cired2005_0447
TRANSCRIPT
-
7/30/2019 cired2005_0447
1/6
CIRED2005
Session No 5
OPTIMAL PLACEMENT OF STATIC VAR COMPENSATORS IN
DISTRIBUTION FEEDERS FOR LOAD BALANCING BY GENETIC
ALGORITHM
M. A. Talebi, A. Kazemi, A. Gholami M. Rajabi
Iran University of Science and Technology Tehran South West Electrical Distribution Company
Abstract:
Unbalanced load is one of the fashionable problems in
distribution systems, which has great unfavorable effects such
as unbalancing in three phase voltages, increase of energy
losses and occupation of feeder capacity. There are two main
sources of unbalanced load, the first ununifored distribution
of the single phase customers and the other, their accidental
and unsimultaneous treatment. For reform load unbalancing
particularly ununiforedness of customers used traditional
methods of customer replacement. But nowadays there is a
novel method that we can balance the load by the reactive
power compensation. Unbalanced load in distribution feeders
has two main features, 1) unbalancing rate is variable
according to the time, 2) it would be dispersion among the
feeder. We can use Static VAR Compensator (SVCs) and so
they will be able to reform this unbalancing according the
specific period of time variation. Therefore if we want to
reform the load unbalancing, according to its dispersion
characteristic, we can use some SVCs among the feeder. In
this paper used an optimal method based on genetic algorithm
for SVCs placement among the feeder for load balancing
during a specific period of time. In addition with this method
a novel algorithm has been used which make a hierarchy of
the priorities in considering the buses. At last, the unbalancetreatment of some real samples of the feeders were studied by
using prepared software which have been done during a week
and effect of SVCs application have been simulated too. The
results of simulation studies show that by using optimally the
SVCs in distribution feeders we can balance the load current
and we are able to decrease considerably unfavorable effects.
Financial analysis shows that this method is optimum from
economical point of view.1-IntroductionUnbalanced loads in distribution system cause many
deficiencies. Actually, amount of load unbalancing
concerned as electrical energy quality index. Ununifored
distribution of the single phase customers among the phases
and accidental and unsimultaneous treatments of the
consumers are the main origins of unbalancing in the low
voltage distribution systems .The main disadvantages of
unbalancing in distribution systems are as follows:
Unbalanced three phase voltage: in spite of balanced
voltage at the beginning of feeder, unbalanced load destroy
voltage profile balancing. The problem disorders in
operation of many consumers, such as induction motor and
reduces their efficiency with heat increment.
Electrical loss increment: it is known that minimum loss in
electrical power transmission requires balanced three phase
currents. Furthermore, in unbalanced state, neutral return
current, intensify the feeder resistive loss in null conductor
and increase copper and iron losses in distribution
transformers.
Network capacity occupancy: in unbalanced load the phase
currents are unequal and one of the amplitudes is bigger
than the others. The maximum capacity of substation or
feeder is based on maximum phase current. Therefore, the
capacity is occupied in spite of free capacity in some
phases.
Null voltages: the return neutral current provides voltage
difference in different points of feeder between earth and
null. This difference depends to neutral current amplitude
and impedance of null conductor which that increases some
phase voltage and decreases others to null.
Accidental and unsimultaneous treatments of consumers
provide dynamic and variable according to the time nature
for load unbalancing. Therefore, load balancing necessitates
a method that determines unbalancing per time and reduces
it to desirable amount. Reactive power compensating is a
suitable process for load balancing that also can improves
load factor.
2-Load balancing with reactive power control [1, 2]
Because one of the unbalanced three phase current
properties is negative and zero component in symmetrical
components, load balancing is based on negative and zero
component elimination. Reactive power compensation
performance is shown with conceptual diagram in fig. 1.
According fig. 1, three phase current and voltage phasors
have measured instantly (on-line) with compensators
sensors and with processing their by compensators
controller, negative and zero components of load current
have determined. Then the compensator has controlled to
inject the same amount of negative and zero components
with 180 degree phase difference to the bus. Its
performance omits and neutralizes the negative and zero
current components and balances the three phase current.
Also the proper control of imaginary part of positive
component, the compensator control and regulate the power
factor of feeder load current. The mentioned procedure can
be applied in specified intervals (e.g. every one hour).
