City of Yankton, SD 2014 Water Treatment Plant Improvements Horizontal Collector Well

Construction Documents Project Manual

VOLUME 2 OF 3

ISSUED For Bids

October 8, 2014

City Project No. ES14-5 HDR Project No. 135-223788-003

Page 2: City of Yankton, SD
Page 3: City of Yankton, SD

CITY OF YANKTON

SOUTH DAKOTA

PROJECT MANUAL

SPECIFICATIONS AND BID FORM

FOR

2014 Water Treatment Plant Improvements Horizontal Collector Well

HDR Project No. 223788 City of Yankton Project No. ES14-5

CITY OF YANKTON, OWNER PO BOX 176

YANKTON, SOUTH DAKOTA 57078

ENGINEER HDR Engineering, Inc.

6300 S. Old Village Place Sioux Falls, SD 57108

Page 4: City of Yankton, SD
Page 5: City of Yankton, SD

\\\\\UI Ill 1111 '''~ESS I ,,,,.

~''\ ~- II ~,~

~~ ·········'Clt,;.~· ~ ~ 1~<:('; A1 < -v,~ ~ .•• ~·'YO. •.. ~ ~ .· ·. : - 0) • 11048 .......... § ia f STEVEN J. i ifi E : !t ~ QUAL : 5Y : -:: ··~~~.. :: ~ •• •• $' ~ ... ..· ~ ~ ··•····•· ~ ~,,,. ,,~ .,,,, \,, ... ,,,,, ... "''\

SEALS AND SIGNATURES

I hereby certify that the portion of this teclmical submission described below was prepared by me or under my direct supervision and that I am a Registered Professional Engineer under the laws of the State of South Dakota.,. ~} _ //

/J~.:-~* ;;R-t:a~r (Steveng Q'uail)

My license renewal date is.September 30, 2015

Pages or sheets covered by this seal:

fDa

Bidding Documents, Contract Documents, and Contract Conditions .

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and that I am a Registered Professional Engineer under the laws of the State of South Dakota.

1(~ ;C 11~~ /o/8/Jf (Kevin F. Newman)

My license renewal date is September 30, 2016

Pages or sheets covered by this seal:

Date

Division 02 and Sections 01010, 01020,01060, 01060A, 01062, 01105, 01200,01320,01340,01342,01560,01600,01601,01640,01650, 01710,01800,11005,11060,11072,13200,15060,15061,15062, 15064, 15090, 15100, 15100A, 15101, 15103, 15104, 15106, 15114, and 15510

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and that I am a Registered Professional Engineer under the laws of the State of South

1 ta (~ (Davidfl-..s 4

My license renewal date is May 31, 2016

Pages or sheets covered by this seal:

Sections 13440, 13440A, 1344GB, 13440C, 13440D, 13440E, 13440F, 13441, 13442, 13446, 13447, 13448, 13449, 13500, 13502, and 13504.

Page 6: City of Yankton, SD

''''''" ,,,,,, ,,, ,,, ,,,,, 'R--orESS lOA, ... '",,.,. ~ ~ ••••••• r "Y/ ~ ..... ~ OO G 00 ~ "" ~ •• 0 ~v . tvo 0.. ~ --:. ' . ' . . ,_

::: : 8073 °o t1 -:. § ,...: i JOHN S. ~ :I: ~ _CI), ·--= - ~ RICKERT : -; = - (.!) 0 • [17 -

~ ~ \ -5;~ 0~~ ..- 9 § .; • \ I' • 7 ' ~ ·•.. D~'r:. ··· ~ ~ ······· ~ ........ ,, ,, ,, ,,, ,,,

,,,,,,,,,,,,,,,,,

,,, ........ ,., ,,, ,,1, ,,,.. ~?.O~ ESS!o~ ,,,,

........ ~ •••• •• • 'Jf( ,r. ,,, ' ;~ .. .. ~:, , .:0 ~ .• ~tG. No •.. "k 0:..

:: {::j • • • • • ~ -:, .. ,.. . . -;.;. " :: &t1 • 7218 • ro "' - Cl:::: : • !"'"' p : i KEVIN K. ! ::a : ; ~ THERNES ! E ~ . . : "" ·· lf'o ~'t- .• :-~ • •• urH or>:o~ .. o... ~ ~~ ·········· ...... .. ,, ... ... ,, A ,,

~~,,, w "''' '"''"'"'''

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and that I am a Registered Professional Engineer under the laws of the State of South

6 .~J--o,ko~ rA . (Jefid~ ,

My license renewal date is September 30, 2015

Pages or sheets covered by this seal:

l>ate

Sections 11077, 15183, 15515, 15605, 15710, 15890, 15970, and 15990.

(Keith R. Kirchner)

My license renewal date is November 30, 2015

Pages or sheets covered by this seal:

' Date

Sections 01452, 01452A, 01452B, 03108, 03208, 03308, 03311, 03350, 05505 and 13200.

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and that I am a Re · red Professional chitect under the laws of the State of South Dako /

license renewal date is July 31, 2015

Pages or sheets covered by this seal:

I IJ • tJB . 'ltJ Date

Divisions 04, 06, 07, 08, and 09 and Sections 03348, 05522, 10200, 10400, 10444, 10520 and 10530.

I hereby certify that the portion of this technical submission described below was prepared by me or under my direct supervision and that I am a Registered Professional Engineer under the laws of the State of South

Dg ota. , 1]:;£ J.AMo ~ ' ~

(Kevin K. Themes)

My license renewal date is December 31,2014

Pages or sheets covered by this seal:

Division 16.

16/ K/14= Dl te 1

Page 7: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - Table of Contents - 1

2014/10/02

Table of Contents

VOLUME 1 OF 3

BIDDING DOCUMENTS

ADVERTISEMENT INSTRUCTION TO BIDDERS PROPOSAL FORM - DBE SUBCONTRACTOR SOLICITATION INFORMATION (DBE-6) - EPA DBE SUBCONTRACTOR PERFORMANCE FORM (EPA FORM 6100-3) - EPA DBE SUBCONTRACTOR UTILIZATION FORM (EPA FORM 6100-4) - CERTIFICATION REGARDING DEBARMENT, SUSPENSION AND OTHER

RESPONSIBILITY MATTERS (DEBAR-2) BID BOND BIDDERS STATEMENT OF QUALIFICATIONS

CONTRACT DOCUMENTS

NOTICE OF AWARD AGREEMENT PAYMENT BOND PERFORMANCE BOND NOTICE TO PROCEED CHANGE ORDER WAIVER AND RELEASE OF LEIN GENERAL CONDITIONS STATE REVOLVING FUND (SRF) GENERAL CONTDITIONS DAVIS BACON GENERAL DECISION NUMBER: SD140005 01/03/2014

CONTRACT CONDITIONS

SUPPLEMENTAL GENERAL CONDITIONS

TECHNICAL SPECIFICATIONS

DIVISION 01 - GENERAL REQUIREMENTS

01010 SUMMARY OF WORK 01020 MEASUREMENT AND PAYMENT 01060 SPECIAL CONDITIONS 01060A PROJECT SIGN 01062 MAJOR EQUIPMENT SUPPLIERS 01105 STORM WATER POLLUTION PREVENTION PLAN 01200 REQUESTS FOR INFORMATION (RFI) 01320 CONSTRUCTION PROGRESS SCHEDULE 01340 SUBMITTALS 01342 OPERATION AND MAINTENANCE MANUALS 01452 SPECIAL INSPECTIONS AND TESTING PROGRAM 01452A STATEMENT OF SPECIAL INSPECTIONS 01452B SPECIAL INSPECTIONS, INSPECTOR QUALIFICATIONS AND REPORTING

REQUIREMENTS 01560 ENVIRONMENTAL PROTECTION AND SPECIAL CONTROLS 01600 PRODUCT DELIVERY, STORAGE, AND HANDLING

Page 8: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - Table of Contents - 2

01601 JOB CONDITIONS 01640 PRODUCT SUBSTITUTIONS 01650 FACILITY START-UP 01710 CLEANING 01800 OPENINGS AND PENETRATIONS IN CONSTRUCTION

DIVISION 02 - SITE WORK

02110 SITE CLEARING 02200 EARTHWORK 02221 TRENCHING, BACKFILLING, AND COMPACTING FOR UTILITIES 02260 TOPSOILING AND FINISHED GRADING 02270 SOIL EROSION AND SEDIMENT CONTROL 02444 CHAIN LINK FENCE AND GATES 02510 AGGREGATE SURFACING 02515 PRECAST CONCRETE MANHOLE STRUCTURES 02660 WATER MAIN CONSTRUCTION 02778 GEOTEXTILES 02930 SEEDING, SODDING AND LANDSCAPING

DIVISION 03 - CONCRETE

03108 FORMWORK 03208 REINFORCEMENT 03308 CONCRETE, MATERIALS AND PROPORTIONING 03311 CONCRETE MIXING, PLACING, JOINTING, AND CURING 03348 CONCRETE FINISHING AND REPAIR OF SURFACE DEFECTS 03350 CONCRETE TESTING

DIVISION 04 - MASONRY

04050 COLD AND HOT WEATHER MASONRY CONSTRUCTION 04110 MASONRY MORTAR AND GROUT 04155 MASONRY ACCESSORIES 04210 BRICK MASONRY 04220 CONCRETE MASONRY 04510 MASONRY CLEANING

DIVISION 05 - METALS

05505 METAL FABRICATIONS 05522 ALUMINUM RAILINGS

DIVISION 06 - WOOD AND PLASTICS

06100 ROUGH CARPENTRY

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07176 LIQUID WATER REPELLENT 07210 BUILDING INSULATION 07215 SPRAYED POLYURETHANE INSULATION 07534 ADHERED ELASTOMERIC (EPDM) SHEET ROOFING 07600 FLASHING AND SHEET METAL 07720 ROOF HATCHES 07900 JOINT SEALANTS

Page 9: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - Table of Contents - 3

DIVISION 08 - DOORS AND WINDOWS

08120 ALUMINUM DOORS AND FRAMES 08305 ACCESS DOORS 08410 STOREFRONT 08700 FINISH HARDWARE 08800 GLASS AND GLAZING

VOLUME 2 OF 3

DIVISION 09 - FINISHES

09905 PAINTING AND PROTECTIVE COATINGS

DIVISION 10 - SPECIALTIES

10200 LOUVERS AND VENTS 10400 IDENTIFICATION DEVICES 10444 SIGNAGE 10520 FIRE EXTINGUISHER 10530 ALUMINUM CANOPIES

DIVISION 11 - EQUIPMENT

11005 EQUIPMENT: BASIC REQUIREMENTS 11060 PUMPING EQUIPMENT: BASIC REQUIREMENTS 11072 PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11077 PUMPING EQUIPMENT: INLINE CENTRIFUGAL PUMPS

DIVISION 13 - SPECIAL CONSTRUCTION

13200 HORIZONTAL COLLECTOR WELL 13440 INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440A LOOP CHECK-OUT SHEET EXAMPLE 13440B LOOP CHECK-OUT SHEET 13440C INSTRUMENT CERTIFICATION SHEET EXAMPLE 13440D INSTRUMENT CERTIFICATION SHEET 13440E FINAL CONTROL ELEMENT CERTIFICATION SHEET EXAMPLE 13440F FINAL CONTROL ELEMENT CERTIFICATION SHEET 13441 CONTROL LOOP DESCRIPTIONS 13442 PRIMARY METERS AND TRANSMITTERS 13446 CONTROL AUXILIARIES 13447 TELEMETRY SYSTEMS 13448 CONTROL PANELS AND ENCLOSURES 13449 SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION

AND CONTROL EQUIPMENT 13500 PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13502 COMPUTER NETWORK AND HUMAN MACHINE INTERFACE (HMI)

HARDWARE 13504 CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI)

AND REPORTS

Page 10: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - Table of Contents - 4

DIVISION 15 - MECHANICAL

15060 PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15061 PIPE: STEEL 15062 PIPE: DUCTILE 15064 PIPE: PLASTIC 15090 PIPE SUPPORT SYSTEMS 15100 VALVES: BASIC REQUIREMENTS 15100A VALVE SCHEDULE 15101 GATE VALVES 15103 BUTTERFLY VALVES 15104 BALL VALVES 15106 CHECK VALVES 15114 MISCELLANEOUS VALVES 15183 PIPE, DUCT AND EQUIPMENT INSULATION 15510 FIRE HYDRANT 15515 HYDRONIC SPECIALTIES 15605 HVAC: EQUIPMENT 15710 HEAT EXCHANGERS AND CONVERTERS 15890 HVAC: DUCTWORK 15970 INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15990 HVAC SYSTEMS: BALANCING AND TESTING

DIVISION 16 - ELECTRICAL

16010 ELECTRICAL: BASIC REQUIREMENTS 16060 GROUNDING 16080 ACCEPTANCE TESTING 16120 WIRE AND CABLE: 600 VOLT AND BELOW 16130 RACEWAYS AND BOXES 16132 CABLE TRAY 16135 ELECTRICAL: EXTERIOR UNDERGROUND 16140 WIRING DEVICES 16230 ENGINE GENERATOR: DIESEL 16265 VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16343 TERMINAL CABINETS 16410 SAFETY SWITCHES 16411 TRANSFER SWITCHES 16412 SEPARATELY MOUNTED CIRCUIT BREAKERS 16440 SWITCHBOARDS 16441 PANELBOARDS 16442 MOTOR CONTROL EQUIPMENT 16460 DRY-TYPE TRANSFORMERS 16490 OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES 16491 LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16493 CONTROL EQUIPMENT ACCESSORIES 16500 INTERIOR AND EXTERIOR LIGHTING

VOLUME 3 OF 3

APPENDIX A - COLLECTOR WELL SITING STUDY AT PADDLEWHEEL POINT

APPENDIX B - GENERAL PERMIT FOR TEMPORARY DISCHARGE ACTIVITIES (SDG071106)

APPENDIX C - GENERAL PERMIT FOR STORMWATER DISCHARGE ASSOCIATED WITH CONSTRUCTION ACTIVITIES (SDR10G804)

Page 11: City of Yankton, SD

T E C H N I C A L S P E C I F I C A T I O N S

Page 12: City of Yankton, SD
Page 13: City of Yankton, SD

D I V I S I O N 0 9 FINISHES

Page 14: City of Yankton, SD
Page 15: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 1

2014/10/07 1

SECTION 09905 2

PAINTING AND PROTECTIVE COATINGS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. High performance industrial coatings (HPIC). 7 2. Any other coating, thinner, accelerator, inhibitor, etc., specified or required as part of a 8

complete System specified in this Specification Section. 9 3. Minimum surface preparation requirements. 10

B. Related Specification Sections include but are not necessarily limited to: 11 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 12 2. Division 01 - General Requirements. 13 3. Section 03348 - Concrete Finishing and Repair of Surface Defects. 14 4. Section 04220 - Concrete Masonry. 15 5. Section 05505 - Metal Fabrications. 16 6. Section 10400 - Identification Devices. 17 7. Section 11005 - Equipment: Basic Requirements. 18

1.2 QUALITY ASSURANCE 19

A. Referenced Standards: 20 1. ASTM International (ASTM): 21

a. D4258, Standard Practice for Surface Cleaning Concrete for Coating. 22 b. D4259, Standard Practice for Abrading Concrete. 23 c. D4261, Standard Practice for Surface Cleaning Concrete Unit Masonry for Coating. 24 d. D4262, Standard Test Method for pH of Chemically Cleaned or Etched Concrete 25

Surfaces. 26 e. D4263, Standard Test Method for Indicating Moisture in Concrete by the Plastic Sheet 27

Method. 28 f. D4414, Standard Practice for Measure of Wet Film Thickness by Notch Gages. 29 g. E84, Standard Test Method for Surface Burning Characteristics of Building Materials. 30

2. National Association of Pipe Fabricators (NAPF): 31 a. 500-03, Surface Preparation Standard for Ductile Iron Pipe and Fittings in Exposed 32

Locations Receiving Special External Coatings and/or Special Internal Linings: 33 1) 500-03-04, Abrasive Blast Cleaning for Ductile Iron Pipe. 34 2) 500-03-05, Abrasive Blast Cleaning for Cast Ductile Iron Fittings. 35

3. National Bureau of Standards (NBS): 36 a. Certified Coating Thickness Calibration Standards. 37

4. National Fire Protection Association (NFPA): 38 a. 101, Life Safety Code. 39

5. NSF International (NSF). 40 6. Steel Door Institute/American National Standards Institute (SDI/ANSI): 41

a. A250.10, Test Procedure and Acceptance Criteria For Prime Painted Steel Surfaces for 42 Steel Doors and Frames. 43

7. The Society for Protective Coatings (SSPC): 44 a. PA 2, Measurement of Dry Coating Thickness with Magnetic Gages. 45 b. SP 1, Solvent Cleaning. 46 c. SP 2, Hand Tool Cleaning. 47 d. SP 3, Power Tool Cleaning. 48

Page 16: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 2

e. SP 16, Brush-off Blast Cleaning of Coated and Uncoated Galvanized Steel, Stainless 1 Steels, and Non-Ferrous Metals. 2

8. The Society for Protective Coatings/NACE International (SSPC/NACE): 3 a. SP 5/NACE No. 1, White Metal Blast Cleaning. 4 b. SP 6/NACE No. 3, Commercial Blast Cleaning. 5 c. SP 7/NACE No. 4, Brush-off Blast Cleaning. 6 d. SP 10/NACE No. 2, Near-White Blast Cleaning. 7 e. SP 12/NACE No. 5, Surface Preparation and Cleaning of Steel and Other Hard 8

Materials by High and Ultrahigh Pressure Water Jetting Prior to Recoating. 9 f. SP 13/NACE No. 6, Surface Preparation of Concrete. 10

B. Qualifications: 11 1. Coating manufacturer's authorized representative shall provide written statement attesting 12

that applicator has been instructed on proper preparation, mixing and application procedures 13 for coatings specified. 14

2. Applicators shall have minimum of 10 years experience in application of similar products 15 on similar project. 16 a. Provide references for minimum of three (3) different projects completed in last five (5) 17

years with similar scope of work. 18 b. Include name and address of project, size of project in value (painting) and contact 19

person. 20

C. Miscellaneous: 21 1. Furnish paint through one (1) manufacturer unless noted otherwise. 22 2. Coating used in all corridors and stairways shall meet requirements of NFPA 101 and 23

ASTM E84. 24

D. Deviation from specified mil thickness or product type is not allowed without written 25 authorization of Engineer. 26

E. Material shall not be thinned unless approved, in writing, by paint manufacturer's authorized 27 representative. 28

1.3 DEFINITIONS 29

A. Installer or Applicator: 30 1. Installer or applicator is the person actually installing or applying the product in the field at 31

the Project site. 32 2. Installer and applicator are synonymous. 33

B. Approved Factory Finish: Finish on a product in compliance with the finish specified in the 34 Specification Section where the product is specified or in Specification Section 11005. 35

C. Exposed Exterior Surface: 36 1. Surface which is exposed to weather but not necessarily exposed to view as well as surface 37

exposed to view. 38 2. Exterior surfaces are considered corrosive environment. 39

a. The following areas are considered highly corrosive: 40 1) All chemical unloading stations and areas within 10 FT-0 IN of containment areas. 41 2) All chemical unloading station containment areas. 42 3) All areas within a 6 FT radius of chemical tank vents. 43

D. Finished Area: An area that is listed in or has finish called for on Room Finish Schedule or is 44 indicated on Drawings to be painted. 45

E. Immersion Surface: 46 1. Any surface immersed in water or some other liquid. 47 2. Surface of any pipe, valve, or any other component of the piping system subject to 48

condensation including the pipe support system. 49

Page 17: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 3

F. Paint includes the following: 1 1. High performance industrial coatings (HPIC) include: Epoxies, urethanes, vinyl ester, 2

waterborne vinyl acrylic emulsions, acrylates, silicones, alkyds, acrylic emulsions and any 3 other coating listed as a HPIC. 4

G. Surface Hidden from View: Surfaces such as those within pipe chases, surfaces between top 5 side of ceilings (including drop-in tile ceilings) and underside of floor or roof structures above, 6 surfaces under overhanging walkways if over five feet above adjacent walking surfaces 7

H. AP: Architectural paints. 8

I. HPIC: High performance industrial coatings. 9

J. SC: Special coatings. 10

K. Water level for purposes of painting: See Drawings. 11

1.4 SUBMITTALS 12

A. Shop Drawings: 13 1. See Specification Section 01340 for requirements for the mechanics and administration of 14

the submittal process. 15 2. Applicator experience qualifications. 16

a. No submittal information will be reviewed until Engineer has received and approved 17 applicator qualifications. 18

3. Product technical data including: 19 a. Acknowledgement that products submitted meet requirements of standards referenced. 20 b. Manufacturer's application instructions. 21 c. Manufacturer's surface preparation instructions. 22 d. If products being used are manufactured by Company other than listed in the 23

MATERIALS Article of this Specification Section}, provide complete individual data 24 sheet comparison of proposed products with specified products including application 25 procedure, coverage rates and verification that product is designed for intended use. 26

e. Contractor's written plan of action for containing airborne particles created by blasting 27 operation and location of disposal of spent contaminated blasting media. 28

f. Coating manufacturer's recommendation on abrasive blasting. 29 g. Manufacturer's recommendation for universal barrier coat. 30 h. Manufacturer's recommendation for providing temporary or supplemental heat or 31

dehumidification or other environmental control measures. 32 4. Manufacturer's statement regarding applicator instruction on product use. 33 5. Certification that High Performance Coating Systems proposed for use have been reviewed 34

and approved by Senior Corrosion Specification Specialist employed by the coating 35 manufacturer. 36

B. Samples: 37 1. Manufacturer's full line of colors for Engineer's preliminary color selection. 38 2. After preliminary color selection by Engineer provide two (2) 3 x 5 IN samples of each final 39

color selected. 40

C. Informational Submittals: 41 1. See Specification Section 01340 for requirements for the mechanics and administration of 42

the submittal process. 43 2. Approval of application equipment. 44 3. Applicator's daily records: 45

a. Submit daily records at end of each week in which painting work is performed unless 46 requested otherwise by Engineer's on-site representative. 47

Page 18: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 4

1.5 DELIVERY, STORAGE, AND HANDLING 1

A. Deliver in original containers, labeled as follows: 2 1. Name or type number of material. 3 2. Manufacturer's name and item stock number. 4 3. Contents, by volume, of major constituents. 5 4. Warning labels. 6 5. VOC content. 7

PART 2 - PRODUCTS 8

2.1 ACCEPTABLE MANUFACTURERS 9

A. Subject to compliance with the Contract Documents, only the following manufacturers are 10 acceptable: 11 1. High performance industrial coatings: 12

a. Tnemec. 13 b. ICI Devoe. 14 c. Carboline Protective Coatings. 15 d. Sherwin Williams. 16 e. Dampney Company, Inc. 17 f. PPG Industries/Amercoat. 18

B. Submit request for substitution in accordance with Specification Section 01640. 19 1. Product VOC content will be an important factor when determining acceptability of 20

substitution. 21

2.2 MATERIALS 22

A. For unspecified materials such as thinner, provide manufacturer's recommended products. 23

B. Paint Systems - General: 24 1. P = prime coat. 25 2. F1, F2 . . . Fn = first finish coat, second finish coat . . . . nth finish coat, color as selected by 26

Engineer. 27 3. If two (2) finish coats of same material are required, Contractor may, at his option and by 28

written approval from paint manufacturer, apply one (1) coat equal to mil thickness of 29 two (2) coats specified. 30

C. HPIC products listed in the MATERIALS Article, Paint Systems paragraph are manufactured by 31 Tnemec. 32 1. Products of other listed manufacturers are acceptable for use providing the product is of the 33

same generic resin, requires comparable surface preparation, has comparable application 34 requirements, meets the same VOC levels or better, provides the same finish and color 35 options and will withstand the atmospheric conditions of the location where it is to be 36 applied. 37

D. Paint Systems (Systems not shown are not used): 38 1. HPIC SYSTEM #1 - Polyamidoamine Epoxy Primer with Polyamidoamine Epoxy or 39

Waterborne Acrylic Polyurethane Finish Coat(s). 40 a. Prime coat: 41

1) P1 = 1 coat, 3 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 42 b. Finish coat(s): 43

1) Interior: 44 a) F1 = 1 coat, 3 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 45 b) F2 = 1 coat, 3 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 46

2) Exterior: 47 a) F1 = 1 coat, 3 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 48

Page 19: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 5

b) F2 = 1 coat, 2.5 mils, Series 1080 Endura-Shield. W.B.(Waterborne Acrylic 1 Polyurethane). 2

2. HPIC SYSTEM #2 - Zinc-Rich Urethane Primer with Polyamidoamine Epoxy or 3 Waterborne Acrylic Polyurethane Finish Coat(s). 4 a. Prime coat: 5

1) P1 = 1 coat, 3.5 mils, Series 90-97 Tneme-Zinc (Zinc-Rich Urethane). 6 b. Finish coat(s): 7

1) Interior: 8 a) F1 = 1 coat, 6 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 9

2) Exterior: 10 a) F1 = 1 coat, 6 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 11 b) F2 = 1 coat, 2.5 mils, Series 1080 Endura-Shield W.B.(Waterborne Acrylic 12

Polyurethane). 13 3. HPIC SYSTEM #3 - Polyamidoamine Epoxy Primer with Polyamidoamine Epoxy or 14

Waterborne Acrylic Polyurethane Top Coat(s). 15 a. Prime coat: 16

1) P1 = 1 coat, 5 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 17 b. Finish coat(s): 18

1) Interior: 19 a) F1 = 1 coat, 5 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 20

2) Exterior: 21 a) F1 = 1 coat, 2.5 mils, Series 1080 Endura-Shield W.B. (Waterborne Acrylic 22

Polyurethane). 23 4. HPIC SYSTEM #4 - Zinc-Rich Urethane Primer with Polyamidoamine Epoxy or 24

Waterborne Acrylic Polyurethane Top Coat(s). 25 a. Prime coat: 26

1) P1 = 1 coat, 2.5 mils, Series 90-97 Tneme-Zinc (Zinc-Rich Urethane). 27 b. Finish coat(s): 28

1) Interior: 29 a) F1 = 1 coat, 3 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 30

2) Exterior: 31 a) F1 = 1 coat, 2.5 mils, Series 1080 Endura-Shield W.B. (Waterborne Acrylic 32

Polyurethane). 33 5. HPIC SYSTEM #5 - Modified Polyamidoamine Epoxy Primer with Polyamidoamine Epoxy 34

or Waterborne Acrylic Polyurethane Top Coat(s). 35 a. Prime coat: 36

1) P1 = 1 coat, 2.0 mils, Series 135 Chembuild (Modified Polyamidoamine Epoxy). 37 b. Finish coat(s): 38

1) Interior: 39 a) F1 = 1 coat, 2.5 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 40

2) Exterior: 41 a) F1 = 1 coat, 2.0 mils, Series 1080 Endura-Shield W.B. (Waterborne Acrylic 42

Polyurethane). 43 6. HPIC SYSTEM #7 - Zinc-Rich Urethane Primer with Polyamidoamine Epoxy or 44

Waterborne Acrylic Polyurethane Top Coat(s). 45 a. Prime coat: 46

1) P1 = 1 coat, 2.5 mils, Series 90-97 Tneme-Zinc (Zinc-Rich Urethane). 47 b. Finish coat(s): 48

1) Interior: 49 a) F1 = 1 coat, 5 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 50

2) Exterior: 51 a) F1 = 1 coat, 3.0 mils, Series 1080 Endura-Shield W.B. (Waterborne Acrylic 52

Polyurethane). 53

Page 20: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 6

7. HPIC SYSTEM #8 - Air Dry Silicone Copolymer Primer with Silicone Copolymer Top 1 Coat. 2 a. Prime coat: 3

1) P1 = 1 coat, 2.0 mils, Dampney Thurmalox 260C Series (Air Dry Silicone 4 Copolymer). 5

b. Finish coat: 6 1) Interior or exterior: 7

a) F1 = 1 coat, 2.0 mils, Dampney Thurmalox 260C Series (Air Dry Silicone 8 Copolymer). 9

8. HPIC SYSTEM #10 - Modified Silicone Co-Polymer Primer with Modified Silicone Co-10 Polymer Top Coat(s). 11 a. Prime coat: 12

1) P1 = 1 coat, 4.0 to 5.0 mils, Dampney Thurmalox 225 HD (Modified Silicone Co-13 Polymer). 14

b. Finish coat(s): 15 1) F1 = 1 coat, 2.5 to 3.0 mils, Dampney Thurmalox 230C. 16

9. HPIC SYSTEM #15 - Polyamidoamine Epoxy Primer with Polyamidoamine Epoxy Top 17 Coat. 18 a. Prime coat: 19

1) P1 = 1 coat, 4 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 20 b. Finish coat: 21

1) Interior: 22 a) F1 = 1 coat, 6 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 23 b) F2 = 1 coat, 6 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 24

10. HPIC SYSTEM #19 - Polyamidoamine Epoxy Coating. 25 a. Prime coat: 26

1) P1 = 1 coat, 5 mils, Series L69 Epoxoline (Polyamidoamine Epoxy). 27 11. HPIC SYSTEM #21 - Modified Polyamidoamine Epoxy. 28

a. Prime coat: 29 1) P1 = 1 coat, 5 mils, 135-1243 Chembuild (Modified Polyamidoamine Epoxy). 30

12. HPIC SYSTEM #23 - Zinc-Rich Urethane Potable Water Approved Primer with Polyamine 31 Epoxy Potable Water Approved Top Coats. 32 a. Prime coat: 33

1) P1 = 1 coat, 3 mils, Series 91 H20 Hydro-Zinc (Zinc-Rich Urethane). 34 b. Finish coat(s): 35

1) Interior: 36 a) F1 = 1 coat, 25 mils, Series 22 Pota-Pox 100 (Modified Polyamine Epoxy). 37

13. HPIC SYSTEM #24 - Vinyl Ester Primer with Vinyl Ester Top Coat. 38 a. Prime coat: 39

1) P1 = 1 coat, 17 mils, Series 120-5002 Vinester (Vinyl Ester). 40 b. Finish coat: 41

1) F1 = 1 coat, 17 mils, Series 120-5001 Vinester (Vinyl Ester). 42 14. SYSTEM #41 - Touch-up of galvanized surfaces not requiring a top coat. 43

a. Refer to Specification Section 05505. 44

PART 3 - EXECUTION 45

3.1 ITEMS TO BE PAINTED 46

A. General: 47

B. Exposed Exterior Surfaces including: 48 1. Equipment supports, and pipe supports . 49 2. Piping, valves, fittings, and supports. 50

a. Field welded connections of factory painted piping. 51 3. Miscellaneous ferrous metal surfaces. 52

Page 21: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 7

4. Steel pipe bollards. 1 5. Steel lintels. 2 6. Steel components of concrete lintels. 3

a. Steel components shall be completely painted (with both prime and finish coats) prior 4 to installing in the wall. 5

7. Galvanized metal surfaces. 6 8. Cast iron pipe plumbing vents. 7

C. Surfaces in Areas Not Considered Finished: 8 1. Paint following surfaces in areas not considered as finished area: 9

a. Piping, valves, fittings, and supports. 10 b. Ductwork and supports. 11 c. Miscellaneous ferrous metal surfaces. 12 d. Steel lintels. 13 e. Steel components of concrete lintels. 14

1) Steel components shall be completely painted (with both prime and finish coats) 15 prior to installing in the wall. 16

3.2 ITEMS NOT TO BE PAINTED 17

A. General: Do not paint items listed in this Article unless specifically noted in the Contract 18 Documents to be painted. 19

B. Items with Approved Factory Finish: These items may require repair of damaged painted areas 20 or painting of welded connections. 21

C. Electrical Equipment: 22 1. Do not field paint electrical equipment except where painting is specifically stated 23

elsewhere in these Contract Documents, or where the equipment is subject to a corrosive 24 environment and is specifically noted to be painted. 25

D. Other Items: 26 1. Stainless steel surfaces except: 27

a. Piping where specifically noted to be painted. 28 b. Banding as required to identify piping. 29

2. Aluminum surfaces except: 30 a. Where specifically shown in the Contract Documents. 31 b. Where in contact with concrete. 32 c. Where in contact with dissimilar metals. 33

3. Fiberglass surfaces except: 34 a. Fiberglass piping where specifically noted to be painted. 35 b. Piping supports where specifically noted to be painted. 36

4. Interior of pipe, ductwork, and conduits. 37 5. Moving parts of mechanical and electrical units where painting would interfere with the 38

operation of the unit. 39 6. Code labels and equipment identification and rating plates. 40 7. Exterior concrete or precast concrete surfaces. 41 8. Interior surfaces of wet well. 42 9. Concrete stair. 43 10. Face brick. 44 11. Aluminum doors and frames. 45 12. Pre-colored masonry 46 13. Aluminum windows, curtainwall and storefront framing systems. 47 14. Structural aluminum. 48 15. Clad aluminum, clad steel, anodized aluminum. 49 16. Contact surfaces of friction-type connections. 50

Page 22: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 8

17. Bituminous coated ductile iron pipe. 1 a. See the ITEMS TO BE PAINTED Article, Interior Finished Areas paragraph of this 2

Specification Section. 3

3.3 SCHEDULE OF ITEMS TO BE PAINTED AND PAINTING SYSTEMS 4

A. Steel: 5 1. Potable water storage tanks and all ferrous metal items subject to contact with potable water 6

requiring NSF approval: SYSTEM #23. 7 a. Includes all ferrous metal surfaces subject to splash, spillage, vapor, condensation or 8

other chronic potable water exposure. 9 b. Also includes ferrous metal surfaces within concrete potable water storage tankage 10

requiring NSF approval. 11 c. Exterior surfaces of potable water storage tanks: SYSTEM #7. 12

B. Ferrous metals: SYSTEM #2. 13 1. Includes ferrous, piping pumps, and similar items. 14 2. Does not include items subject to contact with potable water. 15

C. Galvanized Metals: SYSTEM #3 16

D. Non-ferrous metals: SYSTEM #3. 17 1. Includes copper, brass, aluminum and aluminum flashing specifically indicated on the 18

Drawings to be painted. 19

E. Electrical Conduit: SYSTEM #3 20

F. Pipe, Valves, and Fittings: 21 1. Steel pipe bollards: SYSTEM #3. 22 2. Steel, cast-iron, and uncoated ductile iron not in immersion service: SYSTEM #2. 23 3. Brass and bronze: SYSTEM #3. 24

G. Aluminum buried in concrete, between dissimilar metals and dissimilar materials: SYSTEM 25 #19. 26

H. Emergency generator engine exhaust piping: SYSTEM #10. 27

3.4 PREPARATION 28

A. General: 29 1. Verify that atmosphere in area where painting is to take place is within paint manufacturer's 30

acceptable temperature, humidity and sun exposure limits. 31 a. Provide temporary heating, shade and/or dehumidification as required to bring area 32

within acceptable limits. 33 1) Provide temporary dehumidification equipment properly sized to maintain 34

humidity levels required by paint manufacturer. 35 2) Provide clean heat with heat exchanger type equipment sufficient in size to 36

maintain temperature on a 24 HR basis. 37 a) Vent exhaust gases to exterior environment. 38 b) No exhaust gases shall be allowed to vent into the space being painted or any 39

adjacent space. 40 2. Prepare surfaces to be painted in accordance with coating manufacturer's instructions and 41

this Specification Section unless noted otherwise in this Specification Section. 42 a. Where discrepancy between coating manufacturer's instructions and this Specification 43

Section exists, the more stringent preparation shall be provided unless approved 44 otherwise, in writing, by the Engineer. 45

3. Remove all dust, grease, oil, compounds, dirt and other foreign matter which would prevent 46 bonding of coating to surface. 47

Page 23: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 9

4. Adhere to manufacturer's recoat time surface preparation requirements. 1 a. Surfaces that have exceeded coating manufacturer's published recoat time and/or have 2

exhibited surface chalking shall be prepared prior to additional coating in accordance 3 with manufacturer's published recommendations. 4 1) Minimum SSPC SP 7/NACE No. 4 unless otherwise approved by Engineer. 5

B. Protection: 6 1. Protect surrounding surfaces not to be coated. 7 2. Remove and protect hardware, accessories, plates, fixtures, finished work, and similar 8

items; or provide ample in-place protection. 9

C. Prepare and paint before assembly all surfaces which are inaccessible after assembly. 10

D. Ferrous Metal: 11 1. Prepare ductile iron pipe in accordance with pipe manufacturer's recommendations and 12

NAPF. 13 a. All piping, pumps, valves, fittings and any other component used in any water piping 14

system that requires preparation for painting shall be prepared in accordance with 15 requirements for immersion service. 16 1) Pipe: NAPF 500-03-04. 17 2) Fittings: NAPF 500-03-05 18

b. Prepare all areas requiring patch painting in accordance with recommendations of 19 manufacturer and NAPF. 20

c. Remove bituminous coating per piping manufacturer, paint manufacturer and NAPF 21 recommendations. 22 1) The most stringent recommendations shall apply. 23

2. Complete fabrication, welding or burning before beginning surface preparation. 24 a. Chip or grind off flux, spatter, slag or other laminations left from welding. 25 b. Remove mill scale. 26 c. Grind smooth rough welds and other sharp projections. 27

3. Solvent clean in accordance with SSPC SP 1 or detergent and low-pressure water clean in 28 accordance with SSPC SP 12/NACE No. 5 all surfaces scheduled to receive additional 29 SSPC surface preparation. 30

4. Surfaces subject to immersion service: 31 a. Near-white blast clean in accordance with SSPC SP 10/NACE No. 2. 32

5. Surfaces subject to high temperatures. 33 a. Heat in excess of 600 DegF: SSPC SP 10/NACE No. 2. 34

6. All fusion bonded epoxy coated surfaces identified to be field painted: 35 a. Remove all traces of gloss finish by sanding or by abrasive brush blasting. 36 b. Clean surface after removing gloss finish to remove sanding or blasting residue. 37

7. Restore surface of field welds and adjacent areas to original surface preparation. 38 8. Black iron piping: Remove surface varnish by solvent or waterjet and detergent cleaning or 39

brush-off blast cleaning in accordance with SSPC SP 7/NACE No. 4. 40

E. Galvanized Steel and Non-ferrous Metals: 41 1. Solvent clean in accordance with SSPC SP 1 followed by brush-off blast clean in 42

accordance with SSPC SP 16 to remove zinc oxide and other foreign contaminants. 43 a. Provide uniform 1 mil profile surface. 44

F. Abrasive blast clean the following equipment or surfaces regardless of previous finish, if any. 45 1. Bituminous coated ductile iron pipe where exposed. 46

G. Concrete: 47 1. Cure for minimum of 28 days. 48 2. Verify that concrete surfaces have been cleaned and that voids have been patched in 49

accordance with Specification Section 03348. 50 a. Concrete surfaces shall be cleaned in accordance with ASTM D4258. 51

Page 24: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 10

3. Mechanically abrade concrete surfaces in accordance with ASTM D4259 as recommended 1 by coating manufacturer. 2

4. Abrasive blast concrete surfaces in accordance with SSPC SP 13/NACE No. 6 to provide 3 profile recommended by coatings manufacturer. 4

5. Test pH of surface to be painted in accordance with ASTM D4262. 5 a. If surface pH is not within coating manufacturer's required acceptable range, use 6

methods acceptable to coating manufacturer as required to bring pH within acceptable 7 range. 8

b. Retest pH until acceptable results are obtained. 9 6. Verify that moisture content of surface to be painted is within coating manufacturer's 10

recommended acceptable limits. 11 a. Test moisture content of surface to be coated in accordance with ASTM D4263. 12 b. After remedial measures have been taken to lower or raise moisture content, retest 13

surface until acceptable results are obtained. 14

H. Preparation by Abrasive Blasting: 15 1. All abrasive-blasted ferrous metal surfaces shall be inspected immediately prior to 16

application of paint coatings. 17 a. Inspection shall be performed to determine cleanliness and profile depth of blasted 18

surfaces and to certify that surface has been prepared in accordance with these 19 Specifications. 20

2. Schedule the abrasive blasting operation so blasted surfaces will not be wet after blasting 21 and before painting. 22

3. Perform additional blasting and cleaning as required to achieve surface preparation required. 23 a. Prior to painting, reblast surfaces allowed to set overnight and surfaces that show rust 24

bloom. 25 b. Surfaces allowed to set overnight or surfaces which show rust bloom prior to painting 26

shall be reinspected prior to paint application. 27 4. Profile depth of blasted surface: Not less than 1 mil or greater than 2 mils unless required 28

otherwise by coating manufacturer. 29 5. Provide compressed air for blasting that is free of water and oil. 30

a. Provide accessible separators and traps. 31 6. Confine blast abrasives to area being blasted. 32

a. Provide shields of polyethylene sheeting or other such barriers to confine blast material. 33 b. Plug pipes, holes, or openings before blasting and keep plugged until blast operation is 34

complete and residue is removed. 35 7. Protect nameplates, valve stems, rotating equipment, motors and other items that may be 36

damaged from blasting. 37 8. Reblast surfaces not meeting requirements of these Specifications. 38 9. Abrasive blasting media may be recovered, cleaned and reused providing Contractor 39

submits, for Engineer's review, a comprehensive recovery plan outlining all procedures and 40 equipment proposed in reclamation process. 41

10. Properly dispose of blasting material contaminated with debris from blasting operation not 42 scheduled to be reused. 43

I. All Plastic Surfaces and Non-Ferrous Surfaces Except Galvanized Steel: 44 1. Sand using 80-100 grit sandpaper to scarify surfaces. 45

3.5 APPLICATION 46

A. General: 47 1. Thin, mix and apply coatings by brush, roller, or spray in accordance with manufacturer's 48

installation instructions. 49 a. Application equipment must be inspected and approved in writing by coating 50

manufacturer. 51 b. Hollow metal shall be spray applied only. 52

Page 25: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 11

2. Temperature and weather conditions: 1 a. Do not paint surfaces when surface temperature is below 50 DegF unless product has 2

been formulated specifically for low temperature application and application is 3 approved in writing by Engineer and paint manufacturer's authorized representative. 4

b. Avoid painting surfaces exposed to hot sun. 5 c. Do not paint on damp surfaces. 6

3. Provide complete coverage to mil thickness specified. 7 a. Thickness specified is dry mil thickness. 8 b. All paint systems are "to cover." 9

1) In situations of discrepancy between manufacturer's square footage coverage rates 10 and mil thickness, mil thickness requirements govern. 11

c. When color or undercoats show through, apply additional coats until paint film is of 12 uniform finish and color. 13

4. If so directed by Engineer, do not apply consecutive coats until Engineer has had an 14 opportunity to observe and approve previous coats. 15

5. Apply materials under adequate illumination. 16 6. Evenly spread to provide full, smooth coverage. 17 7. Work each application of material into corners, crevices, joints, and other difficult to work 18

areas. 19 8. Avoid degradation and contamination of blasted surfaces and avoid intercoat contamination. 20

a. Clean contaminated surfaces before applying next coat. 21 9. Smooth out runs or sags immediately, or remove and recoat entire surface. 22 10. Allow preceding coats to dry before recoating. 23

a. Recoat within time limits specified by coating manufacturer. 24 b. If recoat time limits have expired re-prepare surface in accordance with coating 25

manufacturer's printed recommendations. 26 11. Allow coated surfaces to cure prior to allowing traffic or other work to proceed. 27 12. Coat all aluminum in contact with dissimilar materials. 28 13. When coating rough surfaces which cannot be backrolled sufficiently, hand brush coating to 29

work into all recesses. 30

B. Prime Coat Application: 31 1. Prime all surfaces indicated to be painted. 32

a. Apply prime coat in accordance with coating manufacturer's written instructions and as 33 written in this Specification Section. 34

2. Ensure field-applied coatings are compatible with factory-applied coatings. 35 a. Employ services of coating manufacturer's qualified technical representative. 36

1) Certify through material data sheets. 37 2) Perform test patch. 38

b. If field-applied coating is found to be not compatible, require the coating 39 manufacturer's technical representative to recommend, in writing, product to be used as 40 barrier coat, thickness to be applied, surface preparation and method of application. 41

c. At Contractor's option, coatings may be removed, surface re-prepared, and new coating 42 applied using appropriate paint system listed in the MATERIALS Article, Paint 43 Systems paragraph of this Specification Section. 44 1) All damage to surface as result of coating removal shall be repaired to original 45

condition or better by Contractor at no additional cost to Owner. 46 3. Prime ferrous metals embedded in concrete to minimum of 1 IN below exposed surfaces. 47 4. Apply zinc-rich primers while under continuous agitation. 48 5. Ensure abrasive blasting operation does not result in embedment of abrasive particles in 49

paint film. 50 6. Brush or spray bolts, welds, edges and difficult access areas with primer prior to primer 51

application over entire surface. 52 7. Touch up damaged primer coats prior to applying finish coats. 53

a. Restore primed surface equal to surface before damage. 54

Page 26: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 12

8. All surfaces of steel lintels and steel components of concrete lintels used in wall 1 construction shall be completely painted with both prime and finish coats prior to placing in 2 wall. 3

C. Finish Coat Application: 4 1. Apply finish coats in accordance with coating manufacturer's written instructions and in 5

accordance with this Specification Section; manufacturer instructions take precedent over 6 these Specifications. 7

2. Touch up damaged finish coats using same application method and same material specified 8 for finish coat. 9 a. Prepare damaged area in accordance with the PREPARATION Article of this 10

Specification Section. 11

3.6 COLOR CODING 12

A. Color and band piping in accordance with the SCHEDULE Article of this Specification Section. 13 1. Band piping using maximum of three (3) different colors at 20 FT maximum centers. 14 2. Factory painted piping shall be color banded in the factory per the Schedule in the 15

SCHEDULE Article of this Specification Section. 16 3. Place bands: 17

a. Along continuous lines. 18 b. At changes in direction. 19 c. At changes of elevation. 20 d. On both sides of an obstruction (e.g., wall, ceiling) that painted item passes through. 21

4. Band width for individual colors (pipe diameter measured to outside of insulation, if 22 applicable): 23 a. Piping up to 8 IN DIA: 2 IN minimum. 24 b. Piping greater than 8 IN up to 24 IN DIA: 4 IN minimum. 25 c. Piping greater than 24 IN up to 48 IN DIA: 6 IN minimum. 26 d. Piping greater than 48 IN DIA: 8 IN minimum. 27

3.7 FIELD QUALITY CONTROL 28

A. Contractor to provide protection for surfaces painted with epoxy coatings to prevent chalking. 29 1. Surfaces showing chalking will not be accepted. 30

B. Maintain Daily Records: 31 1. Record the following information during application of each coat of paint applied: 32

a. Date, starting time, end time, and all breaks taken by painters. 33 b. For exterior painting: 34

1) Sky condition. 35 2) Wind speed and direction. 36

c. Air temperature. 37 d. Relative humidity. 38 e. Moisture content and surface temperature of substrate prior to each coat. 39 f. Provisions utilized to maintain work area within manufacturer's recommended 40

application parameters including temporary heating, ventilation, cooling, 41 dehumidification and provisions utilized to mitigate wind blown dust and debris from 42 contaminating the wet paint film. 43

g. Record environmental conditions, substrate moisture content and surface temperature 44 information not less than once every four (4) hours during application. 45 1) Record hourly when temperatures are below 50 DegF or above 100 DegF. 46

2. Record the following information daily for the paint manufacturer's recommended curing 47 period: 48 a. Date and start time of cure period for each item or area. 49 b. For exterior painting: 50

1) Sky conditions. 51 2) Wind speed and direction. 52

Page 27: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 13

c. Record environmental conditions not less than once every 12 hours. 1 1) Record once every four (4) hours when ambient temperature is below 35 DegF. 2

d. Provisions utilized to protect each item or area and to maintain areas within 3 manufacturer's recommended curing parameters. 4

3. Format for daily record to be computer generated. 5

C. Measure wet coating with wet film thickness gages in accordance with ASTM D4414. 6

D. Measure coating dry film thickness in accordance with SSPC PA 2 using Mikrotest gage 7 calibrated against NBS "Certified Coating Thickness Calibration Standards." 8 1. Engineer may measure coating thickness at any time during project to assure conformance 9

with these Specifications. 10

E. Measure surface temperature of items to be painted with surface temperature gage specifically 11 designed for such. 12

F. Measure substrate humidity with humidity gage specifically designed for such. 13

G. Provide wet paint signs. 14

3.8 CLEANING 15

A. Clean paint spattered surfaces. 16 1. Use care not to damage finished surfaces. 17

B. Upon completion of painting, replace hardware, accessories, plates, fixtures, and similar items. 18

C. Remove surplus materials, scaffolding, and debris. 19

3.9 SCHEDULE 20

A. Piping and Pipe Banding Color Schedule (Colors based on Tnemec): 21 1. Match piping and banding colors to Owners existing colors scheme. 22 2. Piping systems shown in italics with no paint color shown for the pipe but having paint 23

colors shown for the banding color are systems that will be banded using material other than 24 paint. 25 a. Refer to Specification Section 10400 for the piping system and banding material and 26

refer to this Specification Section and this Schedule for the banding colors. 27 b. Collector Well Piping Schedule: 28

29 SERVICE SYMBOL PIPE COLOR Collector Well Pump Discharge: CWPDIS 110 GN - Clover Condenser Water Return CWR 32GR-Gray Condenser Water Supply CWS 32GR-Gray Raw Water Return RWR 32GR-Gray Raw Water Supply RWS 32GR-Gray Pre-Lube PL 32GR-Gray

30

END OF SECTION 31

32

Page 28: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PAINTING AND PROTECTIVE COATINGS 09905 - 14

1

Page 29: City of Yankton, SD

D I V I S I O N 1 0 SPECIALTIES

Page 30: City of Yankton, SD
Page 31: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOUVERS AND VENTS 10200 - 1

2014/08/29 1

SECTION 10200 2

LOUVERS AND VENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Louvers and vents. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 07600 - Flashing and Sheet Metal. 11 4. Section 07900 - Joint Sealants. 12 5. Section 08410 - Storefront. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. Aluminum Association (AA): 16

a. DAF 45, Designation System for Aluminum Finishes. 17 2. Air Movement and Control Association (AMCA). 18 3. ASTM International (ASTM): 19

a. B221, Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, 20 Rods, Wire, Profiles, and Tubes. 21

1.3 SUBMITTALS 22

A. Shop Drawings: 23 1. See Specification Section 01340 for requirements for the mechanics and administration of 24

the submittal process. 25 2. Drawing showing location of each louver or vent, indicating size and arrangement of blank-26

off plates if required. 27 3. Product technical data including: 28

a. Acknowledgement that products submitted meet requirements of standards referenced. 29 b. Manufacturer's installation instructions. 30 c. Color chart showing manufacturer's full line of colors including exotic and special 31

colors for color selection by Engineer. 32

PART 2 - PRODUCTS 33

2.1 ACCEPTABLE MANUFACTURERS 34

A. Subject to compliance with the Contract Documents, the following manufacturers are 35 acceptable: 36 1. Louvers: 37

a. Airolite Co. 38 b. Construction Specialties, Inc. 39 c. Ruskin Manufacturing. 40 d. Industrial Louvers, Inc. 41 e. American Warming. 42

B. Submit request for substitution in accordance with Specification Section 01640. 43

Page 32: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOUVERS AND VENTS 10200 - 2

2.2 MANUFACTURED UNITS 1

A. Louvers: 2 1. 4 IN deep. 3 2. Drainable with blades at 37-1/2 degrees. 4 3. Continuous blade appearance. 5 4. ASTM B221 extruded aluminum, alloy 6063T5, minimum 0.081 IN thick. 6 5. Minimum free area: 8.58 SF for 4 x 4 FT louver. 7 6. Maximum pressure drop: 0.10 IN of water at 700 fpm. 8 7. Water penetration: 0.01 OZ/SF at 873 fpm. 9 8. AMCA certified. 10 9. Ruskin "ELF 375DX". 11 10. Insect screen: 12

a. 18-16 mesh aluminum. 13 b. Install in standard aluminum frame. 14

11. Glazing Adapter 15 a. Extruded aluminum alloy 6063-T5. 16 b. Size as required for louver model. 17 c. Thickness: 0.081 IN or as required per manufacturers standard. 18 d. Finish to match storefront. 19 e. Coordinate with Section 08410 Storefront. 20

B. Anchors, Fasteners, Reinforcing: Aluminum or stainless steel. 21

C. Finish: 22 1. Architectural Class 1 coating per AA DAF 45. 23

a. Champagne, AA-M10C12C22A44. 24 b. Finish matching storefront, no exceptions. 25

D. Size: Refer to Mechanical Drawings for louver size, and refer to Architectural Drawings for 26 louver shapes. 27

E. Blank-Off Plates: 28 1. Aluminum sheet, 0.050 IN minimum thickness. 29 2. Factory applied flat black painted finish. 30

PART 3 - EXECUTION 31

3.1 INSTALLATION 32

A. Install products in accordance with manufacturer's instructions. 33

B. Install anchoring and bracing accessories as required. 34 1. Install into storefront frame with glazing adaptor. 35

C. Seal around perimeter on exterior and interior. 36 1. See Section 07900. 37

D. Install 0.040 IN aluminum flashing at sill to match louver. 38 1. See Section 07600. 39

END OF SECTION 40

Page 33: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 1

2014/10/07 1

SECTION 10400 2

IDENTIFICATION DEVICES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Tag, tape and stenciling systems for equipment, piping, valves, pumps, ductwork and 7

similar items, and hazard and safety signs. 8

B. Related Specification Sections include but are not necessarily limited to: 9 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 10 2. Division 01 - General Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. American Society of Mechanical Engineers (ASME): 14

a. A13.1, Scheme for the Identification of Piping Systems. 15 2. Instrumentation, Systems, and Automation Society (ISA). 16 3. National Electrical Manufacturers Association/American National Standards Institute 17

(NEMA/ANSI): 18 a. Z535.1, Safety Color Code. 19 b. Z535.2, Environmental and Facility Safety Signs. 20 c. Z535.3, Criteria for Safety Symbols. 21 d. Z535.4, Product Safety Signs and Labels. 22

4. National Fire Protection Association (NFPA): 23 a. 70, National Electrical Code (NEC). 24

5. Occupational Safety and Health Administration (OSHA): 25 a. 29 CFR 1910.145, Specification for Accident Prevention Signs and Tags. 26

1.3 SUBMITTALS 27

A. Shop Drawings: 28 1. See Specification Section 01340 for requirements for the mechanics and administration of 29

the submittal process. 30 2. Product technical data including: 31

a. Catalog information for all identification systems. 32 b. Acknowledgement that products submitted meet requirements of standards referenced. 33

3. Identification register, listing all items in PART 3 of this Specification Section to be 34 identified, type of identification system to be used, lettering, location and color. 35

PART 2 - PRODUCTS 36

2.1 ACCEPTABLE MANUFACTURERS 37

A. Subject to compliance with the Contract Documents, the following manufacturers are 38 acceptable: 39 1. W.H. Brady Co. 40 2. Panduit. 41 3. Seton. 42 4. National Band and Tag Co. 43 5. Carlton Industries, Inc. 44

Page 34: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 2

B. Submit request for substitution in accordance with Specification Section 01640. 1

2.2 MANUFACTURED UNITS 2

A. Type A1 - Round Metal Tags: 3 1. Materials: 4

a. Aluminum or stainless steel. 5 b. Stainless steel shall be used in corrosive environments. 6

2. Size: 7 a. Diameter: 1-1/2 IN minimum. 8 b. Thickness: 0.035 IN (20 GA) minimum. 9

3. Fabrication: 10 a. 3/16 IN minimum mounting hole. 11 b. Legend: Stamped and filled with black coloring. 12

4. Color: Natural. 13

B. Type A2 - Rectangle Metal Tags: 14 1. Materials: Stainless steel. 15 2. Size: 16

a. 3-1/2 IN x 1-1/2 IN minimum. 17 b. Thickness: 0.036 IN (20 GA) minimum. 18

3. Fabrication: 19 a. 3/16 IN minimum mounting hole. 20 b. Legend: Stamped and filled with black coloring. 21

4. Color: Natural. 22

C. Type A3 - Metal Tape Tags: 23 1. Materials: Aluminum or stainless steel. 24 2. Size: 25

a. Width 1/2 IN minimum. 26 b. Length as required by text. 27

3. Fabrication: 28 a. 3/16 IN minimum mounting hole. 29 b. Legend: Embossed. 30

4. Color: Natural. 31

D. Type B1- Square Nonmetallic Tags: 32 1. Materials: Fiberglass reinforced plastic. 33 2. Size: 34

a. Surface: 2 x 2 IN minimum. 35 b. Thickness: 100 mils. 36

3. Fabrication: 37 a. 3/16 IN mounting hole with metal eyelet. 38 b. Legend: Preprinted and permanently embedded and fade resistant. 39

4. Color: 40 a. Background: Manufacturer standard or as specified. 41 b. Lettering: Black. 42

E. Type B2 - Nonmetallic Signs: 43 1. Materials: Fiberglass reinforced or durable plastic. 44 2. Size: 45

a. Surface: As required by text. 46 b. Thickness: 60 mils minimum. 47

3. Fabrication: 48 a. Rounded corners. 49 b. Drilled holes in corners with grommets. 50 c. Legend: Preprinted, permanently embedded and fade resistant for a 10 year minimum 51

outdoor durability. 52

Page 35: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 3

4. Color: 1 a. Background: Manufacturer standard or as specified. 2 b. Lettering: Black. 3

5. Standards for OSHA signs: NEMA/ANSI Z535.1, NEMA/ANSI Z535.2, NEMA/ANSI 4 Z535.3, NEMA/ANSI Z535.4, OSHA 29 CFR 1910.145. 5

F. Type C - Phenolic Name Plates: 6 1. Materials: Phenolic. 7 2. Size: 8

a. Surface: As required by text. 9 b. Thickness: 1/16 IN. 10

3. Fabrication: 11 a. Two (2) layers laminated. 12 b. Legend: Engraved through top lamination into bottom lamination. 13 c. Two (2) drilled side holes, for screw mounting. 14

4. Color: Black top surface, white core, unless otherwise indicated. 15

G. Type D - Self-Adhesive Tape Tags and Signs: 16 1. Materials: Vinyl tape or vinyl cloth. 17 2. Size: 18

a. Surface: As required by text. 19 b. Thickness: 5 mils minimum. 20

3. Fabrication: 21 a. Indoor/Outdoor grade. 22 b. Weather and UV resistant inks. 23 c. Permanent adhesive. 24 d. Legend: Preprinted. 25 e. Wire markers to be self-laminating. 26

4. Color: White with black lettering or as specified. 27 5. Standards for OSHA signs: NEMA/ANSI Z535.1, NEMA/ANSI Z535.2, NEMA/ANSI 28

Z535.3, NEMA/ANSI Z535.4, OSHA 29 CFR 1910.145. 29

H. Type E - Heat Shrinkable Tape Tags: 30 1. Materials: Polyolefin. 31 2. Size: As required by text. 32 3. Fabrication: 33

a. Legend: Preprinted. 34 4. Color: White background, black printing. 35

I. Type F - Underground Warning Tape: 36 1. Materials: Polyethylene. 37 2. Size: 38

a. 6 IN wide (minimum). 39 b. Thickness: 3.5 mils. 40

3. Fabrication: 41 a. Legend: Preprinted and permanently imbedded. 42 b. Message continuous printed. 43 c. Tensile strength: 1750 psi. 44

4. Color: As specified. 45

J. Type G - Stenciling System: 46 1. Materials: 47

a. Exterior type stenciling enamel. 48 b. Either brushing grade or pressurized spray can form and grade. 49

2. Size: As required. 50 3. Fabrication: 51

a. Legend: As required. 52 4. Color: Black or white for best contrast. 53

Page 36: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 4

K. Underground Tracer Wire: 1 1. Materials: 2

a. Wire: 3 1) 12 GA AWG. 4 2) Solid. 5

b. Wire nuts: Waterproof type. 6 c. Split bolts: Brass. 7

2.3 ACCESSORIES 8

A. Fasteners: 9 1. Bead chain: #6 brass, aluminum or stainless steel. 10 2. Plastic strap: Nylon, urethane or polypropylene. 11 3. Screws: Self-tapping, stainless steel. 12 4. Adhesive, solvent activated. 13

2.4 MAINTENANCE MATERIALS 14

A. Where stenciled markers are provided, clean and retain stencils after completion and include in 15 extra stock, along with required stock of paints and applicators. 16

PART 3 - EXECUTION 17

3.1 GENERAL INSTALLATION 18

A. Install identification devices at specified locations. 19

B. All identification devices to be printed by mechanical process, hand printing is not acceptable. 20

C. Attach tags to equipment with sufficient surface or body area with solvent activated adhesive 21 applied to back of each tag. 22

D. Attach tags with 1/8 IN round or flat head screws to equipment without sufficient surface or 23 body area, or porous surfaces. 24 1. Where attachment with screws should not or cannot penetrate substrate, attach with plastic 25

strap. 26

E. Single items of equipment enclosed in a housing or compartment to be tagged on outside of 27 housing. 28 1. Several items of equipment mounted in housing to be individually tagged inside the 29

compartment. 30

F. Tracer Wire: 31 1. Attach to pipe at a maximum of 10 FT intervals with tape or tie-wraps. 32 2. Continuous pass from each valve box and above grade at each structure. 33 3. Coil enough wire at each valve box to extend wire a foot above the ground surface. 34 4. 1,000 FT maximum spacing between valve boxes. 35 5. If split bolts are used for splicing, wrap with electrical tape. 36 6. If wire nuts are used for splicing, knot wire at each splice point leaving 6 IN of wire for 37

splicing. 38 7. Use continuous strand of wire between valve box where possible. 39

a. Continuous length shall be no shorter than 100 FT. 40

3.2 SCHEDULES 41

A. Process Systems: 42 1. General: 43

a. Provide arrows and markers on piping. 44 1) At 20 FT maximum centers along continuous lines. 45 2) At changes in direction (route) or obstructions. 46

Page 37: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 5

3) At valves, risers, "T" joints, machinery or equipment. 1 4) Where pipes pass through floors, walls, ceilings, cladding assemblies and like 2

obstructions provide markers on both sides. 3 b. Position markers on both sides of pipe with arrow markers pointing in flow direction. 4

1) If flow is in both directions use double headed arrow markers. 5 c. Apply tapes and stenciling in uniform manner parallel to piping. 6

2. Trenches with piping: 7 a. Tag type: Type F - Underground Warning Tape 8 b. Location: Halfway between top of piping and finished grade. 9 c. Letter height: 1-1/4 IN minimum. 10 d. (Nonpotable) water piping, except 3 IN and smaller irrigation pipe: 11

1) Color: Green with black letters. 12 2) Legend: 13

a) First line: “CAUTION CAUTION CAUTION” 14 b) Second line: “BURIED NONPOTABLE WATER LINE BELOW” 15

3. Yard valves, buried, with valve box and concrete pad: 16 a. Tag type: Type A2 - Rectangle Metal Tags. 17 b. Fastener: 3/16 IN x 7/8 IN plastic screw anchor with 1 IN #6 stainless steel pan head 18

screw. 19 c. Legend: 20

1) Letter height: 1/4 IN minimum. 21 2) Valve designation as indicated on the Drawings (e.g., “V-xxx”). 22

4. Valves and slide gates: 23 a. Tag type: 24

1) Outdoor locations: Type B1 - Square Nonmetallic Tags. 25 2) Indoor noncorrosive: 26

a) Type A1 - Round Metal Tags. 27 b) Type B1 - Square Nonmetallic Tags. 28

3) Indoor corrosive: 29 a) Stainless steel Type A1 - Round Metal Tags. 30 b) Type B1 - Square Nonmetallic Tags. 31

b. Fastener: 32 1) Type A1: Chain of the same material. 33 2) Type B1: Stainless steel chain. 34

c. Color: Per ASME A13.1 corresponding to the piping system. 35 d. Legend: 36

1) Letter height: 1/4 IN minimum. 37 2) Valve designation as indicated on the Drawings (e.g., “V-xxx”). 38

5. Process equipment (e.g., pumps, pump motors, etc.): 39 a. Tag type: 40

1) Type B2 - Nonmetallic Signs. 41 2) Type D - Self-Adhesive Tape Tags and Signs. 42 3) Type G - Stenciling System. 43

b. Fastener: 44 1) Self. 45 2) Screws. 46 3) Adhesive. 47

c. Legend: 48 1) Letter height: 1/2 IN minimum. 49 2) Equipment designation as indicated on the Drawings (e.g., “Primary Sludge Pump 50

P-xxx”). 51 6. Piping systems: 52

a. Tag type: 53 1) Outdoor locations: Type G - Stenciling System. 54 2) Indoor locations: 55

a) Type D - Self-Adhesive Tape Tags and Signs. 56

Page 38: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 6

b) Type G - Stenciling System. 1 b. Fastener: Self. 2 c. Color: Per ASME A13.1. 3 d. Legend: 4

1) Letter height: Manufacturers standard for the pipe diameter. 5 2) Mark piping in accordance with ASME A13.1. 6 3) Use piping designation as indicated on the Drawings. 7 4) Arrow: Single arrow. 8

7. Equipment that starts automatically: 9 a. Tag type: 10

1) Type B2 - Nonmetallic Signs. 11 2) Type D - Self-Adhesive Tape Tags and Signs. 12

b. Fastener: 13 1) Type B2 - Screw or adhesive. 14 2) Type D - Self. 15

c. Size: 5 IN x 7 IN 16 d. Location: Pumps. 17 e. Legend: 18

1) OSHA Warning Sign. 19 2) Description of Warning: “THIS MACHINE STARTS AUTOMATICALLY”. 20

B. Instrumentation Systems: 21 1. Instrumentation Equipment (e.g., flow control valves, primary elements, etc.): 22

a. Tag type: 23 1) Outdoor locations: Type B1 - Square Nonmetallic Tags. 24 2) Indoor noncorrosive: 25

a) Type A1 - Round Metal Tags. 26 b) Type B1 - Square Nonmetallic Tags. 27

3) Indoor corrosive: 28 a) Stainless steel Type A1 - Round Metal Tags. 29 b) Type B1 - Square Nonmetallic Tags. 30

b. Fastener: 31 1) Type A1: Chain of the same material. 32 2) Type B1: Stainless steel chain. 33

c. Legend: 34 1) Letter height: 1/4 IN minimum. 35 2) Equipment ISA designation as indicated on the Drawings (e.g., “FIT-xxx”). 36

2. Enclosure for instrumentation and control equipment, (e.g., PLC control panels, etc.): 37 a. Tag type: Type C - Phenolic Name Plates. 38 b. Fastener: Screws. 39 c. Legend: 40

1) Letter height: 1/2 IN minimum. 41 2) Equipment name (e.g., "PLC CONTROL PANEL PCP-xxx"). 42

3. Components inside equipment enclosure, (e.g., PLC’s, control relays, contactors, and 43 timers): 44 a. Tag type: Type D - Self-Adhesive Tape Tags. 45 b. Fastener: Self. 46 c. Legend: 47

1) Letter height: 3/16 IN minimum. 48 2) Description or function of component (e.g., "PLC-xxx” or “CR-xxx"). 49

4. Through enclosure door mounted components (e.g., selector switches, controller digital 50 displays, etc.): 51 a. Tag type: Type C - Phenolic Name Plates. 52 b. Fastener: Screws. 53 c. Legend: 54

1) Letter height: 1/4 IN minimum. 55

Page 39: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 7

2) Component ISA tag number as indicated on the Drawings (e.g., “HS-xxx”). 1

C. HVAC Systems: 2 1. General: 3

a. Provide arrows and markers on ducts. 4 1) At 20 FT maximum centers along continuous lines. 5 2) At changes in direction (route) or obstructions. 6 3) At dampers, risers, branches, machinery or equipment. 7 4) Where ducts pass through floors, walls, ceilings, cladding assemblies and like 8

obstructions provide markers on both sides. 9 b. Position markers on both sides of duct with arrow markers pointing in flow direction. 10

1) If flow is in both directions use double headed arrow markers. 11 c. Apply tapes and stenciling in uniform manner parallel to ducts. 12

2. HVAC Equipment (e.g., unit heaters, exhaust fans, air handlers, etc.): 13 a. Tag type: 14

1) Type B2 - Nonmetallic Signs. 15 2) Type C - Phenolic Name Plates. 16

b. Fastener: Screws. 17 c. Legend: 18

1) Letter height: 1 IN minimum. 19 2) Equipment designation as indicated on the Drawings (e.g., "EF-xxx"). 20

3. Ductwork: 21 a. Tag type: 22

1) Type D - Self-Adhesive Tape Tags and Signs. 23 2) Type G - Stenciling System. 24

b. Fastener: Self. 25 c. Legend: 26

1) Letter height: 1 IN minimum. 27 2) Description of ductwork, (e.g., “AIR SUPPLY”). 28 3) Arrows: Single arrow. 29

4. Enclosure for instrumentation and control equipment, (e.g., fan control panels, etc.): 30 a. Tag type: Type C - Phenolic Name Plates. 31 b. Fastener: Screws. 32 c. Legend: 33

1) Letter height: 1/2 IN minimum. 34 2) Equipment designation as indicated on the Drawings (e.g., "FAN CONTROL 35

PANEL FCP-xxx"). 36 5. Wall mounted thermostats: 37

a. Tag type: Type D - Self-Adhesive Tape Tags and Signs. 38 b. Fastener: Self. 39 c. Legend: 40

1) Letter height: 3/16 IN minimum. 41 2) Description of equipment controlled (e.g., "UH-xxx" or AHU-xxx"). 42

6. Components inside equipment enclosure, (e.g., controller’s, control relays, contactors, and 43 timers): 44 a. Tag type: Type D - Self-Adhesive Tape Tags and Signs. 45 b. Fastener: Self. 46 c. Legend: 47

1) Letter height: 3/16 IN minimum. 48 2) Description or function of component (e.g., "CR-xxx"). 49

7. Through enclosure door mounted equipment (e.g., selector switches, controller digital 50 displays, etc.): 51 a. Tag type: Type C - Phenolic Name Plates. 52 b. Fastener: Screws. 53 c. Legend: 54

1) Letter height: 1/4 IN minimum. 55

Page 40: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 8

2) Component tag number as indicated on the Drawings or as defined by contractor 1 (e.g., “HS-xxx”). 2

D. Electrical Systems: 3 1. Trenches with ductbanks, direct-buried conduit, or direct-buried wire and cable. 4

a. Tag type: Type F - Underground Warning Tape. 5 b. Letter height: 1-1/4 IN minimum. 6 c. Location: 7

1) Where trench is 12 IN or more below finished grade: In trench 6 IN below 8 finished grade. 9

2) Where trench is less than 12 IN below finished grade: In trench 3 IN below 10 finished grade. 11

d. Electrical power (e.g., low and medium voltage): 12 1) Color: Red with black letters. 13 2) Legend: 14

a) First line: “CAUTION CAUTION CAUTION”. 15 b) Second line: “BURIED ELECTRIC LINE BELOW”. 16

e. Communications (e.g., telephone, instrumentation, LAN, SCADA): 17 1) Color: Orange with black letters. 18 2) Legend: 19

a) First line: “CAUTION CAUTION CAUTION”. 20 b) Second line: “BURIED COMMUNICATION LINE BELOW”. 21

2. Exterior pad mounted equipment (e.g., transformers, switchgear): 22 a. Tag type: Type D - Self-Adhesive Tape Tags. 23 b. Fastener: Self. 24 c. General legend: 25

1) Letter height: 26 a) First line: 1-1/2 IN minimum. 27 b) Subsequent lines: 1/2 IN minimum. 28

2) First line: Equipment name (e.g., "TRANSFORMER Txxx"). 29 3) Second line: System voltage (e.g., "13,800 V: 480/277 V"). 30

d. Each section/cubical legend: 31 1) Letter height: 1-1/2 IN minimum. 32 2) Description of source or load (e.g., "MAIN DISCONNECT" or "TO 33

SWITCHGEAR SGxxx" or "TO TRANSFORMER Txxx"). 34 3. Switchgear, switchboards and motor control centers: 35

a. Tag type: Type C - Phenolic Name Plates. 36 b. Fastener: Screws. 37 c. Main equipment legend: 38

1) Letter height: 39 a) First line: 1 IN minimum. 40 b) Subsequent lines: 3/8 IN minimum. 41

2) First line: Equipment name (e.g., "MAIN SWITCHBOARD MSBxxx"). 42 3) Second line: 43

a) Source of power (e.g., "FED FROM MCCxxx LOCATED IN ROOM xxx"). 44 b) Include the building name or number if the source is in another building. 45

4) Third line: System voltage and phase (e.g., “480/277 V, 3PH”). 46 d. Main and feeder device legend: 47

1) Letter height: 3/8 IN minimum. 48 2) Description of load (e.g., “MAIN DISCONNECT”, "PUMP Pxxx" or 49

