In This Chapter... Display, Indicators and Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2 Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3 Counter Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5 1-Stage Counting Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5 1-Stage Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9 1-Stage Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . .2-13 1-Stage Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-18 1-Stage Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-23 2-Stage Counting UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-28 2-Stage Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-33 2-Stage Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . .2-38 2-Stage Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-45 2-Stage Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-52 Batch Counting UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-59 Batch Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-64 Batch Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . . .2-69 Batch Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-75 Batch Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-81 Total Counting UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-87 Total Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-92 Total Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . . . .2-97 Total Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-103 Total Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-109 Dual Counting Addition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-115 Dual Counting Subtraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-120 COUNTER CHAPTER CHAPTER CHAPTER 2 2 2 www.automationdirect.com 2-1 Digital Counter / Timer / Tach User Manual, 1st Ed.

Upload: hanhi

Post on 23-Apr-2019

223 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

In This Chapter...

Display, Indicators and Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2

Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3

Counter Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-51-Stage Counting Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-51-Stage Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-91-Stage Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . .2-131-Stage Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-181-Stage Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-232-Stage Counting UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-282-Stage Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-332-Stage Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . .2-382-Stage Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-452-Stage Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-52Batch Counting UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-59Batch Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-64Batch Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . . .2-69Batch Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-75Batch Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-81Total Counting UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-87Total Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-92Total Counting UP/Command Counting Down (UdA) . . . . . . . . . . . . . . . . . . . . . .2-97Total Counting UP/Counting Down (UdB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-103Total Counting Quadrature (UdC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-109Dual Counting Addition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-115Dual Counting Subtraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-120

COUNTERCHAPTERCHAPTERCHAPTER

222222

w w w . a u t o m a t i o n d i r e c t . c o m 2-1Digital Counter / Timer / Tach User Manual, 1st Ed.

Page 2: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-2

Reset 2 indicatorReset 1 indicator

Key protect 2 indicator

Output 2 indicator

Key protect 1 indicator

Output 1 indicator

Special function indicator

Lock keyReset key

Mode and number shift key

PV(Present Value) display

SV(Set Value) display

Counter function indicator

Up/Down key

CTT AUTOMATIONDIRECT .com

Display, Indicators and Keys

LCD Display and IndicatorsRST 1/2 Light on when reset signal is detected BATCH “Batch Counting Mode” in Counter

K/P 1/2 Light on when key-protected mode is enabled SET 1 2 SV1, SV2 display

OUT 1/2 Light on when output is executingCNT Light on in Counter function

TOTAL “Total Counting Mode” in Counter function

Key Operation, . Increase and decrease SV or change paramter settings

´ Left move 1 digit of the selected digit. The indicator of the selected digit will flash.

Ä Save the set parameters or switch among functions.

LOCKPrevent settings from being changed. Key-protected mode still works after the power is switched off. Press LOCK to enter key-protected mode. In non-key-protectedstatus, press LOCK to enter Lock 1, press LOCK again to enter Lock 2. Press Ä and ´ at the same time to disable key-protected mode. LoC1 (Lock 1) dis-ables the functions of all keys. LoC2 (Lock 2) allows users to change SV and functions of RESET remain. LOCK only functions in non-key-protected status.

RESET Clear and reset PV.

Modes: Operation Mode and Configuration Mode

OperationWhen the power is on, the timer/counter/tachometer is in the operation mode. Press ,. to change SV, or ´ to select digit to change. The indicator of theselected digit will flash. After the change is made, press Ä to save the setting. If SV or paramters are not changed, press Ä once to switch between SET1 andSET2.

Configuration Press Ä in operation mode for more than 3 seconds to enter configuration mode. Press Ä once to switch among parameters. To return to operation mode, pressÄ for more than 3 seconds.

Page 3: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-3w w w . a u t o m a t i o n d i r e c t . c o m

Getting Started with Counters

Step 1: Determine Required Counter Function

Counter Functions1-Stage Counting (StA6E 1)

A single count setting value SV is available in 1-Stage Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily or will be maintained ON depending on the Output Mode selected.

2-Stage Counting (StA6E 2)

In 2-Stage Counting, count setting value SV1 controls Output 1 and count setting value SV2 controls Output 2.Outputs will turn ON momentarily or will be maintained ON depending on the output mode selected.

Batch Counting (bAtCH)

In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily or will be maintainedON depending on the output mode selected. Count setting value BATCH SV controls Output 1which will be main-tained ON.

Total Counting (totAL)

A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily or will be maintained ON depending on the Output Mode selected.

Dual Counting (dUAL)

A single count setting value SV is available in Dual Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily or will be maintained ON depending on the Output Mode selected.

Step 2: Determine Required Counter Input Mode

Counter Input Modes:Counting Up (UP)*

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will increment the countpresent value PV by 1. Turning ON the input signal at CP2, will prohibit the input signal at CP1 from incrementingthe PV.

With the input signal ON at input CP1, each trailing edge of the input signal at CP2 will increment the count presentvalue PV by 1. Turning OFF the input signal at CP1, will prohibit the input signal at CP2 from incrementing thePV.

Counting Down (down)*

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will decrement the countpresent value PV by 1. Turning ON the input signal at CP2, will prohibit the input signal at CP1 from decrementingthe PV.

With the input signal ON at input CP1, each trailing edge of the input signal at CP2 will decrement the countpresent value PV by 1. Turning OFF the input signal at CP1, will prohibit the input signal at CP2 from decrementingthe PV.

Counting Up / Command Counting Down (Ud A)*

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will increment the countpresent value PV by 1.

With the input signal ON at input CP2, each leading edge of the input signal at CP1 will decrement the countpresent value PV by 1.

Counting Up / Counting Down (Ud b)*

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.

Page 4: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-4

Quadrature (Ud C)*

When the quadrature input signal at CP1 changes before the input signal at CP2, the trailing edge of CP2 will incre-ment the count present value PV by 1.

When the quadrature input signal at CP2 changes before the input signal at CP1, the leading edge of CP2 will decre-ment the count present value PV by 1.

Addition (Add)**

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Each leading edge of the input signal at CP2 will increment the count present value PV by 1.

Subtraction (SUb)**

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.

*Available only with counter functions 1-stage, 2-stage, batch, total

**Available only with counter function dual

Step 3: Determine the Counter Output Mode by Visiting the Page Numbers Shown for Your Desired Counter Function and Input Mode

Counter Output Modes:Counter Function Counter Input Mode Page Number

1-Stage

Counting Up (UP) 2-5

Counting Down (DOWN) 2-9

Counting UP/Command Counting Down (UdA) 2-13

Counting UP/Counting Down (UdB) 2-18

Counting Quadrature (UdC) 2-23

2-Stage

Counting Up (UP) 2-28

Counting Down (DOWN) 2-33

Counting UP/Command Counting Down (UdA) 2-38

Counting UP/Counting Down (UdB) 2-45

Counting Quadrature (UdC) 2-52

Batch

Counting Up (UP) 2-59

Counting Down (DOWN) 2-64

Counting UP/Command Counting Down (UdA) 2-69

Counting UP/Counting Down (UdB) 2-75

Counting Quadrature (UdC) 2-81

Total

Counting Up (UP) 2-87

Counting Down (DOWN) 2-92

Counting UP/Command Counting Down (UdA) 2-97

Counting UP/Counting Down (UdB) 2-103

Counting Quadrature (UdC) 2-109

DualAddition (Add) 2-115

Subtraction (SUB) 2-120

Click on the above thumbnail or go to https://www.automationdirect.com/VID-RL-0004 for a short Counter demo video.

Click on the above thumbnail or go to https://www.automationdirect.com/VID-RL-0003 for a Counter Set-up video.

Page 5: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-5w w w . a u t o m a t i o n d i r e c t . c o m

1-Stage Counting (StA6E 1)

A single count setting value SV is available in 1-Stage Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter Functions1-Stage Counting (StA6E 1)

Counting Up (UP)

Counting Up (UP)With the input signal OFF at input CP2, each leading edge of theinput signal at CP1 will increment the count present value PV by 1.Turning ON the input signal at CP2, will prohibit the input signal atCP1 from incrementing the PV.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill continue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Mode N (n)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

ProhibitA A

01

23

45

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting up

ProhibitA A

01

23

4

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

With the input signal ON at input CP1, each trailing edge of theinput signal at CP2 will increment the count present value PV by 1.Turning OFF the input signal at CP1, will prohibit the input signal atCP2 from incrementing the PV.

999999RESET

SV

OUT2

OUT1

PV

Stage 1Input Mode UPOutput Mode F

0

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UPOutput Mode N

0

Page 6: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-6

Mode C (C)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2) and thecount PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn bothoutputs OFF, reset the count PV to 0 and prohibit an input signalfrom incrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode R (r)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2).

The count PV is prohibited from incrementing until the end of theoutput pulse time (tout2) when the outputs turn OFF and thecount PV is reset automatically to 0. The leading edge of a “reset”input signal at RST1 will turn OFF both outputs, reset the countPV to 0 and prohibit an input signal from incrementing the countPV.

The trailing edge of the “reset” signal at RST1 enables counting tobegin. The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode K (k)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will continue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode P (P)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV display is prohibited from incrementing until the end of theoutput pulse time, when both outputs turn OFF and the count PVis reset automatically to 0 and any input signals that occurred duringthe output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing the count PV.

The trailing edge of the “reset” signal at RST1 enables counting tobegin. The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

T T T

Stage 1Input Mode UPOutput Mode C

TTT

0

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UPOutput Mode R

T T

0

RESET

999999

SV

PV

OUT2

OUT1

T

T T

T

Stage 1Input Mode UPOutput Mode K

0

RESET

999999

SV

PV

OUT2

OUT1

TT

Stage 1Input Mode UPOutput Mode P

TT

0

Page 7: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-7w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will continue to increment with each input signal until the endof the output pulse time, when the outputs turn OFF and the countPV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode A (A)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RESET

999999

SV

PV

OUT2

OUT1

TT

TT

Stage 1Input Mode UPOutput Mode Q

0

RESET

999999

SV

PV

OUT2

OUT1

T T

T T

Stage 1Input Mode UPOutput Mode A

0

DIP Switch Set Up of the CTT Parameters:

Page 8: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-8

Keypad set up of the parameters for 1-Stage Counting:

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

–FunC Cont taCh –mixtime

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down,counting up/command counting down,counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

or or or or or

or

or

or

or

or or or or

or or or

oror or or or

or or

or or

or or or

or

or or

or or

or or

Ä

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 9: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-9w w w . a u t o m a t i o n d i r e c t . c o m

1-Stage Counting (StA6E 1)

A single count setting value SV is available in 1-Stage Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter Functions1-Stage Counting (StA6E 1)

Counting Down (down)

Counting Down (down)

With the input signal OFF at input CP2, each leading edge of theinput signal at CP1 will decrement the count present value PV by 1.Turning ON the input signal at CP2, will prohibit the input signal atCP1 from decrementing the PV.

Input Mode:

Mode F (F)

When the count present value PV counts down to 0 bothoutputs 1 and 2 will turn ON. The count PV will continue todecrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count setting valueSV, and prohibit an input signal from decrementing the countPV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Mode N (n)When the count present value PV counts down to 0 bothoutputs 1 and 2 will turn ON. The count PV will remain at 0regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count setting valueSV, and prohibit an input signal from decrementing the countPV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

AProhibit

A

nn-1

n-2n-3

n-4n-5

HL

HL

CP1

CP2

0

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting down

ProhibitAA

n

n-2n-1

n-4n-3

HLCP1

CP2

Present Value

0

HL

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

With the input signal ON at input CP1, each trailing edge of theinput signal at CP2 will decrement the count present value PV by 1.Turning OFF the input signal at CP1, will prohibit the input signal atCP2 from decrementing the PV.