2-1-Load balancing algorithm [1, 2]
Star and delta reactive power compensators are used with
-
7/30/2019 cired2005_0447
2/6
CIRED2005
Session No 5
balancing algorithm. The star compensator is applied to
eliminate the current zero component and control imaginary
part of positive component. The delta type is used for
negative component elimination.
Three phase four wires feeder equipped by both star and delta
compensator is shown in figure 2. The connected load to the
feeder is equal to a composed load and modeled in
compensation node, where:
Vns,Vc
s,Vb
s,Va
s: null and phase voltage at the beginning of
the feeder
GcL,Gb
L,Ga
L: the equal conductance of unbalance load.
BaL,Bb
L,Bc
L: the equal susceptance of unbalance load.
BaY,Bb
Y,Bc
Y: star compensator susceptances.
Bca,Bbc
,Bab: delta compensator susceptances.
The feeder node voltages to derive the equations and
control algorithm are considered as follows:
,VVLar
= ,VaV 2Lbr
= VaVLcr
=
,0VV =r
2
3j
2
1ea 3/2j +== (1)
According to load balance importance in network steady
state behavior, phasor quantities can be used in studies and
analysis. Although feeder's load is compound and time
variant, but they can be modeled by impedance or
admittance load instantly:
)sinj(cosV
IjBGY
)sinj(cosV
IjBGY
)sinj(cosV
IjBGY
ccLc
LcL
cLc
Lc
bbLb
LbL
bLb
Lb
aaLa
LaL
aLa
La
=+=
=+=
=+=
(2)
VL
and IL
are phasor quantities of phase voltage and
current, respectively. Symmetric load current componentsin terms of load admittance are as follows:
( ) ( )[ ]( ) ( )[ ]( ) ( )[ ] 3/BaaBBjGaaGGVI
3/BBBjGGGVI
3/aBBaBjaGGaGVI
Lc
2Lb
La
Lc
2Lb
La
L0
Lc
Lb
La
Lc
Lb
La
L
Lc
Lb
2La
Lc
Lb
2La
L0
+++++=
+++++=
+++++=
+ (3)
Negative and zero current components produce as load
inequality and consequently its admittance in different
phases. Three phase current of compensators in terms of
susceptance are calculated as follows:
( )( )( )V.aBBaBaBjI
V.BaBaBBajIV.BaBBaBjI
aVjBVjBI
VajBVjBI
VjBVjBI
bcbc2
cacac
ab2
abbcbc2
b
cacaab2
aba
Yc
Lc
Yc
Yc
2Yb
Lb
Yb
Yb
Ya
La
Ya
Ya
+=
+=+=
==
==
==
(4)
Symmetric current components of compensators are
calculated as follows:
Fig (1): Conceptual diagram of reactive power compensation.
( )( )
( )
( )( )
cabcab2
cabcab
0
Yc
2Yb
Ya
Y
Yc
Yb
Ya
Y
Yc
Yb
2Ya
Y0
aBBBajVI
BBBjVI
0I3/BaaBBjVI
3/BBBjVI
3/aBBaBjVI
++=
++=
=++=
++=
++=
+
+
(5)
Load balancing by star and delta compensators necessitates
neutralization zero and negative current components:
0III YL =++ (6)
0III 0Y0
L0 =++
(7)
Power factor can be regulated to desirable amount by
positive component control. The following equation should
be satisfied for this reason:
( ) ( )( )PFkIIIkIII
f
YL
f
YL
1costan
ReIm
+++
+++
=
++=++(8)
Where:
PF is desirable amount of power factor.
Considering equation (8) as well as (6), (7) real- imaginary
parts separation, five equations obtained for susceptance
calculation, but another equation is required to satisfy the
equations(compensator's suscepatance).Sixth
equation is
additional condition to set and control the compensators
based on their natural behavior. If the imaginary part just
controlled by star compensator, the sixth equation is as
follows:
0=++
cabcab
BBB (9)
Having solved (6)-(9), the compensators amounts are as
follows:
( )
( )
( )LaLcca
L
c
L
bbc
L
b
L
aab
L
b
fL
a
fL
c
fL
c
Y
c
L
a
fL
c
fL
b
fL
b
Y
b
L
c
fL
b
fL
a
fL
a
Y
a
GGB
GGB
GGB
Gk
Gk
Gk
BB
Gk
Gk
Gk
BB
Gk
Gk
Gk
BB
=
=
=
+
+++=
+
+++=
+
+++=
33
2
33
2
33
2
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
(10)
-
7/30/2019 cired2005_0447
3/6
CIRED2005
Session No 5
Fig (2): Three phase feeder equipped by star and delta compensator.