"PANELBOARD HPxxx"). 50 4. Panelboards and transformers: 51

a. Tag type: Type C - Phenolic Name Plates. 52 b. Fastener: Screws. 53

Page 41: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 9

c. Legend: 1 1) Letter height: 2

a) First line: 3/8 IN minimum. 3 b) Subsequent lines: 3/16 IN minimum. 4

2) First line: Equipment name (e.g., "PANELBOARD LPxxx" or "TRANSFORMER 5 Txxx"). 6

3) Second line (panelboards only): System voltage and phase (e.g., “208/120V, 7 3PH”). 8

4) Third line: 9 a) Source of power (e.g., "FED FROM MCCxxx LOCATED IN ROOM xxx"). 10 b) Include the building name or number if the source is in another building. 11

5. Transfer switches: 12 a. Tag type: Type C - Phenolic Name Plates. 13 b. Fastener: Screws. 14 c. Legend: 15

1) Letter height: 16 a) First line: 3/8 IN minimum. 17 b) Subsequent lines: 3/16 IN minimum. 18

2) First line: Equipment name (e.g., "AUTOMATIC TRANSFER SWITCH 19 ATSxxx"). 20

6. Safety switches, separately mounted circuit breakers and motor starters, VFD’s, etc.: 21 a. Tag type: Type C - Phenolic Name Plates. 22 b. Fastener: Screws. 23 c. Legend: 24

1) Letter height: 1/4 IN minimum. 25 2) First line: Description of load equipment is connected to (e.g., "PUMP Pxxx"). 26

7. Enclosure for instrumentation and control equipment, (e.g., lighting control panels, etc.): 27 a. Tag type: Type C - Phenolic Name Plates. 28 b. Fastener: Screws. 29 c. Legend: 30

1) Letter height: 1/2 IN minimum. 31 2) Equipment name (e.g., "LIGHTING CONTROL PANEL LCPxxx"). 32

8. Components inside equipment enclosures (e.g., circuit breakers, fuses, control power 33 transformers, control relays, contactors, timers, etc.): 34 a. Tag type: Type D - Self-Adhesive Tape Tags and Signs. 35 b. Fastener: Self. 36 c. Legend: 37

1) Letter height: 3/16 IN minimum. 38 2) Description or function of component (e.g., "M-xxx”, “CR-xxx” or “TR-xxx"). 39

9. Through enclosure door mounted equipment (e.g., selector switches, controller digital 40 displays, etc.): 41 a. Tag type: Type C - Phenolic Name Plates. 42 b. Fastener: Screws. 43 c. Legend: 44

1) Letter height: 1/4 IN minimum. 45 2) Component tag number as indicated on the Drawings or as defined by contractor 46

(e.g., “HS-xxx”). 47 10. Conductors in control panels and in pull or junction boxes where multiple circuits exist. 48

a. Tag type: Type D - Self-Adhesive Tape Tags. 49 b. Fastener: Self. 50 c. Tag conductor at both ends. 51 d. Legend: 52

1) Letter height: 1/8 IN minimum. 53 2) Circuit number or wire number as scheduled on the Drawings or as furnished with 54

the equipment. 55

Page 42: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 10

11. Conductors in cable trays. 1 a. Tag type: Type D - Self-Adhesive Tape Tags. 2 b. Fastener: Self. 3 c. Tag all conductors at the same location in the tray at 50FT maximum intervals. 4 d. Legend: 5

1) Letter height: 1/8 IN minimum. 6 2) Circuit number or wire number as scheduled on the Drawings. 7

12. Conductors in handholes and manholes. 8 a. Tag type: Type A3 - Metal Tape Tags. 9 b. Fastener: Nylon strap. 10 c. Tag conductor at both ends. 11 d. Legend: 12

1) Letter height: 1/8 IN minimum. 13 2) Circuit number or wire number as scheduled on the Drawings. 14

13. Grounding conductors associated with grounding electrode system in accordance with the 15 following: 16 a. Tag type: Type D - Self-Adhesive Tape Tags. 17 b. Fastener: Self. 18 c. Legend: 19

1) Letter height: 1/8 IN minimum. 20 2) Function of conductor (e.g., "MAIN BONDING JUMPER", "TO GROUND 21

RING", "TO MAIN WATER PIPE"). 22 14. Flash protection for switchboards, panelboards, industrial control panels and motor control 23

centers: 24 a. Tag type: Type D - Self-Adhesive Tape Signs. 25 b. Fastener: Self. 26 c. Legend: Per NFPA 70. 27

15. Power cable trays: 28 a. Tag type: Type D - Self-Adhesive Tape Tags and Signs. 29 b. Fastener: Self. 30 c. Size: 1-3/4 IN x 2-1/2 IN. 31 d. Location: 32

1) Every 50 FT maximum. 33 2) Label each barriered section of tray. 34

e. Legend: 35 1) OSHA Danger Sign. 36 2) Description of Danger, (e.g., “UP TO 480 VOLTS”). 37

16. Entrances to electrical rooms: 38 a. Tag type: Type B2 - Nonmetallic Signs. 39 b. Fastener: Screw or adhesive. 40 c. Size: 5 IN x 7 IN. 41 d. Location: Each door to room. 42 e. Legend: 43

1) OSHA Danger Sign. 44 2) Description of Danger: “HIGH VOLTAGE, AUTHORIZED PERSONNEL 45

ONLY”. 46 17. Equipment where more than one (1) voltage source is present: 47

a. Tag type: 48 1) Type B2 - Nonmetallic Signs. 49 2) Type D - Self-Adhesive Tape Signs. 50

b. Fastener: 51 1) Screw or adhesive. 52 2) Self. 53

c. Size: 1-3/4 IN x 2-1/2 IN. 54 d. Location: Exterior face of enclosure or cubical. 55

Page 43: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 11

e. Legend: 1 1) OSHA Danger Sign. 2 2) Description of Danger: “MULTIPLE VOLTAGE SOURCES”. 3

3.3 HAZARD AND SAFETY SIGNS 4

A. Provide 5 Hazard and Safety Signs: 5 1. Type B2. 6 2. Inscription as directed by Owner. 7

END OF SECTION 8

9

Page 44: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - IDENTIFICATION DEVICES 10400 - 12

1

Page 45: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SIGNAGE 10444 - 1

2014/10/07 1

SECTION 10444 2

SIGNAGE 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Room identification signs. 7 2. Other identification signs: 8

B. Related Specification Sections include but are not necessarily limited to: 9 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 10 2. Division 01 - General Requirements. 11 3. Section 10400 - Identification Devices. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. Americans with Disabilities Act (ADA): 15

a. Accessibility Guidelines for Buildings and Facilities (ADAAG). 16 2. ASTM International (ASTM): 17

a. B26, Standard Specification for Aluminum-Alloy Sand Castings. 18 3. Building code: 19

a. International Code Council (ICC): 20 1) International Building Code and associated standards, 2003 Edition including all 21

amendments, referred to herein as Building Code. 22

1.3 DEFINITIONS 23

A. Wet and/or Corrosive Areas: For the purposes of this Specification Section, the following rooms 24 or areas are considered wet and/or corrosive: 25

1.4 SUBMITTALS 26

A. Shop Drawings: 27 1. See Specification Section 01340 for requirements for the mechanics and administration of 28

the submittal process. 29 2. Product technical data including: 30

a. Acknowledgement that products submitted meet requirements of standards referenced. 31 b. Manufacturer's installation instructions. 32 c. Color charts for Engineer's color selection. 33

1) Color selection shall be made from manufacturer's complete color line including all 34 premium and special colors. 35

3. Schedule of all signs indicating text and graphics. 36 4. Layout drawings of all signage showing size, letter style, text, border, finish, and installation 37

detail. 38 a. Provide drawings for: 39

1) Room identification signs. 40 2) Aluminum letters. 41

B. Samples: 42 1. Room identification signs. 43 2. Aluminum letters. 44

Page 46: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SIGNAGE 10444 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Room identification signs: 5

a. Andco. 6 b. ASE - Architectural Signs and Engraving. 7 c. ASI Sign Systems. 8 d. Best Manufacturing Co. 9 e. Mohawk Engraving Co., Inc. 10 f. Nelson-Harkins. 11 g. Southwell. 12 h. The Supersine Co. 13

B. Submit request for substitution in accordance with Specification Section 01640. 14

2.2 MATERIALS 15

A. Room Identification Signs: 16 1. Exterior: Aluminum or fiberglass suitable for raised lettering and Braille. 17

2.3 FABRICATION 18

A. Room Identification Signs: 19 1. General: 20

a. Raised text, border and graphics. 21 1) Minimum 1/32 IN height. 22 2) Provide international graphic symbology for all toilet, locker and shower rooms or 23

combinations thereof, and for unisex toilet rooms and stairs. 24 3) Provide handicap symbol on all signs for rooms meeting handicap requirements. 25

b. Grade 2 Braille. 26 c. Finish: Eggshell. 27

1) Color: To be selected. 28 d. Text: 29

1) Typeface: Sans Serif. 30 2) Size: Minimum 3/4 IN high. 31 3) Line 1: Collector Well. 32 4) Line 2: Authorized Personnel Only. 33

e. Size: 4 IN high (at sides) and 5 IN at high point of radius top x 6 IN wide. 34 f. Exterior signs shall be rated for exterior use. 35 g. All signs shall comply with requirements of ADA. 36

B. Hazard Communication Signage (OSHA signage): See Specification Section 10400. 37

2.4 MAINTENANCE MATERIALS 38

A. Where stenciled markers are provided, clean and retain stencils after completion and include in 39 extra stock, along with required stock of paints and applicators. 40

Page 47: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SIGNAGE 10444 - 3

PART 3 - EXECUTION 1

3.1 INSTALLATION 2

A. Room Identification Signs: 3 1. Install signs on walls adjacent to the latch side of doors using foam tape for interior signs 4

and stainless steel screws (minimum of two (2)) for exterior signs. 5 a. Stainless steel screws shall be painted to match sign color. 6

2. Where no adjacent wall space is available, mount signs on nearest adjacent wall. 7 a. Mounting of signs shall be such that a person may approach to within 3 IN of sign 8

without encountering any protruding objects or standing in swing of door travel. 9 3. Mount 60 IN above finish floor to centerline of sign. 10

END OF SECTION 11

12

Page 48: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SIGNAGE 10444 - 4

1

Page 49: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - FIRE EXTINGUISHER 10520 - 1

2014/10/07 1

SECTION 10520 2

FIRE EXTINGUISHER 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Fire extinguishers. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10

1.2 QUALITY ASSURANCE 11

A. Referenced Standards: 12 1. National Fire Protection Association (NFPA): 13

a. 10, Standard for Portable Fire Extinguishers. 14 2. Underwriters Laboratories, Inc. (UL): 15

a. Building Materials Directory. 16

1.3 DEFINITIONS 17

A. Authority Having Jurisdiction (AHJ): Building official, fire chief, fire marshal or other 18 individual having statutory authority. 19

1.4 SUBMITTALS 20

A. Shop Drawings: 21 1. See Specification Section 01340 for requirements for the mechanics and administration of 22

the submittal process. 23 2. Product technical data including: 24

a. Acknowledgement that products submitted meet requirements of standards referenced. 25 b. Manufacturer's installation instructions. 26

B. Operation and Maintenance Manuals: 27 1. See Specification Section 01342 for requirements for: 28

a. The mechanics and administration of the submittal process. 29 b. The content of Operation and Maintenance Manuals. 30

1.5 DELIVERY, STORAGE, AND HANDLING 31

A. Deliver and install filled and charged extinguishers just prior to building occupancy. 32

PART 2 - PRODUCTS 33

2.1 ACCEPTABLE MANUFACTURERS 34

A. Subject to compliance with the Contract Documents, the following manufacturers are 35 acceptable: 36 1. Fire extinguishers: 37

a. J. L. Industries. 38 b. Larsen's Manufacturing Co. 39 c. Modern Metal Products. 40 d. Amerex Corporation. 41

Page 50: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - FIRE EXTINGUISHER 10520 - 2

e. Ansul Fire Protection. 1 f. Walter Kidde. 2 g. Potter - Roemer Inc. 3

2. Fire extinguisher signs: 4 a. Seton. 5

B. Submit request for substitution in accordance with Specification Section 01640. 6

2.2 MANUFACTURED UNITS 7

A. Fire Extinguisher (FEXT): 8 1. Steel bodied, all metal top (head) and valves. 9 2. Multi-purpose dry chemical with hose and horn. 10 3. Provide one (1) UL rated 10A-120BC extinguisher for each fire extinguisher location 11

(FEXT) indicated on Drawings. 12 4. Finish: Red with epoxy finish coat. 13

B. Wall Brackets: 14 1. Bracket type to fit specified extinguisher. 15 2. Furnish bracket for each extinguisher not in cabinet. 16 3. Bracket to be finished in red or black enamel. 17

C. Fire Extinguisher Signage: 18 1. Single faced: SETON #21999. 19

PART 3 - EXECUTION 20

3.1 INSTALLATION 21

A. Install products in accordance with manufacturer's instructions and NFPA 10. 22 1. Install units with extinguisher top not over 48 IN above floor. 23 2. Install wall brackets to concrete or masonry substrate with self-tapping concrete anchors. 24

a. See Specification Section 05505. 25

B. Fire extinguisher locations shown on Drawings are approximate locations. 26 1. Verify all extinguisher mounting locations with the AHJ. 27

C. Provide "FIRE EXTINGUISHER" sign for each extinguisher location. 28 1. Provide single or double faced sign to provide optimum visibility for extinguisher location. 29

END OF SECTION 30

Page 51: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ALUMINUM CANOPIES 10530 - 1

2014/10/07 1

SECTION 10530 2

ALUMINUM CANOPIES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Prefabricated aluminum canopies. 7

B. Related Specification Sections: 8 1. Division 00 - Bidding Requirements, Contract Forms and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10

1.2 QUALITY ASSURANCE 11

A. Referenced Standards: 12 1. American Architectural Manufacturers Association (AAMA): 13

a. 2604, Voluntary Specification, Performance Requirements and Test Procedures for 14 High Performance Organic Coatings on Aluminum Extrusions and Panels. 15

2. Building code: 16 a. International Code Council (ICC): 17

1) International Building Code and associated standards, 2003 Edition including all 18 amendments, referred to herein as Building Code. 19

B. Qualifications: 20 1. Engineer for contractor-designed canopy systems and components: Professional Civil or 21

Structural engineer licensed in the State of South Dakota. 22

1.3 SUBMITTALS 23

A. Shop Drawings: 24 1. See Specification Section 01340 for requirements for the mechanics and administration of 25

the submittal process. 26 2. Product technical data including: 27

a. Acknowledgement that products submitted meet requirements of standards referenced. 28 3. Connections. 29 4. Manufacturer's standard load tables. 30 5. Design calculations prepared and signed by an Engineer registered in the State where 31

project is located. 32 a. Calculations shall include all connections to structure. 33 b. Indicate design live loads. 34 c. Engineer will review for general compliance with Contract Documents. 35

6. Fabrication and/or layout drawings. 36 a. Submit drawings for all fabrications and assemblies. 37

1) Include erection drawings, plans, sections, details and connection details. 38

B. Samples: 39 1. Submit three (3) color samples a minimum of 4 IN x 4 IN one of which to be retained by the 40

Engineer. Color chart is not acceptable. 41

1.4 DELIVERY, STORAGE, AND HANDLING 42

A. Deliver and handle fabrications to avoid damage. 43

B. Store above ground on skids or other supports to keep items free of dirt and other foreign debris 44 and to protect against corrosion. 45

Page 52: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ALUMINUM CANOPIES 10530 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. E.L. Burns. 5 2. Dittmer. 6 3. Perfection. 7 4. Mapes Panels. 8 5. Superior Metal. 9 6. Peachtree Protective Covers. 10

B. Submit request for substitution in accordance with Specification Section 01640. 11

2.2 MATERIALS 12

A. Basis of Design: Mapes Canopies, Super Lumideck series. 13

B. Structural Framing System: 14 1. All extruded aluminum system, aluminum alloy 6063-T6. 15

a. Yield: 31,000 psi. 16 b. Ultimate strength: 35,000 psi. 17 c. Hanger rod configuration: Perpendicular, see Drawings. 18

2. Radius-cornered aluminum tubular extrusions of sizes shown on the Drawings. 19

C. Deck: 20 1. Extruded aluminum alloy 6063-T6. 21

a. Interlocking Decking: 2-3/4 IN extruded aluminum. 22 b. Decking thickness: 0.078 IN. 23

2. Size and profile as shown on the Drawings. 24

D. Fascia: 25 1. Extruded aluminum alloy 6063-T6. 26 2. Standard 8 IN extruded J style. 27

E. Fasteners: 28 1. Deck: Manufacturer's standard. 29 2. Trim: Aluminum rivets. 30 3. Others: Stainless steel. 31

F. Finish: 32 1. Canopy Assembly: 33

a. Fluoropolymer coating: 34 1) 70 percent PVDF resin based fluoropolymer, AAC12C42R1, custom color as 35

selected by Engineer. 36 a) Two (2) coat application: Comply with AAMA 2604. 37 b) Color: Antique Bronze. 38

2.3 PERFORMANCE AND DESIGN REQUIREMENTS 39

A. Design Loads: 40 1. Design wind and snow loading is shown on the Drawings. 41

a. Design shall consider uplift forces on canopy due to wind loading. 42 2. Collateral loads: Additional loads imposed by other materials or systems identified in 43

Contract Documents. 44

B. Structural Design: 45 1. Prepare complete structural design calculations for canopy members. 46

a. All connections shall be mechanical fasteners with a minimum shear stress of 350 LBS. 47

Page 53: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ALUMINUM CANOPIES 10530 - 3

C. Expansion and Contraction: 1 1. Roof deck and fascia shall be designed with a maximum of one (1) end of each member 2

fastened rigidly. 3 a. All other fasteners shall allow movement of deck and fascia. 4

2. Deck and fascia shall be designed to allow movement for temperature changes of at least 5 200 DegF. 6

2.4 FABRICATION AND MANUFACTURE 7

A. Prefabricated canopies shall be shipped in preassembled sections for ease of installation. 8

B. Bents: 9 1. Columns and beams heliarc welded together to form one-piece rigid bents. 10 2. Provide beam ties at every other deck projection. 11 3. Water shall drain into gutters. 12

a. Downspouts shall carry water from gutters to grade level discharge. 13

C. Deck: 14 1. Interlocking, self-flashing joints. 15

a. Joints fastened at 8 IN OC. 16 2. Cambered to neutralize deflection and to provide drainage. 17 3. Slope toward gutter. 18

D. Fascia: 19 1. Manufacturer's standard. 20 2. Allow for expansion and contraction. 21 3. Provide square wall escutcheons plates at all hanger rod locations. Form escutcheons to the 22

texture of the wall. 23

E. Gutters and Downspouts: 24 1. Manufacturer’s standard. 25 2. Watertight and secured. 26 3. Drain away from existing structures. 27 4. Concealed drainage. Water shall drain from covered surfaces into intermediate trough and 28

be directed to Downspout from Fascia. 29 5. Drainage outlet location at door canopy locations shall be placed on the hinge side of the 30

door. 31

PART 3 - EXECUTION 32

3.1 EXAMINATION 33

A. Examine building surfaces to which canopy will connect. 34

B. Coordinate with responsible trade to perform corrective work on unsatisfactory footings or 35 surfaces. 36

C. Commencement of Work by installer is acceptance of existing conditions. 37

3.2 ERECTION 38

A. Erect protective covers in accordance with manufacturer's installation instructions. 39

B. Set bents plumb, straight, and true to line, adequately braced to maintain position until grout has 40 cured. 41

C. Keep aluminum surfaces from direct contact with ferrous metal or other incompatible materials 42 by applying one (1) coat of zinc chromate primer. 43 1. Follow with two (2) coats of aluminum paint. 44 2. In lieu of aluminum paint, one (1) coat of high-build bituminous paint applied to 1/16 IN 45

(1.6 mm) thickness may be used. 46

Page 54: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ALUMINUM CANOPIES 10530 - 4

3.3 CLEANING 1

A. Clean surfaces soiled by Work as recommended by manufacturer. 2

B. Remove surplus materials and debris from the site. 3

3.4 PROTECTION 4

A. Protect finished aluminum surfaces from damage due to subsequent construction operations. 5

END OF SECTION 6

Page 55: City of Yankton, SD

D I V I S I O N 1 1 EQUIPMENT

Page 56: City of Yankton, SD
Page 57: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 1

2014/08/14 1

SECTION 11005 2

EQUIPMENT: BASIC REQUIREMENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Requirements of this Specification Section apply to all equipment provided on the Project 7

including those found in other Divisions even if not specifically referenced in individual 8 "Equipment" Articles of those Specification Sections. 9

B. Related Specification Sections include but are not necessarily limited to: 10 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 11 2. Division 01 - General Requirements. 12 3. Section 03308 - Concrete, Materials and Proportioning. 13 4. Section 05505 - Metal Fabrications. 14 5. Section 07900 - Joint Sealants. 15 6. Section 09905 - Painting and Protective Coatings. 16 7. Section 10400 - Identification Devices. 17 8. Division 11 - Equipment. 18 9. Division 12 - Furnishings. 19 10. Section 13442 - Primary Elements and Transmitters. 20 11. Division 14 - Conveying Systems. 21 12. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 22 13. Division 16 - Electrical. 23

1.2 QUALITY ASSURANCE 24

A. Referenced Standards: 25 1. American Bearing Manufacturers Association (ABMA). 26 2. American Gear Manufacturers Association (AGMA). 27 3. ASTM International (ASTM): 28

a. F593, Standard Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs. 29 4. Hydraulic Institute (HI): 30

a. 9.6.4, Centrifugal and Vertical Pumps for Vibration Measurements and Allowable 31 Valves. 32

5. International Electrotechnical Commission (IEC). 33 6. Institute of Electrical and Electronics Engineers, Inc. (IEEE). 34 7. International Organization for Standardization (ISO): 35

a. 1940, Mechanical Vibration - Balance Quality Requirements for Rotors in a Constant 36 (Rigid) State - Part 1: Specification and Verification of Balance Tolerances. 37

8. National Electrical Manufacturers Association (NEMA): 38 a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 39 b. ICS 6, Enclosures for Industrial Control and System. 40 c. MG 1, Motors and Generators. 41

9. InterNational Electrical Testing Association (NETA): 42 a. ATS, Acceptance Testing Specification for Electrical Power Distribution Equipment 43

and Systems. 44 10. National Fire Protection Association (NFPA): 45

a. 70, National Electrical Code (NEC): 46 1) Article 430, Motors, Motor Circuits, and Controllers. 47

11. National Institute for Certification in Engineering Technologies (NICET). 48 12. National Institute of Standards and Technology (NIST). 49

Page 58: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 2

13. Occupational Safety and Health Administration (OSHA): 1 a. 29 CFR 1910, Occupational Safety and Health Standards, referred to herein as OSHA 2

Standards. 3 14. Underwriters Laboratories, Inc. (UL). 4

a. 508, Standard for Safety Industrial Control Equipment. 5 b. 508A, Standard for Safety Industrial Control Panels. 6

15. Vibration Institute. 7

B. Vibration Testing Program: 8 1. Testing firm: 9

a. An independent firm performing, as the sole or principal part of its business for a 10 minimum of 10 years, the inspection, testing, calibration, and adjusting of systems. 11

b. Must have an established monitoring and testing equipment calibration program with 12 accuracy traceable in an unbroken chain, according to NIST. 13

2. Field personnel: 14 a. Minimum of one (1) year field experience covering all phases of field vibration testing 15

and data gathering. 16 b. Qualified Vibration Category I certification from the Vibration Institute. 17

3. Analysis personnel: 18 a. Minimum three (3) years combined field testing and data analysis experience. 19 b. Qualified Vibration Category II certification from the Vibration Institute. 20

C. Electrical Equipment and Connections Testing Program: 21 1. Testing firm: 22

a. An independent firm performing, as the sole or principal part of its business for a 23 minimum of 10 years, the inspection, testing, calibration , and adjusting of systems. 24

b. Must have an established monitoring and testing equipment calibration program with 25 accuracy traceable in an unbroken chain, according to NIST. 26

2. Field personnel: 27 a. Minimum of one (1) year field experience covering all phases of electrical equipment 28

inspection, testing, and calibration. 29 b. Relay test technician having previous experience with testing and calibration of relays 30

of the same manufacturer and type used on project and proficient in setting and testing 31 the types of protection elements used. 32

c. Supervisor certified by NETA or NICET. 33 3. Analysis personnel: 34

a. Minimum three (3) years combined field testing and data analysis experience. 35 b. Supervisor certified by NETA or NICET. 36

D. Miscellaneous: 37 1. A single manufacturer of a "product" to be selected and utilized uniformly throughout 38

Project even though: 39 a. More than one (1) manufacturer is listed for a given "product" in Specifications. 40 b. No manufacturer is listed. 41

2. Equipment, electrical assemblies, related electrical wiring, instrumentation, controls, and 42 system components shall fully comply with specific NEC requirements related to area 43 classification and to NEMA 250 and NEMA ICS 6 designations and defined in Division 16. 44

3. Variable speed equipment applications: The driven equipment manufacturer shall have 45 single source responsibility for coordination of the equipment and VFD system and sure 46 their compatibility. 47

1.3 DEFINITIONS 48

A. Product: Manufactured materials and equipment. 49

B. Major Equipment Supports - Supports for Equipment: 50 1. Located on or suspended from elevated slabs with supported equipment weighing 2000 LBS 51

or greater, or; 52

Page 59: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 3

2. Located on or suspended from roofs with supported equipment weighing 500 LBS or 1 greater, or; 2

3. Located on slab-on-grade or earth with supported equipment weighing 5000 LBS or more. 3

C. Equipment: 4 1. One (1) or more assemblies capable of performing a complete function. 5 2. Mechanical, electrical, instrumentation or other devices requiring an electrical, pneumatic, 6

electronic or hydraulic connection. 7 3. Not limited to items specifically referenced in "Equipment" articles within individual 8

Specifications. 9

D. Installer or Applicator: 10 1. Installer or applicator is the person actually installing or applying the product in the field at 11

the Project site. 12 2. Installer and applicator are synonymous. 13

1.4 SUBMITTALS 14

A. Shop Drawings: 15 1. General for all equipment: 16

a. See Specification Section 01340 for requirements for the mechanics and administration 17 of the submittal process. 18

b. Data sheets that include manufacturer's name and complete product model number. 19 1) Clearly identify all optional accessories that are included. 20

c. Acknowledgement that products submitted comply with the requirements of the 21 standards referenced. 22

d. Manufacturer's delivery, storage, handling, and installation instructions. 23 e. Equipment identification utilizing numbering system and name utilized in Drawings. 24 f. Equipment installation details: 25

1) Location of anchorage. 26 2) Type, size, and materials of construction of anchorage. 27 3) Anchorage setting templates. 28 4) Manufacturer's installation instructions. 29

g. Equipment area classification rating. 30 h. Shipping and operating weight. 31 i. Equipment physical characteristics: 32

1) Dimensions (both horizontal and vertical). 33 2) Materials of construction and construction details. 34

j. Equipment factory primer and paint data. 35 k. Manufacturer's recommended spare parts list. 36 l. Equipment lining and coatings. 37 m. Equipment utility requirements include air, natural gas, electricity, and water. 38 n. Ladders and platforms provided with equipment: 39

1) Certification that all components comply fully with OSHA requirements. 40 2) Full details of construction/fabrication. 41 3) Scaled plan and sections showing relationship to equipment. 42

2. Mechanical and process equipment: 43 a. Operating characteristics: 44

1) Technical information including applicable performance curves showing specified 45 equipment capacity, rangeability, and efficiencies. 46

2) Brake horsepower requirements. 47 3) Copies of equipment data plates. 48

b. Piping and duct connection size, type and location. 49 c. Equipment bearing life certification. 50 d. Equipment foundation data: 51

1) Equipment center of gravity. 52

Page 60: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 4

2) Criteria for designing vibration, special or unbalanced forces resulting from 1 equipment operation. 2

3. Electric motor: 3 a. Motor manufacturer and model number. 4 b. Complete motor nameplate data. 5 c. Weight. 6 d. NEMA design type. 7 e. Enclosure type. 8 f. Frame size. 9 g. Winding insulation class and temperature rise. 10 h. Starts per hour. 11 i. Performance data: 12

1) Guaranteed minimum efficiencies at 100 percent, 75 percent, and 50 percent of full 13 load 14

2) Guaranteed minimum power factor at 100 percent, 75 percent, and 50 percent of 15 full load. 16

j. Fabrication and/or layout drawings: 17 1) Dimensioned outlined drawing. 18 2) Connection diagrams including accessories (strip heaters, thermal protection, etc.). 19

k. Certifications: 20 1) When utilized with a variable frequency controller, certify motor is inverter duty 21

and the controller and motor are compatible. 22 a) Include minimum speed at which the motor may be operated for the driven 23

machinery. 24 l. Electrical gear: 25

1) Unless specified in a narrow-scope Specification Section, provide the following: 26 a) Equipment ratings: Voltage, continuous current, kVa, watts, short circuit with 27

stand, etc., as applicable. 28 2) Control panels: 29

a) Panel construction. 30 b) Point-to-point ladder diagrams. 31 c) Scaled panel face and subpanel layout. 32 d) Technical product data on panel components. 33 e) Panel and subpanel dimensions and weights. 34 f) Panel access openings. 35 g) Nameplate schedule. 36 h) Panel anchorage. 37

4. Systems schematics and data: 38 a. Provide system schematics where required in system specifications. 39

1) Acknowledge all system components being supplied as part of the system. 40 2) Utilize equipment, instrument and valving tag numbers defined in the Contract 41

Documents for all components. 42 3) Provide technical data for each system component showing compliance with the 43

Contract Document requirements. 44 4) For piping components, identify all utility connections, vents and drains which will 45

be included as part of the system. 46 5. For factory painted equipment, provide paint submittals in accordance with Specification 47

Section 09905. 48 6. Qualifications for : 49

a. Vibration testing firm and personnel. 50 b. Electrical equipment and connections testing firm and personnel. 51

7. Testing plans, in accordance with PART 3 of this Specification Section: 52 a. Vibration testing. 53 b. Electrical equipment and connection testing. 54

Page 61: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 5

B. Operation and Maintenance Manuals: 1 1. See Specification Section 01 3304 for requirements for: 2

a. The mechanics and administration of the submittal process. 3 b. The content of Operation and Maintenance Manuals. 4

C. Informational Submittals: 5 1. Sample form letter for equipment field certification. 6 2. Certification that equipment has been installed properly, has been initially started up, has 7

been calibrated and/or adjusted as required, and is ready for operation. 8 3. Certification for major equipment supports that equipment foundation design loads shown 9

on the Drawings or specified have been compared to actual loads exhibited by equipment 10 provided for this Project and that said design loadings are equal to or greater than the loads 11 produced by the equipment provided. 12

4. Field noise testing reports if such testing is specified in narrow-scope Specification 13 Sections. 14

5. Notification, at least one (1) week in advance, that motor testing will be conducted at 15 factory. 16

6. Certification from equipment manufacturer that all manufacturer-supplied control panels 17 that interface in any way with other controls or panels have been submitted to and 18 coordinated with the supplier/installer of those interfacing systems. 19

7. Motor test reports. 20 8. Certification prior to Project closeout that electrical panel drawings for manufacturer-21

supplied control panels truly represent panel wiring including any field-made modifications. 22 9. Provide three (3) bound final written reports documenting vibration monitoring and testing 23

for specified equipment. 24 a. Include the acceptance criteria of all equipment tested. 25 b. Provide individual tabbed sections for information associated with each piece of tested 26

equipment. 27 10. Preliminary field quality control testing format to be used as a basis for final field quality 28

control reporting. 29 11. Testing and monitoring reports in accordance with PART 3 of this Specification Section. 30 12. Certification that driven equipment and VFD are compatible. 31

PART 2 - PRODUCTS 32

2.1 ACCEPTABLE MANUFACTURERS 33

A. Subject to compliance with the Contract Documents, the following manufacturers are 34 acceptable: 35 1. Motors: 36

a. U.S. Motors. 37 b. General Electric 38 c. Marathon Electric 39

B. Submit request for substitution in accordance with Specification Section 01640. 40

2.2 MANUFACTURED UNITS 41

A. General: 42 1. Furnished equipment manufacturer’s field quality control services and testing as specified in 43

the individual equipment Specification Sections. 44 2. Execute pre-demonstration requirements in accordance with Specification Section 01650. 45 3. Perform and report on all tests required by the equipment manufacturer’s Operation and 46

Maintenance Manual. 47 4. Provide testing of electrical equipment and connections in accordance with Division 16. 48

Page 62: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 6

5. Equip testing and analysis personnel with all appropriate project related reference material 1 required to perform tests, analyze results, and provide documentation including, but not 2 limited to: 3 a. Contract Drawings and Specifications. 4 b. Related construction change documentation. 5 c. Approved Shop Drawings. 6 d. Approved Operation and Maintenance Manuals. 7 e. Other pertinent information as required. 8

B. Equipment Monitoring and Testing Plans: 9 1. Approved in accordance with Shop Drawing submittal schedule. 10 2. Included as a minimum: 11

a. Qualifications of firm, field personnel, and analysis personnel doing the Work. 12 b. List and description of testing and analysis equipment to be utilized. 13 c. List of all equipment to be testing, including: 14

1) Name and tag numbers identified in the Contract Documents. 15 2) Manufacturer’s serial numbers. 16 3) Other pertinent manufacturer identification, 17

C. Instruments Used in Equipment and Connections Quality Control Testing: 18 1. Minimum calibration frequency: 19

a. Field analog instruments: Not more than 6 months. 20 b. Field digital instruments: Not more than 12 months. 21 c. Laboratory instruments: Not more than 12 months. 22 d. If instrument manufacturer’s calibration requirements are more stringent, those 23

requirements shall govern. 24 2. Carry current calibration status and labels on all testing instruments. 25 3. See individual testing programs for additional instrumentation compliance requirements. 26

D. Testing and Monitoring Program Documentation: 27 1. Provide reports with tabbed sections for each piece of equipment tested. 28 2. Include all testing results associated with each piece of equipment under that equipment’s 29

tabbed section. 30 a. Include legible copies of all forms used to record field test information. 31

3. Prior to start of testing, submit one (1) copy of preliminary report format for Engineer 32 review and comment 33 a. Include data gathering and sample test report forms that will be utilized. 34

4. In the final report, include as a minimum, the following information for all equipment 35 tested: 36 a. Equipment identification, including: 37

1) Name and tag numbers identified in the Contract Documents. 38 2) Manufacturer’s serial numbers. 39 3) Other pertinent manufacturer identification, 40

b. Date and time of each test. 41 c. Ambient conditions including temperature, humidity, and precipitation. 42 d. Visual inspection report. 43 e. Description of test and referenced standards, if any, followed while conducting tests. 44 f. Results of initial and all retesting. 45 g. Acceptance criteria. 46 h. “As found” and “as left” conditions. 47 i. Corrective action, if required, taken to meet acceptance. 48 j. Verification of corrective action signed by the Contractor, equipment supplier, and 49

Owner’s representative. 50 k. Instrument calibration dates of all instruments used in testing. 51

5. Provide three (3) bound final reports prior to Project final completion. 52

Page 63: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 7

E. Vibration Monitoring and Testing Program: 1 1. Perform vibration monitoring and testing for equipment specified in other Divisions during 2

the Equipment Demonstration Period. 3 2. Provide third party vibration testing on all rotating and reciprocating equipment having 4

driver 25 HP and greater. 5 3. Additional requirements for vibration monitoring and testing equipment: 6

a. Frequency response: 0.18 Hz to 25 kHz. 7 b. Resolution: 6400 lines. 8 c. Amplitude range: 18 bit for 96 dB dynamic range. 9 d. Supports measurements of acceleration, velocity, displacement, envelope demodulation 10

for bearing defect detection. 11 e. Capable of two-place computer balancing. 12 f. Requirements for vibration sensor: 13

1) Sensitivity: +/- 5 percent at 25 DegC= 100 mV/g. 14 2) Acceleration range: 80 g peak. 15 3) Amplitude nonlinearity: 1 percent. 16 4) Frequency response: 17

a) +/- 5 percent = 3-5000 Hz. 18 b) +/- 10 percent = 1-9000 Hz. 19

5) Permanently attach vibration test and monitoring mounting pads to mechanical 20 equipment at location recommended by the equipment manufacturer or as 21 recommended by the testing firm. 22

6) Acceptability of equipment conditions, except pumps, based on ISO 1940-1 23 Balance Quality Grade G2.5 criteria. 24

7) Acceptability of pumping equipment to be based on the latest edition of HI 9.6.4 25 criteria. 26

8) Repair or replace equipment shown to be out of range of the acceptable tolerance 27 until the equipment meets or exceeds acceptability standards. 28

F. Electrical Equipment and Connections Testing Program: 29 1. Perform testing on Division 16 equipment and connections in accordance with Division 16 30

requirements. 31 2. Testing of motors: 32

a. After installation and prior to energizing the motor, perform inspections and tests per 33 NETA ATS 7.15 for all motors 100 HP or above. 34

b. Bump motor to check for correct rotation. 35 3. Repair or replace equipment shown to be out of range of the acceptable tolerance until the 36

equipment meets or exceeds acceptability standards. 37

G. Other Testing: 38 1. Perform tests and inspections not specifically listed but required to assure equipment is safe 39

to energize and operate. 40 2. Subbase that supports the equipment base and that is made in the form of a cast iron or steel 41

structure that has supporting beams, legs, and cross members that are cast, welded, or bolted 42 shall be tested for a natural frequency of vibration after equipment is mounted. 43 a. The ratio of the natural frequency of the structure to the frequency of the disturbing 44

force shall not be between 0.5 and 1.5. 45

H. Electric Motors: 46 1. Where used in conjunction with adjustable speed AC or DC drives, provide motors that are 47

fully compatible with the speed controllers. 48 2. Design for frequent starting duty equivalent to duty service required by driven equipment. 49 3. Design for full voltage starting. 50 4. Design bearing life based upon actual operating load conditions imposed by driven 51

equipment. 52 5. Size for altitude of Project. 53 6. Furnish with stainless steel nameplates which include all data required by NEC Article 430. 54

Page 64: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 8

7. Use of manufacturer's standard motor will be permitted on integrally constructed motor 1 driven equipment specified by model number in which a redesign of the complete unit 2 would be required in order to provide a motor with features specified. 3

8. AC electric motors less than 1/3 HP: 4 a. Single phase, 60 Hz, designed for the supply voltage shown on the Drawings. 5 b. Permanently lubricated sealed bearings conforming to ABMA standards. 6 c. Built-in manual reset thermal protector or integrally mounted manual motor starter with 7

thermal overload element with stainless steel enclosure. 8 9. AC electric motors 1/3 to 1 HP: 9

a. Single or 3 PH, 60 Hz, designed for the supply voltage shown on the Drawings. 10 b. Permanently lubricated sealed bearings conforming to ABMA standards. 11

1) For single phase motors, provide built-in manual reset thermal protector or 12 integrally mounted manual motor starter with thermal overload element. 13

10. AC electric motors 1-1/2 to 10 HP: 14 a. Single or 3 PH, 60 Hz, designed for the supply voltage shown on the Drawings. 15 b. Permanently lubricated sealed bearings conforming to ABMA standards. 16 c. For vertical motors provide 15 year, average-life thrust bearings conforming to ABMA 17

standards. 18 11. AC electric motors greater than 10 HP: 19

a. Single or 3 PH, 60 Hz, designed for the supply voltage shown on the Drawings. 20 b. Oil or grease lubricated antifriction bearings conforming to ABMA standards. 21

1) Design bearing life for 90 percent survival rating at 50,000 HRS of operation for 22 motors up to and including 100 HP. 23

2) For motors greater than 100 HP, design bearing life for 90 percent survival rating 24 at 100,000 HRS of operation. 25

c. For vertical motors provide 15 year, average-life thrust bearings conforming to ABMA 26 standards. 27

d. Thermal protection: 28 1) For motors 50 HP and above controlled from a variable frequency drive and for all 29

other motors 100 HP and above, provide integral thermal detectors with normally 30 closed contacts that will open on overtemperature complete with monitor and alarm 31 panel having a normally closed contact that will open on overtemperature. 32 a) Two (2) thermal sensing devices per phase in each phase hot-spot location. 33 b) Monitor and alarm panel: 34

(1) For constant speed motors, install panel in and energize from the motor 35 starter equipment. 36

(2) For variable speed motors, install panel in and energize from the variable 37 speed drive equipment. 38

12. Severe duty motor to have the following minimum features: 39 a. All cast iron construction. 40 b. Gasketed conduit box. 41 c. Epoxy finish for corrosion protection. 42 d. Hydroscopic varnish on windings for corrosion protection. 43 e. Drain plug and breather. 44

I. NEMA Design Squirrel Cage Induction Motors: 45 1. Provide motors designed and applied in compliance with NEMA and IEEE for the specific 46

duty imposed by the driven equipment. 47 2. Motors to meet NEMA MG 1 (NEMA Premium) efficiencies. 48 3. Do not provide motors having a locked rotor kVA per HP exceeding the NEMA standard 49

for the assigned NEMA code letter. 50 4. For use on variable frequency type adjustable speed drives, provide: 51

a. Induction motors that are in compliance with NEMA MG 1, Part 31. 52 b. Nameplate identification meeting NEMA MG 1 Part 31 requirements. 53 c. Insulated drive end bearing on all motors. 54

Page 65: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 9

d. Insulated non-drive end bearings, at a minimum, on all motors with horizontal shaft 100 1 HP and larger. 2

e. An insulated bearing carrier on both ends for vertical shaft motors 100 HP and larger. 3 f. Shaft grounding ring on all motors: 4

1) Factory installed, maintenance free, circumferential, bearing protection ring with 5 conductive microfiber shaft contacting material. 6

2) Electro Static Technology AEGIS SGR Bearing Protection Ring or approved 7 equal. 8

5. Design motor insulation in accordance with NEMA standards for Class F insulation with 9 Class B temperature rise above a 40 DegC ambient. 10

6. Design motors for continuous duty. 11 7. Size motors having a 1.0 service factor so that nameplate HP is a minimum of 15 percent 12

greater than the maximum HP requirements of the driven equipment over its entire 13 operating range. 14 a. As an alternative, furnish motors with a 1.15 service factor and size so that nameplate 15

HP is at least equal to the maximum HP requirements of the driven equipment over its 16 entire operating range. 17

8. Motor enclosure and winding insulation application: 18 a. The following shall apply unless modified by specific Specification Sections: 19

20 MOTOR LOCATION MOTOR ENCLOSURE / WINDING INSULATION

Unclassified Indoor Areas WP-1, Standard Insulation

Wet indoor Areas TEFC, Standard Insulation

Wet outdoor Areas TEFC, Extra Dip and Bake for Moisture NOTE: Provide TENV motors in the smaller horsepower ratings where TEFC is not available. 21 22

9. Provide oversize conduit box complete with clamp type grounding terminals inside the 23 conduit box. 24

J. Submersible Motors: Refer to individual narrow-scope Specification Sections for submersible 25 motor requirements. 26

2.3 ACCESSORIES 27

A. Guards: 28 1. Provide each piece of equipment having exposed moving parts with full length, easily 29

removable guards, meeting OSHA requirements. 30 2. Interior applications: 31

a. Construct from expanded galvanized steel rolled to conform to shaft or coupling 32 surface. 33

b. Utilize non-flattened type 16 GA galvanized steel with nominal 1/2 IN spacing. 34 c. Connect to equipment frame with hot-dip galvanized bolts and wing nuts. 35

3. Exterior applications: 36 a. Construct from 16 GA stainless steel or aluminum. 37 b. Construct to preclude entrance of rain, snow, or moisture. 38 c. Roll to conform to shaft or coupling surface. 39 d. Connect to equipment frame with stainless steel bolts and wing nuts. 40

B. Anchorage: 41 1. Cast-in-place anchorage: 42

a. Provide ASTM F593, Type 316 stainless steel anchorage for all equipment. 43 b. Configuration and number of anchor bolts shall be per manufacturer's 44

recommendations. 45 c. Provide two (2) nuts for each bolt. 46

2. Drilled anchorage: 47 a. Adhesive anchors per Specification Section 05505. 48

Page 66: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 10

b. Epoxy grout per Specification Section 03308. 1 c. Threaded rods same as cast-in-place. 2

C. Data Plate: 3 1. Attach a stainless steel data plate to each piece of rotary or reciprocating equipment. 4 2. Permanently stamp information on data plate including manufacturer's name, equipment 5

operating parameters, serial number and speed. 6

D. Gages: 7 1. Provide gages in accordance with Specification Section 13442. 8 2. Provide at the following locations: 9

a. Inlet and outlet of all reciprocating, centrifugal and positive displacement mechanical 10 and process equipment. 11

b. At locations identified on Drawings. 12 3. Utilize tapping sleeves for mounting per Specification Section 15060. 13

E. Lifting Eye Bolts or Lugs: 14 1. Provide on all equipment 50 LBS or greater. 15 2. Provide on other equipment or products as specified in the narrow-scope Specification 16

Sections. 17

2.4 FABRICATION 18

A. Design, fabricate, and assemble equipment in accordance with modern engineering and shop 19 practices. 20

B. Manufacture individual parts to standard sizes and gages so that repair parts, furnished at any 21 time, can be installed in field. 22

C. Furnish like parts of duplicate units to be interchangeable. 23

D. Ensure that equipment has not been in service at any time prior to delivery, except as required by 24 tests. 25

E. Furnish equipment which requires periodic internal inspection or adjustment with access panels 26 which will not require disassembly of guards, dismantling of piping or equipment or similar 27 major efforts. 28 1. Quick opening but sound, securable access ports or windows shall be provided for 29

inspection of chains, belts, or similar items. 30

F. Provide common, lipped base plate mounting for equipment and equipment motor where said 31 mounting is a manufacturer's standard option. 32 1. Provide drain connection for 3/4 IN PVC tubing. 33

G. Machine the mounting feet of rotating equipment. 34

H. Fabricate equipment which will be subject to Corrosive Environment in such a way as to avoid 35 back to back placement of surfaces that can not be properly prepared and painted. 36 1. When such back to back fabrication can not be avoided, provide continuous welds to seal 37

such surfaces from contact with corrosive environment. 38 2. Where continuous welds are not practical, after painting seal the back to back surfaces from 39

the environment in accordance with Specification Section 07900. 40

I. Critical Speed: 41 1. All rotating parts accurately machined and in as near perfect rotational balance as 42

practicable. 43 2. Excessive vibration is sufficient cause for equipment rejection. 44 3. Ratio of all rotative speeds to critical speed of a unit or components: Greater than 1.2. 45

J. Control Panels Engineered and Provided with the Equipment by the Manufacturer: 46 1. Manufacturer’s standard design for components and control logic unless specific 47

requirements are specified in the specific equipment Specification Section. 48

Page 67: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 11

2. NEMA or IEC rated components are acceptable, whichever is used in the manufacturer’s 1 standard engineered design, unless specific requirements are required in the specific 2 equipment Specification Section. 3

3. Affix entire assembly with a UL 508A label "Listed Enclosed Industrial Control Panel" 4 prior to delivery. 5 a. Control panels without an affixed UL 508A label shall be rejected. 6

2.5 SHOP OR FACTORY PAINT FINISHES 7

A. Electrical Equipment: 8 1. Provide factory-applied paint coating system(s) for all electrical equipment components 9

except those specified in Specification Section 09905 to receive field painting. 10 a. Field painted equipment: See Specification Section 09905 for factory applied 11

primer/field paint compatibility requirements. 12

B. Field paint other equipment in accordance with Specification Section 09905. 13 1. See Specification Section 09905 for factory applied primer/field paint compatibility 14

requirements. 15

2.6 SOURCE QUALITY CONTROL 16

A. Motor Tests: 17 1. Test motors in accordance with NEMA and IEEE standards. 18 2. Provide routine test for all motors. 19 3. The Owner reserves the right to select and have tested, either routine or complete, any motor 20

included in the project. 21 a. The Owner will pay all costs, including shipping and handling, for all motors 22

successfully passing the tests. 23 b. The Contractor shall pay all costs, including shipping and handling, for all motors 24

failing the tests. 25 c. If two (2) successive motors of the same manufacturer fail testing, the Owner has the 26

right to reject all motors from that manufacturer. 27

PART 3 - EXECUTION 28

3.1 INSTALLATION 29

A. Install equipment as shown on Drawings and in accordance with manufacturer's directions. 30

B. Utilize templates for anchorage placement for slab-mounted equipment. 31

C. For equipment having drainage requirements such as seal water, provide 3/4 IN PVC or clear 32 plastic tubing from equipment base to nearest floor or equipment drain. 33 1. Route clear of major traffic areas and as approved by Engineer. 34

D. DO NOT construct foundations until major equipment supports are approved. 35

E. Extend all non-accessible grease fittings using stainless steel tubing to a location which allows 36 easy access of fittings from closest operating floor level. 37

F. Equipment Base: 38 1. Construct level in both directions. 39 2. Take particular care at anchor bolt locations so these areas are flat and level. 40

G. Machine Base: 41 1. Mount machine base of rotating equipment on equipment base. 42

a. Level in both directions, using a machinist level, according to machined surfaces on 43 base. 44

Page 68: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 12

2. Level machine base on equipment base and align couplings between driver and driven unit 1 using steel blocks and shims. 2 a. Size blocks and shims to provide solid support at each mounting bolt location. 3

1) Provide area size of blocks and shims approximately 1-1/2 times area support 4 surface at each mounting bolt point. 5

b. Provide blocks and shims at each mounting bolt. 6 1) Furnish blocks and shims that are square shape with "U" cut out to allow blocks 7

and shims to be centered on mounting bolts. 8 c. After all leveling and alignment has been completed and before grouting, tighten 9

mounting bolts to proper torque value. 10

H. Couplings: 11 1. Align in the annular and parallel positions. 12

a. For equipment rotating at 1200 rpm or less, align both annular and parallel within 0.001 13 IN tolerance for couplings 4 IN size and smaller. 14 1) Couplings larger than 4 IN size: Increase tolerance 0.0005 IN per inches of 15

coupling diameter, i.e., allow 6 IN coupling 0.002 IN tolerance, and allow a 10 IN 16 coupling 0.004 IN tolerance. 17

b. For equipment rotating at speeds greater than 1200 rpm allow both annular and parallel 18 positions within a tolerance rate of 0.00025 IN per inch coupling diameter. 19

2. If equipment is delivered as a mounted unit from factory, verify factory alignment on site 20 after installation and realigned if necessary. 21

3. Check surfaces for runout before attempting to trim or align units. 22

I. Grouting: 23 1. After machine base has been shimmed, leveled onto equipment base, couplings aligned and 24

mounting bolts tightened to correct torque value, place a dam or formwork around base to 25 contain grouting between equipment base and equipment support pad. 26 a. Extend dam or formwork to cover leveling shims and blocks. 27 b. Do not use nuts below the machine base to level the unit. 28

2. Saturate top of roughened concrete subbase with water before grouting. 29 a. Add grout until entire space under machine base is filled to the top of the base 30

underside. 31 b. Puddle grout by working a stiff wire through the grout and vent holes to work grout in 32

place and release any entrained air in the grout or base cavity. 33 3. When the grout has sufficiently hardened, remove dam or formwork and finish the exposed 34

grout surface to fine, smooth surface. 35 a. Cover exposed grout surfaces with wet burlap and keep covering sufficiently wet to 36

prevent too rapid evaporation of water from the grout. 37 b. When the grout has fully hardened (after a minimum of seven (7) days) tighten all 38

anchor bolts to engage equipment base to grout, shims, and equipment support pad. 39 c. Recheck driver-driven unit for proper alignment. 40

3.2 INSTALLATION CHECKS 41

A. For all equipment specifically required in detailed specifications, secure services of experienced, 42 competent, and authorized representative(s) of equipment manufacturer to visit site of work and 43 inspect, check, adjust and approve equipment installation. 44 1. In each case, representative(s) shall be present during placement and start-up of equipment 45

and as often as necessary to resolve any operational issues which may arise. 46

B. Secure from equipment manufacturer's representative(s) a written report certifying that 47 equipment: 48 1. Has been properly installed and lubricated. 49 2. Is in accurate alignment. 50 3. Is free from any undue stress imposed by connecting piping or anchor bolts. 51 4. Has been operated under full load conditions and that it operated satisfactorily. 52

a. Secure and deliver a field written report to Owner immediately prior to leaving jobsite. 53

Page 69: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 13

C. No separate payment shall be made for installation checks. 1 1. All or any time expended during installation check does not qualify as Operation and 2

Maintenance training or instruction time when specified. 3

3.3 IDENTIFICATION OF EQUIPMENT AND HAZARD WARNING SIGNS 4

A. Identify equipment and install hazard warning signs in accordance with Specification Section 5 10400. 6

3.4 FIELD PAINTING AND PROTECTIVE COATINGS 7

A. For required field painting and protective coatings, comply with Specification Section 09905. 8

3.5 WIRING CONNECTIONS AND TERMINATION 9

A. Clean wires before installing lugs and connectors. 10

B. Coat connection with oxidation eliminating compound for aluminum wire. 11

C. Terminate motor circuit conductors with copper lugs bolted to motor leads. 12

D. Tape stripped ends of conductors and associated connectors with electrical tape. 13 1. Wrapping thickness shall be 150 percent of the conductor insulation thickness. 14

E. Connections to carry full ampacity of conductors without temperature rise. 15

F. Terminate spare conductors with electrical tape. 16

3.6 FIELD QUALITY CONTROL 17

A. Furnish equipment manufacturer services as specified in the individual equipment 18 Specifications. 19

B. Inspect wire and connections for physical damage and proper connection. 20

C. After installation and prior to energizing the motor, provide insulation resistance test of all 21 motors 100 HP and above. 22 1. Conduct test with 500 or 1000 Vdc megger. 23 2. Test each phase separately. 24 3. Disconnect all extraneous leads to the motor. 25 4. Comply with NEMA MG 1 safety requirements and test procedures. 26

D. Bump motor to check for correct rotation: 27 1. Ensure motor has been lubricated. 28 2. Check prior to connection to driven equipment. 29

E. Subbase that supports the equipment base and that is made in the form of a cast iron or steel 30 structure that has supporting beams, legs and cross member that are cast welded or bolted, shall 31 be tested for a natural frequency of vibration after equipment is mounted. 32 1. Keep the ratio of the natural frequency of the structure to the frequency of the disturbing 33

force out of the range from 0.5 to 1.5. 34

F. Equipment Vibration Monitoring and Testing: 35 1. Utilize an Engineer approved testing agency to perform vibration monitoring and testing on 36

equipment defined in the schedule at the end of this Section. 37 2. Permanently attach vibration test and monitoring mounting pads to the equipment at 38

locations recommended by the equipment manufacturer or as recommended by the vibration 39 testing agency. 40

3. Utilize mounting pads suitable for permanent installation and for incorporation into a 41 predictable maintenance program. 42

4. For variable speed equipment provide vibration testing at 1 Hz increments throughout entire 43 operating range. 44

5. Diagnosis to include, but is not limited to the following: 45 a. Unbalance. 46

Page 70: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - EQUIPMENT: BASIC REQUIREMENTS 11005 - 14

b. Misalignment. 1 c. Bent shaft. 2 d. Journal bearing related problems. 3 e. Rolling contract bearing problems. 4 f. Mechanical looseness. 5 g. Resonance. 6 h. Foundation flexibility. 7 i. Electrically induced problems. 8 j. Pump problems. 9 k. Fan problems. 10 l. Coupling problems. 11 m. Drive belt problems. 12 n. Gear problems. 13 o. Centrifugal compressor problems. 14 p. Electric motor induced vibration from VFD or VFD carrier frequency. 15

6. Provide machinery condition diagnosis based on an acceptable machinery vibration severity 16 guide or machinery fault guide analysis provided by the testing agency, ISO 1940 Balance 17 Quality Grade 6.3 as a minimum. 18

7. Tolerances for pumping equipment shall be per the latest edition of HI published standards. 19 8. Repair or replace equipment shown to be out of range of the specified tolerance until the 20

equipment meets the specified normal operation range required in the machinery fault guide 21 analysis. 22

9. Document testing with written report. 23 a. Report to include initial testing results, acceptance criteria, corrective action taken to 24

meet acceptance, verification of corrective action and acceptance report and baseline. 25

3.7 DEMONSTRATION 26

A. Demonstrate equipment in accordance with Specification Section 01650. 27

END OF SECTION 28

Page 71: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: BASIC REQUIREMENTS 11060 - 1

2014/10/07 1

SECTION 11060 2

PUMPING EQUIPMENT: BASIC REQUIREMENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Pumping equipment. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 09905 - Painting and Protective Coatings. 11 4. Section 11005 - Equipment: Basic Requirements. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. Hydraulic Institute (HI): 15

a. 14.6, Rotodynamic Pumps for Hydraulic Performance Acceptance Tests. 16

B. Fully coordinate all mechanical seal systems specified to ensure pump and seal compatibility. 17

C. Pump/motor and VFD coordination: See Specification Section 11005. 18

1.3 DEFINITIONS 19

A. The abbreviations are defined as follows: 20 1. IPS: Iron Pipe Size. 21 2. NPSHR: Net Positive Suction Head Required. 22 3. TDH: Total Dynamic Head. 23 4. TEFC: Totally Enclosed Fan Cooled. 24 5. VFD: Variable Frequency Drive. 25

B. Pump Service Category: Pump or pumps having identical names (not tag numbers) used for 26 specific pumping service. 27

1.4 SUBMITTALS 28

A. Shop Drawings: 29 1. See Specification Section 01340 for requirements for the mechanics and administration of 30

the submittal process. 31 2. See Specification Section 11005. 32 3. Product technical data including: 33

a. Performance data and curves with flow (gpm), head (FT), horsepower, efficiency, 34 NPSH requirements, submergence requirement. 35

b. Pump accessory data. 36 c. Bearing supports, shafting details and lubrication provisions. 37

1) Bearing life calculations. 38 2) Critical speed calculations. 39

d. Solids passage information. 40 4. Certifications: 41

a. Certified pump performance curves as described in the SOURCE QUALITY 42 CONTROL Article. 43

Page 72: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: BASIC REQUIREMENTS 11060 - 2

5. Test reports: 1 a. Factory hydrostatic test. 2

B. Operation and Maintenance Manuals: 3 1. See Specification Section 01342 for requirements for: 4

a. The mechanics and administration of the submittal process. 5 b. The content of Operation and Maintenance Manuals. 6

C. Informational Submittals: 7 1. Certifications: 8

a. Provide a written statement that manufacturer's equipment has been installed properly, 9 started up and is ready for operation by Owner's personnel. 10

PART 2 - PRODUCTS 11

2.1 ACCEPTABLE MANUFACTURERS 12

A. Subject to compliance with the Contract Documents, the following manufacturers are 13 acceptable: 14 1. Pumps: 15

a. See individual pump Specification Sections. 16 2. Mechanical seals: 17

a. Chesterton. 18 b. Garlock. 19 c. Or as noted in the individual pump Specification Sections. 20

3. Seal water station: 21 a. Chesterton. 22 b. John Crane. 23 c. AESSEAL. 24

B. Submit request for substitution in accordance with Specification Section 01640. 25

2.2 CENTRIFUGAL PUMP DESIGN 26

A. Provide units with increasing head characteristics from the end run out portion of the curve to 27 shut-off condition. 28

2.3 ACCESSORIES 29

A. See Specification Section 11005. 30

B. Each Unit: 31 1. Lifting eye bolts or lugs. 32 2. Plugged gage cock connection at suction and discharge nozzles. 33 3. Tapped and plugged openings for casing and bearing housing vents and drains. 34 4. Fittings for properly adding flushing lubricant. 35 5. Pressure relief fittings for grease lubrication. 36

C. Mechanical Seals: Provide as specified in the narrow-scope pump sections. 37

D. Seal Water Station: 38 1. Provide one (1) unit per pump with manual shut-off valve on all pumps with seals. 39 2. Features: 40

a. Pressure regulating. 41 b. Flow regulating. 42 c. Cleanable flow tube(s) while in service. 43 d. Hose barb connection. 44 e. Liquid filled pressure gage. 45

Page 73: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: BASIC REQUIREMENTS 11060 - 3

3. Materials of construction: 1 a. Flowmeter tubes: Polysulfone. 2 b. Unit body: Polyoxymethylene. 3 c. Pressure gage: 316 stainless steel case and wetted parts. 4 d. Pressure regulating valve: 316 stainless steel. 5 e. Flow regulating valve: 316 stainless steel. 6 f. Tube fittings: 316 stainless steel. 7 g. Mounting brackets: 316 stainless steel. 8

4. Service: 9 a. Temperatures up to 150 DegF. 10 b. Pressure up to 140 psig. 11

5. Connection: 12 a. Hose barb threaded to pump. 13 b. Hose barb to seal water unit. 14 c. Reinforced polyurethane hose: 15

1) Minimum size: 3/8 IN ID. 16 2) Minimum pressure rating: 17

a) At 180 DegF: 115 psi. 18 b) At 73 DegF: 200 psi. 19

3) Minimum wall thickness: 1/8 IN. 20 d. Non-potable water to shut-off valve: Cooper with bronze isolation valve. 21

6. Mounting: 22 a. To pump or pipe flange with stainless steel bracket. 23 b. Maximum distance from non-potable water to shut-off ball valve to seal water station 24

and seal water station to pump seal, 2 FT each direction. 25

2.4 FABRICATION 26

A. Pump Support: 27 1. Design base to support weight of drive, shafting and pump. 28 2. Comply with HI vibration limitations. 29 3. Mount horizontal pump, motor and coupling on single piece drip lip type baseplate. 30 4. Mount vertical pumps on single piece pedestal baseplate. 31 5. Fabricate to withstand all operating loads transmitted from the pump and drive. 32

2.5 SOURCE QUALITY CONTROL 33

A. If specifically required in the individual pump specification sections, provide factory tests: 34 1. All units: 35

a. Conduct tests in accordance with HI. 36 1) Shut-off head and design condition: Positive unilateral performance tolerance 37

meeting Grade 1U per HI 14.6. 38 b. Hydrostatic test at 150 percent of shut-off head for a minimum of 5 minutes. 39

2. Adjustable speed units: 40 a. Head (FT) verses flow (gpm) pump curves: 41

1) Maximum, minimum and two (2) equally spaced intermittent speeds. 42 2) Efficiencies along each curve. 43 3) Brake horsepower along each curve. 44

3. Constant speed units: 45 a. Head (FT) versus flow (gpm) pump curves: 46

1) Efficiencies along curve. 47 2) Brake horsepower along each curve. 48

4. Results certified by a registered professional engineer. 49

B. Statically and dynamically balance each pump per HI standards. 50

Page 74: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: BASIC REQUIREMENTS 11060 - 4

PART 3 - EXECUTION 1

3.1 INSTALLATION 2

A. See Specification Section 11005. 3

B. Floor or Pad-Mounted Units (Non-Submersible): 4 1. Align vertically and horizontally level, wedge and plumb units to match piping interfaces. 5 2. Assure no unnecessary stresses are transmitted to equipment flanges. 6 3. Tighten flange bolts at uniform rate and manufacturer's recommended torque for uniform 7

gasket compression. 8 4. Support and match flange faces to uniform contact over entire face area prior to bolting pipe 9

flange and equipment. 10 5. Permit piping connecting to equipment to freely move in directions parallel to longitudinal 11

centerline when and while bolts in connection flange are tightened. 12 6. Grout equipment into place prior to final bolting of piping but not before initial fitting and 13

alignment. 14 7. Assemble connecting piping with gaskets in place and minimum of four (4) bolts per joint 15

installed and tightened. 16 a. Test alignment by loosening flange bolts to see if there is any change in relationship of 17

piping flange with equipment connecting flange. 18 b. Realign as necessary, install flange bolts and make equipment connection. 19

8. Field paint units as defined in Specification Section 09905. 20 9. Provide pressure gage on discharge of all pumps and on suction and discharge of all non-21

submersible units. 22

C. Submersible Units: 23 1. Assemble connecting piping with gaskets in place and minimum of four (4) bolts per joint 24

installed and tightened. 25 a. Test alignment by loosening flange bolts to see if there is any change in relationship of 26

piping flange with equipment connecting flange. 27 b. Realign as necessary, install flange bolts and make equipment connection. 28

2. Field paint units as defined in Specification Section 09905. 29 3. Provide pressure gage on discharge of all pumps and on suction and discharge of all non-30

submersible units. 31

3.2 FIELD QUALITY CONTROL 32

A. Provide services of equipment manufacturer's field service representative(s) to: 33 1. Inspect equipment covered by this Specification Section. 34 2. Supervise pre-start adjustments and installation checks. 35 3. Conduct initial startup of equipment and perform operational checks. 36 4. Instruct Owner's personnel for the specified minimum number of hours at jobsite per 37

Specification Section 01060 on operation and maintenance of each of following pumping 38 equipment: 39 a. Section 11072 - Pumping Equipment: Vertical Turbine Line Shaft, 24 HRS. 40

END OF SECTION 41

Page 75: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11072 - 1

2014/10/08 1

SECTION 11072 2

PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Vertical turbine well pumps. 6

B. Related Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 11005 - Equipment: Basic Requirements. 10 4. Section 11060 - Pump Equipment: Basic Requirements. 11 5. Section 13440 - Instrumentation for Process Control: Basic Requirements. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. American Society of Mechanical Engineers (ASME): 15

a. B16.1, Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250. 16 2. Society of Automotive Engineers (SAE). 17

1.3 SUBMITTALS 18

A. Shop Drawings: 19 1. See Specification Section 01340 for requirements for the mechanics and administration of 20

the submittal process. 21 2. Product technical data including: 22

B. Operation and Maintenance Manuals: 23 1. See Specification Section 01342 for requirements for: 24

a. The mechanics and administration of the submittal process. 25 b. The content of Operation and Maintenance Manuals. 26

1.4 WARRANTY 27

A. A two-year warranty shall be provided. The warranty date will start from the time of project 28 acceptance and will be one (1) date for all equipment. 29

PART 2 - PRODUCTS 30

2.1 ACCEPTABLE MANUFACTURERS 31

A. Subject to compliance with the Contract Documents, the following manufacturers are 32 acceptable: 33 1. Peerless. 34 2. Engineer Approved Equivalent. 35

B. Submit request for substitution in accordance with Specification Section 01640. 36

2.2 PERFORMANCE AND DESIGN REQUIREMENTS 37

A. Performance Parameters: 38 1. Collector Well Pumps, CWP-01, CWP-02, CWP-03: 39

a. Primary design condition: 4,200 gpm at 140 FT TDH, with minimum 86 percent bowl 40 efficiency at maximum speed. 41

b. Secondary design conditions: 42 1) 4,200 gpm at 73 FT TDH. 43

Page 76: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11072 - 2

2) 2,000 gpm at 104 FT TDH. 1 3) 2,000 gpm at 60 FT TDH. 2

c. Maximum motor speed: 1,200 rpm (Variable Frequency Drive). 3 d. Drive motor: 200 HP (Maximum). 4 e. Minimum shutoff head at 100 percent Speed: 183 FT. 5 f. Discharge/Column Size: 16 IN. 6 g. Type of discharge head: Surface type. 7 h. Discharge Pipe Centerline Elevation: 1171.25. 8 i. Pump Base Elevation: 1169.75. 9 j. Bottom of Pump Bowl and Intake Screen Assembly Elevation: 1062.00. 10 k. Minimum NPSHA: 35 FT. 11

2. Collector Well Pumps, CWP-01, CWP-02, CWP-03 to be capable of meeting the following 12 future conditions with replacement of only the motors: 13 a. Primary design condition: 5,600 gpm at 182 FT TDH, with minimum 86 percent bowl 14

efficiency at maximum speed. 15 b. Secondary design conditions: 16

1) 5,600 gpm at 73 FT TDH. 17 2) 2,000 gpm at 141 FT TDH. 18 3) 2,000 gpm at 60 FT TDH. 19

c. Maximum motor speed: 1,800 rpm (Variable Frequency Drive). 20 d. Drive motor: 350 HP (Maximum). 21 e. Minimum shutoff head at 100 percent Speed: 280 FT. 22 f. Discharge/Column Size: 16 IN. 23 g. Bottom of Pump Bowl and Intake Screen Assembly Elevation: 1062.00. 24 h. Minimum NPSHA: 16 FT. 25

B. Provide pumps with increasing head characteristics from secondary design conditions to shutoff 26 condition. Provide pumps with net positive suction head requirements (NPSHR) less than the 27 net positive suction head available (NPSHA) at all operating conditions. 28

2.3 ACCESSORIES 29

A. See Section 11005 and Section 13440. 30

2.4 COMPONENTS 31

A. General: 32 1. Furnish units consisting of a vertical shaft turbine, direct connected to a vertical solid shaft 33

motor. Design unit with non-reversing ratchets. 34 2. Pump manufacturer is to be responsible for the complete pump including bowl assembly, 35

column pipe, lineshaft, bearings, discharge head, motor, and all other components. 36 3. Weight of revolving parts of pump including unbalanced hydraulic thrust of impeller is 37

carried by thrust bearing in driver. 38 4. Make provision at driver shaft for adjusting impeller with reference to bowls. 39 5. Pumps to be water lubricated and must comply in all respects with the applicable 40

regulations of the South Dakota Department of Natural Resources (SD DENR). 41 6. Pumps to be capable of handling reverse flow without loosening of the impeller or causing 42

impeller damage. 43 7. All materials of construction shall adhere to the 2014 EPA standards for lead free. 44

B. Column: 45 1. Construct discharge column pipe of carbon steel meeting the requirements of ASTM A283, 46

Grade B or C; or ASTM A53, Grade A, B, E, or F. Supply column pipe with flanged 47 connections. 48

2. Provide top and bottom sections of column pipes to 5 FT lengths. 49 3. Provide intermediate column sections not exceeding 10 FT in length. 50 4. Column pipe to be designed and hydrostatically tested for 150 percent of the pump shutoff 51

pressure. 52

Page 77: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11072 - 3

5. Sandblast column and coat with a minimum 15 mils dry film thickness epoxy system at the 1 factory. 2

6. Provide epoxy coating recommended by Tnemec or Carboline and must be NSF 61 3 approved for use with potable water. 4

7. The column bolting shall be 304 or 316 stainless steel. 5

C. Open Line Shaft: 6 1. ASTM A743, Grade CF-8M, or ASTM A276, Type 410 or 416 stainless steel, rolled and 7

ground over full length. 8 2. The shaft diameter and spacing of bearing shall be designed to be non-vibrating when 9

operating at the rated pump speed. Calculate the minimum shaft diameter using the 10 formulas given in Subsection A4.3.3 of AWWA E101-88 (ANSI B58.1), for the pump 11 shutoff head and/or maximum horsepower, whichever is greater. 12

3. Provide pump column shaft in lengths equal to the column pipe lengths. Maximum 10 FT 13 length. The pump manufacturer to perform a critical speed analysis to determine bearing 14 spacing. 15

4. Key and thrust-ring or other non-threaded type shaft coupling for shaft diameters 2 IN and 16 larger. Type 316 stainless steel thrust rings, cap screws, and keys to be used. Threaded 17 couplings may be used of shaft diameters 1-15/16 IN and smaller. Provide one-piece bowl 18 shaft. No bowl shaft coupling will be allowed. 19

5. Provide Vesconite bearings at each column connection suitable for dry running during the 20 startup period of the pump. Bearings to be supported by retainers butted between machined 21 faces of discharge column. 22

6. Provide a line shaft prelubrication system, adequately sized, to water lubricate the line shaft 23 bearings prior to pump startup. The pump discharge head shall be provided with a 24 connection for the prelubrication system. 25

D. Pump Bowl and Suction Bell: 26 1. Provide bowl and suction bell constructed of close grained cast iron, free from 27

imperfections and accurately machined and fitted. 28 2. The bowls are to be capable of withstanding a hydrostatic pressure equal to twice the 29

pressure at rated capacity or 150 percent of the shut off head, whichever is greater. 30 3. Each bowl to be fitted with water lubricated dual bearing design consisting of both bronze 31

and rubber sleeve type bearings to reduce abrasive wear in the bearing area. 32 4. Intermediate bowl to have sand lugs cast into the top flange to reduce the wear from 33

abrasives on the pump bowl. 34 5. Bronze sleeve type bearing at the top and bottom of each stage. 35 6. Coat pump bowl water passages with an abrasion-resistant baked enamel, phenolic or 36

epoxy. 37 7. Provide NSF 61 approved epoxy coating on the inside and outside of the bowl and suction 38

bell suitable for potable water service. 39 8. Provide bowls with renewable wear rings adjacent to the impeller. Bowl and impeller wear 40

rings to be stainless steel ASTM A743, Grade CF-8M or CA8M or CA-15; or ASTM A276, 41 Type 410, with Brinell hardness difference of 50. 42

9. Design to ensure easy removal of bearings and impeller. 43 10. Furnish suction bell with flared end to reduce entrance losses and with a sufficient number 44

of vanes to support lower guide bearings and weight of impeller and pump shaft when 45 dismantling pump. 46

