Type three phase (X)-matrix
4 Surge Arrester Non-linear elements, Type metal oxide arrester
5 Circuit Breaker Lumped linear elements for pre-insert resistor, Ordinary switches
6 Shunt Reactor Lumped linear elements
7 Load Lumped linear elements
2.2.4.2 Transmission Line
There are three basic transmission line modeling techniques in
PSCAD/EMTDC: Pi section model, the Bergeron model, and the frequency
dependent line models. The requirements for this research will determine which one
of three models will be suitable [22].
2.2.4.2.1 The Pi Section Model
Equivalent Pi section is shown in Figure 2.8. There are
two Pi line section components: normal Pi line model and coupled Pi line model. One
Pi section is equal 15 km of transmission line length. If the line is longer than 15 km,
then two or more Pi sections should be cascaded in series, a maximum of 10 Pi
sections for a long line is adequate. This model is usually quite short line and it is use
at power frequency, where R, L and C is resistance, inductance and capacitance of
line per unit length [22-24].
1[C]
2
1[ ]
2C
Figure 2.8 The transmission line model Pi-circuit [25].
-
7/27/2019 Chapter02 Transients
15/26
25
2.2.2.4.2 The Bergeron Model
The Bergeron model is based on a distributed LC
parameter traveling wave line model with lumped resistance. It should generally be
chosen over a Pi model, lines over 15 km could be represented by Bergeron model.
The model produces a constant surge impedance and is essentially a single frequency
model, it is roughly equivalent to using an infinite number like of Pi Section except
that resistance is lumped by inserting R/2 in the middle of line and R/4 at each end
of the line. The Bergeron model can be used for any general fundamental frequency
impedance studies, such as relay testing or matching load-flow result.
A line model will be represented as shown in Figure 2.9 (A) and (B) with 0Z for
the characteristic or surge impedance [] and for travel time of the line [s]. The
travel time of the line and the characteristic impedance 0Z can be related to
inductance and capacitance of the transmission line [22-24].
1
4
R 1
4
R1
2
R
(B)
Figure 2.9 (A) Lossless line [6], (B) Equivalent impedance network [22].
2.2.2.4.3. The Frequency Dependent Line Model
The frequency dependent line model represents the
frequency dependence of all parameters R, L and C. This model should be used for all
k m
( )kV t ( )mV t 0
Z 0Z
( )kI t
( )mI t
,k mi
,m ki mk
(A)
-
7/27/2019 Chapter02 Transients
16/26
26
studies that require frequency other than the fundamental to be represented accurately
such as transient overvoltage, harmonic analysis etc. There are two models: the
frequency dependent phase model is the most accurate, as it presents the frequency
dependence of internal transformation matrices, whereas the frequency dependent
mode model assumes a constant transformation. The line is divided into two sections,
each section of transmission line has characteristic impedance. The voltages and
currents at one end of the line at the time ( t ) may be represented in terms of the
voltage and current at the other end at the time ( t- ), and related in terms of sources
( )kb t and ( )mb t . The Bergeron model and frequency dependent model are basically
distributed parameters traveling wave models. This model can be solved using the
more advantage phase domain techniques. The thesis is used this model for
representing equipment models for transmission line, because it is more accurate and
suitable for analysis of switching and temporary overvoltage. The frequency
dependent line model is shown in Figure 2.10 [6], [22-23].
Figure 2.10 Traveling wave frequency dependent line model (Matrix) [6], [9].
2.2.4.3 Transformer
Transformer is device that transfers energy from one circuit to
another by means of a common magnetic field. In all cases except autotransformers,
there is no direct connection from one circuit to the other.
Transformer model in Electromagnetic Transient Program is presented through
one of two fundamental methods. Simulation of transformers requires an
understanding of some of their basic properties involving both core and winding
configuration. This is complicated by the fact that the core of the transformer is prone
-
7/27/2019 Chapter02 Transients
17/26
27
to saturation leading to the phenomena of the inrush current, remanence geomagnetic
current effect and Ferro resonance. The two mutually couple winding is shown in
Figure 2.11.