999999

RESET

SV

OUT2

OUT1

PV

Stage 1Input Mode DOWN

Output Mode F

0

Stage 1Input Mode DOWN

Output Mode N

RESET

999999

SV

PV

OUT2

OUT1

0

Page 10: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-10

Mode C (C)

When the count present value PV counts down to 0 both outputs 1and 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the count PV will reset automaticallyto the count setting value SV.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count SV and prohibit aninput signal from decrementing the count PV. The trailing edge ofthe “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode R (r)

When the count present value PV counts down to 0 both outputs 1and 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV is prohibited from decre-menting until the end of the output pulse time (tout2) when theoutputs turn OFF and the count PV is reset automatically to thecount setting value SV.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count SV and prohibit aninput signal from decrementing the count PV. The trailing edge ofthe “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode K (k)

When the count present value PV counts down to 0 both outputs 1and 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2). The count PV will continue todecrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count setting value SV andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode P (P)

When the count present value PV counts down to 0 both outputs 1and 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2). The count PV display is prohibitedfrom decrementing until the end of the output pulse time whenboth outputs turn OFF and the count PV is reset automatically tothe count setting value SV and any input signals that occurredduring the output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count SV and prohibit aninput signal from decrementing the count PV. The trailing edge ofthe “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TTT

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode DOWN

Output Mode C

TTT

0

T T

Stage 1Input Mode DOWN

Output Mode R

RESET

999999

SV

PV

OUT2

OUT1

T T

0

T T

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode DOWN

Output Mode K

T T

0

TT

Stage 1Input Mode DOWN

Output Mode P

RESET

999999

SV

PV

OUT2

OUT1

TT

0

Page 11: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-11w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts down to 0 both outputs 1and 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV will continue to decre-ment with each input signal until the end of the output pulse timewhen the outputs turn OFF and the count PV is reset automaticallyto the count setting value SV.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count SV and prohibit aninput signal from decrementing the count PV. The trailing edge ofthe “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode A (A)

When the count present value PV counts down to 0 both outputs 1and 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2). The count PV will remain at 0regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count setting value SV andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

TT

RESET

999999

SV

PV

OUT2

OUT1

TT

Stage 1Input Mode DOWN

Output Mode Q

0

T T

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode DOWN

Output Mode A

T T

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 12: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-12

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down,counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

or

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 1-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 13: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-13w w w . a u t o m a t i o n d i r e c t . c o m

1-Stage Counting (StA6E 1)

A single count setting value SV is available in 1-Stage Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter Functions1-Stage Counting (StA6E 1)

Counting Up / Command Counting Down (UdA)

Counting Up / Command Counting Down (Ud A)

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will increment thecount present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Mode N (n)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

With the input signal ON at input CP2, each leading edge of the input signal at CP1 will decrement thecount present value PV by 1.

999999RESET

SV

OUT2

OUT1

PV

Stage 1Input Mode UdAOutput Mode F

0

Stage 1Input Mode UdAOutput Mode N

RESET

999999

SV

PV

OUT2

OUT1

0

Counting up/command counting down

Page 14: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-14

Mode C (C)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2) and the count PV willreset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn bothoutputs OFF, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode R (r)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2). The count PV is prohibitedfrom incrementing or decrementing until the end of the output pulsetime (tout2) when the outputs turn OFF and the count PV is resetautomatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode K (k)

When the count present value PV counts up or counts down to thecount setting value SV, both outputs 1 and 2 will turn ON momen-tarily for the time set in the output pulse width parameter (tout2).The count PV will continue to increment or decrement with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TT

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdAOutput Mode C

TT

0

T

T T

T

Stage 1Input Mode UdAOutput Mode R

RESET

999999

SV

PV

OUT2

OUT1

0

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdAOutput Mode K

TT

T T

T

T

0

T T

T

Stage 1Input Mode UdAOutput Mode P

RESET

999999

SV

PV

OUT2

OUT1

T

0

Mode P (P)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2). The count PV display isprohibited from incrementing or decrementing until the end of theoutput pulse time when both outputs turn OFF and the count PV isreset automatically to 0 and any input signals that occurred during theoutput pulse time.

The leading edge of a “reset” signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Page 15: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-15w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will continue to increment or decrement with each input signaluntil the end of the output pulse time when the outputs turn OFFand the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing or decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode A (A)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing or decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UdAOutput Mode Q

0

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UdAOutput Mode A

0

Mode S (S) and Mode T (t)

When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turn ON.When the count PV counts down to the count SV, both outputs 1 and 2 will turn OFF. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, andprohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RESET999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdA

Output Mode S and T

0

Page 16: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-16

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV both outputs 1 and2 will turn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, andprohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdAOutput Mode D

T

T

T

T

T

T

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 17: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-17w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 1-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 18: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-18

1-Stage Counting (StA6E 1)A single count setting value SV is available in 1-Stage Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter Functions1-Stage Counting (StA6E 1)

Counting Up / Counting Down (Udb)

Counting Up / Counting Down (Ud b)

Each leading edge of the input signal at CP1 will increment the count present value (PV) by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Mode N (n)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Each leading edge of the input signal at CP2 will decrement the count present value (PV) by 1.

999999RESET

SV

OUT2

OUT1

PV

Stage 1Input Mode UdBOutput Mode F

0

Stage 1Input Mode UdBOutput Mode N

RESET

999999

SV

PV

OUT2

OUT1

0

Counting up/down

Page 19: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-19w w w . a u t o m a t i o n d i r e c t . c o m

Mode C (C)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2) and the count PV willreset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn bothoutputs OFF, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode R (r)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2). The count PV is prohibitedfrom incrementing or decrementing until the end of the output pulsetime (tout2) when the outputs turn OFF and the count PV is resetautomatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode K (k)

When the count present value PV counts up or counts down to thecount setting value SV, both outputs 1 and 2 will turn ON momen-tarily for the time set in the output pulse width parameter (tout2).The count PV will continue to increment or decrement with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TT

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdBOutput Mode C

TT

0

T

T T

T

Stage 1Input Mode UdBOutput Mode R

RESET

999999

SV

PV

OUT2

OUT1

0

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdBOutput Mode K

TT

T T

T

T

0

T T

T

Stage 1Input Mode UdBOutput Mode P

RESET

999999

SV

PV

OUT2

OUT1

T

0

Mode P (P)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2). The count PV display isprohibited from incrementing or decrementing until the end of theoutput pulse time when both outputs turn OFF and the count PV isreset automatically to 0 and any input signals that occurred during theoutput pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Page 20: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-20

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will continue to increment or decrement with each input signaluntil the end of the output pulse time when the outputs turn OFFand the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing or decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode A (A)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing or decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UdBOutput Mode Q

0

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UdBOutput Mode A

0

Mode S (S) and Mode T (t)

When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turn ON.When the count PV counts down to the count SV, both outputs 1 and 2 will turn OFF. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, andprohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RESET999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdB

Output Mode S & T

0

Page 21: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-21w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV, both outputs 1 and2 will turn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, andprohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdBOutput Mode D

T

T

T

T

T

T

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 22: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-22

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 1-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 23: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-23w w w . a u t o m a t i o n d i r e c t . c o m

1-Stage Counting (StA6E 1)

A single count setting value SV is available in 1-Stage Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter Functions1-Stage Counting (StA6E 1)

Quadrature (UdC)

Quadrature (Ud C)

When the quadrature input signal at CP1 changes before the input signal at CP2, the trailing edge of CP2will increment the count present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Mode N (n)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON. The count PVwill remain at the count SV regardless of additional inputsignals.

The leading edge of “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0, and prohibit an inputsignal from incrementing or decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8

When the quadrature input signal at CP2 changes before the input signal at CP1, the leading edge of CP2will decrement the count present value PV by 1.

999999RESET

SV

OUT2

OUT1

PV

Stage 1Input Mode UdCOutput Mode F

0

Stage 1Input Mode UdCOutput Mode N

RESET

999999

SV

PV

OUT2

OUT1

0

Quadrature input

B B B B

0

1 12 2

3

HLCP1

CP2

PresentValue

0Note: has to be larger than width of 1/2 min. input signal. B

HL

0

Page 24: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-24

Mode C (C)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2) and the count PV willreset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn bothoutputs OFF, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode R (r)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2). The count PV is prohibitedfrom incrementing or decrementing until the end of the output pulsetime (tout2) when the outputs turn OFF and the count PV is resetautomatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode K (k)

When the count present value PV counts up or counts down to thecount setting value SV, both outputs 1 and 2 will turn ON momen-tarily for the time set in the output pulse width parameter (tout2).The count PV will continue to increment or decrement with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TT

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdCOutput Mode C

TT

0

T

T T

T

Stage 1Input Mode UdCOutput Mode R

RESET

999999

SV

PV

OUT2

OUT1

0

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdCOutput Mode K

TT

T T

T

T

0

T T

T

Stage 1Input Mode UdCOutput Mode P

RESET

999999

SV

PV

OUT2

OUT1

T

0

Mode P (P)

When the count present value PV counts up to the count setting valueSV, both outputs 1 and 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2). The count PV display isprohibited from incrementing or decrementing until the end of theoutput pulse time when both outputs turn OFF and the count PV isreset automatically to 0 and any input signals that occurred during theoutput pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Page 25: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-25w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will continue to increment or decrement with each input signaluntil the end of the output pulse time when the outputs turn OFFand the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing or decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

Mode A (A)

When the count present value PV counts up to the count settingvalue SV, both outputs 1 and 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). The countPV will remain at the count SV regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to 0 and prohibit an input signalfrom incrementing or decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UdCOutput Mode Q

0

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

Stage 1Input Mode UdCOutput Mode A

0

Mode S (S) and Mode T (t)

When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turn ON.When the count PV counts down to the count SV, both outputs 1 and 2 will turn OFF. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, andprohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RESET999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdC

Output Mode S & T

0

Page 26: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-26

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV, both outputs 1 and2 will turn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, andprohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

Stage 1Input Mode UdCOutput Mode D

T

T

T

T

T

T

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 27: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-27w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 1-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 28: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-28

2-Stage Counting (StA6E 2)

In 2-Stage Counting, count setting value SV1 controls Output 1 and count setting value SV2 controls Output 2.Output 1 will turn ON momentarily for the time set in the output pulse width parameter (tout1) or will be main-tained ON (tout1 set to 0.00). Output 2 will turn ON momentarily for the time set in the output pulse width param-eter (tout2) or will be maintained ON depending on the output mode selected.

CTT Counter Functions2-Stage Counting (StA6E 2)

Counting Up (UP)

Counting Up (UP)

With the input signal OFF at input CP2, each leading edge ofthe input signal at CP1 will increment the count present valuePV by 1. Turning ON the input signal at CP2, will prohibitthe input signal at CP1 from incrementing the PV.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON. The count PV will continueto increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP1, each trailing edge ofthe input signal at CP2 will increment the count present valuePV by 1. Turning OFF the input signal at CP1, will prohibitthe input signal at CP2 from incrementing the PV.

