characteristics of different pumps at variable...
TRANSCRIPT
-
CHARACTERISTICS OF DIFFERENT PUMPS AT VARIABLE HEADS AND
FLOW RATES
S:No HP KWImpeller
Type
Dia
mm
Conne-
ctionsModel M³ LPH
MW
C
Kg/C
m²
Amper
es
Motor
rpm
1 0.25 0.18 OPEN ø60 25 SMSCP -
2.53 3000 5 0.5 0.6 2880
2 0.5 0.37 OPEN ø90 38 SMSCP -
56.5 6500 4 0.4 0.55 2880
3 1 0.75 OPEN ø95 38 SMSCP -
108 8000 4 0.4 0.82 2880
4 1.5 1.1 OPEN ø104 38 SMSCP -
158.5 85000 6 0.6 1.5 2880
5 2 1.5 OPEN ø120 38 SMSCP -
2010.5 10500 10 1.1 1.6 2880
6 3 2.2 CLOSED ø155 51 SMSCP -
3013.5 13500 19 1.9 3 2880
7 53.7
/5CLOSED ø165
63/51
SMS
CP -
5015.25 15250 27 2.7 4.6 2880
-
0
5
10
15
20
25
30
0 5 10 15 20 25
Head
MW
C
Discharge m3/hr
0.5 HP
1 HP
2 HP
3 HP
CP-05
CP-10CP-20
CP-30
CP-05
CP-10CP-20
CP-30
PUMP CHARACTERISTIC CURVES
0
0.5
1
1.5
2
2.5
3
3.5
4
0 5 10 15 20 25
Curr
ent,
Am
ps
Discharge, m3/hr
CP-05
CP-10
CP-20
CP-30
-
TECHNICAL INFORMATION
Maximum Inlet Pressure 58 PSI
Temperature Range 0°– 130° F
MOC
Product contact components AISI 304
Seal Components - Carbon V/s TC, TC Vs TC
Gaskets O ring - EPDM, Viton,
Product Contact Surfaces finish- 32 Ra
Motor - 3 Phase, 50 Hz, 415 VAC, 2880 RPM
Recommended Preventive & seal maintenance
Regular visually inspect of mechanical seal for
any leakage.
Replace mechanical seal after 1 year Replace
Lubricate Before fitting the O-rings with Silicone
grease/food lubricant.
ELASTOMER INSPECTION
Inspect all Gaskets and O-rings while performing
Pump maintenance ,we recommend to replace
The gaskets / o rings.
Pump shaft, seal replacement.
MOTOR LUBRICATION
Use a standard grade ball bearing grease.
-
INSTALLATION
Prior to actually installing the pump, ensure that:
• The pump will be readily accessible for maintenance, inspection
and cleaning.
• Adequate ventilation is provided for motor cooling.
• The drive motor type is suitable for the environment where it is to
be operated. Pumps intended for
Use in hazardous environments e.g., explosive, corrosive, etc., must
use a motor and drive with the appropriate enclosure
characteristics. Failure to use an appropriate motor type may result
in serious damage and/or injury.
PIPING GUIDELINES
This section describes good piping practices to obtain maximum
efficiency and service life from your pump.
Maximum performance and trouble-free operation require adherence
to good piping practices.
• Ensuring proper piping support and alignment at both the suction
inlet and discharge outlet can help prevent serious damage to
the pump housing
• Avoid abrupt interruptions in the piping system
• Avoid throttling valves in the suction piping.
• Keep suction lines as short and direct as possible.
• Avoid the formation of air pockets in the piping
ELECTRICAL INSTALLATION
Have an electrician connect the motor using sound electrical
practices. Provide adequate protection. Pumps
fitted with mechanical seals must not run dry, not even momentarily.
Determine the direction of rotation by
watching the motor fan, which must turn clockwise.
-
PUMP OPERATIONS & START-UP INSTRUCTIONS
• Remove any foreign matter that may have entered the pump.
• Turn shaft by hand to make sure seals do not stick together
otherwise, if motor is bumped in wrong direction it may unwind the
seal spring.
