circuit breaker application & distribution systems - 2014

107
© ABB Group March 12, 2014 | Slide 1 Lionel Ng, LPBS - Low Voltage Products Welcome Technical Sharing Session

Upload: arokia-kupri

Post on 02-Oct-2015

31 views

Category:

Documents


6 download

DESCRIPTION

All right reserved by ABB. For knowledge and education purposes use only.

TRANSCRIPT

  • ABB Group March 12, 2014 | Slide 1

    Lionel Ng, LPBS - Low Voltage Products

    Welcome Technical Sharing Session

  • ABB Group March 12, 2014 | Slide 2

    Lionel Ng, LPBS - Low Voltage Products, 2014

    Electrical Installation Circuit Breaker Selection

  • As to be able to protect LV/MV transformers LV side, we must mainly

    take into account:

    Rated current of the protected transformer, LV side, from which

    the rated current of the circuit breaker and the setting depend on

    (In);

    The maximum estimated short circuit current in the installation

    point which defines the minimal breaking power of the protection

    circuit breaker (Isc).

    Protection of Transformers

  • Sn

    In

    Isc

    U20

    Protection of Transformers Switchboards with one transformer

    The rated current of the transformers LV side is defined by the

    following expression

    where

    Sn = rated power of the transformer [kVA]

    U20 = rated secondary voltage (no load) of the transformer [V]

    ln = rated current of the transformer, LV side [A]

    In = Sn x 103

    3 x U20

  • The full voltage three-phase short circuit current immediately after the LV

    side of the transformer can be expressed by the following relation once we

    suppose infinite power at the primary:

    where

    Ucc % = short circuit voltage of the transformer [%]

    ln = rated current, LV side, [A]

    lsc = three-phase rated short circuit current, LV side, [A]

    Isc = In x 100

    Ucc %

    Protection of Transformers

    The short circuit current is normally lesser than the deduced value if

    the circuit breaker is installed at a certain distance by means of a cable

    or bar connection, according to the connection impedance.

  • Circ

    uit b

    reaker B

    I1 I2 I3

    1 2 3

    Isc2 + Isc3

    Isc1 + Isc2 + Isc3

    I4 I5

    Circ

    uit b

    reaker A

    Isc1

    Protection of Transformers Switchboards with more than 1 transformer in Parallel

  • As far as the calculation of the rated current of the transformer is

    concerned, the rules beforehand indicated are completely valid.

    The minimum breaking capacity of each circuit breaker LV side must be

    greater than the highest of the following values: (the example refers to

    machine 1 of the figure and it is valid for the three machines in parallel):

    lsc 1 (short circuit current of transformer 1) in case of fault

    immediately downstream circuit breaker 1;

    lsc2 + lsc3 (short circuit currents of transformer 2 and 3) in case of

    fault immediately upstream circuit breaker 1;

    Protection of Transformers

    Circuit breakers l4 and l5 on the load side must have a short circuit

    capacity greater than lsc1 + lsc2 + lsc3; naturally every transformer

    contribution in the short circuit current calculation is to be lessened by the

    connection line transformer - circuit breaker (to be defined case by case).

  • The choice of the circuit breakers for switching and protection of cables

    means the perfect knowledge of:

    rated operating line current lB

    max admissable cable current lZ

    presumed short circuit current in the point of installation of the circuit

    breaker Icc

    Protection of Cables

  • The correct circuit breaker must be selected to satisfy the following

    conditions:

    It must have a short circuit breaking capacity (lcu or eventually lcs) greater

    or equal to the short circuit current lcc

    It must use a protection release so that its overload setting current ln (l1)

    satisfies the relation lB < ln < lZ (Oveload protection)

    The let through energy (l2t) that flows through the circuit breaker must be

    lesser or equal to the maximal one allowed by the cable (KS) (Short-

    circuit protection)

    Protection of Cables

  • It

    Icc

    Cable KS

    Circuit breaker It

    Icc max

    Protection of Cables

  • As far as the verification required by IEC 60364, according to which

    the overload protection must have an intervention current (lf) that

    assures the operation for a value lesser than 1.45 lz (lf < 1.45 lz), we

    must state that it is always verified for ABB Circuit breakers, since

    according to IEC 60947-2 the required value is less than 1.3 ln.