999999

RESET

SV2

SV1

OUT2

OUT1

PV

T1 T1

Stage 2Input Mode UPOutput Mode F

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

0

ProhibitA A

01

23

45

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting up

ProhibitA A

01

23

4

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

Page 29: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-29w w w . a u t o m a t i o n d i r e c t . c o m

Mode N (n)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON. The count PV will remainat the count SV2 regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1 T1

Stage 2Input Mode UPOutput Mode N

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

0

Mode C (C)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2) and the count PVwill reset automatically to 0. If Output 1 is ON when Output 2turns OFF, Output 1 will also turn OFF.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV2

PV

OUT2

OUT1

SV1

T1 T1 T1

T2 T2 T2

Stage 2Input Mode UPOutput Mode C

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode R (r)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2). The count PV isprohibited from incrementing until the end of the output pulsetime (tout2) when both outputs turn OFF and the count PVis reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1 T1

T2 T2

Stage 2Input Mode UPOutput Mode R

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 30: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-30

Mode K (k)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2). If Output 1 isON when Output 2 turns OFF, Output 1 will also turn OFF.The count PV will continue to increment with each inputsignal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV1

SV2

PV

OUT2

OUT1

T1 T1

T2 T2

Stage 2Input Mode UPOutput Mode K

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode P (P)When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2). The count PVdisplay is prohibited from incrementing until the end of theoutput pulse time (tout2) when both outputs turn OFF andthe count PV is reset automatically to 0 and any input signalsthat occurred during the output pulse time. The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1T1

T2T2

Stage 2Input Mode UPOutput Mode P

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 31: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-31w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2). The count PVwill continue to increment with each input signal until the endof the output pulse time (tout2) when both outputs turn OFFand the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1T1

T2T2

Stage 2Input Mode UPOutput Mode Q

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode A (A)

When the count present value PV counts up to the count settingvalue SV1, Output 1 will turn ON momentarily for the time setin the output pulse width parameter (tout1) or will be main-tained ON if the output pulse width parameter (tout1) is setto 0.00. When the count PV counts up to the count settingvalue SV2, Output 2 will turn ON momentarily for the time setin the output pulse width parameter (tout2). The count PVwill remain at the count SV2 regardless of additional inputsignals.

The leading edge of a “reset” signal at RST1 will turn OFF bothoutputs, reset the count PV to 0 and prohibit an input signalfrom incrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV1

SV2

PV

OUT2

OUT1

T1 T1

T2 T2

Stage 2Input Mode UPOutput Mode A

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 32: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-32

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for 2-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 33: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-33w w w . a u t o m a t i o n d i r e c t . c o m

2-Stage Counting (StA6E 2)

In 2-Stage Counting, count setting value SV1 controls Output 1 and count setting value SV2 controls Output 2.Output 1 will turn ON momentarily for the time set in the output pulse width parameter (tout1) or will be main-tained ON (tout1 set to 0.00). Output 2 will turn ON momentarily for the time set in the output pulse width param-eter (tout2) or will be maintained ON depending on the output mode selected.

CTT Counter Functions2-Stage Counting (StA6E 2)

Counting Down (down)

Counting Down (down)

With the input signal OFF at input CP2, each leading edge ofthe input signal at CP1 will decrement the count present valuePV by 1. Turning ON the input signal at CP2, will prohibitthe input signal at CP1 from decrementing the PV.

Input Mode:

Mode F (F)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON. The count PV will continue to decrement witheach input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count SV2, andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP1, each trailing edge ofthe input signal at CP2 will decrement the count present valuePV by 1. Turning OFF the input signal at CP1, will prohibitthe input signal at CP2 from decrementing the PV.

T1 T1

999999

RESET

SV2

SV1

OUT2

OUT1

Stage 2Input Mode DOWN

Output Mode FNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

PV0

AProhibit

A

nn-1

n-2n-3

n-4n-5

HL

HL

CP1

CP2

0

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting down

ProhibitAA

n

n-2n-1

n-4n-3

HLCP1

CP2

Present Value

0

HL

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

Page 34: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-34

Mode N (n)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON. The count PV will remain at 0 regardless of addi-tional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count SV2, andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode DOWN

Output Mode NNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

0

Mode C (C)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the count PV will reset automat-ically to the count SV2. If Output 1 is ON when Output 2turns OFF, Output 1 will also turn OFF.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count SV2 andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1T1

RESET

999999

SV2

PV

OUT2

OUT1

SV1

T2 T2 T2

Stage 2Input Mode DOWN

Output Mode CNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode R (r)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV is prohibited fromdecrementing until the end of the output pulse time (tout2)when both outputs turn OFF and the count PV is reset auto-matically to the count SV2.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count SV2 andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1

T2T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode DOWN

Output Mode RNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 35: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-35w w w . a u t o m a t i o n d i r e c t . c o m

Mode K (k)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). If Output 1 is ON when Output 2turns OFF, Output 1 will also turn OFF. The count PV willcontinue to decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count SV2 andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1

T2 T2

Stage 2Input Mode DOWN

Output Mode KNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

RESET

999999

SV1

SV2

PV

OUT2

OUT1

0

Mode P (P)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV display is prohibitedfrom decrementing until the end of the output pulse time(tout2) when both outputs turn OFF and the count PV is resetautomatically to the count SV2 and any input signals thatoccurred during the output pulse time.

The leading edge of a “reset” signal at RST1 will turn OFF bothoutputs, reset the count PV to the count SV2 and prohibit aninput signal from decrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1

T2T2

T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode DOWN

Output Mode PNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 36: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-36

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Mode Q (q)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV will continue todecrement with each input signal until the end of the outputpulse time (tout2) when both outputs turn OFF and the countPV is reset automatically to the count SV2.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to the count SV2 andprohibit an input signal from decrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

T2T2

Stage 2Input Mode DOWN

Output Mode QNote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode A (A)

When the count present value PV counts down to the countsetting value SV1, Output 1 will turn ON momentarily for thetime set in the output pulse width parameter (tout1) or will bemaintained ON if the output pulse width parameter (tout1) isset to 0.00. When the count PV counts down to 0, Output 2will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV will remain at 0regardless of additional input signals.

The leading edge of “reset” input signal at RST1 will turn OFFboth outputs, reset the count PV to the count SV2 and prohibitan input signal from decrementing the count PV. The trailingedge of the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1

T2 T2

RESET

999999

SV1

SV2

PV

OUT2

OUT1

Stage 2Input Mode DOWN

Output Mode ANote: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 37: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-37w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or or

or or

or or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for 2-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 38: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-38

Mode F (F)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Stage 2Input Mode UdAOutput Mode F

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

T1 T1 T1 T1T1T1

999999

RESET

SV2

SV1

OUT2

OUT1

PV0

2-Stage Counting (StA6E 2)

In 2-Stage Counting, count setting value SV1 controls Output 1 and count setting value SV2 controls Output 2.Output 1 will turn ON momentarily for the time set in the output pulse width parameter (tout1) or will be main-tained ON (tout1 set to 0.00). Output 2 will turn ON momentarily for the time set in the output pulse width param-eter (tout2) or will be maintained ON depending on the output mode selected.

CTT Counter Functions2-Stage Counting (StA6E 2)

Counting Up / Command Counting Down (UdA)

Counting Up / Command Counting Down (Ud A)

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will increment thecount present value PV by 1.

Input Mode:

With the input signal ON at input CP2, each leading edge of the input signal at CP1 will decrement thecount present value PV by 1.

Counting up/command counting down

Page 39: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-39w w w . a u t o m a t i o n d i r e c t . c o m

Mode N (n)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON. The count PVwill remain at the count SV2 regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8

T1 T1T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdAOutput Mode N

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

0

Mode C (C)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to 0. If Output 1 is ONwhen Output 2 turns OFF, Output 1 will also turn OFF.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1 T1T1 T1 T1

RESET

999999

SV2

PV

OUT2

OUT1

SV1

T2 T2

Stage 2Input Mode UdAOutput Mode C

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode R (r)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV is prohibited from incrementing or decrementinguntil the end of the output pulse time (tout2) when bothoutputs turn OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1T1 T1 T1 T1

T2 T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdAOutput Mode R

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 40: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-40

Mode K (k)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup or counts down to the count SV2, Output 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). If Output 1 is ON when Output 2 turns OFF,Output 1 will also turn OFF. The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1 T1 T1 T1

T2 T2 T2

T1

Stage 2Input Mode UdAOutput Mode K

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

RESET

999999

SV1

SV2

PV

OUT2

OUT1

0

Mode P (P)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV display is prohibited from incrementing or decre-menting until the end of the output pulse time (tout2) whenboth outputs turn OFF and the count PV is reset automaticallyto 0 and any input signals that occurred during the output pulsetime.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1 T1T1T1 T1

T2T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdAOutput Mode P

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 41: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-41w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV counts upto the count SV2, Output 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). Thecount PV will continue to increment or decrement with eachinput signal until the end of the output pulse time (tout2)when both outputs turn OFF and the count PV is reset auto-matically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Stage 2Input Mode UdAOutput Mode Q

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

T1T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1T1T1

T2T2

0

Mode A (A)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will remain at the count SV2 regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.

The trailing edge of the “reset” signal at RST1 enables countingto begin. The "reset" signal minimum pulse width is set by resetpulse width parameter ( rtSr ) or DIP Switch 8.

Stage 2Input Mode UdAOutput Mode A

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

T1 T1T1 T1

T2 T2

RESET

999999

SV1

SV2

PV

OUT2

OUT1

0

Mode S (S)When the count present value PV counts up to the count setting value SV1 Output 1 will turn ON. When the countPV counts down to the count SV1 Output 1 will turn OFF. When the count PV counts up to the count setting valueSV2 Output 2 will turn ON. When the count PV counts down to the count SV2 Output 2 will turn OFF. The countPV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV.

The trailing edge of the “reset” signal at RST1 enables counting to begin. The "reset" signal minimum pulse width isset by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 42: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-42

RESET999999

SV2SV1

PV

OUT2

OUT1

Stage 2Input Mode UdAOutput Mode S

0

Mode T(t)

When the count present value PV is less than count setting value SV1, Output 1 will be ON and will turn OFF whenthe count PV counts up to the count SV1. When the count PV counts down to the count SV1 Output 1 will turn ON.When the count PV counts up to the count SV2 Output 2 will turn ON. When the count PV counts down to thecount SV2 Output 2 will turn OFF. The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV.

The trailing edge of the “reset” signal at RST1 enables counting to begin. The "reset" signal minimum pulse width isset by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Stage 2Input Mode UdAOutput Mode T

RESET

999999

SV2SV1

PV

OUT2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV1 Output 1 will turn ONmomentarily for the time set in the output pulse width parameter (tout1). When the count PV counts up or countsdown to the count SV2 Output 2 will turn ON momentarily for the time set in the output pulse width parameter(tout2). The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 43: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-43w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RESET

999999

SV1

SV2

PV

OUT2

OUT1

T1 T1 T1 T1 T1 T1 T1 T1 T1 T1

T2 T2 T2

Stage 2Input Mode UdAOutput Mode D

Note: T1 momentary ON time set in outputpulse parameter (tout1), T2 = Momentary ON time set in output pulseparameter (tout2).

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 44: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-44

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 2-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 45: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-45w w w . a u t o m a t i o n d i r e c t . c o m

CTT Counter Functions2-Stage Counting (StA6E 2)

Counting Up / Counting Down (Udb)

Mode F (F)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Stage 2Input Mode UdBOutput Mode F

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

T1 T1 T1 T1T1T1

999999

RESET

SV2

SV1

OUT2

OUT1

PV0

2-Stage Counting (StA6E 2)

In 2-Stage Counting, count setting value SV1 controls Output 1 and count setting value SV2 controls Output 2.Output 1 will turn ON momentarily for the time set in the output pulse width parameter (tout1) or will be main-tained ON (tout1 set to 0.00). Output 2 will turn ON momentarily for the time set in the output pulse width param-eter (tout2) or will be maintained ON depending on the output mode selected.

Counting Up / Counting Down (Ud b)

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Input Mode:

Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.

Counting up/down

Page 46: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-46

Mode N (n)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON. The count PVwill remain at the count SV2 regardless of additional inputsignals.