11. The bowl bolting to be 304or 316 stainless steel. 47

E. Bearings: 48 1. Provide units with sleeve bearings of SAE 600 bronze, lead free, in each bowl and in 49

suction bell. 50 2. In bowl, provide main bronze bearing immediately above impeller and a lower bronze 51

bearing immediately below impeller. 52 3. Provide for lubrication of bowl bearings with pumped liquid. 53 4. Furnish suction bell bearing having minimum length equal to five (5) shaft diameters. 54

Page 78: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11072 - 4

5. Ensure bell bearing is permanently packed type with packing to be a nonsoluble grease. 1 6. Provide SAE 40 bronze collar for bell bearing to prevent abrasives from entering bearing. 2

F. Pump Shaft and Impeller: 3 1. Provide pump unit shaft constructed of rolled and ground 416 or 410 stainless steel. 4 2. Furnish one-piece enclosed type impellers constructed of bronze, ASTM B584 or stainless 5

steel A276, Type 316 and securely attached to impeller shaft with stainless steel tapered 6 collets. 7

3. Ensure impeller is accurately fitted and statically and dynamically balanced. 8

G. Discharge Head Assemblies: 9 1. Design discharge head assembly for 150 psi working pressure and 250 psi test pressure. 10 2. Provide discharge head for above ground mounting constructed of fabricated steel with 11

integral discharge flange. 12 3. Construct discharge nozzle with a vertical vane to minimize turbulence. 13 4. Furnish ASME B16.1, 125/150 LB flange. 14 5. Supply the discharge head with lifting lugs capable of supporting weight of entire unit. 15 6. Weld flange to the discharge nozzle at specified elevation. 16 7. The discharge head shall be fitted with a flanged adjustable spacer coupling to allow for 17

easy removal of the mechanical seal without disturbing the motor. 18 8. The interior of the discharge head shall be coated with an NSF approved epoxy coating. 19

The outside of the discharge head shall be primed to allow for finish coating by the 20 Contractor. 21

H. Mechanical Seal: 22 1. Provide a mechanical seal suitable for use in non-potable water. 23 2. The mechanical seal metal parts shall be Type 316 stainless steel. Seal rotating and 24

stationary parts shall be tungsten carbide on carbon face or silicone carbide on carbon face. 25 Mechanical seal nuts and bolts, gland bolts, and nuts to be fabricated of stainless steel, type 26 316. Mechanical seal housing to be cast iron ASTM A48, Class 30. 27

3. Design seal housing to provide space and clearance for a single inside cartridge-type 28 mechanical seal. 29

4. Provide a seal water flushing system through copper tubing placed from flush port orifice on 30 the mechanical seal back to the well caisson. Provide seal water flushing system with 31 needle valve and flow indicator device. Utilize dielectric unions where necessary. See 32 Section 11060 for additional seal water station requirements. 33

5. Mechanical seals shall be John Crane, Model No. 8B1, John Crane, Model 5610, or 34 Chesterton Model No. 155 or engineer approved equal. 35

I. Suction Strainer: 36 1. Supply basket type strainer constructed of 316 stainless steel with net open area of not less 37

than four times the throat area of the suction bell. 38 2. Maximum opening shall not be more than 75 percent of the minimum opening of the water 39

passage through the bowls and impellers. 40

J. Data Plates: 41 1. Provide stainless steel data plate securely attached to pump. 42 2. Include manufacturer's name, pump size and type, serial number, speed, impeller diameter, 43

capacity and head rating, and other pertinent data. 44

K. Motors: 45 1. Inverter duty rated for VFD operation, vertical solid shaft, squirrel cage, induction type. 46 2. 460 V, 60 HZ, 3 PH. 47 3. WP-I type with 1.15 service factor. 48 4. Size motor to drive pump continuously over the complete head - capacity range without the 49

load exceeding the nameplate rating. 50 5. Design motor for 40 DegC ambient. 51 6. Comply with Section 11005. 52

Page 79: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11072 - 5

2.5 MAINTENANCE MATERIALS 1

A. Extra Materials: Furnish the Owner the following extra parts for each individual pump (3 sets 2 total): 3 1. Impeller. 4 2. Flanged Column Rubber Bearings. 5 3. Bowl SS Bolting. 6 4. Flange Column SST Bolt. 7 5. One (1) set of wear rings. 8 6. One (1) set of bowl bearings. 9 7. One (1) set of line shaft bearings. 10 8. One (1) mechanical seal and gland (only provide one spare seals for similar pumps). 11 9. One (1) set of shaft couplings. 12 10. One (1) Stainless steel collet 13 11. One (1) gallon of each type of lubricant. 14

PART 3 - EXECUTION 15

3.1 INSTALLATION 16

A. Install products in accordance with manufacturer's instructions. 17

3.2 FACTORY TESTS 18

A. Each pump bowl assembly shall be factory performance testing in accordance with Section 19 11060, with curve approval by the Engineer, prior to shipment. 20

B. The pump bowl assembly is to be hydrostatically tested in the factory in accordance with Section 21 11060. 22

3.3 FIELD QUALITY CONTROL 23

A. See Section 11005. 24

B. See Section 11060. 25

C. Field Tests: Each pump shall be field tested on water for vibration, capacity/head, full load 26 amperage, and voltage. 27 1. Field test all pumps to demonstrate satisfactory operation without excessive noise, vibration, 28

cavitation, or overheating in accordance with Section 11005. 29 2. Contractor shall provide an acceptable testing agency specialized in the field of baseline 30

vibration testing and machinery condition diagnosis on all rotating equipment, including 31 drivers in accordance with Section 11005. 32

3. All field testing shall be conducted in the presence of the Owner and/or Engineer. 33 4. Manufacturer’s representative shall be present for all field testing of pumps. Provide on-site 34

services as indicated in Section 11060. In addition it shall be the responsibility of the pump 35 manufacturer to perform pump tests utilizing the variable frequency drive unit, pump, and 36 motor combinations. The manufacturer shall supply all equipment for conducting the flow 37 testing. If measured flows corresponding to the given pump heads are more then 5 percent 38 below the flows provided in the factory test, adjustment to the impeller is needed. 39 Alternatively, provide new impellers or rework the pumps. 40 a. On-site pump testing shall show a minimum of five (5) operating points along the curve 41

while running at maximum specified pump speed including efficiency for each point, 42 operating point at peak efficiency, and pump run-out points. 43 1) Operation points shall include the design condition for each pump and for flow 44

conditions approximately 10 percent above this flow condition and 10 percent 45 below this flow condition. 46

2) Pumps shall be operated at each selected point for a duration of not less than one 47 (1) HR each and shall be operated at the design point for a minimum of six (6) 48 HRS. 49

Page 80: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: VERTICAL TURBINE (LINE SHAFT) 11072 - 6

3) Water used for on-site testing shall be well water from the collector well caisson. 1 b. Pump curve tests shall be conducted on site for each pump while operating at 70 2

percent of specified pump speed and shall include pump efficiency for each point, 3 operating point at peak efficiency, shut-off head, and pump run-out point. 4

END OF SECTION 5

Page 81: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: INLINE CENTRIFUGAL PUMPS 11077 - 1

2014/08/28 1

SECTION 11077 2

PUMPING EQUIPMENT: INLINE CENTRIFUGAL PUMPS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Inline centrifugal pumps. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 11005 - Equipment: Basic Requirements. 11 4. Section 11060 - Pumping Equipment: Basic Requirements. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. American Bearing Manufacturers Association (ABMA). 15 2. ASTM International (ASTM): 16

a. A48, Standard Specification for Gray Iron Castings. 17 b. B584, Standard Specification for Copper Alloy Sand Castings for General Applications. 18

3. Hydraulic Institute (HI): 19 a. Standards for Centrifugal, Rotary and Reciprocating Pumps. 20

1.3 SUBMITTALS 21

A. Shop Drawings: 22 1. See Specification Section 01340 for requirements for the mechanics and administration of 23

the submittal process. 24 2. See Section 11060. 25

B. Operation and Maintenance Manuals: 26 1. See Specification Section 01342 for requirements for: 27

a. The mechanics and administration of the submittal process. 28 b. The content of Operation and Maintenance Manuals. 29

PART 2 - PRODUCTS 30

2.1 ACCEPTABLE MANUFACTURERS 31

A. Subject to compliance with the Contract Documents, the following manufacturers are 32 acceptable: 33 1. Inline centrifugal pumps: 34

a. Taco. 35 b. Bell & Gossett. 36 c. Gould. 37

B. Submit request for substitution in accordance with Specification Section 01640. 38

2.2 MATERIALS 39

A. Pump Service Category and Tag Number: 40 1. Pump casing: Cast iron, ASTM A48, Class 30. 41

Page 82: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: INLINE CENTRIFUGAL PUMPS 11077 - 2

2. Impellers: Bronze, ASTM B584 (836). 1 3. Shaft: Carbon steel. 2 4. Impeller wear rings: Bronze, ASTM B584 (836). 3 5. Shaft sleeve: Bronze, ASTM B584 (831). 4

2.3 EQUIPMENT 5

A. Performance and Configuration Requirements: 6 1. Pump service category and tag number: P-01 7

a. Design condition: 90 gpm at 61 FT TDH with minimum pump efficiency of 8 50 percent. 9

b. Shutoff condition: 0 gpm at 61 FT TDH. 10 c. Pump configuration: In-line. 11 d. Maximum pump speed: 1760 rpm. 12 e. Nameplate driver horsepower: 3.0. 13 f. Drive type: Constant speed. 14 g. Drive configuration: Direct coupled. 15 h. Net Positive Suction Head Required (NPSHR): 2.5 FT. 16

2. Pump service category and tag number: P-02 17 a. Design condition: 65 gpm at 28 FT TDH with minimum pump efficiency of 50 18

percent. 19 b. Shutoff condition: 0 gpm at 37 FT TDH. 20 c. Pump configuration: In-line. 21 d. Maximum pump speed: 1760 rpm. 22 e. Nameplate driver horsepower: 1.0. 23 f. Drive type: Constant speed. 24 g. Drive configuration: Direct coupled. 25 h. Net Positive Suction Head Required (NPSHR): 5 FT. 26

2.4 ACCESSORIES 27

A. See Section 11060. 28

2.5 FABRICATION 29

A. Fabricate pump case to withstand 175 psig or 200 percent of maximum working pressure 30 specified by pump performance, whichever is greater. 31

B. Furnish anti-friction type bearings rated for minimum ABMA L-10 life of 20,000 HRS at 24 HR 32 continuous operation. 33

C. Provide grease lubrication. 34

D. Furnish rigid, one piece cast bearing housing with catch reservoir. 35

E. Provide pump case with case rings at impeller skirt. Lock ring in place with pin. 36

F. Statically and dynamically balance impellers per HI standards. 37

G. Key impeller to driven shafts and secure impeller to shaft with stainless steel locking screw. 38

2.6 SOURCE QUALITY CONTROL 39

A. Factory test one pump of each service category. 40

2.7 MAINTENANCE MATERIALS 41

A. Extra Materials: 42 1. Furnish the Owner the following extra parts for each pump service category: 43

a. Shaft sleeve: One set. 44 b. Shaft O-rings: One set. 45 c. Bearings: One set. 46

Page 83: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: INLINE CENTRIFUGAL PUMPS 11077 - 3

d. Wear rings: Two each. 1 e. Gaskets: One set. 2 f. Set seals: One set. 3

PART 3 - EXECUTION 4

3.1 INSTALLATION 5

A. See Section 11060. 6

3.2 FIELD QUALITY CONTROL 7

A. See Section 11060. 8

END OF SECTION 9

10

Page 84: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PUMPING EQUIPMENT: INLINE CENTRIFUGAL PUMPS 11077 - 4

1

Page 85: City of Yankton, SD

D I V I S I O N 1 3 SPECIAL CONSTRUCTION

Page 86: City of Yankton, SD
Page 87: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 1

2014/08/28 1

SECTION 13200 2

HORIZONTAL COLLECTOR WELL 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Construction of a horizontal collector well, which includes design and construction of 7

caisson, lateral projections, lateral development, and performance testing. The location of 8 the caisson shall be as indicated on the Drawings. 9

B. Related Specification Sections include but are not necessarily limited to: 10 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 11 2. Division 01 - General Requirements. 12

1.2 QUALITY ASSURANCE 13

A. The requirements specified herein shall be considered the minimum requirements for 14 construction of the well. 15 1. The Contractor shall be responsible for satisfying any State regulations otherwise exceeding 16

these specifications. The Contractor shall possess a well driller's license as required by the 17 South Dakota Department of Environment and Natural Resources. 18

2. The Contractor shall employ certified welders for each material to be welded. 19 3. The Contractor shall employ a qualified geotechnical engineer to provide any necessary soil 20

investigations and geotechnical recommendations required for the Contractor to complete 21 the design and construction of the caisson. 22

B. Referenced Standards: 23 1. American Iron and Steel Institute (AISI). 24 2. American National Standards Institute/American Society of Mechanical Engineers 25

(ANSI/ASME): 26 a. B1.20.1, Pipe Threads, General Purpose (Inch). 27 b. B16.5, Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24 Metric/Inch 28

Standard. 29 c. B31.1, Power Piping. 30

3. ASTM International (ASTM): 31 a. A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked 32

Austenitic Stainless Steel Pipes. 33 b. A778, Standard Specification for Welded, Unannealed Austenitic Stainless Steel 34

Tubular Products. 35 c. D5716, Standard Test Method for Measuring the Rate of Well Discharge by Circular 36

Orifice Weir. 37 4. Building Code: 38

a. International Code Conference (ICC): 39 1) International Building Code and associated standards, 2003 Edition including all 40

amendments, referred to herein as Building Code. 41 5. American Society of Civil Engineers(ASCE): 42

a. ASCE 7-05, Minimum Design Loads for Buildings and Other Structures. 43 6. American Concrete Institute (ACI): 44

a. ACI 350-06, Code Requirements for Environmental Engineering Concrete Structures. 45

Page 88: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 2

C. Qualifications: 1 1. Structural Engineer for Collector Well: Professional Engineer licensed in the State of South 2

Dakota at the time of shop drawing submittal. 3 a. Engineer to have minimum five (5) years experience in design of collector wells in 4

scope similar to this Project. 5 2. Welding operators and processes to be qualified in accordance with: 6

a. AWS D1.1 for welding steel shapes and plates. 7 b. AWS D1.4 for welding reinforcing bars. 8

3. Contractor shall comply with and be responsible to adhere to the terms and conditions of the 9 Owner-supplied general permit for temporary dewatering and temporary water use permit. 10

1.3 SYSTEM DESCRIPTION 11

A. The work shall include the installation of a horizontal collector well with an expected capacity 12 ranging from 12 million gallons per day (MGD) (8,350 gallons per minute (gpm)) to 20 MGD 13 (13,900 gpm), depending on water temperature and river level. Lateral screens shall be radially 14 projected from within the caisson through a port assembly and terminated within the caisson 15 with a gate valve. 16

B. Grade elevation at the site is as shown on the Drawings. Static groundwater level typically 17 varies and the site is located within the floodplain of the Missouri River and as such is subject to 18 flooding. 19

C. Provide all equipment, personnel, materials, and services to satisfactorily complete this work in 20 accordance with these specifications. All materials utilized shall be new unless otherwise 21 specifically provided for in the specifications. All workmanship and materials shall meet or 22 exceed the industry standards usually applied to such work. 23

1.4 SUBMITTALS 24

A. Complete drawings and specifications covering materials to be furnished, and dimensions, sizes, 25 and thicknesses of members shall be submitted in accordance with the submittals section. 26 Additional items to be furnished shall include: 27 1. Method of measuring and controlling plumbness during the sinking of the caisson. 28 2. Details pertaining to the lateral installation, including lateral pipe, slotting, packer, digging 29

head, seals, valves, and other items necessary to indicate the proposed Work. 30 3. Shop drawings of all penetrations, ports, and hatches. 31 4. Reinforcing shop drawing. 32 5. Current certificates for each welder to be employed on the project. 33 6. Complete details of lateral pipe welding. 34 7. Performance testing plan, including pumping capacities of the temporary pumps to be 35

utilized for the utilized during the performance testing. 36 8. Erosion control plan. 37 9. Excavation spoil and dewatering water disposal plan. 38 10. Product technical data including: 39

a. Acknowledgement that products submitted meet requirements of standards referenced. 40 b. Manufacturer's instructions. 41

11. Concrete mix designs in accordance with Section 03308 and 03350. 42 a. Manufacturer and type of proposed admixtures. 43 b. Certification that the fly ash meets the quality requirements stated in this Specification 44

Section, and fly ash supplier's certified test reports for each shipment of fly ash 45 delivered to concrete supplier, if fly ash is used. 46

12. Well lateral development documentation: 47 a. Development procedures and duration of development. 48 b. Sediment removal and sand production testing. 49

13. Post well performance testing data to include: 50 a. Pumping rate measurements. 51 b. Water level measurements. 52

Page 89: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 3

c. Pressure transducer data in electronic format. 1 d. Individual lateral flow rate testing. 2 e. Results of sand content testing. 3

14. Calculations: 4 a. Provide calculations for caisson and all structural components and connections of 5

collector well. 6 b. Calculations shall include coordination of pump station to be placed upon collector 7

well. Connections shall match pump station elements shown on the Drawings. 8 c. Calculations will not be reviewed and are submitted for record purposes only. 9 d. Calculations shall be unique for this project and consider specific depths, diameters, 10

connections, and loading as described herein and on the Drawings. 11 e. Calculations shall be sealed by a Registered Civil or Structural Engineer in the State of 12

South Dakota. 13 f. Include any geotechnical reports and investigations developed or used for this design. 14

1.5 DEFINITIONS 15

A. Collector Well: Entire system of concrete caisson, horizontal laterals, and associated 16 components as described in this section. 17

B. Caisson: Structural concrete component of the Collector Well. 18

C. Laterals: Piping component that extends laterally from the base of the Caisson. 19

PART 2 - PRODUCTS 20

2.1 MATERIALS 21

A. Concrete and Reinforcement: As specified in Division 3. 22 1. Minimum Concrete Strength: F’c = 4000 psi. 23

B. Concrete Accessories including but not limited to waterstops, reinforcing chairs, and formwork: 24 As specified in Division 3. 25

C. Stainless Steel Pipe: Schedule 40S. 26

D. Lateral Pipe: ASTM A312 or ASTM A778, Grade TP304L. 27

E. Fittings: As specified in Section 15060. 28

F. Backing Flanges: AISI Type 304 stainless steel plate, with ANSI/ASME B16.5, Class 150 29 diameter and drilling; bolt holes shall be enlarged to accept bolt insulating sleeves; with the 30 following thickness: 31

32 Nominal Pipe Size (IN)

Flange Thickness (IN)

1/2 - 8 1/2 10 – 14 5/8 16 – 18 3/4 20 – 30 1

33

G. Flange Bolts and Nuts: As specified in Section 15060. 34

H. Insulated Flanges: 35 1. Gaskets: PSI “Linebacker, Type E”, full faced, insulating and sealing flange gasket. 1/8 IN 36

thick Pyrox G-10 glass reinforced epoxy retainer with teflon quad-ring seal. Inside diameter 37 shall be 1/8 IN less than inside diameter of flange. 38

2. Sleeves: Pyrox G-10 insulated sleeve, 1/32 IN thick, for each flange bolt. 39

Page 90: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 4

3. Washers: 1 a. Insulating: Two flat Pyrox G-10 insulating washers, 1/8 IN thick, for each flange bolt. 2 b. Metal: Two (2) flat AISI Type 304 stainless steel washers, 1/8 IN thick, for each flange 3

bolt. OD shall not be larger than OD of insulating washer. 4 c. Primer: Tapecoat “TC Coldprime”. 5

I. Lateral Screens: Type 304 Stainless Steel, wire wrapped. 6

2.2 PERFORMANCE AND DESIGN REQUIREMENTS 7

A. The horizontal collector well shall be designed for the following minimum operating conditions 8 and requirements unless otherwise noted. 9

10 Anticipated Minimum Capacity 12.0 MGD Anticipated Maximum Capacity 20 MGD Minimum Inside Caisson Diameter 16 FT Minimum Outside Caisson Diameter 19 FT Minimum Number of Laterals 13 Number of Lateral Tiers 2 Caisson shoe elevation 1048.00 FT Elevation Caisson floor elevation 1052.00 FT Elevation Centerline of Lower Laterals 1055.00 FT Elevation Centerline of Upper Laterals 1059.00 FT Elevation Min Concrete Bottom Plug Thickness 4 FT Min Number of Ports 15 Estimated Effective Length 185 FT per lateral Min Lateral Diameter 10 IN Max Screen Entrance Velocity 2 FT/min (50% blockage) at 20 MGD Max Lateral In-Line Velocity 5 FT/Sec

11

B. The horizontal collector well caisson shall be designed to meet the following minimum 12 structural requirements: 13 1. Assumed wall thickness is shown on Drawings. If different wall thickness is desired contact 14

Engineer for resolution prior to installation. Contractor shall coordinate all pump station 15 dimensions with caisson wall thickness and vertical alignment. 16

2. Contractor to establish end bearing and skin friction values as required for design and 17 construction. 18

3. Caisson shaft shall be designed according to requirements of ACI 350. 19 a. Design for loading indicated on the Drawings. 20 b. Use requirements of ASCE 7 as referenced by the Building Code to develop caisson 21

loads acting in addition to the pump station loads shown on the Drawings. 22 c. Use load combinations in ACI 350 to obtain required strength. 23 d. Design for groundwater level as follows: 24

1) Minimum water level at lowest drawdown elevation 25 2) Maximum water level at 500 year flood elevation shown on Drawings. 26 3) Bottom plug shall be designed as required for construction and to resist hydrostatic 27

pressure with an empty caisson and maximum design groundwater. 28 4) Design entire caisson system to resist flotation in its completed state. 29

e. Design to resist flotation of caisson during construction. If external restraint or 30 flooding of caisson is required to resist flotation after completion of the plug but prior 31 to project completion, show critical water levels on shop drawings. 32

f. Design caisson to resist loads that may be encountered during construction, including 33 point and unbalanced pressure loads on caisson cutting edge, restraint loads from a 34 deadman or other driving aids, and tension loads from loss of vertical support in lower 35 caisson during driving. 36

4. Design caisson for pipe penetrations and structural connections shown on Drawings. 37

Page 91: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 5

2.3 WALL PORTS 1

A. The ports for the well laterals shall be fabricated of Type 304 stainless steel. The flanges shall 2 be threaded for standard studs. Port assemblies shall be in accordance with the Contractor’s 3 design and shall be submitted to the Engineer for approval. Unused ports shall be furnished with 4 blind flanges. 5

2.4 LATERAL PIPE 6

A. Lateral pipe shall be stainless steel as indicated in the materials list. 7 1. Threaded Joints: 8

a. Pipe threads shall conform to ANSI/ASME B1.20.1, NPT, and shall be fully and 9 cleanly cut with sharp dies. Not more than three threads at each pipe connection shall 10 remain exposed after installation. Ends of pipe shall be reamed, after threading and 11 before assembly, to remove all burrs. Threaded joints in stainless steel piping shall be 12 made up with teflon thread sealer and teflon thread tape applied to all male threads. 13

2. Flanged Joints: 14 a. Flanged joints between cast-iron valves and stainless steel flanges shall use insulated 15

flange kits as specified in the materials section. Insulated flange kits shall be installed 16 in accordance with the manufacturer’s recommendations. Flange bolts shall be 17 tightened sufficiently to slightly compress the gasket and effect a seal, but not so tight 18 as to fracture or distort the flanges. Anti-seize thread lubricant shall be applied to the 19 threaded portion of all stainless steel bolts during assembly. 20

b. Welded Joints: 21 1) Welding shall conform to the specifications and recommendations in the "Code for 22

Pressure Piping", ANSI B31.1. 23

2.5 SCREEN 24

A. Screens shall be of continuous slot, wire-wound construction, as manufactured by Johnson, or 25 approved equal, with flush joint connections and have a minimum diameter as specified in 26 Paragraph 2.2.A. Screens shall be sized to provide the specified well capacity in accordance 27 with the manufacturer's design, pipe-size type, with flush joint connections. Screens shall be 28 adequate to provide the specified capacities with an average entrance velocity through the screen 29 openings of 2.0 FT per minute or less assuming a screen blockage of 50 percent. The number, 30 length and orientation of the lateral screens are as shown on the drawings. The intent of the 31 specifications is to have thirteen 185 FT laterals, each equipped with 175 FT of screen. The slot 32 openings of the lateral screens shall be determined by the Contractor to produce the specified 33 yield and meet the sand production limits as specified in Article 3.3. Actual screen slot sizes 34 shall be determined based upon selected sieve analyses of samples collected at 5 FT intervals 35 during lateral pipe projection and subject to the approval of the Engineer prior to installation. 36 Screen collapse strength shall include a safety factor of 2 times the ground/loading pressure 37 across the entire range of anticipated slot sizes. Screen projection pipe shall be sized to install 38 the screen. If filter pack is used, screen slots shall be sized to retain 90 percent or more of the 39 filter pack. Pipe shall be of sufficient strength to withstand the stresses of projection into and 40 withdrawal from the aquifer. 41

2.6 FILTER PACK 42

A. Provide filter pack material consisting of clean well rounded grains that are smooth and uniform. 43 The material shall be ceramic or glass beads, or siliceous natural aggregate with a limit of 5 44 percent by weight of calcareous material. 45

B. Provide filter pack consisting of hard, rounded grains with an average specific gravity of not less 46 than 2.5. Not more than 1 percent by weight of the material shall have a specific gravity of 2.25 47 or less. 48

Page 92: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 6

C. Provide filter material containing not more than 2 percent by weight of thin, flat or elongated 1 pieces and free of shale, mica, clay, sand, dirt, loam, and organic impurities and containing no 2 iron or manganese in a form which will adversely affect water quality. 3

D. Gradation: Contractor shall select gravel pack gradation subject to review by Engineer. The 4 acceptable filter pack envelope for the lateral screens will be based on the results of the grain 5 size distribution analysis performed on samples collected during jacking of the blank projection 6 pipe. 7 1. A multiplier range of 3 to 6 times the d30 (cumulative percent passing) of the finest sample 8

within the screened interval of each production well is acceptable for the filter pack. 9 2. Engineer will supply sieve analysis from formation samples collected during test drilling at 10

production well locations. 11 3. The recommended filter pack should have a uniformity coefficient of < 2.5. 12

PART 3 - EXECUTION 13

3.1 CAISSON CONSTRUCTION 14

A. The caisson shall be constructed in lifts by the open caisson method. 15 1. The deviation from plumb shall not exceed 15 IN in 100 FT. 16

a. Any correction of caisson deviation, and any construction and associated costs resulting 17 from relocation of appurtenances inside the caisson, including but not limited to pumps, 18 motors, power supply, piping, controls, valves, valve stems, etc., caused deviation of 19 the caisson from vertical shall be at the Contractor’s expense. 20

2. Final caisson lift shall be formed vertical. 21 3. Terminate the top of the caisson at the elevation shown on the plans. The top of the caisson 22

shall be finished flush within ±0.25 FT of the finished elevation. 23 4. At each concrete lift or construction joint, provide 6 IN PVC continuous waterstop across 24

joint. 25

B. At the option of the Contractor, a dead man and hydraulic ram system may be used to pull the 26 caisson in to the ground. 27

C. If a concrete dead man is cast around the caisson, top of concrete for this dead man must be at or 28 below elevation 1158.00 FT MSL at the completion of caisson construction. Contractor shall 29 remove all portions of the deadman that interfere with site piping, electrical conduit, grounding, 30 or other utilites. When the cutting edge of the caisson has been sunk to at least 1048.00 FT 31 MSL, and the top of the caisson is at the final elevation, the Contractor shall clean the cutting 32 shoe bevel area and place plug concrete by tremie. After the plug has attained design 33 compressive strength, the Contractor shall dewater the caisson and remove all loose material to 34 a sound surface. Place a concrete floor surface with a wood float finish. 35

D. The interior of the caisson shall be cleaned of all debris, materials, and equipment and left 36 washed clean prior to performance testing. 37

E. Within 4 weeks of final completion, review grading around the caisson for any low spots or 38 areas of improper drainage away from the structure. Make final finish grading corrections as 39 required. 40

Page 93: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 7

3.2 SCREEN INSTALLATION 1

A. Lateral screens shall be installed at an elevation and in the orientation as shown on the drawings. 2 Installation of lateral screens shall proceed initially by jacking blank projection pipe into the 3 aquifer radially from the central caisson to the required distance from the caisson wall or to 4 refusal or an indication of excessive jacking pressure. After the blank pipe has been projected, 5 lateral screens shall be inserted into the projection pipe, and then the projection pipe shall be 6 withdrawn. Each line of lateral screen shall be completed with 10 FT of blank pipe extending 7 from the inside wall of the caisson. The blank pipe shall conform to the requirements specified 8 for stainless steel lateral pipe. Any lateral terminated less than 50 FT from the interior caisson 9 wall will be considered ineffective and shall be closed with a blind flange and abandoned; its 10 length shall not be counted in computing the total aggregate screen length required to be 11 installed to meet contract requirements. 12

B. Each lateral shall be installed horizontally in a straight radial line throughout its full length. 13 Deviation of more than one foot from horizontal shall be immediately called to the attention of 14 the Engineer, and deviation of more than 1 foot vertically in 100 horizontal feet is unacceptable. 15 The Contractor shall provide during projection suitable means to effect removal of aquifer 16 material equal to the minimum of the volume of the pipe projected. At the conclusion of lateral 17 installation, all installation equipment and appurtenances shall be removed from the interior of 18 the screen pipe and the control valve shall be affixed to the interior end and shall be closed to 19 await development. 20

3.3 LATERAL DEVELOPMENT 21

A. Each lateral screen shall be developed by hydraulically isolating the screen in sections not to 22 exceed 6 FT in length. Development shall be by jetting, compressed air, flushing, or by a 23 combination of these methods. Alternative methods may be utilized, subject to review and 24 acceptance by the Engineer. Development shall be continued until one of the following 25 conditions can be demonstrated, and each line shall be tested individually. 26 1. Sand production from each screen line is less than 3 ppm at a flow rate equivalent to at least 27

1.2 times the desired design rate times the total length of that line. 28 2. Maximum sand production from all screen lines shall be less than 2 ppm during pumping of 29

the collector well at a discharge rate of 20 MGD. 30 3. Sand production from each isolated section of the screen has reached stability and cannot be 31

improved by further development. 32

B. To demonstrate compliance with the above conditions, sand production shall be measured by a 33 centrifugal sand separating device or Rossum Sand Tester attached to the discharge line, and 34 flow rates shall be measured using either a flow meter or free discharge orifice as discussed in 35 Article 3.4. The Contractor shall furnish all required test equipment. The Engineer shall be the 36 final judge of whether or not development of the well has attained these objectives, and is, 37 therefore, complete. 38

C. Water produced during development pumping shall remain on-site and appropriate 39 erosion/sedimentation control measures, which may include straw bales and filter fencing, will 40 be employed to prevent the discharge of sediment to the Missouri River. After sediment 41 separation, water may be discharged to the Missouri River 42

3.4 PERFORMANCE TESTING 43

A. After development of the horizontal collector well, pumping tests shall be conducted to 44 determine its installed capacity. A multiple step drawdown pumping test shall be conducted to 45 determine the efficiency and optimum rate of pumping for the well; a constant rate method 46 pumping test shall be conducted to evaluate impact on the surrounding area and to confirm 47 capacity. 48

Page 94: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 8

B. The Contractor shall be required to pump the wells during the tests for the full-specified period 1 without shutdown. Water level measurements shall be made in the horizontal collector well, in 2 existing Observation Wells (OW) Nos. OW-1-13, OW- 3-13, OW-2-13, OW-75P, and OW-60R, 3 and a river stilling well during the test at intervals and in the manner directed by the Engineer. 4

C. After drawdown has substantially stabilized, the Contractor shall measure the velocity of the 5 flow and water temperature from each lateral using remote measuring equipment. The 6 Contractor shall furnish all necessary equipment to conduct the specified pump tests. All 7 measurements of drawdown shall be made with an electric tapeline, or automated measuring 8 device and shall be accurate within ±0.01 FT. Power to drive the pumps at the site will be 9 furnished by the Contractor. The Contractor shall be responsible for providing power to all 10 equipment for the pump tests. 11

D. Flow shall be measured using standard free-discharging circular pipe orifices. The orifices shall 12 be constructed and operated in accordance with ASTM D5716. If multiple discharge pipes are 13 used, the Contractor shall monitor flow on each discharge. The discharge pipe must extend a 14 distance of at least 10 pipe diameters back of the orifice plate. Exactly 24 IN from the orifice 15 plate, or 3 pipe diameters, whichever is greater, the pipe wall shall be tapped midway between 16 the top and bottom with a 1/8 or 1/4 IN hole. No burrs shall be inside the pipe. The tap shall be 17 fitted with a nipple that does not protrude inside the pipe. The nipple shall be fitted with a 18 transparent flexible tube attached to an accurate scale set to measure the pressure head above the 19 centerline of the pipe. If multiple discharge pipes are required, the Contractor shall monitor flow 20 on each discharge. 21

E. The Owner intends to conduct water quality testing throughout the project. The Contractor shall 22 provide sampling ports on discharge piping and assist the Owner in obtaining water samples as 23 required. 24

F. During development of the well and during the period of final testing of the well, the Contractor 25 shall be required to discharge the water to the Missouri River. The Engineer will assist Owner in 26 obtaining discharge permit. The method of discharge shall be in accordance with all applicable 27 rules and regulations and shall be acceptable to the Engineer. The Contractor shall furnish all 28 labor, materials, and equipment for constructing temporary pipelines. 29 1. Stepped-Rate Drawdown Pumping Test: 30

a. Following completion of the well, the well shall be allowed to recover for at least 31 48 HRS before the stepped-rate drawdown pumping test is started. The stepped-rate 32 drawdown pumping test period shall be 8 HRS pumping and 2 HRS recovery time. To 33 confirm compliance with specified sand content requirements (2 ppm or less), a sand 34 test as specified in Article 3.3 shall be conducted at the end of each step. If the average 35 of these four tests is greater than 2.0 ppm, additional development will be required. 36

b. The stepped-rate drawdown test shall be an increasing rate type pumping test in which 37 pumping rates shall be as follows: 38

39 Step Rate Period 1 3500 gpm 2 hours 2 8300 gpm 2 hours 3 11,100 gpm 2 hours 4 13,900 gpm 2 hours

40 c. During each step of the stepped-rate drawdown test, water levels will be measured at 41

the following frequencies (at a minimum) at the following monitoring points. Water 42 levels at all of the measurements points shall be collected using an electronic water 43 meter prior to initiating the stepped-rate test and at the end of the recovery period. 44 Measurements collected using electronic water meters will be recorded on standardized 45 data forms. 46 1) Collector Well: 47

a) Every 1 minute for the first 15 minutes from the start of each step; 48

Page 95: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 9

b) Every 5 minutes for 15 to 60 minutes from the start of the step; 1 c) Every 10 minutes for 60 to 120 minutes from the start of the step; 2

2) Observations Wells (with transducers provided by Contractor): 3 a) Every 5 minutes throughout the testing period. 4

3) River (stilling well): 5 a) Every 10 minutes throughout testing period. 6

d. The pumping rate shall also be measured and recorded to every 10 minutes. Following 7 the shut down of the pump, water levels measurements will be collected at the same 8 frequency noted above for 2 HRS. Optimum rate of pumping for the Collector Well 9 shall be determined by Contractor in consultation with the Engineer from the results of 10 the step drawdown test. 11

e. Sand content testing: 12 1) The sand content shall be determined by collecting well samples at the following 13

times during the final step of the Stepped-Rate Drawdown Pumping Test: 14 a) 1 minute after the start of the test. 15 b) 5 minutes after the start of the test. 16 c) 10 minutest after the start of the test. 17 d) 15 minutes after start of the test. 18 e) 20 minutes after start of the test. 19 f) 25 minutes after start of the test. 20 g) After 1/4 of the total planned test time has elapsed. 21 h) After 1/2 of the time has elapsed. 22 i) After 3/4 of the time has elapsed. 23 j) Near the end of the pumping test. 24

2) The maximum acceptable sand content shall be 3 mg/l from any one measurement. 25 The maximum average sand content for the time intervals specified above shall be 26 2 mg/l or less. every sample without exception. 27

3) Sand content shall be determined by using a Rossum testing apparatus as available 28 from Roscoe Moss Company, Los Angeles, California, or equivalent. 29

2. Constant Rate Test: 30 a. Following the stepped-rate method pumping test, the well shall be allowed to recover 31

for at least 16 HRS before the constant rate method pumping test is started. The 32 constant rate method pumping test period shall be 72 HRS pumping time and 24 HRS 33 recovery time. To confirm compliance with specified sand content requirements (2 34 ppm or less), a sand test as specified in Article 3.3 shall be conducted at elapsed times 35 of 1 HR, 24 HRS and 48 HRS during the constant rate test. If the average of these three 36 tests is greater than 2.0 ppm, additional development will be required. The optimum 37 rate of pumping determined by the Contractor in consultation with the Engineer from 38 the step drawdown test shall be used for the constant rate pumping test. 39

b. During the test, discharge from the pumping well will be maintained at a constant rate 40 (within 5%), with flow monitored by the metering equipment specified. The pumping 41 rate will be 20 MGD and based upon the results from the variable (stepped) rate 42 pumping test. At the conclusion of the test, the pump will be shut off and the recovery 43 of water levels monitored for 24 hours. Water levels at all of the measurements points 44 shall be collected using an electronic water meter prior to initiating the constant rate 45 test, minimally daily during the constant rate test, prior to the end of the pumping 46 portion of the test, and at the end of the recovery period. During the constant rate test, 47 water levels measurements will be collected at the following frequencies at the 48 following monitoring points, and measurements obtained using electronic water meters 49 will be recorded on standardized data forms. 50 1) Collector Well: 51

a) Every 1 minute for the first 15 minutes from the start of the test; 52 b) Every 5 minutes for 15 to 60 minutes from the start of the test; 53 c) Every 10 minutes for 60 to 120 minutes from the start of the test; 54 d) Every 20 minutes for 120 to 180 minutes from the start of the test; 55 e) Every 30 minutes for 180 to 300 minutes from the start of the test; 56

Page 96: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 10

f) Every 60 minutes for 300 to 4320 minutes from the start of the test; 1 2) Observation Wells (with transducers provided by Contractor): 2

a) Every 1 minute for 1 to 10 minutes from the start of the test; 3 b) Every 5 minutes for 10 to 60 minutes from the start of the test; 4 c) Every 10 minutes for 60 to 180 minutes from the start of the test; 5 d) Every 30 minutes for 180 to 600 minutes from the start of the test; 6 e) Every 60 minutes for 600 to 4320 minutes from the start of the test 7

3) River (stilling well): 8 a) Every 10 minutes throughout testing period. 9

c. Recovery Frequency and period shall be measured to the above drawdown schedule for 10 a period of 24 HRS. However, if the Engineer determines that the recovery level has 11 stabilized to the natural static water level, measurements may be discontinued. The 12 pumping rate shall also be measured and recorded at the same frequency listed above. 13

3. Well efficiency: 14 a. Minimum well efficiency shall be 80 percent or greater as calculated by Engineer. 15 b. Engineer shall use the Cooper-Jacob Distance Drawdown Method based on the constant 16

rate test data to calculate well efficiency. 17 c. If the calculated well efficiency is below 80 percent, the Contractor shall be responsible 18

to do the following: 19 1) Redevelop and retest (variable and constant rate) the well to meet the well 20

efficiency requirements at no additional cost to the Owner. 21 4. Test Report: 22

a. The Contractor shall furnish to the Engineer copies of the field data, any calculations 23 and graphs of water level plotted to logarithmic scale of the step and constant rate pump 24 tests performed for the well. 25

5. Aborted Test: 26 a. Failure of pump operation for a period longer than 2 percent of the elapsed pumping 27

time shall require suspension of the test until the water level in the pumped well has 28 recovered to within 95 percent of original level. Once the water level has recovered, 29 the test must be restarted. Recovery shall be considered "complete" after the well has 30 been allowed to rest for a period at least equal to the elapsed pumping time of the 31 aborted test, except that if any three successive water level measurements spaced at 32 least 20 minutes apart show no further rise in the water level in the pumped well, the 33 test may be resumed immediately. The Engineer shall be the sole judge as to whether 34 this latter condition exists. 35

G. Production Well Water Quality and Sampling Analysis: 36 1. During the constant rate test, collect water quality samples at the beginning, middle and end 37

of the constant rate test. 38 a. Samples will be collected for radiological, EPA priority pollutants and general water 39

quality, including ammonia and TOC. 40 b. Sample bottles, sample shipment and testing will be the responsibility of Contractor. 41 c. Provide 24 HR notice to Engineer prior to sampling. 42

1) Engineer shall witness the collection of sample, preparation of sample for shipment 43 and be provided confirmation of shipment. 44

3.5 EROSION AND POLLUTION CONTROL 45

A. During construction and pumping tests, the Contractor shall employ techniques to prevent 46 harmful materials, construction debris, and excessive suspended solids from entering the 47 waterway. The Contractor shall submit his proposed methods to the Engineer for review prior to 48 the start of well construction and shall address the following: 49 1. Diversion of sand, silt, and debris removed from the bottom of the caisson and pumped 50

discharges carrying these materials, to prevent erosion and runoff of solids and debris. 51 2. Protection of the site from surface erosion during construction. 52 3. Disposal of waste construction materials, including concrete wash. 53

Page 97: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 11

4. Disposal of other potential contaminants that would otherwise be dumped, sprayed, or 1 placed near waterways or disposed of onsite. 2

3.6 CONCRETE FINISHES 3

A. See Section 03348 for concrete finishes exterior above grade and interior concrete finishes. 4

3.7 CONCRETE TESTING 5

A. Testing for cast in place concrete shall be in accordance with Section 03350. 6

END OF SECTION 7

8

Page 98: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HORIZONTAL COLLECTOR WELL 13200 - 12

1

Page 99: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440 - 1

2014/10/08 1

SECTION 13440 2

INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Basic requirements for complete instrumentation system for process control. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 10400 - Identification Devices. 11 4. Section 13448 - Control Panels and Enclosures. 12 5. Division 16 - Electrical. 13 6. Section 16120 - Wire and Cable - 600 Volt and Below. 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. Canadian Standards Association (CSA). 17 2. FM Global (FM). 18 3. The Instrumentation, Systems, and Automation Society (ISA): 19

a. S5.1, Instrumentation Symbols and Identification. 20 b. S5.3, Graphic Symbols for Distributed Control/Shared Display Instrumentation, Logic 21

and Computer Systems. 22 c. S5.4, Standard Instrument Loop Diagrams. 23 d. S20, Standard Specification Forms for Process Measurement and Control Instruments, 24

Primary Elements and Control Valves. 25 4. National Electrical Manufacturers Association (NEMA): 26

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 27 5. National Fire Protection Association (NFPA): 28

a. 70, National Electrical Code (NEC). 29 6. National Institute of Standards and Technology (NIST). 30 7. Underwriters Laboratories, Inc. (UL): 31

a. 913, Standard for Safety, Intrinsically Safe Apparatus and Associated Apparatus for 32 Use in Class I, II, and III, Division 1, Hazardous (Classified) Locations. 33

B. Pre-Negotiated Pricing: 34 1. The Owner has negotiated a price for procuring most of the equipment and manufacturer’s 35

services associated with Specification Sections 13440 through 13504. The pricing is listed 36 in the Bid Form. In addition to this cost, the Contractor shall include in its Bid additional 37 costs for unloading, storage, provision, installation, startup, demonstration, all applicable 38 taxes and fees, and other appurtenant costs associated with the control system as required to 39 meet all requirements of these Contract Documents. 40

2. The proposal defining materials and services provided for the pricing shown in the Bid 41 Form is attached at the end of this Specification Section. In addition, the Contractor shall 42 include in its Bid any and all requirements of these Specification Sections that are not 43 included in Huffman Engineering’s proposal. 44

Page 100: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440 - 2

C. Pre-Approved Instrumentation and Control System Integrator: 1 1. Design Solutions & Integration (DSI, Inc.). 2

716 N Helen Ave. 3 Sioux Falls, SD 57104 4 (605)-330-0202 5

D. Miscellaneous: 6 1. Comply with electrical classifications and NEMA enclosure types shown on Drawings. 7

1.3 DEFINITIONS 8

A. Architecturally finished area: Offices, laboratories, conference rooms, restrooms, corridors and 9 other similar occupied spaces. 10

B. Non-architecturally Finished Area: Pump, chemical, mechanical, electrical rooms and other 11 similar process type rooms. 12

C. Outdoor Area: Exterior locations where the equipment is normally exposed to the weather and 13 including below grade structures, such as vaults, manholes, handholes and in-ground pump 14 stations. 15

D. Calibrate: To standardize a device so that it provides a specified response to known inputs. 16

1.4 SYSTEM DESCRIPTION 17

A. Control System Requirements: 18 1. This Specification Section provides the general requirements for the instrument and control 19

system. 20 2. The instrument and control system consists of all primary elements, transmitters, switches, 21

controllers, computers, recorders, indicators, panels, signal converters, signal boosters, 22 amplifiers, special power supplies, special or shielded cable, special grounding or isolation, 23 auxiliaries, software, wiring, and other devices required to provide complete control of the 24 plant as specified in the Contract Documents. 25

B. All signals shall be directly linearly proportional to measured variable unless specifically noted 26 otherwise. 27

C. Single Instrumentation Subcontractor: 28 1. Furnish and coordinate instrumentation system through a single instrumentation 29

subcontractor. 30 a. The instrumentation subcontractor shall be responsible for functional operations of all 31

systems, performance of control system engineering, supervision of installation, final 32 connections, calibrations, preparation of Drawings and Operation and Maintenance 33 Manuals, start-up, training, demonstration of substantial completion and all other 34 aspects of the control system. 35

2. Ensure coordination of instrumentation with other work to ensure that necessary wiring, 36 conduits, contacts, relays, converters, and incidentals are provided in order to transmit, 37 receive, and control necessary signals to other control elements, to control panels, and to 38 receiving stations. 39

3. Prior to Shop Drawing preparation, the Instrumentation Subcontractor shall inspect the 40 Owner's existing equipment and as-constructed electrical documentation so as to be able to 41 fully coordinate the interface of new and existing instrumentation and controls. 42

4. All costs associated with this Work shall be incorporated into the original bid. 43 5. Although such Work is not specifically indicated, furnish and install all supplementary or 44

miscellaneous items, appurtenances and devices incidental to or necessary for a sound, 45 secure, complete and compatible installation. 46

Page 101: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440 - 3

1.5 SUBMITTALS 1

A. Shop Drawings: 2 1. See Specification Section 01340 for requirements for the mechanics and administration of 3

the submittal process. 4 2. Submittals shall be original printed material or clear unblemished photocopies of original 5

printed material. 6 a. Facsimile information is not acceptable. 7

3. Limit the scope of each submittal to one (1) Specification Section. 8 a. Each submittal must be submitted under the Specification Section containing 9

requirements of submittal contents. 10 b. Do not provide any submittals for Specification Section 13440. 11

4. Product technical data including: 12 a. Equipment catalog cut sheets. 13 b. Instrument data sheets: 14

1) ISA S20 or approved equal. 15 2) Separate data sheet for each instrument. 16

c. Materials of construction. 17 d. Minimum and maximum flow ranges. 18 e. Pressure loss curves. 19 f. Physical limits of components including temperature and pressure limits. 20 g. Size and weight. 21 h. Electrical power requirements and wiring diagrams. 22 i. NEMA rating of housings. 23 j. Submittals shall be marked with arrows to show exact features to be provided. 24

5. Comprehensive set of wiring diagrams as specified in Specification Section 13448. 25 6. Panel fabrication Drawings as specified in Specification Section 13448. 26 7. PLC equipment Drawings. 27 8. HMI graphics. 28 9. Nameplate layout Drawings. 29 10. Drawings, systems, and other elements are represented schematically in accordance with 30

ISA S5.1 and ISA S5.3. 31 a. The nomenclature, tag numbers, equipment numbers, panel numbers, and related series 32

identification contained in the Contract Documents shall be employed exclusively 33 throughout submittals. 34

11. All Shop Drawings shall be modified with as-built information/corrections. 35 12. All panel and wiring drawings shall be provided in both hardcopy and softcopy. 36

a. Furnish electronic files on CD-ROM or DVD-ROM media. 37 b. Drawings in AUTO CAD format. 38

13. Provide a parameter setting summary sheet for each field configurable device. 39 14. Certifications: 40

a. Documentation verifying that calibration equipment is certified with NIST traceability. 41 b. Approvals from independent testing laboratories or approval agencies, such as UL, FM 42

or CSA. 43 1) Certification documentation is required for all equipment for which the 44

specifications require independent agency approval. 45 15. Testing reports: Source quality control reports. 46

B. Operation and Maintenance Manuals: 47 1. See Specification Section 01342 for requirements for: 48

a. The mechanics and administration of the submittal process. 49 b. The content of Operation and Maintenance Manuals. 50

2. Warranties: Provide copies of warranties and list of factory authorized service agents. 51

Page 102: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440 - 4

1.6 DELIVERY, STORAGE, AND HANDLING 1

A. Do not remove shipping blocks, plugs, caps, and desiccant dryers installed to protect the 2 instrumentation during shipment until the instruments are installed and permanent connections 3 are made. 4

1.7 SITE CONDITIONS 5

A. Unless designated otherwise on the Drawings, area designations are as follows: 6 1. Outdoor area: 7

a. Wet. 8 b. Corrosive and/or hazardous when specifically designated on the Drawings or in the 9

Specifications. 10 c. Below grade vaults and manholes: 11

1) Subject to temporary submergence when specifically designated on the Drawings 12 or Specifications. 13

2. Architecturally finished area: 14 a. Dry. 15 b. Noncorrosive unless designated otherwise on the Drawings or in the Specifications. 16 c. Nonhazardous unless designated otherwise on the Drawings or in the Specifications. 17

3. Non-architecturally finished area: As designated elsewhere on the Drawings or in the 18 Specifications. 19

PART 2 - PRODUCTS 20

2.1 NEMA TYPE REQUIREMENTS 21

A. Provide enclosures/housing for control system components in accordance with the following: 22 1. Areas designated as wet: NEMA Type 4. 23 2. Areas designated as wet and/or corrosive: NEMA Type 4X. 24 3. Areas designated as Class I hazardous, Groups A, B, C, or D as defined in NFPA 70: 25

a. NEMA Type 7 unless all electrical components within enclosure utilize intrinsically 26 safe circuitry. 27 1) Utilize intrinsically safe circuits to the maximum extent practical and as depicted in 28

the Contract Documents. 29 4. Areas designated as Class II hazardous, Groups E, F, or G as defined in NFPA 70: 30

a. NEMA Type 9 unless all electrical components within enclosure utilize intrinsically 31 safe circuitry. 32 1) Utilize intrinsically safe circuits to the maximum extent practical and as depicted in 33

the Contract Documents. 34 5. Either architecturally or non-architecturally finished areas designated as dry, noncorrosive, 35

and nonhazardous: NEMA Type 12. 36 6. Areas designated to be subject to temporary submersion: NEMA 6P. 37

2.2 PERFORMANCE AND DESIGN REQUIREMENTS 38

A. System Operating Criteria: 39 1. Stability: After controls have taken corrective action, as result of a change in the controlled 40

variable or a change in setpoint, oscillation of final control element shall not exceed two (2) 41 cycles per minute or a magnitude of movement of 0.5 percent full travel. 42

2. Response: Any change in setpoint or change in controlled variable shall produce a 43 corresponding corrective change in position of final control element and become stabilized 44 within 30 seconds. 45

3. Agreement: Setpoint indication of controlled variable and measured indication of controlled 46 variable shall agree within 3 percent of full scale over a 6:1 operating range. 47

Page 103: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440 - 5

4. Repeatability: For any repeated magnitude of control signal, from either an increasing or 1 decreasing direction, the final control element shall take a repeated position within 0.5 2 percent of full travel regardless of force required to position final element. 3

5. Sensitivity: Controls shall respond to setpoint deviations and measured variable deviations 4 within 1.0 percent of full scale. 5

6. Performance: All instruments and control devices shall perform in accordance with 6 manufacturer's specifications. 7

2.3 ACCESSORIES 8

A. Provide identification devices for instrumentation system components in accordance with 9 Specification Section 10400. 10

B. Provide corrosion resistant spacers to maintain 1/4 IN separation between equipment and 11 mounting surface in wet areas, on below grade walls and on walls of liquid containment or 12 processing areas such as Clarifiers, Digesters, Reservoirs, etc. 13

PART 3 - EXECUTION 14

3.1 INSTALLATION 15

A. Wherever feasible, use bottom entry for all conduit entry to instruments and junction boxes. 16

B. Install electrical components per Division 16. 17

C. Panel-Mounted Instruments: 18 1. Mount and wire so removal or replacement may be accomplished without interruption of 19

service to adjacent devices. 20 2. Locate all devices mounted inside enclosures so terminals and adjustment devices are 21

readily accessible without use of special tools and with terminal markings clearly visible. 22

D. See Specification Section 16120. 23

3.2 FIELD QUALITY CONTROL 24

A. See Specification Section 01650. 25

B. Maintain accurate daily log of all startup activities, calibration functions, and final setpoint 26 adjustments. 27 1. Documentation requirements include the utilization of the forms located at the end of this 28

Specification Section. 29 a. Loop Check-out Sheet. 30 b. Instrument Certification Sheet. 31

C. Instrumentation Calibration: 32 1. Verify that all instruments and control devices are calibrated to provide the performance 33

required by the Contract Documents. 34 2. Calibrate all field-mounted instruments, other than local pressure and temperature gages, 35

after the device is mounted in place to assure proper installed operation. 36 3. Calibrate in accordance with the manufacturer's specifications. 37 4. Bench calibrate pressure and temperature gages. 38

a. Field mount gage within seven (7) days of calibration. 39 5. Check the calibration of each transmitter and gage across its specified range at 0, 25, 50, 75, 40

and 100 percent. 41 a. Check for both increasing and decreasing input signals to detect hysteresis. 42

6. Replace any instrument which cannot be properly adjusted. 43 7. Stroke control valves with clean dry air to verify control action, positioner settings, and 44

solenoid functions. 45

Page 104: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION FOR PROCESS CONTROL: BASIC REQUIREMENTS 13440 - 6

8. Calibration equipment shall be certified by an independent agency with traceability to NIST. 1 a. Certification shall be up-to-date. 2 b. Use of equipment with expired certifications shall not be permitted. 3

9. Calibration equipment shall be at least three (3) times more accurate as the device being 4 calibrated. 5

D. Loop check-out requirements are as follows: 6 1. Check control signal generation, transmission, reception and response for all control loops 7

under simulated operating conditions by imposing a signal on the loop at the instrument 8 connections. 9 a. Use actual signals where available. 10 b. Closely observe controllers, indicators, transmitters, HMI displays, recorders, alarm and 11

trip units, remote setpoints, ratio systems, and other control components. 12 1) Verify that readings at all loop components are in agreement. 13 2) Make corrections as required. 14

a) Following any corrections, retest the loop as before. 15 2. Stroke all control valves, cylinders, drives and connecting linkages from the local OIT 16

(Operator Interface Terminal and from the remote control room HMI (Human Machine 17 Interface). 18

3. Check all interlocks to the maximum extent possible. 19 4. In addition to any other as-recorded documents, record all setpoint and calibration changes 20

on all affected Contract Documents and turn over to the Owner. 21

E. Provide verification of system assembly, power, ground, and I/O tests. 22

F. Verify existence and measure adequacy of all grounds required for instrumentation and controls. 23

END OF SECTION 24

Page 105: City of Yankton, SD

October 6, 2014 Dave Penner HDR Engineering INC. Re: Yankton WTP Collector Well Addition Scope Letter DSI Quote # XXXXXX-XXXX Design Solutions & Integration is pleased to provide the following scope letter on the controls integration of the Horizontal Collector Well for the City of Yankton WTP. Sections that we are covering are 13440. 13441, 13442, 13446, 13447, 13448, 13449, 13500, 13502 and 13504. DSI will be providing control panels, instrumentation and programming. Below is a list of control panels to be provided: 1. One Collector Well PLC Panel 2. One Remote I/O Panel Below is a list of instrumentation to be provided: 1. Three flow meters- (FE/FIT-01, FE/FIT-02, FE/FIT-03) 2. One Pressure Transmitter (PIT-05) 3. Three Pressure Switches (PSH-01, PSH-02, PSH-03) 4. Four Pressure Gages (PI-01, PI-02, PI-03, PI-05) 5. One Submersible Level Transmitter (LT-06) 6. Four Door Switches (ZS-50, ZS-51, ZS-52, ZS-53) *Note- Pipe tubing, instrument valves, accessory hardware are not included and to be provided by others. Below is a list of Telemetry equipment to be provided: 1. One MDS iNET II Radio 2. One radio antenna and cables 3. One antenna mast and mounting hardware Labor Included in this quote 1. Drawings of control panels 2. UL 508A Listing 3. Panel building and factory test in shop 4. PLC Programming 5. HMI Programming 6. Startup Onsite 1 of 2

Page 106: City of Yankton, SD

DSI Quotation Number: XXXXXX-XXXX Re: Yankton WTP Collector Well Addition Scope Letter This quote does not include the following: 1. Installation of any kind onsite 2. Demolition of any kind onsite 3. Wiring of any kind onsite 4. Termination in control panels onsite 5. Termination of instrumentation onsite 6. Any taxes other than sales tax for DSI-furnished items Project Total price not including taxes……………………………………………………$xxxxx.xx Thanks for the opportunity and please call with any questions or concerns. Respectfully, Brian Pistulka 716 North Helen Ave Sioux Falls SD, 57104 (605)330-0202 ext 203 (605)330-0203 fax [email protected] Payment Terms: •Due net 30. •Prices are firm if accepted in within 60 days. Purchase Orders issued on the above proposal are subject to final acceptance by Design Solutions & Integration, Inc and to all of the Payment Terms listed on this proposal. Acceptance of this proposal indicates the purchaser’s agreement to these Payment Terms. Acceptance of Proposal – The preceding prices, specifications and Terms are satisfactory and hereby accepted. You are authorized to proceed. Signature Name Print/Type Official Position Date Page 2 of 2

Page 107: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Loop Check-out Sheet

Project Name: BIG PROJECT Owner’s Project No. (if applicable): Page 1 of 2

Project Owner: ABC Company Regulatory Agency Project No. (if applicable):

HDR Project No.: 10050-211-134 Date: 12/19/98

Control Loop No. 107

LEAK AND TERMINATION/CONTINUITY CHECKS FIELD CONTROL CAB

DESCRIPTION LEAK CHECK(1) TERM/CONT CHECK(2) TERM/CONT CHECK(2)

Device Tag No.

Process Conn.

Signal Tube

Device Tag No.

Termination Ident.

Device Tag No.

Termination Ident.

P201 Start Sig VFD-107 21, 22 PLC Cab 103, 104

P201, Speed inp VFD-107 27, 28 PLC Cab 67, 68, 69

P201 Start out VFD-107 31, 32 PLC Cab 72, 73, 74

Press transmit PIT-107 JS -- PIT-107 + / - PLC Cab 98, 99, 100

1. Leak check for pneumatic signal tubing to be per ISA-PR7.1. 2. Termination/continuity check includes check at terminated equipment for: (a) correct polarity, (b) appropriate signal generation, transmission

and reception, and (c) correct shield & ground terminations.

OPERATOR INTERFACE CHECK-OUT

MONITORING POINTS OBSERVED PARAMETER TYPE TAG NO. TAG NO. TAG NO. TAG NO. TAG NO. TAG NO.

PROCESS VAR PI-107A SI-107

EQUIP STATUS P201 ON P201 OFF V-107 open V-107 close

ALARM POINT PAH-107

OPERATOR CONTROL FUNCTIONS CHECKED FUNCTION TYPE TAG NO. LOCATION TAG NO. LOCATION TAG NO. LOCATION

H-O-A sel sw HS-107A VFD-107

L-O-R sel sw HS-107B @ P201

S/S switch HS-107C MCC HS-107D MCC

AS LEFT SETTINGS TAG NO. SWITCH & ALARM SP CONTROLLERS

Gain Reset, rpm Deriv. (rate), min PV Set Point

PAH-107 120 psi

SC-107 2.0 5.0 0.2 80 psi

Describe all interlocks checked, equipment started/stopped, valves/operators stroked. Describe modes of operation checked, and location of operator interface (local/remote). (1) HS-107B in Local: (a) start/stop operation via HS-107A and HS-107C, D (b) Manual/auto operation via HS-107A. In auto, pump stopped on hi press, started on lo press. (2) HS-107B in Remote: Observed operation from PLC-pump stopped on hi press, started on lo press. (3) Observed V-107 open/close automatically in accord with pump run condition. (4) Observed all indications and terminations shown above. (5) Tuned SC-107 I certify that the control loop referenced on this page has been completely checked and functions in accordance with applicable drawings and specifications. Certified by: Joe Smith Date: 12/19/98 (Work Performed By)

Page 108: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Loop Check-out Sheet

Project Name: BIG PROJECT Owner’s Project No. (if applicable): Page 2 of 2

Project Owner: ABC Company Regulatory Agency Project No. (if applicable):

HDR Project No.: 10050-211-134 Date: 12/19/98

Control Loop No. 107

LEAK AND TERMINATION/CONTINUITY CHECKS FIELD CONTROL CAB

DESCRIPTION LEAK CHECK(1) TERM/CONT CHECK(2) TERM/CONT CHECK(2)

Device Tag No.

Process Conn.

Signal Tube

Device Tag No.

Termination Ident.

Device Tag No.

Termination Ident.

V-107 open ZS ZSO-107 + / - PLC Cab 112, 113

V-107 close ZS ZSC-107 + / - PLC Cab 114, 115

1. Leak check for pneumatic signal tubing to be per ISA-PR7.1. 2. Termination/continuity check includes check at terminated equipment for: (a) correct polarity, (b) appropriate signal generation, transmission

and reception, and (c) correct shield & ground terminations.

OPERATOR INTERFACE CHECK-OUT

MONITORING POINTS OBSERVED PARAMETER TYPE TAG NO. TAG NO. TAG NO. TAG NO. TAG NO. TAG NO.

PROCESS VAR

EQUIP STATUS ZOI-107 ZCI-107

ALARM POINT

OPERATOR CONTROL FUNCTIONS CHECKED FUNCTION TYPE TAG NO. LOCATION TAG NO. LOCATION TAG NO. LOCATION

AS LEFT SETTINGS TAG NO. SWITCH & ALARM SP CONTROLLERS

Gain Reset, rpm Deriv. (rate), min PV Set Point

Describe all interlocks checked, equipment started/stopped, valves/operators stroked. Describe modes of operation checked, and location of operator interface (local/remote). Checked terminations and verified indications shown above. I certify that the control loop referenced on this page has been completely checked and functions in accordance with applicable drawings and specifications. Certified by: Joe Smith Date: 12/19/98 (Work Performed By)

Page 109: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Loop Check-out Sheet

Project Name: Owner’s Project No. (if applicable): Page of

Project Owner: Regulatory Agency Project No. (if applicable):

HDR Project No.: Date:

LEAK AND TERMINATION/CONTINUITY CHECKS FIELD CONTROL CAB

DESCRIPTION LEAK CHECK(1) TERM/CONT CHECK(2) TERM/CONT CHECK(2)

Device Tag No.

Process Conn.

Signal Tube

Device Tag No.

Termination Ident.

Device Tag No.

Termination Ident.

1. Leak check for pneumatic signal tubing to be per ISA-PR7.1. 2. Termination/continuity check includes check at terminated equipment for: (a) correct polarity, (b) appropriate signal generation, transmission

and reception, and (c) correct shield & ground terminations.

OPERATOR INTERFACE CHECK-OUT

MONITORING POINTS OBSERVED PARAMETER TYPE TAG NO. TAG NO. TAG NO. TAG NO. TAG NO. TAG NO.

PROCESS VAR

EQUIP STATUS

ALARM POINT

OPERATOR CONTROL FUNCTIONS CHECKED FUNCTION TYPE TAG NO. LOCATION TAG NO. LOCATION TAG NO. LOCATION

AS LEFT SETTINGS TAG NO. SWITCH & ALARM SP CONTROLLERS

Gain Reset, rpm Deriv. (rate), min PV Set Point

Describe all interlocks checked, equipment started/stopped, valves/operators stroked. Describe modes of operation checked, and location of operator interface (local/remote). I certify that the control loop referenced on this page has been completely checked and functions in accordance with applicable drawings and specifications. Certified by: Date: (Work Performed By)

Page 110: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Page 111: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Instrument Certification Sheet

Project Name: BIG PROJECT Owner’s Project No. (if applicable):

Project Owner: ABC Company Regulatory Agency Project No. (if applicable):

HDR Project No. 10050-211-134 Date: 12/19/98

Control Loop No.: 222

Instrument Tag No. TSH-222 Transmitter/gauge span:

Manufacturer: ACE, Inc. Switch set-point: 50 F

Model No. TL-2983-SH5 Switch dead band: 5 F

Serial No. 10293583 Switch range: 32-200 F

TRANSMITTERS AND INDICATORS INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT OUTPUT ERROR (% of span)

INPUT OUTPUT ERROR (% of span)

0%

25%

50%

75%

100%

Other (if applicable)

Other (if applicable)

SWITCHES INCREASING INPUT DECREASING INPUT ACTUATION POINT INPUT OUTPUT ERROR

(% of range) INPUT OUTPUT ERROR

(% of range)

High (Increasing input) 49.8 F Contact Close 0.1% 45.1 F Contact Open 0.2%

Low (Decreasing input)

Maximum allowable error (per Contract Documents): 1.0% Switch Range Remarks:

CALIBRATION EQUIPMENT UTILIZED DEVICE TYPE MFR/MODEL NO. ACCURACY NIST TRACEABILITY?

Temperature (dry block) calibrator

Hart Scientific XL5897T 0.1 F Yes

Certified by: Joe Smith Date Certified: 12/19/98

Page 112: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Instrument Certification Sheet

Project Name: BIG PROJECT Owner’s Project No. (if applicable):

Project Owner: ABC Company Regulatory Agency Project No. (if applicable):

HDR Project No. 10050-211-134 Date: 12/19/98

Control Loop No.: 106

Instrument Tag No. PIT-106A Transmitter/gauge span: 0-200 psi

Manufacturer: ACE, Inc. Switch set-point:

Model No. 1275-X Switch dead band:

Serial No. 3049569TSH Switch range:

TRANSMITTERS AND INDICATORS INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT OUTPUT ERROR (% of span)

INPUT OUTPUT ERROR (% of span)

0% 0.00 psi 4.02 mA 0.13 0.00 psi 4.00 mA 0.00

25% 50.00 psi 8.00 mA 0.00 50.00 psi 8.01 mA 0.06

50% 100.00 psi 12.01 mA 0.06 100.00 psi 12.00 mA 0.00

75% 150.00 psi 16.00 mA 0.00 150.00 psi 16.01 mA 0.06

100% 200.00 psi 20.00 mA 0.00 200.00 psi 19.99 mA 0.06

Other (if applicable)

Other (if applicable)

SWITCHES INCREASING INPUT DECREASING INPUT ACTUATION POINT INPUT OUTPUT ERROR

(% of range) INPUT OUTPUT ERROR

(% of range)

High (Increasing input)

Low (Decreasing input)

Maximum allowable error (per Contract Documents): 0.15% span Remarks: Adjusted zero-otherwise no adjustments required

CALIBRATION EQUIPMENT UTILIZED DEVICE TYPE MFR/MODEL NO. ACCURACY NIST TRACEABILITY?

Pressure calibrator

Hathaway/Beta XL5946P 0.025% full scale Yes

Pressure module

Hathaway/Beta XL5948P-6:0-150 psi

0.025% full scale Yes

Certified by: Joe Smith Date Certified: 12/19/98

Page 113: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Instrument Certification Sheet

Project Name: Owner’s Project No. (if applicable):

Project Owner: Regulatory Agency Project No. (if applicable):

HDR Project No. Date:

Control Loop No.:

Instrument Tag No. Transmitter/gauge span:

Manufacturer: Switch set-point:

Model No. Switch dead band:

Serial No. Switch range:

TRANSMITTERS AND INDICATORS INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT OUTPUT ERROR (% of span)

INPUT OUTPUT ERROR (% of span)

0%

25%

50%

75%

100%

Other (if applicable)

Other (if applicable)

SWITCHES INCREASING INPUT DECREASING INPUT ACTUATION POINT INPUT OUTPUT ERROR

(% of range) INPUT OUTPUT ERROR

(% of range)

High (Increasing input)

Low (Decreasing input)

Maximum allowable error (per Contract Documents): Remarks:

CALIBRATION EQUIPMENT UTILIZED DEVICE TYPE MFR/MODEL NO. ACCURACY NIST TRACEABILITY?

Certified by: Date Certified:

Page 114: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Page 115: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Final Control Element Certification Sheet

Project Name: BIG PROJECT Owner’s Project No. (if applicable):

Project Owner: ABC Company Regulatory Agency Project No. (if applicable):

HDR Project No. 10050-211-134 Date: 12/19/98

Control Loop No.: 056

Actuator: Pneumatic: X Electric:

Tag No. LCV-056A Positioner: Direct: X Reverse: ________

Description: Control Valve Positioner: Input: 9-15 psi Output: 0-100%

Manufacturer: ACE, Inc. I/P Converter: Input: 4-20 mA Output: 3-15 psi

Model No. XYZ-123 Valve to Open on air failure

Serial No. 748569AP2 Valve to Open on power failure

I/P CONVERTER INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT OUTPUT ERROR (% of span)

INPUT OUTPUT ERROR (% of span)

0% 4.00 mA 3.01 psi 0.08 4.00 mA 3.02 psi 0.17

25% 8.00 mA 6.04 psi 0.33 8.00 mA 6.05 psi 0.42

50% 12.00 mA 9.00 psi 0.00 12.00 mA 9.01 psi 0.08

75% 16.00 mA 11.97 psi 0.25 16.00 mA 12.03 psi 0.25

100% 20.00 mA 14.99 psi 0.08 20.00 mA 14.99 psi 0.08

Specified I/P converter accuracy: 0.50% % of span.

FINAL CONTROL ELEMENT INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT TRAVEL ERROR (% of full travel)

INPUT TRAVEL ERROR (% of full travel)

0% 9.00 psi 0% - 9.00 psi 0% -

25% 10.50 psi 25% - 10.50 psi 25% -

50% 12.00 psi 50% - 12.00 psi 50% -

75% 13.50 psi 75% - 13.50 psi 75% -

100% 15.00 psi 100% - 15.00 psi 100% - Remarks: LCV-056A is not furnished with position transmitter, so travel checks were visual.

CALIBRATION EQUIPMENT UTILIZED DEVICE TYPE MFR/MODEL NO. ACCURACY NIST TRACEABILITY?

Multi-fct calibrator

Fluke-XL743B 0.01% Rdg + 0.015% FS Yes

Pressure Module

Fluke-XL700POS (0-30”) 0.05% FS Yes

Certified by: Joe Smith Date Certified: 12/19/98

Page 116: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Page 117: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Final Control Element Certification Sheet

Project Name: Owner’s Project No. (if applicable):

Project Owner: Regulatory Agency Project No. (if applicable):

HDR Project No. Date:

Control Loop No.:

Actuator: Pneumatic: Electric:

Tag No. Positioner: Direct: Reverse:

Description: Positioner: Input: Output:

Manufacturer: I/P Converter: Input: Output:

Model No. Valve to on air failure

Serial No. Valve to on power failure

I/P CONVERTER INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT OUTPUT ERROR (% of span)

INPUT OUTPUT ERROR (% of span)

0%

25%

50%

75%

100%

Specified I/P converter accuracy: % of span.

FINAL CONTROL ELEMENT INCREASING INPUT DECREASING INPUT

% OF SPAN INPUT TRAVEL ERROR (% of full travel)

INPUT TRAVEL ERROR (% of full travel)

0%

25%

50%

75%

100% Remarks:

CALIBRATION EQUIPMENT UTILIZED DEVICE TYPE MFR/MODEL NO. ACCURACY NIST TRACEABILITY?

Certified by: Date Certified:

Page 118: City of Yankton, SD

(Version 2.0, May 2014) Copyright 2014 HDR Inc.