• Do not use the pump to flush the system!
Check pump for proper rotation as indicated on the pump. Proper
motor direction is clockwise when looking at the fan end of the motor.
(NOTE: When checking the direction of rotation, the pump must be full
of liquid.)
• Never run the pump dry, even momentarily. Seal damage can result.
SHUT-DOWN INSTRUCTIONS
• Shut off the power supply to the pump.
• Close the shut-off valves in the suction and discharge piping.
• Drain and clean the pump.
• Protect the pump against dust, heat, moisture and impact damage.
INSTALLATION OF WATER FLUSH FOR DOUBLE MECHANICAL
SEAL
Set up the water flush for the double mechanical seal -Excessive flow
of water ,Through with 2-5 feet physical height of tubing. This ensures
that some water is always in the center seal and the seal never runs
dry. It is possible to inject steam through the center seal (within the
pressure requirements). We do not recommend using steam alone for
the cooling/lubricating of the seal. It is desirable to have the flush water
on the outlet side visible. This allows an easy check to see that the
flush water is on and also if the seal is functioning properly. In a
malfunctioning seal the flush water will disappear, become
discolored, or show an unusual increase in flow. If these conditions
exist, check the seal and replace if necessary.
-
INSTALLATION OF WATER CASCADE
The water cascade (if supplied) is piped through the hub of the
pump housing and into the stationary seal. Since there is no rear
seal, the flush water will exit through the rear of the seal area
TROUBLESHOOTING
Pumps are relatively maintenance free, however, in the event that
a problem does arise, If a motor problem arises
please contact your local motor repair representative.
POSSIBLE CAUSES OF TROUBLE
•Pump does not deliver liquid
•Not enough capacity delivered
•Not enough pressure developed
•Pump loses prime after starting
•Pump requires too much power
•Seal leaks
•Seal has short life
•Pump vibrates or is noisy
•Motor bearings have short life
•Pump overheats and seizes
•Pump leaks from cover
-
SUCTION PROBLEMS
• Pump not primed - Adjust piping so that pump is flooded, Install a
foot valve to keep liquid in the Pump
• Pump or suction pipe not completely filled with liquid - Adjust piping
so that suction pipe is filled with liquid
• Suction lift too high - Raise the level of the liquid, lower the level of
the pump.
• Insufficient difference between suction pressure and vapor
pressure (cavitations) - Use larger pipe on the inlet side of the
pump, raise
• The level of liquid above the pump center line, lower the
temperature of the liquid, eliminate fittings in suction line if
possible, check inlet pipe for obstructions
• Too much air or gas in liquid - Install air relief valve, turn pump
head so discharge is at 45° angle
• Air pocket in suction line- Adjust pipe to eliminate pocket
• Air leaks into suction line - Find and fix air leak
• Air leaks into pump through seal - Check seal for proper
installation, replace seal if defective
• Foot valve too small - Replace with larger foot valve
• Foot valve partially clogged - Clear obstruction from foot valve
• Seal flush water not on - Turn on water to seal flush
• Water seal pipe plugged - Clear obstruction from seal water pipe
• Seal water flush pressure too high - Adjust water flow to seal flush
to 1-2 at a maximum of 5 psi.