The leading edge of a “reset” input signal signal at RST1 willturn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the countPV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdBOutput Mode N

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

0

Mode C (C)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to 0. If Output 1 is ONwhen Output 2 turns OFF, Output 1 will also turn OFF.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1 T1T1 T1 T1

RESET

999999

SV2

PV

OUT2

OUT1

SV1

T2 T2

Stage 2Input Mode UdBOutput Mode C

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode R (r)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV is prohibited from incrementing or decrementinguntil the end of the output pulse time (tout2) when bothoutputs turn OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1T1 T1 T1 T1

T2 T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdBOutput Mode R

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 47: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-47w w w . a u t o m a t i o n d i r e c t . c o m

Mode K (k)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup or counts down to the count SV2, Output 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). If Output 1 is ON when Output 2 turns OFF,Output 1 will also turn OFF. The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1 T1 T1 T1

T2 T2 T2

T1

Stage 2Input Mode UdBOutput Mode K

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

RESET

999999

SV1

SV2

PV

OUT2

OUT1

0

Mode P (P)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV display is prohibited from incrementing or decre-menting until the end of the output pulse time (tout2) whenboth outputs turn OFF and the count PV is reset automaticallyto 0 and any input signals that occurred during the output pulsetime.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1 T1T1T1 T1

T2T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdBOutput Mode P

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 48: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-48

Mode Q (q)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will continue to increment or decrement with eachinput signal until the end of the output pulse time (tout2)when both outputs turn OFF and the count PV is reset auto-matically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1T1T1

T2T2

Stage 2Input Mode UdBOutput Mode Q

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode A (A)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will remain at the count SV2 regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8

T1 T1T1 T1

T2 T2

RESET

999999

SV1

SV2

PV

OUT2

OUT1

Stage 2Input Mode UdBOutput Mode A

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode S (S)When the count present value PV counts up to the count setting value SV1 Output 1 will turn ON. When the countPV counts down to or below the count SV1 Output 1 will turn OFF. When the count PV counts up to the count SV2Output 2 will turn ON. When the count PV counts down to the count SV2 Output 2 will turn OFF. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 49: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-49w w w . a u t o m a t i o n d i r e c t . c o m

RESET999999

SV2SV1

PV

OUT2

OUT1

Stage 2Input Mode UdBOutput Mode S

0

Mode T(t)

When the count present value PV is less than the count setting value SV1, Output 1 will be ON and will turn OFFwhen the count PV counts up to the count SV1. When the count PV counts down to the count SV1 Output 1 turnON. . When the count PV counts up to the count SV2 Output 2 will turn ON. When the count PV counts down tothe count SV2 Output 2 will turn OFF. The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Stage 2Input Mode UdBOutput Mode T

RESET

999999

SV2SV1

PV

OUT2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV1 Output 1 will turn ONmomentarily for the time set in the output pulse width parameter (tout1). When the count present value PV countsup or counts down to the count SV2 Output 2 will turn ON momentarily for the time set in the output pulse widthparameter (tout2). The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 50: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-50

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RESET

999999

SV1

SV2

PV

OUT2

OUT1

T1 T1 T1 T1 T1 T1 T1 T1 T1 T1

T2 T2 T2

Stage 2Input Mode UdBOutput Mode D

Note: T1 momentary ON time set in outputpulse parameter (tout1),T2 = Momentary ON time set in output pulseparameter (tout2).

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 51: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-51w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 2-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 52: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-52

2-Stage Counting (StA6E 2)

In 2-Stage Counting, count setting value SV1 controls Output 1 and count setting value SV2 controls Output 2.Output 1 will turn ON momentarily for the time set in the output pulse width parameter (tout1) or will be main-tained ON (tout1 set to 0.00). Output 2 will turn ON momentarily for the time set in the output pulse widthparameter (tout2) or will be maintained ON depending on the output mode selected

CTT Counter Functions2-Stage Counting (StA6E 2)

Quadrature (UdC)

Quadrature (Ud C)

When the quadrature input signal at CP1 leads the input signal at CP2, the trailing edge of CP2 will incre-ment the count present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

When the quadrature input signal at CP2 leads the input signal at CP1, the leading edge of CP2 will decre-ment the count present value PV by 1.

Quadrature input

B B B B

0

1 12 2

3

HLCP1

CP2

PresentValue

0Note: has to be larger than width of 1/2 min. input signal. B

HL

0

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

T1 T1 T1 T1T1T1

999999

RESET

SV2

SV1

OUT2

OUT1

Stage 2Input Mode UdCOutput Mode F

PV0

Page 53: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-53w w w . a u t o m a t i o n d i r e c t . c o m

Mode N (n)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON. The count PVwill remain at the count SV2 regardless of additional inputsignals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdCOutput Mode N

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.

0

Mode C (C)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to 0. If Output 1 is ONwhen Output 2 turns OFF, Output 1 will also turn OFF.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1 T1T1 T1 T1

RESET

999999

SV2

PV

OUT2

OUT1

SV1

T2 T2

Stage 2Input Mode UdCOutput Mode C

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode R (r)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV counts upto the count SV2, Output 2 will turn ON momentarily for thetime set in the output pulse width parameter (tout2). Thecount PV is prohibited from incrementing or decrementinguntil the end of the output pulse time (tout2) when bothoutputs turn OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1T1 T1 T1 T1

T2 T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdCOutput Mode R

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 54: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-54

Mode K (k)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup or counts down to the count SV2, Output 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). If Output 1 is ON when Output 2 turns OFF,Output 1 will also turn OFF. The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1 T1 T1 T1

T2 T2 T2

T1

Stage 2Input Mode UdCOutput Mode K

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

RESET

999999

SV1

SV2

PV

OUT2

OUT1

0

Mode P (P)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV display is prohibited from incrementing or decre-menting until the end of the output pulse time (tout2) whenboth outputs turn OFF and the count PV is reset automaticallyto 0 and any input signals that occurred during the output pulsetime.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1 T1 T1T1T1 T1

T2T2

RESET

999999

SV2

SV1PV

OUT2

OUT1

Stage 2Input Mode UdCOutput Mode P

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Page 55: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-55w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will continue to increment or decrement with eachinput signal until the end of the output pulse time (tout2)when both outputs turn OFF and the count PV is reset auto-matically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T1T1 T1

RESET

999999

SV2

SV1PV

OUT2

OUT1

T1T1T1

T2T2

Stage 2Input Mode UdCOutput Mode Q

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

0

Mode A (A)

When the count present value PV counts up or counts down tothe count setting value SV1, Output 1 will turn ON momen-tarily for the time set in the output pulse width parameter(tout1) or will be maintained ON if the output pulse widthparameter (tout1) is set to 0.00. When the count PV countsup to the count SV2, Output 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will remain at the count SV2 regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Stage 2Input Mode UdCOutput Mode A

Note: T1 momentary ON time set in outputpulse parameter (tout1), setting tout1=0.00results in output 1 maintained ON.T2 = Momentary ON time set in output pulseparameter (tout2).

T1 T1T1 T1

T2 T2

RESET

999999

SV1

SV2

PV

OUT2

OUT1

0

Mode S (S)When the count present value PV counts up to the count setting value SV1 Output 1 will turn ON. When the countPV counts down to or below the count SV1 Output 1 will turn OFF. When the count PV counts up to the count SV2Output 2 will turn ON. When the count PV counts down to the count SV2 Output 2 will turn OFF. The count PVwill continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 56: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-56

RESET999999

SV2SV1

PV

OUT2

OUT1

Stage 2Input Mode UdCOutput Mode S

0

Mode T(t)

When the count present value PV is less than count setting value SV1, Output 1 will be ON and will turn OFF whenthe count PV counts up to the count SV1. When the count PV counts down to the count SV1 Output 1 turn ON. .When the count PV counts up to the count SV2 Output 2 will turn ON. When the count PV counts down to thecount SV2 Output 2 will turn OFF. The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Stage 2Input Mode UdCOutput Mode T

RESET

999999

SV2SV1

PV

OUT2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV1 Output 1 will turn ONmomentarily for the time set in the output pulse width parameter (tout1). When the count present value PV countsup or counts down to the count SV2 Output 2 will turn ON momentarily for the time set in the output pulse widthparameter (tout2). The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 57: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-57w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RESET

999999

SV1

SV2

PV

OUT2

OUT1

T1 T1 T1 T1 T1 T1 T1 T1 T1 T1

T2 T2 T2

Stage 2Input Mode UdCOutput Mode D

Note: T1 momentary ON time set in outputpulse parameter (tout1), T2 = Momentary ON time set in output pulseparameter (tout2).

0

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Page 58: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-58

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or or

or or

or or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for 2-Stage Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet perminute etc. See Tachometer Examples in Chapter 6

Page 59: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-59w w w . a u t o m a t i o n d i r e c t . c o m

Batch Counting (bAtCH)

In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily for the time set inthe output pulse width parameter (tout2) or will be maintained ON depending on the output mode selected. Countsetting value BATCH SV controls Output 1which will be maintained ON.

CTT Counter FunctionsBatch Counting (batCH)

Counting Up (Up)

Counting Up (UP)

With the input signal OFF at input CP2, each leading edge of theinput signal at CP1 will increment the count present value PV by1. Turning ON the input signal at CP2, will prohibit the inputsignal at CP1 from incrementing the PV.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV, Output 2 will turn ON and the batch count presentvalue BATCH PV will increment by one. The count PV willcontinue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF Output 2, reset the count PV to 0, and prohibit an inputsignal from incrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1will turn ON. The leading edge of a “reset” input signal at RST2will turn OFF Output 1, reset the BATCH PV to 0, andprohibit an input signal from incrementing the BATCH PV.The trailing edge of the “reset” signal at RST2 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP1, each trailing edge of theinput signal at CP2 will increment the count present value PV by1. Turning OFF the input signal at CP1, will prohibit the inputsignal at CP2 from incrementing the PV.

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

BATCHInput Mode UPOutput Mode F

RST2RESET

BATCH PV

OUT1

BATCH SV=2

0

ProhibitA A

01

23

45

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting up

ProhibitA A

01

23

4

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

Page 60: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-60

Mode N (n)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON and the batch count present valueBATCH PV will increment by one. The count PV will remain at thecount SV regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UPOutput Mode N

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode C (C)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2), the count PV will reset automaticallyto 0, and the batch count present value BATCH PV will increment byone.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

RST1RESET999999

COUNT SV

COUNT PV

RST2RESET

OUT2

T T T

BATCHInput Mode UPOutput Mode C

BATCHSV=3

OUT2

BATCHPV

0

Mode R (r)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2) and the batch count present valueBATCH PV will increment by one. The count PV is prohibited fromincrementing until the end of the output pulse time (tout2) whenOutput 2 turns OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

RESET

999999

COUNT SV

COUNT PV

T T

BATCHInput Mode UPOutput Mode R

RST2RESET

BATCH PV

OUT1

BATCH SV=2

OUT2

0

Page 61: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-61w w w . a u t o m a t i o n d i r e c t . c o m

Mode K (k)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2) and the batch count present valueBATCH PV will increment by one. The count PV will continue to incre-ment with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incre-menting the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

BATCHInput Mode UPOutput Mode K

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode P (P)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV display is prohibited from incre-menting until the end of the output pulse time when Output 2 turns OFFand the count PV is reset automatically to 0 and any input signals thatoccurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingthe count PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

TT

OUT2

BATCHInput Mode UPOutput Mode P

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

COUNT PV

0

Page 62: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-62

Mode Q (q)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV will continue to increment witheach input signal until the end of the output pulse time when Output 2turns OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingthe count PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin. The "reset" signal minimum pulse widthis set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

TT

BATCHInput Mode UPOutput Mode Q

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode A (A)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV will remain at the count SV regard-less of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingthe count PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

OUT2

BATCHInput Mode UPOutput Mode A

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

COUNT PV

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 63: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-63w w w . a u t o m a t i o n d i r e c t . c o m

Keypad set up of the parameters for Batch Counting:

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or or

or or

or or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 64: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-64

Batch Counting (bAtCH)

In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily for the time set inthe output pulse width parameter (tout2) or will be maintained ON depending on the output mode selected. Countsetting value BATCH SV controls Output 1which will be maintained ON.