Page 119: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL LOOP DESCRIPTIONS 13441 - 1

2014/08/28 1

SECTION 13441 2

CONTROL LOOP DESCRIPTIONS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Instrumentation control loops. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 13440 - Instrumentation for Process Control: Basic Requirements. 10

1.2 QUALITY ASSURANCE 11

A. See Specification Section 13440. 12

1.3 SYSTEM DESCRIPTION 13

A. General Requirements: 14 1. In addition to the requirements specifically stated within the control loop descriptions, all 15

control software and hardware shall be provided as required to ensure the safe and reliable 16 operation of all controlled equipment. 17

2. A "transmitter trouble" alarm shall be generated upon the loss of each transmitter signal, or 18 if the signal is "out-of-range" (outside the 4 to 20 mA signal). 19

3. A "fail-safe" design shall be incorporated into the design such that the loss of any signal or 20 loss of power shall not endanger personnel or result in equipment damage. 21

4. All "soft" alarms on analog signal shall reside in the PLC logic with de-bounce timers. The 22 soft setpoint shall be able to be modified through the OIT/HMI system with appropriate 23 security. 24

5. All alarm and trip time delays shall be operator adjustable from the OIT/HMI system with 25 appropriate security. 26

6. All process values, ranges, and setpoints described herein shall be considered "Initial 27 values" and may be changed during installation and start-up. 28

7. Flow signal inputs are to be totalized for each calendar day. The HMI system shall display 29 a value for "today's total flow" (FQI-xxxx), and "yesterday's total flow" (FQIY-xxxx). Each 30 day's total is to be stored in the HMI system for eventual printout on a monthly basis. 31

8. All PID loops shall be programmed for "bumpless transfer" between the auto and manual 32 modes from the HMI system. 33

B. The control loop descriptions provide the functional requirements of the control loops 34 represented in the Contract Documents. 35 1. Descriptions are provided as follows: 36

a. Control system overview and general description. 37 b. Major equipment to be controlled. 38 c. Major field mounted instruments (does not include local gages). 39 d. Manual control functions. 40 e. Automatic control functions/interlocks. 41 f. Remote indications and alarms. 42

C. The Control Loop Descriptions are not intended to be an inclusive listing of all elements and 43 appurtenances required to execute loop functions, but are rather intended to supplement and 44 complement the Drawings and other Specification Sections. 45 1. The control loop descriptions shall not be considered equal to a bill of materials. 46

Page 120: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL LOOP DESCRIPTIONS 13441 - 2

D. Provide instrumentation hardware and software as necessary to perform control functions 1 specified herein and shown on Drawings. 2

1.4 SUBMITTALS 3

A. See Specification Section 01340 for requirements for the mechanics and administration of the 4 submittal process. 5

B. See Specification Section 13440. 6

C. Operation and Maintenance Manuals: 7 1. See Specification Section 01342 for requirements for: 8

a. The mechanics and administration of the submittal process. 9 b. The content of Operation and Maintenance Manuals. 10

D. Control Strategy for Record Documents: 11 1. Obtain this Specification Section 13441 in electronic format (Microsoft Word) from 12

Engineer at beginning of Project. 13 2. Revise and update the file monthly during construction and start-up to reflect all changes 14

that occur due to specific equipment and systems supplied on the Project. 15 a. Show all revisions in 'track change' mode. 16 b. Change Specification Section Title to read "Control Loop Descriptions - Contractor 17

Record Document." 18 c. Reference all changes by Request for Information (RFI) number or Change Proposal 19

Request (CPR) number. 20 d. Submit revised file monthly to Engineer for review. 21

3. Deliver the revised and updated file as a final control loop description Record Document in 22 the Operation and Maintenance Manual described in Specification Section 01342. 23

4. Provide both paper copy and electronic copy (on CD-ROM) of the Record Document 24 control loop descriptions in the Operation and Maintenance Manual described in 25 Specification Section 01342. 26

PART 2 - PRODUCTS - (NOT APPLICABLE TO THIS SPECIFICATION SECTION) 27

PART 3 - EXECUTION 28

3.1 CONTROL LOOPS 29

A. Control Loop 01: Collector Well Pump CWP-01. 30 1. Major Equipment: 31

a. PLC and local OIT. 32 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 33

Plant No. 2). 34 c. Collector Well Pump CWP-01 and associated VFD. 35

2. Major Field Instruments: 36 a. Pump discharge pressure switch: PSH-01. 37 b. Pump discharge magnetic flow meter: FE/FIT-01. 38

3. Control Logic: 39 a. Control of Collector Well Pump CWP-01 is in accordance with selections made at the 40

VFD. 41 1) When LOCAL mode is selected at the VFD, the operator can manually start/stop 42

the pump and control pump speed from the VFD. 43

Page 121: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL LOOP DESCRIPTIONS 13441 - 3

2) When REMOTE mode is selected at the VFD, the pump is controlled by Operator 1 selections made from the local OIT or any remote HMI via START-STOP selector 2 switch function HS-01. 3 a) Pump speed is controlled by PLC flow controller function FIC-01. 4

(1) When placed in the MANUAL mode at the OIT or HMI, FIC-01 5 commands the pump to operate at whatever speed is input by the Operator 6 at the OIT/HMI via speed controller faceplate SIC-01. 7

(2) In AUTO mode, FIC-01 modulates the pump speed to maintain a set flow 8 rate. Flow feedback is provided to FIC-01 by magnetic flowmeter 9 FE/FIT-01. 10

b. See Control Diagram in Drawings for details of the hardwired interlocks between 11 operation of the pump and the pump discharge control valve. Interlocks are in place 12 regardless of whether the pump is in the LOCAL or REMOTE control mode as selected 13 at the VFD. Interlocks are as follows: 14 1) Pump is commanded to start against a closed discharge control valve. 15 2) The pump start command energizes the control valve’s solenoid valve and the valve begins 16

to open, gradually increasing line pressure to full pumping head. 17 3) When the pump is signaled to shut-off, the solenoid valve is de- energized and the 18

valve begins to close slowly, gradually reducing flow while the pump continues to 19 run. 20

4) When the discharge valve is fully closed as detected by a limit switch assembly, the 21 pump is stopped. 22

5) The pump will trip via hardwired interlock in the event any of the following 23 conditions occur: 24 a) Pump motor winding temperature is high-high. 25 b) Pump discharge pressure rises above a set point for a set period of time. 26 c) Discharge valve fails to open after a set period of time following pump start. 27

c. Pump bearing lubrication control: 28 1) When a pump is requested to start, hardwired relay logic utilizes a time delay to 29

allow water time to lubricate the pump bearings prior to pump start. When the time 30 delay relay actuates it energizes the water solenoid to admit lubricating water to the 31 pump bearings. See Control Diagram for details. 32

4. Indications at OIT/SCADA HMI: 33 a. CWP-01 flow rate: FI-01. 34 b. CWP-01 total flow rate since last reset: FQI-01. 35 c. Pump pre-lube time: KI-07. 36

1) Indication provided at OIT/HMI prior to pump start that pump pre-lube is taking 37 place. This indication remains until the pre-lube timer expires. Pre-lube timer is 38 adjustable by the Operator. 39

d. CWP-01 discharge header pressure high alarm: PAH-01. 40 e. CWP-01 in REMOTE control mode: ZI-01. 41 f. CWP-01 fail alarm: XA-01A (pump fails to run within 5 seconds of PLC run 42

command). 43 g. VFD fault alarm: XA-01B. 44 h. CWP-01 run status: YI-01. 45 i. CWP-01 total running time (since last reset): KQI-01. 46 j. CWP-01 speed: SI-01. 47 k. Discharge valve closed indication: ZCI-01. 48 l. CWP-01 motor temperature high-high alarm: TAHH-01. 49

B. Control Loop 02: Collector Well Pump CWP-02. 50 1. Description for Control Loop 01 is typical for description for Control Loop 02. 51

C. Control Loop 03: Collector Well Pump CWP-03. 52 1. Description for Control Loop 01 is typical for description for Control Loop 02. 53

D. Control Loop 04: Future Collector Well Pump CWP-04. 54

Page 122: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL LOOP DESCRIPTIONS 13441 - 4

E. Control Loop 05: Collector Well Pump Discharge Header Pressure. 1 1. Major Equipment: 2

a. PLC and local OIT. 3 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 4

Plant No. 2). 5 2. Major Field Instruments: 6

a. Pump discharge pressure transmitter: PIT-05. 7 3. Control Logic: 8

a. None; pressure transmitter is utilized for indication only. 9 4. Indications at OIT/SCADA HMI: 10

a. Collector well pump header pressure indication: PI-05. 11

F. Control Loop 06: Collector Well Level. 12 1. Major Equipment: 13

a. PLC and local OIT. 14 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 15

Plant No. 2). 16 2. Major Field Instruments: 17

a. Collector well level transmitter: LT-06. 18 3. Control Logic: 19

a. None; level transmitter is utilized for indication and alarm purposes only. 20 4. Indications at OIT/SCADA HMI: 21

a. Collector well level indication: LI-06. 22 b. Collector well high level alarm: LAH-06. 23

G. Control Loop 07 – PLC Control Panel UPS Alarms. 24 1. Major Equipment: 25

a. PLC and local OIT. 26 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and Plant No. 27

2). 28 2. Control Logic: None. 29 3. Indications at OIT/SCADA HMI: 30

a. UPS trouble alarm: XA-07A. 31 b. UPS on battery power: XA-07B. 32

H. Control Loop 08 – Switchgear MSB-01 Surge Protection Device Monitoring. 33 1. Major Equipment: 34

a. Switchgear MSB-01. 35 b. PLC and local OIT. 36 c. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 37

Plant No. 2). 38 2. Control Logic: 39

a. SCADA System provides monitoring capabilities only for the switchgear. 40 3. Indications at OIT/SCADA HMI: 41

a. Switchgear MSB-01 surge protection device trouble alarm: XA-08. 42

I. Control Loop 09 – Collector Well Smoke Detection Alarm Monitoring. 43 1. Major Equipment: 44

a. PLC and local OIT. 45 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 46

Plant No. 2). 47 2. Major Field Instrumentation: 48

a. Collector Well Smoke detector. 49 3. Control Logic: 50

a. SCADA System provides monitoring capabilities only for the smoke detector. 51 4. Indications at OIT/SCADA HMI: 52

a. Collector Well smoke detected alarm: XA-09. 53

Page 123: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL LOOP DESCRIPTIONS 13441 - 5

J. Control Loop 10 - Generator Monitoring. 1 1. Major Equipment: 2

a. Vendor-furnished Generator Control Panel. 3 b. PLC, Remote I/O Panel and local OIT. 4 c. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 5

Plant No. 2). 6 2. Control Logic: 7

a. All generator control logic resides in control panel(s) furnished by the Generator 8 supplier. SCADA System provides monitoring capabilities only for the generator. 9

3. Indications at OIT/SCADA HMI: 10 a. Generator run status: YI-10. 11 b. Generator trouble alarm: XA-10A. 12 c. Generator fail alarm: XA-10B. 13 d. Generator fuel low level: LAL-10. 14 e. Generator not in AUTO control mode: ZA-10. 15

K. Control Loop 11 – Switchgear PDP01 Monitoring. 16 1. Major Equipment: 17

a. Switchgear PDP01. 18 b. PLC, Remote I/O Panel and local OIT. 19 c. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 20

Plant No. 2). 21 2. Control Logic: 22

a. SCADA System provides monitoring capabilities only for the switchgear. 23 3. Indications at OIT/SCADA HMI: 24

a. Switchgear PDP01 surge protection device alarm: XA-11. 25 b. Collector Well on Utility Power (Main Utility Breaker closed): ZI-11A. 26 c. Collector Well on Generator Power (Generator Breaker closed): ZI-11B. 27

L. Control Loop 12 – Remote I/O Panel UPS Alarms. 28 1. Major Equipment: 29

a. PLC, Remote I/O Panel and local OIT. 30 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 31

Plant No. 2). 32 2. Control Logic: None. 33 3. Indications at OIT/SCADA HMI: 34

a. UPS trouble alarm: XA-12A. 35 b. UPS on battery power: XA-12B. 36

M. Control Loops 50 - 53 – Intrusion Alarms. 37 1. Major Equipment: 38

a. PLC and local OIT. 39 b. SCADA HMIs (PC based HMIs in existing Water Treatment Plant No. 1 and 40

Plant No. 2). 41 2. Major Field Instruments: 42

a. Door intrusion switch: ZS-50. 43 b. North roof hatch intrusion switch: ZS-51. 44 c. South roof hatch intrusion switch: ZS-52. 45 d. Valve level hatch intrusion switch: ZS-53. 46

3. Control Logic: 47 a. An alarm is generated at the OIT and the SCADA HMIs immediately whenever any of 48

the following hatches are open: 49 1) North roof hatch. 50 2) South roof hatch. 51 3) Valve level hatch. 52

Page 124: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL LOOP DESCRIPTIONS 13441 - 6

b. ACTIVE – BYPASS selector switch HS-50 with key lock is utilized to bypass the door 1 intrusion alarm. An intrusion alarm is generated at the OIT/HMIs after a time delay 2 (adjustable from 0 to 60 seconds) following the opening of the door. No intrusion alarm 3 is generated when HS-50 is in the BYPASS position. Control logic associated with the 4 BYPASS mode and the time delay associated with the ACTIVE mode resides within 5 the PLC. 6

4. Indications at OIT/SCADA HMI: 7 a. Door intrusion alarm: ZA-50. 8 b. North hatch intrusion alarm: ZA-51. 9 c. South hatch intrusion alarm: ZA-52. 10 d. Valve level hatch intrusion alarm: ZA-53. 11

END OF SECTION 12

Page 125: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 1

2014/08/28 1

SECTION 13442 2

PRIMARY METERS AND TRANSMITTERS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Flow components. 7 2. Pressure components. 8 3. Level components. 9 4. Door and hatch intrusion switches. 10 5. Pipe, tubing and fittings. 11 6. Instrument valves. 12

B. Related Specification Sections include but are not necessarily limited to: 13 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 14 2. Division 01 - General Requirements. 15 3. Section 13440 - Instrumentation for Process Control: Basic Requirements. 16 4. Section 13441 - Control Loop Descriptions. 17

1.2 QUALITY ASSURANCE 18

A. Referenced Standards: 19 1. American Society of Mechanical Engineers (ASME): 20

a. B16.5, Pipe Flanges and Flanged Fittings. 21 b. B31.1, Power Piping. 22 c. Section II, Part A SA-182, Forged or Rolled Alloy Steel Pipe Flanges, Forged Fittings, 23

and Valves and Parts for High-Temperature Service. 24 d. Section II, Part A SA-479, Stainless Steel Bars and Shapes for Use in Boilers and Other 25

Pressure Vessels. 26 2. ASTM International (ASTM): 27

a. A106, Standard Specification for Seamless Carbon Steel Pipe for High-Temperature 28 Service. 29

b. A234, Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy 30 Steel for Moderate and High Temperature Service. 31

c. A269, Standard Specification for Seamless and Welded Austenitic Stainless Steel 32 Tubing for General Service. 33

d. A276, Standard Specification for Stainless Steel Bars and Shapes. 34 e. A479, Standard Specification for Stainless Steel Bars and Shapes for Use in Boilers and 35

Other Pressure Vessels. 36

1.3 SYSTEM DESCRIPTION 37

A. The instruments specified in this Specification Section are the primary element components for 38 the control loops shown on the "Y" series Drawings and specified in Specification Section 39 13441. 40 1. These instruments are integrated with other control system components specified under 41

Specification Section 13440 series to produce the functional control defined in the Contract 42 Documents. 43

Page 126: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 2

1.4 SUBMITTALS 1

A. Shop Drawings: 2 1. See Specification Section 01340 for requirements for the mechanics and administration of 3

the submittal process. 4 2. See Specification Section 13440. 5

B. Operation and Maintenance Manuals: 6 1. See Specification Section 01342 for requirements for: 7

a. The mechanics and administration of the submittal process. 8 b. The content of Operation and Maintenance Manuals. 9

PART 2 - PRODUCTS 10

2.1 ACCEPTABLE MANUFACTURERS 11

A. Subject to compliance with the Contract Documents, the manufacturers listed in the Articles 12 describing the elements are acceptable. 13

B. Submit request for substitution in accordance with Specification Section 01640. 14

2.2 FLOW COMPONENTS 15

A. Magnetic Flow Meters: 16 1. Acceptable manufacturers: 17

a. ABB. 18 b. Johnson Yokogawa. 19 c. Rosemount. 20 d. Krohne. 21 e. Endress + Hauser. 22 f. Seimens. 23

2. Design and fabrication: 24 a. Utilize characterized field principle of electromagnetic induction to produce signal 25

directly proportional to flow rate. 26 b. High input impedance pre-amplifiers. 27

1) Minimum impedance: 1010 ohms. 28 c. Provide flanged end connections per ASME B16.5 rated for piping system operating 29

and test conditions. 30 d. Grounding requirements: 31

1) Nonmetallic or lined pipe: 32 a) Inlet and outlet grounding rings of same material as electrode. 33

2) Conductive piping: 34 a) Conductive path between the meter and the piping flanges. 35

e. Provide cable between magnetic flow meter and transmitter. 36 f. Pulsed DC magnetic field excitation. 37 g. Automatic zero. 38 h. Adjustable low flow cutoff. 39 i. Minimum signal lock (empty tube zero) to prevent false measurement when tube is 40

empty. 41 j. Inaccuracy: 42

1) Above 10 percent of range: +/-1.0 percent of rate. 43 2) Below 10 percent of range: +/-0.1 percent of range setting. 44 3) Add +0.1 percent of range to above inaccuracies for analog outputs. 45

k. 4-20 mA DC isolated output into maximum 800 ohms. 46 l. Power supply: 117 V +/-10 percent, 60 Hz. 47 m. Indication of flow rate and totalized flow at transmitter. 48 n. Meter operable as specified in liquids with 5.0 micro mho/cm or more conductivity. 49

Page 127: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 3

o. Transmitter electronics shall use microprocessor based architecture and be configured 1 using parameters. 2

3. Schedule: 3 4

TAG NUMBER SERVICE

FLOW RANGE (GPM)

METER SIZE (IN)

FE/FIT-01 CWP-01 discharge 0-5,000 16 FE/FIT-02 CWP-02 discharge 0-5,000 16 FE/FIT-03 CWP-03 discharge 0-5,000 16

5

TAG NUMBER LINER MATERIAL

ELECTRODE MATERIAL

INTEGRAL, FIELD OR PANEL-MOUNTED TRANSMITTER

FE/FIT-01 Rubber 316 SS Integral FE/FIT-02 Rubber 316 SS Integral FE/FIT-03 Rubber 316 SS Integral

6

2.3 PRESSURE COMPONENTS 7

A. Pressure Transmitters: 8 1. Acceptable manufacturers: 9

a. Rosemount, Model 2051. 10 b. Foxboro, I/A series. 11 c. Honeywell SmartLine ST 700 series. 12

2. Materials: 13 a. Isolating diaphragm: 316 stainless steel. 14 b. Process flanges and adapters: 316 stainless steel. 15 c. Housing: Aluminum. 16 d. Vent/drain valve: 316 stainless steel. 17 e. Fill fluid: 18

1) Utilize manufacturer's standard fill for other applications. 19 a) Ensure fill is suitable for application temperatures. 20

3. Design and fabrication: 21 a. Smart transmitters utilizing microprocessor based electronics. 22 b. Output: 4-20 mA DC proportional to pressure. 23 c. Nonvolatile EEPROM memory. 24 d. Power supply: 24 Vdc. 25 e. Adjustable zero and span. 26 f. Temperature limits: -20 to 180 DegF. 27

1) -4 to 175 DegF for LCD indicators. 28 g. Overpressure limits: Withstand 150 percent of stated maximum service pressure 29

without damage. 30 h. Humidity limits: 0 to 100 percent relative humidity. 31 i. Damping: Adjustable between 0 and 32 seconds. 32 j. Inaccuracy (includes effects of linearity, repeatability and hysteresis): +/-0.10 percent 33

of calibrated span for 15:1 rangeability. 34 k. Stability: +/-0.2 percent of upper range limit for 12 months. 35 l. Temperature effect: 36

1) Total effect including span and zero errors: +/-0.2 percent of upper range limit per 37 100 DegF for minimum 15:1 rangeability. 38

m. Minimum 1/2 IN pressure connection. 39 n. Equip with test jacks or accessible terminals for testing output. 40 o. Equip with isolation valve and test connections with isolation valves and/or plugs. 41

Page 128: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 4

4. Schedule: 1 2

TAG NUMBER SERVICE SPAN PIT-05 Collector Well pump discharge 0-100 PSI

3

B. Pressure Switches: 4 1. Acceptable manufacturers: 5

a. Mercoid. 6 b. Automatic Switch Company. 7 c. United Electric. 8

2. Materials: 9 a. Wetted switch elements: 316 stainless steel. 10

3. Accessories: 11 a. Provide ball valve to isolate pressure switch from source. 12

4. Design and fabrication: 13 a. Utilize hermetically sealed contact switches. 14 b. SPDT contacts rated: 15

1) 1 amp inductive at 125 Vdc. 16 2) 5 amp inductive at 120 Vac. 17

c. Switch set points: 18 1) Set points between 30 and 70 percent of switch rated working range. 19 2) Operating pressure not to exceed 75 percent of switch rated working range. 20

d. Accuracy: Better than 1 percent of full scale. 21 e. Process connection: Minimum of 1/4 IN. 22

5. Schedule: 23 24

TAG NUMBER SERVICE HIGH SETTING PSH-01 CWP-01 discharge TBD PSH-02 CWP-02 discharge TBD PSH-03 CWP-03 discharge TBD

25

C. Pressure Gage: 26 1. Acceptable manufacturers: 27

a. Ashcroft. 28 b. Ametek. 29

2. Materials: 30 a. Bourdon tube, socket, connecting tube: 316 stainless steel. 31 b. Case: Phenolic. 32

3. Accessories: 33 a. Provide valve at point of connection to equipment and at panel if panel mounted. 34

4. Design and fabrication: 35 a. Provide viewer protection from element rupture. 36 b. Calibrate gages at jobsite for pressure and temperature in accordance with 37

manufacturer's instructions. 38 c. Unless otherwise required by codes, provide stem mounted or flush mounted, as 39

required, with dial diameter as follows: 40 41

PIPE SIZE DIAL SIZE GAGE CONNECTION 1-1/2 IN or less 2-1/2 IN 1/4 IN Larger than 1-1/2 IN 4-1/2 IN 1/2 IN

42 d. Equip with white faces, black numerals and black pointers. 43

Page 129: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 5

e. Gage tapping position to be clear of equipment functions and movements, and protected 1 from maintenance and operation of equipment. 2 1) Gage to be readable from an accessible standing position. 3

f. Gage accuracy: 1 percent of full range. 4 g. Select gage range so that: 5

1) The normal operating value is in the middle third of the dial. 6 2) Maximum operating pressure does not exceed 75 percent of the full scale range. 7

D. Schedule: 8 9

TAG NUMBER APPLICATION

PRESSURE RANGE (PSI)

DIAL SIZE (IN) LIQUID FILLED

PI-01 CWP-01 0-160 4 1/2 Yes PI-02 CWP-02 0-160 4 1/2 Yes PI-03 CWP-03 0-160 4 1/2 Yes PI-05 Collector Well

Pump Discharge 0-160 4 1/2 No

10

2.4 LEVEL ELEMENTS 11

A. Submersible Type Level Transmitters: 12 1. Acceptable Manufacturers: 13

a. Siemens SITRANS P, MPS series. 14 b. Endress + Hauser Waterpilot FMX 21. 15

2. Materials: 16 a. Sensor wetted materials: 316 stainless steel, Viton, Teflon, or equivalent. 17 b. Cable insulation/jacket: Polyethylene, polyurethane, or equivalent. 18 c. Terminal box: As required to meet area classifications shown on drawings. 19 d. Cable/sensor installation devices: Polyethylene, Teflon, 316 stainless steel. 20

3. Design and fabrication: 21 a. Two-wire, 24 Vdc loop-powered. 22 b. Supply voltage: 24 Vdc. 23 c. Output signal: 4-20 mA. 24 d. Barometric pressure tube with Teflon filter or desiccant located in dry junction box or 25

control panel. 26 e. Operating temperature: 14 to 158 DegF. 27 f. Ambient temperature: -14 to 158 DdegF. 28 g. Over range protection: Up to twice specified span. 29 h. Strain relief cable clamp for suspending cable. 30 i. Maximum measured error: ±0.5 percent of upper range value. 31 j. Stability: ±0.25 percent of upper range value per year. 32 k. Integral transient overvoltage protection. 33

4. Schedule: 34 35

TAG NUMBER SERVICE SPAN, FT

LT-06 Collector Well 0-TBD

2.5 DOOR AND HATCH INTRUSION SWITCHES 36

A. Acceptable Manufacturer: 37 1. GO SWITCH. 38

B. Design and Operation: 39 1. Hermetically sealed, leverless operation switch. 40 2. Side sensitive. 41 3. Potted cable connections. 42

Page 130: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 6

4. Suitable for outdoor use. 1 5. Door sensors are side sensitive, style 11 looking at a magnetic metal target or range 2

extending magnet assembly attached to the door. 3 6. Schedule: 4 5

TAG NUMBER SERVICE

CONTACT NO/NC

ZS-50 ZS-51 ZS-52 ZS-53

Door open switch North hatch open switch South hatch open switch Valve Level hatch open switch

NO NO NO NO

6

2.6 PIPE, TUBING, AND FITTINGS 7

A. Acceptable Manufacturers: 8 1. Tube fittings: 9

a. Parker CPI. 10 b. Swagelok. 11

B. Instrument Tubing and Fittings: 12 1. Material: 13

a. Tubing: ASTM A269, Grade TP 316 stainless steel. 14 b. Straight fittings: 316 stainless steel per ASME SA-479 or ASTM A276. 15 c. Shaped bodies: ASME SA-182 F316 stainless steel. 16

2. Design and fabrication: 17 a. Tubing: 18

1) Seamless. 19 2) Fully annealed. 20 3) Maximum hardness: 80 Rb. 21 4) Free from surface scratches and imperfections. 22 5) Diameter: 1/2 IN OD unless specified otherwise. 23 6) Wall thickness: 24

a) Meet requirements of ASME B31.1, Paragraph 122.3. 25 b) Minimum 0.049 IN for 1/2 IN OD tubing. 26

b. Fittings: 27 1) Flareless. 28 2) Compression type. 29

C. Instrument Piping: 30 1. For applications where the instrument is supported solely by the sensing line, ( e.g., pressure 31

gauge directly mounted to process line), utilize piping as specified below. 32 a. Diameter: 1/2 IN unless specified otherwise. 33 b. Schedule 80. 34 c. ASTM A106 Grade B carbon steel with steel fittings per ASTM A234. 35

2.7 INSTRUMENT VALVES 36

A. Process instrument multi-valve manifolds, isolation, vent and blow-down valves: 37 1. Acceptable manufacturers: 38

a. Whitey Co. 39 b. Anderson-Greenwood USA, Inc. 40

2. Materials: 41 a. Packing: Graphite or Teflon. 42 b. Body: 316 stainless steel per ASTM A479. 43 c. Stem: 316 stainless steel per ASTM A276. 44 d. Ball: 316 stainless steel per ASTM A276. 45 e. Support rings: 316 stainless steel per ASTM A276. 46

Page 131: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 7

f. Seats: 1 1) Metal: 2

a) 316 stainless steel per ASTM A276. 3 2) Soft: 4

a) Teflon, Delrin. 5 b) Only utilized on applications where manufacturer's temperature and pressure 6

ratings exceed process design conditions. 7 3. Design and fabrication: 8

a. Either of the following: 9 1) Ball valve with 1/4 turn activation. 10 2) Free-swiveling ball stem. 11

b. Provide body wall thickness sufficient for process design conditions per ASME B31.1. 12 c. Temperature: Manufacturer's temperature rating for all components shall exceed 13

process design conditions. 14

2.8 ACCESSORIES 15

A. Furnish all mounting brackets, hardware and appurtenances required for mounting primary 16 elements and transmitters. 17 1. Materials, unless otherwise specified, shall be as follows: 18

a. Bolts, nuts, washers, expansion anchors: 316 stainless steel. 19 b. Mounting brackets, plates, angles: 316 stainless steel. 20 c. Instrument pipe stands: 21

1) Hot-dip galvanized 2 IN schedule 40, ASTM A106, Grade B carbon steel. 22

B. Tubing Support Angles and Brackets: 23 1. Any of the following materials are acceptable: 24

a. Aluminum support with dielectric material between support and tubing. 25 b. Type 316 stainless steel. 26 c. Fiberglass. 27

C. Cable lengths between sensors and transmitters shall be continuous (without splices) and as 28 required to accommodate locations as shown on Drawings. 29

PART 3 - EXECUTION 30

3.1 INSTALLATION 31

A. Install products in accordance with manufacturer's instructions. 32

B. Install instrument mounting pipe stands level and plumb. 33

C. Instrument Valves: 34 1. Orient stems for proper operation. 35 2. Install arrays orderly and neat in appearance with true horizontal and vertical lines. 36 3. Provide a minimum of 2 IN clearance between valve handle turning radii where there are 37

multiple valve handles appearing in a straight line. 38 4. Valves shall have bonnets and any soft seals removed during welding or soldering into the 39

line. 40 a. When cool, reassemble the valves. 41

5. Support each valve individually. 42 a. The tubing system does not qualify as support for the valve. 43

D. Locate instrument piping and tubing so as to be free of vibration and interference with other 44 piping, conduit, or equipment. 45

E. Keep foreign matter out of the system. 46

F. Remove all oil on piping and tubing with solvent before piping and tubing installation. 47

Page 132: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 8

G. Plug all open ends and connections to keep out contaminants. 1

H. Tubing Installation: 2 1. General: 3

a. Install such that tube shows no sign of crumpling, bends of too short a radius, or 4 flattening, etc. 5

b. Make tube runs straight and parallel or perpendicular to the floor, equipment and piping 6 runs. 7

c. For liquid and steam applications, slope continuously from the process to the 8 instrument with a minimum slope of 0.50 IN per foot. 9

d. For gas and air applications, slope continuously from the instrument to the process with 10 a minimum slope of 0.50 IN per foot. 11

e. If the sensing line cannot be continuously sloped, install high point vents and low point 12 drains. 13

f. Keep instrument tubing clean during all phases of work. 14 g. Blow out with clean, dry, oil-free air immediately before final assembly. 15 h. Cut by sawing only and debur. 16

2. Bending: 17 a. Make each bend with tube bender of the correct size for the tube. 18 b. Make all bends smooth and continuous. 19 c. Rebending is not permitted. 20 d. Make bends true to angle and radius. 21 e. Maintain a true circular cross section of tubing without buckling or undue stretch of 22

tube wall. 23 f. Allowable tolerance for flattening out of tubing bends: Maximum of 8 percent of the 24

OD for stainless steel tubing. 25 g. Minimum bending radius for stainless steel tubing: 26

27

TUBE OD, INCHES MINIMUM BENDING

RADIUS, INCHES 1/4 9/16 3/8 15/16 1/2 1-1/2

28 3. Tubing support: 29

a. Intermittently support by clamping to support angle. 30 b. Install supports to be self-draining, supported by hangers, or cantilevered from walls or 31

structural beams. 32 c. Support at 5 FT-0 IN maximum spans for horizontal or vertical runs. 33 d. Align tubing in orderly rows and retain in the tray by bolted clips. 34

1) The use of spring or speed clips is not acceptable. 35 e. Maintain order of the tubing throughout the length of the tray. 36 f. Locate angle, channel and tray installation to protect tubing from spills and mechanical 37

damage. 38 g. Locate support members to clear all piping, conduit, equipment, hatchways, monorails, 39

and personnel access ways and allow access for equipment operation and maintenance. 40 h. Permanently attach supports to building steel or other permanent structural members. 41 i. Arrange supports and trays so that they do not become a trough or trap. 42

4. Routing and orientation: 43 a. Route to maintain a minimum headroom clearance of 8 FT. 44 b. Locate and orient valves and specialties so that they are accessible for operation and 45

maintenance from the operating floor. 46 1) Do not route through or over equipment removal areas, below monorails or cranes 47

nor above or below hatches. 48

Page 133: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 9

I. Threaded Connection Seals: 1 1. Use Tite-Seal or acceptable alternate. 2 2. Use of lead base pipe dope or Teflon tape is not acceptable. 3 3. Do not apply Tite-Seal to tubing threads of compression fittings. 4

J. Instrument Mounting: 5 1. Mount all instruments where they will be accessible from fixed ladders, platforms, or grade. 6 2. Mount all local indicating instruments with face forward toward the normal operating area, 7

within reading distance, and in the line of sight. 8 3. Mount instruments level, plumb, and support rigidly. 9 4. Mount to provide: 10

a. Protection from heat, shock, and vibrations. 11 b. Accessibility for maintenance. 12 c. Freedom from interference with piping, conduit and equipment. 13

3.2 TRAINING 14

A. Provide on-site training in accordance with Specification Section 01650. 15

END OF SECTION 16

17

Page 134: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PRIMARY METERS AND TRANSMITTERS 13442 - 10

1

Page 135: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL AUXILIARIES 13446 - 1

2014/08/14 1

SECTION 13446 2

CONTROL AUXILIARIES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Relays/timers: 7

a. Control relay. 8 b. Time delay relays. 9

2. Termination equipment: 10 a. Terminal blocks. 11 b. Fuse holders. 12

3. Power supplies: 13 a. DC power supplies. 14 b. Isolation transformers. 15 c. Uninterruptible power supplies. 16

B. Related Specification Sections include but are not necessarily limited to: 17 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 18 2. Division 01 - General Requirements. 19 3. Section 13440 - Instrumentation for Process Control: Basic Requirements. 20

1.2 QUALITY ASSURANCE 21

A. Referenced Standards: 22 1. National Electrical Manufacturers Association (NEMA): 23

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 24 b. ICS 2, Industrial Control and Systems: Controllers, Contactors, and Overload Relays 25

Rated 600 Volts. 26 2. Underwriters Laboratories, Inc. (UL). 27

B. Miscellaneous: 28 1. Assure units comply with electrical area classifications and NEMA enclosure type shown on 29

Drawings. 30

1.3 SUBMITTALS 31

A. Shop Drawings: 32 1. See Specification Section 01340 for requirements for the mechanics and administration of 33

the submittal process. 34 2. See Specification Section 13440. 35

B. Operation and Maintenance Manuals: 36 1. See Specification Section 01342 for requirements for: 37

a. The mechanics and administration of the submittal process. 38 b. The content of Operation and Maintenance Manuals. 39

PART 2 - PRODUCTS 40

2.1 ACCEPTABLE MANUFACTURERS 41

A. Subject to compliance with the Contract Documents, the manufacturers listed in the applicable 42 Articles below are acceptable. 43

Page 136: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL AUXILIARIES 13446 - 2

B. Provide similar components from the same manufacturer for uniformity of appearance, 1 operations, and maintenance. 2

C. Submit request for substitution in accordance with Specification Section 01640. 3

2.2 RELAYS/TIMERS 4

A. Control Relays: 5 1. Acceptable manufacturers: 6

a. Idec. 7 b. Potter & Brumsfield. 8 c. Allen-Bradley. 9

2. Design and fabrication: 10 a. Plug-in general purpose relay. 11 b. Blade connector type. 12 c. Switching capacity: 10 A. 13 d. Contact material: Silver cadmium oxide. 14 e. Provide relays with a minimum of 3 SPDT contacts. 15 f. Coil voltage: 120 Vac or 24 Vdc. 16 g. Relay sockets are DIN rail mounted. 17 h. Internal neon or LED indicator is lit when coil is energized. 18 i. Clear polycarbonate dust cover with clip fastener. 19 j. Check button. 20 k. Temperature rise: 21

1) Coil: 85 DegF maximum. 22 2) Contact: 65 DegF maximum. 23

l. Insulation resistance: 100 Meg minimum. 24 m. Frequency response: 1800 operations/hour. 25 n. Operating temperature: -20 to +150 DegF. 26 o. Life expectancy: 27

1) Electrical: 250,000 operations or more. 28 2) Mechanical: 10,000,000 operations or more. 29

p. UL listed or recognized. 30

B. Signal-Level Switching Relays: 31 1. Acceptable manufacturers: 32

a. Idec. 33 b. Potter & Brumsfield. 34

2. Design fabrication: 35 a. Minimum of 2 SPDT gold-flashed, bifurcated contacts. 36 b. Hermetically sealed. 37 c. Rated at 3 A resistive at 120 Vac or 24 Vdc. 38

C. Time Delay Relays: 39 1. Acceptable manufacturers: 40

a. Eagle Signal Controls. 41 b. Idec. 42

2. Design and fabrication: 43 a. Melt design test and performance requirements of NEMA ICS 2-218. 44 b. Heavy-duty. 45 c. Solid-state construction. 46 d. External adjusting dial. 47 e. Auxiliary relays as required to perform functions specified or shown on Drawings. 48 f. Operates on 117 Vac (±10 percent) power source. 49 g. Contact rating: A150 per NEMA ICS 2-125. 50 h. Furnish with "on" and "timing out" indicators. 51

Page 137: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL AUXILIARIES 13446 - 3

2.3 TERMINATION EQUIPMENT 1

A. Terminal Blocks: 2 1. Acceptable manufacturers: 3

a. Phoenix Contact. 4 b. Allen-Bradley. 5

2. Design and fabrication: 6 a. Modular type with screw compression clamp. 7 b. Screws: Stainless steel. 8 c. Current bar: Nickel-plated copper allow. 9 d. Thermoplastic insulation rated for -40 to +90 DegC. 10 e. Wire insertion area: Funnel-shaped to guide all conductor strands into terminal. 11 f. Install end sections and end stops at each end of terminal strip. 12 g. Install machine-printed terminal markers on both sides of block. 13 h. Spacing: 6 mm. 14 i. Wire size: 22-12 AWG. 15 j. Rated voltage: 600 V. 16 k. Din rail mounting. 17 l. UL listed. 18

3. Standard-type block: 19 a. Rated current: 30 A. 20 b. Color: Gray body. 21

4. Bladed-type block: 22 a. Terminal block with knife blade disconnect which connects or isolated the two (2) sides 23

of the block. 24 b. Rated current: 10 A. 25 c. Color: 26

1) Panel control voltage leaves enclosure - normal: Gray body, orange switch. 27 2) Foreign voltage entering enclosure: Orange body, orange switch. 28

5. Grounded-type block: 29 a. Electrically grounded to mounting rail. 30 b. Use to terminal ground wires and analog cable shields. 31 c. Color: Green and yellow body. 32

B. Fuse Holders: 33 1. Acceptable manufacturers: 34

a. Phoenix Contact. 35 b. Allen-Bradley. 36

2. Design and fabrication: 37 a. Modular-type with screw compression clamp. 38 b. Screws: Stainless steel. 39 c. Current bar: Nickel-plated copper alloy. 40 d. Thermoplastic insulation rated for -40 to +105 DegC. 41 e. Wire insertion area: Funnel-shaped to guide all conductor strands into terminal. 42 f. Blocks can be ganged for multi-pole operation. 43 g. Install end sections and end stops at each end of terminal strip. 44 h. Install machine-printed terminal markers on both sides of block. 45 i. Spacing: 9.1 mm. 46 j. Wire size: 30-12 AWG. 47 k. Rated voltage: 300 V. 48 l. Rated current: 12 A. 49 m. Fuse size: 1/4 x 1-1/4. 50 n. Blown fuse indication. 51 o. DIN rail mounting. 52 p. UL listed. 53

Page 138: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL AUXILIARIES 13446 - 4

2.4 POWER SUPPLIES 1

A. DC Power Supplies: 2 1. Acceptable manufacturers: 3

a. Sola Hevi-Duty. 4 b. Phoenix Contact. 5 c. Rockwell Automation. 6

2. Design and fabrication: 7 a. Converts 120 Vac input to DC power at required voltage. 8 b. DIN rail mount with enclosure (i.e., not open frame). 9 c. Switching type. 10 d. AC input: 120 Vac +/-15 percent, nominal 60 Hz. 11 e. Efficiency: Minimum 86 percent. 12 f. Rated mean time between failure (MTBF): 500,000 HRS. 13 g. Voltage regulation: 14

1) Static: Less than 1.0 percent Vout. 15 2) Dynamic: +/-2 percent Vout overall. 16

h. Output ripple/noise: Less than 100 mV peak to peak (20 MHz). 17 i. Overload, short circuit and open circuit protection. 18 j. Temperature rating: 0 to 60 DegC full rated, derated linearly to 50 percent at 70 DegC. 19 k. Humidity rating: Up to 90 percent, non-condensing. 20 l. LED status indication for DC power. 21

B. Isolation Transformers: 22 1. Acceptable manufacturers: 23

a. Topaz Noise Suppressor Noise Isolator. 24 b. MGE UPS Systems, Topaz T1. 25

2. Design and fabrication: 26 a. Protects sensitive electronic equipment from electrical noise. 27 b. Common-mode noise attenuation: 146 dB at 0.0005 pF coupling capacitance. 28 c. Normal-mode attenuation: 60 dB. 29 d. Input voltage range: ±10 percent of rated. 30 e. Regulation: 3.5 percent or less from full-load to no-load. 31 f. Dielectric strength: 2,500 Vac minimum. 32 g. Harmonic distortion: 1 percent maximum. 33 h. Electromagnetic interference: 0-1 gauss maximum at 18 IN. 34 i. UL listed. 35

C. Uninterruptible Power Supplies (UPS): 36 1. Acceptable manufacturers: 37

a. Double conversion type to be utilized in conjunction with input isolation transformer: 38 1) Powerware 9130 UPS. 39

b. UPS with integral isolation transformer: 40 1) Best FERRUPS. 41 2) Controlled Power Co. LT series. 42

2. Design and fabrication: 43 a. Minimum 15 minutes power ride through without incoming power. 44 b. Frequency range: 45-65 Hz. 45 c. Input protection: 46

1) Fuse or circuit breaker. 47 d. Output voltage regulation: 48

1) ±2 percent online. 49 2) ±3 percent on battery mode. 50

e. Battery: Sealed, lead-acid; maintenance free. 51 f. Operating temperature: 32 to 104 DegF. 52 g. Relative humidity: 0-95 percent non-condensing. 53

Page 139: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL AUXILIARIES 13446 - 5

PART 3 - EXECUTION 1

3.1 INSTALLATION 2

A. Install products in accordance with manufacturer's instructions. 3

END OF SECTION 4

5

Page 140: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL AUXILIARIES 13446 - 6

1

Page 141: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TELEMETRY SYSTEMS 13447 - 1

2014/08/14 1

SECTION 13447 2

TELEMETRY SYSTEMS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Items required include but are not necessarily limited to the following: 7

a. Radios. 8 b. Antennas, masts, and associated appurtenances. 9

B. Related Specification Sections include but are not necessarily limited to: 10 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 11 2. Division 01 - General Requirements. 12 3. Section 10400 - Identification Devices. 13 4. Section 13440 - Instrumentation for Process Control: Basic Requirements. 14 5. Section 13441 - Control Loop Descriptions. 15

1.2 QUALITY ASSURANCE 16

A. Referenced Standards: 17 1. Federal Communications Commission (FCC): 18

a. 47 CFR 15 - Radio Frequency Devices, Section 15.247 - Operation within the bands 19 902 - 928 MHz, 2400 - 2483.5 MHz, and 5725 - 5850 MHz. 20

2. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 21 a. 802.3, Information Processing Systems - Local Area Networks - Part 3: Carrier Sense 22

Multiple Access with Collision Detection (CSMA/CD) Access Method and Physical 23 Layer Specifications. 24

1.3 SUBMITTALS 25

A. Shop Drawings: 26 1. See Specification Section 01340 for requirements for the mechanics and administration of 27

the submittal process. 28 2. See Specification Section 13440. 29 3. Product technical data: 30

a. As required by Specification Section 13440. 31 b. Manufacturer's installation instructions. 32

4. Submit all catalog cut sheets under Specification Section 13447 submittals. 33

B. Miscellaneous Submittals: Results of factory testing procedures. 34

C. Operation and Maintenance Manuals: 35 1. See Specification Section 01342 for requirements for: 36

a. The mechanics and administration of the submittal process. 37 b. The content of Operation and Maintenance Manuals. 38

PART 2 - PRODUCTS 39

2.1 ACCEPTABLE MANUFACTURERS 40

A. Subject to compliance with the Contract Documents, the manufacturers listed in the applicable 41 Articles below are acceptable. 42

Page 142: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TELEMETRY SYSTEMS 13447 - 2

B. Submit request for substitution in accordance with Specification Section 01640. 1

2.2 RADIOS 2

A. Acceptable Manufacturers: 3 1. Microwave Data Systems (MDS) iNET II. 4

a. No “or equals” accepted. 5

B. Design and Fabrication: 6 1. Communication: 7

a. Type: 8 1) Ethernet communication in accordance with IEEE 802.3. 9

2. Security: 128-bit data encryption. 10 3. License free. 11 4. Frequency hopping spread spectrum. 12 5. Frequency band: 902-928 MHz. 13 6. Configuration: 14

a. Provide remote configuration capability. 15 1) Provide licensed copies to the Owner of any software required for remote 16

configuration. 17 7. Error detection/correction: 16 bit CRC with ARQ (Automatic Re-send Query). 18 8. Input power: 10.5-24 Vdc. 19 9. Case: Aluminum. 20 10. Agency approvals: FCC 47 CFR 15.247. 21

C. Schedule: See schedule below for both radio and antenna. 22

2.3 ANTENNAS, TOWERS AND MASTS 23

A. Antenna: 24 1. Acceptable Manufacturer: 25

a. Sinclair SP-440. 26 2. Design and Fabrication: 27

a. ABS radome-enclosed log-periodic antenna. 28 b. 200 MHz bandwidth. 29 c. Hardware and fastenings: stainless steel. 30

B. Antenna Mounting: 31 1. Provide all masts, supports, lightning suppressors, and other apparatus required to make a 32

complete and operable radio telemetry system. 33 2. Lightning protected: Mast or tower direct connected to ground. 34 3. Mast materials: 35

a. Antenna Mounting Hardware: 36 1) 316 stainless steel or aluminum. 37

4. Schedule: 38 39

APPLICATION RADIO ANTENNA HEIGHT (FT ABOVE GRADE)

TOWER/MAST TYPE

Collector Well Remote Slave Radio

15 2-IN Pipe Attached to Building (See Installation Detail)

2.4 TRANSMISSION CABLE AND MISCELLANEOUS 40

A. Acceptable Cable Manufacturers: 41 1. Andrew Corp. LDF Series. 42 2. Times Microwave Systems LMR Series. 43

Page 143: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TELEMETRY SYSTEMS 13447 - 3

B. Provide low-loss foam-dielectric type cable connecting radio antenna port(s) with the antenna. 1 1. Cable: 1/2 IN or larger diameter as required to prevent signal losses in cable from 2

degrading performance. 3 2. Weatherproof, suitable for direct environmental exposure. 4

a. Use "O" ring seals on connections. 5

C. Provide "superflexible" transmission cable (length as required) at the radio antenna port. 6 1. Provide standard Type N connectors for connection to a continuous piece of cable extending 7

to the antenna. 8

D. Provide antenna surge suppressor and connect to coaxial cable in cabinet housing radio. 9 1. Acceptable manufacturer: 10

a. Polyphaser. 11

E. Provide grounding connections to the antenna mast and cable in accordance with manufacturer’s 12 recommendations. 13

2.5 ACCESSORIES 14

A. Provide all accessories required to furnish a complete telemetry system to accomplish the 15 requirements of the Drawings and Specifications. 16

PART 3 - EXECUTION 17

3.1 INSTALLATION 18

A. Install radio telemetry system as shown on Drawings in accordance with manufacturer's written 19 instruction. 20

B. Provide documentation verifying the data communication rate (actual throughput), signal 21 strength and signal quality for the Collector Well radio. 22

3.2 FIELD QUALITY CONTROL 23

A. Conduct startup of equipment and perform operational checks. 24

B. Maintain and submit an accurate daily or weekly log of all commissioning and startup functions. 25 1. All commissioning/startup functions may be witnessed by the Engineer. 26 2. All reports shall be signed and dated by the Contractor. 27

C. Provide Owner with a written statement that equipment has been installed properly, started up, 28 and is ready for operation by Owner’s personnel. 29

3.3 DEMONSTRATION 30

A. Demonstrate system in accordance with Specification Section 01650. 31

END OF SECTION 32

33

Page 144: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TELEMETRY SYSTEMS 13447 - 4

1

Page 145: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 1

2014/08/28 1

SECTION 13448 2

CONTROL PANELS AND ENCLOSURES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Requirements for control panels and enclosures utilized as follows: 7

a. Unless noted otherwise, all control panels and enclosures housing control components 8 that are specified in Specification Section 13442, Specification Section 13446, 9 Specification Section 13447, Specification Section 13449 or Specification Section 10 13500. 11

B. This Specification Section is only applicable to panels furnished with Division 11 equipment 12 packages when so stated in the applicable Division 11 Specification Section. 13

C. This Section is only applicable to panels housing Division 16 specified equipment (e.g., motor 14 starters, lighting controls, etc.) when so stated in the applicable Division 16 Specification 15 Section. 16

D. Related Sections include but are not necessarily limited to: 17 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 18 2. Division 01 - General Requirements. 19 3. Section 10400 - Identification Devices. 20 4. Division 11 - Equipment. 21 5. Section 13440 - Instrumentation for Process Control: Basic Requirements. 22 6. Section 13442 - Primary Elements and Transmitters. 23 7. Section 13446 - Control Auxiliaries. 24 8. Section 13449 - Surge Protection Devices (SPD) for Instrumentation and Control 25

Equipment. 26 9. Section 13500 - Programmable Logic Controller (PLC) Control System. 27 10. Division 16 - Electrical. 28

1.2 QUALITY ASSURANCE 29

A. Referenced Standards: 30 1. American National Standards Institute (ANSI). 31 2. ASTM International (ASTM): 32

a. B75, Standard Specification for Seamless Copper Tube. 33 3. National Electrical Manufacturers Association (NEMA): 34

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 35 b. ICS 4, Industrial Control and Systems: Terminal Blocks. 36

4. National Fire Protection Association (NFPA): 37 a. 70, National Electrical Code (NEC): 38

1) Article 409, Industrial Control Panels. 39 5. Underwriters Laboratories, Inc. (UL): 40

a. 508A, Standard for Safety Industrial Control Panels. 41

B. Miscellaneous: 42 1. Approved supplier of Industrial Control Panels under provisions of UL 508A. 43

a. Entire assembly shall be affixed with a UL 508A label "Listed Enclosed Industrial 44 Control Panel" prior to shipment to the jobsite. 45

b. Control panel(s) without an affixed UL 508A label shall be rejected and sent back to 46 the Contractor’s factory. 47

Page 146: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 2

1.3 DEFINITIONS 1

A. The term "panel" refers to control panels or enclosures listed in the schedule included in this 2 Specification Section. 3

B. Foreign Voltages: Voltages that may be present in circuits when the panel main power is 4 disconnected. 5

C. Intrinsically Safe: 6 1. A device, instrument or component that will not produce sparks or thermal effects under 7

normal or abnormal conditions that will ignite a specified gas mixture. 8 2. Designed such that electrical and thermal energy limits inherently are at levels incapable of 9

causing ignition. 10

D. Cable: Multi-conductor, insulated, with outer sheath containing either building wire or 11 instrumentation wire. 12

E. Instrumentation Cable: 13 1. Multiple conductor, insulated, twisted or untwisted, with outer sheath. 14 2. Instrumentation cable is typically either TSP (twisted-shielded pair) or TST (twisted-15

shielded triad), and is used for the transmission of low current or low voltage signals. 16

F. Ground Fault Circuit Interrupter (GFCI): A type of device (e.g., circuit breaker or receptacle) 17 which detects an abnormal current flow to ground and opens the circuit preventing a hazardous 18 situation. 19

G. Programmable Logic Controller (PLC): A specialized industrial computer using programmed, 20 custom instructions to provide automated monitoring and control functions by interfacing 21 software control strategies to input/output devices. 22

H. Remote Terminal Unit (RTU): An industrial data collection device designed for location at a 23 remote site, that communicates data to a host system by using telemetry such as radio, dial-up 24 telephone, or leased lines. 25

I. Input/Output (I/O): Hardware for the moving of control signals into and/or out of a PLC or 26 RTU. 27

J. Supervisory Control and Data Acquisition (SCADA): Used in process control applications, 28 where programmable logic controllers (PLCs) perform control functions but are monitored and 29 supervised by computer workstations. 30

K. Highway Addressable Remote Transducer (HART): An open, master-slave protocol for bus 31 addressable field instruments. 32

L. Digital Signal Cable: Used for the transmission of digital communication signals between 33 computers, PLCs, RTUs, etc. 34

M. Uninterruptible Power Supply (UPS): A backup power unit that provides continuous power 35 when the normal power supply is interrupted. 36

N. Loop Calibrator: Portable testing and measurement tool capable of accurately generating and 37 measuring 4-20ma DC analog signals. 38

1.4 SUBMITTALS 39

A. Shop Drawings: 40 1. See Specification Section 01340 for requirements for the mechanics and administration of 41

the submittal process. 42 2. See Specification Section 13440. 43 3. Prepared with computer aided design (CAD) software. 44 4. Printed on 11 by 17 IN sheets. 45 5. Drawings shall include a title block containing the following: 46

a. Plant or facility name where panel(s) are to be installed. 47

Page 147: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 3

b. Drawing title. 1 c. Drawing number. 2 d. Revision list with revision number and date. 3 e. Drawing date. 4 f. Drawing scale. 5 g. Manufacturer name, address, and telephone number. 6

6. Cover sheet for each drawing set shall indicate the following: 7 a. Plant or facility name. 8 b. Project name. 9 c. Submittal description. 10 d. Revision number. 11 e. Issue date. 12

7. Table of contents sheet(s) shall indicate the following for each drawing in the set: 13 a. Drawing number. 14 b. Drawing title. 15 c. Sheet number. 16

8. Legend and abbreviation sheet shall indicate the following: 17 a. Description of symbols and abbreviations used. 18 b. Panel construction notes including enclosure NEMA rating, finish type and color, wire 19

type, wire color strategy, conductor sizes, and wire labeling strategy. 20 c. Confirmation that the panel(s) are to be affixed with a UL 508A label prior to shipment 21

from the factory. 22 9. Bill of Material for each panel shall include the following component information: 23

a. Instrument tag number. 24 b. Quantity. 25 c. Functional name or description. 26 d. Manufacturer. 27 e. Complete model number. 28 f. Size or rating. 29

10. Panel exterior layout Drawings to scale and shall indicate the following: 30 a. Panel materials of construction, dimensions, and total assembled weight. 31 b. Panel access openings. 32 c. Conduit access locations. 33 d. Front panel device layout. 34 e. Nameplate schedule: 35

1) Nameplate location. 36 2) Legend which indicates text, letter height and color, and background color. 37

f. Alarm annunciator window engraving schedule. 38 g. Layouts of graphic panels or mosaic displays. 39

11. Panel interior layout Drawings shall be drawn to scale and shall indicate the following: 40 a. Sub-panel or mounting pan dimensions. 41 b. Interior device layouts. 42 c. PLC/Remote I/O rack general arrangement layouts. 43 d. Wire-way locations, purpose, and dimensions. 44 e. Terminal strip designations. 45 f. Location of external wiring and/or piping connections. 46 g. Location of lighting fixtures, switches and receptacles. 47

12. Wiring diagrams shall consist of the following: 48 a. Panel power distribution diagrams. 49 b. Control and instrumentation wiring diagrams. 50 c. PLC/Remote I/O information: 51

1) Model number of I/O module. 52 2) Description of I/O module type and function. 53 3) Rack and slot number. 54 4) Terminal number on module. 55 5) Point or channel number. 56

Page 148: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 4

6) Programmed point addresses. 1 7) Signal function and type. 2

d. Wiring diagrams shall identify each wire as it is to be labeled. 3

B. Manufacturer catalog cut sheets for enclosure, finish, panel devices, control auxiliaries, and 4 accessories. 5

C. Electrical load calculations for each panel: 6 1. Total connected load. 7 2. Peak electrical demand for each panel. 8

D. Climate control calculations for each panel. 9 1. Verify that sufficient dissipation and/or generation of heat is provided to maintain interior 10

panel temperatures within the rated operating temperatures of panel components. 11

E. Operation and Maintenance Manuals: 12 1. See Specification Section 01342 for requirements for: 13

a. The mechanics and administration of the submittal process. 14 b. The content of Operation and Maintenance Manuals. 15

2. See Specification Section 13440. 16

F. Informational Submittals: 17 1. Record Drawings: 18

a. Updated panel drawings delivered with the panel(s) from the Contractor’s factory. 19 b. Drawings shall be enclosed in transparent plastic and firmly secured within each panel. 20

PART 2 - PRODUCTS 21

2.1 ACCEPTABLE MANUFACTURERS 22

A. Subject to compliance with the Contract Documents, the following manufacturers are 23 acceptable: 24 1. Enclosures: 25

a. Hoffman Engineering Co. 26 b. Rittal. 27 c. Hammond Manufacturing. 28 d. Millbank Mfg. Co. 29

2. Panel heaters: 30 a. Hoffman Enclosures, Inc. 31 b. Rittal. 32 c. Hammond Manufacturing. 33

3. Cooling fans and exhaust packages: 34 a. Hoffman Enclosures, Inc. 35 b. Rittal. 36

4. Internal corrosion inhibitors: 37 a. Hoffman Enclosures, Inc.; Model A-HCI. 38 b. Northern Technologies International Corporation (NTIC); Model Zerust VC. 39 c. Cortec Corporation; Model VpCl Emitting Systems. 40

B. Submit request for substitution in accordance with Specification Section 01640. 41

2.2 ACCESSORIES 42

A. Panel Nameplates and Identification: See Section 10400. 43

Page 149: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 5

2.3 FABRICATION 1

A. General: 2 1. Fabricate panels with instrument arrangements and dimensions identified in the Contract 3

Documents. 4 2. Provide panel(s) with the required enclosure rating per NEMA 250 to meet classifications 5

identified in the Contract Documents. 6 3. Devices installed in panel openings shall have a NEMA enclosure rating at least equal to the 7

panel enclosure rating. 8 a. Devices that cannot be obtained with an adequate NEMA rating shall be installed 9

behind a transparent viewing window. 10 b. The window shall maintain the required NEMA rating of the enclosure. 11

4. Panel(s) shall be completely assembled at the Contractor’s factory. 12 a. No fabrication other than correction of minor defects or minor transit damage shall be 13

performed on panels at the jobsite. 14 5. Painting: 15

a. Panels fabricated from steel shall have their internal and external surfaces prepared, 16 cleaned, primed, and painted. 17 1) Mechanically abrade all surfaces to remove rust, scale, and surface imperfections. 18 2) Provide final surface treatment with 120 grit abrasives or finer, followed by spot 19

putty to fill all voids. 20 3) Utilize solvent or chemical methods to clean panel surfaces. 21 4) Apply surface conversion of zinc phosphate prior to painting to improve paint 22

adhesion and to increase corrosion resistance. 23 5) Electrostatically apply polyester urethane powder coating to all inside and outside 24

surfaces. 25 6) Bake powder coating at high temperatures to bond coating to enclosure surface. 26

a) Panel interior shall be white with semi-gloss finish. 27 b) Panel exterior shall be ANSI #61 gray with flat finish. 28

7) Application of alkyd liquid enamel coating shall be allowed in lieu of polyester 29 urethane powder for wall mounted NEMA 1 or NEMA 12 rated panels. 30

b. Panels fabricated from stainless steel, aluminum, or fiberglass shall not be painted. 31 6. Finish opening edges of panel cutouts to smooth and true surface conditions. 32

a. Panels fabricated from steel shall have the opening edges finished with the panel 33 exterior paint. 34

7. Panel shall meet all requirements of UL 508A. 35 a. If more than one (1) disconnect switch is required to disconnect all power within a 36

panel or enclosure, provide a cautionary marking with the word "CAUTION" and the 37 following or equivalent, "Risk of Electric Shock-More than one (1) disconnect switch 38 required to de-energize the equipment before servicing." 39

8. Provide control panel in accordance with NFPA 70, Article 409. 40 a. In the event of any conflict between NFPA 70, Article 409 and UL 508A, the more 41

stringent requirement shall apply. 42

B. Free-Standing Panels: 43 1. Welded construction. 44 2. Completely enclosed, self-supporting, and gasketed dusttight. 45 3. Rolled lip around all sides of enclosure door opening. 46 4. Seams and corners welded and ground smooth to touch and smooth in visual appearance. 47 5. Full height, fully gasketed flush pan doors. 48 6. Full length piano hinges rated for 1.5 times door plus instrument weight. 49 7. Doors with keyed alike locking handles and three-point catch. 50 8. Appropriate conduit, wiring, and instrument openings shall be provided. 51 9. Lifting eyebolts to allow simple, safe rigging and lifting of panel during installation. 52

C. Wall Mounted Panels: 53 1. Seams continuously welded and ground smooth. 54

Page 150: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 6

2. Rolled lip around all sides of enclosure door opening. 1 3. Gasketed dust tight. 2 4. Three-point latching mechanism operated by oil tight key-locking handle. 3 5. Key doors alike. 4 6. Continuous heavy GA hinge pin on doors. 5

a. Hinges rated for 1.5 times door plus instrument weight. 6 7. Front full opening door. 7 8. Brackets for wall mounting. 8

D. Internal Panel Wiring: 9 1. Panel wire duct shall be installed between each row of components, and adjacent to each 10

terminal strip. 11 a. Route wiring within the panel in wire-duct neatly tied and bundled with tie wraps. 12 b. Follow wire-duct manufacturer's recommended fill limits. 13 c. Wire-duct shall have removable snap-on covers and perforated walls for easy wire 14

entrance. 15 d. Wire-duct shall be constructed of nonmetallic materials with rating in excess of the 16

maximum voltage carried therein. 17 2. Wiring shall be installed such that if wires are removed from one (1) device, source of 18

power will not be disrupted to other devices. 19 3. Splicing and tapping of wires permitted only at terminal blocks. 20 4. Wire bunches to doors shall be secured at each end so that bending or twisting will be 21

around longitudinal axis of wire. 22 a. Protect bend area with sleeve. 23

5. Arrange wiring neatly, cut to proper length, with surplus wire removed. 24 a. Arrange wiring with sufficient clearance. 25 b. Provide abrasion protection for wire bundles that pass through openings or across edges 26

of sheet metal. 27 6. AC circuits shall be routed separate from analog signal cables and digital signal cables. 28

a. Separate by at least 6 IN, except at unavoidable crossover points and at device 29 terminations. 30

7. Provide at least 6 IN of separation between intrinsically safe devices and circuits and non-31 intrinsically safe devices and circuits. 32

8. Wiring to pilot devices or rotary switches shall be individually bundled and installed with a 33 "flexible loop" of sufficient length to permit the component to be removed from panel for 34 maintenance without removing terminations. 35

9. Conductors for AC and DC circuits shall be type MTW stranded copper listed for operation 36 with 600 V at 90 DegC. 37 a. Conductor size shall be as required for load and 16 AWG minimum. 38 b. Internal panel wiring color code: 39

1) AC circuits: 40 a) Power wiring: Black. 41 b) Control interconnections: Yellow. 42 c) Neutral: White. 43 d) Ground: Green. 44

2) Low voltage DC circuits: 45 a) Power wiring: Blue. 46 b) Control interconnections: Violet. 47

3) Foreign voltage circuits: Pink. 48 4) Annunciator circuits: Red. 49 5) Intrinsically safe circuits: Orange. 50

10. Analog signal cables shall be of 600 V insulation, stranded copper, twisted-shielded pairs. 51 a. Conductor size: 18 AWG minimum. 52 b. Terminate shield drain conductors to ground only at one (1) end of the cable. 53

Page 151: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 7

11. High precision 250 ohm resistors with 0.25 percent accuracy shall be used where 4-20 mA 1 DC analog signals are converted to 1-5 Vdc signals. 2 a. Resistors located at terminal strips. 3 b. Resistors terminated using individual terminal blocks and with no other conductors. 4 c. Resistor leads shall be un-insulated and of sufficient length to allow test or calibration 5

equipment (e.g., HART communicator, loop calibrator) to be properly attached to the 6 circuit with clamped test leads. 7

12. Analog signals for devices in separate enclosures shall not be wired in series. 8 a. Loop isolators shall be used where analog signals are transmitted between control 9

enclosures. 10 13. Wire and cable identification: 11

a. Wire and cables numbered and tagged at each termination. 12 b. Wire tags: 13

1) Slip-on, PVC wire sleeves with legible, machine-printed markings. 14 2) Adhesive, snap-on, or adhesive type labels are not acceptable. 15

c. Markings as identified in the Shop Drawings. 16

E. Grounding Requirements: 17 1. Equipment grounding conductors shall be separated from incoming power conductors at the 18

point of entry. 19 2. Minimize grounding conductor length within the enclosure by locating the ground reference 20

point as close as practical to the incoming power point of entry. 21 3. Bond electrical racks, chassis and machine elements to a central ground bus. 22

a. Nonconductive materials, such as paint, shall be removed from the area where the 23 equipment contacts the enclosure. 24

4. Bond the enclosure to the ground bus. 25 a. It is imperative that good electrical connections are made at the point of contact 26

between the ground bus and enclosure. 27 5. Panel-mounted devices shall be bonded to the panel enclosure or the panel grounding 28

system by means of locknuts or pressure mounting methods. 29 6. Sub-panels and doors shall be bonded to ground. 30

F. Termination Requirements: 31 1. Wiring to circuits external to the panel connected to interposing terminal blocks. 32 2. Terminal blocks rigidly mounted on DIN rail mounting channels. 33 3. Terminal strips located to provide adequate space for entrance and termination of the field 34

conductors. 35 4. One (1) side of each strip of terminal blocks reserved exclusively for the termination of field 36

conductors. 37 5. Terminal block markings: 38

a. Marking shall be the same as associated wire marking. 39 b. Legible, machine-printed markings. 40 c. Markings as identified in the shop drawings. 41

6. Terminal block mechanical characteristics, and electrical characteristics shall be in 42 accordance with NEMA ICS 4. 43

7. Terminal blocks with continuous marking strips. 44 a. Each terminal block shall be identified with machine printed labels. 45

8. Terminals shall facilitate wire sizes as follows: 46 a. 120 Vac applications: Conductor size 12 AWG minimum. 47 b. Other: Conductor size 14 AWG minimum.. 48

9. Analog signal cable shield drain conductors shall be individually terminated. 49 10. Install minimum of 20 percent spare terminals. 50 11. Bladed, knife switch, isolating type terminal blocks where control voltages enter or leave 51

the panel. 52 12. Fused terminal blocks shall be used in the following circuits: 53

a. Control voltage is used to energize a solenoid valve. 54 b. DC power is connected to 2-wire, loop-powered instruments. 55

Page 152: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 8

13. Fused terminal blocks shall be provided with blown fuse indicators. 1 14. When control circuits require more than one (1) field conductor connected to a single wiring 2

point, a sufficient number of terminal points shall be connected internally to allow 3 termination of only one (1) field conductor per terminal block. 4

15. DIN rail mounting channels shall be installed along full length of the terminal strip areas to 5 facilitate future expansion. 6

16. Connections to devices with screw type terminals shall be made using spade-tongue, 7 insulated, compression terminators. 8

G. Component Mounting and Placement: 9 1. Components shall be installed per manufacturer instructions. 10 2. Control relays and other control auxiliaries shall be mounted on DIN rail mounting channels 11

where practical. 12 3. Front panel devices shall be mounted within a range of 40 to 70 IN above the finished floor, 13

unless otherwise shown in the Contract Documents. 14 4. PLC and I/O rack installation: 15

a. Located such that the LED indicators and switches are readily visible with the panel 16 door open. 17

b. Located such that repair and/or replacement of component can be accomplished without 18 the need to remove wire terminations or other installed components. 19

5. Locate power supplies with sufficient spacing for circulation of air. 20 6. Where components such as magnetic starters, contactors, relays, and other electromagnetic 21

devices are installed within the same enclosure as the PLC/RTU system components, 22 provide a barrier of at least 6 IN of separation between the “power area containing the 23 electromagnetic devices” and the “control area”. 24

7. Components mounted in the panel interior shall be fastened to an interior sub-panel using 25 machine screws. 26 a. Fastening devices shall not project through the outer surface of the panel enclosure. 27

8. Excess mounting space of at least 20 percent for component types listed below to facilitate 28 future expansion: 29 a. Fuse holders. 30 b. Circuit breakers. 31 c. Control relays. 32 d. Time delay relays. 33 e. Intrinsically safe barriers and relays. 34

9. Components installed on sub-panels shall be provides with a minimum spacing between 35 component and wire duct of 1 IN. 36 a. Minimum of 2 IN separation between terminal strips and wire ducts. 37

H. Power Distribution: 38 1. Main incoming power circuits shall be protected with a thermal magnetic circuit breaker. 39

a. Limit load to maximum of 80 percent of circuit breaker rating. 40 2. Component types listed below shall be individually fused so that they may be individually 41

de-energized for maintenance: 42 a. PLC power supply modules. 43 b. As required. 44

3. Each control panel with PLC components shall be furnished with power protection in the 45 form of a double conversion UPS. 46

4. Equip each panel with necessary power supplies with ratings required for installed 47 equipment and with minimum 25 percent spare capacity. 48

5. Constant voltage transformers, balancing potentiometers, and rectifiers as necessary for 49 specific instrument requirements. 50

I. Internal Panel Lighting and Service Receptacles: 51 1. Panels less than or equal to 4 FT wide: 52

a. One (1) electrical GFCI duplex receptacle. 53 b. One (1) compact fluorescent light fixture with manual switch(es). 54

Page 153: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 9

2. Panels or panel faces greater than 4 FT wide: 1 a. One (1) duplex electrical GFCI receptacle per 6 FT of length. 2 b. Continuous fluorescent lighting strip with manual switches. 3

J. Environmental Controls: 4 1. Indoor panels located in a designated electrical room or control room: 5

a. Thermostat controlled cooling fans if required to preclude hot spots from exceeding 6 allowable temperature inside panel(s). 7

b. Internal corrosion inhibitors. 8 2. Indoor panels not located within a designated electrical room or control room: 9

a. Thermostat controlled heaters to maintain temperature approximately 10 DegF above 10 ambient for condensation prevention inside the panels. 11

b. Thermostat controlled cooling fans if required to preclude hot spots from exceeding 12 allowable temperature inside panel(s). 13

c. Internal corrosion inhibitors. 14 3. Environmental control components: 15

a. Panel heaters: 16 1) Thermostat controlled. 17 2) Components mounted in an anodized aluminum housing. 18 3) Designed for sub-panel mounting. 19 4) Powered from 120 Vac and protected with a dedicated circuit breaker. 20

b. Cooling fans: 21 1) Cooling fan controlled with a separately mounted thermostat with bi-metal sensor 22

and adjustable dial for temperature setting. 23 2) Powered from 120 Vac and protected with a dedicated circuit breaker. 24

c. Internal corrosion inhibitors: 25 1) Contains chemical which vaporizes and condenses on surfaces in the enclosure. 26 2) Inhibitor shall be applied in accordance with manufacturer instructions for the 27

enclosure volume. 28 3) Inhibitor shall be applied in the panel(s) prior to shipment from the Contractor’s 29

factory. 30

2.4 MAINTENANCE MATERIALS 31

A. Extra Materials: 32 1. One (1) quart of exterior finish touch-up paint. 33 2. One (1) complete set of replacement corrosion inhibitors in sealed packages for each panel. 34

PART 3 - EXECUTION 35

3.1 FACTORY TESTING 36

A. Scope: Inspect and test entire panel assembly to verify readiness for shipment. 37

B. Location: Contractor’s factory. 38

C. Factory Tests: 39 1. Tests shall be fully documented and signed by the Contractor’s factory supervisor. 40 2. The panel shop shall fully test the control panel for correct wiring. 41

a. Each I/O point shall be checked by measuring or connecting circuits at the field 42 terminal blocks. 43

3. Burn-in test: Panel(s) shall be fully energized for a minimum period of 48 HRS. 44 4. A PLC Central Processing Unit (CPU) shall be obtained and connected to the panel(s) if 45

necessary for testing purposes. 46 5. Testing equipment (such as digital multi-meters, analog loop calibrators, and laptop 47

computers with PLC programming software) shall be used as required for testing. 48

Page 154: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL PANELS AND ENCLOSURES 13448 - 10

6. The following functions shall be tested as a minimum: 1 a. Demonstrate functions of the panel(s) required by the Contract Documents. 2 b. Correctness of wiring from all panel field terminals to all I/O points and to all panel 3

components. 4 c. Simulate and test each discrete signal at the field terminal strips. 5 d. Simulate and test each analog signal using loop calibrators. 6 e. Correct operation of communications between PLC system Central Processing Units 7

(CPUs) and Remote I/O bases or radio. 8 f. Correct operation of all digital communication devices. 9 g. Demonstrate online and offline diagnostic tests and procedures. 10 h. The Contractor shall notify the Engineer in writing a minimum of 15 calendar days 11

prior to the Factory Tests. 12 1) Engineer has the option to witness all required tests. 13

7. Make following documentation available to the Engineer at test site during the tests: 14 a. Contract Documents. 15 b. Factory Demonstration Testing procedures. 16 c. List of equipment to be testing including make, model, and serial number. 17 d. Shop Drawing submittal data for equipment being tested. 18