Therefore, compensators susceptances can be set to
neutralize the unbalanced load with on-line measurement ofvoltage-currents phasors, the power factors and load
balanced admittances. Therefore, with current and voltage
phasors sampling each time, compensators susceptances
can be set to load current balancing and power factor
regulating at any node of the feeder.
2-2-Application principles of the compensators [2, 4]
According to the previous parts, feeder load balancing
process can be performed by SVC. Sometimes more than
one SVC is required, so the appropriate load balancing
necessitate a specific performance sequence. Respect to 2-
1, SVC on each bus balance input current of this bus. In
load balancing with reactive power compensation, phase
current unbalancing is measured every 30 minutes or onehour then based on the measured data as well as algorithm,
reactive power injects to balance the currents.
Assume a situation with two SVC installed on a feeder
(figure 3). If compensator No.1 performs faster that No.2,
balancing failed. In figure 3, if compensator No.1 performs
faster, this compensator balances input current of bus No. 1
that consist of buses No. 4,5,7,8,9 and 10 load currents. But
input current of bus No. 6 is unbalanced yet. Then by
performance compensator No. 2, input current of bus No. 6
is balanced (consist of load currents of buses No. 7 and 8).
In fact the required reactive power for balancing load
currents of buses No. 7 and 8 injected to the feeder twice.
But if compensator No. 2 performs faster, this compensator
balances input current of bus No. 6 that consists of loadcurrents of buses No. 7 and 8. Then by performance
compensator No. 1, input current of bus No. 1 is balanced.
In this state, only required reactive power for balancing
load currents of buses No. 4, 5, 9 and 10 injected to the bus
No. 1. Generally, appropriate compensation needs faster
performance in compensator 2 than 1.
In this case, it is simple to distinguish the sequence, but
greater network require classification algorithm.
Classification algorithm is used in radial and multi radial
networks and each bus classified. Connected bus to
substation called No. 1 and classified in zero bunch. The
others classified as follows:
ith bus bunch = bunch of bus that ith bus fed from it + 1.
In other word, bus bunch is the number of branchesbetween ith bus and the bus No. 1. The bus classified
descendingly based on their bunch numbers. The sequence
presents their performance turn. Compensators in higher
rank of classification perform faster than then lower ones.
The algorithm applied on multi radial network (figure 4)
and the results are as follows:
[27 26 25 24 19 18 23 22 17 16 12 8 21 15 11 7 20 14 10 6 13 9 5 4 3 2 1]
Fig (3): Three phase feeder equipped by two compensators.
3-Optimal balancing and compensation in distribution
feeders
Low voltage feeders are the main origin of unbalancing in
power systems and there are the best places to apply
compensation for load balancing. Actually unbalancing in
low voltage feeders has two properties: 1) time variant
intense, 2) inequality dispersion in feeder. Therefore, the
balancing should be performed based on these properties.
The second property necessitates compensator in more than
on point of feeder. Obviously, compensation based on
unbalanced load balancing is a suitable approach, called
perfect-ideal balancing. But, technical-economical
considerations make this unfeasible. So, compensator
application on some feeder buses, called partial or non-
ideal compensation is an applicable approach.
The second choice requires optimal quantity of
compensators as well as their placement. Each
compensation process has three effective components (as
follows), so the most appropriate design is unique way.
1) technical-operational improvement considering feeder
voltage profile and its balancing.
2) Saving with loss reduction and free capacity provision.
3) Compensator application cost
The best compensation choice is a process which optimizes
and coordinates the above issues.
4- Feeder balancing algorithm and optimization
principle [2]
Each optimization process intends to minimize or maximize
definite objective(s). Therefore, objective definition is the
first step in optimize balancing.