CTT Counter FunctionsBatch Counting (batCH)

Counting Down (down)

Counting Down (down)

With the input signal OFF at input CP2, each leading edge of theinput signal at CP1 will decrement the count present value PV by1. Turning ON the input signal at CP2, will prohibit the inputsignal at CP1 from decrementing the PV.

Input Mode:

Mode F (F)

When the count present value PV counts down to 0, Output 2will turn ON and the batch count present value BATCH PVwill increment by one. The count PV will continue to decre-ment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF Output 2, reset the count PV to the count setting valueSV, and prohibit an input signal from decrementing the countPV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1will turn ON. The leading edge of a “reset” input signal at RST2will turn OFF Output 1, reset the BATCH PV to 0, andprohibit an input signal from incrementing the BATCH PV.The trailing edge of the “reset” signal at RST2 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP1, each trailing edge of theinput signal at CP2 will decrement the count present value PV by1. Turning OFF the input signal at CP1, will prohibit the inputsignal at CP2 from decrementing the PV.

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

COUNT PV

OUT2

BATCHInput Mode DOWN

Output Mode F

0

AProhibit

A

nn-1

n-2n-3

n-4n-5

HL

HL

CP1

CP2

0

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting down

ProhibitAA

n

n-2n-1

n-4n-3

HLCP1

CP2

Present Value

0

HL

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

Page 65: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-65w w w . a u t o m a t i o n d i r e c t . c o m

Mode N (n)

When the count present value PV counts down to 0, Output 2 willturn ON and the batch count present value BATCH PV will incre-ment by one. The count PV will remain at 0 regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to the count setting value SV, andprohibit an input signal from decrementing the count PV. The trailingedge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

OUT2

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

COUNT PV

BATCHInput Mode DOWN

Output Mode N

0

Mode C (C)

When the count present value PV counts down to 0, Output 2 willturn ON momentarily for the time set in the output pulse widthparameter (tout2), the count PV will reset automatically to the countsetting value SV, and the batch count present value BATCH PV willincrement by one.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to the count SV, and prohibit an inputsignal from decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TTT

OUT2

BATCHInput Mode DOWN

Output Mode C

BATCHSV=3

OUT2

RST1RESET999999

COUNT SV

COUNT PV

BATCHPV

RST2RESET

0

Mode R (r)

When the count present value PV counts down to 0, Output 2 willturn ON momentarily for the time set in the output pulse widthparameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV is prohibited from decrementinguntil the end of the output pulse time (tout2) when Output 2 turnsOFF and the count PV is reset automatically to the count setting valueSV.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to the count SV, and prohibit an inputsignal from decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

BATCHInput Mode DOWN

Output Mode R

RESET

999999

COUNT SV

COUNT PV

RST2RESET

BATCH PV

OUT1

BATCH SV=2

OUT2

0

Page 66: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-66

Mode K (k)

When the count present value PV counts down to 0, Output 2 will turnON momentarily for the time set in the output pulse width parameter(tout2) and the batch count present value BATCH PV will incrementby one. The count PV will continue to decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to the count setting value SV, and prohibit an inputsignal from decrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

BATCHInput Mode DOWN

Output Mode K

RST2RESET

BATCH PV

OUT1

BATCH SV=2

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode P (P)

When the count present value PV counts down to 0, Output 2 will turnON momentarily for the time set in the output pulse width parameter(tout2) and the batch count present value BATCH PV will increment byone. The count PV display is prohibited from decrementing until the endof the output pulse time when Output 2 turns OFF and the count PV isreset automatically to the count setting value SV and any input signalsthat occurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to the count SV, and prohibit an input signal fromdecrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

TT

OUT2

BATCHInput Mode DOWN

Output Mode P

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

COUNT PV

0

Page 67: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-67w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

When the count present value PV counts down to 0, Output 2 will turnON momentarily for the time set in the output pulse width parameter(tout2) and the batch count present value BATCH PV will increment byone. The count PV will continue to decrement with each input signaluntil the end of the output pulse time when Output 2 turns OFF and thecount PV is reset automatically to the count setting value SV.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to the count SV, and prohibit an input signal fromdecrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

TT

BATCHInput Mode DOWN

Output Mode Q

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode A (A)

When the count present value PV counts down to 0, Output 2 will turnON momentarily for the time set in the output pulse width parameter(tout2) and the batch count present value BATCH PV will increment byone. The count PV will remain at 0 regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to the count setting value SV, and prohibit an inputsignal from decrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

OUT2

BATCHInput Mode DOWN

Output Mode A

RST2RESET

BATCH PV

OUT1

BATCH SV=2

999999

RST1RESET

COUNT SV

COUNT PV

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 68: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-68

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad setup of the parameters for Batch Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 69: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-69w w w . a u t o m a t i o n d i r e c t . c o m

Batch Counting (bAtCH)

In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily for the time set inthe output pulse width parameter (tout2) or will be maintained ON depending on the output mode selected. Countsetting value BATCH SV controls Output 1which will be maintained ON.

CTT Counter FunctionsBatch Counting (batCH)

Counting Up / Command Counting Down (Ud A)

Counting Up / Command Counting Down (Ud A)

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will increment the countpresent value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up or counts down tothe count setting value SV, Output 2 will turn ON and thebatch count present value BATCH PV will increment by one.The count PV will continue to increment or decrement witheach input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF Output 2, reset the count PV to 0, and prohibit an inputsignal from incrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1will turn ON. The leading edge of a “reset” input signal at RST2will turn OFF Output 1, reset the BATCH PV to 0, andprohibit an input signal from incrementing the BATCH PV.The trailing edge of the “reset” signal at RST2 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP2, each leading edge of the input signal at CP1 will decrement the countpresent value PV by 1.

999999

OUT2RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdAOutput Mode F

RST1RESET

COUNT SV

COUNT PV

0

Counting up/command counting down

Page 70: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-70

Mode N (n)

When the count present value PV counts up or counts down to thecount setting value SV, Output 2 will turn ON and the batch countpresent value BATCH PV will increment by one. The count PV willremain at the count SV regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdAOutput Mode N

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode C (C)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2), the count PV will reset automaticallyto 0, and the batch count present value BATCH PV will increment byone.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TT

RESET

999999

OUT2

RST2RESET

BATCHInput Mode UdAOutput Mode C

BATCHSV=2

OUT1

BATCHPV

0

COUNT SV

COUNT PV

Mode R (r)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2) and the batch count present valueBATCH PV will increment by one. The count PV is prohibited fromincrementing or decrementing until the end of the output pulse time(tout2) when Output 2 turns OFF and the count PV is reset auto-matically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

RESET

999999

COUNT SV

COUNT PV

RST2RESET

BATCHInput Mode UdAOutput Mode R

BATCHSV=2

OUT2

BATCHPV

0

Page 71: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-71w w w . a u t o m a t i o n d i r e c t . c o m

Mode K (k)

When the count present value PV counts up or counts down to the countsetting value SV, Output 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2) and the batch count presentvalue BATCH PV will increment by one. The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incre-menting or decrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TTT

RST2RESET

BATCH PV

OUT1

BATCH SV=2

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

BATCHInput Mode UdAOutput Mode K

0

Mode P (P)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV display is prohibited from incre-menting or decrementing until the end of the output pulse time (tout2)when Output 2 turns OFF and the count PV is reset automatically to 0and any input signals that occurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

RST2RESET

BATCHInput Mode UdAOutput Mode P

BATCHSV=2

OUT1

BATCHPV

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Page 72: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-72

Mode Q (q)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. When the count present value PV counts down tothe count SV, the batch count present value BATCH PV will incrementby one. The count PV will continue to increment or decrement with eachinput signal until the end of the output pulse time (tout2) when Output2 turns OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdAOutput Mode Q

OUT2

0

Mode A (A)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV will remain at the count SV regard-less of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdAOutput Mode A

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode S (S) & Mode T (t)

When the count present value PV counts up the count setting value SV, Output 2 will turn ON and the batch countpresent value BATCH PV will increment by one. When the count PV counts down to the count SV, Output 2 will turnOFF and the batch count BATCH PV will increment by one. The count PV will continue to increment or decrementwith each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output 2, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turn ON. The leading edge of a “reset” input signalat RST2 will turn OFF Output 1, reset the BATCH PV to 0, and prohibit an input signal from incrementing theBATCH PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 73: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-73w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RST1RESET999999

COUNT SV

OUT2

BATCHInput Mode UdA

Output Mode S & T

RST2RESET

BATCH PV

BATCH SV=2

OUT1

RST1RESET999999

COUNT SV

OUT2

RST2RESET

BATCH PV

BATCH SV=2

OUT1

RST1RESET999999

COUNT SV COUNT PV

OUT2

RST2RESET

BATCH PV

BATCH SV=2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV, Output 2 will turn ONmomentarily for the time set in the output pulse width parameter (tout2) and the batch count present value BATCHPV will increment by one. The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output 2, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turn ON. The leading edge of a “reset” input signalat RST2 will turn OFF Output 1, reset the BATCH PV to 0, and prohibit an input signal from incrementing theBATCH PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UdAOutput Mode D

T T T

RST1RESET999999

COUNT SV

COUNT PV

OUT2

RST2RESET

BATCH PV

BATCH SV=2

OUT1

0

Page 74: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-74

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Batch Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 75: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-75w w w . a u t o m a t i o n d i r e c t . c o m

Batch Counting (bAtCH)

In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily for the time set inthe output pulse width parameter (tout2) or will be maintained ON depending on the output mode selected. Countsetting value BATCH SV controls Output 1which will be maintained ON.

CTT Counter FunctionsBatch Counting (batCH)

Counting Up / Counting Down (Ud b)

Counting Up / Counting Down (Ud b)

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up or counts down tothe count setting value SV, Output 2 will turn ON and thebatch count present value BATCH PV will increment by one.The count PV will continue to increment or decrement witheach input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF Output 2, reset the count PV to 0, and prohibit an inputsignal from incrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1will turn ON. The leading edge of a “reset” input signal at RST2will turn OFF Output 1, reset the BATCH PV to 0, andprohibit an input signal from incrementing the BATCH PV.The trailing edge of the “reset” signal at RST2 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.