8. Deficiencies shall be corrected prior to shipment from the Contractor’s factory. 19

3.2 INSTALLATION 20

A. Install free-standing panels on 4 IN high concrete housekeeping pads. 21

B. Anchor panels in a manner to prevent the enclosure from racking, which may cause the access 22 doors to become misaligned. 23

C. Obtain approved panel layouts prior to installation of conduits. 24

D. Install products in accordance with manufacturer’s instructions. 25

3.3 SCHEDULE 26

A. Schedule: 27 28

LOCATION/SERVICE TYPE MATERIAL NEMA RATING

Collector Well PLC Panel Wall Mount Steel NEMA 12 Remote I/O Panel Rack Mount Steel NEMA 4

END OF SECTION 29

Page 155: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION AND CONTROL EQUIPMENT 13449 - 1

2014/08/14 1

SECTION 13449 2

SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION 3 AND CONTROL EQUIPMENT 4

PART 1 - GENERAL 5

1.1 SUMMARY 6

A. Section Includes: 7 1. Type IC1 SPD - Dedicated 120 Vac circuit, series connection, control panel mounted. 8 2. Type IC2 SPD – not used. 9 3. Type IC3 SPD - Discrete 120 Vac control signal, control panel mounted. 10 4. Type IC4 SPD - not used. 11 5. Type IC5 SPD - not used. 12 6. Type IC6 SPD - not used. 13 7. Type IC7 SPD - Discrete low voltage control signal, control panel mounted. 14 8. Type IC8 SPD - not used. 15

B. Related Sections include but are not necessarily limited to: 16 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 17 2. Division 01 - General Requirements. 18 3. Section 13440 - Instrumentation for Process Control: Basic Requirements. 19

1.2 QUALITY ASSURANCE 20

A. Referenced Standards: 21 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 22

a. C62.41, Recommended Practice for Surge Voltages in Low-Voltage AC Power 23 Circuits. 24

2. National Electrical Manufacturers Association (NEMA): 25 a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 26 b. LS 1, Low Voltage Surge Protection Devices. 27

3. Underwriters Laboratories, Inc. (UL): 28 a. 497B, Standard for Safety Protectors for Data Communications and Fire-Alarm 29

Circuits. 30 b. 1283, Standard for Safety Electromagnetic Interference Filters. 31 c. 1363, Standard for Safety Relocatable Power Taps. 32 d. 1449, Standard for Safety Transient Voltage Surge Suppressors. 33

B. Qualifications: 34 1. Provide devices for a manufacturer who has been regularly engaged in the development, 35

design, testing, listing and manufacturing of SPDs of the types and ratings required for a 36 period of 10 years or more and whose products have been in satisfactory use in similar 37 service. 38

2. Upon request, suppliers or manufacturers shall provide a list of not less than three (3) 39 customer references showing satisfactory operation. 40

1.3 DEFINITIONS 41

A. Clamping Voltage: The voltage measured at the end of the 6 IN output leads of the SPD and 42 from the zero voltage reference to the peak of the surge when the applied surge is induced at the 43 90 degree phase angle of the applied system frequency voltage. 44

Page 156: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION AND CONTROL EQUIPMENT 13449 - 2

B. Let-Through Voltage: The voltage measured at the end of the 6 IN output leads of the SPD and 1 from the system peak voltage to the peak of the surge when the applied surge is induced at the 2 90 degree phase angle of the applied system frequency voltage. 3

C. Maximum Continuous Operating Voltage (MCOV): The maximum steady state voltage at 4 which the SPD device can operate and meet it specification within its rated temperature. 5

D. Maximum Surge Current: 6 1. The maximum 8 x 20 microsecond surge current pulse the SPD device is capable of 7

surviving on a single-impulse basis without suffering either performance degradation or 8 more than 10 percent deviation of clamping voltage at a specified surge current. 9

2. Listed by mode, since number and type of components in any SPD may vary by mode. 10

E. Protection Modes: This parameter identifies the modes for which the SPD has directly 11 connected protection elements, i.e., line-to-neutral (L-N), line-to-line (L-L), line-to-ground (L-12 G), neutral-to-ground (N-G). 13

F. Surge Current per Phase: 14 1. The per phase rating is the total surge current capacity connected to a given phase 15

conductor. 16 2. For example, a wye system surge current per phase would equal L-N plus L-G; a delta 17

system surge current per phase would equal L-L plus L-G. 18 a. The N-G mode is not included in the per phase calculation. 19

G. System Peak Voltage: The electrical equipment supply voltage sine wave peak (i.e., for a 120 V 20 system the L-N peak voltage is 170 V). 21

1.4 SUBMITTALS 22

A. Shop Drawings: 23 1. See Specification Section 01340 for requirements for the mechanics and administration of 24

the submittal process. 25 2. For named products, submit only a catalog cut sheet. 26

a. For all other products, submit the data required below. 27 3. See Specification Section 13440. 28 4. Product technical data for non-specified models: 29

a. Manufacturer’s experience. 30 b. Standard catalog cut sheet. 31 c. Electrical and Mechanical Drawings showing unit dimensions, weights, mounting 32

provisions, connection details and layout diagram of the unit. 33 d. Create a Product Data Sheet for each different model number of SPD provided. 34

1) Data in the Product Data Sheet heading: 35 a) SPD Type per PART 2 of the Specification. 36 b) Manufacturer’s Name. 37 c) Product model number. 38

2) Data in the Product Data Sheet body: 39 a) Column one: Specified value/feature of every paragraph of PART 2 of the 40

Specification. 41 b) Column two: Manufacturer’s certified value confirming the product meets the 42

specified value/feature. 43 3) Data in the Product Data Sheet closing: 44

a) Signature of the manufacturer’s official (printed and signed). 45 b) Title of the official. 46 c) Date of signature. 47

B. Operation and Maintenance Manuals: 48 1. See Specification Section 01342 for requirements for: 49

a. The mechanics and administration of the submittal process. 50 b. The content of Operation and Maintenance Manuals. 51

Page 157: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION AND CONTROL EQUIPMENT 13449 - 3

1.5 WARRANTY 1

A. The manufacturer shall provide a minimum of a five (5) year Limited Warranty from date of 2 shipment against failure when installed in compliance with applicable national/local electrical 3 codes and the manufacturer’s installation, operation and maintenance instructions. 4

PART 2 - PRODUCTS 5

2.1 ACCEPTABLE MANUFACTURERS 6

A. Subject to compliance with the Contract Documents, the manufacturers model numbers listed in 7 the individual product paragraphs below are acceptable. 8

2.2 TYPE IC1 SPD 9

A. Approved Products: 10 1. Eaton AGSHW CH-120N-15-XS. 11 2. EDCO HSP121BT-1RU. 12 3. MTL MA15/D/1/SI. 13 4. Phoenix Contact SFP 1-20/120AC (2856702). 14

B. Standards: UL 1449. 15

C. Design: 16 1. General: 17

a. Mounted internally to control panels for point-of-use loads. 18 b. MOV based or multi-stage hybrid solid state high performance suppression system. 19 c. Designed for series connection. 20 d. Enclosure: Metallic or plastic, flange or DIN rail mounting. 21 e. Field connection: Provide unit with external terminal screws for each phase, neutral 22

and ground that will accept #14 through #12 conductors. 23 f. Device monitoring: Long-life, solid state, externally visible indicators that monitors the 24

on-line status of the units suppression filter system or power loss in any of the phases. 25 2. Operating voltage: 120 Vac. 26 3. Operating current: 15A minimum. 27 4. Operating frequency: 45 to 65 Hz. 28 5. Modes of protection: All modes, L-N, L-G and N-G. 29 6. Maximum continuous operating voltage: Less than 130 percent of system peak voltage. 30 7. Maximum surge current: 20,000A per phase, 10,000A per mode minimum. 31 8. Minimum repetitive surge current capacity: 1000 impulses with no degradation of more 32

than 10 percent deviation of the clamping voltage. 33 9. Fusing: Optional integral unit level and/or component level short circuit and/or thermal 34

overload protection. 35 a. External protection as recommended by manufacturer. 36

10. Maximum clamping voltages, dynamic test with voltages measured from the zero voltage 37 reference and 90 degree phase angle: 38

39

System Voltage Test Mode IEEE C62.41

UL 1449 B Comb. Wave A Ring Wave L-N = 120 V L-N 400 V 300 V 330 V

L-G 500 V 400 V 400 V N-G 500 V 400 V 400 V

40

Page 158: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION AND CONTROL EQUIPMENT 13449 - 4

2.3 TYPE IC3 SPD 1

A. Approved Products: 2 1. EDCO DRS-130RMS. 3 2. MTL MA-15/D/1/SI. 4 3. MTL SD-150X. 5 4. Phoenix Contact PT 2x1VA-120AC-ST (2839185) with PT BE/FM (2839282) base for non-6

isolated wiring. 7 5. Phoenix Contact PT-2 PE/S-120 AC-ST (2839334 with PT-BE/FM (2839282) base for 8

isolated wiring. 9

B. Standards: UL 497B or UL 1449. 10

C. Design: 11 1. General: 12

a. Mounted internally to control panels for point-of-use loads. 13 b. Multi-stage hybrid solid state high performance suppression system. 14 c. Designed for series connection. 15 d. Enclosure: Metallic or plastic, flange or DIN rail mounting. 16 e. Field connection: Provide unit with external terminal screws for each phase, neutral 17

and ground that will accept #14 through #12 conductors. 18 f. Device monitoring: Long-life, solid state, externally visible indicators that monitors the 19

on-line status of the units suppression filter system or power loss in any of the phases. 20 2. Operating voltage: 120 Vac. 21 3. Operating current: 3 A minimum. 22 4. Operating frequency: 45 to 65 Hz. 23 5. Modes of protection: L-N; when ground conductor is present L-G and N-G. 24 6. Maximum continuous operating voltage: Less than 130 percent of system peak voltage. 25 7. Maximum surge current: 6000 A per phase, 3000A per mode minimum. 26 8. Minimum repetitive surge current capacity: 27

a. The SPD shall meet one (1) of the following: 28 1) 1000 occurrences of a 200A, 10x1000 microsecond waveform. 29 2) 400 occurrences of a 500A, 10x1000 microsecond waveform. 30 3) 100 occurrences of a 400A, 10x700 microsecond waveform. 31 4) 100 occurrences of a 2000A, 8x20 microsecond waveform. 32

9. Maximum clamping voltages, measured from the zero voltage reference: 33 a. The SPD shall meet one (1) of the following: 34

1) 400A, 10x700 microsecond waveform: 200 percent of system voltage. 35 2) IEEE B3 combination wave: 250 percent of system voltage. 36 3) IEEE B3 ring wave: 200 percent of system peak voltage. 37 4) IEEE A3 ring wave: 200 percent of system peak voltage. 38 5) Mode N-G clamping voltage may be 175 percent higher than the L-G levels. 39

2.4 TYPE IC7 SPD 40

A. Approved Products: 41 1. Eaton DDIN Series. 42 2. EDCO DRS Series. 43 3. MTL SD Series. 44 4. Phoenix Contact: PT Series. 45

B. Standards: UL 497B. 46

C. Design: 47 1. General: 48

a. Mounted internally to control panels for protection of equipment connected to a discrete 49 signal. 50

b. Multi-stage hybrid solid state high performance suppression system. 51

Page 159: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION AND CONTROL EQUIPMENT 13449 - 5

c. Designed for series connection. 1 d. Enclosure: Metallic or plastic, flange or DIN rail mounting. 2 e. Field connection: Provide unit with external terminal screws for line and ground 3

conductors. 4 2. Operating voltage: 24 Vdc or 24 Vac or 120 Vac or as indicated on the Drawings. 5 3. Modes of protection: All modes: 6

a. AC applications: L-N, L-G, N-G 7 b. DC applications: Pos-Neg, Pos-Gnd, Neg-Gnd. 8

4. Maximum continuous operating voltage: Less than 130 percent of system peak voltage. 9 5. Maximum surge current: 10,000 A. 10 6. Minimum repetitive surge current capacity: 11

a. The SPD shall meet one (1) of the following: 12 1) 1000 occurrences of a 200A, 10 x 1000 microsecond waveform. 13 2) 400 occurrences of a 500A, 10 x 1000 microsecond waveform. 14 3) 100 occurrences of a 400A, 10 x 700 microsecond waveform. 15 4) 100 occurrences of a 2000A, 8 x 20 microsecond waveform. 16 5) 10 occurrences of a 10,000A, 8 x 20 microsecond waveform. 17

7. Maximum clamping voltages, L-L (Pos-Neg): 18 a. The SPD shall meet one (1) of the following: 19

1) 400A, 10x700 microsecond waveform: 400 percent of system voltage. 20 2) 10,000A, 8x20 microsecond waveform: 400 percent of system voltage. 21 3) IEEE B3 combination wave: 250 percent of system voltage. 22

8. Maximum clamping voltages, L-G: 23 a. The SPD shall meet one (1) of the following: 24

1) 400A, 10x700 microsecond waveform: 200 percent of system voltage. 25 2) 10,000A, 8x20 microsecond waveform: 200 percent of system voltage. 26 3) IEEE B3 combination wave: 300 percent of system voltage. 27

2.5 SOURCE QUALITY CONTROL 28

A. Performance tests to be performed or independently verified by a certified testing laboratory. 29

B. The SPD are to be tested as a complete SPD system including: Integral unit level and/or 30 component level fusing. 31

PART 3 - EXECUTION 32

3.1 INSTALLATION 33

A. Install products in accordance with manufacturer's instructions. 34

B. Type IC1 SPD: 35 1. Provide on the following applications: 36

a. Line side of 120 V power terminals in panels with PLC components. 37 2. Connected in series with the panel's or equipment’s branch circuit. 38 3. Provide fuse protection as recommended by manufacturer. 39 4. Flange mount or DIN rail mount in control panel. 40 5. Connect all SPDs in the panel to the same grounding point. 41

C. Type IC3 SPD: 42 1. Provide on the following applications: 43

a. 120 V discrete PLC signals into a control panel from float switches, position switches, 44 etc., where the device is mounted outdoors or in a remote building or structure from the 45 control panel and where the control conductors are routed above grade or underground. 46

b. 120 V discrete PLC signals into a control panel from float switches, position switches, 47 etc., where both the device and control panel are mounted outdoors and the control 48 conductors are routed above grade or underground. 49

Page 160: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SURGE PROTECTION DEVICES (SPD) FOR INSTRUMENTATION AND CONTROL EQUIPMENT 13449 - 6

2. Connected in series with the equipment. 1 3. Provide fuse protection as recommended by manufacturer. 2 4. Flange mount or DIN rail mount in control panel. 3 5. Connect all SPDs in the panel to the same grounding point. 4

D. Type IC7 SPD: 5 1. Provide on the following applications: 6

a. Low voltage (e.g., 24 Vac, 24 Vdc) discrete PLC signals into a control panel from float 7 switches, position switches, etc., where the device is mounted outdoors or in a remote 8 building or structure from the control panel and where the control conductors are routed 9 above grade or underground. 10

b. Low voltage (e.g., 24 Vac, 24 Vdc) discrete PLC signals into a control panel from float 11 switches, position switches, etc., where both the device and control panel are mounted 12 outdoors and the control conductors are routed above grade or underground. 13

2. Connect in series with the equipment. 14 3. Flange mount or DIN rail mount in control panel. 15 4. Connect all SPDs in the control panel to the same grounding point. 16

END OF SECTION 17

Page 161: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 1

2014/08/28 1

SECTION 13500 2

PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Programmable logic controller (PLC) control system(s), including software, programming, 7

and training. 8

B. Related Sections include but are not necessarily limited to: 9 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 10 2. Division 01 - General Requirements. 11 3. Section 10400 - Identification Devices. 12 4. Section 11005 - Equipment: Basic Requirements. 13 5. Section 13440 - Instrumentation for Process Control: Basic Requirements. 14 6. Section 13441 - Control Loop Descriptions. 15 7. Section 13446 - Control Auxiliaries. 16 8. Section 13448 - Control Panels and Enclosures. 17 9. Section 16120 - Wire and Cable - 600 Volt and Below. 18

1.2 QUALITY ASSURANCE 19

A. Referenced Standards: 20 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 21

a. C37.90.2, Trial-Use Standard Withstand Capability of Relay Systems to Radiated 22 Electromagnetic Interference from Transceivers. 23

b. C62.41, Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits. 24 2. National Electrical Manufacturers Association (NEMA): 25

a. ICS 1, General Standards for Industrial Control and Systems. 26

B. Qualifications: 27 1. Installation supervisor shall have had experience in overseeing installation and startup of at 28

least three (3) similar installations. 29 2. Programmer(s) shall have had experience in programming PLCs for at least two (2) projects 30

of similar size and complexity. 31

1.3 SUBMITTALS 32

A. Shop Drawings: 33 1. See Specification Section 01340 for requirements for the mechanics and administration of 34

the submittal process. 35 2. See Specification Section 13440. 36 3. Product technical data including: 37

a. Annotated hard copies of PLC software programs. 38 1) Submit program for logic in ladder diagram format as used for the specific PLC 39

system. 40 2) Annotate program listing to include the following: 41

a) Written description of each rung's function. 42 b) Reference to control loop number for each rung where applicable. 43 c) Reference to instrumentation tag number of I/O devices for each rung where 44

applicable. 45 3) Provide written descriptions completely defining all function blocks used in 46

program. 47

Page 162: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 2

4) Provide list of all addresses referenced in logic diagram with description of data 1 associated with each address. 2

b. Results of factory testing procedures. 3 c. Drawings containing the following information to be submitted as part of Specification 4

Section 13448 submittals: 5 1) Arrangement Drawings for PLC system components. 6 2) Panel and enclosure plans, sections and details. 7 3) Access opening locations and required clearances for each panel and enclosure. 8 4) Enclosure internal wiring and terminal blocks. 9

d. Catalog cut sheets containing information on PLC components to be submitted as part 10 of this Specification Section submittals. 11

B. Miscellaneous Submittals: 12 1. Certifications: 13

a. Qualifications of installation supervisor. 14 b. Qualifications of programmer(s). 15

C. Operation and Maintenance Manuals: 16 1. See Specification Section 01342 for requirements for: 17

a. The mechanics and administration of the submittal process. 18 b. The content of Operation and Maintenance Manuals. 19

2. Submit maintenance procedures available to Owner. 20 a. Include the location and phone numbers of service centers (including 24 HR "hot 21

lines"). 22 b. Provide specific information including operation and maintenance requirements, 23

programming assistance, troubleshooting guide, parts ordering, field service personnel 24 requests, and service contracts. 25

PART 2 - PRODUCTS 26

2.1 ACCEPTABLE MANUFACTURERS 27

A. Subject to compliance with the Contract Documents, the following manufacturers are 28 acceptable: 29 1. Rockwell Automation, Allen-Bradley. 30 2. No “or equals” acceptable. 31

2.2 PERFORMANCE AND DESIGN REQUIREMENTS 32

A. See Section 13440. 33

B. The PLC system shall accomplish the control requirements of the loop descriptions, Drawings, 34 and Specifications. 35

C. PLC programming shall be documented and factory tested. 36

D. The PLC system shall operate in ambient conditions of 32 to 140 DegF temperature and 5 to 95 37 percent relative humidity without the need for purging or air conditioning. 38

E. Environmental Controls: 39 1. Furnish circulation fans in solid state control system enclosures. 40

F. Where the PLC is utilized to control multiple trains of equipment and where the equipment in 41 each train operates as a unit relatively independent of other equipment trains (e.g., facility with 42 multiple boiler units or filter trains), the PLC components (I/O modules, power supplies, etc.) 43 shall be assigned so that the failure of any one (1) component does not affect equipment on all 44 trains. 45 1. I/O modules shall be segregated on a train basis unless required otherwise for safety 46

reasons. 47

Page 163: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 3

2. Where several equipment units operate in parallel, but are not considered assigned to a 1 particular equipment train (e.g., multiple raw water pumps or chemical feed pumps all 2 discharging into a common system), the PLC I/O modules associated with each equipment 3 unit shall be assigned so that the failure of any one (1) I/O module does not affect all of the 4 parallel operating equipment units. 5

G. All PLC control system components shall be capable of meeting or exceeding electromagnetic 6 interference tests per IEEE C37.90.2. 7

H. Incorporate the following minimum safety measures: 8 1. Watchdog function to monitor: 9

a. Internal processor clock failure. 10 b. Processor memory failure. 11 c. Loss of communication between processor and I/O modules. 12 d. Processor ceases to execute logic program. 13

2. Safety function wiring: Emergency shutdown switches shall not be wired into the 14 controller. 15

3. Safe wiring: 16 a. Unless otherwise specified, activation of alarms and stopping of equipment shall result 17

from the de-energization of control circuits, rather than the energization of control 18 circuits. 19

b. Low voltage control signal wires: 20 1) Place in conduit segregated for that purpose only. 21 2) Twisted shielded wire pair. 22 3) Not located in the same conduit or bundle with power wiring. 23

4. Initial safety conditions: 24 a. Utilize program module to dictate output states in a known and safe manner prior to 25

running of control program. 26 b. Utilize program each time PLC is re-initiated and the control program activated. 27

5. Monitoring of internal faults and display: 28 a. Internal PLC system status and faults shall be monitored and displayed. 29

1) Monitored items shall include: 30 a) Memory ok/loss of memory. 31 b) Processor ok/processor fault. 32 c) Scan time overrun. 33

6. Control of programs: Protect access to PLC program loading with password protection or 34 with locked, key operated selector switches. 35

7. Design PLC system with high noise immunity to prevent occurrence of false logic signals 36 resulting from switching transients, relay and circuit breaker noise or conducted and 37 radiated radio frequency interference. 38

2.3 COMPONENTS 39

A. PLC System Central Processor Unit (CPU): 40 1. Rockwell Automation ControlLogix. 41 2. CPU shall provide communications with other control systems and man-machine interfaces 42

as specified. 43 3. Memory: 44

a. Non-volatile memory. 45 4. Plug-in card design to allow quick field replacement of faulty devices. 46

a. Provide unit designed for field replacement and expansion of memory without requiring 47 rewiring or use of special tools. 48

5. 20 percent minimum spare useable memory capacity after all required programming is in 49 place and operating. 50

6. Capable of executing all control functions required by the Specifications and Drawings. 51

Page 164: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 4

7. Built-in three-mode (proportional-integral-derivative) control capabilities. 1 a. As directly selectable algorithms requiring no user knowledge of programming 2

languages. 3 8. On-line reconfigurable. 4 9. Lighted status indicators for "RUN" and "FAILURE." 5 10. Capable of manual or automatic control mode transfer from the operating console stations or 6

from within the control strategy. 7 a. Transfer shall be bumpless and balanceless. 8

B. Input/output (I/O) Modules: 9 1. Provide plug-in modular-type I/O racks with cables to connect to all other required PLC 10

system components. 11 2. Provide I/O system with: 12

a. I/O solid state boards with status lights indicating I/O status. 13 b. Electric isolation between logic and field device. 14 c. Capability of withstanding low energy common mode transient to 1000 V without 15

failure. 16 d. Incorporate noise suppression design. 17 e. Capable of being removed and inserted into the I/O rack under power, without affecting 18

any other I/O modules in the rack. 19 f. Install 20 percent spare I/O points (in addition to points listed in PLC Points list at end 20

of this section). 21 3. Input/output connection requirements: 22

a. Make connections to I/O subsystem by terminating all field wiring on terminal blocks 23 within the I/O enclosure. 24

b. Prewire I/O modules to terminal blocks. 25 c. Provide terminal blocks with continuous marking strip. 26 d. Size terminals to accommodate all active data base points and spares. 27 e. Provide terminals for individual termination of each signal shield. 28 f. Field wiring shall not be disturbed when removing or replacing an I/O module. 29

4. Discrete I/O modules: 30 a. Interface to ON/OFF devices. 31 b. I/O status indicator on module front. 32 c. Voltage rating to match circuit voltage. 33 d. Output module current rating: 34

1) Match maximum circuit current draw. 35 2) Minimum 1.0 continuous A/point for 120 Vac applications. 36

e. Isolated modules for applications where one (1) module interfaces with devices 37 utilizing different sources of power. 38

5. Discrete outputs shall be fused: 39 a. Provide one (1) fuse per common or per isolated output. 40 b. Provide blown fuse indication. 41 c. External fusing shall be provided if output module does not possess internal fusing. 42 d. Fuses provided external to output model shall: 43

1) Be in accordance with module manufacturer's specifications. 44 2) Be installed at terminal block. 45

6. Analog I/O modules: 46 a. Input modules to accept signals indicated on Drawings or Specifications. 47 b. Minimum 12 bit resolution. 48 c. I/O chassis supplied power for powering connected field devices. 49 d. Differential inputs and outputs. 50 e. User configurable for desired fault-response state. 51 f. Provide output signals as indicated on Drawings and Specifications. 52 g. Individual D/A converter for each output module. 53 h. Individual A/D converter for each input module. 54

Page 165: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 5

C. Power Supply Units: 1 1. Provide regulated power units: 2

a. Designed to operate with PLC system and shall provide power to: 3 1) All components of PLC system. 4 2) All two-wire field instruments. 5 3) Other devices as indicated on Drawings or Specifications. 6

b. Capable of supplying PLC system when all of the specified spare capacity is utilized. 7 c. Each power supply shall be sized such that it will carry no more than 75 percent of 8

capacity under normal loads. 9 2. Electrical service to PLC system is 105 to 125 V, 60 Hz, +1 percent, 1 PH power. 10 3. Separate AC circuit breakers shall be provided for each power supply. 11 4. If the PLC system is field expandable beyond the specified spare capacity, and if such 12

expansion requires power supply modification, note such requirements in the submittals and 13 allow room for power supply modification in the PLC system enclosure. 14

5. Power distribution: 15 a. Immune to transients and surges resultant from noisy environment. 16 b. Shall provide constant voltage level DC distribution to all devices. 17

6. Provide uninterruptible power supply (UPS) in accordance with Section 13446 to sustain 18 full power to UPS powered loads listed below for a minimum of 15minutes following loss 19 of primary power and to ensure that the transient power surges and dips do not affect the 20 operation of the PLC system. 21 a. UPS powered loads: 22

1) All rack mounted PLC components. 23 2) Local operator consoles. 24 3) All power supplies furnished with the PLC and associated loads. 25

D. PLC System Enclosure: 26 1. In accordance with Section 13448. 27 2. Component placement: 28

a. Mount all controller components vertically within the enclosure to allow maximum 29 convection cooling. 30

b. Either install power supplies above all other equipment with at least 10 IN of clearance 31 between the power supply and the enclosure top, or adjacent to other components, but 32 with sufficient spacing for circulation of cooling air. 33

c. Do not place I/O racks directly above the CPU or power supply. 34 d. Locate incoming line devices (isolation or constant voltage transformers, local power 35

disconnects, surge suppressors, etc.) so as to keep power wire runs within an enclosure 36 as short as possible. 37

e. If items such as magnetic starters, contactors, relays, and other electromagnetic devices 38 must be located within the same enclosure as the PLC system components, place a 39 barrier with at least 6 IN of separation between the magnetic area and the control area. 40

f. Place circulating fans close to major heat generating devices. 41 g. Segregate input/output modules into groups of identical type. 42

3. Wiring and grounding to be in accordance with Section 13448. 43 4. Termination requirements: 44

a. In accordance with Section 13448. 45 b. Make connections to I/O subsystem by terminating all field wiring on terminal blocks 46

within the enclosure. 47 c. Prewire I/O modules to terminal blocks. 48 d. Size terminals to accommodate all active database points and spares. 49 e. Provide terminals for individual termination of each signal shield. 50 f. Field wiring shall not be disturbed when removing or replacing an I/O module. 51

E. PLC System Software and Programming: 52 1. Provide all hardware and programming required to provide communication between the 53

PLC and the man-machine interface. 54

Page 166: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 6

2. Provide programming to accomplish all control and monitoring requirements of the 1 Drawings and Specifications. 2

3. Provide two (2) copies of control logic program on 3-1/2 IN disks or on CD. 3 4. Full documentation capability. 4

a. Provide description for each rung. 5 5. On/off line programming. 6

2.4 ACCESSORIES 7

A. Provide all accessories required to furnish a complete PLC control system to accomplish the 8 requirements of the Drawings and Specifications. 9

2.5 SOURCE QUALITY CONTROL 10

A. Provide a performance test after factory completion and prior to shipment. 11 1. Conduct a test where the system is operated continuously and checked for correct operation 12

including loop controls, displays, printing, keyboard functions, alarm responses, and on/off 13 sequencing control. 14

2. Conduct testing with dummy I/Os to verify each control loop operation. 15 3. Allow for Owner and Engineer representatives to witness testing program. 16

a. Provide minimum of 15 days notice prior to testing. 17 4. Do not ship prior to successful completion of this testing program. 18

2.6 MAINTENANCE MATERIALS 19

A. Furnish Owner with the following extra materials: 20 1. One (1) spare I/O card of each card type for every 10 cards or fraction thereof installed. 21

PART 3 - EXECUTION 22

3.1 INSTALLATION 23

A. Install PLC control system in accordance with manufacturer's written instructions. 24

3.2 FIELD QUALITY CONTROL 25

A. Employ and pay for services of equipment manufacturer's field service representative(s) to: 26 1. Inspect equipment covered by these Specifications. 27 2. Supervise adjustments and installation checks. 28 3. Maintain and submit an accurate daily or weekly log of all commissioning functions. 29

a. All commissioning functions may be witnessed by the Engineer. 30 b. All reports shall be cosigned by the Contractor and the Engineer if witnessed. 31

4. Conduct startup of equipment and perform operational checks. 32 5. Provide Owner with a written statement that manufacturer's equipment has been installed 33

properly, started up, and is ready for operation by Owner's personnel. 34

3.3 DEMONSTRATION 35

A. Demonstrate system in accordance with Section 01650. 36

B. On-Site Training: 37 1. Provide employee of the manufacturer or certified representative to provide one (1) day of 38

operation and maintenance training at the Project site after the system has successfully 39 undergone all field testing and acceptance procedures. 40 a. As a minimum, training shall cover: 41

1) Hardware overview. 42 2) Software overview. 43 3) Maintenance. 44 4) Trouble shooting. 45

Page 167: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 7

5) Operation, e.g., changing set points, passwords, etc. 1

3.4 PLC I/O POINTS LIST 2

3 4 ANALOG INPUTS – COLLECTOR WELL PLC 5 No. TAG DESCRIPTION FROM

1. FI-01 CWP-01 discharge flow rate FIT-01 2. SI-01 CWP-01 pump speed VFD 3. FI-02 CWP-02 discharge flow rate FIT-02 4. SI-02 CWP-02 pump speed VFD 5. FI-03 CWP-03 discharge flow rate FIT-03 6. SI-03 CWP-03 pump speed VFD 7. FI-04 Future CWP-04 discharge flow rate Future FIT-04 8. SI-04 Future CWP-04 pump speed Future VFD 9. PI-05 Collector Well Pump discharge pressure PIT-05 10. LI-06 Collector Well level LT-06

6 7 ANALOG OUTPUTS – COLLECTOR WELL PLC 8 No. TAG DESCRIPTION TO 1. FIC-01/SIC-01 CWP-01 pump speed control VFD 2. FIC-02/SIC-02 CWP-02 pump speed control VFD 3. FIC-03/SIC-03 CWP-03 pump speed control VFD 4. FIC-04/SIC-04 Future CWP-04 pump speed control Future VFD

9 10 DISCRETE INPUTS – COLLECTOR WELL PLC 11 No. TAG DESCRIPTION FROM 1. KI-01 CWP-01 in pre-lube time sequence VFD 2. PAH-01 CWP-01 discharge high pressure alarm VFD 3. TAHH-01 CWP-01 motor temperature high-high VFD 4. XA-01B CWP-01 VFD Fault VFD 5. YI-01 CWP-01 run status VFD 6. ZCI-01 CWP-01 discharge valve closed status VFD 7. ZI-01 CWP-01 in Remote mode VFD 8. KI-02 CWP-02 in pre-lube time sequence VFD 9. PAH-02 CWP-02 discharge high pressure alarm VFD 10. TAHH-02 CWP-02 motor temperature high-high VFD 11. XA-02B CWP-02 VFD Fault VFD 12. YI-02 CWP-02 run status VFD 13. ZCI-02 CWP-02 discharge valve closed status VFD 14. ZI-02 CWP-02 in Remote mode VFD 15. KI-03 CWP-03 in pre-lube time sequence VFD 16. PAH-03 CWP-03 discharge high pressure alarm VFD 17. TAHH-03 CWP-03 motor temperature high-high VFD 18. XA-03B CWP-03 VFD Fault VFD 19. YI-03 CWP-03 run status VFD 20. ZCI-03 CWP-03 discharge valve closed status VFD 21. ZI-03 CWP-03 in Remote mode VFD 22. KI-04 Future CWP-04 in pre-lube time sequence Future VFD 23. PAH-04 Future CWP-04 discharge high pressure alarm Future VFD 24. TAHH-04 Future CWP-04 motor temperature high-high Future VFD 25. XA-04B Future CWP-04 VFD Fault Future VFD

Page 168: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PROGRAMMABLE LOGIC CONTROLLER (PLC) CONTROL SYSTEM 13500 - 8

No. TAG DESCRIPTION FROM 26. YI-04 Future CWP-04 run status Future VFD 27. ZCI-04 Future CWP-04 discharge valve closed status Future VFD 28. ZI-04 Future CWP-04 in Remote mode Future VFD 29. XA-07A PLC Control Panel UPS trouble alarm UPS in Control

Panel 30. XA-07B PLC Control Panel UPS on battery UPS in Control

Panel 31. XA-08 Switchgear MSB-01 surge protection device alarm Switchgear MSB-01 32. XA-09 Collector Well smoke detected Smoke detector 33. ZA-50 Door intrusion alarm ZS-50 34. HS-50 Door intrusion alarm bypass HS-50 35. ZA-51 North roof hatch intrusion alarm ZS-51 36. ZA-52 South roof hatch intrusion alarm ZS-52 37. ZA-53 Valve level hatch intrusion alarm ZS-53

1 2 DISCRETE OUTPUTS – COLLECTOR WELL PLC 3 No. TAG DESCRIPTION TO 1. HS-01 CWP-01 start/stop control VFD 2. HS-02 CWP-02 start/stop control VFD 3. HS-03 CWP-03 start/stop control VFD 4. HS-04 Future CWP-04 start/stop control Future VFD

4 5 DISCRETE INPUTS – REMOTE I/O PANEL 6 No. TAG DESCRIPTION FROM 1. YI-10 Generator run status Generator CP 2. XA-10A Generator trouble alarm Generator CP 3. XA-10B Generator fail alarm Generator CP 4. LAL-10 Generator low fuel alarm Generator CP 5. ZI-11A Collector Well on Utility Power (Main Utility

Breaker closed) Switchgear PDP01

6. ZI-11B Collector Well on Generator Power (Generator Breaker closed)

Switchgear PDP01

7. XA-11 Switchgear surge protection device alarm Switchgear PDP01 8. XA-12A Remote I/O Panel UPS trouble alarm UPS in Remote I/O

Panel 9. XA-12B Remote I/O Panel UPS on battery UPS in Remote I/O

Panel

END OF SECTION 7

Page 169: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - COMPUTER NETWORK AND HUMAN MACHINE INTERFACE (HMI) HARDWARE 13502 - 1

2014/08/28 1

SECTION 13502 2

COMPUTER NETWORK AND HUMAN MACHINE INTERFACE (HMI) HARDWARE 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Computer network and HMI hardware requirements which includes but is not necessarily 7

limited to: 8 a. Panel mounted OIT (Operator Interface Terminals). 9 b. Ethernet switches. 10 c. Software. 11 d. Accessories and maintenance materials. 12

B. Related Specification Sections include but are not necessarily limited to: 13 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 14 2. Division 01 - General Requirements. 15 3. Section 13440 - Instrumentation for Process Control: Basic Requirements. 16

1.2 DEFINITIONS 17

A. OIT: Operator Interface Terminal. 18

B. SNMP: Simple Network Management Protocol, a set of protocols for managing complex 19 networks. 20

1.3 SUBMITTALS 21

A. Shop Drawings: 22 1. See Specification Section 01340 for requirements for the mechanics and administration of 23

the submittal process. 24 2. See Specification Section 13440. 25 3. Product technical data including: 26

a. Acknowledgement that products submitted meet requirements of standards referenced. 27

B. Operation and Maintenance Manuals: 28 1. See Specification Section 01342 for requirements for: 29

a. The mechanics and administration of the submittal process. 30 b. The content of Operation and Maintenance Manuals. 31

PART 2 - PRODUCTS 32

2.1 ACCEPTABLE MANUFACTURERS 33

A. Subject to compliance with the Contract Documents, the manufacturers listed within the 34 following Articles are acceptable. 35

B. Submit request for substitution in accordance with Specification Section 01640. 36

2.2 PANEL MOUNTED OPERATOR INTERFACE PANELS (OIT) 37

A. Acceptable Manufacturers: Allen-Bradley Panel View Plus 6. 38

B. Design and Fabrication: 39 1. Display: color graphics. 40

Page 170: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - COMPUTER NETWORK AND HUMAN MACHINE INTERFACE (HMI) HARDWARE 13502 - 2

2. Touch screen. 1 3. Communicate via Ethernet to PLC. 2 4. Provide password protection to prevent unauthorized entries for a minimum of two (2) 3

levels: 4 a. Authorization to operate. 5 b. Authorization to adjust setpoints. 6

5. Operating temperature: 32 DegF to 131 DegF. 7 6. Humidity: 10 to 90 percent RH non-condensing. 8

C. Configuration software: 9 1. Utilize Factory Talk View Studio Machine Edition. 10

D. Schedule: 11 1. Provide flat face panels on the face of each of the following control panels. 12

13 LOCATION SIZE, INCHES Collector Well PLC Panel 15

14

2.3 ETHERNET SWITCHES 15

A. Acceptable Manufacturers: 16 1. Hirschmann. 17 2. Siemens. 18 3. N-TRON. 19 4. Allen-Bradley/Cisco. 20 5. SixNet. 21

B. Managed Ethernet Switches: 22 1. Design and fabrication: 23

a. Support Ethernet 100 MBit/s. 24 b. Provide fiber port where required to communicate via fiber optic cable. 25 c. Support SNMP and Web based management. 26 d. Rapid Spanning Tree Protocol. 27 e. IGMP (Internet Group Management Protocol) support for IP multicast filtering to 28

enable switches to automatically route messages only to appropriate ports. 29 f. 10/100 MBit/s twisted pair ports (RJ45) as required for communication with devices as 30

depicted in the Contract Documents. 31 g. Check all received data for validity. 32

1) Discard invalid and defective frames or fragments. 33 h. As applicable, meet requirements of IEEE 802.3. 34 i. Provide LED status lights to indicate: 35

1) Power: Supply voltage present. 36 2) Fault. 37 3) Port status. 38

j. Environmental rating: 39 1) Operating temperature: 32 Deg F to 122 Deg F. 40 2) Humidity: 95 percent relative humidity, non-condensing. 41

C. Fiber Interconnect Panel: 42 1. Acceptable Manufacturers: 43

a. Corning. 44 b. Or Equal. 45

2. Design and fabrication: 46 a. Furnish LC style multi mode adapter for each port. 47 b. Adapter panels shall snap-in for easy installation, removal, and expansion. 48 c. Open access with single door and latch. 49

Page 171: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - COMPUTER NETWORK AND HUMAN MACHINE INTERFACE (HMI) HARDWARE 13502 - 3

d. Complete internal cable management with designation lables for proper cable 1 administration. 2

e. Provide easy access for installer to terminate cables. 3

2.4 SOFTWARE 4

A. Provide all software and associated programming/configuration required to meet performance 5 requirements of the Contract Documents. 6 1. At substantial completion of the Project: 7

a. Turn current licenses for all software over to the Owner in the Owner's name and install 8 the latest version, upgrade or service pack for all software. 9

B. All software must be latest edition and licensed to the Owner. 10

2.5 ACCESSORIES AND MAINTENANCE MATERIALS 11

A. Provide all accessories required to furnish a complete computer-based network for the control 12 system to accomplish the requirements of the Drawings and Specifications. 13

PART 3 - EXECUTION 14

3.1 DEMONSTRATION 15

A. Demonstrate system in accordance with Specification Section 01650. 16

3.2 INSTALLATION AND CHECKOUT 17

A. Provide installation and checkout in accordance with Specification Section 13440. 18

END OF SECTION 19

20

Page 172: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - COMPUTER NETWORK AND HUMAN MACHINE INTERFACE (HMI) HARDWARE 13502 - 4

1

Page 173: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND REPORTS 13504 - 1

2014/08/14 1

SECTION 13504 2

CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND 3 REPORTS 4

PART 1 - GENERAL 5

1.1 SUMMARY 6

A. Section Includes: 7 1. Configuration requirements for HMI and reports which includes but is not necessarily 8

limited to. 9 a. Specific software functional descriptions. 10 b. Graphics requirements. 11 c. HMI functionality requirements. 12 d. Plant overview screens. 13 e. Process overview screens. 14 f. Detail displays. 15 g. Trend displays. 16 h. PLC hardware/HMI status screen. 17 i. Alarm monitoring. 18 j. Report generation. 19 k. Configuration standards and conventions. 20 l. Screen configuration review meetings. 21 m. Report configuration review meetings. 22 n. Coordination. 23

B. Related Specification Sections include but are not necessarily limited to: 24 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 25 2. Division 01 - General Requirements. 26 3. Section 13440 - Instrumentation for Process Control: Basic Requirements. 27

1.2 QUALITY ASSURANCE 28

A. Qualifications: 29 1. Programmer(s) shall have had experience in software configuration and installation for at 30

least two (2) projects of similar size and complexity. 31

1.3 DEFINITIONS 32

A. HMI: Human Machine Interface. 33

B. I/O: Input/Output. 34

C. OLE: Object Linking and Embedding, a document standard developed by Microsoft that 35 enables the creation of an object with one application and the linking or embedding of the object 36 in a second application. 37

D. OPC: "OLE for Process Control"; a software standard utilizing a client/server model that makes 38 interoperability possible between automation/control applications and field systems/devices. 39

E. PC: Personal Computer. 40

F. PLC: Programmable Logic Controller. 41

Page 174: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND REPORTS 13504 - 2

1.4 SUBMITTALS 1

A. Shop Drawings: 2 1. See Specification Section 01340 for requirements for the mechanics and administration of 3

the submittal process. 4 2. See Specification Section 13440. 5 3. Software Configuration Standards and Conventions document. 6 4. Graphic screen displays; provide in actual colors utilized. 7 5. Sample reports. 8 6. Certifications: 9

a. Qualifications of programmer(s). 10

B. Operation and Maintenance Manuals: 11 1. See Specification Section 01342 for requirements for: 12

a. The mechanics and administration of the submittal process. 13 b. The content of Operation and Maintenance Manuals. 14

2. Software Configuration Standards and Conventions - final version. 15

C. Informational Submittals: 16 1. Results of factory testing procedures. 17 2. Proposed training agendas and schedule. 18

1.5 GENERAL FUNCTIONAL REQUIREMENTS 19

A. Software Functional Requirements: 20 1. General functional requirements for system configuration are indicated on the Drawings and 21

described in the Specifications. 22 2. The information presented herein and indicated on the Drawings illustrates the general 23

functional intent of the system and may not be sufficient to fully configure the system. 24 3. The Contractor is responsible for determining what additional information may be required 25

to complete the configuration tasks, and for obtaining this information from the Owner. 26

B. Available Process Values: 27 1. All process alarm, equipment status, and process variable values shall be available at any 28

HMI. 29 2. If communications to a particular I/O point has failed for any reason, then wherever that 30

data is displayed, the software shall post a visual indication that the point is not valid. 31

C. Provide comprehensive on-line help for all development functions. 32

D. Manual Entry of Data: 33 1. All PC-based HMIs must allow manual entry of surrogate data and other variables, which 34

must then be available for display and use in reports. 35 a. Operator-entered commands from any of the operator workstations must be logged by 36

the computer servers. 37

E. System Failure: 38 1. Failure of any PLC, remote I/O hardware, or network communication link must be 39

individually alarmed at HMIs. 40 2. Unless otherwise specified, each alarm must be specific to a single point of failure. 41

F. All process related functions, calculations, timers, and numeric manipulations, shall be 42 accomplished in the PLC hardware and not in the HMI. 43 1. The HMI shall function as a monitoring system, not as a process controller. 44 2. The HMI shall transfer data to the PLC system and the PLC system shall perform all control 45

algorithms. 46

Page 175: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND REPORTS 13504 - 3

1.6 SECURITY 1

A. Fully integrate security into the SCADA system to allow only users with appropriate security 2 levels access to individual parts of the system. 3

PART 2 - PRODUCTS 4

2.1 SPECIFIC SOFTWARE FUNCTIONAL DESCRIPTIONS 5

A. Specific functional requirements for various software control blocks within the computer system 6 are as follows. 7

B. Descriptions are general and are not intended to fully indicate the complete functionality of the 8 system. 9 1. Monitoring of process values: 10

a. Process values derived from analog process variable signals must be historically 11 archived. 12 1) Store all historical data with time and date of occurrence. 13 2) Make values available for use in reports. 14 3) Assign high and low alarms to process values as defined below and otherwise 15

deemed appropriate. 16 b. Provide capability for computer server(s) to retrieve real-time values from the PLC 17

system at adjustable time periods. 18 c. Alarm limits: 19

1) Set per direction from the Owner. 20 2) An operator having proper security authorization must be able to enable, disable, 21

and adjust the setpoint of any individual alarm. 22

C. Utilize graphic screen displays at the OIT and HMI(s) to provide monitoring and control 23 functionality. 24 1. Hierarchy of HMI screens is in descending order as follows: 25

a. Plant overview screen(s). 26 b. Process overview screens. 27 c. Process screens. 28 d. Pop-up/control screens. 29

D. OIT and HMI operator interface functionality shall include: 30 1. Indication of process variables. 31 2. Configuration of control loop parameters (e.g., setpoints, gains, etc.). 32 3. Adjustment of controller output. 33 4. Display of real time and historical process trends. 34 5. Selector switch and pushbutton station controls. 35 6. System and process status indicators. 36 7. Graphic representation of plant operations with interactive status and measurement symbols. 37 8. Annunciation. 38

E. Graphics: 39 1. Match the existing graphic screen format, functionality, and appearance to the maximum 40

extent practical. 41 2. Utilize dynamic variables with unique tags per graphic. 42 3. All monitored and or controlled process equipment shall be animated or color-highlighted to 43

indicate status changes. 44

F. Trend Displays: 45 1. Real time historical trend displays. 46 2. Real time on-line trend displays. 47 3. Capable of displaying multiple points per display. 48 4. Operator shall be able to select any desired sample time interval. 49

Page 176: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND REPORTS 13504 - 4

5. Provide flexibility and easy access to real time and historical trend information for any 1 variable TAG defined within the SCADA application. 2

G. PLC Hardware/HMI Status Screen: 3 1. Provide a status screen to depict status conditions and diagnostic information for all major 4

networked equipment. 5 2. Depict communication status for all networked communicating devices, such as PLC 6

processors, Ethernet switches, PCs, and radios. 7

H. Alarm Monitoring: 8 1. Provide standard alarm screen functionality to ensure flexibility and quick access to live 9

alarms, alarm history and alarm grouping parameters. 10 2. Analog alarms: 11

a. The SCADA software shall monitor analog and discrete variables and calculated 12 conditions, and determine if the variable is in an alarm condition. 13

b. For each Analog Tag, an alarm for each of the following conditions shall be assignable: 14 1) Low-low. 15 2) Low. 16 3) High. 17 4) High-high. 18 5) Deviation low. 19 6) Deviation high. 20 7) Rate of change. 21

c. Provide adjustable dead bands and delay timers for all analog alarms. 22 3. Present alarms in order of: 23

a. Priority. 24 b. Time of occurrence. 25 c. Non-acknowledged presented ahead of acknowledged. 26

4. Utilize single keystroke or pushbutton to: 27 a. Acknowledge alarms. 28

5. Alarm list presented to operator shall include: 29 a. Time of occurrence. 30 b. Time of acknowledgement. 31 c. Description. 32 d. Acknowledgement status. 33

2.2 SOURCE QUALITY CONTROL 34

A. Include performance test of OIT software in factory with the overall PLC System test. 35 1. Conduct a test where the system is operated continuously and checked for correct operation 36

including loop controls, displays, printing, keyboard functions, alarm responses, and on/off 37 sequencing control. 38

2. Allow for Owner and Engineer representatives to witness testing program. 39 a. Provide minimum of 15 days notice prior to testing. 40

PART 3 - EXECUTION 41

3.1 CONFIGURATION REQUIREMENTS 42

A. Provide all programming and configuration required for all HMIs furnished under this Contract: 43

3.2 CONFIGURATION STANDARDS AND CONVENTIONS 44

A. Prepare and submit a "Software Configuration Standards and Conventions." 45 1. Submit for review and approval prior to commencing with software configuration. 46 2. Describe and define such items as: 47

a. Proposed graphic display process colors/representations. 48

Page 177: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND REPORTS 13504 - 5

b. Color standards for "ON," "OFF," and "ALARM" conditions. 1 c. Font type and size. 2 d. Alarm handling conventions. 3 e. Methods for navigation between displays. 4 f. Address usage/naming conventions. 5 g. Security setup. 6

3. Prior to submitting the initial draft document, the Contractor must meet with the Owner to 7 review any of the Owner’s existing standards and conventions. 8

4. In addition to submitting the initial document for review, submit an updated version of the 9 document as part of the Operation and Maintenance Manuals. 10 a. Revise this document to include any additional standards that are established 11

throughout the configuration process. 12

3.3 SCREEN CONFIGURATION REVIEW MEETINGS 13

A. Conduct a minimum of one configuration conference with the Owner to review and discuss 14 system configuration programming and related topics. 15 1. The purpose of the conference will be to discuss, in detail, how each I/O point will be 16

handled and the types, quantities, hierarchies, and functioning of display screens. 17 2. Review of the Owner’s existing systems, standards, conventions, file and tag naming 18

requirements, font type and size requirements, and reporting requirements must be part of 19 each conference. 20

3. Review the navigation bar to be utilized. 21 4. Conferences will be held at the Water Treatment Plant. 22 5. Each screen will be reviewed at each conference. 23

a. If required, to review all screens, each conference will occur on multiple days. 24 6. Submit five (5) color copies of printed screens via shop drawing submittal process 10 25

calendar days before each conference. 26 7. Bring equipment to project screens on wall or provide multiple monitors for viewing by 27

attendees. 28

B. Proposed graphic screens and report formats must be reviewed with the Owner throughout the 29 configuration process. 30

3.4 FIELD QUALITY CONTROL 31

A. Employ and pay for services of equipment manufacturer's field service representative(s) to: 32 1. Inspect equipment covered by this Specification Section. 33 2. Supervise adjustments and installation checks. 34 3. Maintain and submit an accurate daily or weekly log of all commissioning functions. 35

a. All commissioning functions may be witnessed by the Engineer. 36 b. All reports shall be cosigned by the Contractor and the Engineer if witnessed. 37

4. Conduct startup of equipment and perform operational checks. 38 5. Provide Owner with a written statement that manufacturer's equipment has been installed 39

properly, started up, and is ready for operation by Owner's personnel. 40

3.5 DEMONSTRATION 41

A. Demonstrate system in accordance with Specification Section 01650. 42

END OF SECTION 43

44

Page 178: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONFIGURATION REQUIREMENTS: HUMAN MACHINE INTERFACE (HMI) AND REPORTS 13504 - 6

1

Page 179: City of Yankton, SD

D I V I S I O N 1 5 MECHANICAL

Page 180: City of Yankton, SD
Page 181: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 1

2014/10/07 1

SECTION 15060 2

PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Process piping systems. 7 2. Utility piping systems. 8 3. Plumbing piping systems. 9

B. Related Specification Sections include but are not necessarily limited to: 10 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 11 2. Division 01 - General Requirements. 12 3. Section 02221 - Trenching, Backfilling, and Compacting for Utilities. 13 4. Section 09905 - Painting and Protective Coatings. 14 5. Section 10400 - Identification Devices. 15 6. Section 11005 - Equipment: Basic Requirements. 16 7. Section 13442 - Primary Elements and Transmitters. 17 8. Section 15090 - Pipe Support Systems. 18 9. Section 15100 - Valves: Basic Requirements. 19 10. Section 15183 - Pipe, Duct and Equipment Insulation. 20

1.2 QUALITY ASSURANCE 21

A. Referenced Standards: 22 1. American Association of State Highway and Transportation Officials (AASHTO): 23

a. M36, Corrugated Steel Pipe, Metallic-Coated, for Sewers and Drains (Equivalent 24 ASTM A760). 25

b. M190, Standard Specification for Bituminous Coated Corrugated Metal Culvert Pipe 26 and Pipe Arches. 27

c. M252, Standard Specification for Corrugated Polyethylene Drainage Tubing. 28 d. M294, Interim Specification for Corrugated Polyethylene Pipe 12 to 24 Inch Diameter. 29

2. American Iron and Steel Institute (AISI). 30 3. American Society of Mechanical Engineers (ASME): 31

a. B16.3, Malleable Iron Threaded Fittings. 32 b. B16.5, Pipe Flanges and Flanged Fittings. 33 c. B16.9, Factory-Made Wrought Steel Butt-Welding Fittings. 34 d. B16.22, Wrought Copper and Bronze Solder - Joint Pressure Fittings. 35 e. B16.26, Cast Copper Alloy Fittings for Flared Copper Tubes. 36 f. B36.19, Stainless Steel Pipe. 37 g. B40.100, Pressure Gauges and Gauge Attachments. 38

4. ASTM International (ASTM): 39 a. A53, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, 40

Welded and Seamless. 41 b. A74, Standard Specification for Cast Iron Soil Pipe and Fittings. 42 c. A106, Standard Specification for Seamless Carbon Steel Pipe for High-Temperature 43

Service. 44 d. A126, Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe 45

Fittings. 46 e. A182, Standard Specification for Forged or Rolled Alloy-Steel Pipe Flanges, Forged 47

Fittings, and Valves and Parts for High-Temperature Service. 48 f. A197, Standard Specification for Cupola Malleable Iron. 49

Page 182: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 2

g. A234, Standard Specification for Pipe Fittings of Wrought Carbon Steel and Alloy 1 Steel for Moderate and High Temperature Service. 2

h. A269, Standard Specification for Seamless and Welded Austenitic Stainless Steel 3 Tubing for General Service. 4

i. A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked 5 Austenitic Stainless Steel Pipes. 6

j. A518, Standard Specification for Corrosion-Resistant High-Silicon Iron Castings. 7 k. A536, Standard Specification for Ductile Iron Castings. 8 l. A587, Standard Specification for Electric-Resistance-Welded Low-Carbon Steel Pipe 9

for the Chemical Industry. 10 m. A760, Standard Specification for Corrugated Steel Pipe, Metallic-Coated for Sewers 11

and Drains. 12 n. A774, Standard Specification for As-Welded Wrought Austenitic Stainless Steel 13

Fittings for General Corrosive Service at Low and Moderate Temperatures. 14 o. A778, Standard Specification for Welded, Unannealed Austenitic Stainless Steel 15

Tubular Products. 16 p. B88, Standard Specification for Seamless Copper Water Tube. 17 q. C14, Standard Specification for Concrete Sewer, Storm Drain, and Culvert Pipe. 18 r. C76, Standard Specification for Reinforced Concrete Culvert, Storm Drain, and Sewer 19

Pipe. 20 s. C425, Standard Specification for Compression Joints for Vitrified Clay Pipe and 21

Fittings. 22 t. C443, Standard Specification for Joints for Concrete Pipe and Manholes, Using Rubber 23

Gaskets. 24 u. C564, Standard Specification for Rubber Gaskets for Cast Iron Soil Pipe and Fittings. 25 v. C700, Standard Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength 26

and Perforated. 27 w. D1785, Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe, Schedules 28

40, 80, and 120. 29 x. D2466, Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, 30

Schedule 40. 31 y. D2467, Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, 32

Schedule 80. 33 z. D4101, Standard Specification for Polypropylene Plastic Injection and Extrusion 34

Materials. 35 aa. F439, Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic Pipe 36

Fittings, Schedule 80. 37 bb. F441, Standard Specification for Chlorinated Poly(Vinyl Chloride) (CPVC) Plastic 38

Pipe, Schedules 40 and 80. 39 5. American Water Works Association (AWWA): 40

a. B300, Standard for Hypochlorites. 41 b. C200, Standard for Steel Water Pipe - 6 IN and Larger. 42 c. C207, Standard for Steel Pipe Flanges for Waterworks Service - Sizes 4 IN through 144 43

IN. 44 d. C208, Standard for Dimensions for Fabricated Steel Water Pipe Fittings. 45 e. C606, Standard for Grooved and Shouldered Joints. 46 f. C651, Standard for Disinfecting Water Mains. 47 g. C800, Standard for Underground Service Line Valves and Fittings. 48

6. American Water Works Association/American National Standards Institute 49 (AWWA/ANSI): 50 a. C110/A21.10, Standard for Ductile-Iron and Gray-Iron Fittings. 51 b. C111/A21.11, Standard for Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and 52

Fittings. 53 c. C115/A21.15, Standard for Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron 54

Threaded Flanges. 55 d. C151/A21.51, Standard for Ductile-Iron Pipe, Centrifugally Cast, for Water. 56

Page 183: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 3

e. C153/A21.53, Standard for Ductile-Iron Compact Fittings for Water Service. 1 7. Chlorine Institute, Inc. (CI): 2

a. Pamphlet 6, Piping Systems for Dry Chlorine. 3 8. Cast Iron Soil Pipe Institute (CISPI): 4

a. 301, Standard Specification for Hubless Cast Iron Soil Pipe and Fittings for Sanitary 5 and Storm Drain, Waste, and Vent Piping Applications. 6

9. International Plumbing Code (IPC). 7 10. National Fire Protection Association (NFPA): 8

a. 54, National Fuel Gas Code. 9 b. 69, Standard on Explosion Prevention Systems. 10

11. Underwriters Laboratories, Inc. (UL). 11

B. Coordinate flange dimensions and drillings between piping, valves, and equipment. 12

1.3 SYSTEM DESCRIPTION 13

A. Piping Systems Organization and Definition: 14 1. Piping services are grouped into designated systems according to the chemical and physical 15

properties of the fluid conveyed, system pressure, piping size and system materials of 16 construction. 17

2. See PIPING SPECIFICATION SCHEDULES in PART 3. 18 3. The table below identifies each service classification, its symbol, the designated system 19

number for each service, and when the installation of a tracer wire is required: 20 21

SYSTEM SYMBOL SYSTEM NO. TRACER WIRE

Raw Water Transmission Main Piping RWTM 2

Collector Well Pump Discharge CWPDIS 2

Condenser Water Supply CWS 6

Condenser Water Return CWR 6

Raw Water Supply RWS 6

Raw Water Return RWR 6

Pre-Lube PL 7

Air Release/Vacuum Valve Vent ARVV 7

Vent V 7

22

1.4 SUBMITTALS 23

A. Shop Drawings: 24 1. See Specification Section 01340 for requirements for the mechanics and administration of 25

the submittal process. 26 2. Product technical data including: 27

a. Acknowledgement that products submitted meet requirements of standards referenced. 28 b. Copies of manufacturer's written directions regarding material handling, delivery, 29

storage and installation. 30 c. Separate schedule sheet for each piping system scheduled in this Specification Section 31

showing compliance of all system components. 32 1) Attach technical product data on gaskets, pipe, fittings, and other components. 33

Page 184: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 4

3. Fabrication and/or layout Drawings: 1 a. Exterior yard piping Drawings (minimum scale 1 IN equals 10 FT) with information 2

including: 3 1) Dimensions of piping lengths. 4 2) Invert or centerline elevations of piping crossings. 5 3) Acknowledgement of bury depth requirements. 6 4) Details of fittings, tapping locations, thrust blocks, restrained joint segments, 7

harnessed joint segments, hydrants, and related appurtenances. 8 5) Acknowledge designated valve or gate tag numbers, manhole numbers, instrument 9

tag numbers, pipe and line numbers. 10 6) Line slopes and vents. 11

b. Interior piping Drawings (minimum scale 1/8 IN equals 1 FT) with information 12 including: 13 1) Dimensions of piping from column lines or wall surfaces. 14 2) Centerline dimensions of piping. 15 3) Centerline elevation and size of intersecting ductwork, conduit/conduit racks, or 16

other potential interferences requiring coordination. 17 4) Location and type of pipe supports and anchors. 18 5) Locations of valves and valve actuator type. 19 6) Details of fittings, tapping locations, equipment connections, flexible expansion 20

joints, connections to equipment, and related appurtenances. 21 7) Acknowledgement of valve, equipment and instrument tag numbers. 22 8) Provisions for expansion and contraction. 23 9) Line slopes and air release vents. 24 10) Rough-in data for plumbing fixtures. 25

c. Schedule of interconnections to existing piping and method of connection. 26

B. Operation and Maintenance Manuals: 27 1. See Specification Section 01342 for requirements for: 28

a. The mechanics and administration of the submittal process. 29 b. The content of Operation and Maintenance Manuals. 30

C. Informational Submittals: 31 1. Qualifications of lab performing disinfection analysis on water systems. 32 2. Test reports: 33

a. Copies of pressure test results on all piping systems. 34 b. Reports defining results of dielectric testing and corrective action taken. 35 c. Disinfection test report. 36 d. Notification of time and date of piping pressure tests. 37

1.5 DELIVERY, STORAGE, AND HANDLING 38

A. Protect pipe coating during handling using methods recommended by manufacturer. 39 1. Use of bare cables, chains, hooks, metal bars or narrow skids in contact with coated pipe is 40

not permitted. 41

B. Prevent Damage to Pipe During Transit. 42 1. Repair abrasions, scars, and blemishes. 43 2. If repair of satisfactory quality cannot be achieved, replace damaged material immediately. 44

PART 2 - PRODUCTS 45

2.1 ACCEPTABLE MANUFACTURERS 46

A. Subject to compliance with the Contract Documents, the following manufacturers are 47 acceptable: 48 1. Insulating unions: 49

a. "Dielectric" by Epco. 50

Page 185: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 5

b. Central. 1 2. Dirt strainers (Y type): 2

a. Mueller (#351). 3 b. Sarco. 4 c. Armstrong. 5

3. Chemical strainers (Y type): 6 a. Chemtrol. 7 b. Asahi. 8

4. Dry disconnect couplings: 9 a. Kamlock. 10

5. Dielectric flange kit: 11 a. PSI. 12 b. Maloney. 13 c. Central Plastics. 14

6. Pipe saddles (for gage installation): 15 a. Dresser Style 91 (steel and ductile iron systems). 16 b. Dresser Style 194 (nonmetallic systems). 17

7. Rubber expansion joints (REJ): 18 a. Mercer Rubber Company. 19 b. Unaflex, Inc. 20

8. Non-shear couplings: 21 a. Power Seal Pipeline Products Corp., Power Steel Model 3541. 22 b. Repair Coupling Fernco, Inc., Strong back RC Series. 23

B. Submit request for substitution in accordance with Specification Section 01640. 24

2.2 PIPING SPECIFICATION SCHEDULES 25

A. Piping system materials, fittings and appurtenances are subject to requirements of specific piping 26 specification schedules located at the end of PART 3 of this Specification Section. 27

2.3 COMPONENTS AND ACCESSORIES 28

A. Insulating Components: 29 1. Dielectric flange kits: 30

a. Flat faced. 31 b. 1/8 IN thick dielectric gasket, phenolic, non-asbestos. 32 c. Suitable for 175 psi, 210 DegF. 33 d. 1/32 IN wall thickness bolt sleeves. 34 e. 1/8 IN thick phenolic insulating washers. 35

2. Dielectric unions: 36 a. Screwed end connections. 37 b. Rated at 175 psi, 210 DegF. 38 c. Provide dielectric gaskets suitable for continuous operation at union rated temperature 39

and pressure. 40

B. Dirt Strainers: 41 1. Y-type. 42 2. Composition bronze. 43 3. Rated for test pressure and temperature of system in which they are installed. 44 4. 20 mesh Monel screen. 45 5. Threaded bronze plug in the blowoff outlet. 46 6. Threaded NPT end connections. 47

C. Reducers: 48 1. Furnish appropriate size reducers and reducing fittings to mate pipe to equipment 49

connections. 50 2. Connection size requirements may change from those shown on Drawings depending on 51

equipment furnished. 52

Page 186: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 6

D. Protective Coating and Lining: 1 1. Include pipe, fittings, and appurtenances where coatings, linings, paint, tests and other items 2

are specified. 3 2. Field paint pipe in accordance with Specification Section 09905. 4

E. Underground Warning Tape: See Specification Section 10400. 5

F. Pressure Gages: 6 1. See Specification Section 11005 and Specification Section 13442. 7

G. Valves: 8 1. See schematics and details for definition of manual valves used in each system under 4 IN 9

in size. 10 a. See Specification Section 15100 schedule for valve types 4 IN and above and for 11

automatic valves used in each system. 12 2. See Specification Section 15100. 13

PART 3 - EXECUTION 14

3.1 EXTERIOR BURIED PIPING INSTALLATION 15

A. Unless otherwise shown on the Drawings, provide a minimum of 7 FT earth cover over exterior 16 buried piping systems and appurtenances conveying water, fluids, or solutions subject to 17 freezing. 18

B. Enter and exit through structure walls, floors, and ceilings by using penetrations and seals 19 specified in Specification Section 01800 and as shown on Drawings. 20

C. When entering or leaving structures with buried mechanical joint piping, install joint within 2 FT 21 of point where pipe enters or leaves structure. 22 1. Install second joint not more than 6 FT nor less than 4 FT from first joint. 23

D. Install expansion devices as necessary to allow expansion and contraction movement. 24

E. Laying Pipe In Trench: 25 1. Excavate and backfill trench in accordance with Specification Section 02221. 26 2. Clean each pipe length thoroughly and inspect for compliance to specifications. 27 3. Grade trench bottom and excavate for pipe bell and lay pipe on trench bottom. 28 4. Install gasket or joint material according to manufacturer's directions after joints have been 29

thoroughly cleaned and examined. 30 5. Except for first two (2) joints, before making final connections of joints, install two (2) full 31

sections of pipe with earth tamped along side of pipe or final with bedding material placed. 32 6. Lay pipe in only suitable weather with good trench conditions. 33

a. Never lay pipe in water except where approved by Engineer. 34 7. Seal open end of line with watertight plug if pipe laying stopped. 35 8. Remove water in trench before removal of plug. 36

F. Lining Up Push-On Joint Piping: 37 1. Lay piping on route lines shown on Drawings. 38 2. Deflect from straight alignments or grades by vertical or horizontal curves or offsets. 39 3. Observe maximum deflection values stated in manufacturer's written literature. 40 4. Provide special bends when specified or where required alignment exceeds allowable 41

deflections stipulated. 42 5. Install shorter lengths of pipe in such length and number that angular deflection of any joint, 43

as represented by specified maximum deflection, is not exceeded. 44

G. Anchorage and Blocking: 45 1. Provide reaction blocking, anchors, joint harnesses, or other acceptable means for 46

preventing movement of piping caused by forces in or on buried piping tees, wye branches, 47 plugs, or bends. 48

Page 187: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 7

2. Place concrete blocking so that it extends from fitting into solid undisturbed earth wall. 1 a. Concrete blocks shall not cover pipe joints. 2

3. Provide bearing area of concrete in accordance with drawing detail. 3

H. Install underground hazard warning tape per Specification Section 10400. 4

I. Install insulating components where dissimilar metals are joined together. 5

3.2 INTERIOR AND EXPOSED EXTERIOR PIPING INSTALLATION 6

A. Install piping in vertical and horizontal alignment as shown on Drawings. 7

B. Alignment of piping smaller than 4 IN may not be shown; however, install according to Drawing 8 intent and with clearance and allowance for: 9 1. Expansion and contraction. 10 2. Operation and access to equipment, doors, windows, hoists, moving equipment. 11 3. Headroom and walking space for working areas and aisles. 12 4. System drainage and air removal. 13

C. Enter and exit through structure walls, floor and ceilings using penetrations and seals specified 14 in Specification Section 01800 and as shown on the Drawings. 15

D. Install vertical piping runs plumb and horizontal piping runs parallel with structure walls. 16

E. Pipe Support: 17 1. Use methods of piping support as shown on Drawings and as required in Specification 18

Section 15090. 19 2. Where pipes run parallel and at same elevation or grade, they may be grouped and 20

supported from common trapeze-type hanger, provided hanger rods are increased in size as 21 specified for total supported weight. 22 a. The pipe in the group requiring the least maximum distance between supports shall set 23

the distance between trapeze hangers. 24 3. Size pipe supports with consideration to specific gravity of liquid being piped. 25

F. Locate and size sleeves and castings required for piping system. 26 1. Arrange for chases, recesses, inserts or anchors at proper elevation and location. 27

G. Use reducing fittings throughout piping systems. 28 1. Bushings will not be allowed unless specifically approved. 29

H. Equipment Drainage and Miscellaneous Piping: 30 1. Provide drip pans and piping at equipment where condensation may occur. 31 2. Hard pipe stuffing box leakage to nearest floor drain. 32 3. Avoid piping over electrical components such as motor control centers, panelboards, etc. 33

a. If piping must be so routed, utilize 16 GA, 316 stainless steel drip pan under piping and 34 over full length of electrical equipment. 35

b. Hard pipe drainage to nearest floor drain. 36 4. Collect system condensate at drip pockets, traps and blowoff valves. 37 5. Provide drainage for process piping at locations shown on Drawings in accordance with 38

Drawing details. 39 6. For applications defined above and for other miscellaneous piping which is not addressed by 40

a specific piping service category in PART 1, provide 304 stainless steel piping and fittings. 41 a. Size to handle application with 3/4 IN being minimum size provided. 42

I. Unions: 43 1. Install in position which will permit valve or equipment to be removed without dismantling 44

adjacent piping. 45 2. Mechanical type couplings may serve as unions. 46 3. Additional flange unions are not required at flanged connections. 47

J. Install expansion devices as necessary to allow expansion/contraction movement. 48

Page 188: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 8

K. Provide full face gaskets on all systems. 1

L. Anchorage and Blocking: 2 1. Block, anchor, or harness exposed piping subjected to forces in which joints are installed to 3

prevent separation of joints and transmission of stress into equipment or structural 4 components not designed to resist those stresses. 5

M. Equipment Pipe Connections: 6 1. Equipment - General: 7

a. Exercise care in bolting flanged joints so that there is no restraint on the opposite end of 8 pipe or fitting which would prevent uniform gasket pressure at connection or would 9 cause unnecessary stresses to be transmitted to equipment flanges. 10

b. Where push-on joints are used in conjunction with flanged joints, final positioning of 11 push-on joints shall not be made until flange joints have been tightened without strain. 12

c. Tighten flange bolts at uniform rate which will result in uniform gasket compression 13 over entire area of joint. 14 1) Provide tightening torque in accordance with manufacturer's recommendations. 15

d. Support and match flange faces to uniform contact over their entire face area prior to 16 installation of any bolt between the piping flange and equipment connecting flange. 17

e. Permit piping connected to equipment to freely move in directions parallel to 18 longitudinal centerline when and while bolts in connection flange are tightened. 19

f. Align, level, and wedge equipment into place during fitting and alignment of 20 connecting piping. 21

g. Grout equipment into place prior to final bolting of piping but not before initial fitting 22 and alignment. 23

h. To provide maximum flexibility and ease of alignment, assemble connecting piping 24 with gaskets in place and minimum of four (4) bolts per joint installed and tightened. 25 1) Test alignment by loosening flange bolts to see if there is any change in 26

relationship of piping flange with equipment connecting flange. 27 2) Realign as necessary, install flange bolts and make equipment connection. 28

i. Provide utility connections to equipment shown on Drawings, scheduled or specified. 29 2. Plumbing and HVAC equipment: 30

a. Make piping connections to plumbing and HVAC equipment, including but not limited 31 to installation of fittings, strainers, pressure reducing valves, flow control valves and 32 relief valves provided with or as integral part of equipment. 33

b. Furnish and install sinks, fittings, strainers, pressure reducing valves, flow control 34 valves, pressure relief valves, and shock absorbers which are not specified to be 35 provided with or as integral part of equipment. 36

c. For each water supply piping connection to equipment, furnish and install union and 37 gate or angle valve. 38 1) Provide wheel handle stop valve at each laboratory sink water supply. 39 2) Minimum size: 1/2 IN. 40

d. Furnish and install "P" trap for each waste piping connection to equipment if waste is 41 connected directly to building sewer system. 42 1) Size trap as required by IPC. 43

e. Stub piping for equipment, sinks, lavatories, supply and drain fittings, key stops, "P" 44 traps, miscellaneous traps and miscellaneous brass through wall or floor and cap and 45 protect until such time when later installation is performed. 46