-
MECHANICAL PROBLEMS
14. Speed too low - Check electrical connections, consult motor
manufacturer
15. Speed too high - Check electrical connections, consult motor
16. Direction of rotation incorrect - On a three-phase motor, switch any
two of the three leads
17. Total head of system higher than design head of pump - Check for
restrictions in the pipe, use larger diameter pipe, use larger diameter
impeller
18. Total head of system lower than pump design head - Install
throttling valve in line, use smaller diameter pipe, use smaller diameter
impeller
19. Specific gravity of liquid greater than expected - Use larger
motor, check application
20. Viscosity of liquid greater than expected -. Use larger motor, use
larger diameter pipe, check application
21. Operation at very low capacity - Install throttling valve
22. Parallel operation of pumps unsuitable for such operation - Replace
parallel pumps with a single larger pump
23. Foreign matter in impeller - Remove pump cover and clear foreign
matter
24. Foundations not rigid - Provide firmer foundation for the pump
25. Shaft bent - Replace shaft
26. Impeller rubbing on pump housing - Re-establish gap of the
impeller, replace impeller if defective, make sure impeller nut is
tightened properly
27. Motor bearings worn - Replace motor bearings
28. Impeller damage - Replace impeller
29. Cover gasket defective permitting leakage - Replace cover gasket
30. Shaft or shaft collar worn or scored - Replace pump shaft and/or
collar
31. Seal improperly installed - Install seal correctly, replace seal if
defective
32. Type of seal incorrect for operating conditions - Replace seal with
correct type of seal, check with your local representative
33. Pump shaft running off center because of worn bearings or
misalignment - Check motor bearings and replace if defective
34. Impeller out of balance causing vibration - Balance the impeller
-
35. Motor front bearing not locked - Contact motor manufacturer for
locking shim or to replace motor with a motor with locked front bearing
36. Dirt or grit in sealing liquid, leading to scoring of shaft or seal surface
- Use clean source of water for seal flush
37. Lack of lubrication in motor bearing - Lubricate motor bearings
38. Improper installation of antifriction bearings (damage during
assembly, incorrect assembly of stacked bearings, use of unmatched
bearings as a pair, etc.)- Reinstall bearings correctly
39. Dirt in bearings - Clean bearings, replace if defective
40. Piping is obstructed - Remove obstruction in pipe, check for closed
valve .
-
PUMP INSPECTION cum Test Certificate
ITEM: SS 304 Grade 1 HP CENTRIFUGAL PUMPDESPATCH
DATE27/10/2012
DWG.NO.: FD-1HP-95-38 MODEL CP - 10
P.O.NO.: FBE/12/1740Manufactur
erGOWTHAMI PUMPS AND VALVES
CUSTOMER Food & Biotech Engineers(I)pvt.ltd Quantity 1 NO of 1
A PUMP B MECHANICAL SEAL
1
IMPEL
LER
TYPE
OPEN MATL.AISI
3041 MAKE:
2
IMPEL
LER
DIA
95 FINISH 2 SIZE: 22 MM
3
CONN
ECTIO
NS
Weldable WELDING
TIG
/CF
8
3 TYPE: CARBON V/S STERLITE
(A)
SUCTI
ON
38 mm HEAD
8
MW
C
(B)
DISCH
ARGE
38 mm DISCHARGE
800
0
LPH
4PUMP
S/No.CP10-124
C MOTOR
5MA
KELaxmi Hydraulics Pvt. Ltd INSUL. CL. F
RP
M2800
6 TYPEDeg.Of
Protection.A°C 50
RAT
ED
CUR
REN
T
1.61 AmpsRATIN
G(kW
/ HP)
0.75 KW/1 HP Frequency (HZ) 50
7
MOTO
R
EFFY.
Operating Volt 415+10%Dut
yS1
8
MOTO
R
S/NO.
1000203084 Connection Star IP 55
DB. TESTING MEDIA : WATER
S/NO CAPACITY HEAD
IN MWC
MAX
CURRENTIN LPH Cum/Hr
1 2500 2.5 9 0.6
2 4500 4.5 7 0.7
3 5500 5.5 6 0.8
4 8000 8.0 4 0.8
5 14500 14.5 2 1.1
NOTE: 1) PUMP HAS BEEN TESTED AT
AMBIENT TEMPERATURE.
3) DURING RUNNING TRAIL, LEAKAGE WAS
NOT FOUND.2) TOLERANCES : Q= ±8% ; H=± 6%. 4) IMPELLER IS DYNAMICALLY BALANCED.