999999

OUT2RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdBOutput Mode F

RST1RESET

COUNT SV

COUNT PV

0

Counting up/down

Page 76: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-76

Mode N (n)

When the count present value PV counts up or counts down to thecount setting value SV, Output 2 will turn ON and the batch countpresent value BATCH PV will increment by one. The count PV willremain at the count SV regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdBOutput Mode N

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode C (C)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2), the count PV will reset automaticallyto 0, and the batch count present value BATCH PV will increment byone.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UdBOutput Mode C

TT

RESET

999999

OUT2

RST2RESET

BATCHSV=2

OUT1

BATCHPV

COUNT SV

COUNT PV

0

Mode R (r)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2) and the batch count present valueBATCH PV will increment by one. The count PV is prohibited fromincrementing or decrementing until the end of the output pulse time(tout2) when Output 2 turns OFF and the count PV is reset auto-matically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

BATCHInput Mode UdBOutput Mode R

RESET

999999

COUNT SV

COUNT PV

RST2RESET

BATCHSV=2

OUT1

BATCHPV

0

OUT2

Page 77: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-77w w w . a u t o m a t i o n d i r e c t . c o m

Mode K (k)

When the count present value PV counts up or counts down to the countsetting value SV, Output 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2) and the batch count presentvalue BATCH PV will increment by one. The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incre-menting or decrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UdBOutput Mode K

TTT

RST2RESET

BATCH PV

OUT1

BATCH SV=2

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode P (P)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV display is prohibited from incre-menting or decrementing until the end of the output pulse time (tout2)when Output 2 turns OFF and the count PV is reset automatically to 0and any input signals that occurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

RST2RESET

BATCHInput Mode UdBOutput Mode P

BATCHSV=2

OUT1

BATCHPV

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Page 78: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-78

Mode Q (q)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. When the count present value PV counts down tothe count SV, the batch count present value BATCH PV will incrementby one. The count PV will continue to increment or decrement with eachinput signal until the end of the output pulse time (tout2) when Output2 turns OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdBOutput Mode Q

OUT2

0

Mode A (A)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV will remain at the count SV regard-less of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdBOutput Mode A

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode S (S) & Mode T (t)

When the count present value PV counts up the count setting value SV, Output 2 will turn ON and the batch countpresent value BATCH PV will increment by one. When the count PV counts down to the count SV, Output 2 will turnOFF and the batch count BATCH PV will increment by one. The count PV will continue to increment or decrementwith each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output 2, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turn ON. The leading edge of a “reset” input signalat RST2 will turn OFF Output 1, reset the BATCH PV to 0, and prohibit an input signal from incrementing theBATCH PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 79: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-79w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RST1RESET999999

COUNT SV

COUNT PV

OUT2

BATCHInput Mode UdB

Output Mode S & T

RST2RESET

BATCH PV

BATCH SV=2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV, Output 2 will turn ONmomentarily for the time set in the output pulse width parameter (tout2) and the batch count present value BATCHPV will increment by one. The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output 2, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turn ON. The leading edge of a “reset” input signalat RST2 will turn OFF Output 1, reset the BATCH PV to 0, and prohibit an input signal from incrementing theBATCH PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UdBOutput Mode D

T T T

RST1RESET999999

COUNT SV

COUNT PV

OUT2

RST2RESET

BATCH PV

BATCH SV=2

OUT1

0

Page 80: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-80

–FunC Cont taCh –mixtime

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Batch Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 81: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-81w w w . a u t o m a t i o n d i r e c t . c o m

Batch Counting (bAtCH)

In Batch Counting, count setting value SV controls Output 2 which will turn ON momentarily for the time set inthe output pulse width parameter (tout2) or will be maintained ON depending on the output mode selected. Countsetting value BATCH SV controls Output 1which will be maintained ON.

CTT Counter FunctionsBatch Counting (batCH)

Quadrature (Ud C)

Quadrature (Ud C)

When the quadrature input signal at CP1 leads the input signal at CP2, the trailing edge of CP2 will increment thecount present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up or counts down tothe count setting value SV, Output 2 will turn ON and thebatch count present value BATCH PV will increment by one.The count PV will continue to increment or decrement witheach input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF Output 2, reset the count PV to 0, and prohibit an inputsignal from incrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1will turn ON. The leading edge of a “reset” input signal at RST2will turn OFF Output 1, reset the BATCH PV to 0, andprohibit an input signal from incrementing the BATCH PV.The trailing edge of the “reset” signal at RST2 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

When the quadrature input signal at CP2 leads the input signal at CP1, the leading edge of CP2 will decrement thecount present value PV by 1.

999999

OUT2RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdCOutput Mode F

RST1RESET

COUNT SV

COUNT PV

0

Quadrature input

B B B B

0

1 12 2

3

HLCP1

CP2

PresentValue

0Note: has to be larger than width of 1/2 min. input signal. B

HL

0

Page 82: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-82

Mode N (n)

When the count present value PV counts up or counts down to thecount setting value SV, Output 2 will turn ON and the batch countpresent value BATCH PV will increment by one. The count PV willremain at the count SV regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdCOutput Mode N

999999

RST1RESET

COUNT SV

OUT2

COUNT PV

0

Mode C (C)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2), the count PV will reset automaticallyto 0, and the batch count present value BATCH PV will increment byone.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UdCOutput Mode C

TT

RESET

999999

OUT2

RST2RESET

BATCHSV=2

OUT1

BATCHPV

COUNT SV

COUNT PV

0

Mode R (r)

When the count present value PV counts up to the count setting valueSV, Output 2 will turn ON momentarily for the time set in the outputpulse width parameter (tout2) and the batch count present valueBATCH PV will increment by one. The count PV is prohibited fromincrementing or decrementing until the end of the output pulse time(tout2) when Output 2 turns OFF and the count PV is reset auto-matically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFFOutput 2, reset the count PV to 0, and prohibit an input signal fromincrementing or decrementing the count PV. The trailing edge of the“reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 willturn ON. The leading edge of a “reset” input signal at RST2 will turnOFF Output 1, reset the BATCH PV to 0, and prohibit an inputsignal from incrementing the BATCH PV. The trailing edge of the“reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

T T

BATCHInput Mode UdCOutput Mode R

RESET

999999

COUNT SV

COUNT PV

RST2RESET

BATCHSV=2

OUT1

BATCHPV

0

OUT2

Page 83: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-83w w w . a u t o m a t i o n d i r e c t . c o m

Mode K (k)

When the count present value PV counts up or counts down to the countsetting value SV, Output 2 will turn ON momentarily for the time set inthe output pulse width parameter (tout2) and the batch count presentvalue BATCH PV will increment by one. The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incre-menting or decrementing the count PV. The trailing edge of the “reset”signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse widthparameter ( rtSr ) or DIP Switch 8.

TTT

RST2RESET

BATCH PV

OUT1

BATCH SV=2

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

BATCHInput Mode UdCOutput Mode K

0

Mode P (P)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV display is prohibited from incre-menting or decrementing until the end of the output pulse time (tout2)when Output 2 turns OFF and the count PV is reset automatically to 0and any input signals that occurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

RST2RESET

BATCHInput Mode UdCOutput Mode P

BATCHSV=2

OUT1

BATCHPV

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Page 84: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-84

Mode Q (q)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. When the count present value PV counts down tothe count SV, the batch count present value BATCH PV will incrementby one. The count PV will continue to increment or decrement with eachinput signal until the end of the output pulse time (tout2) when Output2 turns OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdCOutput Mode Q

OUT2

0

Mode A (A)

When the count present value PV counts up to the count setting value SV,Output 2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2) and the batch count present value BATCH PVwill increment by one. The count PV will remain at the count SV regard-less of additional input signals.

The leading edge of a “reset” input signal at RST1 will turn OFF Output2, reset the count PV to 0, and prohibit an input signal from incrementingor decrementing the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turnON. The leading edge of a “reset” input signal at RST2 will turn OFFOutput 1, reset the BATCH PV to 0, and prohibit an input signal fromincrementing the BATCH PV. The trailing edge of the “reset” signal atRST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width param-eter ( rtSr ) or DIP Switch 8.

T T

RST2RESET

BATCH PV

OUT1

BATCH SV=2

BATCHInput Mode UdCOutput Mode A

OUT2

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode S (S) & Mode T (t)

When the count present value PV counts up the count setting value SV, Output 2 will turn ON and the batch countpresent value BATCH PV will increment by one. When the count PV counts down to the count SV, Output 2 will turnOFF and the batch count BATCH PV will increment by one. The count PV will continue to increment or decrementwith each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output 2, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turn ON. The leading edge of a “reset” input signalat RST2 will turn OFF Output 1, reset the BATCH PV to 0, and prohibit an input signal from incrementing theBATCH PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

Page 85: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-85w w w . a u t o m a t i o n d i r e c t . c o m

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

RST1RESET999999

COUNT SV

COUNT PV

OUT2

BATCHInput Mode UdC

Output Mode S & T

RST2RESET

BATCH PV

BATCH SV=2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV, Output 2 will turn ONmomentarily for the time set in the output pulse width parameter (tout2) and the batch count present value BATCHPV will increment by one. The count PV will continue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF Output 2, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edge of the “reset” signal at RST1 enables counting to begin.

When the BATCH PV counts up to the BATCH SV, Output 1 will turn ON. The leading edge of a “reset” input signalat RST2 will turn OFF Output 1, reset the BATCH PV to 0, and prohibit an input signal from incrementing theBATCH PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

BATCHInput Mode UdCOutput Mode D

T T T

RST1RESET999999

COUNT SV

COUNT PV

OUT2

RST2RESET

BATCH PV

BATCH SV=2

OUT1

0

Page 86: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-86

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad setup of the parameters for Batch Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 87: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-87w w w . a u t o m a t i o n d i r e c t . c o m

Total Counting (totAL)A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsTotal Counting (total)

Counting Up (UP)

Counting Up (UP)

With the input signal OFF at input CP2, each leading edge of theinput signal at CP1 will increment the count present value PV by1. Turning ON the input signal at CP2, will prohibit the inputsignal at CP1 from incrementing the PV.

Input Mode:

Mode F (F)

The Total PV increments with each count present value PV.When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON. The count PV andTotal PV will continue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP1, each trailing edge of theinput signal at CP2 will increment the count present value PV by1. Turning OFF the input signal at CP1, will prohibit the inputsignal at CP2 from incrementing the PV.

999999

RST1RESET

COUNT SV

OUT2

OUT1

COUNT PV

TOTALInput Mode UPOutput Mode F

RST2RESET

TOTAL PV

0

ProhibitA A

01

23

45

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting up

ProhibitA A

01

23

4

HL

HL

0

CP1

CP2

Present Value

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

Page 88: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-88

Mode N (n)

The Total PV increments with each count present value PV.When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON. The count PV andTotal PV will remain at the count SV regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

TOTALInput Mode UPOutput Mode N

RST2RESET

TOTAL PV

0

Mode C (C)

The Total PV increments with each count present value PV.When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

T T T

TOTALInput Mode UPOutput Mode C

TTT

RST2RESET

TOTAL PV

0

Mode R (r)

Not available in Total Counting

Page 89: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-89w w w . a u t o m a t i o n d i r e c t . c o m

OUT2

OUT1

T

T T

T

TOTALInput Mode UPOutput Mode K

RST2RESET

TOTAL PV

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode K (k)

The Total PV increments with each count present value PV.When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV and Total PV will continue to increment with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode P (P)

The Total PV increments with each count present value PV.When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV display is prohibited from incrementing until the endof the output pulse time when both outputs turn OFF and thecount PV is reset automatically to 0 and any input signals thatoccurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin. The "reset" signal minimum pulsewidth is set by reset pulse width parameter ( rtSr ) or DIPSwitch 8.

TT

TOTALInput Mode UPOutput Mode P

TT

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Accumulatedcounts duringoutput pulse

Accumulatedcounts duringoutput pulse

Page 90: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-90

Mode Q (q)

Not available in Total Counting

Mode A (A)

The Total PV increments with each count present value PV.When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV and Total PV will remain at the count SV regardlessof additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

OUT2

OUT1

T T

T T

TOTALInput Mode UPOutput Mode A

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 91: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-91w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

or or

or or

or or or or

or

or or

or or

or or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Total Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 92: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-92

Total Counting (totAL)

A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsTotal Counting (total)

Counting Down (down)

Counting Down (down)

With the input signal OFF at input CP2, each leading edge of theinput signal at CP1 will decrement the count present value PV by 1.Turning ON the input signal at CP2, will prohibit the input signal atCP1 from decrementing the PV.

Input Mode:

Mode F (F)

The Total PV increments with each decrement of the countpresent value PV. When the count present value PV countsdown to 0 both outputs 1 and 2 will turn ON. The count PVwill continue to decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to thecount setting value SV, and prohibit an input signal from decre-menting the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP1, each trailing edge of theinput signal at CP2 will decrement the count present value PV by 1.Turning OFF the input signal at CP1, will prohibit the input signalat CP2 from decrementing the PV.