In this paper the objective for optimal compensator
placement is defined based on (2) and (3). But, applied
constraints to provide the technical performance
considering voltage profile and unbalancing. The defined
objective function is as follows:
=
+=
t
1i
RCRCmaxSLi
lossWL CNSCWhCf (11)
Where:
CWL: economical cost of electrical energy loss in Rial/KWh
W: total electrical energy loss in feeder in balanced state
to unbalanced state in Ith time.
t: consumed time of assessment.h: conversion coefficients of achieved economic value to
the present value, considering profit rate and inflation
CSL: economic value of released feeder capacity and
balancing in terms of Rial / KVA.
I II III
IV
V
VI
VII VIII
-
7/30/2019 cired2005_0447
4/6
CIRED2005
Session No 5
Fig (4): Classification algorithm for radial and multi radial networks.
Smax: balanced state feeder's released capacity to theunbalanced state in KVA
CRC: purchase, install and maintenance cost of a
compensator in Rial
Voltage unbalancing index is as follows:
{ }ijcnijbnijanijmax
ijcn
ij
bnij
anijavr
t
1i
n
1jij
avr
ijavr
ijmax
V
V,V,VmaxV3
VVVV
V
VV
n
1
t
1U
=
++=
=
= =
(12)
Where: ijcnij
bnij
an V,V,V are a,b and c phase voltage amplitude to
null in p.u for ith time and jth bus, n is bus amount and tisthe simulation period.
Voltage diversion profile index in kth phase defines as
follows (kcan be a, b or c):
= =
=
t
1i
n
1j
2ij
knk )V1(n
1
t
1VI (13)
Constraints are as follows:
maxc
maxb
maxa
maxVV
VIVI,VIVI,VIVI
UU
(14)
Now, the problem is to maximize (11) under (14)
constraints with appropriate compensation design (their
placement and amount). In this paper, genetic algorithm isused as an optimization process.
4-1-Optimization algorithm [2]
Genetic algorithm is a random-statistical research technique
to access maximum or minimum point of objective
function. According to its simulation capability, it is
efficient in complicate and multipurpose problems. The
principle is based on genetic systems of creatures and the
following calculation process:
-Each answer codifies as variable set, known as a
chromosome.
-Selection of chromosomes as new (basic) population.
-Value function calculation for each chromosome, known
as chromosome fitness.-Genetic operator application with specified probabilities.
-Convergence check and decision making to finish or
continue the algorithm.
In this paper each chromosome consists of a string with the
genes equal to feeder buses. Gene values set as 0, 1 those
represent presence or absence of compensator related bus,
respectively.
5-Load balancing software
MATLAB platform software is provided to simulate
unbalanced load in distribution feeder in specified period,
algorithm application and of compensator optimal
placement determination. The simulation is based on the
measured data at the beginning of the feeder with
unbalanced load flow as well as bus voltage, branch
current, energy loss, occupied capacity and unbalanced
load characteristics calculation. Also, it can simulate star-
delta compensator performance or their combination as
well as their effects on feeder behavior and operation. The
software specifies the optimal placement of reactive power
compensator by genetic algorithm.
6-Simulation study
A low voltage feeder in Tehran South West Electrical
Distribution Company is chosen as an example to apply
simulation. Single diagram of the feeder is shown in
figure(4). The feeder contain 27 buses with 40, 38, 38
participates on phase a, b and c, respectively.
The feeder performance and operation is simulated for 48
hours. Feeder performance is assessed by the software in
the following states:
-Unbalanced load without balancing-Unbalanced load with perfect and ideal balancing
-Unbalanced load with optimal balancing
Table (1): Unbalanced load without balancing
A. unbalanced load without balancing: in this state no
reactive power compensator is installed on buses. The
results for 48 hours are shown in table (1). The occupied
capacity in each phase based on maximum power (kVA) in
168 hour is achieved by simulation. It is the maximumvalue among the three phases as occupied capacity. It can
be seen that, occupied feeder capacity is 3*83.72=251.16
kVA and only 79% used for power transition.