    Protection of Cables

  • LV protection devices

    L function protection against

    overload

    Circuit Breaker Curves

  • S function protection against

    delayed short-circuit

    LV protection devices

    Circuit Breaker Curves

  • LV protection devices

    Circuit Breaker Curves

    I function protection

    against instantaneous

    short-circuit

  • LV protection devices

    Circuit Breaker Curves

    G function protection

    against earth-fault

  • A

    B

    C

    Protection of Primary & Secondary Distribution

    Selective Protection

    The example emphasizes the need for co-

    ordination between circuit breakers A and

    B, such that in case of fault in C, only circuit

    breaker B trips, thus leaving complete

    continuity to the rest of the plant supplied

    by the circuit breaker A.

    Selectivity might be Total or Partial:

    Total selectivity: only the circuit breaker B

    trips for every current value lesser or equal to

    the max short circuit current foreseen in C;

    Partial selectivity: the circuit breaker B opens

    only according to fault current lower than a

    certain value; values that are equal or greater

    than this will give the intervention of both

    circuit breakers A and B.

  • Amperometric (Current) selectivity is obtained

    by setting on different values the

    instantaneous tripping currents of the circuit

    breakers chain (greater values for upstream

    circuit breakers)

    Protection of Primary & Secondary Distribution

    Selective Protection

    A B

    ImB ImA

    ImA is the selectivity limit

  • Chronometric (Time) selectivity is obtained by

    introducing intentionally always greater delays in

    the intervention tripping timings of the upstream

    circuit breakers in the chain.

    Protection of Primary & Secondary Distribution

    Selective Protection

    Total selectivity

    B A

    t

  • Switchboard A

    Switchboard B

    400V

    400V

    2500 kVA

    (fault current 57,5 kA)

    E2N20 MS (disconnector)

    E4S40

    with PR121

    E2N20

    with PR121

    T5H 630

    with PR222

    Protection of Primary & Secondary Distribution

  • Protection of Primary & Secondary Distribution

  • Protection of Primary & Secondary Distribution

  • A

    B

    C

    Protection of Primary & Secondary Distribution

    Back-up Protection

    In the figure, the circuit breaker B, downstream in respect

    with A, might have a short circuit breaking capacity lesser

    than the presumed short circuit current in case of fault in

    C if the circuit breaker A satisfies at all the two following

    conditions:

    It has a short circuit rating greater or equal to the

    presumed short circuit current in its installation point and

    obviously greater than the short circuit current in C

    In case of fault in C with short circuit values greater

    than the short circuit breaking capacity of circuit breaker

    B, the circuit breaker A must limit the let through energy

    by limiting it to a correct value than can be stood by

    circuit breaker B and by the protected lines

  • The back-up protection is used in electric plants where operation continuity

    is not a main need. This means that the up stream breaker will always trip

    with or without the help from the down stream protection device. This

    means the whole system including the sound parts of the installation will

    be without power.

    This co-ordination solution is used by those who need to contain the plant

    costs by reducing the general performance in case of a fault.

    Protection of Primary & Secondary Distribution

    Back-up Protection

  • U Load

    B

    A

    Ib = 1300 A

    Icc = 65 kA

    Icc 30 kA

    Ib = 300 A

    Protection of Primary & Secondary Distribution

    Back-up Protection

    Electrical characteristics of the employed circuit breakers

    Reference Rated Type Rated Breaking Selectivity Back-up

    current uninterrupted capacity limit limit

    current

    [A] Iu [A] Icu [kA] [kA] [kA]

    A 1300 SACE Emax E2L16 1600 130

    B 300 SACE Tmax T4N 320 320 36

    36 (T) 65

  • 50 kA !!!