Figure 2.11 Two mutually couple winding.
Where:
11L : Self inductance of winding 1
12L : Mutual inductance between winding 1 and 2
22L : Self inductance of winding 2
The voltage across the first winding is 1Vand the voltage across the second
winding is 2V . The following equation describes the voltage and current relationship
for two coupled coil [22].
1
2
V
V
=11
12
L
L
12
22
L
L
.1
2
Id
Idt
. (2.32)
2.2.4.4 Generator
In electricity generation, an electrical generator is a device that
converts mechanical energy to electrical energy, generally using electromagnetic
induction. The reverse conversion of electrical energy into mechanical energy is done
by a motor, and motors and generators have many similarities. A generator forces
electric charges to move through an external electrical circuit, but it does not create
electricity or charge, which is presented already in the wire of its windings.
Synchronous machines are simply represented as voltage sources. Switches arenot needed for the connection of these sources since they are connected to the network
-
7/27/2019 Chapter02 Transients
18/26
28
at all times. However, sources parameters ( StartT and StopT ) are employed to model the
period during which the source is in effect. Therefore, the source functions are zero
between 0 < t Stop
T . The source functions are evaluated at discrete
time step t t= , 2 t ,. only. Linear interpolation is assumed by the program to be
in-between. The following option is adopted for the sinusoidal function
representation:
max 0( ) cos( ( ) )startv t V t T = + , (2.33)
wheremaxV , 0 ( in degrees), startT ( in second ) must be supplied. The value 0startT < is
used to get AC steady state solution. Before entering the transient solution, negative
value ofstart
T are set to zero and treated as zero in the equation 2.33 [26].
2.2.4.5 Surge Arrester
The arrester equipments used in the transmission line are Metal-
Oxide and Zinc-Oxide. The resistance property of arrester equipment is non-linear, it
is normal practice in the 500 kV transmission line between Nam Theun 2 and Roi Et 2
to install surge arresters to protect transmission system equipments from the damage
by lightning. A bank of surge arrester is connected to one end of a three phases
distributed parameter transmission line. The non-linear current voltage characteristic
of a metal oxide arrester ( MOA) is shown in equation 2.34.
/ .k k
I V C
= (sign of kV ) , k= 1,2,,m, (2.34)
where m = 3 for three phase
= is constant.
C = difference voltage.
These equations are solved simultaneously with the rest of the network, which is
represented by the three phase Thevenin equivalent circuit
[ ] [ ] [ ][ ]open THEV
V V R i= . (2.35)
In each time step. Since the equations are nonlinear, a solution can only be
obtained iteratively. Newtons method is used to solve these equations for the voltage.
The accuracy of the convergence is determined according to a predefined tolerance
V . It is shown in Figure 2.12 [26].
-
7/27/2019 Chapter02 Transients
19/26
29
1k 2k 3k
1m 2m 3m
Figure 2.12 Equivalent circuit of surge arrester [6].
2.2.4.6 Circuit Breaker
In general, there are five basic switch types in electromagnetic
transient program which are modeled as ideal switches. In this thesis the time
controlled switch is used for modeling transmission line circuit breakers, as well as
for fault representation. The switch is originally open, and close atclose
T . It opens
again afteropen
T ( if maxopenT Tp ), where maxT is the maximum time for the transient
simulation, either as soon as the absolute value of the switch current falls below a user
defined current margin, or as soon as the current goes through zero. 0close
T p signal to
the program that switch is normally closed. The switching operation due to fault
inception and/or fault clearing is modeled as shown in Figure 2.13 [26].
R
2
switch R
2
switch
Figure 2.13 Equivalent of circuit breaker.
2.2.4.7 Shunt Reactor
Shunt reactor has been employed on power to partially compensate
the capacitive charging currents of long high voltage AC overhead lines or high
voltage cable systems. The technical advantages they provide include:
- Control of voltage rise at the ends of long high voltage lines at periods of high
load or following load rejection.