TOTALInput Mode DOWN

Output Mode F

OUT2

OUT1

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

TOTAL PV

0

AProhibit

A

nn-1

n-2n-3

n-4n-5

HL

HL

CP1

CP2

0

Present Value

CP1: Counter input prohibited CP2: Counter input

Note: has to be larger than width of min. Input signalA

Counting down

ProhibitAA

n

n-2n-1

n-4n-3

HLCP1

CP2

Present Value

0

HL

CP1: Counter input CP2: Counter input prohibited

Note: has to be larger than width of min. Input signalA

Page 93: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-93w w w . a u t o m a t i o n d i r e c t . c o m

Mode N (n)

The Total PV increments with each decrement of the countpresent value PV. When the count present value PV countsdown to 0 both outputs 1 and 2 will turn ON. The count PVwill remain at 0 regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to thecount setting value SV, and prohibit an input signal from decre-menting the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode DOWN

Output Mode N

OUT1

OUT2

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

Mode C (C)

The Total PV increments with each decrement of the countpresent value PV. When the count present value PV countsdown to 0 both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to the count setting valueSV.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to thecount setting value SV, and prohibit an input signal from decre-menting the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TTT

TOTALInput Mode DOWN

Output Mode C

TTT

OUT2

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

OUT1

0

Mode R (r)

Not available in Total Counting

Page 94: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-94

T T

OUT2

OUT1

TOTALInput Mode DOWN

Output Mode K

T T

RST2RESET

TOTAL PV

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode K (k)

The Total PV increments with each decrement of the countpresent value PV. When the count present value PV countsdown to 0 both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will continue to decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to thecount setting value SV, and prohibit an input signal from decre-menting the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode P (P)

The Total PV increments with each decrement of the countpresent value PV. When the count present value PV countsdown to 0 both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV is prohibited from decrementing until the end of theoutput pulse time when both outputs turn OFF and the countPV is reset automatically to the count setting value SV and anyinput signals that occurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to thecount setting value SV, and prohibit an input signal from decre-menting the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TT

TOTALInput Mode DOWN

Output Mode P

TT

OUT2

RST1RESET

999999

COUNT SV

COUNT PV

OUT1

0

RST2RESET

TOTAL PV

Accumulatedcounts duringoutput pulse

Accumulatedcounts duringoutput pulse

Page 95: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-95w w w . a u t o m a t i o n d i r e c t . c o m

Mode Q (q)

Not available in Total Counting

Mode A (A)

The Total PV increments with each decrement of the countpresent value PV. When the count present value PV countsdown to 0 both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will remain at 0 regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to thecount setting value SV, and prohibit an input signal from decre-menting the count PV. The trailing edge of the “reset” signal atRST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingthe Total PV. The trailing edge of the “reset” signal at RST2enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

OUT1

TOTALInput Mode DOWN

Output Mode A

T T

RST1RESET

999999

COUNT SV

COUNT PV

RST2RESET

TOTAL PV

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 96: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-96

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Total Counting:

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 97: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-97w w w . a u t o m a t i o n d i r e c t . c o m

Total Counting (totAL)

A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsTotal Counting (total)

Counting Up / Command Counting Down (Ud A)

Counting Up / Command Counting Down (Ud A)

With the input signal OFF at input CP2, each leading edge of the input signal at CP1 will increment the countpresent value PV by 1.

Input Mode:

Mode F (F)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ON. Thecount PV will continue to increment or decrement with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

With the input signal ON at input CP2, each leading edge of the input signal at CP1 will decrement the countpresent value PV by 1.

TOTALInput Mode UdAOutput Mode F

OUT2

OUT1

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

TOTAL PV

0

Counting up/command counting down

Page 98: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-98

Mode N (n)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ON. Thecount PV will remain at the count SV regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdAOutput Mode N

OUT1

OUT2

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

Mode C (C)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2) and the count PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TT

TT

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

TOTALInput Mode UdAOutput Mode C

0

Mode R (r)

Not available in Total Counting

Page 99: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-99w w w . a u t o m a t i o n d i r e c t . c o m

OUT2

OUT1

TOTALInput Mode UdAOutput Mode K

TT

T T

T

T

RST2RESET

TOTAL PV

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode K (k)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up orcounts down to the count setting value SV both outputs 1 and2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV will continue to incre-ment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode P (P)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV display is prohibited from incre-menting or decrementing until the end of the output pulse timewhen both outputs turn OFF and the count PV is reset auto-matically to 0 and any input signals that occurred during theoutput pulse time.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

T

TOTALInput Mode UdAOutput Mode P

T

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Mode Q (q)

Not available in Total Counting

Page 100: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-100

Mode A (A)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV will remain at the count SVregardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

OUT2

OUT1

T T

TOTALInput Mode UdAOutput Mode A

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

Mode S (S) and Mode T(t)The Total PV increments with each increment of the count present value PV and decrements with each decrement ofthe count PV. When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turnON. When the count PV counts down to the count SV both outputs 1 and 2 will turn OFF. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count present value PV to 0,and prohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset the Total PV to 0, and prohibit an input signal from incre-menting or decrementing the Total PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RST1RESET999999

COUNT SV

COUNT PV

OUT2

OUT1

TOTALInput Mode UdA

Output Mode S & T

RST2RESET

TOTAL PV

0

Page 101: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-101w w w . a u t o m a t i o n d i r e c t . c o m

Mode D (d)

The Total PV increments with each increment of the count present value PV and decrements with each decrement ofthe count PV. When the count present value PV counts up or counts down to the count setting value SV both outputs1 and 2 will turn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV willcontinue to increment or decrement with each input signal.The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count present value PV to 0,and prohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset the Total PV to 0, and prohibit an input signal from incre-menting or decrementing the Total PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

RST1RESET999999

COUNT SV

COUNT PV

OUT2

OUT1

TOTALInput Mode UdAOutput Mode D

RST2RESET

TOTAL PV

T

T

T

T

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 102: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-102

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Total Counting:

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 103: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-103w w w . a u t o m a t i o n d i r e c t . c o m

Total Counting (totAL)

A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsTotal Counting (total)

Counting Up / Counting Down (Ud b)

Counting Up / Counting Down (Ud B)

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Input Mode:

Mode F (F)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ON. Thecount PV will continue to increment or decrement with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.

TOTALInput Mode UdBOutput Mode F

OUT2

OUT1

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

TOTAL PV

0

Counting up/down

Page 104: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-104

Mode N (n)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ON. Thecount PV will remain at the count SV regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode C (C)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2) and the count PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode R (r)

Not available in Total Counting

TOTALInput Mode UdBOutput Mode N

OUT1

OUT2

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

TOTALInput Mode UdBOutput Mode C

TT

TT

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Page 105: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-105w w w . a u t o m a t i o n d i r e c t . c o m

OUT2

OUT1

TOTALInput Mode UdBOutput Mode K

TT

T T

T

T

RST2RESET

TOTAL PV

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode K (k)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up orcounts down to the count setting value SV both outputs 1 and2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV will continue to incre-ment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode P (P)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV display is prohibited from incre-menting or decrementing until the end of the output pulse timewhen both outputs turn OFF and the count PV is reset auto-matically to 0 and any input signals that occurred during theoutput pulse time.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

T

TOTALInput Mode UdBOutput Mode P

T

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Mode Q (q)

Not available in Total Counting

Page 106: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-106

Mode A (A)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV will remain at the count SVregardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdBOutput Mode A

T T

OUT2

OUT1

T T

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

Mode S (S) and Mode T(t)

The Total PV increments with each increment of the count present value PV and decrements with each decrement ofthe count PV. When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turnON. When the count PV counts down to the count SV both outputs 1 and 2 will turn OFF. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count present value PV to 0,and prohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset the Total PV to 0, and prohibit an input signal from incre-menting or decrementing the Total PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdB

Output Mode S & T

RST1RESET999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Page 107: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-107w w w . a u t o m a t i o n d i r e c t . c o m

Mode D (d)

The Total PV increments with each increment of the count present value PV and decrements with each decrement ofthe count PV. When the count present value PV counts up or counts down to the count setting value SV both outputs1 and 2 will turn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count present value PV to 0,and prohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset the Total PV to 0, and prohibit an input signal from incre-menting or decrementing the Total PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdBOutput Mode D

RST1RESET999999

COUNT SVCOUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

T

T

T

T

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 108: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-108

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Total Counting:

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 109: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-109w w w . a u t o m a t i o n d i r e c t . c o m

Total Counting (totAL)

A single count setting value SV is available in Total Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsTotal Counting (total)

Quadrature (Ud C)

Quadrature (Ud C)

When the quadrature input signal at CP1 leads the input signal at CP2, the trailing edge of CP2 will increment thecount present value PV by 1.

Input Mode:

Mode F (F)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ON. Thecount PV will continue to increment or decrement with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

When the quadrature input signal at CP2 leads the input signal at CP1, the leading edge of CP2 will decrement thecount present value PV by 1.

TOTALInput Mode UdCOutput Mode F

OUT2

OUT1

999999

RST1RESET

COUNT SV

COUNT PV

RST2RESET

TOTAL PV

0

Quadrature input

B B B B

0

1 12 2

3

HLCP1

CP2

PresentValue

0Note: has to be larger than width of 1/2 min. input signal. B

HL

0

Page 110: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-110

Mode N (n)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ON. Thecount PV will remain at the count SV regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode C (C)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2) and the count PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode R (r)

Not available in Total Counting

TOTALInput Mode UdCOutput Mode N

OUT1

OUT2

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

TOTALInput Mode UdCOutput Mode C

TT

TT

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Page 111: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-111w w w . a u t o m a t i o n d i r e c t . c o m

OUT2

OUT1

TOTALInput Mode UdCOutput Mode K

TT

T T

T

T

RST2RESET

TOTAL PV

999999

RST1RESET

COUNT SV

COUNT PV

0

Mode K (k)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up orcounts down to the count setting value SV both outputs 1 and2 will turn ON momentarily for the time set in the output pulsewidth parameter (tout2). The count PV will continue to incre-ment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Mode P (P)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV display is prohibited from incre-menting or decrementing until the end of the output pulse timewhen both outputs turn OFF and the count PV is reset auto-matically to 0 and any input signals that occurred during theoutput pulse time.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

T

TOTALInput Mode UdCOutput Mode P

T

RST1RESET

999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Mode Q (q)

Not available in Total Counting

Page 112: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-112

Mode A (A)

The Total PV increments with each increment of the countpresent value PV and decrements with each decrement of thecount PV. When the count present value PV counts up to thecount setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV will remain at the count SVregardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The leading edge of a “reset” input signal at RST2 will reset theTotal PV to 0, and prohibit an input signal from incrementingor decrementing the Total PV. The trailing edge of the “reset”signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdCOutput Mode A

T T

OUT2

OUT1

T T

RST2RESET

TOTAL PV

RST1RESET

999999

COUNT SV

COUNT PV

0

Mode S (S) and Mode T(t)

The Total PV increments with each increment of the count present value PV and decrements with each decrement ofthe count PV. When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turnON. When the count PV counts down to the count SV both outputs 1 and 2 will turn OFF. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count present value PV to 0,and prohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset the Total PV to 0, and prohibit an input signal from incre-menting or decrementing the Total PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdC

Output Mode S & T

RST1RESET999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

0

Page 113: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-113w w w . a u t o m a t i o n d i r e c t . c o m

Mode D (d)

The Total PV increments with each increment of the count present value PV and decrements with each decrement ofthe count PV. When the count present value PV counts up or counts down to the count setting value SV both outputs1 and 2 will turn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count present value PV to 0,and prohibit an input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signalat RST1 enables counting to begin.