    T4S 250

    T1N 160 * T1N 160 is 36 kA only mccb

    Protection of Primary & Secondary Distribution

    Back-up Protection

  • T6H 800 (70kA)

    70 kA

    T4H 250 (70kA)

    Protection of Primary & Secondary Distribution

    Selectivity

  • Rated operational voltage Ue: the value of voltage which

    determines the application and to which all the other

    parameters are referred to.

    Rated uninterrupted current Iu: the value of current which the

    device is able to carry for an indefinite time. It defines the size

    of the CB

    Rated current In: the value of current which characterizes the

    protection release installed. Is often related to the rated

    current of the load protected

    T5N400 PR221DS-LS/I In 320

    Iu In

    Selection of Protective Devices Main electrical parameters

  • Rated ultimate short-circuit breaking capacity Icu: it is the

    r.m.s. value of the symmetrical component of the short-circuit

    current which the circuit-breaker is able to break (test cycle O-

    t-CO)

    Rated service short-circuit breaking capacity Ics: it is the r.m.s.

    value of the symmetrical component of the shortcircuit current

    which the circuit-breaker is able to break (O-t-CO-t-CO)

    T5N400 PR221DS-LS/I In 320

    Icu

    Selection of Protective Devices Main electrical parameters

  • Rated short-circuit making capacity Icm: it is the maximum

    prospective peak current which the circuit-breaker must be

    able to make Icm=n x Icu

    T5N400 PR221DS-LS/I In 320

    Icu 36kA Icm 75.6 kA @415V

    Selection of Protective Devices Main electrical parameters

  • Rated short-time withstand current Icw: it is the r.m.s. value of

    the alternate current component which the circuit-breaker is

    able to withstand without damages for a determined time,

    preferred values being 1s and 3 s

    Defined for category B only

    Selection of Protective Devices Main electrical parameters

  • Selection of Protective Devices Main electrical parameters

  • Generalities about the main electrical parameters Dont forget

    Ue Un Icu or Ics Ik Icm Ip

    Ue, Icu, Ics, Icm?

    Selection of Protective Devices Main electrical parameters

  • ABB Group March 12, 2014 | Slide 34

    Lionel Ng, Low Voltage Products, 2014

    Distribution systems Protection against indirect contact and earth fault

  • Agenda

    Main definitions

    Distribution systems and protection

    against indirect contact and earth fault

    ABB solutions for protection

    against earth fault

    Discrimination of the protections

    against earth fault

  • Definitions

    Indirect contact

    Electric contact of persons with exposed-conductive-parts which have become live under fault condiction (deterioration)

    Direct contact

    Electric contact of persons with live parts

  • Definitions

    Earth fault

    The loss of insulation between normally live conductors and exposed-conductive-parts may generate a earth fault

    Main causes of the loss of insulation:

    time decay of dieletric properties

    mechanical breaking

    particularly aggressive environments

    rodent action

    overvoltages of atmospheric origin or due to switching

  • Definitions

    Main effects of the earth fault current

    energizing of exposed-conductive-

    parts

    localized electric arcs and consequent

    overheatings

    disturbances to telecommunication systems

    erosion phenomena of earth electrodes

  • Definitions

    Time-current zones of the effects of alternating current on the human body

    A contact with a live part causes the flowing of current through

    the human body, the danger of this current depends on its :

    duration

    size

    Reversible pathological effects

    No reaction

    No physiological effect

    Fibrillation risk greater than

    50%

    1

    2

    3

    4

  • Definitions

    Live part

    Conductor or conductive part intended to be enegized in normal operation

    Including a neutral conductor

    By convetion not a PEN.