N. Provide insulating components where dissimilar metals are joined together. 47

O. Instrument Connections: See Drawing details. 48

3.3 CONNECTIONS WITH EXISTING PIPING 49

A. Where connection between new work and existing work is made, use suitable and proper fittings 50 to suit conditions encountered. 51

Page 189: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 9

B. Perform connections with existing piping at time and under conditions which will least interfere 1 with service to customers affected by such operation. 2

C. Undertake connections in fashion which will disturb system as little as possible. 3

D. Provide suitable equipment and facilities to dewater, drain, and dispose of liquid removed 4 without damage to adjacent property. 5

E. Where connections to existing systems necessitate employment of past installation methods not 6 currently part of trade practice, utilize necessary special piping components. 7

F. Where connection involves potable water systems, provide disinfection methods as prescribed in 8 this Specification Section. 9

G. Once tie-in to each existing system is initiated, continue work continuously until tie-in is made 10 and tested. 11

3.4 ACCESS PROVISIONS 12

A. Provide access doors or panels in walls, floors, and ceilings to permit access to valves, piping 13 and piping appurtenances requiring service. 14

B. Size of access panels to allow inspection and removal of items served, minimum 10 x 14 IN size. 15

C. Fabricate door and frame of minimum 14 GA, stretcher leveled stock, cadmium plated or 16 galvanized after fabrication and fitted with screw driver lock of cam type. 17

D. Provide with key locks, keyed alike, in public use areas. 18

E. Furnish panels with prime coat of paint. 19

F. Style and type as required for material in which door installed. 20

G. Where door is installed in fire-rated construction, provide door bearing UL label required for 21 condition. 22

3.5 CATHODIC PROTECTION 23

A. Isolate, dielectrically, all piping from all other metals including reinforcing bars in concrete 24 slabs, other pipe lines, and miscellaneous metal. 25

B. Make all connections from wire or cable by Thermit Cadwelding accomplished by operators 26 experienced in this process. 27

C. Install all cables with a loop and overhead knot around each pipe and slack equal to at least 50 28 percent of the straight line length. 29

D. After cadwelding, coat all exposed metallic surfaces with hot applied tape. 30

3.6 PRESSURE GAGES 31

A. Provide at locations shown on the Drawings and specified. 32

B. See Specification Section 11005. 33

3.7 FIELD QUALITY CONTROL 34

A. Pipe Testing - General: 35 1. Test piping systems as follows: 36

a. Test exposed, non-insulated piping systems upon completion of system. 37 b. Test exposed, insulated piping systems upon completion of system but prior to 38

application of insulation. 39 c. Test concealed interior piping systems prior to concealment and, if system is insulated, 40

prior to application of insulation. 41 d. Test buried piping (insulated and non-insulated) prior to backfilling and, if insulated, 42

prior to application of insulation. 43

Page 190: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 10

2. Utilize pressures, media and pressure test durations as specified in the PIPING 1 SPECIFICATION SCHEDULES. 2

3. Isolate equipment which may be damaged by the specified pressure test conditions. 3 4. Perform pressure test using calibrated pressure gages and calibrated volumetric measuring 4

equipment to determine leakage rates. 5 a. Select each gage so that the specified test pressure falls within the upper half of the 6

gage's range. 7 b. Notify the Engineer 24 HRS prior to each test. 8

5. Completely assemble and test new piping systems prior to connection to existing pipe 9 systems. 10

6. Acknowledge satisfactory performance of tests and inspections in writing to Engineer prior 11 to final acceptance. 12

7. Bear the cost of all testing and inspecting, locating and remedying of leaks and any 13 necessary retesting and re-examination. 14

B. Pressure Testing: 15 1. Testing medium: Unless otherwise specified in the PIPING SPECIFICATION 16

SCHEDULES, utilize the following test media. 17 a. Liquid systems: 18

19

PIPE LINE SIZE (DIA) GRAVITY

OR PUMPED SPECIFIED TEST

PRESSURE TESTING MEDIUM

Up to and including 48 IN Gravity 25 psig or less Air or water All sizes Pumped 250 psig or less Water

20 2. Allowable leakage rates: 21

a. Hazardous gas systems, all exposed piping systems, all pressure piping systems and all 22 buried, insulated piping systems which are hydrostatically pressure tested shall have 23 zero leakage at the specified test pressure throughout the duration of the test. 24

b. Hydrostatic exfiltration and infiltration for sanitary and stormwater sewers 25 (groundwater level is below the top of pipe): 26 1) Leakage rate: 200 GAL per inch diameter per mile of pipe per day at average head 27

on test section of 3 FT. 28 2) Average head is defined from groundwater elevation to average pipe crown. 29 3) Acceptable test head leakage rate for heads greater than 3 FT: Acceptable leakage 30

rate (gallons per inch diameter per mile per day) equals 115 by (actual test head to 31 the 1/2 power). 32

c. Hydrostatic infiltration test for sanitary and stormwater sewers (groundwater level is 33 above the top of pipe): 34 1) Allowable leakage rate: 200 GAL per inch diameter per mile of pipe per day when 35

depth of groundwater over top of pipe is 2 to 6 FT. 36 2) Leakage rate at heads greater than 6 FT: Allowable leakage rate (gallons per inch 37

diameter per mile of pipe per day) equals 82 by (actual head to the 1/2 power). 38 d. Large diameter (above 48 IN) gravity plant piping systems shall have a maximum 39

exfiltration of 25 gpd per inch-mile. 40 e. Non-hazardous gas and air systems which are tested with air shall have a maximum 41

pressure drop of 5 percent of the specified test pressure throughout the duration of the 42 test. 43

f. For low pressure (less than 25 psig) air testing, the acceptable time for loss of 1 psig of 44 air pressure shall be: 45

46 PIPE SIZE (IN DIA) TIME, MINUTES/100 FT

4 0.3 6 0.7 8 1.2

Page 191: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 11

PIPE SIZE (IN DIA) TIME, MINUTES/100 FT 10 1.5 12 1.8 15 2.1 18 2.4 21 3.0 24 3.6 27 4.2 30 4.8 33 5.4 36 6.0 42 7.3 48 7.6

1 3. Hydrostatic pressure testing methodology: 2

a. General: 3 1) All joints, including welds, are to be left exposed for examination during the test. 4 2) Provide additional temporary supports for piping systems designed for vapor or gas 5

to support the weight of the test water. 6 3) Provide temporary restraints for expansion joints for additional pressure load under 7

test. 8 4) Isolate equipment in piping system with rated pressure lower than pipe test 9

pressure. 10 5) Do not paint or insulate exposed piping until successful performance of pressure 11

test. 12 b. Soil, waste, drain and vent systems: 13

1) Test at completion of installation of each stack or section of piping by filling 14 system with water and checking joints and fittings for leaks. 15

2) Eliminate leaks before proceeding with work or concealing piping. 16 3) Minimum test heights shall be 10 FT above highest stack inlet. 17

c. Larger diameter (above 36 IN) gravity plant piping: 18 1) Plug downstream end of segment to be tested. 19

a) Provide bracing as required. 20 2) Fill segment and upstream structure to normal operating level as per hydraulic 21

profile. 22 3) Allow 24 HRS for absorption losses. 23

a) Refill to original level. 24 4) Provide reservoir to maintain constant head over duration of test. 25 5) Record reservoir water volume at beginning and end of test. 26

4. Natural gas systems - testing methodology: 27 a. Maintain specified test pressure until each joint has been thoroughly examined for leaks 28

by means of soap suds and glycerine. 29 b. Wipe joints clean after test. 30

5. Air testing methodology: 31 a. General: 32

1) Assure air is ambient temperature. 33 b. Low pressure air testing: 34

1) Place plugs in line and inflate to 25 psig. 35 2) Check pneumatic plugs for proper sealing. 36 3) Introduce low pressure air into sealed line segment until air pressure reaches 4 psig 37

greater than ground water that may be over the pipe. 38 a) Use test gage conforming to ASME B40.100 with 0 to 15 psi scale and 39

accuracy of 1 percent of full range. 40 4) Allow 2 minutes for air pressure to stabilize. 41

Page 192: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 12

5) After stabilization period (3.5 psig minimum pressure in pipe) discontinue air 1 supply to line segment. 2

6) Record pressure at beginning and end of test. 3

C. Dielectric Testing Methods and Criteria: 4 1. Provide electrical check between metallic non-ferrous pipe or appurtenances and ferrous 5

elements of construction to assure discontinuity has been maintained. 6 2. Wherever electrical contact is demonstrated by such test, locate the point or points of 7

continuity and correct the condition. 8

3.8 CLEANING, DISINFECTION AND PURGING 9

A. Cleaning: 10 1. Clean interior of piping systems thoroughly before installing. 11 2. Maintain pipe in clean condition during installation. 12 3. Before jointing piping, thoroughly clean and wipe joint contact surfaces and then properly 13

dress and make joint. 14 4. Immediately prior to pressure testing, clean and remove grease, metal cuttings, dirt, or other 15

foreign materials which may have entered the system. 16 5. At completion of work and prior to Final Acceptance, thoroughly clean work installed under 17

these Specifications. 18 a. Clean equipment, fixtures, pipe, valves, and fittings of grease, metal cuttings, and 19

sludge which may have accumulated by operation of system, from testing, or from 20 other causes. 21

b. Repair any stoppage or discoloration or other damage to parts of building, its finish, or 22 furnishings, due to failure to properly clean piping system, without cost to Owner. 23

6. After erection of piping and tubing, but prior to installation of service outlet valves, blow 24 systems clear of free moisture and foreign matter by means of air, nitrogen or carbon 25 dioxide. 26 a. Oxygen shall never be used. 27

7. Clean chlorine piping in accordance with CI Pamphlet 6. 28 8. Purge all neat liquid polymer tubing or piping between the neat polymer storage tank or tote 29

and the polymer blending units with mineral oil to remove residual water prior to 30 introducing neat polymer. Following purging, drain as much of the mineral oil out of the 31 system as possible. Dispose of purged fluids and waste mineral oil in accordance with local 32 environmental regulations. 33

B. Disinfection of Potable Water Systems: 34 1. After favorable performance of pressure test and prior to Final Acceptance, thoroughly flush 35

entire potable water piping system including supply, source and any appurtenant devices 36 and perform disinfection as prescribed. 37

2. Perform work, including preventative measures during construction, in full compliance with 38 AWWA C651. 39

3. Perform disinfection using sodium hypochlorite complying with AWWA B300. 40 4. Flush each segment of system to provide flushing velocity of not less than 2.5 FT per 41

second. 42 5. Drain flushing water to sanitary sewer. 43

a. Do not drain flushing water to receiving stream. 44 6. Use continuous feed method of application. 45

a. Tag system during disinfection procedure to prevent use. 46 7. After required contact period, flush system to remove traces of heavily chlorinated water. 47 8. After final flushing and before placing water in service, obtain an independent laboratory 48

approved by the Owner to collect samples and test for bacteriological quality. 49 a. Repeat entire disinfection procedures until satisfactory results are obtained. 50

Page 193: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 13

9. Secure and deliver to Owner, satisfactory bacteriological reports on samples taken from 1 system. 2 a. Ensure sampling and testing procedures are in full compliance to AWWA C651, local 3

water purveyor and applicable requirements of State of South Dakota. 4

3.9 LOCATION OF BURIED OBSTACLES 5

A. Furnish exact location and description of buried utilities encountered and thrust block placement. 6

B. Reference items to definitive reference point locations such as found property corners, entrances 7 to buildings, existing structure lines, fire hydrants and related fixed structures. 8

C. Include such information as location, elevation, coverage, supports and additional pertinent 9 information. 10

D. Incorporate information on "As-Recorded" Drawings. 11

3.10 PIPE INSULATION 12

A. Insulate pipe and pipe fittings in accordance with Specification Section 15183. 13

3.11 SCHEDULES 14

15

Page 194: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 14

A. SPECIFICATION SCHEDULE - SYSTEM 2 1 1. General: 2

a. Piping symbol and service: 3 1) RWTM – Raw Water Transmission Main Piping. 4 2) CWPDIS – Collector Well Discharge Piping. 5

b. Test requirements: 6 1) Test medium: Water. 7 2) Pressure: 150 psig. 8 3) Duration: 6 HRS. 9

c. Gaskets: 10 1) Flanged, push-on, and mechanical joints (ductile iron): Rubber, 11

AWWA/ANSI C111/A21.11. 12 2. System components: 13

a. Pipe size 3 IN through 30 IN: 14 1) Exposed service: 15

a) Material: 16 (1) Flanged: Ductile iron, Class 53. 17

b) Reference: AWWA/ANSI C115/A21.15. 18 c) Lining: Cement. 19 d) Coating: Paint per Section 09905. 20 e) Fittings: AWWA/ANSI C110/A21.10 ductile. 21 f) Joints: 22

(1) AWWA/ANSI C115/A21.15 flanged joints with flanges at valves and 23 structure penetrations. 24

(2) Provide restrained flange adapters for one joint at each flanged equipment 25 valve and penetration as shown on the drawings. 26

2) Buried service: 27 a) 30 IN 28

(1) Materials: Ductile iron, pressure class 350. 29 (2) Reference: AWWA/ANSI C151/A21.51. 30 (3) Lining: Cement. 31 (4) Coating: Bituminous. 32 (5) Fittings: 33

(a) Either AWWA/ANSI C110/A21.10 ductile or gray iron. 34 (b) Optional: AWWA/ANSI C153/A21.53 ductile iron compact fittings. 35

(6) Joints: 36 (a) Buried Fittings shall be restrained mechanical joint. 37 (b) Restrained mechanical joints at fittings and valves 38

(7) Provide Flex-Lok Socket and Flex-Lok Ball Joints at the Collector Well 39 Structure as shown on the drawings. 40

(8) Polyethylene encasement per AWWA C105. 41 (9) Warning tape: Tape shall not be in contact with pipe. 42

b) 24 IN 43 (1) Materials: 44

(a) PVC, AWWA C905, DR 18 (C.I.O.D) 45 (2) Lining: Cement – DIP Fittings 46 (3) Coating: None. 47 (4) Corrosion Protection: Polywrap on buried DIP and Fittings. 48 (5) Fittings: 49

(a) Either AWWA/ANSI C110/A21.10 ductile or gray iron. 50 (b) Optional: AWWA/ANSI C153/A21.53 ductile iron compact fittings. 51

(6) Joints: 52 (a) Elastomeric-gasket type with a pressure rating not less than the pipe 53

pressure rating meeting performance requirements of ASTM D3139. 54

Page 195: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 15

(b) Restrained mechanical joints at fittings and valves; EBAA Iron, 1 Series 2000PV or Engineer Approved Equal. 2

(c) Buried Fittings shall be restrained mechanical joint. 3 (7) Tracer wire: #12 AWG HS-CCS high-strength, Copper Clad Steel 4

Conductor (HS-CCS), Stainless Steel. 380 LBS average tensile break 5 load with 21% conductivity for locating purposes. Insulation with 30 mil, 6 high-density, high molecular weight polyethylene insulation rated for 7 direct buriel use at 30 V volt. Waterproof connector – 3M DBR, 8 Copperhead SnakeBit or Engineer approved equal. Insulation color shall 9 meet the APWA color code standard for identification of buried utilites. 10

(8) Transition from DIP to PVC with restrained mechanical joint coupling; 11 EBAA Series 3800 Restained Joint Coupling or Engineer approved 12 equivalent. 13

14 15

Page 196: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 16

B. SPECIFICATION SCHEDULE - SYSTEM 6 1 1. General: 2

a. Piping symbol and service: 3 1) CWR - Condenser Water Return. 4 2) CWS - Condenser Water Supply. 5 3) RWR - Raw Water Return. 6 4) RWS - Raw Water Supply. 7

b. Test requirements: 8 1) Test medium: Water. 9 2) Pressure: 125 psig. 10 3) Duration: 6 HRS. 11

c. Gaskets and O-rings: EPDM. 12 2. System components: 13

a. Pipe size through 26 IN: 14 1) Exposed service: 15

a) Material: 16 (1) Threaded: Steel, Grade B, black, Schedule 40. 17 (2) Grooved type joint system: Use pipe thickness per AWWA C606. 18

b) Reference: ASTM A53. 19 c) Lining: None. 20 d) Coating: Paint. 21 e) Fittings: Malleable iron or steel meeting ASME B16.3 and ASTM A234. 22 f) Joints: 23

(1) Threaded or grooved type mechanical coupling (AWWA C606) joints. 24 (2) With both systems, provide rigid flanges at equipment, valves and 25

structure penetrations above 2 IN and unions at those locations 2 IN and 26 below. 27

28

Page 197: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 17

C. SPECIFICATION SCHEDULE - SYSTEM 7 1 1. General: 2

a. Piping symbol and service: 3 1) PL – Pre-Lube Piping 4 2) ARVV – Air Release/Vacuum Valve Vent Piping 5 3) V – Vent Piping. 6

b. Test requirements pressure lines: 7 1) Test medium: Water. 8 2) Pressure: 125 psig. 9 3) Duration: 6 HRS. 10

c. Gaskets and O-rings: 11 1) Flanged, push-on, and mechanical joints (ductile iron): Rubber, 12

AWWA/ANSI C111/A21.11. 13 2. System components: 14

a. Pipe size 6 IN and smaller: 15 1) Interior Exposed service: 16

a) Material: PVC, Type 1, Grade 1, Schedule 80. 17 b) Reference: ASTM D1785. 18 c) Lining: None. 19 d) Coating: None. 20 e) Fittings: Solvent welded (compatable solvent) socket type complying with 21

ASTM D2467. 22 f) Joints: Solvent welded (compatable solvent) with unions at valves, 23

penetrations through structures and equipment connections for pipe 2 IN and 24 less and flanges at those locations for pipe above 2 IN. 25

2) Exterior Exposed service: 26 a) Material: 27

(1) Flanged: Ductile iron, Class 53. 28 b) Reference: AWWA/ANSI C115/A21.15. 29 c) Lining: Cement. 30 d) Coating: Paint per Section 09905. 31 e) Fittings: AWWA/ANSI C110/A21.10 ductile. 32 f) Joints: 33

(1) AWWA/ANSI C115/A21.15 flanged joints with flanges at valves and 34 structure penetrations. 35

(2) Provide restrained flange adapters for one joint at each flanged equipment 36 valve and penetration as shown on the drawings. 37

END OF SECTION 38

39

Page 198: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE AND PIPE FITTINGS: BASIC REQUIREMENTS 15060 - 18

1

Page 199: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: STEEL 15061 - 1

2014/08/26 1

SECTION 15061 2

PIPE: STEEL 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Steel pipe, fittings, and appurtenances. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 09905 - Painting and Protective Coatings. 11 4. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. American Society of Mechanical Engineers (ASME): 15

a. B1.1, Unified Inch Screw Threads (UN and UNR Thread Form). 16 b. B1.2, Gages and Gaging for Unified Inch Screw Threads. 17 c. B16.3, Malleable Iron Threaded Fittings. 18 d. B16.5, Pipe Flanges and Flanged Fittings. 19 e. B16.9, Factory-Made Wrought Steel Butt-Welding Fittings. 20 f. B16.11, Forged Steel Fittings, Socket Welding and Threaded. 21 g. B31.1, Power Piping. 22 h. B31.3, Process Piping. 23 i. B31.9, Building Services Piping. 24 j. Section IX, Qualification Standard for Welding and Brazing Procedures, Welders, 25

Brazers, and Welding and Brazing Operators. 26 2. ASTM International (ASTM): 27

a. A36, Standard Specification for Carbon Structural Steel. 28 b. A53, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, 29

Welded and Seamless. 30 c. A181, Standard Specification for Carbon Steel Forgings, for General-Purpose Piping. 31 d. A234, Standard Specification for Pipe Fittings of Wrought Carbon Steel and Alloy 32

Steel for Moderate and High Temperature Service. 33 e. A283, Standard Specification for Low and Intermediate Tensile Strength Carbon Steel 34

Plates. 35 f. A572, Standard Specification for High-Strength Low-Alloy Columbium-Vanadium 36

Structural Steel. 37 g. A1011, Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, 38

Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved 39 Formability, and Ultra-High Strength. 40

h. B6, Standard Specification for Zinc. 41 i. B695, Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and 42

Steel. 43 3. American Water Works Association (AWWA): 44

a. C200, Standard for Steel Water Pipe - 6 IN and Larger. 45 b. C203, Standard for Coal-Tar Protective Coatings and Linings for Steel water Pipeline - 46

Enamel and Tape - Hot Applied. 47

Page 200: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: STEEL 15061 - 2

c. C205, Standard for Cement-Mortar Lining and Coating for Steel Water Pipe - 4 IN and 1 Larger - Shop Applied. 2

d. C206, Standard for Field Welding of Steel Water Pipe. 3 e. C207, Standard for Steel Pipe Flanges for Waterworks Service - Sizes 4 IN through 4

144 IN. 5 f. C208, Standard for Dimensions for Fabricated Steel Water Pipe Fittings. 6 g. C209, Standard for Cold-Applied Tape Coatings for the Exterior of Special Sections, 7

Connections, and Fittings for Steel Water Pipelines. 8 h. C210, Standard for Liquid-Epoxy Coating Systems for the Interior and Exterior of Steel 9

Water Pipelines. 10 i. C606, Standard for Grooved and Shouldered Joints. 11 j. M11, Steel Pipe - A Guide for Design and Installation. 12

4. Society of Automotive Engineers (SAE): 13 a. AMS-QQ-P-416, Cadmium Plating Electro deposited. 14

B. Qualifications: 15 1. Application of lining and coating materials including preparation of surfaces, priming, and 16

lining and coating of pipe, fittings, and specials, in shop, repairs of any damage to lining or 17 coating occurring during shipment or any other time, and field lining and coating of ends 18 where linings or coatings have been held back for welded field joints, shall be done by 19 established and recognized pipe company acceptable to Engineer. 20

2. Use only certified welders meeting procedures and performance outlined in ASME Section 21 IX, AWWA C200 Section 3.3.3 and other codes and requirements per local building and 22 utility requirements. 23

1.3 SUBMITTALS 24

A. Shop Drawings: 25 1. See Specification Section 01340 for requirements for the mechanics and administration of 26

the submittal process. 27 2. See Specification Section 15060. 28 3. Factory test reports. 29 4. If mechanical grooved type coupling system is used, submit piping, fittings, and appurtenant 30

items which will be utilized. 31 5. Coating manufacturer's qualifications. 32 6. Welders certificates. 33

PART 2 - PRODUCTS 34

2.1 ACCEPTABLE MANUFACTURERS 35

A. Subject to compliance with the Contract Documents, the following manufacturers are 36 acceptable: 37 1. Flanged adaptors: 38

a. Rockwell (Style 913 (steel)). 39 b. Dresser (Style 128 (steel)). 40

2. Insulating couplings: 41 a. Rockwell (Style 416). 42 b. Dresser (Style 39). 43

3. Reducing couplings: 44 a. Rockwell (Style 415). 45 b. Dresser (Style 62). 46

4. Transition coupling: 47 a. Rockwell (Style 413). 48 b. Dresser (Style 62). 49

Page 201: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: STEEL 15061 - 3

5. Compression sleeve coupling: 1 a. Rockwell (Style 411 (steel)). 2 b. Dresser (Style 38 (steel)). 3

6. Mechanical couplings and fittings: 4 a. Victaulic (Style 07 or 77). 5 b. S.P. Fittings. 6

7. Vibration isolation equipment connections for natural gas: 7 a. Flexonics (Model 401H). 8

8. Flexible connectors for hot water equipment: 9 a. Flexonics (FLG Series). 10 b. Thermo Tech (F/J/R Series). 11

9. Factory-applied plastic or epoxy coatings: 12 a. "Encoat" Division of Energy Coating Company. 13 b. "Scotchkote" Division of 3M Company. 14

B. Submit request for substitution in accordance with Specification Section 01640. 15

2.2 MATERIALS 16

A. All materials used in steel piping systems defined in Section 15060 shall meet or exceed 17 pressure test requirements specified for each respective system. 18

B. Steel Pipe (Fabricated Type): 19 1. AWWA C200: 20

a. ASTM A36, Grade C steel plate. 21 b. ASTM A283, Grade D steel plate. 22 c. ASTM A572, steel plate. 23 d. ASTM A1011, steel sheet. 24

C. Steel Pipe (Mill Type): ASTM A53, Type E or S. 25

D. Fittings (For Fabricated Pipe): AWWA C208. 26

E. Fittings (For Mill Type Pipe): 27 1. ASTM A234. 28 2. ASME B16.3, ASME B16.5, ASME B16.9, ASME B16.11. 29

F. Flanges (Fabricated Pipe): 30 1. Flange material: ASTM A283, Grade C or D, ASTM A181, Grade 1. 31 2. Flange finish: Flat faced. 32

G. Flanges (Mill Type Pipe): 33 1. ASME B16.5. 34 2. Flat faced. 35 3. Slip-on flanges. 36

H. Nuts and Bolts: 37 1. Buried: Cadmium-plated meeting SAE AMS-QQ-P-416, Type 1, Class 2 (Cor-Ten) for 38

buried application. 39 2. Exposed: Mechanical galvanized ASTM B695, Class 40. 40 3. Heads and dimensions per ASME B1.1. 41 4. Threaded per ASME B1.1. 42 5. Project ends 1/4 to 1/2 IN beyond nuts. 43

I. Gaskets: See individual piping systems in Section 15060. 44

2.3 MANUFACTURED UNITS 45

A. Couplings: 46 1. Flanged adaptors: 47

a. Steel or carbon steel body sleeve, flange, followers and Grade 30 rubber gaskets. 48

Page 202: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: STEEL 15061 - 4

b. Provide units specified in Article 2.1. 1 c. Flanges meeting standards of adjoining flanges. 2 d. Entire assembly to be rated for test pressure specified on Piping Schedule for each 3

respective application. 4 2. Compression sleeve coupling: 5

a. Steel sleeve, followers Grade 30 and rubber gaskets. 6 b. Provide units specified in Article 2.1. 7 c. Flanges meeting standards of adjoining flanges. 8 d. Entire assembly to be rated for test pressure specified on Piping Schedule for each 9

respective application. 10 e. Provide field coating for buried couplings per AWWA C203. 11

3. Mechanical coupling joint: 12 a. Use of mechanical grooved (AWWA C606) type couplings and fittings in lieu of 13

flanged joints is acceptable where specifically specified in Section 15060. 14 b. Utilize units defined in Article 2.1. 15

2.4 ACCESSORIES 16

A. Heating Water Application: 17 1. For steel heating lines, provide braided, flanged stainless steel connectors for connection to 18

equipment. 19 2. Provide pump connectors with stainless steel construction, rubber filled bellows and flanged 20

end connections. 21

B. Natural Gas Equipment Isolator: 316L stainless steel, T-321 stainless steel braid with 22 connections compatible with joints in piping system. 23

2.5 FABRICATION 24

A. Provide piping (mill or fabricated) for use in this Project with minimum wall thicknesses as 25 follows: 26 1. 1/8 - 5 IN DIA pipe: Schedule 40. 27 2. 6 - 10 IN DIA pipe: 3/16 IN. 28 3. 12 - 14 IN DIA pipe: 7/32 IN. 29 4. 16 - 48 IN DIA pipe: 1/4 IN. 30 5. 54 - 60 IN DIA pipe: 5/16 IN. 31 6. 66 - 72 IN DIA pipe: 3/8 IN. 32 7. Sizes through 24 IN are nominal OD. 33

a. Sizes greater than 24 are ID. 34 8. Wall thicknesses indicated are for standard weight pipe. 35

a. Design pipe in accordance with operating pressures shown in Piping Schedules for a 36 design stress limited to 50 percent of yield. 37

B. Furnish cast parts with lacquer finish compatible with finish coating. 38

C. Furnish without outside coating of bituminous material any exposed pipe scheduled to be 39 painted. 40

D. Fabricated Fittings: 41 1. AWWA C208. 42 2. Assure ratio of radius of bend to diameter of pipe equal to or greater than 1.0. 43

E. Taper cement mortar linings as required for valve interfacing. 44

F. Protective Coatings and Linings: 45 1. Provide enamel linings and coatings in accordance with AWWA C203 and the following: 46

a. Potable water: Provide minimum dry film of 5 mils of asphaltic coating non-toxic 47 blend of Gilsonite and brown and steam distilled asphalt. 48

b. Nonpotable fluids: Provide minimum dry film of 5 mils of acceptable asphalt base 49 material. 50

Page 203: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: STEEL 15061 - 5

c. Provide coating in accordance with AWWA C203 and subject to following additional 1 requirements. 2 1) Do not use enamel lined or coated steel pipe exposed to temperatures below 3

10 DegF. 4 2) Do not handle enamel-lined or coated pipe when temperature of pipe is below 5

20 DegF. 6 2. Provide cement mortar lining in accordance with AWWA C205. 7 3. Provide cement mortar coating in accordance with AWWA C205. 8 4. Galvanize surface in accordance with hot-dip method using any grade of zinc acceptable to 9

ASTM B6. 10 5. Wrap pipe in accordance with AWWA C209. 11 6. Field paint pipe in accordance with Section 09905. 12

2.6 SOURCE QUALITY CONTROL 13

A. Testing: 14 1. Shop hydrostatic test fabricated steel pipe and fittings. 15 2. Field hydrostatic test all pipe as specified in Section 15060. 16

PART 3 - EXECUTION 17

3.1 INSTALLATION 18

A. Install products in accordance with manufacturer's instructions. 19

B. Joining Methods - Flanges: 20 1. Facing method: 21

a. Insert slip-on flange on pipe. 22 b. Assure maximum tolerances for flange faces from normal with respect to axis of pipe is 23

0.005 IN per foot of flange diameter. 24 c. Test flanges after welding to pipe for true to face condition and reface, if necessary, to 25

bring to specified tolerance. 26 2. Joining method: 27

a. Leave 1/8 to 3/8 IN of flange bolts projecting beyond face of nut after tightening. 28 b. Coordinate dimensions and drillings of flanges with flanges for valves, pumps, 29

equipment, tank, and other interconnecting piping systems. 30 c. When bolting flange joints, exercise extreme care to assure that there is no restraint on 31

opposite end of pipe or fitting which would prevent uniform gasket compression or 32 cause unnecessary stress, bending or torsional strains being applied to cast flanges or 33 flanged fittings. 34 1) Allow one (1) flange free movement in any direction while bolts are being 35

tightened. 36 d. Do not assemble adjoining flexible coupled, mechanical coupled or welded joints until 37

flanged joints in piping system have been tightened. 38 e. Gradually tighten flange bolts uniformly to permit even gasket compression. 39 f. Do not overstress bolts to compensate for poor installation. 40

C. Joining Method - Welded Joints: 41 1. Perform welding in accordance with AWWA C206 and this Section. 42 2. For flange attachment perform in accordance with AWWA C207. 43 3. Have each welding operator affix an assigned symbol to all his welds. 44

a. Mark each longitudinal joint at the extent of each operator's welding. 45 b. Mark each circumferential joint, nozzle, or other weld into places 180 degrees apart. 46

4. Welding for all process piping shall conform with ASME B31.3. 47 a. Welding of utility piping 125 psi and less shall be welded per ASME B31.9. 48 b. Utility piping above 125 psi shall conform to ASME B31.1. 49

5. Provide caps, tees, elbows, reducers, etc., manufactured for welded applications. 50

Page 204: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: STEEL 15061 - 6

6. Weldolets may be used for 5 IN and larger pipe provided all slag is removed from inside the 1 pipe. 2

7. Weld-in nozzles may be used for branch connections to mains and where approved by 3 Engineer. 4

8. Use all long radius welding elbows for expansion loops and bends. 5 9. Use long radius reducing welding elbows 90 degree bends and size changes are required. 6

D. Joining Method - Couplings: 7 1. Compression sleeve: 8

a. Install coupling to allow space of not less than 1/4 IN but not more than 1 IN. 9 b. Provide harnessed joint. 10

1) Use joint harness arrangements detailed in AWWA M11. 11 c. Design harness assembly with adequate number of tie rods for test pressures indicated 12

in Section 15060 and allow for expansion of pipe. 13 d. Provide ends to be joined or fitted with compression sleeve couplings of the plain end 14

type. 15 e. Grind smooth welds the length of one (1) coupling on either side of joint to be fitted 16

with any coupling. 17 f. Assure that outside diameter and out-of-round tolerances are within limits required by 18

coupling manufacturer. 19 2. Mechanical coupling: 20

a. Arrange piping so that pipe ends are in full contact. 21 b. Groove and shoulder ends of piping in accordance with manufacturer's 22

recommendations. 23 c. Provide coupling and grooving technique assuring a connection which passes pressure 24

testing requirements. 25

E. Joining Method - Threaded and Coupled (T/C): 26 1. Provide T/C end conditions that meet ASME B1.2 requirements. 27 2. Furnish pipe with factory-made T/C ends. 28 3. Field cut additional threads full and clean with sharp dies. 29 4. Leave not more than three (3) pipe threads exposed at each branch connection. 30 5. Ream ends of pipe after threading and before assembly to remove burrs. 31 6. Use Teflon thread tape on male thread in mating joints. 32

F. Support exposed piping in accordance with Section 15060. 33

G. Install buried piping per Section 15060. 34

3.2 FIELD QUALITY CONTROL 35

A. Test piping systems in accordance with Section 15060. 36

END OF SECTION 37

Page 205: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: DUCTILE 15062 - 1

2014/08/28 1

SECTION 15062 2

PIPE: DUCTILE 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Ductile iron piping, fittings, and appurtenances. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. American Society of Mechanical Engineers (ASME): 14

a. B1.1, Unified Inch Screw Threads (UN and UNR Thread Form). 15 b. B16.1, Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250. 16

2. ASTM International (ASTM): 17 a. B695, Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and 18

Steel. 19 3. American Water Works Association (AWWA): 20

a. C203, Standard for Coal-Tar Protective Coatings and Linings for Steel Water Pipelines 21 - Enamel and Tape - Hot Applied. 22

b. C606, Standard for Grooved and Shouldered Joints. 23 4. American Water Works Association/American National Standards Institute 24

(AWWA/ANSI): 25 a. C105/A21.5, Standard for Polyethylene Encasement for Ductile-Iron Pipe Systems. 26 b. C110/A21.10, Standard for Ductile-Iron and Gray-Iron Fittings. 27 c. C111/A21.11, Standard for Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and 28

Fittings. 29 d. C115/A21.15, Standard for Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron 30

Threaded Flanges. 31 e. C150/A21.50, Standard for Thickness Design of Ductile-Iron Pipe. 32 f. C151/A21.51, Standard for Ductile-Iron Pipe, Centrifugally Cast, for Water. 33

5. Society of Automotive Engineers (SAE): 34 a. AMS-QQ-P-416, Cadmium Plating - Electro-deposited. 35

1.3 SUBMITTALS 36

A. Shop Drawings: 37 1. See Specification Section 01340 for requirements for the mechanics and administration of 38

the submittal process. 39 2. See Specification Section 15060. 40 3. Certification of factory hydrostatic testing. 41 4. If mechanical coupling system is used, submit piping, fittings, and appurtenant items which 42

will be utilized to meet system requirements. 43

Page 206: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: DUCTILE 15062 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Restrained flanged coupling adaptors: 5

a. Smith-Blair (Series 911 (cast)). 6 b. ROMAC (Series FC400) 7 c. EBBA (Style 2100) 8

2. Compression or split sleeve coupling: 9 a. Rockwell (Style 431 (cast)). 10 b. Dresser (Style 153 (cast)). 11

3. Insulating couplings: 12 a. Rockwell (Style 416). 13 b. Dresser (Style 39). 14

4. Reducing couplings: 15 a. Rockwell (Style 415). 16 b. Dresser (Style 62). 17

5. Transition coupling: 18 a. Rockwell (Style 413). 19 b. Dresser (Style 62). 20

6. Restrained Joints: 21 a. EBBA (Style 2100). 22

7. Rubber (elastomeric) expansion joint (with limit rods and nuts): 23 a. Mercer, Series 450. 24

1) Outside nuts to restrict expansion. 25 2) Inside nuts (or sleeves) to restrict contraction. 26

b. Unaflex, Style 150. 27 1) Outside nuts to restrict expansion. 28 2) Inside nuts (or sleeves) to restrict contraction. 29

8. Restrained compression coupling harness. 30 a. Dresser Star Anchor. 31 b. Smith-Blair harness assembly. 32

9. Polyethylene encasement tape: 33 a. Chase (Chasekote 750). 34 b. Kendall (Polyken 900). 35 c. 3 M (Scotchrap 50). 36

10. Restrained joints: 37 a. U.S. Pipe (TR-Flex) - 4 IN to 54 IN. 38 b. American (Lock Fast) - Above 12 IN. 39

11. Accepted Pipe and Fitting Manufacturer: 40 a. American Cast Iron Pipe Company. 41 b. US Pipe. 42

B. Submit request for substitution in accordance with Specification Section 01640. 43

2.2 MATERIALS 44

A. Ductile Iron Pipe: 45 1. AWWA/ANSI C115/A21.15. 46 2. AWWA/ANSI C150/A21.50. 47 3. AWWA/ANSI C151/A21.51. 48

B. Fittings and Flanges: 49 1. AWWA/ANSI C110/A21.10. 50 2. AWWA/ANSI C115/A21.15. 51

Page 207: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: DUCTILE 15062 - 3

3. Flanges drilled and faced per ASME B16.1 for both 125 and 250 psi applications. 1 4. Ductile iron fittings for buried service to be either AWWA/ANSI C110/A21.10 or 2

AWWA/ANSI C153/A21.53 ductile iron compact fittings. 3

C. Nuts and Bolts: 4 1. Buried: Cadmium-plated meeting SAE AMS-QQ-P-416, Type 1, Class 2 (Cor-Ten) or 304 5

Stainless Steel for buried application. 6 2. Exposed: Mechanical galvanized ASTM B695, Class 40. 7 3. Heads and dimensions per ASME B1.1. 8 4. Threaded per ASME B1.1. 9 5. Project ends 1/4 to 1/2 IN beyond nuts. 10

D. Gaskets: See individual piping system requirements in Section 15060. 11

E. If mechanical coupling system is used, utilize pipe thickness and grade in accordance with 12 AWWA C606. 13

F. Polyethylene Encasement: See AWWA/ANSI C105/A21.5. 14

G. See Piping Schedules in Section 15060. 15

2.3 MANUFACTURED UNITS 16

A. Couplings: 17 1. Pipe manufacturer is responsible for welding restraint rings required for couplings. 18

a. Restraint rings to be supplied and designed by coupling manufacturer. 19 b. Coupling manufacturer to ship restraint rings to the pipe manufacturer. 20 c. Weld restraint rings per coupling manufacturer requirements. 21

2. Flanged adaptors: 22 a. Unit consisting of steel or carbon steel body sleeve, flange, followers, Grade 30 rubber 23

gaskets. 24 b. Provide units specified in Article 2.1. 25 c. Supply flanges meeting standards of adjoining flanges. 26 d. Rate entire assembly for test pressure specified on piping schedule for each respective 27

application. 28 3. Compression or split sleeve coupling: 29

a. Unit consisting of steel sleeve, followers, Grade 30 rubber gaskets. 30 b. Provide units specified in Article 2.1. 31 c. Supply flanges meeting standards of adjoining flanges. 32 d. Entire assembly to be rated for test pressure specified on piping schedule for each 33

respective application. 34 e. Factory applied fusion-bonded epoxy, interior and exterior surfaces. 35

4. Expansion joint: 36 a. Provide control rods and compression sleeves. 37 b. Number and diameter per manufacturer's recommendation for working pressure. 38 c. Two (2) rod/sleeve assemblies, minimum. 39

5. Mechanical couplings: 40 a. Use of mechanical couplings and fittings in lieu of flanged joints is acceptable where 41

specifically specified in Section 15060. 42 b. Utilize units defined in Article 2.1. 43

2.4 FABRICATION 44

A. Furnish and install without outside coatings of bituminous material any exposed pipe scheduled 45 to be painted. 46

B. Furnish cast parts with lacquer finish compatible with finish coat. 47

Page 208: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: DUCTILE 15062 - 4

2.5 SOURCE QUALITY CONTROL 1

A. Factory Test: 2 1. Subject pipe to hydrostatic test of not less than 500 psi with the pipe under the full test 3

pressure for at least 10 seconds. 4

PART 3 - EXECUTION 5

3.1 INSTALLATION 6

A. Joining Method - Push-On Mechanical (Gland-Type) Joints: 7 1. Install in accordance with AWWA/ANSI C111/A21.11. 8 2. Assemble mechanical joints carefully according to manufacturer's recommendations. 9 3. If effective sealing is not obtained, disassemble, thoroughly clean, and reassemble the joint. 10 4. Do not overstress bolts. 11 5. Where piping utilizes mechanical joints with tie rods, align joint holes to permit installation 12

of harness bolts. 13

B. Joining Method - Push-On Joints: 14 1. Install in accordance with AWWA/ANSI C151/A21.51. 15 2. Assemble push-on joints in accordance with manufacturer's directions. 16 3. Bevel and lubricate spigot end of pipe to facilitate assembly without damage to gasket. 17

a. Use lubricant that is non-toxic, does not support the growth of bacteria, has no 18 deteriorating effects on the gasket material, and imparts no taste or odor to water in 19 pipe. 20

4. Assure the gasket groove is thoroughly clean. 21 5. For cold weather installation, warm gasket prior to placement in bell. 22 6. Taper of bevel shall be approximately 30 degrees with centerline of pipe and approximately 23

1/4 IN back. 24

C. Joining Method - Flanged Joints: 25 1. Install in accordance with AWWA/ANSI C115/A21.15. 26 2. Extend pipe completely through screwed-on flanged and machine flange face and pipe in 27

single operation. 28 3. Make flange faces flat and perpendicular to pipe centerline. 29 4. When bolting flange joints, exercise extreme care to ensure that there is no restraint on 30

opposite end of pipe or fitting which would prevent uniform gasket compression or would 31 cause unnecessary stress, bending or torsional strains to be applied to cast flanges or flanged 32 fittings. 33

5. Allow one (1) flange free movement in any direction while bolts are being tightened. 34 6. Do not assemble adjoining flexible joints until flanged joints in piping system have been 35

tightened. 36 7. Gradually tighten flange bolts uniformly to permit even gasket compression. 37

D. Joining Method - Mechanical Coupling Joint: 38 1. Arrange piping so that pipe ends are in full contact. 39 2. Groove and shoulder ends of piping in accordance with manufacturer's recommendations. 40 3. Provide coupling and grooving technique assuring a connection which passes pressure 41

testing requirements. 42

E. Flange Adaptors 12 IN and Less: 43 1. Locate and drill holes for anchor studs after pipe is in place and bolted tight. 44 2. Drill holes not more than 1/8 IN larger than diameter of stud projection. 45

F. Cutting: 46 1. Do not damage interior lining material during cutting. 47 2. Use abrasive wheel cutters or saws. 48 3. Make square cuts. 49

Page 209: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: DUCTILE 15062 - 5

4. Bevel and free cut ends of sharp edges after cutting. 1

G. Support exposed pipe in accordance with Section 15060. 2

H. Install buried piping in accordance with Section 15060. 3

I. Install restrained joint systems where specified in Section 15060 under specific piping system. 4

J. Mechanical Coupling Joints-Jointing Method: 5 1. Pipe ends shall be in full contact. 6 2. Install pipe and fitting with grooved mechanical couplings in accordance with the 7

manufacturer’s recommendation. 8 3. Provide technique for installing grooved mechanical coupling systems that will assure 9

connections to pass the pressure testing requirements. 10

3.2 FIELD QUALITY CONTROL 11

A. Test piping systems in accordance with Section 15060. 12

END OF SECTION 13

14

Page 210: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: DUCTILE 15062 - 6

1

Page 211: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: PLASTIC 15064 - 1

2014/08/26 1

SECTION 15064 2

PIPE: PLASTIC 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Plastic pipe. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. See Specification Section 15060. 13

B. Referenced Standards: 14 1. ASTM International (ASTM): 15

a. PVC (polyvinyl chloride) materials: 16 1) D1784, Standard Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds 17

and Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds. 18 2) D1785, Standard Specification for Poly(Vinyl Chloride) PVC Plastic Pipe, 19

Schedules 40, 80 and 120. 20 3) D2467, Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe 21

Fittings, Schedule 80. 22 4) D3034, Standard Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer 23

Pipe and Fittings. 24 5) D3139, Standard Specification for Joints for Plastic Pressure Pipes Using Flexible 25

Elastomeric Seals. 26 6) D3212, Standard Specification for Joints for Drain and Sewer Plastic Pipes Using 27

Flexible Elastomeric Seals. 28 7) F593, Standard Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs. 29 8) F679, Standard Specification for Poly(Vinyl Chloride) (PVC) Large-Diameter 30

Plastic Gravity Sewer Pipe and Fittings. 31 9) F794, Standard Specification for Poly(Vinyl Chloride) (PVC) Profile Gravity 32

Sewer Pipe and Fittings Based on Controlled Inside Diameter. 33 10) F949, Standard Specification for Poly(Vinyl Chloride) (PVC) Corrugated Sewer 34

Pipe with a Smooth Interior and Fittings. 35 b. Installation: 36

1) D2321, Standard Practice for Underground Installation of Thermosplastic Pipe for 37 Sewers and Other Gravity-Flow Applications. 38

2. American Water Works Association (AWWA): 39 a. PVC (polyvinyl chloride) materials: 40

1) C900, Standard for Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated 41 Fittings, 4 IN Through 12 IN, for Water Distribution. 42

2) C905, Standard for Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated 43 Fittings, 14 IN through 48 IN, for Water Transmission and Distribution. 44

b. Polyethylene (PE) materials: 45 1) C901, Standard for Polyethylene (PE) Pressure Pipe and Tubing, 1/2 IN through 46

3 IN, for Water Service. 47 3. NSF International (NSF). 48

Page 212: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: PLASTIC 15064 - 2

1.3 SUBMITTALS 1

A. See Specification Section 01340 for requirements for the mechanics and administration of the 2 submittal process. 3

B. See Specification Section 15060. 4

PART 2 - PRODUCTS 5

2.1 PVC PRESSURE PIPING (EXPOSED) 6

A. General: 7 1. Provide Schedule 80 pipe with Schedule 80 fittings and appurtenances to locations shown 8

on Drawings. 9 2. Furnish materials in full compliance to following material specifications: 10

a. Manufacture pipe, fittings and appurtenances from polyvinyl chloride (PVC) compound 11 which meets the requirements of Type 1, Grade 1 (12454-B) Polyvinyl Chloride as 12 outlined in ASTM D1784. 13

b. Manufacture pipe, fittings and valves from materials that have been tested and 14 approved for conveying potable water by the NSF. 15

B. Pipe: 16 1. Furnish pipe meeting requirements of ASTM D1785. 17 2. Pipe 2 IN and less to be solvent welded. 18 3. Pipe larger than 2 IN may be either flanged or solvent welded unless shown otherwise on 19

Drawings. 20

C. Fittings: Provide ASTM D2467 PVC socket type fittings having the same pressure and 21 temperature rating as the pipe. 22

D. Flanges/Unions: 23 1. Furnish flanges and unions at locations shown on Drawings. 24 2. Provide either flanges or unions at valves, penetrations through structures and equipment 25

connections. 26 3. For pipe larger than 2 IN, provide 150 LB socket type PVC flange. 27 4. For pipe 2 IN and less, provide socket type PVC union with Buna O-rings. 28 5. Use flat, full faced natural rubber gaskets at flanged connections. 29

a. Furnish heavy hex head bolts, each with one (1) heavy hex nut, ASTM F593 Type 316 30 stainless steel. 31

6. Use spacers supplied by pipe manufacturer when mating raised-faced flanges to other 32 flanges. 33

E. Installation: 34 1. Field threading PVC will not be permitted. 35

a. Perform required threaded connections or attachments by the use of factory molded 36 socket by threaded adapters. 37

b. Female adapters are not acceptable. 38 2. Employ installation and pipe support practices and solvent welding all in compliance to the 39

manufacturer's printed recommendation. 40 a. Continuously support PVC piping at liquid operating temperatures in excess of 41

100 DegF. 42 b. For vertical piping, band the pipe at intervals to rigidly support load of twice vertical 43

load. 44 c. Support riser clamps on spring hangers. 45 d. Do not clamp PVC tightly or restrict movement for expansion and contraction. 46

Page 213: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: PLASTIC 15064 - 3

2.2 PRESSURE PIPING (UNDERGROUND) 1

A. Materials: Furnish materials in full compliance with following requirements: 2 1. 1/2-3 IN: AWWA C901 PE with Pressure Class of 200 psi per Table A3, AWWA C901. 3 2. 4-12 IN: AWWA C900 PVC with Pressure Class of 200 psi per Table 2, AWWA C900. 4 3. Joints for polyethylene pipe shall be fusion type in accordance with AWWA C901. 5 4. Joints for PVC pipe shall be the elastomeric-gasket type with a pressure rating not less than 6

pipe pressure rating meeting performance requirements of ASTM D3139. 7

B. Installation: 8 1. Field threading of PVC pipe will not be permitted. 9 2. Perform installation procedures, handling, thrust blocking, connections, and other 10

appurtenant operations in full compliance to the manufacturer's printed recommendations 11 and in full observance to plan details when more stringent. 12

2.3 PVC DRAINAGE, SEWER PIPING AND UNDERGROUND AIR DUCTS 13

A. Materials: 14 1. Furnish materials in full compliance to the following material specification. 15 2. PVC pipe shall be rigid, unplasticized polyvinyl chloride (PVC) made of PVC plastic 16

having a cell classification of 12454-B or 12454-C as described in specification 17 ASTM D1784. 18

3. The requirements of this Specification are intended to provide for pipe and fittings suitable 19 for non-pressure drainage of wastewater and surface water. 20

4. Joining systems shall consist of an elastomeric gasket joint meeting requirements of 21 ASTM D3212. 22

5. Supply to the Engineer all information and sample of joining method for his evaluation. 23 a. Only jointing methods acceptable to the Engineer will be permitted. 24

6. Provide pipe and fittings meeting or exceeding the following requirements: 25 a. 4-27 IN DIA: ASTM D3034 and ASTM F679, SDR 35. 26 b. 8-30 IN DIA: ASTM F794. 27 c. 4-18 IN DIA: ASTM F949. 28

7. Ensure impact strengths and pipe stiffnesses in full compliance to these Specifications. 29

B. Installation: Install pipe and fittings in accordance with ASTM D2321 and as recommended by 30 the manufacturer. 31 1. Provide for a maximum deflection of not more than 5 percent. 32

C. Infiltration and Exfiltration: 33 1. The maximum allowable infiltration measured by test shall not exceed 100 GAL per inch of 34

pipe diameter per mile per 24 HRS. 35 2. For exfiltration, all the pipe and fittings shall exceed performance requirements by an air 36

test procedure as specified in Section 15060. 37 3. Observe full instructions of the Engineer for carrying of testing procedures. 38

a. Perform tests only during presence of the Engineer or his authorized representative. 39 4. Should any test on any section of pipe line disclose either infiltration rates greater than 40

allowed or disclose air loss rate greater than that permitted, locate and repair the defective 41 joints or pipes at no cost to Owner and retest until requirements stated are met. 42

D. Deflection: 43 1. After backfilling, each section of pipe shall be checked for deflection by pulling a mandrel 44

through the pipe. 45 2. Pipe with deflection exceeding 5 percent of the inside diameter shall have backfill removed 46

and replaced to provide a deflection of less than 5 percent. 47 3. Any repaired pipe shall be retested. 48

2.4 PVC TUBING 49

A. General: Provide nylon tubing with fittings and appurtenances as shown on Drawings. 50

Page 214: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: PLASTIC 15064 - 4

B. Materials: 1 1. Furnish clear outer braided tubing with braid outside the walls. 2 2. Have tubing manufactured of nylon with working temperatures from 5 to 180 DegF. 3 3. Design tubing with a minimum safety factor of 4 to 1 ratio of burst pressure to working 4

pressure at maximum temperature. 5 4. Provide tubing with working pressure of 75 psi at 180 DegF. 6 5. Ensure that tubing is self-extinguishing and fire resistant. 7

C. Fittings: 8 1. Install tubing with nylon fittings and connectors. 9 2. Use barbed type adapters with stainless steel clamps. 10 3. Provide fittings capable of withstanding temperatures from a -70 to 250 DegF. 11 4. Ensure fittings have the same pressure and temperature rating as the tubing. 12

PART 3 - EXECUTION 13

3.1 IDENTIFICATION 14

A. Identify each length of pipe clearly at intervals of 5 FT or less. 15 1. Include manufacturer's name and trademark. 16 2. Nominal size of pipe, appurtenant information regarding polymer cell classification and 17

critical identifications regarding performance specifications and NSF approvals when 18 applicable. 19

3.2 PRESSURE PIPING (UNDERGROUND) 20

A. Installation: 21 1. Field threading of PVC pipe will not be permitted. 22 2. Perform installation procedures, handling, thrust blocking, connections, and other 23

appurtenant operations in full compliance to the manufacturer's printed recommendations 24 and in full observance to plan details when more stringent. 25

3.3 PVC DRAINAGE, SEWER PIPING AND UNDERGROUND AIR DUCTS 26

A. Installation: Install pipe and fittings in accordance with ASTM D2321 and as recommended by 27 the manufacturer. 28 1. Provide for a maximum deflection of not more than 5 percent. 29

B. Infiltration and Exfiltration: 30 1. The maximum allowable infiltration measured by test shall not exceed 100 GAL per inch of 31

pipe diameter per mile per 24 HRS. 32 2. For exfiltration, all the pipe and fittings shall exceed performance requirements by an air 33

test procedure as specified in Section 15060. 34 3. Observe full instructions of the Engineer for carrying of testing procedures. 35

a. Perform tests only during presence of the Engineer or his authorized representative. 36 4. Should any test on any section of pipe line disclose either infiltration rates greater than 37

allowed or disclose air loss rate greater than that permitted, locate and repair the defective 38 joints or pipes at no cost to Owner and retest until requirements stated are met. 39

C. Deflection: 40 1. After backfilling, each section of pipe shall be checked for deflection by pulling a mandrel 41

through the pipe. 42 2. Pipe with deflection exceeding 5 percent of the inside diameter shall have backfill removed 43

and replaced to provide a deflection of less than 5 percent. 44 3. Any repaired pipe shall be retested. 45

Page 215: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: PLASTIC 15064 - 5

3.4 PVC TUBING 1

A. Fittings: 2 1. Install tubing with nylon fittings and connectors. 3 2. Use barbed type adapters with stainless steel clamps. 4 3. Provide fittings capable of withstanding temperatures from a -70 to 250 DegF. 5 4. Ensure fittings have the same pressure and temperature rating as the tubing. 6

END OF SECTION 7

8

Page 216: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE: PLASTIC 15064 - 6

1

Page 217: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE SUPPORT SYSTEMS 15090 - 1

2014/08/26 1

SECTION 15090 2

PIPE SUPPORT SYSTEMS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Pipe support and anchor systems. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 09905 - Painting and Protective Coatings. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. American Society of Mechanical Engineers (ASME): 14

a. B31.1, Power Piping. 15 b. B31.3, Process Piping. 16

2. ASTM International (ASTM): 17 a. A36, Standard Specification for Carbon Structural Steel. 18 b. A575, Standard Specification for Steel Bars, Carbon, Merchant Quality, M-Grades. 19 c. A576, Standard Specification for Steel Bars, Carbon, Hot-Wrought, Special Quality. 20

3. American Welding Society (AWS): 21 a. D1.1, Structural Welding Code - Steel. 22

4. Manufacturers Standardization Society of the Valve and Fittings Industry Inc. (MSS): 23 a. SP-58, Pipe Hangers and Supports - Materials, Design and Manufacture. 24 b. SP-69, Pipe Hangers and Supports - Selection and Application. 25

1.3 SUBMITTALS 26

A. Shop Drawings: 27 1. See Specification Section 01340 for requirements for the mechanics and administration of 28

the submittal process. 29 2. Product technical data including: 30

a. Acknowledgement that products submitted meet requirements of standards referenced. 31 b. Manufacturer's installation instructions. 32 c. Itemized list of wall sleeves, anchors, support devices and all other items related to pipe 33

support system. 34 d. Scale drawings showing guides, hangers, supports, anchors, structural members and 35

appurtenances to describe the pipe support system. 36

PART 2 - PRODUCTS 37

2.1 ACCEPTABLE MANUFACTURERS 38

A. Subject to compliance with the Contract Documents, the manufacturers listed in the applicable 39 Articles below are acceptable. 40

B. Submit request for substitution in accordance with Specification Section 01640. 41

Page 218: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE SUPPORT SYSTEMS 15090 - 2

2.2 MANUFACTURED UNITS 1

A. Hanger Rods: 2 1. Material: 3

a. ASTM A36. 4 b. ASTM A510, Grade 1020. 5 c. ASTM A575, Grade M1020. 6 d. ASTM A576, Grade 1020. 7 e. Minimum allowable tensile stress of 12,000 psi at 650 DegF per MSS SP-58. 8

2. Continuously threaded. 9 3. Electro-galvanized or cadmium plated after threads are cut. 10 4. Load limit: 11

12 NOMINAL ROD DIAMETER MAXIMUM SAFE LOAD, (LBS)

3/8 IN DIA (min) 610 1/2 IN DIA 1,130 5/8 IN DIA 1,810 3/4 IN DIA 2,710 7/8 IN DIA 3,770 1 IN DIA 4,960

13

B. Hangers: 14 1. Hangers for use directly on copper pipe: Copper or cadmium plated. 15 2. Hangers for use other than directly on copper pipe: Cadmium plated or galvanized. 16 3. Hanger type schedule: 17

18 APPLICATION PIPE SIZE HANGER TYPE

All except noted 4 IN and less ANVIL Figure 108 with Figure 114 All except noted Over 4 IN ANVIL Figure 590 Steam, condensate and hot water All ANVIL Figure 181, Figure 82

19

C. Concrete Inserts for Hanger Rods: 20 1. Continuous slots: Unistrut #P1000. 21 2. Individual inserts: ANVIL Figure 281. 22 3. Self-drilling expansion anchors: Phillips flush-end or snap-off end type. 23

D. Beam Clamps for Hanger Rods: 24 1. Heavy duty. 25 2. ANVIL Figure 134. 26

E. Trapeze Hangers for Suspended Piping: 27 1. Material: Steel. 28 2. Galvanized. 29 3. Angles, channels, or other structural shapes. 30 4. Curved roller surfaces at support point corresponding with type of hanger required. 31

F. Vertical Pipe Supports: 32 1. At base of riser. 33 2. Lateral movement: 34

a. Clamps or brackets: 35 1) ANVIL Figure 103. 36

G. Expanding Pipe Supports: 37 1. Spring hanger type. 38 2. MSS SP-58. 39

Page 219: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE SUPPORT SYSTEMS 15090 - 3

H. Pipe Support Saddle: 1 1. For pipe located 3 FT or less from floor elevation, except as otherwise indicated on 2

Drawings. 3 2. ANVIL Figure 264. 4

I. Pipe Support Risers: 5 1. Schedule 40 pipe. 6 2. Galvanized. 7 3. As recommended by saddle manufacturer. 8

J. Pipe Support Base Plate: 9 1. 4 IN larger than support. 10 2. Collar 3/16 IN thickness, circular in shape, and sleeve type connection to pipe. 11 3. Collar fitted over outside of support pipe and extended 2 IN from floor plate. 12 4. Collar welded to floor plate. 13 5. Edges ground smooth. 14 6. Assembly hot-dipped galvanized after fabrication. 15

K. Pipe Covering Protection Saddle: 16 1. For insulated pipe at point of support. 17 2. ANVIL Figure 167, Type B. 18

L. Wall Brackets: 19 1. For pipe located near walls and 8 FT or more above floor elevation or as otherwise indicated 20

on the Drawings. 21 2. ANVIL Figure 199. 22

M. Pipe Anchors: 23 1. For locations shown on the Drawings. 24 2. 1/4 IN steel plate construction. 25 3. Hot-dipped galvanized after fabrication. 26 4. Designed to prevent movement of pipe at point of attachment. 27

N. Pipe Guides: 28 1. For locations on both sides on each expansion joint or loop. 29 2. To ensure proper alignment of expanding or contracting pipe. 30 3. ANVIL Figure 256. 31

2.3 DESIGN REQUIREMENTS 32

A. Supports capable of supporting the pipe for all service and testing conditions. 33 1. Provide 5 to 1 safety factor. 34

B. Allow free expansion and contraction of the piping to prevent excessive stress resulting from 35 service and testing conditions or from weight transferred from the piping or attached equipment. 36

C. Design supports and hangers to allow for proper pitch of pipes. 37

D. For chemical and waste piping, design, materials of construction and installation of pipe 38 hangers, supports, guides, restraints, and anchors: 39 1. ASME B31.3. 40 2. MSS SP-58 and MSS SP-69. 41 3. Except where modified by this Specification. 42

E. For steam and hot and cold water piping, design, materials of construction and installation of 43 pipe hangers, supports, guides, restraints, and anchors: 44 1. ASME B31.1. 45 2. MSS SP-58 and MSS SP-69. 46

F. Check all physical clearances between piping, support system and structure. 47 1. Provide for vertical adjustment after erection. 48

Page 220: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE SUPPORT SYSTEMS 15090 - 4

G. Support vertical pipe runs in pipe chases at base of riser. 1 1. Support pipes for lateral movement with clamps or brackets. 2

H. Place hangers on outside of pipe insulation. 3 1. Use a pipe covering protection saddle for insulated pipe at support point. 4 2. Insulated piping 1-1/2 IN and less: Provide a 9 IN length of 9 LB density fiberglass 5

insulation at saddle. 6 3. Insulated piping over 1-1/2 IN: Provide a 12 IN length of 9 LB density fiberglass insulation 7

on saddle. 8

I. Provide 20 GA galvanized steel pipe saddle for fiberglass and plastic support points to ensure 9 minimum contact width of 4 IN. 10

J. Pipe Support Spacing: 11 1. General: 12

a. Factor loads by specific weight of liquid conveyed if specific weight is greater than 13 water. 14

b. Locate pipe supports at maximum spacing scheduled unless indicated otherwise on the 15 Drawings. 16

c. Provide at least one (1) support for each length of pipe at each change of direction and 17 at each valve. 18

2. Steel, stainless steel, cast-iron pipe support schedule: 19 20

PIPE SIZES - IN MAXIMUM SPAN - FT 1-1/2 and less 5

2 thru 4 10 5 thru 8 15

10 and greater 20 21

3. Copper pipe support schedule: 22 23

PIPE SIZES - IN MAXIMUM SPAN - FT 2-1/2 and less 5

3 thru 6 10 8 and greater 15

24 4. PVC pipe support schedule: 25

26 PIPE SIZES - IN MAXIMUM SPAN - FT

1-1/4 and less 3 1-1/2 thru 3 4 4 and greater 5

* Maximum fluid temperature of 120 DegF. 27 28

5. Support each length and every fitting: 29 a. Bell and spigot piping: 30

1) At least one (1) hanger. 31 2) Applied at bell. 32

b. Mechanical coupling joints: 33 1) Place hanger within 2 FT of each side of fittings to keep pipes in alignment. 34

6. Space supports for soil and waste pipe and other piping systems not included above every 35 5 FT. 36

7. Provide continuous support for nylon tubing. 37

Page 221: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE SUPPORT SYSTEMS 15090 - 5

PART 3 - EXECUTION 1

3.1 INSTALLATION 2

A. Provide piping systems exhibiting pulsation, vibration, swaying, or impact with suitable 3 constraints to correct the condition. 4 1. Included in this requirement are movements from: 5

a. Trap discharge. 6 b. Water hammer. 7 c. Similar internal forces. 8

B. Weld Supports: 9 1. AWS D1.1. 10 2. Weld anchors to pipe in accordance with ASME B31.3. 11

C. Locate piping and pipe supports as to not interfere with open accesses, walkways, platforms, and 12 with maintenance or disassembly of equipment. 13

D. Inspect hangers for: 14 1. Design offset. 15 2. Adequacy of clearance for piping and supports in the hot and cold positions. 16 3. Guides to permit movement without binding. 17 4. Adequacy of anchors. 18

E. Inspect hangers after erection of piping systems and prior to pipe testing and flushing. 19

F. Install individual or continuous slot concrete inserts for use with hangers for piping and 20 equipment. 21 1. Install concrete inserts as concrete forms are installed. 22

G. Welding: 23 1. Welding rods: ASTM and AWS standards. 24 2. Integral attachments: 25

a. Include welded-on ears, shoes, plates and angle clips. 26 b. Ensure material for integral attachments is of good weldable quality. 27

3. Preheating, welding and postheat treating: ASME B31.3, Chapter V. 28

H. Field Painting: 29 1. Comply with Specification Section 09905. 30

END OF SECTION 31

32

Page 222: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE SUPPORT SYSTEMS 15090 - 6

1

Page 223: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VALVES: BASIC REQUIREMENTS 15100 - 1

2014/08/26 1

SECTION 15100 2

VALVES: BASIC REQUIREMENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Valving, actuators, and valving appurtenances. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 09905 - Painting and Protective Coatings. 11 4. Section 11005 - Equipment: Basic Requirements. 12 5. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. American Society of Mechanical Engineers (ASME): 16

a. B1.20.1, Pipe Threads, General Purpose. 17 b. B16.1, Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250. 18 c. B16.18, Cast Copper Alloy Solder Joint Pressure Fittings. 19

2. ASTM International (ASTM): 20 a. A126, Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe 21

Fittings. 22 b. D256, Standard Test Methods for Determining the Izod Pendulum Impact Resistance of 23

Plastics. 24 c. D638, Standard Test Method for Tensile Properties of Plastics. 25 d. D648, Standard Test Method for Deflection Temperature of Plastics Under Flexural 26

Load in the Edgewise Position. 27 e. D695, Standard Test Method for Compressive Properties of Rigid Plastics. 28 f. D2240, Standard Test Method for Rubber Property-Durometer Hardness. 29

3. American Water Works Association (AWWA): 30 a. C207, Standard for Steel Pipe Flanges for Waterworks Service - Sizes 4 IN through 31

144 IN. 32 b. C500, Standard for Metal-Seated Gate Valves for Water Supply Service. 33 c. C504, Standard for Rubber-Seated Butterfly Valves. 34 d. C507, Standard for Ball Valves, 6 IN through 48 IN (150 MM through 1200 MM). 35 e. C509, Standard for Resilient-Seated Gate Valves for Water Supply Service. 36 f. C542, Standard for Electric Motor Actuators for Valves and Slide Gates. 37 g. C550, Standard for Protective Coatings for Valves and Hydrants. 38 h. C606, Standard for Grooved and Shouldered Joints. 39

4. American Water Works Association/American National Standards Institute 40 (AWWA/ANSI): 41 a. C111/A21.11, Standard for Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and 42

Fittings. 43 5. National Electrical Manufacturers Association (NEMA): 44

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 45 b. MG 1, Motors and Generators. 46

Page 224: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VALVES: BASIC REQUIREMENTS 15100 - 2

1.3 DEFINITIONS 1

A. The following are definitions of abbreviations used in this Specification Section or one (1) of the 2 individual valve sections: 3 1. CWP: Cold water working pressure. 4 2. SWP: Steam working pressure. 5 3. WOG: Water, oil, gas working pressure. 6 4. WWP: Water working pressure. 7

1.4 SUBMITTALS 8

A. Shop Drawings: 9 1. See Specification Section 01340 for requirements for the mechanics and administration of 10

the submittal process. 11 2. Product technical data including: 12

a. Acknowledgement that products submitted meet requirements of standards referenced. 13 b. Manufacturer's installation instructions. 14 c. Valve pressure and temperature rating. 15 d. Valve material of construction. 16 e. Special linings. 17 f. Valve dimensions and weight. 18 g. Valve flow coefficient. 19 h. Wiring and control diagrams for electric or cylinder actuators. 20

3. Test reports. 21

B. Operation and Maintenance Manuals: 22 1. See Specification Section 01342 for requirements for: 23

a. The mechanics and administration of the submittal process. 24 b. The content of Operation and Maintenance Manuals. 25

C. Informational Submittals: 26 1. Verification from valve actuator manufacturer that actuators have been installed properly, 27

that all limit switches and position potentiometers have been properly adjusted, and that the 28 valve actuator responds correctly to the valve position command. 29

PART 2 - PRODUCTS 30

2.1 ACCEPTABLE MANUFACTURERS 31

A. Subject to compliance with the Contract Documents, refer to individual valve Specification 32 Sections for acceptable manufacturers. 33

2.2 MATERIALS 34

A. Refer to individual valve Specification Sections. 35

2.3 VALVE ACTUATORS 36

A. Valve Actuators - General: 37 1. Provide actuators as shown on Drawings or specified. 38 2. Counter clockwise opening as viewed from the top. 39 3. Direction of opening and the word OPEN to be cast in handwheel or valve bonnet. 40 4. Size actuator to produce required torque with a maximum pull of 80 LB at the maximum 41

pressure rating of the valve provided and withstand without damage a pull of 200 LB on 42 handwheel or chainwheel or 300 foot-pounds torque on the operating nut. 43

5. Unless otherwise specified, actuators for valves to be buried, submerged or installed in 44 vaults or manholes shall be sealed to withstand at least 20 FT of submergence. 45

Page 225: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VALVES: BASIC REQUIREMENTS 15100 - 3

6. Extension stem: 1 a. Install where shown or specified. 2 b. Solid steel with actuator key and nut, diameter not less than stem of valve actuator 3

shaft. 4 c. Pin all stem connections. 5 d. Center in valve box or grating opening band with guide bushing. 6

B. Buried Valve Actuators: 7 1. Provide screw or slide type adjustable cast iron valve box, 5 IN minimum diameter, 3/16 IN 8

minimum thickness, and identifying cast iron cover rated for traffic load. 9 2. Box base to enclose buried valve gear box or bonnet. 10 3. Provide 2 IN standard actuator nuts complying with AWWA C500, Section 3.16. 11 4. Provide at least two (2) tee handle keys for actuator nuts, with 5 FT extension between key 12

and handle. 13 5. Extension stem: 14

a. Provide for buried valves greater than 4 FT below finish grade. 15 b. Extend to within 6 IN of finish grade. 16

6. Provide concrete pad encasement of valve box as shown for all buried valves unless shown 17 otherwise. 18

C. Exposed Valve Manual Actuators: 19 1. Provide for all exposed valves not having electric or cylinder actuators. 20 2. Provide handwheels for gate and globe valves. 21

a. Size handwheels for valves in accordance with AWWA C500. 22 3. Provide lever actuators for plug valves, butterfly valves and ball valves 3 IN DIA and 23

smaller. 24 a. Lever actuators for butterfly valves shall have a minimum of 5 intermediate lock 25

positions between full open and full close. 26 b. Provide at least two (2) levers for each type and size of valve furnished. 27

4. Gear actuators required for plug valves, butterfly valves, and ball valves 4 IN DIA and 28 larger. 29

5. Provide gearing for gate valves 20 IN and larger in accordance with AWWA C500. 30 6. Gear actuators to be totally enclosed, permanently lubricated and with sealed bearings. 31 7. Provide chain actuators for valves 6 FT or higher from finish floor to valve centerline. 32

a. Cadmium-plated chain looped to within 3 FT of finish floor. 33 b. Equip chain wheels with chain guides to permit rapid operation with reasonable side 34

pull without "gagging" the wheel. 35 8. Provide cast iron floor stands where shown on Drawings. 36

a. Stands to be furnished by valve manufacturer with actuator. 37 b. Stands or actuator to include thrust bearings for valve operation and weight of 38

accessories. 39

D. Submerged Actuators: 40 1. Mount the valve actuator on top of an extension bonnet 3 FT above any adjacent personnel 41

access. 42 2. The valve and bonnet connection shall be flanged and watertight. 43 3. Provide a top brace support and intermediate support(s). 44

a. Install intermediate supports per manufacturer’s recommendations. 45 4. Materials: 46

a. Brace supports and anchor bolts: Type 304 stainless steel. 47

2.4 FABRICATION 48

A. End Connections: 49 1. Provide the type of end connections for valves as required in the Piping Schedules presented 50

in Specification Section 15060 or as shown on the Drawings. 51 2. Comply with the following standards: 52

a. Threaded: ASME B1.20.1. 53

Page 226: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VALVES: BASIC REQUIREMENTS 15100 - 4

b. Flanged: ASME B16.1, Class 125 unless otherwise noted or AWWA C207. 1 c. Bell and spigot or mechanical (gland) type: AWWA/ANSI C111/A21.11. 2 d. Soldered: ASME B16.18. 3 e. Grooved: Rigid joints per Table 5 of AWWA C606. 4

B. Refer to individual valve Specification Sections for specifications of each type of valve used on 5 Project. 6

C. Nuts, Bolts, and Washers: 7 1. Wetted or internal to be bronze or stainless steel. 8

a. Exposed to be zinc or cadmium plated. 9

D. On Insulated Piping: Provide valves with extended stems to permit proper insulation application 10 without interference from handle. 11