- Prevention of self-excitation of generators on leading power factor load.
-
7/27/2019 Chapter02 Transients
20/26
30
- Reduction of overvoltage due to line to ground fault.
- Reduction of switching overvoltage due to the initial charging of lines.
Shunt reactor compensation has a two fold effect when situated at the
transmission line receiving end, both respects of which contribute to a reduction in the
severity of the transient overvoltages. The reactor reduces the magnitude of the
Ferranti rise long line by negating the effect of portion of the line shunt capacitance
and presents a line termination other than an open circuit to any traveling waves from
the transmission line sending end as shown in Figure 2.14 [27].
Neutral reactors is compensated in additional to ensuring that the design of the
main reactors will satisfactory for single phase recloser, it is necessary to eliminate
the risk of an arc being maintained by capacitance coupling after this phase on with
the fault occurred has been disconnected by circuit breaker operation. This can be
achieved by connection a neutral reactor between the star point of the phase reactor
and earth [20].
, ( )k mi t t
2LR
t=
( )k
V t ( )m
V t
, ( )k mi t
Figure 2.14 Equivalent circuit shunt reactor using lumped elements [22].
2.3 Control Transient Overvoltages in Power System
The adverse effects of overvoltages on power networks can be reduced in two
ways: by using protective devices such as surge arrester or by reducing their
magnitudes wherever the surge originates. The latter way is commonly known
overvoltage control. The techniques employed to control switching surges and
temporary overvoltages are outlined briefly below.
-
7/27/2019 Chapter02 Transients
21/26
31
2.3.1 Pre-Insertion Resistor in Circuit Breaker Devices
This is one of the most common methods for reducing energization
overvoltages. It is effected by initially applying the voltage to the line, normally
between one-third or one- half of a cycle, the pre-insertion is short circuit, allowing
the full apply voltage to be applied to the line. The initial amplitude of the
energization surge when the pre-insertion resistor of value R is used would be only
0 0/( )Z R Z+ of reached in the absence of the resistor. It is shown in Figure 2.15,
where 0Z is surge impedance of the line. When the resistor is short at the end of the
pre-insertion period, another surge will develop. If R is too small, control of the first
surge become ineffective; if it is too large, the second surge become dangerous. An
optimal value of T would normally be a fraction of 0Z , and depend on transmission
line length [16].
Figure 2.15 Diagram of circuit breaker with pre-inserted resistor.
( R Pre-inserted resistor, 1K - Arcing contract and 2K - Main contract )
It is effected by initially applying the apply voltage to the line through a resistor.
By the end of the pre-insertion period, the magnitude of the energization surge is
usually is much reduced by the effect of the system damping.
2.3.2 Use of Shunt Reactor
Shunt reactors are used on many high voltage transmission lines as a
means of shunt compensation to improve the performance of the line, which would
otherwise draw large capacitive currents from the supply. The additional advantage of
shunt reactor is to decrease the transient surge magnitudes. This is accomplished
mainly by reduction in temporary overvoltages, as will be seen in the next section.
R 1
K
2K
-
7/27/2019 Chapter02 Transients
22/26
32
The shunt reactors can effectively control the temporary particularly the Ferranti
voltage rise.
2.3.3 Use of Surge Arrester
Surge arresters are used to control transient overvoltages effect on power
system, particularly the Zinc Oxide arrester, as shown in Figure 2.16.
Figure 2.16 Typical voltage-current characteristic of surge arrester [24].
Surge arresters are used of protective of power system equipment against surge
ovevoltages because they offer low protection levels and permit the decreasing of
insulation levels, which has a substantial effect on the cost of high voltage equipment.
2.4 Statistical Switching Studies
Circuit breaker closing in power systems can produce transient overvoltages
whose maximum peaks depend on several factors such as network configuration on
the source side of the circuit breaker and the amount of trapped charge in reclosing
operations of transmission lines. Therefore, statistical switching studies are used to
determine the maximum switching overvoltages along the transmission line [28].