    Exposed-conductive-part

    Conductive part

    Can be touched

    Is not normally live

    Can become live when basic insulation fails

  • Definitions

    Basic insulation

    Isolation of live part

    Base protection against direct and indirect contact

    Supplementary isolation

    independent insulation applied in addition to basic insulation

    Insures the protection when the basic insulation fails

    Double isolation

    comprises both basic insulation and supplementary insulation

    Reinforced insulation

    provides a degree of protection against electric shock equivalent to double insulation (unique insulation)

    Fault current current which flows across a given point of fault resulting from an insulation

    fault

  • Definitions

    Live part

    functional isolation: in an electrical device it insulates the parts at different potentials thus enabling operations

    basic insulation is the insulation of the normally live parts

    supplementary insulation is applied in addition to basic insulation in case of a failure of the last

    reinforced insulation, a unique insulation which can guarantee the equivalent protection degree which can be provided by basic insulation plus supplementary insulation

    Double insulation: comprises both basic insulation and supplementary insulation

    +

  • Definitions

    Reference earth

    part of the Earth considered as conductive, the electric potential of which is conventionally taken as zero

    Earth electrode

    conductive part, which may be embedded in a specific conductive medium, e.g. concrete or coke, in electric contact with the Earth

    Earthing resistance

    resistance between the main earth collector (or node) and the Earth

  • Definitions

    L1

    L2

    L3

    N PE

    Protective conductor PE

    conductor provided for purposes of safety (protection against electric shock)

    it connects:

    exposed-conductive-parts

    main earth collector (or node)

    earth electrode

    earthed point of the source or artificial neutral

    PEN conductor

    combines the functions of both a PE conductor and a neutral conductors

    Residual current:

    vectorial sum of the values of the electric currents in all live conductors

    Id = IL1+ IL2+ IL3+ IN

  • Classification of electrical distribution systems

    Protection against indirect contact

    Protection throught automatic disconnection :

    CBs with thermomagnetic or electronic releases;

    CBs with electronic releases with G function against earth fault

    CBs with residual current devices integrated

    Residual current circuit breaker

    Residual current releases

    protection without automatic disconnection:

    Protection by double or reinforced insulation;

    Protection by earth-free local equipotential bonding;

    Protection by electrical separation for the supply of only one item of current-using equipment

    Protection by electrical separation for the supply of more than one item of current-using equipment

  • Classification of electrical distribution systems

    The IEC 60364-3 classifies the electrical systems with the combination of two letters

    The first letter indicates the relationship of the power system to earth

    T direct connection to earth of one point

    I all live parts isolated from earth or one point connected to earth through an impedance

    The second letter indicates the relationship of the exposed-conductive- parts of the installation to earth

    T direct connection to earth

    N direct electrical connection of the exposed-conductive-parts to the earthed point of the power system

  • Classification of electrical distribution systems

    Subsequent letters, if any, indicates the arrangement of neutral and protective

    conductors

    S neutral and protective functions provided by separate conductors

    C neutral and protective functions combined in a single conductor (PEN

    conductor)

    PE N

    PEN

  • Classification of electrical distribution systems

    TT system

    the neutral and the exposed-conductive-parts are connected to

    earth electrodes electrically independent

  • Classification of electrical distribution systems

    TT system

    The earth fault current returns to the power supply node through the soil

  • Classification of electrical distribution systems

    TT system

    The exposed-conductive-part assumes the potential UT = Ik RA

    The person touching the exposed-conductive-part is subjected to the voltage UT

    Ik

  • Classification of electrical distribution systems

    Condition to be fulfilled :

    Ra is the total resistance of the earth electrode and of the protective conductor of the exposed-conductive-parts

    IDn is the rated residual operating current of the residual current circuit- breaker

    the time defined in the following table for the terminal circuits with a rated current In32A

    0UIR na D

  • Classification of electrical distribution systems

    Thanks to a more sensitive residual current device, from a pratical point of view it will be easier to realize an earthing system coordinated with the characteristics of the device itself. This table shows the maximum values of earth resistance which can be obtained with residual current devices and making reference to a common environment (50V)

  • toroid

    trip coil

    test button

    main contact

    resistance

    electronic circuit (if any)