E. Epoxy Interior Coating: Provide epoxy interior coating for all ferrous surfaces in accordance 12 with AWWA C550. 13

PART 3 - EXECUTION 14

3.1 INSTALLATION 15

A. Install products in accordance with manufacturer's instructions. 16

B. Painting Requirements: Comply with Specification Section 09905 for painting and protective 17 coatings. 18

C. Setting Buried Valves: 19 1. Locate valves installed in pipe trenches where buried pipe indicated on Drawings. 20 2. Set valves and valve boxes plumb. 21 3. Place valve boxes directly over valves with top of box being brought to surface of finished 22

grade. 23 4. Install in closed position. 24 5. Place valve on firm footing in trench to prevent settling and excessive strain on connection 25

to pipe. 26 6. After installation, backfill up to top of box for a minimum distance of 4 FT on each side of 27

box. 28

D. Support exposed valves and piping adjacent to valves independently to eliminate pipe loads 29 being transferred to valve and valve loads being transferred to the piping. 30

E. For grooved coupling valves, install rigid type couplings. 31

F. Install electric or cylinder actuators above or horizontally adjacent to valve and gear box to 32 optimize access to controls and external handwheel. 33

G. For threaded valves, provide union on one (1) side within 2 FT of valve to allow valve removal. 34

H. Install valves accessible for operation, inspection, and maintenance. 35

3.2 ADJUSTMENT 36

A. Adjust valves, actuators and appurtenant equipment to comply with Specification Section 01650. 37 1. Operate valve, open and close at system pressures. 38

3.3 SCHEDULES 39

A. Valves less than 4 IN may not be scheduled but type and size are defined on Drawings in plan, 40 section, isometric or schematic. 41

B. Mechanical valves are not scheduled but type and size are defined on Drawings in plan, section, 42 isometric or schematic. 43

Page 227: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VALVES: BASIC REQUIREMENTS 15100 - 5

C. Column "Remote or Integral Operation" refers to operator's position when valve is operated (i.e., 1 handwheel/lever, chainwheel, pushbutton, etc.). 2

D. See Section 15060 and the Drawings for Piping Service designations. 3

E. Unless shown otherwise on Drawings and Drawing schedules, provide valves as shown in 4 schedule attached at the end of this Section. 5

F. The attached schedule is provided to assist the Contractor in identifying manual valves 4 IN and 6 greater in size and control valves. 7 1. Manual valves below 4 IN in size are defined at other locations in the Contract Documents. 8 2. The Contractor shall not use this schedule as a bill of materials but shall review the Contract 9

Documents in their entirety to establish the number, sizes and types of valves on the project. 10 3. Valves not listed generally include small valves and certain valves furnished as components 11

in items of equipment. 12 4. The Contractor is responsible for furnishing all valves to provide a complete, ready-to-13

operate facility. 14

END OF SECTION 15

16

Page 228: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VALVES: BASIC REQUIREMENTS 15100 - 6

1

Page 229: City of Yankton, SD

City of Yankton, SD - Water System Improvements, Horizontal Collector Well - Process Valve Schedule

Valve Location Size Type ActuatorExposed/

Buried Joints

PCV01 Collector Well Pump No. 1 Pump Control Valve 16 Diaphragm Solenoid/Automatic Exposed FlangedPCV02 Collector Well Pump No. 2 Pump Control Valve 16 Diaphragm Solenoid/Automatic Exposed FlangedPCV03 Collector Well Pump No. 3 Pump Control Valve 16 Diaphragm Solenoid/Automatic Exposed FlangedBFV01 Collector Well Pump No. 1 Isolation Valve 16 AWWA Butterfly Manual Exposed FlangedBFV02 Collector Well Pump No. 2 Isolation Valve 16 AWWA Butterfly Manual Exposed FlangedBFV03 Collector Well Pump No. 3 Isolation Valve 16 AWWA Butterfly Manual Exposed FlangedBFV04 Future Collector Well Pump No. 4 Isolation Valve 16 AWWA Butterfly Manual Exposed Flanged

CWGV01 Collector Well Gate Valve No. 1 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV02 Collector Well Gate Valve No. 2 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV03 Collector Well Gate Valve No. 3 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV04 Collector Well Gate Valve No. 4 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV05 Collector Well Gate Valve No. 5 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV06 Collector Well Gate Valve No. 6 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV07 Collector Well Gate Valve No. 7 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV08 Collector Well Gate Valve No. 8 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV09 Collector Well Gate Valve No. 9 12 RW Gate Valve Manual W/Extension Stem Exposed Flanged

CWGV010 Collector Well Gate Valve No. 10 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV011 Collector Well Gate Valve No. 11 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV012 Collector Well Gate Valve No. 12 12 RW Gate Valve Manual W/Extension Stem Exposed FlangedCWGV013 Collector Well Gate Valve No. 13 12 RW Gate Valve Manual W/Extension Stem Exposed Flanged

AVV01 Collector Well Pump No. 1 Air/Vacuum Valve 3 Air/Vacuum Valve Automatic Exposed FlangedAVV02 Collector Well Pump No. 2 Air/Vacuum Valve 3 Air/Vacuum Valve Automatic Exposed FlangedAVV03 Collector Well Pump No. 3 Air/Vacuum Valve 3 Air/Vacuum Valve Automatic Exposed FlangedAVV05 Main Discharge Header Air/Vacuum Valve 6 Air/Vacuum Valve Automatic Exposed Flanged

135-223788

City of Yankton, SD2014 Water Treatment Plant Improvements, Horizontal Collector Well -

VALVE SCHEDULE 15100A - 1

Page 230: City of Yankton, SD
Page 231: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GATE VALVES 15101 - 1

2014/08/28 1

SECTION 15101 2

GATE VALVES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Gate valves. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 15100 - Valves: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. ASTM International (ASTM): 14

a. A126, Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe 15 Fittings. 16

2. American Water Works Association (AWWA): 17 a. C500, Standard for Metal-Seated Gate Valves for Water Supply Service. 18 b. C504, Standard for Rubber-Seated Butterfly Valves. 19 c. C509, Standard for Resilient-Seated Gate Valves for Water Supply Service. 20 d. C550, Standard for Protective Epoxy Interior Coatings for Valves and Hydrants. 21

3. Manufacturers Standardization Society of the Valve and Fittings Industry Inc. (MSS): 22 a. SP-9, Spot Facing for Bronze, Iron and Steel Flanges. 23 b. SP-70, Cast Iron Gate Valves, Flanged and Threaded Ends. 24 c. SP-80, Bronze Gate, Globe, Angle and Check Valves. 25

1.3 DEFINITIONS 26

A. OS&Y: Outside Screw and Yoke. 27

B. NRS: Non-rising Stem. 28

C. RS: Rising Stem. 29

1.4 SUBMITTALS 30

A. Shop Drawings: 31 1. See Specification Section 01340 for requirements for the mechanics and administration of 32

the submittal process. 33 2. See Specification Section 15100. 34

B. Operation and Maintenance Manuals: 35 1. See Specification Section 01342 for requirements for: 36

a. The mechanics and administration of the submittal process. 37 b. The content of Operation and Maintenance Manuals. 38

Page 232: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GATE VALVES 15101 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the manufacturers listed in the applicable 3 Articles below are acceptable. 4

B. Submit request for substitution in accordance with Specification Section 01640. 5

2.2 VALVES: WATER; 2-1/2 IN AND SMALLER 6

A. Class 125 bronze gate valve. 7

B. Comply with MSS SP-80. 8

C. Materials: 9 1. Body, bonnet, wedge: Bronze. 10 2. Stem: Silicon bronze. 11 3. Packing: Aramid fibers with graphite (Kevlar®). 12

D. Design Requirements: 13 1. 125 psi steam, 200 psi nonshock WOG. 14 2. Screw in bonnet, non-rising stem, solid wedge. 15

E. Acceptable Manufacturers: 16 1. Nibco. 17 2. Stockham. 18

2.3 VALVES: WATER (HOT, COLD, HEATING, COOLING, SERVICE, PROCESS, 19 POTABLE, AND NON-POTABLE) 20

A. Double Disc Gate Valve, 3 to 12 IN (Water Application): 21 1. Comply with AWWA C500. 22 2. Materials: 23

a. Seating surfaces, stems, stem nut: Bronze. 24 b. Body, disc: Cast iron. 25

3. Design requirements: 26 a. 200 psi working pressure. 27 b. Buried: NRS, O-ring stem seal, 2 IN operation nut. 28 c. Exposed: NRS, O-ring stem seal, handwheel. 29

4. Acceptable manufacturers: 30 a. American Flow Control. 31 b. Clow. 32 c. M&H. 33 d. Mueller. 34

B. Resilient Wedge Gate Valves, 2 to 48 IN (Water, Wastewater Application): 35 1. Comply with AWWA C509. 36 2. Materials: 37

a. Stem and stem nut: Bronze. 38 1) Wetted bronze parts in low zinc bronze. 39 2) Aluminum bronze components: Heat treated per AWWA C504. 40

b. Body, gate: Cast iron. 41 c. Resilient wedge: Styrene Butadiene Rubber (SBR). 42

3. Design requirements: 43 a. Minimum 200 psi working pressure. 44 b. Buried: NRS, O-ring stem seal, 2 IN square operating nut. 45 c. Exposed: OS&Y, stuffing box stem seal, handwheel. 46 d. Submerged: RS, stuffing box stem seal. 47 e. Counter clockwise open rotation. 48

Page 233: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GATE VALVES 15101 - 3

f. Fusion bonded epoxy coating interior and exterior except stainless steel and bearing 1 surfaces. 2 1) Comply with AWWA C550. 3 2) Wetted bronze parts in low zinc bronze. 4 3) Aluminum bronze components: Heat treated per AWWA C504. 5

4. Acceptable manufacturers: 6 a. Clow. 7 b. Mueller. 8 c. American Flow Control. 9 d. M & H. 10

2.4 ACCESSORIES 11

A. Refer to Drawings and valve schedule for type of actuators. 12 1. Furnish actuator integral with valve. 13 2. Gate valves on the collector well laterals are to be provided with extensions stems with 2” 14

actuator nuts, guides, and bracing as shown on the drawings. 15

B. Refer to Specification Section 15100 for actuator requirements. 16

2.5 FABRICATION 17

A. General: 18 1. Provide valves with clear waterways the full diameter of the valve. 19

B. Spot valves in accordance with MSS SP-9. 20

PART 3 - EXECUTION 21

3.1 INSTALLATION 22

A. See Specification Section 15100. 23

B. Where larger buried valves utilize smaller bypass valves, provide a second valve box installed 24 over the bypass valve operating nut. 25

C. Do not install gate valves inverted or with the stems sloped more than 45 degrees from the 26 upright unless the valve was ordered and manufactured specifically for this orientation. 27

END OF SECTION 28

29

Page 234: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GATE VALVES 15101 - 4

1

Page 235: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BUTTERFLY VALVES 15103 - 1

2014/08/14 1

SECTION 15103 2

BUTTERFLY VALVES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Butterfly valves. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 11 4. Section 15100 - Valves: Basic Requirements. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. American Society of Mechanical Engineers (ASME): 15

a. B16.5, Pipe Flanges and Flanged Fittings - NPS 1/2 Through NPS 24. 16 2. ASTM International (ASTM): 17

a. A48, Standard Specification for Gray Iron Castings. 18 b. A126, Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe 19

Fittings. 20 c. A276, Standard Specification for Stainless Steel Bars and Shapes. 21 d. A395, Standard Specification for Ferritic Ductile Iron Pressure-Retaining Castings for 22

Use at Elevated Temperatures. 23 e. A436, Standard Specification for Austenitic Gray Iron Castings. 24 f. A536, Standard Specification for Ductile Iron Castings. 25 g. B148, Standard Specification for Aluminum-Bronze Sand Castings. 26

3. American Water Works Association (AWWA): 27 a. C504, Standard for Rubber-Seated Butterfly Valves. 28

4. Manufacturers Standardization Society of the Valve and Fittings Industry Inc. (MSS): 29 a. SP-67, Butterfly Valves. 30

1.3 SUBMITTALS 31

A. Shop Drawings: 32 1. See Specification Section 01340 for requirements for the mechanics and administration of 33

the submittal process. 34 2. See Specification Section 15100. 35 3. For valves 8 IN and larger, furnish "Affidavit of Compliance" with Owner in accordance 36

with AWWA C504. 37

B. Operation and Maintenance Manuals: 38 1. See Specification Section 01342 for requirements for: 39

a. The mechanics and administration of the submittal process. 40 b. The content of Operation and Maintenance Manuals. 41

Page 236: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BUTTERFLY VALVES 15103 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. DeZurik. 5 2. Clow. 6 3. Mueller. 7 4. Pratt. 8

B. Submit request for substitution in accordance with Specification Section 01640. 9

2.2 BUTTERFLY VALVES (AWWA C504) 10

A. Comply with AWWA C504. 11

B. Materials: 12 1. Valve bodies: 13

a. ASTM A126, Class B or ASTM A536 Grade 65-45-12 ductile iron. 14 b. Wafer valves may be constructed of ASTM A48, Class 40 cast iron. 15

2. Valve shafts: 16 a. Stainless steel, 18-8, Type 304 or 316. 17

3. Valve discs: 18 a. Potable and nonpotable water: 19

1) ASTM A48, Class 40 cast iron. 20 2) ASTM A536, Grade 65-45-12 ductile iron. 21 3) ASTM A436, Type 1 alloy cast iron. 22 4) Bronze in accordance with AWWA C504. 23

b. Air and similar applications: ASTM A48, Class 40 cast iron. 24 4. Valve seats: 25

a. Potable and nonpotable water below 150 DegF: 26 1) Natural rubber. 27

b. Potable and nonpotable water and air below 180 DegF: 28 1) Buna-N. 29

c. Heating water and air 180 to 250 DegF. 30 1) EPDM. 31

5. Mating surfaces: 32 a. Valves less than 30 IN: ASTM A276, 18-8, stainless steel or bronze. 33 b. Valves 30 IN and larger: ASTM A276, 18-8, stainless steel. 34

C. Design Requirements: 35 1. Seat type: 36

a. Resilient. 37 b. Comply with AWWA C504. 38

2. Exposed and submerged valves 3 through 20 IN. 39 a. Body type: Wafer or short body flange (laying length may vary from AWWA C504). 40 b. Equip wafer type with fully tapped anchor lugs drilled per ASME B16.5. 41

3. Exposed and submerged valves 24 IN and larger: 42 a. Body type: Short body flange. 43 b. Working pressure: Rated for 150 psi (Class 150B per AWWA C504). 44

4. Direct buried valves: 45 a. All valves: Working pressure rated for 150 psi (Class 150B per AWWA C504). 46

2.3 ACCESSORIES 47

A. Refer to Drawings and/or valve schedule for type of actuators. 48 1. Furnish actuator integral with valve. 49

Page 237: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BUTTERFLY VALVES 15103 - 3

B. Refer to Section 15100 for actuator requirements. 1

PART 3 - EXECUTION 2

3.1 INSTALLATION 3

A. See Section 15100. 4

END OF SECTIO 5

6

Page 238: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BUTTERFLY VALVES 15103 - 4

N1

Page 239: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BALL VALVES 15104 - 1

2014/08/26 1

SECTION 15104 2

BALL VALVES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Ball valves. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 15100 - Valves: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. ASTM International (ASTM): 14

a. A48, Standard Specification for Gray Iron Castings. 15 b. A126, Standard Specification for Gray Iron Castings for Valves, Flanges, and Pipe 16

Fittings. 17 c. D1784, Standard Specification for Rigid Poly(Vinyl Chloride) (PVC) Compounds and 18

Chlorinated Poly(Vinyl Chloride) (CPVC) Compounds. 19 2. American Water Works Association (AWWA): 20

a. C507, Standard for Ball Valves, 6 IN through 48 IN. 21 3. Federal Specification (FS): 22

a. WW-V-35C, Valve, Ball. 23

1.3 SUBMITTALS 24

A. Shop Drawings: 25 1. See Specification Section 01340 for requirements for the mechanics and administration of 26

the submittal process. 27 2. See Specification Section 15100. 28 3. Test results for AWWA valves. 29

B. Operation and Maintenance Manuals: 30 1. See Specification Section 01342 for requirements for: 31

a. The mechanics and administration of the submittal process. 32 b. The content of Operation and Maintenance Manuals. 33

PART 2 - PRODUCTS 34

2.1 ACCEPTABLE MANUFACTURERS 35

A. Subject to compliance with the Contract Documents, the manufacturers listed in the applicable 36 Articles below are acceptable. 37

B. Submit request for substitution in accordance with Specification Section 01640. 38

2.2 METALLIC BALL VALVES 1/4 TO 3 IN DIA 39

A. Comply with FS WW-V-35C Type II, Class A. 40

Page 240: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BALL VALVES 15104 - 2

B. Acceptable Manufacturers: 1 1. Apollo. 2 2. Jamesbury. 3 3. Watts. 4 4. Stockham. 5 5. Nibco. 6

C. Materials: 7 1. Body: Bronze. 8 2. Stem, stem gland nut: Brass. 9 3. Ball: Brass, chrome plated. 10 4. Seats, stuffing box ring, and thrust washer: Reinforced Teflon. 11 5. Handle: Vinyl coated or zinc- or cadmium-plated steel. 12

D. Design Requirements: 13 1. Rated for 400 psi and 250 DegF, WOG for threaded end applications and 285 psi WOG and 14

150 psi saturated steam service for flanged end applications. 15 2. Handles showing direction of opening. 16 3. Stuffing boxes capable of being repacked under pressure and adjustable for wear. 17 4. Stem with reinforced Teflon stuffing box ring and blowout-proof design. 18 5. Renewable reinforced Teflon seats. 19 6. Ball design which does not allow media contact with stem. 20 7. Balancing stop for all applications. 21 8. Bodies with mounting pad for applications requiring actuators. 22

2.3 PLASTIC BALL VALVES: 1/2 IN TO 4 IN DIA 23

A. Acceptable Manufacturers: 24 1. Chemtrol. 25 2. Spears. 26 3. ASAHI/America. 27

B. Materials: 28 1. Body, stem, ball, handle, end connectors: 29

a. PVC ASTM D1784-12454B or CPVC ASTM D1784-23447-B to match piping. 30 2. Ball Seat: Teflon. 31 3. O-rings: Viton. 32

C. Design Requirements: 33 1. Rated at 150 psi at 75 DegF. 34 2. Full round ball. 35 3. Double or "true union" design. 36 4. Blocks both directions, upstream and downstream. 37 5. Union nut capable of compensating for seat wear. 38 6. Body with mounting pad for actuators where required. 39 7. Capable of being disconnected at downstream end under full line pressure. 40

2.4 ACCESSORIES 41

A. Refer to Drawings and valve schedule for type of actuators. 42 1. Furnish actuator integral with valve. 43

B. Refer to Specification Section 15100 for actuator requirements. 44

2.5 SOURCE QUALITY CONTROL 45

A. Shop test AWWA C507 ball valves in accordance with AWWA C507. 46

B. Furnish record of test. 47

Page 241: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BALL VALVES 15104 - 3

PART 3 - EXECUTION 1

3.1 INSTALLATION 2

A. See Specification Section 15100. 3

3.2 FIELD QUALITY CONTROL 4

A. For AWWA C507 ball valves, and in accordance with Specification Section 01650 employ and 5 pay for services of equipment manufacturer's field service representative(s) to: 6 1. Inspect equipment covered by this Specification Section. 7 2. Supervise adjustments and installation checks. 8 3. Provide test equipment, tools, and instruments necessary to accomplish equipment testing. 9 4. Conduct startup of equipment and perform operational checks. 10 5. Provide Owner with a written statement that manufacturer's equipment has been installed 11

properly, has been started up, and is ready for operation by Owner's personnel. 12

END OF SECTION 13

14

Page 242: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - BALL VALVES 15104 - 4

1

Page 243: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CHECK VALVES 15106 - 1

2014/08/26 1

SECTION 15106 2

CHECK VALVES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Check valves. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 15100 - Valves: Basic Requirements. 10

1.2 QUALITY ASSURANCE 11

A. Referenced Standards: 12 1. American Society of Mechanical Engineers (ASME): 13

a. B16.1, Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250. 14 2. American Water Works Association (AWWA): 15

a. C508, Standard for Swing-Check Valves for Waterworks Service, 2 IN through 24 IN 16 NPS. 17

3. Manufacturers Standardization Society of the Valve and Fittings Industry Inc. (MSS): 18 a. SP-71, Cast Iron Swing Check Valves, Flanged and Threaded Ends. 19 b. SP-80, Bronze Gate, Globe, Angle and Check Valves. 20

1.3 DEFINITIONS 21

A. PVDF: Polyvinylidene fluoride. 22

1.4 SUBMITTALS 23

A. Shop Drawings: 24 1. See Specification Section 01340 for requirements for the mechanics and administration of 25

the submittal process. 26 2. See Specification Section 15100. 27

B. Operation and Maintenance Manuals: 28 1. See Specification Section 01342 for requirements for: 29

a. The mechanics and administration of the submittal process. 30 b. The content of Operation and Maintenance Manuals. 31

PART 2 - PRODUCTS 32

2.1 ACCEPTABLE MANUFACTURERS 33

A. Subject to compliance with the Contract Documents, manufacturers listed under the valve with 34 types are acceptable. 35

B. Submit request for substitution in accordance with Specification Section 01640. 36

2.2 CHECK VALVES: 2.5 IN AND SMALLER 37

A. Class 125 Bronze Swing Check Valves (Water): 38 1. Comply with MSS SP-80. 39

Page 244: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CHECK VALVES 15106 - 2

2. Acceptable manufacturers: 1 a. Nibco T413-Y. 2 b. Stockham B-319Y. 3

3. Materials: 4 a. Body, bonnet, disc: Bronze. 5

4. Design requirements: 6 a. 125 psi steam to 406 DegF, 200 psi WOG. 7 b. Horizontal swing, renewable disc. 8

2.3 SWING CHECK VALVES: 3 IN TO 24 IN 9

A. Swing Check Valves (Water): 10 1. Comply with AWWA C508. 11 2. Acceptable manufacturers: 12

a. Clow. 13 b. American Darling. 14 c. Golden Anderson. 15

3. Materials: 16 a. Body and cover: Cast iron. 17 b. Seat ring, hinge: Bronze. 18 c. Disc: 19

1) 3 to 4 IN: Bronze. 20 2) 6 to 24 IN: Cast iron with bronze face. 21 3) 6 to 24 IN: Cast iron with rubber face. 22

d. Hinge shaft: Stainless steel. 23 e. Bearings, connecting hardware: Bronze. 24

4. Design requirements: 25 a. 175 psi working pressure (3 to 12 IN). 26 b. 150 psi working pressure (14 to 24 IN). 27 c. Furnish with outside weight and lever or lever and spring. 28

2.4 BALL CHECK VALVES: 1/2 IN TO 4 IN 29

A. Smaller than 4 IN: 30 1. 150 psi at 73 DegF. 31 2. Acceptable manufacturers: 32

a. R&G Sloane. 33 b. Corr Tech. 34 c. Or approved equal. 35

3. Materials: 36 a. Body: PVDF. 37 b. Ball: PVDF. 38 c. Seals: Teflon. 39

4. Design requirements: 40 a. Connectors: Double union. 41

B. 4 IN through 14 IN: 42 1. 145 psi at 176 DegF. 43 2. Acceptable manufacturers: 44

a. Flygt. 45 b. Ball Check.com, Division of Process Equipment. 46 c. Or approved equal. 47

3. Materials: 48 a. Body and cover: Nodular cast iron. 49 b. Joints: 50

1) ASME B16.1, Class 125 flat face. 51 2) Bolt holds shall straddle valve centerline. 52

Page 245: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CHECK VALVES 15106 - 3

c. Ball: Metal core with vulcanized nitrile rubber covering. 1 4. Style: Manufacturer to select correct ball type and weight for intended fluid. 2 5. Fluid: Thickened lime sludge (20 percent solids maximum) from gravity thickeners and, 3

lime residual (5 percent solids maximum) from contact basins. 4 6. Installation: Able to be installed in either the vertical or horizontal position. 5

2.5 AUTOMATIC CONTROL VALVES (PUMP CONTROL VALVES, PCV01, PCV02, AND 6 PCV03) 7

A. Basic Valve: 8 1. Type: 9

a. Diaphragm-actuated hydraulically operated. 10 1) Acceptable manufacturers (Model as shown for specific valve): 11

a) Cla-Val Model 660-31. 12 b) Singer. 13

2) Pattern: Globe with flange end connections, 150 Class. 14 3) Materials: 15

a) Body: Ductile iron. 16 b) Disc retainer & diaphragm washer: Cast iron. 17 c) Seat insert: Stainless steel. 18 d) Stem, nut, and spring: Stainless Steel. 19 e) Disc: Buna-N. 20 f) Diaphragm: Nylon fabric bonded with synthetic rubber. 21

4) Design requirements: Do not use diaphragm as seating surface. 22 2. Design requirements: 23

a. Simple Hydraulic Operation. 24 b. Low Head Loss. 25 c. Built-in Check Valve 26 d. Size: 16 IN, reduced port. 27 e. Operating pressure: 28

1) Maximum 90 psi. 29 2) Minimum 55 psi. 30

f. Flow range: 31 1) Normal maximum 5,600 gpm. 32 2) Normal minimum 2,000 gpm. 33

B. Control: 34 1. Design requirements: 35

a. Control opening and closing speed of basic valve to minimize surge associated with 36 starting and stopping of a pump. See Section 13441 for control loop description. 37

b. Design normal opening and closing to be concurrent with pump operation. 38 c. Provide for a more rapid valve closure in event of power outage. 39 d. Provide adjustable controlled rates for all opening and closing speeds. 40

C. Design Requirements: 41 1. Assembles all control features and hardware on basic valve at factory. 42 2. Use corrosion-resistant metal for all exposed portions of the control. 43 3. Include with valve control: 44

a. Stop valves. 45 b. Strainer. 46 c. Valves for opening and closing speed control. 47 d. Pilot valves. 48 e. Solenoid valves. 49

1) Body: Brass ASTM B283. 50 2) Enclosure: Weatherproof, watertight 4X. 51 3) Voltage: 120 volts. 52 4) Insulation: Class F. 53

Page 246: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CHECK VALVES 15106 - 4

f. Limit switches: 120 volt. 1 g. Pressure switches as necessary to provide control function. 2

4. Electric components: 3 a. 120 V, 1 PH. 4 b. In weatherproof enclosure unless shown otherwise on the Drawings. 5

PART 3 - EXECUTION 6

3.1 INSTALLATION 7

A. See Specification Section 15100. 8

B. Install in accordance with manufacturer's instructions. 9

END OF SECTION 10

Page 247: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MISCELLANEOUS VALVES 15114 - 1

2014/08/28 1

SECTION 15114 2

MISCELLANEOUS VALVES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Air release and vacuum relief valves. 7 2. Pressure-reducing valves (2 IN and smaller). 8 3. Pressure relief valves (1 IN and smaller). 9 4. Solenoid valves. 10

B. Related Specification Sections include but are not necessarily limited to: 11 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 12 2. Division 01 - General Requirements. 13 3. Section 11005 - Equipment: Basic Requirements. 14 4. Section 15100 - Valves: Basic Requirements. 15

1.2 QUALITY ASSURANCE 16

A. Referenced Standards: 17 1. American Society of Mechanical Engineers (ASME): 18

a. B16.1, Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250. 19 2. American Water Works Association (AWWA): 20

a. C512, Standard for Air-Release, Air-Vacuum, and Combination Air Valves for 21 Waterworks Service. 22

b. C550, Standard for Protective Interior Coatings for Valves and Hydrants. 23 3. Canadian Standards Association (CSA). 24 4. National Electrical Manufacturers Association (NEMA): 25

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 26

1.3 SUBMITTALS 27

A. Shop Drawings: 28 1. See Specification Section 01340 for requirements for the mechanics and administration of 29

the submittal process. 30 2. See Specification Section 15100. 31

B. Operation and Maintenance Manuals: 32 1. See Specification Section 01342 for requirements for: 33

a. The mechanics and administration of the submittal process. 34 b. The content of Operation and Maintenance Manuals. 35

PART 2 - PRODUCTS 36

2.1 ACCEPTABLE MANUFACTURERS 37

A. Subject to compliance with the Contract Documents, the manufacturers listed in the applicable 38 Articles below are acceptable. 39

B. Submit request for substitution in accordance with Specification Section 01640. 40

2.2 AIR RELEASE AND VACUUM RELIEF VALVES 41

A. General: Conform to AWWA C512. 42

Page 248: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MISCELLANEOUS VALVES 15114 - 2

B. Air Release Valve: 1 1. Acceptable manufacturers: 2

a. APCO 200A. 3 b. GA Industries, Figure 920. 4

2. Materials: 5 a. Body and cover: Cast iron or semi-steel. 6 b. Float: Stainless steel. 7 c. Linkage and trim: Bronze or stainless steel. 8

3. Design requirements: 9 a. Specifier: Verify size for the project. 10 b. Size: 1 IN. 11 c. Working pressure: Refer to applicable systems. 12 d. Release 10 cfm at 10 psi differential at 150 psi line pressure. 13

C. Air/ Vacuum Valve (AVV01, AVV02, AVV03, and ARV-04): 14 1. Acceptable manufacturers: 15

a. APCO Series 140/150. 16 b. GA Industries, Figure 945 or 960. 17 c. ARI. 18

2. Materials: 19 a. Body and cover: Cast iron or Ductile Iron. 20 b. Float, linkage and hardware: Stainless steel. 21 c. Seat: Buna-N. 22

3. Design requirements: 23 a. Size: As shown on the Drawings. Manufacturer to confirm size. 24

1) Collector Well Pump 16 IN Discharge (AVV01, AVV02, and AVV03): 25 a) Flow: 2,000 to 5,600 gpm. 26 b) Working pressure: 55 to 95 psi. 27

2) High Service Pump 30 IN Discharge Header (AVV05): 28 a) Flow: 2,000 to 16,700 gpm. 29 b) Working pressure: 55 to 95 psi. 30

b. Release 10 cfm at 10 psi differential at 150 psi line pressure. 31 c. Air vacuum capacity: Refer to Process Valve Schedule. 32 d. Provide isolation valve, type as shown on the Drawings. 33

2.3 PRESSURE RELIEF VALVE (1 IN AND SMALLER) 34

A. Acceptable Manufacturer: 35 1. Fisher 98 Series. 36

B. Materials: 37 1. Body: Stainless steel. 38 2. Spring: Steel. 39 3. Diaphragm water - neoprene. 40 4. Trim: 416 stainless steel. 41

C. Design Requirements: 42 1. Pipe relief to discharge at non-hazardous location. 43

2.4 SOLENOID VALVES (1 IN AND SMALLER) 44

A. General Service (Air - Water): 45 1. Acceptable manufacturer: 46

a. ASCO. 47 2. Materials: 48

a. Body: Brass. 49 b. Seat: Buna-N. 50 c. Insulation: Class F. 51

Page 249: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MISCELLANEOUS VALVES 15114 - 3

3. Design requirements: 1 a. 110 Vac. 2 b. Two-way, normally closed. 3 c. Enclosure: Compatible with area classifications indicated on Drawings. 4 d. Working pressure, air and water: 125 psig. 5

4. Accessories: Provide strainer on supply. 6

2.5 ACCESSORIES 7

A. Furnish any accessories required to provide a completely operable valve. 8

2.6 FABRICATION 9

A. Completely shop assemble unit including any interconnecting piping, speed control valves, 10 control isolation valves and electrical components. 11

B. Provide internal epoxy coating suitable for potable water for all iron body valves in accordance 12 with AWWA C550. 13

2.7 SOURCE QUALITY CONTROL 14

A. Shop hydrostatically test to piping system test pressure. 15

2.8 MAINTENANCE MATERIALS 16

A. Provide one (1) set of any special tools or wrenches required for operation or maintenance for 17 each type valve. 18

PART 3 - EXECUTION 19

3.1 INSTALLATION 20

A. General: See Specification Section 11005 and Specification Section 15100. 21

B. Air Release, Vacuum Relief, and Pressure Relief Valves: 22 1. Pipe exhaust to a suitable disposal point. 23 2. Where exhausted to a trapped floor drain, terminate exhaust line 6 IN minimum above floor. 24

C. Float-Operated Valves: Install baffle around float to minimize turbulence adjacent to float. 25

3.2 FIELD QUALITY CONTROL 26

A. Clean, inspect, and operate valve to ensure all parts are operable and valve seats properly. 27

B. Check and adjust valves and accessories in accordance with manufacturer's instructions and 28 place into operation. 29

END OF SECTION 30

31

Page 250: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MISCELLANEOUS VALVES 15114 - 4

1

Page 251: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 1

2014/08/28 1

SECTION 15183 2

PIPE, DUCT AND EQUIPMENT INSULATION 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Insulation: 7

a. Piping insulation. 8 b. Duct insulation. 9 c. Equipment insulation. 10

B. Related Specification Sections include but are not necessarily limited to: 11 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 12 2. Division 01 - General Requirements. 13 3. Section 15890 – HVAC: Ductwork. 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. ASTM International (ASTM): 17

a. C177, Standard Test Method for Steady-State Heat Flux Measurements and Thermal 18 Transmission Properties by Means of Guarded-Hot-Plate Apparatus. 19

b. C411, Standard Test Method for Hot-Surface Performance of High-Temperature 20 Thermal Insulation. 21

c. C423, Standard Test Method for Sound Absorption and Sound Absorption Coefficients 22 by the Reverberation Room Method. 23

d. C518, Standard Test Method for Steady-State Thermal Transmission Properties by 24 Means of the Heat Flow Meter Apparatus. 25

e. C553, Standard Specification for Mineral Fiber Blanket Thermal Insulation for 26 Commercial and Industrial Applications. 27

f. C665, Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light 28 Frame Construction and Manufactured Housing. 29

g. C1071, Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and 30 Sound Absorbing Material). 31

h. D1056, Standard Specification for Flexible Cellular Materials-Sponge or Expanded 32 Rubber. 33

i. E84, Standard Test Method for Surface Burning Characteristics of Building Materials. 34 j. E96, Standard Test Methods for Water Vapor Transmission of Materials. 35 k. F25, Standard Test Method for Sizing and Counting Airborne Particulate 36

Contamination in Cleanrooms and Other Dust-Controlled Areas. 37 2. National Fire Protection Association (NFPA): 38

a. 255, Standard Method of Test of Surface Burning Characteristics of Building Materials. 39 3. Underwriters Laboratories, Inc. (UL): 40

a. 723, Standard for Test for Surface Burning Characteristics of Building Materials. 41

1.3 SUBMITTALS 42

A. Shop Drawings: 43 1. See Specification Section 01340 for requirements for the mechanics and administration of 44

the submittal process. 45 2. Product technical data including: 46

a. Acknowledgement that products submitted meet requirements of standards referenced. 47

Page 252: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 2

b. Manufacturer's installation instructions. 1 c. Submit complete specification of insulation materials, adhesives, cement, together with 2

manufacturer's recommended methods of application and coverage for coatings and 3 adhesives. 4

3. Submit itemized schedule by building of proposed insulation systems showing density, 5 thermal conductivity, thickness, adhesive, jackets and vapor barriers. 6

4. Certifications: Products will meet the requirements of the Contract Documents. 7

PART 2 - PRODUCTS 8

2.1 ACCEPTABLE MANUFACTURERS 9

A. Subject to compliance with the Contract Documents, the following manufacturers are 10 acceptable: 11 1. Elastomeric insulation: 12

a. Rubatex. 13 b. Armstrong. 14

2. Fiberglass insulation: 15 a. Certainteed Corporation. 16 b. Schuller (Manville). 17 c. Owens Corning. 18 d. Knauf. 19

3. PVC jacket: 20 a. Ceel-Co. 21 b. PIC Plastics. 22

4. Equipment insulation: 23 a. Certainteed Corporation. 24 b. Schuller (Manville). 25 c. Owens Corning. 26

5. Ductwork insulation: 27 a. Certainteed. 28 b. Schuller (Manville). 29 c. Owens Corning. 30

B. Submit request for substitution in accordance with Specification Section 01640. 31

2.2 PIPING INSULATION - ELASTOMERIC 32

A. General: 33 1. Insulation fire and smoke hazard ratings for composite (insulation, jacket or facing, and 34

adhesive used to adhere the facing or jacket to the insulation), as tested by procedure 35 ASTM E84, NFPA 255 and UL 723, not exceeding: 36 a. Flame spread: 25. 37 b. Smoke developed: 50. 38

2. Accessories (adhesives, mastics, cements, and tapes: Same component ratings as listed 39 above. 40

3. Indicate on product labels or their shipping cartons: Flame and smoke ratings do not exceed 41 above requirements. 42

4. Permanent treatment of jackets or facings to impart flame and smoke safety is required. 43 a. Water-soluble treatments are prohibited. 44

5. Insulated shields at pipe support points. 45

Page 253: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 3

B. Pipe, Fitting, and Valve Insulation: 1 1. Flexible elastomeric closed cell pipe insulation. 2

a. Average thermal conductivity not to exceed 0.27 (Btu-IN)/(HR-FT2-DegF) at mean 3 temperature of 75 DegF, temperature range -40 to 220 DegF; permeability not to 4 exceed 0.20 by ASTM E96; water absorption 3 percent by ASTM D1056 and ozone 5 resistance. 6

2. Provide minimum insulation thickness conforming to schedules or as shown on the 7 Drawings. 8

2.3 PIPING INSULATION - FIBERGLASS 9

A. Pipe and Fitting Insulation: 10 1. Preformed fiberglass pipe insulation: 11

a. Density: 4 LBS/CF. 12 b. Temperature rated: 650 DegF. 13 c. Average thermal conductivity not to exceed 0.22 (Btu-IN)/(HR-FT2-DegF) at mean 14

temperature of 75 DegF. 15 d. Fire hazard rating: 16

1) UL 723, ASTM E84, NFPA 255. 17 2) Flame spread not exceeding 25 and smoke developed not exceeding 50. 18

2. Moisture adsorption: 19 a. ASTM C553. 20 b. Not greater than 0.5 percent moisture by volume when exposed to moisture laden air at 21

120 DegF and 96 percent RH. 22 3. Fungi and bacteria resistance: 23

a. ASTM C665. 24 b. Does not breed or promote growth. 25 c. Flame attenuated glass fibers bonded with thermosetting resin. 26

4. Piping jackets (general applications): 27 a. Aluminum: 16 mil embossed aluminum. 28 b. PVC: Preformed 0.028 IN thick PVC jackets fabricated from B.F. Goodrich PVC 29

sheeting V-66 with proven resistance to ultraviolet degradation when temperatures do 30 not exceed the limits of PVC. 31

c. Piping jacket not required on concealed piping. 32 5. Provide minimum insulation thickness conforming to schedules or as shown on the 33

Drawings. 34

2.4 EQUIPMENT INSULATION 35

A. Insulation for Equipment: 36 1. Fire hazard classification: 37

a. UL 723, ASTM E84, NFPA 255. 38 b. Flame spread not exceeding 25 and smoke developed not exceeding 50. 39

2. Provide minimum insulation thickness conforming to Schedules, or as shown on Drawings. 40

2.5 DUCTWORK INSULATION: FIBERGLASS 41

A. Flexible Insulation: 42 1. Scheduled thickness: Schuller (Manville) Microlite. 43 2. Factory-applied foil scrim vapor barrier facing. 44 3. Average thermal conductivity not to exceed 0.27 (Btu-IN)/(HR-FT2-DegF) at a mean 45

temperature of 75 DegF (installed). 46 4. Minimum density: 0.75 LB/CF. 47 5. Fire hazard classification: 48

a. UL 723, ASTM E84, NFPA 255. 49 b. Flame spread not exceeding 25 and smoke developed not exceeding 50. 50

Page 254: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 4

B. Semi-Rigid Insulation for Indoor Installation: 1 1. Scheduled thickness Schuller (Manville) #814 SPIN-GLASS fiberglass duct insulation. 2 2. Factory applied vapor barrier facing-white scrim foil. 3 3. Average thermal conductivity not to exceed 0.23 (Btu-IN)/(HR-FT2-DegF) at a mean 4

temperature of 75 DegF. 5 4. Minimum density: 3.0 LB/CF. 6 5. Moisture adsorption: 7

a. ASTM C553. 8 b. Not greater than 0.5 percent moisture by volume when exposed to moisture laden air at 9

120 DegF and 96 percent RH. 10

C. Semi-Rigid Insulation for Outdoor Installation: 11 1. Outside ducts: Surface with scheduled thickness of Schuller (Manville) 800 Series SPIN-12

GLASS #815 fiberglass duct insulation. 13 2. Factory-applied foil scrim vapor barrier facing. 14 3. Average thermal conductivity not to exceed 0.23 (Btu-IN)/(HR-FT2-DegF) at mean 15

temperature of 75 DegF. 16 4. Minimum density: 3 LBS/CF. 17 5. Finish with Benjamin Foster #4610 weatherproof mastic with white glass fabric membrane. 18 6. Fungi and bacteria resistance: 19

a. ASTM C665. 20 b. Does not breed or promote growth. 21

D. Provide minimum insulation thickness conforming to Schedule, or as shown on Drawings. 22

E. Duct Interior Lining Board: 23 1. Acoustical performance: Minimum noise reduction coefficients (NRC) is 0.45 when tested 24

in accordance with ASTM C423 on ASTM F25 mounting. 25 2. Fire hazard classification: 26

a. UL 723, ASTM E84, NFPA 255. 27 b. Flame spread not exceeding 25 and smoke developed not exceeding 50. 28

3. Service temperature: 29 a. ASTM C411. 30 b. Cooling and heating ducts up to 200 DegF. 31

4. Velocity rating: 32 a. ASTM C1071. 33 b. Maximum average air velocity is rated at 600 fpm. 34

5. Moisture adsorption: 35 a. ASTM C553. 36 b. Not greater than 0.5 percent moisture by volume when exposed to moisture laden air at 37

120 DegF and 96 percent RH. 38 6. Fungi and bacteria resistance: 39

a. ASTM C665. 40 b. Does not breed or promote growth. 41

7. Size and performance: 42 a. ASTM C518 and ASTM C177. 43 b. 1 IN thickness, long textiled glass-type fibers firmly bonded by thermosetting resin. 44 c. At 75 DegF mean temperature, the k value, expressed as (Btu-IN)/(HR-FT2-DegF) does 45

not exceed 0.27. 46

PART 3 - EXECUTION 47

3.1 INSTALLATION 48

A. Install products in accordance with manufacturer's instructions. 49

Page 255: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 5

B. General: 1 1. Consider ductwork, piping and equipment as exposed, except as otherwise indicated. 2 2. Consider ductwork, piping and equipment in walls, partitions, floors, pipe chases, pipe 3

shafts and duct shafts as concealed. 4 a. Consider ductwork, piping and equipment above ceilings as concealed. 5

3. Provide release for insulation application after installation and testing is complete. 6 a. Apply insulation on clean, dry surfaces after inspection. 7

4. Provide insulation continuous through wall, roof and ceiling openings, pipe hangers, 8 supports and sleeves. 9

5. Provide insulation with vapor barrier for piping, ductwork and equipment where surfaces 10 may be cooler than surrounding air temperatures. 11 a. Provide vapor barrier (0.17 perm-IN; ASTM C553) continuous and unbroken. 12 b. Hangers, supports, anchors, and related items that are secured directly to cold surfaces 13

must be adequately insulated and vapor-sealed to prevent condensation. 14 6. Apply specified adhesives, mastics and coatings at the manufacturer's recommended 15

coverage per unit volume. 16

C. Piping Insulation - Elastomeric: 17 1. Slip insulation on pipe prior to connection. 18

a. Whenever the slip-on technique is not possible provide insulation neatly slit and 19 snapped over the pipe. 20

2. Fabricate and install fitting cover insulation according to manufacturer's recommendations. 21 3. Seal joints, slits, miter-cuts and other exposed edges of insulation with adhesive, 22

recommended by the insulation manufacturer, to ensure complete vapor barrier. 23

D. Piping Insulation - Fiberglass: 24 1. Apply over clean dry pipe. 25

a. Butt all joints together firmly. 26 2. Seal joints, slits, miter-cuts and other exposed edges of insulation as recommended by the 27

insulation manufacturer. 28 3. Insulate fittings, valves, and flanges with insulation thickness equal to adjacent pipe. 29 4. PVC pipe jacket: 30

a. Apply jacketing with a minimum of 1 IN overlap. 31 1) Weld longitudinal and circumferential seams with adhesives as recommended by 32

manufacturer. 33 b. Provide slip-joints every 30 FT and between fittings if distance exceeds 8 FT. 34

1) Construct slip-joints by overlapping jacket sections 6 to 10 IN. 35 c. Provide premolded PVC covers of same material and manufacturer as jacket for 36

fittings, valves, flanges, and related items in insulated piping systems. 37 5. Aluminum pipe jacket: 38

a. Field-applied aluminum jacket with vapor-sealed longitudinal and butt joints. 39 b. Provide smooth and straight joint with a minimum 2 IN overlap. 40 c. Secure joints with corrosion-resistant screws spaced 0.25 to 0.50 IN back from edge. 41 d. Center spacing of screws 5 IN maximum or as required to provide smooth tight-fitted 42

joints. 43 e. Place joints on least exposed side of piping to obtain neat appearance. 44

E. Equipment: Install per manufacturer's instructions. 45

F. Ductwork Insulation - Fiberglass: 46 1. Flexible insulation: 47

a. Butt edges tightly. 48 1) Secure insulation with Benjamin Foster 85-20 adhesive applied in 6 IN strips on 12 49

IN centers and/or pins, applied on not more than 18 IN centers so that the 50 insulation conforms to the duct surfaces uniformly and firmly. 51

b. Seal joints with facing overlap or 4 IN wide strips of like facing material adhered and 52 stapled in place. 53

Page 256: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 6

c. Properly seal any penetration in vapor barrier facing with Benjamin Foster 85-20. 1 d. Cut insulation slightly longer than the perimeter of the duct to ensure full thickness at 2

corners. 3 2. Semi-rigid insulation and duct interior lining board: 4

a. Impaling over pins. 5 1) Apply insulation with edges tightly butted. 6 2) Apply insulation with mechanically welded fasteners to the duct and secured with 7

speed clips. 8 3) Clip pins off close to clip. 9 4) Space pins as required to hold insulation firmly against duct surface but not less 10

than one (1) pin per 1.5 SF. 11 5) Seal joints and speed clips with 3 IN wide strip of facing adhered with Benjamin 12

Foster 85-20 adhesive. 13 b. If the welded pin method is impossible, secure insulation to the duct with Benjamin 14

Foster 85-20 adhesive. 15 1) Cover the entire surface of duct with adhesive. 16 2) Use corner metal angle to protect edge of insulation. 17 3) Protect edge of insulation. 18 4) Seal joints as above. 19

G. Install interior duct lining board as indicated above. 20 1. Overall length shall be as indicated on the Drawings or a minimum of 10 LF past any type 21

of air supply fan. 22

3.2 REPAIR 23

A. Whenever any factory applied insulation or job-applied insulation is removed or damaged, 24 replace with the same quality of material and workmanship. 25

3.3 SCHEDULES 26

A. Refrigeration Lines (35-60 DegF): 27 1. Elastomeric. 28 2. 1/2 IN thickness for lines 1 IN and smaller. 29

B. Pipe, Fittings and Valves: 30 1. Fiberglass. 31

32 APPLICATION PIPE SIZE THICKNESS JACKET

Roof Drainage 2-1/2 to 6 IN 1/2 IN PVC

Hot Water (domestic) 6 IN and less 3/4 IN PVC

Cold Water (domestic) 3 IN and less 3/4 IN PVC Over 3 IN 1 IN

Heating Water (120 - 230 DegF) 6 IN and less 1 IN PVC

Refrigeration Lines (35 - 60 DegF) Over 1 IN 1 IN PVC

Chilled Water (35 - 60 DegF) 4 IN and less 1 IN PVC Over 4 IN 1-1/2 IN

33

Page 257: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 7

C. Equipment: 1 2

EQUIPMENT INSULATION SYSTEM

Hot water and steam, heating equipment, heat exchangers, air separators, strainers, condensate, receivers

2 IN fiberglass insulation. Glass mesh jacket adhered and coated with two (2) coats of Foster 30-36 white insulation coatings.

Hot water pumps, flash tanks, compression tanks Uninsulated

Below drain pans serving cooling coils, pre-heat systems, domestic water heaters

1 IN flexible elastomeric closed cell sheet.

3

D. Ductwork: 4 1. Metallic: 5

6

DUCT SERVICE INSULATION AND

THICKNESS

Supply air ducts downstream of cooling coils 1 IN flexible with vapor barrier

All other ductwork Uninsulated

END OF SECTION 7

8

Page 258: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PIPE, DUCT AND EQUIPMENT INSULATION 15183 - 8

1

Page 259: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - FIRE HYDRANT 15510 - 1

2014/07/31 1

SECTION 15510 2

FIRE HYDRANT 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Dry-barrel fire hydrant. 6

B. Related Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 09905 - Painting and Protective Coatings. 10 4. Section 15060 - Pipe and Pipe Fittings: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. American Water Works Association (AWWA): 14

a. C502, Standard for Dry-Barrel Fire Hydrants. 15 b. M17, Installation, Operation and Maintenance of Fire Hydrants. 16

1.3 SUBMITTALS 17

A. Shop Drawings: 18 1. See Specification Section 01340 for requirements for the mechanics and administration of 19

the submittal process. 20 2. Product technical data: 21

a. Acknowledgement that products submitted meet the requirements of the standards 22 referenced. 23

b. Manufacturer's installation instructions. 24 c. Acknowledge and verify dimensions and provide list of integral parts and materials. 25

3. Prior to submission of Shop Drawings, submit one (1) copy of complete submittal 26 information direct to local fire department, Attn: Fire Chief, and request and secure written 27 approval of hydrant selection. 28 a. Incorporate copies of written approval letter with submittals. 29

B. Operation and Maintenance Manuals: 30 1. See Specification Section 01342 for requirements for: 31

a. The mechanics and administration of the submittal process. 32 b. The content of Operation and Maintenance Manuals. 33

PART 2 - PRODUCTS 34

2.1 ACCEPTABLE MANUFACTURERS 35

A. Subject to compliance with the Contract Documents, the following manufacturers are 36 acceptable: 37 1. Mueller, 38 2. American Flow Control, 39 3. Waterous. 40

B. Submit request for substitution in accordance with Specification Section 01640. 41

2.2 FIRE HYDRANT 42

A. Design and Fabrication: 43 1. Conform to AWWA C502. 44

Page 260: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - FIRE HYDRANT 15510 - 2

2. Provide with either compression or gate design. 1 3. Provide with a 5-1/4 IN valve opening, nozzle section consisting of two (2) 2-1/2 IN hose 2

nozzles and one (1) 4-1/2 IN steamer. 3 4. Provide with water passages to permit full flow of water to minimize friction loss. 4 5. Furnish with multiple weep holes for positive draining to allow water to escape readily from 5

standpipe when hydrant valve is closed. 6 6. Designed to throttle flow when partially opened. 7 7. Designed to allow removal of valve and valve stem without digging up hydrant. 8 8. Suitable for 7.5 FT of bury. 9 9. Furnish with mechanical (gland type) joint inlet connections. 10 10. Design to break off at ground line when struck by a vehicle. 11 11. Furnish with O-ring packing only. 12 12. Furnish hose and steamer nozzles with threads conforming to standard threads used by local 13

Fire Department. 14 13. Furnish with direction of opening as required by local Fire Department with direction of 15

opening cast on dome. 16 14. Color: Red. 17

PART 3 - EXECUTION 18

3.1 INSTALLATION 19

A. Install hydrants at locations indicated in accordance with AWWA M17 and the following: 20 1. Remove foreign material from barrel of hydrant before placement. 21 2. Install plumb and at same elevation as connecting pipe and main. 22 3. Place each hydrant on a slab of concrete not less than 6 IN thick and 18 IN SQ. 23 4. Block backside of hydrant, opposite pipe connection, with concrete firmly wedged between 24

hydrant and vertical face of undisturbed trench. 25 5. Place granular bedding material around base of hydrant to the dimensions shown in the 26

Drawings. 27 6. Firmly tamp carefully compacted backfill around hydrant to surface of ground and to a 28

distance of 5 FT in front of hydrant. 29

3.2 COATINGS AND FINISHES 30

A. Provide hydrant with below grade and above grade coatings as per Section 09905. 31 1. Paint above grade with color conforming to the requirements of the local Fire Department. 32

END OF SECTION 33

Page 261: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HYDRONIC SPECIALTIES 15515 - 1

2014/08/14 1

SECTION 15515 2

HYDRONIC SPECIALTIES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Hydronic specialties. 6

B. Related Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 11005 - Equipment: Basic Requirements. 10 4. Section 15970 - Instrumentation and Control for HVAC Systems. 11 5. Section 15990 - HVAC Systems: Balancing and Testing. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. American National Standards Institute (ANSI). 15 2. American Society of Mechanical Engineers (ASME). 16 3. ASTM International (ASTM): 17

a. A159, Standard Specification for Automotive Gray Iron Coating. 18 b. B36, Standard Specification for Brass Plate, Sheet, Strip and Rolled Bar. 19 c. B62, Standard Specification for Composition Bronze or Ounce Metal Castings. 20 d. B85, Standard Specification for Aluminum-Alloy Die Castings. 21 e. B99, Standard Specification for Copper-Silicon Alloy Wire for General Purposes. 22 f. B371, Standard Specification for Copper-Zinc-Silicon Alloy Rod. 23 g. B584, Standard Specification for Copper Alloy Sand Castings for General Applications. 24

4. Expansion Joint Manufacturer's Association (EJMA). 25 5. National Electrical Manufacturers Association (NEMA). 26 6. Society of Automotive Engineers (SAE). 27

1.3 SUBMITTALS 28

A. Shop Drawings: 29 1. See Specification Section 01340 for requirements for the mechanics and administration of 30

the submittal process. 31 2. See Specification Section 11005. 32 3. Product technical data including: 33

a. Acknowledgement that products submitted meet requirements of standards referenced. 34 b. Manufacturer's installation instructions. 35 c. Manufacturer's catalog cuts and technical information. 36 d. Pump curves. 37

4. Certifications. 38 5. Test reports. 39

B. Operation and Maintenance Manuals: 40 1. See Specification Section 01342 for requirements for: 41

a. The mechanics and administration of the submittal process. 42 b. The content of Operation and Maintenance Manuals. 43

Page 262: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HYDRONIC SPECIALTIES 15515 - 2

1.4 ACCEPTABLE MANUFACTURERS 1

A. Subject to compliance with the Contract Documents, the following manufacturers are 2 acceptable: 3 1. Combination strainer and air separator: 4

a. Bell and Gossett; Rollairtrol. 5 2. Balancing valves and readout meters: 6

a. Bell and Gossett; Circuit Setter Balance valves and Model R0-2 meter. 7 3. Flow measuring devices and meters: 8

a. Aeroquip. 9 b. Barco. 10 c. Dieterich Standard Corp. 11

4. Heating water pumps: 12 a. Bell and Gossett. 13

5. Expansion joints: 14 a. Flexonics Div. 15 b. Zallea Brothers, Inc. 16 c. Pathway Bellows, Inc. 17

6. Flexible connections: 18 a. Flexonics Div. 19 b. Barco. 20 c. Anaconda Metal Hose. 21

B. Submit request for substitution in accordance with Specification Section 01640. 22

1.5 EQUIPMENT 23

A. Manual Air Relief Vents: 24 1. Type: Class 150 bronze gate with rising stem and solid wedge. 25 2. Material: 26

a. Bonnet, body and wedge: Bronze ASTM B62. 27 b. Packing nut and packing gland: Bronze ASTM B62 or ASTM B584 alloy C84400. 28 c. Stem: Silicon Bronze ASTM B371 Alloy C69400 or ASTM B99 alloy C65100 H04. 29 d. Hand wheel: Aluminum ASTM B85 Alloy A03800. 30 e. Hand wheel nut: Zinc-plated steel with clear chromate. 31

3. Design limitations: 150 psi steam at 406 DegF minimum. 32 4. Relief tubing: K copper. 33 5. Size: As required. 34

B. Combination Strainer and Air Separator: 35 1. ASME code constructed. 36 2. Type: Tangential flow. 37 3. Design pressure: 125 psig minimum at 350 DegF. 38 4. Air collector tube. 39

a. Stainless steel. 40 b. 63 percent open area design (minimum). 41

5. NPT vent connection. 42 6. NPT blowdown connection. 43 7. Tangential nozzles: 44

a. NPT up to 3 IN DIA. 45 b. Flanged, 4 IN and larger. 46

8. Strainer: 47 a. Galvanized steel. 48 b. Free area not less than five (5) times the cross sectional area of the connecting pipe. 49 c. Removable. 50

9. GPM: As indicated. 51

Page 263: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HYDRONIC SPECIALTIES 15515 - 3

C. Balancing Valve: 1 1. Type: Calibrated balance valve. 2 2. Connections: 3

a. NPT up to 3 IN DIA. 4 b. Flanged for 4 IN or larger. 5

3. Readout valve: Brass fitted with integral EPT insert and check valve. 6 4. Calibrated nameplate. 7 5. Integral seals. 8 6. Preformed polyurethane insulation. 9 7. Working pressure: 125 psig at 250 DegF minimum. 10

D. Readout Meter for Balancing Valves: 11 1. Type: Portable. 12 2. Range: 0 to 100 FT of water. 13 3. Increments: 0.5 FT. 14 4. Accuracy: +0.5 percent. 15 5. Accessories: 16

a. Carrying case. 17 b. 10 FT hoses. 18 c. Shut-off and vent valves. 19 d. Balance valve calculator. 20

6. Maximum operating temperature: 250 DegF liquids and gases. 21

E. Heating Water Pump: 22 1. Type: Centrifugal, single-stage, in-line type, in-line suction and discharge, base mounted. 23 2. Material: 24

a. Volute: Cast iron ASTM A159. 25 b. Impeller: 26

1) AA sizes: Brass, ASTM B36. 27 2) A, F sizes: Cast bronze, ASTM B584. 28

c. Pump shaft: Steel, SAE 1144. 29 d. Seal assembly: 30

1) Housing: Brass. 31 2) Bellows: Buna-N. 32 3) Ring: Carbon. 33 4) Spring: 304 stainless steel. 34 5) Seat: Ceramic. 35 6) Seat gasket: Buna-N. 36

e. Volute gasket: Cellulose fiber. 37 f. Companion flanges: 38

1) 1 to 1-1/2 IN: Formed steel. 39 2) 2 IN: Cast iron, ASTM A159. 40

g. Shaft sleeve: Copper alloy 110 or aluminum bronze, ASTM B584. 41 h. Motor: 42

1) Meets NEMA 4 requirements. 43 2) 3 HP, 480 V, 3 PH, 60 HZ. 44

F. Expansion Joints: 45 1. For piping 2-1/2 IN or smaller. 46

a. Type: Bellows. 47 b. Material: 48

1) Bellows: Two-ply stainless steel. 49 2) Shrouds and end fittings: Carbon steel. 50

c. Stroke: 1-3/4 IN compression, 1/4 IN extension minimum. 51 d. Maximum operating temperature: 750 DegF. 52 e. Maximum working pressure: 175 psi. 53 f. Maximum test pressure: 250 psi. 54

Page 264: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HYDRONIC SPECIALTIES 15515 - 4

g. Fittings: NPT. 1 2. For piping 3 IN or larger: 2

a. Type: Controlled flexing bellows. 3 b. Material: 4

1) Bellows: Stainless steel. 5 2) Carrier rings and fittings: Steel. 6

c. Maximum transverse travel: 7-1/2 IN. 7 d. Temperature limits: -20 to 850 DegF. 8 e. Allowable pressure: Vacuum to 300 psi. 9 f. Fittings: Flanged. 10

G. Pipe Guides: 11 1. Type: System consisting of a spider which rigidly attaches to pipe and is housed in a sleeve 12

which can be rigidly anchored. 13 2. Material: Steel. 14

H. Flexible Connectors: 15 1. Type: Flexible corrugated single braid hose. 16 2. Material: Stainless steel. 17 3. Maximum working pressure: 150 psig. 18 4. Maximum test pressure: 250 psig. 19 5. Normal burst pressure: 650 psig minimum. 20 6. Fittings: 21

a. For sizes up to 2-1/2 IN DIA: NPT. 22 b. For sizes 3 IN or larger: Flanged. 23

I. Hot water pumps to meet the following minimum requirements: 24 1. Pump numbers: P-01. 25

a. Design condition: 90 gpm at 61 FT/TDH. 26

1.6 FABRICATION 27

A. Fabricate pumps complete with motor and pump as one (1) unit. 28

1.7 SOURCE QUALITY CONTROL 29

A. Pump Impeller Trimming: 30 1. Trim impellers to a diameter to provide design flow to each terminal with minimum pump 31

power consumption for each pump. 32

PART 2 - EXECUTION 33

2.1 INSTALLATION 34

A. Install hydronic specialty items where indicated or required. 35

B. Install at high point in closed water systems and at high point of coil headers an automatic relief 36 vent. 37 1. Install shut-off valve ahead of each vent. 38 2. Extend relief tubing from vent to drippan or drain. 39

C. Install flexible connectors at pump suction and discharge and where indicated. 40

D. Install pipe guides in accordance with EJMA Standards. 41 1. Space at 4 and 14 pipe diameters from expansion joints. 42 2. Install at expansion loops as indicated. 43

Page 265: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HYDRONIC SPECIALTIES 15515 - 5

2.2 FIELD QUALITY CONTROL 1

A. See Section 15990. 2

END OF SECTION 3

4

Page 266: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HYDRONIC SPECIALTIES 15515 - 6

1

Page 267: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: EQUIPMENT 15605 - 1

2014/08/28 1

SECTION 15605 2

HVAC: EQUIPMENT 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Heating, ventilating, and cooling equipment. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 11005 - Equipment: Basic Requirements. 10 4. Section 15890 - HVAC: Ductwork. 11 5. Section 15970 - Instrumentation and Control for HVAC Systems. 12 6. Section 15990 - HVAC Systems: Balancing and Testing. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. Air Movement and Control Association (AMCA). 16 2. Air Conditioning and Refrigeration Institute (ARI). 17 3. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE): 18

a. HVAC Applications Handbook, Chapter entitled "Sound and Vibration Control." 19 b. 20, Methods of Testing for Rating Remote Mechanical-Draft Air-Cooled Refrigerant 20

Condensers. 21 c. 52.2, Method of Testing General Ventilation Air-Cleaning Devices for Removal 22

Efficiency by Particle Size. 23 4. Canadian Standards Association (CSA). 24 5. National Electrical Manufacturers Association (NEMA): 25

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 26 6. National Fire Protection Association (NFPA): 27

a. 70, National Electrical Code (NEC). 28 7. National Roofing Contractors Association (NRCA). 29 8. Underwriters Laboratories, Inc. (UL): 30

a. 507, Standard for Electric Fans. 31 9. Building Code: 32

a. International Code Council (ICC): 33 1) International Building Code and associated standards, 2003 Edition including all 34

amendments, referred to herein as Building Code. 35

B. Miscellaneous: 36 1. Gage thickness specified herein shall be manufacturer's standard gage for steel and Brown 37

and Sharpe gage for non-ferrous metals. 38 2. Corrosion protection of equipment to be as specified herein. 39

1.3 SUBMITTALS 40

A. Shop Drawings: 41 1. See Specification Section 01340 for requirements for the mechanics and administration of 42

the submittal process. 43 2. Fabrication and/or layout Drawings. 44 3. Product technical data including: 45

a. Acknowledgement that products submitted meet requirements of standards referenced. 46 b. Manufacturer's installation instructions. 47

Page 268: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: EQUIPMENT 15605 - 2

c. Wiring diagrams. 1 d. Control diagrams. 2 e. Manufacturer's catalog cuts and technical data. 3 f. Fan curves. 4 g. Sound data. 5 h. Vibration isolation. 6 i. Control description. 7 j. Performance data on all equipment. 8

4. Certifications: 9 a. Provide certification of thickness of corrosion-protection coating. 10

B. Operation and Maintenance Manuals: 11 1. See Specification Section 01342 for requirements for: 12

a. The mechanics and administration of the submittal process. 13 b. The content of Operation and Maintenance Manuals. 14

PART 2 - PRODUCTS 15

2.1 ACCEPTABLE MANUFACTURERS 16

A. Subject to compliance with the Contract Documents, the following manufacturers are 17 acceptable: 18 1. Vibration isolation assemblies: 19

a. Mason. 20 b. Vibration Mounting and Controls Co. 21 c. Vibro-Acoustics. 22

2. Heating and cooling coils - water - steam: 23 a. Carrier. 24 b. Daikin Applied. 25 c. AAON. 26

3. Fan coils: 27 a. Carrier. 28 b. Daikin Applied. 29 c. AAON. 30

4. Roof-mounted centrifugal exhaust fans: 31 a. Loren Cook. 32 b. Greenheck. 33 c. PennBarry Ventilator Co., Inc. 34

B. Submit request for substitution in accordance with Specification Section 01640. 35

2.2 GENERAL 36

A. All Manufactured Units: 37 1. Comply with Specification Section 11005. 38 2. Factory wired and assembled. 39 3. Use fasteners made of same material as unit. 40 4. Fabricate motor assemblies and unit housings with vibration isolation assemblies: 41

a. Type: As per Table 47, Chapter 48, ASHRAE HVAC Applications Handbook. 42

B. All manufactured units shall be constructed with corrosion-resistant materials or have corrosion-43 resistant coating. 44 1. Type: 45

a. Corrosion-resistant materials: 46 1) Aluminum. 47 2) Stainless steel. 48 3) FRP. 49

Page 269: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: EQUIPMENT 15605 - 3

2.3 MANUFACTURED UNITS 1

A. Equipment Coils: 2 1. Heating and cooling coils - water - steam: 3

a. ARI certified. 4 b. Material: 5

1) Aluminum. 6 2) Copper with aluminum fins for use in administration units only. 7

c. Fin spacing: Minimum 80 fins per foot. 8 d. Minimum standard operating limit: 200 psi. 9 e. Equip with vent, drain and condensate connections. 10 f. Size and capacity as scheduled on Drawings. 11

B. Fan Coils: 12 1. ARI certified. 13 2. Coils: See paragraph(s) in Article 2.3, Equipment Coils. 14 3. Blower: 15

a. Fan wheels: Centrifugal forward-curved, double width. 16 b. Fan housing: Galvanized steel. 17 c. Statically and dynamically balanced. 18 d. Motor: 19

1) See Specification Section 11005. 20 2) Integral overload protection. 21

4. Cabinet: 22 a. Material: Galvanized steel, 18 GA minimum. 23 b. Exposed units equipped with hinged access panel, intake and discharge grilles. 24 c. Concealed units equipped with return plenum, filter section and discharge duct collar. 25

5. Drain pans: 26 a. Material: Galvanized steel. 27 b. Equip with drain connection. 28 c. Insulated. 29

6. Filters: See Specification Section 15890. 30 7. Size and capacity as scheduled on Drawings. 31

C. Roof-Mounted Centrifugal Exhaust Fans: 32 1. AMCA certified. 33 2. Non-overloading horsepower capability. 34 3. Materials: 35

a. Top cap: Spun aluminum. 36 b. Wheel and inlet shroud: Aluminum. 37 c. Baffle: Aluminum. 38 d. Base: One-piece aluminum. 39 e. Drive assembly supports: Steel. 40 f. Drive shaft: Solid stainless steel. 41 g. Minimum 10 GA motor mounting plate. 42

4. Backward inclined blades. 43 5. Tapered inlet shroud. 44 6. Statically and dynamically balanced wheel. 45 7. Bearings: 46

a. Cast iron pillow blocks. 47 b. Concentric bearing locking collar for drive shafts 1 IN and larger. 48

1) SKF "ConCentra." 49 2) Dodge "D Lock." 50

c. Regreaseable. 51 d. 200,000 HR average life. 52 e. Five-to-one load capability to actual load ratio. 53

Page 270: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: EQUIPMENT 15605 - 4

8. Weathertight compartment for motor and drives. 1 a. Separated from airstream. 2

9. Motor: 3 a. See Specification Section 11005. 4 b. Driver and driven sheaves: 5

1) Keyed hub type. 6 2) Drive sheaves: Fixed pitch diameter. 7 3) Driver: 8

a) Shipped with variable pitch diameter sheave. 9 b) Fixed pitch diameter size based on approved test and balance reports. 10

4) V-belt drives sized for 150 percent motor horsepower. 11 10. Automatic drive belt tensioner. 12 11. Vibration isolated drive assembly. 13 12. Accessories: 14

a. Prefabricated insulated aluminum roof curb. 15 b. Backdraft damper: See Specification Section 15890. 16 c. Bird screen. 17 d. Extended grease lines and fittings. 18

13. Size and capacity as scheduled on Drawings. 19

PART 3 - EXECUTION 20

3.1 INSTALLATION 21

A. Install in accordance with Specification Section 11005. 22

B. Install fixed pitched drive sheave after sheave has been sized based on accepted test and balance 23 report. 24

3.2 FIELD QUALITY CONTROL 25

A. Comply with Specification Section 15990. 26

3.3 ADJUSTING 27

A. Install new filters on units which have been running prior to acceptance of Project. 28

END OF SECTION 29

Page 271: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HEAT EXCHANGERS AND CONVERTERS 15710 - 1

2014/08/14 1

SECTION 15710 2

HEAT EXCHANGERS AND CONVERTERS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Liquid and vapor heat exchange equipment for heating, ventilating, and cooling equipment. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 0 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 1 - General Requirements. 10 3. Section 11005 - Equipment: Basic Requirements. 11 4. Section 15970 - HVAC Control System. 12 5. Section 15990 - HVAC Systems - Balancing and Testing. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. Acoustical Society of America (ASA). 16 2. American Society of Mechanical Engineers (ASME): 17

a. Section VIII, Construction of Pressure Vessels - Division 1. 18

B. Miscellaneous: 19 1. Gage thickness specified herein shall be manufacturer's standard gage for steel and Brown 20

and Sharpe gage for non-ferrous metals. 21 2. Corrosion protection of equipment to be as specified herein. 22

1.3 SUBMITTALS 23

A. Shop Drawings: 24 1. See Section 01340. 25 2. Fabrication and/or layout Drawings. 26 3. Product technical data including: 27

a. Acknowledgement that products submitted meet requirements of standards referenced. 28 b. Manufacturer's installation instructions. 29 c. Manufacturer's catalog cuts and technical data. 30 d. Corrosion-protection information. 31 e. Performance data on all equipment. 32

4. Certifications: Provide certification of thickness of corrosion-protection coating. 33

B. Operation and Maintenance Manuals: See Section 01342. 34

PART 2 - PRODUCTS 35

2.1 ACCEPTABLE MANUFACTURERS 36

A. Subject to compliance with the Contract Documents, the following manufacturers are 37 acceptable: 38 1. Heat exchanger, plate: 39

a. Base: 40 1) Bell & Gossett. 41 2) Alfa Laval Pumps. 42 3) Patterson-Kelly. 43

Page 272: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HEAT EXCHANGERS AND CONVERTERS 15710 - 2

4) Tranter. 1 2. Heat exchanger: 2

a. Double-wall plate and frame. 3 b. Base: 4

1) Bell & Gossett. 5

B. Submit requests for substitution in accordance with Specification Section 01640. 6

2.2 GENERAL 7

A. All manufactured units shall be factory assembled. 8

B. Units shall meet specific requirement, characteristics and capacities scheduled, noted, and 9 indicated on the Drawings. 10

2.3 HEAT EXCHANGERS; PLATE 11

A. Instantaneous flat plat and frame type with corrugated heat transfer plates, support frame, 12 nozzles, tightening mechanism, and sheet metal shroud. 13 1. Capacity as scheduled. 14 2. Maximum Operating Pressure: 150 psig. 15 3. Design temperature as scheduled. 16 4. Maximum Pressure Drop: As scheduled. 17 5. Plates: Stainless steel, herringbone type. 18 6. Heat Transfer Coefficient: Greater than 1000 BTU/HR/SF/DegF. 19 7. Plate Gaskets: EPDM, single piece, molded construction, bonded to plates. 20 8. Nozzles: 150 LB ASA rated flange type. 21 9. ASME Code construction. 22 10. Finish: Baked epoxy with manufacturer’s standard color. 23

2.4 HEAT EXCHANGERS; DOUBLE-WALL, PLATE AND FRAME TYPE 24

A. Description: 25 1. A series of plates are hung from a carrier bar and clamped between fixed and moveable 26

plates. 27 2. Gaskets between plates allow for fluid flow and distribution through main ports in each 28

plate. 29 3. Hot and cold fluids are distributed through alternate plates in counter flow direction. 30 4. Moveable end plate allows separation of the plates for cleaning. 31 5. Each suspended plate is double walled, composed of two (2) thin plates, welded together at 32

the port openings, with the outside edges open, allowing any fluid from a possible leak to 33 drip outside, alerting the user. 34