B. unbalance loads with ideal and perfect compensation:Reactive power compensators are installed at all the
unbalanced buses. The results for 168 hour period are
shown in table (2). It can be seen current-voltage
unbalancing is eliminated. The voltage diversion profile is
reduced and balanced in each phase. Comparing A state,
resistive loss reduced 54% and 50% of the occupied
Phase A Phase B Phase C Null
Energy Losses (kWh) 58.34 184.67 127.93 36.11
Occupied Capacity(kVA) 45.97 83.72 65.66 -
Voltage Index (VI) 4.9e-4 1.0e-2 5.8e-3 -
Unbalancing indexUv
4.78 %
Table (2): Unbalanced load with perfect and ideal balancing
Phase A Phase B Phase C Null
Energy Losses (kWh) 62.31 62.31 127.93 0
Occupied Capacity(kVA) 41.55 41.55 41.55 -
Voltage Index (VI) 1.6e-3 1.6e-3 1.6e-3 -Unbalancing indexU
v 0
Table (3): Unbalanced load with optimal balancingPhase A Phase B Phase C Null
Energy Losses (kWh) 61.87 74.14 70.06 3.43
Occupied Capacity(kVA) 41.85 41.85 41.85 -
Voltage Index (VI) 1.4e-3 2.0e-3 1.9e-3 -
Unbalancing indexUv
0.40 %
-
7/30/2019 cired2005_0447
5/6
CIRED2005
Session No 5
capacity released.
C. unbalanced load with optimal compensation:According to the optimal calculations of genetic algorithm,
three buses (No. 4, 6, 8) are recommended for optimal
installation. The results are shown in table (3). Feeder
resistive loss reduced 48.5% and occupied feeder capacity
released 50% comparing state A.
Figure (5): Profile of three phase voltages at the 12th bus of feeder
Having compared state c and b, in spite of using 3 buses
instead 15, no significant changes happened in feeder loss
reduction or occupied capacity, 89.8% and 99.3% of state
b, respectively. Also, the compensators reduced 0.80. But,
voltage diversion profile, unbalancing characteristics and
feeder current improved significantly than state A.
It can be seen, optimal compensation effects significantly
on voltage, loss and capacity release performance of low
voltage feeders. Time profile situation of three phase
currents at the beginning of feeder and time profile
situation of three phase voltages at the 12th
bus are shown
in figures 5 and 6 as an example for A, B and C states in 48
hours.
7-Concluion
The simulation results using the software for typical feeders
represent the optimal efficiency in unbalanced load
modification, energy loss reduction, network capacity
emptying and voltage profile improvement. The followings
results are achieved:
-Unbalanced load and its power factor can be modified
desirably by reactive power compensation.
-Genetic algorithm is an effective way to optimal placement
of compensators in distribution feeders. Load balancing
with a few compensators, modify unbalancing.
-The optimal amount of reactive power compensators are
achieve 3 or 4. Note that more that apply no significant
difference in addition to cost increment.
Figure (6): Profile of three phase currents at the beginning of feeder
References:
[1] M. R. Aghamohammadi; M.A. Talebi and M. Rajabi,
2004, "Optimal load balancing by reactive power
compensation in distribution feeders", International Power
Systems conference, Tehran.
[2] M.A. Talebi, 2003, "Optimal placement of reactive power
compensators for load balancing and power factor
correction by genetic algorithm", B. S. Thesis, Power and
Water Institute of Technology.
[3] S. Y. Lee and C. J. Wu., 2000, Reactive power
compensation and load balancing for unbalanced three
phase four wire system by an SVC, IEE Proc. Electr.Power, Vol. 147, No. 6, pp 563-570.
[4] Jen-Hung Chen; Wei-Jen Lee; Mo-Shing Chen, 1999,
Using a static VAR compensator to balance a
distribution system, Industry Applications, IEEE
Transactions on Power Systems , Vol. 35 , pp 298 304.
[5] Singh, B.; Saxena, A.; Kothari, D.P,1998, Power factor
correction and load balancing in three-phase distribution
systems, 1998 IEEE Region 10 International Conference
on Global Connectivity in Energy, Computer,
Perfect and ideal balancing
Optimal compensation
Unbalanced load without balancing
Perfect balancing
Optimal compensation
Unbalanced load without balancing
-
7/30/2019 cired2005_0447
6/6
CIRED2005
Session No 5
Communication and Control , Volume: 2.