    How an RCD works

  • How an RCD works

  • How the RCD works

    TEST

  • Classification of electrical distribution systems

    Condition to be fulfilled :

    Zs is the total impedance of the loop;

    Ia is the disconnection current in these time:

    the time defined in the following table for the terminal circuits with a rated current In32A

    0UIZ as

  • Conclusion about TT system

    Domestic installations and similar, small industries with LV power supply

    Typical value of earth fault currents 10 ~ 100A

    The standards allow the use of:

    CBs with inverse time tripping characteristics

    CBs with instantaneus tripping characteristics

    Residual current devices

    If automatic disconnection cannot be obtained in compliance with the disconnection times of the table or within the conventional time, it shall be necessary to provide supplementary equipotential bonding connnected to earth, however the use of supplementary protective bonding does not exclude the need to disconnect the supply for other reasons, for example protection against fire, thermal stresses in equipment

    Classification of electrical distribution systems

  • Classification of electrical distribution systems

    TN-S system

    the neutral and the exposed-conductive-parts are connected to the same earthing arrangement

    the exposed-conductive-parts are connected to the earth electrode by means of the PE

    N

    PE

  • Classification of electrical distribution systems

    TN-C system

    the neutral and the exposed-conductive-parts are connected to the same

    earthing arrangement

    the exposed-conductive-parts are connected to the earth electrode by

    means of the PEN

    PEN

  • Classification of electrical distribution systems

    TN system

    the earth fault current returns to the power supply node without practically

    affecting the earth electrode

    the current is limited by the impedance of the fault loop

  • Classification of electrical distribution systems

    TN system

    It is necessary to interrupt the fault because person touching the exposed-conductive-part is subjected to the voltage UT

  • Classification of electrical distribution systems

    Condition to be fulfilled :

    Zs is the impedance of the fault loop

    U0 is the nominal voltage to earth

    Ia is the diconnection time in ampere of the protective devices within:

    the time defined in the following table for the terminal circuits with a rated current In32A

    0aS UIZ

  • Classification of electrical distribution systems

    TN system: example

    Un = 400 V (U0=230V)

    This system supplies a terminal circuit with In>32A

    Earth fault = 3 kA

  • Classification of electrical distribution systems

    Conclusion about TN system:

    Industries and big installations with MV power supply

    Fault current values similar to those of the single-phase fault

    The standard allow the use of:

    Automaic devices against overcurrents

    RCD or CBs with G function

    In the TN-C systems disconnection of the neutral and use of the residual current devices or devices with similar operating principle (function G against earth fault) is not possible

    if automatic disconnection cannot be obtained in compliance with the disconnection times of the table or within the conventional time, it shall be necessary to provide supplementary equipotential bonding connected to earth, however the use of supplementary protective bonding do not exclude the need to disconnect the supply for other reasons, for the example protection against fire, thermal stresses in equipment

  • Classification of electrical distribution systems

    Why in TN-C system it is not possible to use RCD or

    function G against earth fault?

    TN-S

    TN-C

  • Classification of electrical distribution systems

    IT system

    has no active parts directly earthed

    may have live parts connected to earth through high value impedance

    the exposed-conductive-parts are connected to an independent earth electrode

  • Classification of electrical distribution systems

    Dieletric insulator+air

    Electric field

    Plate

    Plate area

    IT system

    The earth fault current returns to the power supply through the earthing arrangement of the exposed-conductive-parts and the capacities to earth of the line conductors

    the fault current value depends on the size of the installation

  • capacities to earth of the line conductors

    capacitor

    cable

    plate area

    dielectric insulator+air

    plate area

    electric field

    electric field

    plate area

    plate area

    dielectric

    Classification of electrical distribution systems

  • Classification of electrical distribution systems

    IT system

    the automatic disconnection of the circuit is not necessary

    condition to be fulfilled:

    RE is the sum of the resistance, in ohms, of the earth electrode and protective conductor for exposed-conductive-parts;

    Id is the fault current, in amperes, of the first fault of negligible impedance between a line conductor and an exposed-conductive-part; such value takes account of the leakage currents and of the total earthing impedance of the electrical installation

    an insulation monitoring device shall be provided to indicate the presence of

    fault.