Current ( A)
Voltage in (p.u) of rate voltage ( Crest value )
-
7/27/2019 Chapter02 Transients
23/26
33
Since all switching surges are products of circuit breaker actions, the random
variation in switching surges is attributed primarily to the performance of these
devises, as well as the network circumstances at the time of switching. Random
angles of switching are mainly responsible for this variation. The following factors
contribute to the randomness in switching angle:- The mechanical movement of circuit breaker contacts produces fluctuations
about the aiming angle of interruption or closure.
- Circuit closure may be prematurely effected following a breakdown betweenthe breakers contacts.
- Arc interruption, whose timing is relevant to the production of recoverytransient voltages, involves a number of physical processes, many of which
are inherently random.
In Figure 2.17 shows the closing and the delay times of circuit breaker. When
the operator closes the circuit breaker at time = t. Each phase of the circuit breaker
does not close immediately since the delay time of mechanical equipment. Normally,
each phase does not close at the same time. Therefore, in this work, it should be
assumed that circuit breaker phases a, b and c are closed at t+ta, t+tb and t+tc
respectively [16], [28], [29].
Figure 2.17 Circuit breaker closing and delay times [6].
The closing angles of the three breaker poles are the phase angles of the source
side voltages at the instant of electrical closure of the contract. The angles have a
strong influence on the line closing and reclosing overvoltages as they determine the
initial conditions for the transients. For transients, when they are not controlled,
undesired closing instants of the three poles many occur, but only within the limits of
-
7/27/2019 Chapter02 Transients
24/26
34
the circuit breakers pole span. The pole span is the time between the first and the last
pole to close. When all the three breaker poles close simultaneously, the overvoltages
are smaller than those of random closing.
If pre-insertion resistors are used to mitigate switching overvoltages, the closing
times of both main and auxiliary contacts are statistically determined. The closing
times can be determined assuming that main contacts aim at the same closing time
and both switches have a normal distribution. If statistical switches are used to normal
present a circuit breaker with pre-insertion resistors, the closing time of the auxiliary
contact is determined as follow [28]:
( ) ( )close slave close master off set T T T= + , (2.36)
whereoffset
T is now a constant value.
Therefore, the transient overvoltages depend upon the instant on the voltage
waveform at which the circuit breaker contacts close electrically. A statistical
switching case study typically consists of 100 or more separate simulations, each
using different set of circuit breaker closing times shown in Figure 2.18. The statistic
can be used to process the peak overvoltages from all the simulations. Normally, the
2% value on the cumulative frequency distribution curve is used to design
overvoltages. This thesis selects a numerically 200 times closing poles of circuit
breaker [6], [16], [28].
-
7/27/2019 Chapter02 Transients
25/26
35
-3
T
T
3
T
+
2
T
+
T
+-
2
T
-
T
6
Figure 2.18 Breaker pole random closing orders for the simulation of SOV during
line energization and reclosing [16].
In the transient overvoltage study, the breaker trip order is given at a precisetime during the simulation since the system separation time has a minor impact on the
near steady state overvoltage. During line energizing or single phase reclosing tests,
the breaker pole closing orders are generated as follows [16]:
- The _
T angle is first randomly selected recording to an even distribution
between 0and 360of period of the fundamental frequency.
- Afterwards, the closing time of the three breaker poles auxiliary contacts is
selected according to normal distribution around point _T truncated at
3 (3 2 )ms = . The operation simulates breaker three poles closing time
dispersion.
- Finally, the closing time of the breaker three main interrupting heads is
delayed by 10 ms with respect to point _
T with a standard deviation of
2 ms normally distribute around this point (3 2 )ms= . The operation is to
simulate the insertion time of the reclosing resistors. This procedure is
illustrated in the following Figure2.18 [4], [16].
-
7/27/2019 Chapter02 Transients
26/26
36