-
PUMP INSPECTION cum Test Certificate
ITEM: SS304 Grade 0.5 HP CENTRIFUGAL PUMP DESPATCH DATE 27/10/2012
DWG.NO.: FD-0.5 HP-94-38 MODEL CP - 0.5
P.O.NO.: PO.NO: FBE/12/1740 Manufacturer
GOWTHAMI
PUMPS AND
VALVES
CUSTOMER M/s. Food & Biotech Engineers (I)Pvt.Ltd. Quantity 1 NO of 1
A PUMP BMECHANICAL
SEAL
1 IMPELLER TYPE OPEN MATL. AISI 304 1 MAKE:
2 IMPELLER DIA 90 FINISH 2 SIZE: 22 MM
3 CONNECTIONS Weldable WELDIN
GTIG/CF8 3
TYPE: CARBON
V/S STERLITE
(A) SUCTION 38 mm HEAD6.5
MWC
(B) DISCHARGE 38 mm DISCHAR
GE
6500
lph
4 PUMP S/No. CP 05 - 54
C MOTOR
5 MAKE Laxmi Hydraulics Pvt. LtdINSUL.
CL.F RPM 2800
6 TYPE
Deg.Of
Protecti
on.
A°C 50RATED
CURREN
T
0.92
Amps
RATING(kW / HP) 0.37 KW/0.5 HPFrequen
cy (HZ)50
7 MOTOR EFFY. 70%Operati
ng Volt
415+10
%Duty S1
8 MOTOR S/NO.Connect
ionStar IP 55
DTESTING: A. MEASURING METHOD : WITH ELECTROMAGNETIC FLOWMETER
B. TESTING MEDIA : WATER
S/NO CAPACITY HEAD MAX
IN LPH Cum/Hr IN MWCCURREN
T
2 2500 2.5 6 0.40
3 4500 4.5 5 0.45
4 6500 6.5 4 0.55
5 10300 10.3 2 0.65
6 12000 12.0 1 0.66
NOTE: 1) PUMP HAS BEEN TESTED AT AMBIENT TEMPERATURE.
2) TOLERANCES : Q= ±8% ; H=± 6%.
3) DURING RUNNING TRAIL, LEAKAGE WAS NOT FOUND.
4) IMPELLER IS DYNAMICALLY BALANCED.
-
CENTRIFUGAL PUMP SAFETY INSTRUCTIONS & WARRANTY CARD
Caution:
•Be sure that your Pipe lines, storage tanks and process equipments are cleaned.
(without any minute dust particles)
•Take out the Pump only from packing as and when it is required to be installed.
•Position the pump horizontally by adjusting the ball feet’s.
•Ensure that there is no packing material at inlet and the outlet.
•Avoid the weight of piping on the pump casing by providing pipe support suitably.
•Check the pump for any visible transport damages.
•Tighten the clamping ring well before starting the pump.
•Pump electrical connection have to be done by authorized personnel.
•Check for the correct flow direction. Ensure that impeller rotates in clock wise direction
when seen from fan side of pump motor
•The pump must not run in dry.
• Run the pump at rated throughput.
•All centrifugal pumps have a required head (pressure) at the suction side of the pump
•For hot liquid transfer pump be ensure that normal temperature water should be
continuously flown in to cooling chamber and at the out let, water can be recycled after
obtaining normal temperature.
•Double mechanical seal will be damaged if water circulation is not provided hence it
won’t cover under warranty.
-
The Centrifugal Pump is covered by a limited warranty. The customer is required to perform routine maintenance (Cleaning) as required
Warranty:
Gowthami pumps and valves warranty the products manufactured and sold by it to be free from defects in material and workmanship for normal use and service from the date of delivery to original purchaser for a period of 1 year from the date of shipment. This limited warranty does not cover, and no warranty is provided, for parts that by their nature are required to be replaced periodically as a function of use of the normal operation of the system. (Mechanical Seal, O Rings)These items include, without limitation: Mishandling of Centrifugal Pump (improper handling damages Pump), misuse, negligence, accident, and alteration of the Pump or Operated by untrained professional or repaired by an unauthorized individual is not covered by the warranty.
Nominal Pressure:
Maximum product pressure........58 PSI maximum (4 Bars)Test pressure ……. 70 PSI (5 Bars)
Temperature range: 0° C to + 130° C
GOWTHAMI PUMPS AND VALVES
Warranty Card