    VIR dE 50

  • Classification of electrical distribution systems

    IT system

    the occurrence of a first earth fault modifies the distribution system

    two situations may occur in the event of a fault to earth

  • Classification of electrical distribution systems

    IT system

    the occurrence of a first earth fault modifies the distribution system

    two situations may occur in the event of a fault to earth

  • Classification of electrical distribution systems

    according to TT system

    IT system

    in the event of a second fault, the supply shall be disconnected

  • Classification of electrical distribution systems

    according to TN system

    IT system

    in the event of a second fault, the supply shall be disconnected

  • Neutral distribuited:

    Classification of electrical distribution systems

    a

    sI

    UZ

    2a

    sI

    UZ

    2

    0'

    Neutral not distribuited:

    U0= is the nominal voltage between line conductor and neutral conductor

    U = is the nominal voltage between line conductor

    Zs = is the impedance of the fault loop comprising the line conductor and the protective conductor of the circuit

    Zs= is the impedance of the fault loop comprising the neutral conductor and the protective conductor of the circuit

    Ia = is the current causing the operation of protective device within the time required for TN system

  • Classification of electrical distribution systems

    Conclusion about IT system:

    chemical and petrochemical industries, i.e. plants for

    which service continuity is fundamental

    fault currents A ~ 2A dependent on the size of the

    installation

    system suitable for the cases in which service continuity

    must be assured

    The presence of a first fault does not cause high current and/or currents dangerous for the people

  • A reliable and safe protection is realized by combining:

    The protection functions against overcurrent with those against earth faults

    An effective earthing arrangement

    This choice allows to obtain:

    Protection against indrect contact

    A timely protection against earth falts of small value where prevention from fire risks is absolutely necessary

    Protection Solution

  • Protection Solution

    For an adequate protection against earth faults ABB has designed the following product categories:

    Miniature circuit breaker

    Residual current operated circuit-breakers with integral overcurrent protection DS201 & DS202;

    Residual current operated circuit-breakers with integral

    overcurrent protection DS200;

    Residual current operated circuit-breakers with integral

    overcurrent protection DS800

    Residual current blocks DDA200

    Residual current blocks DDA 60, DDA 70, DDA 90 (S290)

    Residual current blocks DDA 800

    Residual current circuit breaker F200

  • Protection Solution

    Miniature circuit-breaker

    Residual current operated circuit-breakers with integral

    overcurrent protection DS201

  • Protection Solution

    Miniature circuit-breaker

    Residual current operated circuit-breakers with integral

    overcurrent protection DS202

  • Protection Solution

    Miniature circuit-breaker

    Residual current operated circuit-breakers with

    integral overcurrent protection DS200

  • Protection Solution

    Miniature circuit-breaker

    Residual block DDA200

  • Protection Solution

    Miniature circuit breaker

    Residual block DDA 60, DDA 70, DDA 90

  • Protection Solution

    Miniature circuit breaker

    Residual block DDA 800

  • Protection Solution

    Miniature circuit breaker

    Residual current circuit breaker F200

  • Protection Solution

    For an adequate protection against earth faults

    ABB SACE has designed the following product

    categories:

    Moulded case circuit breaker

    RC221 residual current devices

    RC222 residual caurrent devices

    RC223 residual current devices

    Electronic release LSIG: PR222, PR223

    Electronic release LSIG: PR331, PR332

    Electronic release LSIRc: PR332

    Description

  • Moulded case circuit breaker

    Residual current devices RC221, RC222, RC223

    Protection Solution

  • Protection Solution

    Moulded case circuit breaker

    Electronic releases LSIG:

    PR222: T2, T4, T5, T6

    PR223: T4, T5, T6

    PR331, PR332: T7

    G function setting

    I4= 0.2..1 x In

    t4= 0.1.0.8 x In con I2t=k o t=k

    (depending by the type of

    release)

  • Protection Solution

    G function:

    currently used in MV/LV transformer substations to protect both transformers as well as distribution lines

    guarantees selectivity with regard to the residual current releases located on the load side

    can be used for protection against indirect contact, when allowed by the installation conditions

    improve protection against earth faults with regard to the normal phase protections

  • Protection Solution

    Moulded case circuit breaker

    Electronic release PR332 LSIRc for T7

  • Protection Solution

    Moulded case circuit breaker

    Summary table

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories:

    Air circuit breakers

    Electronic releases LSIG: PR331, PR332, PR333

    Electronic release LSIG: PR121, PR122, PR123

    Electronic release LSIRc: PR332

    Electronic release LSIRc: PR122

    Description

  • Protection Solution

    G function setting

    I4= 0.2..1 x In

    t4= 0.1.0.8 x In con I2t=k o t=k

    (depending by the releases)

    For an adequate protection against earth faults

    ABB has designed the following product

    categories:

    Air circuit breakers

    Electronic releases LSIG: PR331, PR332, PR333

    Electronic releases LSIG: PR121, PR122, PR123

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories:

    Air circuit breaker

    Electronic releases LSIRc: PR332

    Electronic releases LSIRc: PR122

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories

    Residual current relay with external trasformer

    SACE RCQ switchboard electronic residual current relay

    Residual current relay for DIN rail: RD2 & RD3

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories

    Residual current relay with external trasformer

    SACE RCQ switchboard electronic residual current relay

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories

    Residual current relay for DIN rail: RD2

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories

    Residual current relay for DIN rail: RD3

  • Protection Solution

    For an adequate protection against earth faults

    ABB has designed the following product

    categories

    Front panel residual current relay: ELR

  • Two types of residual current discrimination

    horizontal residual current discrimination

    vertical residual current discrimination

    Discrimination of the protections against earth fault

  • To ensure discrimination

    for residual current CBs type S located on the supply side (in compliance with Standards IEC 61008-1 and IEC 61009)

    downstream non-selective residual current CBs having In three times lower

    for residual current electronic releases (RC 221/222/223, RCQ and RD2)

    tripping times and currents of the device on the supply side are immediately higher than those of the device on the load side

    Discrimination of the protections against earth fault

  • Example

    E1N 1250 PR121/P-LSIG In=1250A 4p

    T5N 400 PR222DS/P-LSI In =400A con RC222

    T1B 160 TMD In=160A con RC221

    Discrimination of the protections against earth fault

  • Example

    Discrimination of the protections against earth fault

  • Domestic Installation (TT)

    Application of RCD

    IdRCCB

    MCB Load

    MCB Load

  • Industrial installation (TN-S)

    long cables

    CB+RC Id

    Application of RCD

  • Protection function G or residual current protection?

    the choice can be done taking in consideration:

    the distribution system

    the value of the fault current

    RCD:

    particularly suitable for protection of people

    absolutely necessary

    in TT systems (small fault current to earth)

    earthing of the exposed-conductive-parts is deficient

    normal protections are not sufficient to provide protection that falls within the limits set by the Standards

    dangerous environmental conditions (e.g. excessive humidity)

    Application of RCD

  • G function:

    currently used in MV/LV transformer substations to protect both transformers as well as distribution lines

    guarantees selectivity with regard to the residual current releases located on the load side

    can be used for protection against indirect contact, when allowed by the installation conditions

    improve protection against earth faults with regard to the normal phase protections

    Application of RCD

  • Typical application:

    all types of construction sites (building, naval, etc.)

    mobile equipment or plants

    hospital environments and operating rooms

    excavations and mines

    campground electric installations

    pools, saunas, canteens and, generally, environments with high humidity levels

    aquarium and fountain lighting

    agricultural premises

    school laboratories

    Application of RCD