The leading edge of a “reset” input signal at RST2 will reset the Total PV to 0, and prohibit an input signal from incre-menting or decrementing the Total PV. The trailing edge of the “reset” signal at RST2 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

TOTALInput Mode UdCOutput Mode D

RST1RESET999999

COUNT SV

COUNT PV

OUT2

OUT1

RST2RESET

TOTAL PV

T T

TT

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 114: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-114

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

C–inPt ––UP down ud–a ud–b ud–C

Select input modes: counting up, counting down, counting up/command counting down, counting up/counting down, quadrature input.

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

ororororor

or or or or or or

or or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Total Counting:

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 115: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-115w w w . a u t o m a t i o n d i r e c t . c o m

Dual Counting (dUAL)A single count setting value SV is available in Dual Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsDual Counting (dual)

Addition (add)

Addition (Add)

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON. The count PV willcontinue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Each leading edge of the input signal at CP2 will increment the count present value PV by 1.

999999RESET

SV

OUT2

OUT1

PV

DUALInput Mode ADDITION

Output Mode F

0

Mode N (n)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON. The count PV willremain at the count SV regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

DUALInput Mode ADDITION

Output Mode N

0

Page 116: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-116

Mode C (C)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing the count PV. Thetrailing edge of the “reset” signal at RST1 enables counting tobegin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

T T T

DUALInput Mode ADDITION

Output Mode C

TTT

0

Mode R (r)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV is prohibited from incrementing until the end of theoutput pulse time (tout2) when the outputs turn OFF and thecount PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

T T

DUALInput Mode ADDITION

Output Mode R

T T

0

Mode K (k)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will continue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

T

T

DUALInput Mode ADDITION

Output Mode K

T

T

0

Page 117: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-117w w w . a u t o m a t i o n d i r e c t . c o m

Mode P (P)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV display is prohibited from incrementing until the endof the output pulse time when both outputs turn OFF and thecount PV is reset automatically to 0 and any input signals thatoccurred during the output pulse time.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

TT

DUALInput Mode ADDITION

Output Mode P

TT

0

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will continue to increment with each input signaluntil the end of the output pulse time when the outputs turnOFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

TT

TT

DUALInput Mode ADDITION

Output Mode Q

0

Mode A (A)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will remain at the count SV regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

T T

T T

DUALInput Mode ADDITION

Output Mode A

0

Page 118: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-118

Mode S (S) and Mode T(t)

When the count present value PV counts up to the countsetting value SV both outputs 1 and 2 will turn ON. The countPV will continue to increment with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

999999RESET

SV

OUT2

OUT1

PV

DUALInput Mode ADDITION

Output Mode S & T

0

Mode D (d)When the count present value PV counts up to the countsetting value SV both outputs 1 and 2 will turn ON momen-tarily for the time set in the output pulse width parameter(tout2). The count PV will continue to increment with eachinput signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0, and prohibit aninput signal from incrementing the count PV. The trailing edgeof the “reset” signal at RST1 enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

999999RESET

SV

OUT2

OUT1

PV

DUALInput Mode ADDITION

Output Mode D

0

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 119: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-119w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

Dual –add –sub

Select dual mode: Add or Subtract

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

oror

or or or or or or

or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:

Keypad set up of the parameters for Dual Counting:

Output Mode - Table 2Switch 3 Switch 4 Output Mode

OFF OFF F

ON OFF N

OFF ON C

ON ON R

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6

Page 120: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-120

Dual Counting (dUAL)A single count setting value SV is available in Dual Counting. Both Outputs 1 and 2 operate concurrently and willturn ON momentarily for the time set in the output pulse width parameter (tout2) or will be maintained ONdepending on the Output Mode selected.

CTT Counter FunctionsDual Counting (dual)

Subtraction (Sub)

Subtraction (SUb)

Each leading edge of the input signal at CP1 will increment the count present value PV by 1.

Input Mode:

Mode F (F)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON. The count PV willcontinue to increment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

Output Modes:

Each leading edge of the input signal at CP2 will decrement the count present value PV by 1.

999999RESET

SV

OUT2

OUT1

PV

DUALInput Mode SUBTRACTION

Output Mode F

0

Mode N (n)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON. The count PV willremain at the count SV regardless of additional input signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

DUALInput Mode SUBTRACTION

Output Mode N

RESET

999999

SV

PV

OUT2

OUT1

0

Page 121: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-121w w w . a u t o m a t i o n d i r e c t . c o m

Mode C (C)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2) andthe count PV will reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count present value PV to 0, andprohibit an input signal from incrementing or decrementing thecount PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

TT

RESET

999999

SV

PV

OUT2

OUT1

DUALInput Mode SUBTRACTION

Output Mode C

TT

0

Mode R (r)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV is prohibited from incrementing or decrementinguntil the end of the output pulse time (tout2) when theoutputs turn OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T

T T

T

DUALInput Mode SUBTRACTION

Output Mode R

RESET

999999

SV

PV

OUT2

OUT1

0

Mode K (k)

When the count present value PV counts up or counts down tothe count setting value SV both outputs 1 and 2 will turn ONmomentarily for the time set in the output pulse width param-eter (tout2). The count PV will continue to increment ordecrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

RESET

999999

SV

PV

OUT2

OUT1

DUALInput Mode SUBTRACTION

Output Mode K

TT

T T

T

T

0

Page 122: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-122

Mode P (P)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV display is prohibited from incrementing or decre-menting until the end of the output pulse time when bothoutputs turn OFF and the count PV is reset automatically to 0and any input signals that occurred during the output pulsetime.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

T

DUALInput Mode SUBTRACTION

Output Mode P

RESET

999999

SV

PV

OUT2

OUT1

T

0

Mode Q (q)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will continue to increment or decrement with eachinput signal until the end of the output pulse time when theoutputs turn OFF and the count PV is reset automatically to 0.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

DUALInput Mode SUBTRACTION

Output Mode Q

0

Mode A (A)

When the count present value PV counts up to the count settingvalue SV both outputs 1 and 2 will turn ON momentarily forthe time set in the output pulse width parameter (tout2). Thecount PV will remain at the count SV regardless of additionalinput signals.

The leading edge of a “reset” input signal at RST1 will turnOFF both outputs, reset the count PV to 0 and prohibit aninput signal from incrementing or decrementing the count PV.The trailing edge of the “reset” signal at RST1 enables countingto begin.

The "reset" signal minimum pulse width is set by reset pulsewidth parameter ( rtSr ) or DIP Switch 8.

T T

RESET

999999

SV

PV

OUT2

OUT1

T T

DUALInput Mode SUBTRACTION

Output Mode A

0

Page 123: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-123w w w . a u t o m a t i o n d i r e c t . c o m

Mode S (S) and Mode T(t)

When the count present value PV counts up to the count setting value SV both outputs 1 and 2 will turn ON. Whenthe count PV counts down to the count SV both outputs 1 and 2 will turn OFF. The count PV will continue to incre-ment or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1 enablescounting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

DUALInput Mode SUBTRACTION

Output Mode S & T

RESET999999

SVPV

OUT2

OUT1

0

Mode D (d)

When the count present value PV counts up or counts down to the count setting value SV both outputs 1 and 2 willturn ON momentarily for the time set in the output pulse width parameter (tout2). The count PV will continue toincrement or decrement with each input signal.

The leading edge of a “reset” input signal at RST1 will turn OFF both outputs, reset the count PV to 0, and prohibitan input signal from incrementing or decrementing the count PV. The trailing edge of the “reset” signal at RST1enables counting to begin.

The "reset" signal minimum pulse width is set by reset pulse width parameter ( rtSr ) or DIP Switch 8.

DUALInput Mode SUBTRACTION

Output Mode D

RESET

999999

SV

PV

OUT2

OUT1

T

T

T

T

T

T

0

Page 124: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 1 - 8 0 0 - 6 3 3 - 0 4 0 52-124

Dip Switch Settings - Table 1Switch Function Off On

1 Dip switch Disabled Enabled

2 Counting mode Counting up Counting down

3Output mode See Output Mode Table - Table 2

4

5 Counting speed 30cps 10Kps

6 Reserved - -

7 Input signal NPN PNP

8 Reset signalpulse width 20 ms 1 ms

DIP Switch Set Up of the CTT Parameters:Output Mode - Table 2

Switch 3 Switch 4 Output ModeOFF OFF F

ON OFF N

OFF ON C

ON ON R

Outputs

Load

Load

OUT1NPN/

SINKING

OUT2SPDT

Load

OUT1SPST

0V CP1CP2/ GATE (Pause)

+12V RST1RST2/ START

CP2 Input

CP1 Input

Reset

0V CP1

+12V RST1RST2/ START

Reset

0V CP1

+12V RST1RST2/ START

Reset

PNPINPUTS

L-

Load

OUT2NPN/

SINKING

Load

0V CP1

+12V RST1RST2/ START

Reset

L-

L+

NPNINPUTS

CP1 Input

CP2 Input

CP2 Input

CP1 Input

CP1 Input

CP2 Input

L+

+VDC 0VDC

Externally Powered

Internally Powered

+VDC 0VDC

Externally Powered

Internally Powered

(Optional)

(Optional)

(Optional) (Optional)

+VDC

0VDC +VDC

0VDC

109

3211514

10

15

876

131211

876

131211

876

131211

321

876

131211

Counter Wiring Examples

CP2/ GATE (Pause)

CP2/ GATE (Pause)

CP2/ GATE (Pause)

Page 125: CHHAAPPTTEERR COUNTER - AutomationDirect · 2-6 Digital Counter / Timer / Tach User Manual, 1st Ed. 1-800-633-0405 Mode C (C) When the count present value PV counts up to the count

Digital Counter / Timer / Tach User Manual, 1st Ed. 2-125w w w . a u t o m a t i o n d i r e c t . c o m

Select functions: There are 4 modes in CTT, (left to right) timer, counter, tachometer and timer + counter.

Select counter functions: 1-stage counting, 2-stage counting, batch counting, total counting, dual counting.Ä

CntFun sta6e1 sta6e2 batCh total dual

Dual –add –sub

Select dual mode: Add or Subtract

C–otmd F n C r k p

q a s t d

Select output modes: CTT offer 11 output modes, among which mode S, T and D are only valid with input modesUd_A, Ud_b and Ud_C.

Select counting speed: Maximum 10Kcps; others 5K, 1K, 200, 30 and 1cps.

C–Sped –10k ––5k ––1k –200 ––30

t–out1

Pulse width of output 1: The default output time is 0.02 second. When the parameter is set to 0.00 second, the output status will be maintained ON.

–––1

–002 –000

t–out2

Pulse width of output 2: This paramter is adjustable according to different output modes selected. If the output mode is C,the default output time will be 0.02 second, When the parameter is set to 0.00 second, the output status will be maintained ON.

–002 –000

–point

Set up the position of decimal point: 0 (no decimal point), 1 (one digit after decimal point), 2 (two digits after decimalpoint), 3 (three digits after decimal point).

0 1 2 3

psCale 1000

Set up pre-scale value: 1.000 (default 1:1) Range: 0.001 to 99.999

–pwers

Save the data while switching off the power: When SAVE is selected, the PV will be saved; when CLEAR is selected,the PV will not be saved.

Clear save

–rtsr

Set up minimum width of reset signal: Default = 20ms; 1ms is also selectable

––20 –––1

inptlC

Select input signal types: NPN and PNP

–npn –pnp

Back to Top

–FunC Cont taCh –mixtime

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

Ä

or

or or or or

or or or or or

oror

or or or or or or

or or or or or

or or or or or or

or or

or or

or or or or

or

or

or

or

or

or

To enter the page for parameter setting of the counter, press Ä for the main menu for more than 3 seconds. Afterthe setup is completed, press Ä for more than 3 seconds under any of the parameter page you are in and returnto the main menu.

Keypad set up of the parameters for Dual Counting:

Used to convert the displayed PV into engineering unit, such as RPM, inches, millimeters, feet per minute etc. SeeTachometer Examples in Chapter 6