B. Capacity as indicated. 35 1. Provide space 20 percent additional plates for expansion and to facilitate cleaning. 36

C. ASME Code constructed and stamped for the pressure indicated. 37

D. All surfaces exposed to fluid constructed of stainless steel, including the top, plate hanger bar 38 and the bottom guide bar. 39

E. Protective shroud to be stainless steel. 40

F. Unit is factory assembled and tested. 41

PART 3 - EXECUTION 42

3.1 INSTALLATION 43

A. Install in accordance with Section 11005. 44

Page 273: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HEAT EXCHANGERS AND CONVERTERS 15710 - 3

3.2 FIELD QUALITY CONTROL 1

A. Comply with Section 15990. 2

3.3 ADJUSTING 3

A. Comply with Section 15990. 4

END OF SECTION 5

6

Page 274: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HEAT EXCHANGERS AND CONVERTERS 15710 - 4

1

Page 275: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: DUCTWORK 15890 - 1

2014/08/14 1

SECTION 15890 2

HVAC: DUCTWORK 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: HVAC ductwork and accessories. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 10200 - Louvers and Vents. 10 4. Section 11005 - Equipment: Basic Requirements. 11 5. Section 15970 - Instrumentation and Control for HVAC Systems. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE): 15

a. 52, Method of Testing Air Conditioning Devices Used in General Ventilation for 16 Removing Particulate Matter. 17

2. National Fire Protection Association (NFPA). 18 3. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA): 19

a. Ducted Electric Heat Guide for Air Handling Systems. 20 b. HVAC Duct Construction Standards - Metal and Flexible. 21

4. Underwriters Laboratory, Inc. (UL): 22 a. 555, Standard for Safety Fire Damper and Ceiling Fire Damper. 23 b. 555S, Standard for Safety Leakage Rated Dampers for Use in Smoke Control Systems. 24 c. Building Materials Directory. 25

5. Building Code: 26 a. International Code Council (ICC): 27

1) International Building Code and associated standards, 2003 Edition including all 28 amendments, referred to herein as Building Code. 29

B. Qualifications: 30 1. Fabricator: Firms regularly engaged in the manufacture of the specific product, of type, size 31

required, whose products have been in use in similar service for not less than three (3) years. 32 2. Installers: Firm with at least five (5) years installation experience on products similar to that 33

required for this Project. 34

1.3 DEFINITIONS 35

A. Installer or Applicator: 36 1. Installer or applicator is the person actually installing or applying the product in the field at 37

the Project site. 38 2. Installer and applicator are synonymous. 39

1.4 SUBMITTALS 40

A. Shop Drawings: 41 1. See Specification Section 01340 for requirements for the mechanics and administration of 42

the submittal process. 43 2. See Specification Section 11005. 44 3. Efficiency ratings per ASHRAE 52 for factory built and assembled filter units. 45

Page 276: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: DUCTWORK 15890 - 2

4. Scaled ductwork Drawings (1/4 IN equals 1 FT) showing duct and accessory layout and 1 support. 2

B. Operation and Maintenance Manuals: 3 1. See Specification Section 01342 for requirements for: 4

a. The mechanics and administration of the submittal process. 5 b. The content of Operation and Maintenance Manuals. 6

C. Miscellaneous Submittal: 7 1. Documentation of qualifications for fabricators and installers. 8

PART 2 - PRODUCTS 9

2.1 ACCEPTABLE MANUFACTURERS 10

A. Subject to compliance with the Contract Documents, the following manufacturers are 11 acceptable: 12 1. Transverse joints (factory fabricated aluminum): 13

a. Ductmate Industries, Inc. 14 2. Turning vanes: 15

a. Ductmate Industries, Inc. 16 b. Duro Dyne. 17 c. SEMCO Incorporated. 18 d. Ward Industries, Inc. 19

3. Grilles and registers: 20 a. Anemostat. 21 b. Carnes. 22 c. Titus. 23

4. Air filters: 24 a. American Air Filter. 25 b. Farr. 26 c. Continental. 27

5. Manual (volume) dampers: 28 a. Air Balance. 29 b. Ruskin. 30 c. American Warming. 31

6. Duct sealers: 32 a. Chicago Mastic. 33 b. 3M Co. 34 c. Permatex. 35 d. Benjamin Foster. 36

7. Louvers: 37 a. Ruskin. 38 b. Air Balance. 39 c. American Warming. 40

B. Submit request for substitution in accordance with Specification Section 01640. 41

2.2 COMPONENTS 42

A. Duct and Fittings (Metallic): 43 1. Materials: 3003 H-14 aluminum alloy. 44 2. Fabrication: 45

a. Minimum sheet material thickness: 46 1) Ducts with largest side or diameter to 30 IN: 0.05 IN thick. 47 2) Ducts with largest side or diameter greater than 30 IN: 0.08 IN thick. 48

Page 277: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: DUCTWORK 15890 - 3

b. Utilize SMACNA HVAC Duct Construction Standards for minimum of 2 IN water 1 gage static pressure for the minimum sheet material thickness specified herein. 2 1) Heavier gage sheet material may be used with associated reinforcement as an 3

alternate to minimum thickness specified. 4 2) Lighter gage sheet material with associated reinforcement shall not be used as an 5

alternate to minimum thickness specified. 6 c. Longitudinal seams: 7

1) 0.050 material: 8 a) Pittsburgh seam. 9 b) Continuously welded. 10

2) 0.080 material: Continuously welded. 11 d. Continuously weld seams on factory assembled units. 12 e. Transverse joints (Alternate A): 13

1) SMACNA T-22 companion flange. 14 2) Gasketed. 15 3) Rigidity class: 16

a) Ducts with largest side or diameter to 30 IN: SMACNA Class D (1-1/2 x 1-17 1/2 x 1/8 IN angles). 18

b) Ducts with largest side or diameter greater than 30 to 54 IN: SMACNA Class 19 H (2-1/2 x 2-1/2 x 3/16 IN angles). 20

f. Transverse joints (Alternate B): 21 1) Materials and fabrication: 22

a) Angles: Aluminum. 23 (1) Ductmate 35. 24

b) Corners: Aluminum. 25 (1) Ductmate DC 35. 26

c) Snap cleats: Aluminized or stainless steel. 27 d) Gaskets: Closed cell neoprene. 28 e) Bolts: Stainless steel. 29 f) Sheet metal screws: Self-drilling stainless steel with unthreaded section under 30

head. 31 2) Fabrication: 32

a) Rigidity class: SMACNA Class H. 33 b) 3/8 IN DIA x 1 IN bolts. 34

B. Supports and Hangers: 35 1. Materials: 36

a. Support angles: Aluminum or stainless steel. 37 b. Hanger rods: Stainless steel. 38 c. Anchors: Stainless steel wedge type. 39

2. Fabrication: Trapeze type units. 40

C. Turning Vanes: 41 1. Materials: Same as duct. 42 2. Fabrication: 43

a. Fabricate double vane units. 44 b. Pressure drop through elbows: Maximum 20 percent of velocity pressure. 45

D. Air Grille and Register Assembly: 46 1. Materials: 47

a. Assembly: Extruded aluminum. 48 b. Gaskets: Sponge rubber. 49

2. Fabrication: 50 a. Supply registers: Two (2) sets individually adjustable louvers. 51 b. Exhaust and return registers: 45-degree deflection front blades. 52 c. Dampers: Key-operated opposed blade. 53 d. Screws, duct collars, and transitions as required. 54

Page 278: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: DUCTWORK 15890 - 4

e. Finish: 1 1) Manufacturer's standard factory applied finish. 2 2) Color: White. 3

E. Air Filter Enclosure: 4 1. Housing: 5

a. Factory fabricated. 6 b. 16 GA galvanized steel. 7 c. Bracing to eliminate racking. 8 d. Two-side access doors. 9

2. Access doors: 10 a. 16 GA galvanized steel. 11 b. Replaceable positive sealing latches. 12 c. Replaceable hinges. 13 d. Neoprene door gasket. 14 e. Holding frame to door gasket: Polyurethane foam. 15

3. Tracks: 16 a. Field adjustable. 17 b. Anodized extruded aluminum. 18 c. Polypropylene seal between holding frame and track. 19

4. Holding frame: 20 a. Galvanized steel. 21 b. Multiple fastener lances. 22 c. Polyurethane foam gasket. 23

1) Internally. 24 2) Frame sides. 25

d. Accommodate nominal 24 x 24 IN or 12 x 24 IN filters without modifications to frame 26 or housing. 27

F. Air Filters: 28 1. Materials: 29

a. Holding frame: Aluminum. 30 2. Fabrication: 31

a. Factory built and assembled unit. 32 b. Efficiency rating as per ASHRAE 52. 33 c. 2 IN thickness minimum. 34 d. Efficiency: 20 percent. 35 e. Air velocity: 450 FPM maximum. 36 f. Clean pressure drop: 0.2 IN WG maximum. 37 g. Size, capacity, and type: As indicated on Drawings. 38

G. Temperature Control, Automatic and Manually (Volume) Operated Dampers: 39 1. Material: 40

a. Body: 6063 T5 aluminum. 41 b. Seal blade edge: Extruded vinyl. 42

2. Fabrication: 43 a. Frame thickness: 0.125 IN minimum. 44 b. Provide flanged connections. 45 c. Blades: 46

1) Two-position damper: Parallel blade. 47 2) Mixing and volume damper: Opposed blade. 48 3) Airfoil shape. 49 4) Maximum 6 IN width. 50

d. Linkage: Concealed in frame. 51 e. Axles: 1/2 IN plated steel hex. 52 f. Bearings: Molded synthetic. 53

Page 279: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: DUCTWORK 15890 - 5

g. Seals: 1 1) Jamb: Flexible compression type. 2

h. Control shaft: Removable, 1/2 IN DIA. 3 i. Air leakage (4 FT SQ damper) at 4 IN WG pressure: 99 cfm maximum. 4 j. Motors for motor operated damper: See Specification Section 15970. 5 k. Provide outboard support for operator linkage where damper motor is to be installed 6

outside of duct. 7 l. Provide stainless steel locking quadrants for manual (volume) dampers. 8 m. Provide fold out operator mounting bracket where damper motor is to be installed on 9

face of damper or inside duct. 10 n. Finish: 215 R1 anodized. 11

H. Louvers: See Specification Section 10200. 12

2.3 MAINTENANCE MATERIALS 13

A. Extra Materials: 14 1. Furnish Owner with the following extra materials: 15

a. Twelve complete filter media changes for each filter unit. 16 b. Filter media used during construction is in addition to this requirement. 17

PART 3 - EXECUTION 18

3.1 INSTALLATION 19

A. See Specification Section 11005. 20

B. Metal Ductwork: 21 1. Install with longitudinal seams sealed for zero leakage. 22

a. For welded seams, submit sample for approval by Engineer. 23 2. Install gaskets at each transverse joint and fasten sections together with bolts. 24

a. Tighten for zero leakage. 25 3. Install supports and hangers with anchors in accordance with SMACNA HVAC Duct 26

Construction Standards. 27 4. Install turning vanes in square elbows: 28

a. Unsupported vane length not to exceed 48 IN. 29 b. Position vanes at proper angle to meet specified pressure drop. 30

5. Install flexible connections at fans: 31 a. Locate as close as possible to fan. 32 b. Allow 1 IN of slack to prevent vibration transmission. 33 c. Install thrust restraints across connectors. 34

6. Install access doors where indicated on Drawings and at smoke and fire damper in 35 accordance with NFPA requirements. 36

7. Volume extractors: 37 a. Install at supply registers, grilles, diffusers and supply branch connections from ducts. 38 b. Provide branch duct extensions into main duct above and below extractor when branch 39

duct is narrower than main duct. 40

C. Dampers: 41 1. Install where indicated on Drawings of sizes shown. 42 2. Install fire and smoke dampers in ductwork passing through 1 HR or higher fire-rated 43

construction. 44 a. Install in wall and floor openings utilizing steel sleeves, angles and other materials 45

following practices required to provide installation in accordance with local Building 46 Codes. 47

D. Air Grille and Register Assemblies: 48 1. Install where shown on Drawings of size and capacities scheduled on Drawings. 49

Page 280: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC: DUCTWORK 15890 - 6

2. Install prime painted grilles and registers in areas where duct work is concealed. 1 a. Field paint to match adjacent surface finish. 2

E. Air Filters: 3 1. Install where shown on Drawings of size and capacity scheduled on Drawings. 4 2. Do not operate equipment during construction without filters. 5

END OF SECTION 6

Page 281: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 1

2014/08/28 1

SECTION 15970 2

INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Instrumentation and control for HVAC systems. 7 2. Temperature control. 8 3. Ventilation control. 9 4. Heating control. 10 5. Cooling control. 11 6. Control wiring. 12 7. Panels and accessories. 13 8. Miscellaneous. 14

B. Related Specification Sections include but are not necessarily limited to: 15 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 16 2. Division 01 - General Requirements. 17 3. Section 10400 -Identification Devices. 18 4. Section 11005 - Equipment: Basic Requirements. 19 5. Section 13440 - Instrumentation for Process Control: Basic Requirements. 20 6. Section 15605 - HVAC: Equipment. 21 7. Section 15890 - HVAC: Ductwork. 22 8. Division 16 - Electrical. 23

1.2 QUALITY ASSURANCE 24

A. See Specification Section 11005. 25

B. Referenced Standards: 26 1. ASTM International (ASTM): 27

a. D1693, Standard Test Method for Environmental Stress-Cracking of Ethylene Plastics. 28 2. Instrumentation, Systems, and Automation Society (ISA): 29

a. S5.1, Instrumentation Symbols and Identification. 30 b. S5.4, Standard Instrument Loop Diagrams. 31

3. National Electrical Manufacturers Association (NEMA): 32 a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 33

4. National Fire Protection Association (NFPA): 34 a. 70, National Electrical Code (NEC). 35

5. Underwriters Laboratories, Inc. (UL). 36

C. Miscellaneous: 37 1. Controls to be in compliance with Specification Section 16010 for NEMA and NFPA 70 38

enclosure class requirements unless noted or specified otherwise. 39 2. Unless specifically noted otherwise, components of systems shall be industrial duty suitable 40

for moist, corrosive environments. 41

1.3 SYSTEM DESCRIPTION 42

A. Work shall be provided as an integrated operating system. 43

Page 282: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 2

B. Provide a complete system of automatic temperature control, thermostats, relays, valves, damper 1 operators and other associated controls and appurtenances required to maintain minimum 2 conditions described in detail herein and on Drawings, together with thermometers, gages and 3 other accessory equipment. 4 1. Assemble control system with complete system of wiring and air piping to fulfill 5

requirements of the Contract Documents. 6

C. Install system using competent mechanics under direct supervision of control manufacturer. 7

D. Controls, as set out in "Sequence of Operation," are designed to illustrate operating functions 8 only. 9 1. Control sequence shall be considered supplementary to "Sequence of Operation." 10 2. These minimum specified items, and any additional controls, not indicated but required to 11

meet performance as outlined in the Contract Documents, shall be furnished and installed at 12 no additional cost to Owner to make a complete system. 13

E. Sequence of Operation - General: 14 1. Sequence of operation indicated illustrates basic operating functions only. 15 2. Contractor shall review Drawings and submit complete installation data, including minor 16

details, to provide proper operation in his proposal. 17 3. Where an item differs from specifications, control manufacturer shall submit manufacturer's 18

recommendations subject to Engineer's approval. 19 4. Collector Well: 20

a. AHU-01. 21 1) Circuited from MSB01. 22 2) Controlled by HOA switch. 23

a) HAND: AHU-01 fan is “ON”. 24 b) OFF: AHU-01 fan is “OFF”. 25 c) AUTO: AHU-01 is controlled by a wall-mounted thermostat. 26

(1) Maintain summer cooling set point of 80 DegF (adjustable). 27 (2) Maintain winter heating set point of 60 DegF (adjustable). 28

b. P-01 and P-02: 29 1) Circuited from MSB01. 30 2) Controlled by contacts from AHU-01. 31

a) Pumps will turn on after receiving a signal from AHU-01 calling for heating or 32 cooling. 33

c. EF-01 and SF-01. 34 1) Circuited from LP2. 35 2) Controlled by HO switch. 36

a) HAND: EF-01 and SF-01 are “ON”. 37 b) OFF: EF-01 and SF-01 are “OFF”. 38

d. MOD-01. 39 1) Circuited from LP2. 40 2) Controlled by HOA switch. 41

a) HAND: MOD-01 is “OPEN”. 42 b) OFF: MOD-01 is “CLOSED”. 43 c) AUTO: MOD-01 is controlled by wall-mounted thermostat. 44

(1) Above set point 85 DegF (adjustable): MOD-01 is “OPEN”. 45 (2) Below set point 85 DegF (adjustable): MOD-01 is “CLOSED”. 46

e. EF-02. 47 1) Circuited from LP2. 48 2) Controlled by end switch on MOD-01. 49

a) MOD-01 is “OPEN”: EF-02 is “ON”. 50 b) MOD-01 is “CLOSED”: EF-02 is “OFF”. 51

Page 283: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 3

1.4 SUBMITTALS 1

A. Shop Drawings: 2 1. See Specification Section 01340 for requirements for the mechanics and administration of 3

the submittal process. 4 2. Wiring diagrams showing point to point termination with auxiliary interlocks for each item 5

in each control loop. 6 3. Pneumatic piping diagrams. 7 4. Information on equipment proposed for use including corrosion protection. 8 5. Instrument loop diagrams and word description of loop function for each individual unit 9

controlled including auxiliary interlocks in full compliance with ISA S5.4. 10 a. Show components in system and ensure diagrams are in full compliance with ISA S5.1 11

(Instrumentation Symbols and Identification) and other related ISA standards. 12

B. Quality Control Submittals: 13 1. Secure from equipment manufacturers, detailed and complete control and power wiring 14

diagrams, word descriptions of controls provided as part of the HVAC equipment or 15 equipment interfaced or interlocked thereto, and submit with equipment manufacturer's 16 submittals. 17 a. Provide the above information to control manufacturer. 18

C. Operation and Maintenance Manuals: 19 1. See Specification Section 01342 for requirements for: 20

a. The mechanics and administration of the submittal process. 21 b. The content of Operation and Maintenance Manuals. 22

1.5 SITE CONDITIONS 23

A. Unless stated otherwise, the environment and air streams will include varying concentrations of 24 the following chemical components: 25 1. Condensation. 26

PART 2 - PRODUCTS 27

2.1 ACCEPTABLE MANUFACTURERS 28

A. Subject to compliance with the Contract Documents, the following manufacturers are 29 acceptable: 30 1. Manufacturer's catalog numbers hereinafter are for reference to type, style, dimension, 31

related items and to establish a standard of quality. 32 a. Reference to a manufacturer's number hereinafter does not imply full compliance to 33

these Specifications. 34 2. Instrumentation and control systems: 35

a. Honeywell. 36 b. Johnson Control Co. 37

B. Submit request for substitution in accordance with Specification Section 01640. 38

2.2 EQUIPMENT 39

A. Dampers: Refer to Specification Section 15890. 40

B. Damper Operators: 41 1. Provide operators of proper size and number to secure true throttling or two-position action 42

as required. 43 2. Furnish damper operators for installation inside ductwork and attached to frame of damper, 44

or installed outside ductwork and connected to extended shaft as required. 45 3. Provide operators for outside air, spring-loaded with sufficient power to assure tight closing 46

of dampers on fan shutdown or in the fail safe position indicated by "Sequence of Controls." 47

Page 284: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 4

4. Electric operators: 1 a. Provide operators: 2

1) Fully immersed in oil gear train. 3 2) Enclosed in closed cast aluminum housing. 4

b. As an alternate to 5.a.: Provide operators in NEMA 4X enclosure, Belimo ZS-300. 5 c. Provide damper operators with integral spring return motor springs to make controls 6

fail safe in position specified under "Sequence of Controls." 7 d. Provide fully modulating operators from proportional electric controllers. 8 e. Provide end switches or proportioning controllers permitting simultaneous operation or 9

interlocking with other equipment. 10 f. Provide separate electrical circuits for damper operators with no more than four (4) 11

operators on a circuit. 12 5. Coordinate with dampers provided: 13

a. Provide damper operators that are rated for the required torque. 14 b. If single damper operator can not meet torque requirement, provide sectional dampers 15

to match operator torque. 16 6. Use of electric operators shall be limited to small dampers in those applications where it is 17

impractical to provide pneumatic operators and are to be approved by the Engineer. 18 7. Ensure coordination to provide for the installation of tight closing dampers low leakage type 19

(6 cfm per square foot at 4 IN WC pressure across damper) with compatible dampers, 20 damper operators and related controls. 21

C. Electric Control Instruments: 22 1. Provide stainless steel sensing elements type thermostats with liquid filled, compensated 23

thermal systems so that equally spaced dial graduations are possible over entire range. 24 a. Make thermal systems field detachable with averaging or plain bulbs as installation 25

conditions dictate. 26 b. Provide sensing elements minimum of 60 IN in length and suitable for operation from -27

30 to 300 DegF. 28 c. Provide reverse acting on-off type thermostats for controlling ventilating fans. 29 d. Provide multiple stage thermostats where designated in Paragraph "Sequence of 30

Operation." 31 2. Provide transformers for supplying current to control equipment operating at less than 120 32

V and where required by manufacturer's automatic control system design capable of 33 supplying 125 percent of energy requirements of equipment connected for not less than 1 34 HR. 35 a. Enclose transformers in UL listed cabinets with conduit connections. 36 b. Provide fused disconnect switches on both primary and secondary sides. 37 c. Provide in full compliance with Division 16 Specification Sections. 38

3. Provide low limit electric thermostats of two-position type with 20 FT bulb and manual 39 reset. 40 a. Shall be capable of opening thermostat circuit if any 1 FT section of bulb is subjected to 41

a temperature below thermostat setting. 42 b. Each thermostat shall have two (2) circuits, one (1) to shut down fan, another for alarm. 43 c. Install all freeze-stats to override starter circuits regardless of position. 44 d. For corrosive environments provide thermostats with stainless steel sensing elements. 45

1) Ensure element is installed to sense coldest point should stratification occur. 46 4. Provide each thermostat with an accurate red-reading thermometer sensing temperature 47

outside of enclosure. 48 5. Label thermostat with identification tag of HVAC equipment controlled using phenolic 49

nameplate in accordance with Specification Section 10400. 50

D. Industrial Controllers: 51 1. Provide control instruments, devices, and incidentals of industrial process control quality 52

capable of producing the outlined performances. 53 2. Controller shall be capable of receiving both pneumatic and analog electric systems. 54

Page 285: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 5

3. The pneumatic controller shall have three (3) control mode capabilities of proportional, 1 automatic reset, and rate (derivative) within following minimum performance and 2 application criteria: 3 a. Proportional band: 1 to 40 percent. 4 b. Reset rate: 1 to 20 repeats per minute. 5 c. Rate (derivative): 0.1 to 15 minutes. 6 d. Hysteresis: Less than 0.25 percent of span. 7 e. Tracking accuracy: Within 0.5 percent of span. 8 f. Repeatability: Within 0.1 percent of span. 9 g. Response level: Less than 0.01 percent of span. 10

4. Electronic (and electric) controller shall have three (3) control mode capabilities of 11 proportional rate (time), and dead band within following minimum performance and 12 application criteria: 13 a. Setpoint adjustment: 0 to 110 percent of span. 14 b. Repeatability: Setpoint repeats within +0.1 percent of span. 15 c. Dead band: 1 percent of span, standard. 16 d. Rate: 5 to 30 seconds adjustable. 17 e. Response level: 50 milliseconds for a step change of 1 percent of span beyond 18

setpoints. 19 f. Output: SPDT relay contacts, 5 amps at 117 Vac noninductive. 20

5. Controller shall be capable of remote setpoint adjustment, permanently mounted in air flow 21 control panel unless otherwise indicated. 22

6. Provide each controller with instruments (pressure gages, milliampmeters, voltmeters, etc.) 23 to indicate magnitude of output signal in both medium of signal (psig, mA, volt DC, etc.) 24 and percentage of full output signal. 25

7. Recording controllers: 26 a. Where recording controllers are required by "Sequence of Controls," they shall be 10 27

IN chart, 24 HR or 30-day charts (field selection), with one (1), two (2), or three (3) 28 pens as listed in control sequence. 29

b. Pens shall have capillary ink supply and cartridge type ink supply. 30 c. Recorders shall operate on 110 V power supply. 31 d. Optional 4 IN strip chart recorders may be used with the strip traveling vertically. 32

E. Static Pressure Gages: 33 1. Install gages on control panel for each system. 34

a. One (1) gage shall serve each filter while others shall serve as a check on system. 35 b. Gages shall be Magnahelic by Dwyer 2000 ASF, flush mounted with signal flag for 36

filter gage. 37 c. Install static pressure tips as scheduled under control panel indication points. 38 d. Static pressure ranges: 39

1) Filter (cartridge): 0 to 2.0 IN WC. 40 2) Air-handling systems: 0 to 10.0 IN WC (one (1) per air-handling unit). 41

F. Local Temperature Control Panel: 42 1. Panel shall be floor or wall-mounted and be sized to accommodate electrical switches, 43

protective devices (except electrical switches and devices furnished as an integral part of air 44 handling unit). 45

2. Mount indicating controllers or receiver-controllers, three-way air valves, relay, EP and PE 46 switches, switching relays, ammeters and other accessory items on local sub-panels set in 47 vicinity of equipment to be served. 48 a. Where two (2) similar items of equipment, such as pumps, are installed adjacent to each 49

other a single panel may be used to contain all instruments. 50 3. Fully compensated capillaries connected to instruments shall be of sufficient length to allow 51

them to be run between equipment and placed in such a position so that they will not 52 obstruct service of equipment or become damaged. 53

Page 286: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 6

4. Air pressure gages for pneumatic controls of at least 2 IN in diameter shall be provided for 1 indication of transmitter signals and output signal of all controllers, relays, EP switches, 2 outdoor air dampers, PE switches, control valves larger than 4 IN and other points 3 throughout system. 4 a. Provide visual indication for operating purposes. 5 b. Temperature and pressure indicating gages where scheduled for panel door mounting 6

shall be not less than 2-1/2 IN in diameter, flush mounted with accuracy of +1 DegF. 7 c. Where a temperature indication gage is used, a pressure gage is not required for same 8

signal. 9 d. Transmitter signal and controller output gages shall be in-line mounted or mounted on 10

controllers if provided with tapped connections. 11 e. One (1) or more permanently mounted gages with flexible hose terminating in a 12

hypodermic needle may be used for checking other parts of control signals; however, 13 signal connections may not be used as a substitute for in-line mounted gages. 14

f. All gages and instruments shall be suitably tagged with their function. 15 5. Miniature milliamp meters for electronic temperature transmission may be used. 16 6. Manufacture panels in one (1) of the following manners: 17

a. NEMA electrical panel boxes with windows. 18 b. Install gages flush mounted in swing out panel behind window with instruments and 19

other control items located inside enclosures behind panel. 20 1) Refer to Paragraph "Corrosion Protection." 21

7. Mount all relays, PE switches, pressure switches, etc., on rear inside of enclosure. 22 a. Tag each instrument corresponding to symbols used on control diagrams. 23

8. Temperatures, pressures, equipment operation, and related items shall be continuously 24 indicated on panels. 25

9. Points to be monitored are scheduled under another paragraph of this Specification Section. 26

2.3 FABRICATION 27

A. Corrosion Protection: 28 1. Protect metal parts of controls, instrumentation and related items from corrosive atmosphere 29

by either protective coatings or select materials. 30 a. Aluminum and stainless steel require no further protection. 31

2. Provide NEMA 4X fiberglass control enclosures with tempered glass windows and vapor 32 tight gaskets, illustrated in Hoffman Bulletin A-50, for protection of controls from corrosive 33 environment. 34 a. Install control instruments inside enclosure and extend remote stainless steel sensing 35

elements through enclosure wall. 36 b. Provide vaportight seals for penetrations of enclosure. 37

3. Provide in each enclosure industrial corrosion inhibitors, Hoffman Corrosion Inhibitors, as 38 illustrated in Hoffman's technical Bulletin HCI. 39

4. Protect metal accessory items such as mounting brackets and fasteners not stainless steel, 40 fiberglass or aluminum by epoxy or phenolic coatings. 41

5. Protect electric motor operator with corrosion inhibitors inside enclosure. 42

PART 3 - EXECUTION 43

3.1 INSTALLATION 44

A. Comply with requirements of Specification Section 16120 and Specification Section 16130. 45

B. Identification: See Specification Section 10400. 46

C. Connect control devices to perform functions indicated and perform in required sequence. 47

D. Use remote element temperature transmitters for points of temperature transmitters for points of 48 temperature measurement occurring in air ducts or shafts, or in mechanical piping system. 49

Page 287: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 7

E. Use remote element pressure transmitters of panel-mounted pressure gages. 1

F. Where continuous indication of space temperature is on local control panels, install a thermostat 2 and a temperature transmitter side by side. 3 1. Pipe continuous indication signal to a receiver on panel. 4 2. A resistance element or thermocouple signal may be used with continuous indicating meter, 5

calibrated in degrees Fahrenheit. 6

G. In general, locate thermostats for room control immediately inside door, above light switch, 7 unless shown otherwise. 8 1. Where light switch is in an entryway to room, locate thermostat on wall within room so it is 9

capable of sensing true space conditions. 10 2. Prior to installation, coordinate thermostat location with Engineer. 11

H. Mount local control panels adjacent to equipment served. 12

I. Where a temperature indicating gage is used at the panel, a pressure gage indicating transmitter 13 signal is not required. 14

J. Provide appropriate type continuous reading indicator for each controller, transmitter and 15 transducer. 16 1. Mount in-line or tapped on controller. 17 2. Mount at local control panel. 18

K. Gages with flexible hose terminating with hypodermic needle may be used for checking control 19 system. 20 1. Do not substitute for in-line gages. 21

L. Locate panels so visual observation and adjustment can be accomplished from floor level. 22

END OF SECTION 23

24

Page 288: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INSTRUMENTATION AND CONTROL FOR HVAC SYSTEMS 15970 - 8

1

Page 289: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC SYSTEMS: BALANCING AND TESTING 15990 - 1

2014/08/14 1

SECTION 15990 2

HVAC SYSTEMS: BALANCING AND TESTING 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Adjusting, balancing, and testing of all heating, ventilating and air conditioning (HVAC) 7

systems, including the following systems: 8 a. Air distribution and exhaust systems. 9 b. Air moving equipment. 10 c. Circulating water systems, including pumps. 11 d. Control systems. 12 e. Chilled water system. 13 f. Heating system. 14

B. Related Sections include but are not necessarily limited to: 15 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 16 2. Division 01 - General Requirements. 17 3. Section 15605 - HVAC: Equipment. 18 4. Section 15890 - HVAC: Ductwork. 19 5. Section 15970 - Instrumentation and Control for HVAC Systems. 20

1.2 QUALITY ASSURANCE 21

A. Referenced Standards: 22 1. Associated Air Balance Council (AABC): 23

a. National Standards for Total System Balance. 24 2. American Industrial Hygiene Association (AIHA): 25

a. Z9.5, Laboratory Ventilation. 26 3. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE): 27

a. HVAC Applications Handbook, Chapter entitled "Laboratories." 28 b. HVAC Systems and Equipment Handbook, Chapter entitled "Testing, Adjusting, and 29

Balancing." 30 4. National Environmental Balancing Bureau (NEBB): 31

a. Procedural Standards for Testing Adjusting Balancing of Environmental Systems. 32

B. Qualifications: 33 1. Work of this Section to be accomplished by an independent testing and balancing firm 34

certified by one (1) of the following: 35 a. Associated Air Balance Council (AABC). 36 b. National Environmental Balancing Bureau (NEBB). 37 c. Other certification entity approved by Engineer. 38

2. The independent firm shall not be the same firm as the firm installing the HVAC equipment, 39 nor under contract to the firm installing the equipment. 40

1.3 SUBMITTALS 41

A. Shop Drawings: 42 1. See Specification Section 01340 for requirements for the mechanics and administration of 43

the submittal process. 44 2. Certifications: 45

a. Letter stating the name and qualifications of the firm proposed. 46

Page 290: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC SYSTEMS: BALANCING AND TESTING 15990 - 2

b. Evidence that relevant subcontractors have been notified of the requirement to 1 coordinate balance and test elements in the work with the testing and balancing firm. 2

3. Report forms: 3 a. Procedures and forms to be used in calibrating of test instruments, balancing systems, 4

and recording and reporting test data. 5

B. Informational Submittals: 6 1. Completed test reports and data forms upon completion of installation, balance and testing 7

of HVAC systems. 8 a. Insert recorded information on report forms required by specifications and approved for 9

use on project. 10 b. Additional written verification and other related information clearly identifying project, 11

date and specifics of verification. 12 c. Utilize report forms similar to those shown in Section V of AABC Standard. 13 d. Provide forms typed and signed by the testing and balancing firm. 14

PART 2 - PRODUCTS - (NOT APPLICABLE TO THIS SECTION) 15

PART 3 - EXECUTION 16

3.1 PREPARATION 17

A. Secure approved Shop Drawings of all HVAC equipment. 18

B. Procedures and Forms: 19 1. Submit procedures and forms to be used in calibration of test instruments, balancing 20

systems, and recording and reporting test data. 21 2. Obtain approval before beginning balancing and testing. 22

C. Do not begin balancing and testing until HVAC systems are complete and in full working order. 23 1. Place HVAC systems into full operation and continue their operation during each working 24

day of balancing and testing. 25

D. Provide qualified heating and ventilating Engineer(s) to supervise and perform balancing and 26 testing. 27

E. Review design Drawings, specifications, approved Shop Drawings and other related items to 28 become thoroughly acquainted with the design of HVAC systems. 29

F. Check all installed systems against Contract Drawings, Specifications and Shop Drawings to see 30 that system is installed as required. 31 1. Report deficiencies to the Engineer. 32 2. Report deficiencies to Contractor for remedial action including providing corrective 33

measures required in the function of any part of system to complete balancing. 34

G. Make necessary adjustments as required to balance the systems. 35

3.2 FIELD QUALITY CONTROL 36

A. Balance and Test Air Systems: 37 1. Adjust equipment RPM to design requirements. 38 2. Report motor full load amperes. 39 3. Obtain design CFM at fans. 40

a. Make pitot tube traverse of main supply and exhaust ducts within 5 percent. 41 4. Test and record system static pressures, suction and discharge. 42 5. Obtain design CFM for recirculated air. 43 6. Obtain design CFM outside air. 44 7. Test and record entering air temperatures, (DB, heating and cooling). 45

Page 291: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC SYSTEMS: BALANCING AND TESTING 15990 - 3

8. Test and record leaving air temperatures, (DB, heating and cooling). 1 9. Test and record leaving air temperatures, (WB, cooling). 2 10. Adjust dampers in supply, exhaust and return air ducts to design CFM. 3 11. Test diffusers, grilles, and registers as follows: 4

a. Adjust to comply with design requirements within 10 percent. 5 b. Identify location and area of each. 6 c. Adjust face velocity to establish required CFM. 7

1) Retest after initial adjustments. 8 d. Adjust to minimize drafts and to ensure uniform air distribution in all areas. 9

12. Identify and list size, type and manufacturer of diffusers, grilles, registers, and HVAC 10 equipment. 11 a. Use manufacturer's ratings on equipment to make required calculations. 12

13. Adjust and assure that the operation of automatically operated dampers are as specified. 13 a. Check and calibrate controls. 14

14. Prepare and submit reports. 15

B. Balance and Test Water Systems: 16 1. Phase 1: 17

a. Complete air balance before beginning actual water balance. 18 b. Open valves to full open position. 19

1) Close coil bypass stop valves. 20 2) Set mixing valve to full coil flow. 21

c. Check operation of relief valves. 22 d. Examine water in system and determine if water has been treated and cleaned. 23

1) Clean strainers before and after balancing. 24 e. Check pump rotation. 25 f. Check expansion tanks to determine they are not air bound and system is completely 26

full of water. 27 g. Check air vents at high points of water systems and determine all are installed and 28

operating correctly. 29 h. Set temperature controls so coils are calling for full heating. 30

1) This should close automatic bypass valves. 31 2) Utilize same procedure when balancing chilled water coils, set on call for full 32

cooling. 33 i. Check operation of automatic bypass valves. 34

2. Phase 2: 35 a. Set pumps to proper flow delivery. 36 b. Adjust and record waterflow at system entrance. 37 c. Adjust and record waterflow through pumps. 38 d. Check and record water entering temperatures and return water temperatures at system 39

entrance. 40 1) Set to correct design temperatures. 41

e. Check water temperatures at inlet side of cooling and heating coils. 42 1) Record rise or drop of temperatures from source. 43

f. Proceed to balance each chilled water and hot water coil. 44 g. Upon completion of flow readings and adjustments at coils, mark settings and record 45

data. 46 3. Phase 3: 47

a. After adjustments to coils are made, recheck settings at pumps and readjust if required. 48 b. Install pressure gauges on coil, read pressure drop through coil at set flowrate. 49

1) Set pressure drop across bypass valve to match coil full flow pressure drop to 50 prevent unbalanced flow conditions when coils are on full bypass. 51

c. Check and record the following items at each cooling heating element: 52 1) Inlet water temperatures. 53 2) Leaving water temperatures. 54 3) Pressure drop of each coil. 55

Page 292: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - HVAC SYSTEMS: BALANCING AND TESTING 15990 - 4

4) Pressure drop across bypass valve. 1 5) Pump operating suction and discharge pressures and final TDH. 2 6) Water metering device readings. 3

d. List mechanical specifications of pumps. 4 e. Record rated and actual running amperage of pump motor. 5 f. Prepare and submit report. 6

END OF SECTION 7

Page 293: City of Yankton, SD

D I V I S I O N 1 6 ELECTRICAL

Page 294: City of Yankton, SD
Page 295: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: BASIC REQUIREMENTS 16010 - 1

2014/08/14 1

SECTION 16010 2

ELECTRICAL: BASIC REQUIREMENTS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Basic requirements for electrical systems. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 10400 - Identification Devices. 10 4. Section 11005 - Equipment: Basic Requirements. 11 5. Division 16 - Electrical. 12 6. Section 16120 - Wire and Cable - 600 Volt and Below. 13 7. Section 16130 - Raceways and Boxes. 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. Aluminum Association (AA). 17 2. ETL Testing Laboratories (ETL). 18 3. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 19

a. C2, National Electrical Safety Code (NESC). 20 4. National Electrical Manufacturers Association (NEMA): 21

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 22 5. National Fire Protection Association (NFPA): 23

a. 70, National Electrical Code (NEC). 24 6. Underwriters Laboratories, Inc. (UL). 25

B. Where UL test procedures have been established for the product type, use UL or ETL approved 26 electrical equipment and provide with the UL or ETL label. 27

1.3 DEFINITIONS 28

A. For the purposes of providing materials and installing electrical work the following definitions 29 shall be used. 30 1. Outdoor area: Exterior locations where the equipment is normally exposed to the weather 31

and including below grade structures, such as vaults, manholes, handholes and in-ground 32 pump stations. 33

2. Non-architecturally finished interior area: Pump, chemical, mechanical, electrical rooms 34 and other similar process type rooms. 35

3. Shop fabricated: Manufactured or assembled equipment for which a UL test procedure has 36 not been established. 37

1.4 SUBMITTALS 38

A. Shop Drawings: 39 1. See Specification Section 01340 for requirements for the mechanics and administration of 40

submittal process. 41 2. See Specification Section 11005 and individual specification sections for submittal 42

requirements for products defined as equipment. 43

Page 296: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: BASIC REQUIREMENTS 16010 - 2

3. General requirements: 1 a. Provide manufacturer's technical information on products to be used, including product 2

descriptive bulletin. 3 b. Include data sheets that include manufacturer's name and product model number. 4

1) Clearly identify all optional accessories. 5 c. Acknowledgement that products are UL or ETL listed or are constructed utilizing UL 6

or ETL recognized components. 7 d. Manufacturer's delivery, storage, handling and installation instructions. 8 e. Product installation details. 9 f. See individual specification sections for any additional requirements. 10

4. Product technical data: 11 a. Provide submittal data for all products specified in PART 2 of this Specification 12

Section. 13

B. Operation and Maintenance Manuals: 14 1. See Specification Section 01342 for requirements for: 15

a. The mechanics and administration of the submittal process. 16 b. The content process of Operation and Maintenance Manuals. 17

C. When a Specification Section includes products specified in another Specification Section, each 18 Specification Section shall have the required Shop Drawing transmittal form per Specification 19 Section 01340 and all Specification Sections shall be submitted simultaneously. 20

1.5 DELIVERY, STORAGE, AND HANDLING 21

A. See Specification Section 01600. 22

B. Protect nameplates on electrical equipment to prevent defacing. 23

1.6 AREA DESIGNATIONS 24

A. Designation of an area will determine the NEMA rating of the electrical equipment enclosures, 25 types of conduits and installation methods to be used in that area. 26 1. Outdoor areas: 27

a. Wet. 28 2. Indoor areas: 29

a. Dry. 30 b. Also, wet, when specifically designated on the Drawings or in the Specifications. 31

PART 2 - PRODUCTS 32

2.1 ACCEPTABLE MANUFACTURERS 33

A. Subject to compliance with the Contract Documents, refer to specific Division 16 Specification 34 Sections and specific material paragraphs below for acceptable manufacturers. 35

B. Submit request for substitution in accordance with Specification Section 01640. 36

C. Provide all components of a similar type by one (1) manufacturer. 37

2.2 MATERIALS 38

A. Electrical Equipment Support Pedestals and/or Racks: 39 1. Approved manufacturers: 40

a. Modular strut: 41 1) Unistrut Building Systems. 42 2) Eaton B-Line. 43 3) Globe Strut. 44 4) Thomas & Betts Superstrut. 45

Page 297: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: BASIC REQUIREMENTS 16010 - 3

2. Material requirements: 1 a. Modular strut: 2

1) Stainless steel: AISI Type 316. 3 2) Aluminum: AA Type 6063-T6. 4

b. Mounting plates: 5 1) Aluminum: AA Type 6063-T6. 6

c. Mounting hardware: 7 1) Stainless steel. 8

d. Anchorage per Specification Section 05505. 9

PART 3 - EXECUTION 10

3.1 INSTALLATION 11

A. Install and wire all equipment, including pre-purchased equipment, and perform all tests 12 necessary to assure conformance to the Drawings and Specification Sections and ensure that 13 equipment is ready and safe for energization. 14

B. Install equipment in accordance with the requirements of: 15 1. NFPA 70. 16 2. IEEE C2. 17 3. The manufacturer's instructions. 18

C. In general, conduit routing is not shown on the Drawings. 19 1. The Contractor is responsible for routing all conduits including those shown on one-line and 20

control block diagrams and home runs shown on floor plans. 21 2. Conduit routings and stub-up locations that are shown are approximate; exact routing to be 22

as required for equipment furnished and field conditions. 23

D. When complete branch circuiting is not shown on the Drawings: 24 1. A homerun indicating panelboard name and circuit number will be shown and the circuit 25

number will be shown adjacent to the additional devices (e.g., light fixture and receptacles) 26 on the same circuit. 27

2. The Contractor shall furnish and install all conduit and conductors required for proper 28 operation of the circuit. 29

3. The indicated home run conduit and conductor size shall be used for the entire branch 30 circuit. 31

4. See Specification Section 16120 for combining multiple branch circuits in a common 32 conduit. 33

E. Do not use equipment that exceeds dimensions or reduces clearances indicated on the Drawings 34 or as required by the NFPA 70. 35

F. Install equipment plumb, square and true with construction features and securely fastened. 36

G. Install electrical equipment, including pull and junction boxes, minimum of 6 IN from process, 37 gas, air and water piping and equipment. 38

H. Install equipment so it is readily accessible for operation and maintenance, is not blocked or 39 concealed and does not interfere with normal operation and maintenance requirements of other 40 equipment. 41

I. Device Mounting Schedule: 42 1. Unless indicated otherwise on the Drawings, mounting heights are as indicated below: 43

a. Light switch (to center): 48 IN. 44 b. Receptacle in non-architecturally finished areas (to center): 48 IN. 45 c. Safety switch (to center of operating handle): 54 IN. 46 d. Separately mounted motor starter (to center of operating handle): 54 IN. 47 e. Pushbutton or selector switch control station (to center): 48 IN. 48

Page 298: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: BASIC REQUIREMENTS 16010 - 4

f. Panelboard (to top): 72 IN. 1

J. Avoid interference of electrical equipment operation and maintenance with structural members, 2 building features and equipment of other trades. 3 1. When it is necessary to adjust the intended location of electrical equipment, unless 4

specifically dimensioned or detailed, the Contractor may make adjustments in equipment 5 locations in accordance with the following without obtaining the Engineer's approval: 6 a. 1 FT at grade, floor and roof level in any direction in the horizontal plane. 7 b. 1 FT for equipment other than lighting at ceiling level in any direction in the horizontal 8

plane. 9 c. 1 FT for lighting fixtures at ceiling level in any direction in the horizontal plane.. 10 d. 1 FT on walls in a horizontal direction within the vertical plane. 11 e. Changes in equipment location exceeding those defined above require the Engineer's 12

approval. 13

K. Provide electrical equipment support system per the following area designations: 14 1. Dry areas: 15

a. Aluminum system consisting of aluminum channels and fittings with stainless steel nuts 16 and hardware. 17

2. Wet areas: 18 a. Aluminum system consisting of aluminum channels and fittings with stainless steel nuts 19

and hardware. 20

L. Provide all necessary anchoring devices and supports rated for the equipment load based on 21 dimensions and weights verified from approved submittals, or as recommended by the 22 manufacturer. 23 1. See Specification Section 05505. 24 2. Do not cut, or weld to, building structural members. 25 3. Do not mount safety switches or other equipment to equipment enclosures, unless enclosure 26

mounting surface is properly braced to accept mounting of external equipment. 27

M. Provide corrosion resistant spacers to maintain 1/4 IN separation between metallic equipment 28 and/or metallic equipment supports and mounting surface in wet areas, on below grade walls and 29 on walls of liquid containment or processing areas such as Basins, Clarifiers, Digesters, 30 Reservoirs, etc. 31

N. Do not place equipment fabricated from aluminum in direct contact with earth or concrete. 32

O. Screen or seal all openings into equipment mounted outdoors to prevent the entrance of rodents 33 and insects. 34

P. Do not use materials that may cause the walls or roof of a building to discolor or rust. 35

Q. Identify electrical equipment and components in accordance with Specification Section 10400. 36

3.2 FIELD QUALITY CONTROL 37

A. Verify exact rough-in location and dimensions for connection to electrified equipment, provided 38 by others. 39 1. See Specification Section 01800 for openings and penetrations in structures. 40

B. Replace equipment and systems found inoperative or defective and re-test. 41

C. Cleaning: 42 1. See Specification Section 01710. 43

D. The protective coating integrity of support structures and equipment enclosures shall be 44 maintained. 45 1. Repair galvanized components utilizing a zinc rich paint. 46 2. Repair painted components utilizing touch up paint provided by or approved by the 47

manufacturer. 48

Page 299: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: BASIC REQUIREMENTS 16010 - 5

3. Repair PVC coated components utilizing a patching compound, of the same material as the 1 coating, provided by the manufacturer of the component. 2

4. Repair surfaces which will be inaccessible after installation prior to installation. 3 5. See Specification Section 16130 for requirements for conduits and associated accessories. 4

E. Replace nameplates damaged during installation. 5

3.3 DEMONSTRATION 6

A. Demonstrate equipment in accordance with Specification Section 01650. 7

END OF SECTION 8

9

Page 300: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: BASIC REQUIREMENTS 16010 - 6

1

Page 301: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GROUNDING 16060 - 1

2014/08/28 1

SECTION 16060 2

GROUNDING 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Material and installation requirements for grounding system(s). 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 02444 - Chain Link Fence and Gates. 10 4. Section 10400 - Identification Devices. 11 5. Section 16010 - Electrical: Basic Requirements. 12 6. Section 16080 - Acceptance Testing. 13 7. Section 16120 - Wire and Cable - 600 Volt and Below. 14 8. Section 16130 - Raceways and Boxes. 15

1.2 QUALITY ASSURANCE 16

A. Referenced Standards: 17 1. ASTM International (ASTM): 18

a. B8, Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, 19 Medium-Hard, or Soft. 20

2. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 21 a. 837, Standard for Qualifying Permanent Connections Used in Substation Grounding. 22

3. National Fire Protection Association (NFPA): 23 a. 70, National Electrical Code (NEC). 24

1) Article 250, Grounding and Bonding. 25 4. Underwriters Laboratories, Inc. (UL): 26

a. 467, Grounding and Bonding Equipment. 27

B. Assure ground continuity is continuous throughout the entire Project. 28

1.3 SUBMITTALS 29

A. Shop Drawings: 30 1. See Specification Section 01340 for requirements for the mechanics and administration of 31

the submittal process. 32 2. Product technical data. 33

a. Provide submittal data for all products specified in PART 2 of this Specification 34 Section except: 35 1) Grounding clamps, terminals and connectors. 36 2) Exothermic welding system. 37

b. See Specification Section 16010 for additional requirements. 38

Page 302: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GROUNDING 16060 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Ground rods and bars and grounding clamps, connectors and terminals: 5

a. Burndy. 6 b. Harger Lightning Protection. 7 c. Heary Brothers. 8 d. Joslyn. 9 e. Robbins Lightning Protection. 10 f. Thomas & Betts Blackburn. 11 g. Thompson. 12

2. Exothermic weld connections: 13 a. Erico Products Inc., Cadweld. 14 b. Harger Lightning Protection. 15 c. Thermoweld. 16 d. Thomas & Betts Furseweld. 17

B. Submit request for substitution in accordance with Specification Section 01640. 18

2.2 COMPONENTS 19

A. Wire and Cable: 20 1. Bare conductors: Soft drawn stranded copper meeting ASTM B8. 21 2. Insulated conductors: Color coded green, per Specification Section 16120. 22

B. Conduit: As specified in Specification Section 16130. 23

C. Ground Bars: 24 1. Solid copper: 25

a. 1/4 IN thick. 26 b. 2 IN wide. 27 c. 24 IN long minimum in main service entrance electrical rooms, 12 IN long elsewhere. 28

2. Predrilled grounding lug mounting holes. 29 3. Stainless steel or galvanized steel mounting brackets. 30 4. Insulated standoffs. 31

D. Ground Rods: 32 1. 3/4 IN x 10 FT, or as indicated on the Drawings. 33 2. Copperclad: 34

a. Heavy uniform coating of electrolytic copper molecularly bonded to a rigid steel core. 35 b. Corrosion resistant bond between the copper and steel. 36 c. Hard drawn for a scar-resistant surface. 37

E. Grounding Clamps, Connectors and Terminals: 38 1. Mechanical type: 39

a. Standards: UL 467. 40 b. High copper alloy content. 41

2. Compression type for interior locations: 42 a. Standards: UL 467. 43 b. High copper alloy content. 44 c. Non-reversible. 45 d. Terminals for connection to bus bars shall have two bolt holes. 46

3. Compression type suitable for direct burial in earth or concrete: 47 a. Standards: UL 467, IEEE 837. 48 b. High copper alloy content. 49 c. Non-reversible. 50

Page 303: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GROUNDING 16060 - 3

F. Exothermic Weld Connections: 1 1. Copper oxide reduction by aluminum process. 2 2. Molds properly sized for each application. 3

PART 3 - EXECUTION 4

3.1 INSTALLATION 5

A. General: 6 1. Install products in accordance with manufacturer's instructions. 7 2. Size grounding conductors and bonding jumpers in accordance with NFPA 70, Article 250, 8

except where larger sizes are indicated on the Drawings. 9 3. Remove paint, rust, or other non-conducting material from contact surfaces before making 10

ground connections. 11 4. Where ground conductors pass through floor slabs or building walls provide nonmetallic 12

sleeves and install per Specification Section 01800. 13 5. Do not splice grounding conductors except at ground rods. 14 6. Install ground rods and grounding conductors in undisturbed, firm soil. 15

a. Provide excavation required for installation of ground rods and ground conductors. 16 b. Use driving studs or other suitable means to prevent damage to threaded ends of 17

sectional rods. 18 c. Unless otherwise specified, connect conductors to ground rods with compressor type 19

connectors or exothermic weld. 20 d. Provide sufficient slack in grounding conductor to prevent conductor breakage during 21

backfill or due to ground movement. 22 e. Backfill excavation completely, thoroughly tamping to provide good contact between 23

backfill materials and ground rods and conductors. 24 7. Do not use exothermic welding if it will damage the structure the grounding conductor is 25

being welded to. 26

B. Grounding Electrode System: 27 1. Provide a grounding electrode system in accordance with NFPA 70, Article 250 and as 28

indicated on the Drawings. 29 2. Grounding conductor terminations: 30

a. Ground bars mounted on wall, use compression type terminal and bolt it to the ground 31 bar with two bolts. 32

b. Ground bars in electrical equipment, use compression type terminal and bolt it to the 33 ground bar. 34

c. Piping systems use mechanical type connections. 35 d. Building steel, below grade and encased in concrete, use compression type connector or 36

exothermic weld. 37 e. At all above grade terminations, the conductors shall be labeled per Specification 38

Section 10400. 39 3. Triad grounding system: 40

a. Triad consists of three ground rods arranged in a triangle separated by 10 FT and a 41 grounding conductor interconnecting each ground rod. 42

b. Place first ground rod a minimum of 10 FT from the structure foundation and 2 FT-6 IN 43 below grade. 44

c. Grounding conductor: Bare conductor, size as indicated on the Drawings. 45

C. Supplemental Grounding Electrode: 46 1. Provide the following grounding in addition to the equipment ground conductor supplied 47

with the feeder conductors whether or not shown on the Drawings. 48 2. Equipment support rack and pedestals mounted outdoors: 49

a. Connect metallic structure to a ground rod. 50 b. Grounding conductor: #6 AWG minimum. 51

Page 304: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - GROUNDING 16060 - 4

3. Engine generator: 1 a. Connect generator frame to the ground ring at two locations (opposite corners of 2

frame). 3 b. Grounding conductor: Bare conductor, size as indicated on the Drawings. 4

D. Other Bonding Requirements: 5

E. Low Voltage Transformer Separately Derived Grounding System: 6 1. Ground separately mounted step-down transformers XO terminal to one of the following: 7

a. Closest building steel using mechanical type terminal bolted to the steel, compression 8 type connection or exothermic weld. 9

b. Ground bar. 10 2. Grounding bar: 1 FT in length and mounted in electrical room or adjacent to transformer. 11 3. Interconnect all ground bars in a daisy chain or radial fashion to the main ground bar. 12

a. Terminate the conductors on ground bars with a compression type terminal and bolt it 13 to the ground bar with two bolts. 14

b. Grounding conductor: Bare conductor, size as indicated on the Drawings. 15

F. Raceway Bonding/Grounding: 16 1. All metallic conduit shall be installed so that it is electrically continuous. 17 2. All conduits to contain a grounding conductor with insulation identical to the phase 18

conductors, unless otherwise indicated on the Drawings. 19 3. NFPA 70 required grounding bushings shall be of the insulating type. 20 4. Provide double locknuts at all panels. 21 5. Bond all conduit, at entrance and exit of equipment, to the equipment ground bus or lug. 22 6. Provide bonding jumpers if conduits are installed in concentric knockouts. 23 7. Make all metallic raceway fittings and grounding clamps tight to ensure equipment 24

grounding system will operate continuously at ground potential to provide low impedance 25 current path for proper operation of overcurrent devices during possible ground fault 26 conditions. 27

G. Equipment Grounding: 28 1. All utilization equipment shall be grounded with an equipment ground conductor. 29 2. Use generator manufacturer's provisions for grounding electric generators, or manufacturer's 30

written instructions, except as shown on the Contract Drawings. 31

H. Cable Tray Grounding: 32 1. Make metal cable tray electrically continuous by one of the following methods: 33

a. Tray sections and fittings suitable for grounding purposes. 34 b. Provide bonding jumpers at discontinuous joints. 35

I. Manhole and Handhole Grounding: 36 1. Provide a ground rod and ground bar, when indicated or as needed, in each manhole and 37

handhole with exposed metal parts. 38 a. Expose a minimum of 4 IN of the rod above the floor for field connections to the rod. 39

2. Connect all exposed metal parts (e.g., conduits and cable racks) to the ground rod. 40

J. Fence grounding: See Specification Section 02444. 41

3.2 FIELD QUALITY CONTROL 42

A. Leave grounding system uncovered until observed by Owner. 43

B. Acceptance Testing: See Specification Section 16080. 44

END OF SECTION 45

Page 305: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ACCEPTANCE TESTING 16080 - 1

2014/08/28 1

SECTION 16080 2

ACCEPTANCE TESTING 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Basic requirements for acceptance testing. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 11005 - Equipment: Basic Requirements. 10 4. Division 16 - Electrical. 11 5. Section 16230 - Engine Generator - Diesel. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 15

a. 400, Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable 16 Systems. 17

b. 400.3, Guide for Partial Discharge Testing of Power Cable Systems in a Field 18 Environment. 19

2. InterNational Electrical Testing Association (NETA): 20 a. ATS, Standard for Acceptance Testing Specifications for Electric Power Equipment 21

and Systems. 22 3. Nationally Recognized Testing Laboratory (NRTL). 23 4. Telecommunications Industry Association/Electronic Industries Alliance/American National 24

Standards Institute (TIA/EIA/ANSI): 25 a. 455-78-B, Optical Fibers - PART 1-40: Measurement Methods and Test Procedures - 26

Attenuation. 27

B. Qualifications: 28 1. Testing firm qualifications: See Specification Section 11005. 29 2. Field personnel: 30

a. See Specification Section 11005. 31 b. As an alternative, supervising technician may be certified by the equipment 32

manufacturer. 33 3. Analysis personnel: 34

a. See Specification Section 11005 35 b. As an alternative, supervising technician may be certified by the equipment 36

manufacturer. 37

C. Phasing Diagram: 38 1. Coordinate with Utility Company for phase rotations and Phase A, B and C markings. 39

a. Create a phasing diagram showing the coordinated phase rotations with generators and 40 motors through the transformers. 41

1.3 SUBMITTALS 42

A. Shop Drawings: 43 1. See Specification Section 01340 for requirements for the mechanics and administration of 44

the submittal process. 45

Page 306: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ACCEPTANCE TESTING 16080 - 2

2. See Specification Section 11005 for electrical equipment and connection testing plan 1 submittal requirements. 2

B. Informational Submittals: 3 1. See Specification Section 01340 for requirements for the mechanics and administration of 4

the submittal process. 5 2. Prior to energizing equipment: 6

a. Coordinated phasing diagram. 7 b. Photocopies of continuity tests. 8

3. Within two (2) weeks after successful completion of Demonstration Period (Commissioning 9 Period): 10 a. Single report containing information including: 11

1) Summary of Project. 12 2) Information from pre-energization testing. 13 3) See testing and monitoring reporting requirements in Specification Section 11005. 14

PART 2 - PRODUCTS 15

2.1 FACTORY QUALITY CONTROL 16

A. Provide Division 16 equipment with all routing factory tests required by the applicable industry 17 standards or NRTL. 18

B. Factory testing will not be accepted in lieu of field acceptance testing requirements specified in 19 this Specification Section and Specification Section 11005. 20

PART 3 - EXECUTION 21

3.1 FIELD QUALITY CONTROL 22

A. General: 23 1. See Specification Section 11005. 24 2. Complete electrical testing in three (3) phases: 25

a. Pre-energization testing phase. 26 b. Equipment energized with no load. 27 c. Equipment energized under load. 28

3. Perform testing in accordance with this Specification Section and NETA ATS. 29 4. Provide field setting and programming of all adjustable protective devices and meters to 30

settings provided by the Engineer. 31

B. Equipment Monitoring and Testing Plan: See Specification Section 11005. 32

C. Instruments Used in Equipment and Connections Quality Control Testing: See Specification 33 Section 11005. 34

D. Testing and Monitoring Program Documentation: See Specification Section 11005. 35

E. Electrical Equipment and Connections Testing Program: 36 1. See Specification Section 11005. 37 2. See individual Division 16 Specification Sections for equipment specific testing 38

requirements. 39 3. Test all electrical equipment. 40

a. Perform all required NETA testing plus the optional testing identified with each 41 specific type of equipment in Article 3.2 of this Specification Section. 42

4. See Schedule at the end of PART 3 for equipment to be tested and specific test 43 requirements. 44

Page 307: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ACCEPTANCE TESTING 16080 - 3

3.2 SPECIFIC EQUIPMENT TESTING REQUIREMENTS 1

A. Switchgear and Switchboards: 2 1. Perform inspections and tests per NETA ATS 7.1. 3 2. Components: Test all components per applicable paragraphs of this Specification Section 4

and NETA ATS. 5 3. Perform the following additional tests: 6

a. Weatherproof switchgear/switchboards: 7 1) Verify correct location, operation and current draw of heaters. 8 2) Verify correct operation of thermostat. 9

B. Transformers - Small Dry Type: 10 1. Perform inspections and tests per NETA ATS 7.2.1.1. 11 2. Perform the following additional tests: 12

a. Record phase-to-phase, phase-to-neutral, and neutral-to-ground voltages at no load after 13 energizing, and at operating load after startup. 14

3. Adjust tap connections as required to provide secondary voltage within 2-1/2 percent of 15 nominal under normal load after approval of Engineer. 16

4. Record as-left tap connections. 17

C. Cable - Low Voltage: 18 1. Perform inspections and tests per NETA ATS 7.3.2. 19

D. Cable - Optical Fiber: 20 1. Perform inspections on tests per TIA/EIA/ANSI 455-78-B, including: 21

a. Optional time domain reflectometer test. 22 b. Power attenuation test. 23 c. Gain margin test. 24

E. Low Voltage Molded Case Circuit Breakers: 25 1. Perform inspections and tests per NETA ATS 7.6.1.1. 26 2. Components: 27

a. Test all components per applicable paragraphs of this Specification Section and NETA 28 ATS. 29

b. Thermal magnetic breakers: Visual and mechanical inspection per NETA ATS only. 30 c. Solid state trip type: Visual and mechanical inspection and electrical tests per NETA 31

ATS. 32 3. Record as-left settings. 33

F. Grounding: 34 1. Perform inspections and tests per NETA ATS 7.13. 35 2. Components: Test all components per applicable paragraphs of this Specification Section 36

and NETA ATS. 37

G. Ground Fault Protection: 38 1. Perform inspections and tests per NETA ATS 7.14. 39 2. Components: Test all components per applicable paragraphs of this Specification Section 40

and NETA ATS. 41 3. Perform the following optional tests per NETA ATS: 42

a. Control wiring insulation resistance. 43 4. Perform the following additional tests for four-wire systems: 44

a. Primary current injection into switchgear bus with test set configured to simulate 45 transformer source and high current jumper used to simulate unbalanced load and 46 ground fault conditions. 47

b. Verify no tripping for unbalanced load on each feeder and each main breaker. 48 c. Verify no tripping for unbalanced load across tie breaker for dual-source schemes. 49 d. Verify tripping for ground fault on load side of feeder each feeder and on each main 50

bus. 51

Page 308: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ACCEPTANCE TESTING 16080 - 4

e. Verify tripping for ground fault on a single feeder and on each main bus through tie 1 breaker(s) for multiple-source schemes. 2

H. Motors: 3 1. Perform inspections and tests per NETA ATS 7.15. 4 2. See Specification Section 11005. 5

I. Motor Controllers: 6 1. Perform inspections and tests per NETA ATS 7.16. 7 2. Components: Test all components per applicable paragraphs of this Specification Section 8

and NETA ATS. 9

J. Generators: 10 1. Perform inspections and tests per NETA ATS 7.15.2. 11 2. Components: Test all components per applicable paragraphs of this Specification Section 12

and NETA ATS. 13 3. Perform the following additional tests: 14

a. Load and cycle crank test per Specification Section 16230. 15

K. Control System Functional Test: 16 1. Perform test upon completion of equipment acceptance tests. 17 2. The test is to prove the correct interaction of all sensing, processing and action devices. 18 3. Develop a test plan and parameters for the purpose of evaluating the performance of the 19

system. 20 4. Perform the following tests: 21

a. Verify the correct operation of all interlock safety devices for fail-safe functions in 22 addition to design function. 23

b. Verify the correct operation of all sensing devices, alarms and indicating devices. 24 c. Standby Generator Systems. 25 d. Automatic Transfer Switch Schemes. 26

END OF SECTION 27

Page 309: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 1

2014/08/28 1

SECTION 16120 2

WIRE AND CABLE: 600 VOLT AND BELOW 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Material and installation requirements for: 7

a. Building wire. 8 b. Power cable. 9 c. Control cable. 10 d. Shielded VFD cable. 11 e. Instrumentation cable. 12 f. Fiber optic cable. 13 g. Wire connectors. 14 h. Insulating tape. 15 i. Pulling lubricant. 16

B. Related Specification Sections include but are not necessarily limited to: 17 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 18 2. Division 01 - General Requirements. 19 3. Section 16010 - Electrical: Basic Requirements. 20 4. Section 16080 - Acceptance Testing. 21

1.2 QUALITY ASSURANCE 22

A. Referenced Standards: 23 1. Insulated Cable Engineers Association (ICEA): 24

a. S-58-679, Standard for Control Cable Conductor Identification. 25 2. National Electrical Manufacturers Association (NEMA): 26

a. ICS 4, Industrial Control and Systems: Terminal Blocks. 27 3. National Electrical Manufacturers Association/Insulated Cable Engineers Association 28

(NEMA/ICEA): 29 a. WC 57/S-73-532, Standard for Control Cables. 30 b. WC 70/S-95-658, Non-Shielded Power Cables Rated 2000 Volts or Less for the 31

Distribution of Electrical Energy. 32 4. National Fire Protection Association (NFPA): 33

a. 70, National Electrical Code (NEC). 34 5. Telecommunications Industry Association/Electronic Industries Alliance (TIA/EIA): 35

a. 598-C, Optical Fiber Cable Color Coding. 36 6. Underwriters Laboratories, Inc. (UL): 37

a. 44, Standard for Safety Thermoset-Insulated Wires and Cables. 38 b. 83, Standard for Safety Thermoplastic-Insulated Wires and Cables. 39 c. 467, Standard for Safety Grounding and Bonding Equipment. 40 d. 486A, Standard for Safety Wire Connectors and Soldering Lugs for use with Copper 41

Conductors. 42 e. 486C, Standard for Safety Splicing Wire Connections. 43 f. 510, Standard for Safety Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape. 44 g. 1581, Standard for Safety Reference Standard for Electrical Wires, Cables, and Flexible 45

Cords. 46

Page 310: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 2

1.3 DEFINITIONS 1

A. Cable: Multi-conductor, insulated, with outer sheath containing either building wire or 2 instrumentation wire. 3

B. Instrumentation Cable: 4 1. Multiple conductor, insulated, twisted or untwisted, with outer sheath. 5 2. The following are specific types of instrumentation cables: 6

a. Analog signal cable: 7 1) Used for the transmission of low current (e.g., 4-20mA DC) or low voltage (e.g., 0-8

10 Vdc) signals, using No. 16 AWG and smaller conductors. 9 2) Commonly used types are defined in the following: 10

a) TSP: Twisted shielded pair. 11 b) TST: Twisted shielded triad. 12

b. Digital signal cable: Used for the transmission of digital signals between computers, 13 PLC's, RTU's, etc. 14

C. Power Cable: Multi-conductor, insulated, with outer sheath containing building wire, No. 8 15 AWG and larger. 16

D. Shielded VFD Cable: Multi-conductor, insulated, with shield, drain wire and building wires, 17 No. 12 and larger. 18

E. Control Cable: Multi-conductor, insulated, with outer sheath containing building wires, No. 14, 19 No. 12 or No. 10 AWG. 20

F. Building Wire: Single conductor, insulated, with or without outer jacket depending upon type. 21

1.4 SUBMITTALS 22

A. Shop Drawings: 23 1. See Specification Section 01340 for requirements for the mechanics and administration of 24

the submittal process. 25 2. Product technical data: 26

a. Provide submittal data for all products specified in PART 2 of this Specification 27 Section except: 28 1) Wire connectors. 29 2) Insulating tape. 30 3) Cable lubricant. 31

b. See Specification Section 16010 for additional requirements. 32 3. Test reports: 33

a. Fiber optic cable test reports per Specification 16080. 34

1.5 DELIVERY, STORAGE, AND HANDLING 35

A. See Specification Section 16010. 36

PART 2 - PRODUCTS 37

2.1 ACCEPTABLE MANUFACTURERS 38

A. Subject to compliance with the Contract Documents, the following manufacturers are 39 acceptable: 40 1. Building wire, power and control cable: 41

a. Aetna Insulated Wire. 42 b. Alphawire. 43 c. Cerrowire. 44 d. Encore Wire Corporation. 45 e. General Cable. 46

Page 311: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 3

f. Okonite Company. 1 g. Southwire Company. 2

2. Shielded VFD cable: 3 a. Belden Inc. 4 b. General Cable. 5 c. Okonite Company. 6 d. Olfex Wire and Cable, Inc. 7 e. Priority Wire and Cable (Prysmian). 8 f. Rockbestos-Surprenant Cable Corp. 9 g. Southwire Company. 10

3. Instrumentation cable: 11 a. Analog cable: 12

1) Alphawire. 13 2) Belden Inc. 14 3) General Cable. 15

4. Wire connectors: 16 a. Burndy Corporation. 17 b. Buchanan. 18 c. Ideal. 19 d. Ilsco. 20 e. 3M Co. 21 f. Teledyne Penn Union. 22 g. Thomas and Betts. 23 h. Phoenix Contact. 24

5. Insulating and color coding tape: 25 a. 3M Co. 26 b. Plymouth Bishop Tapes. 27 c. Red Seal Electric Co. 28

B. Submit request for substitution in accordance with Specification Section 01640. 29

2.2 MANUFACTURED UNITS 30

A. Building Wire: 31 1. Conductor shall be copper with 600 V rated insulation. 32 2. Conductors shall be stranded, except for conductors used in lighting and receptacle circuits 33

which may be stranded or solid. 34 3. Surface mark with manufacturer's name or trademark, conductor size, insulation type and 35

UL label. 36 4. When direct buried, UL listed and marked as suitable for direct bury. 37 5. Conform to NEMA/ICEA WC 70/S-95-658 and UL 83 for type THHN/THWN and 38

THHN/THWN-2 insulation. 39 6. Conform to NEMA/ICEA WC 70/S-95-658 and UL 44 for type XHHW-2 insulation. 40 7. Conductors No. 1/0 and larger used in a cable tray shall have a UL CT rating and conform 41

to IEEE 1202 or CSA FT-4. 42

B. Power Cable: 43 1. Conductor shall be copper with 600 V rated insulation. 44 2. Surface mark with manufacturer's name or trademark, conductor size, insulation type and 45

UL label. 46 3. Conform to NEMA/ICEA WC 70/S-95-658 and UL 83 and UL 1277 for type 47

THHN/THWN insulation with an overall PVC jacket. 48 4. Conform to NEMA/ICEA WC 70/S-95-658 and UL 44 and UL 1277 for type XHHW-2 49

insulation with an overall PVC jacket. 50 5. Number of conductors as required, including a bare ground conductor. 51 6. Individual conductor color coding: 52

a. ICEA S-58-679, Method 4. 53

Page 312: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 4

b. See PART 3 of this Specification Section for additional requirements. 1 7. Conform to NFPA 70 Type TC. 2

C. Control Cable: 3 1. Conductor shall be copper with 600 V rated insulation. 4 2. Surface mark with manufacturer's name or trademark, conductor size, insulation type and 5

UL label. 6 3. Conform to NEMA/ICEA WC 57/S-73-532 and UL 83 and UL 1277 for type 7

THHN/THWN insulation with an overall PVC jacket. 8 4. Number of conductors as required, provided with or without bare ground conductor of the 9

same AWG size. 10 a. When a bare ground conductor is not provided, an additional insulated conductor shall 11

be provided and used as the ground conductor (e.g., 6/c No. 14 w/g and 7/c No. 14 are 12 equal). 13

5. Individual conductor color coding: 14 a. ICEA S-58-679, Method 1, Table E-2. 15 b. See PART 3 of this Specification Section for additional requirements. 16

6. Conform to NFPA 70 Type TC. 17

D. Electrical Equipment Control Wire: 18 1. Conductor shall be copper with 600 V rated insulation. 19 2. Conductors shall be stranded. 20 3. Surface mark with manufacturer's name or trademark, conductor size, insulation type and 21

UL label. 22 4. Conform to UL 44 for Type SIS insulation. 23 5. Conform to UL 83 for Type MTW insulation. 24

E. Shielded VFD Cable: 25 1. Conductor shall be copper, stranded with 600 V rated insulation. 26 2. Surface mark with manufacturer's name or trademark, conductor size, insulation type and 27

UL label. 28 3. Cables No. 00 through 750 kcmil: 29

a. Conform to NEMA/ICEA WC 70/S-95-658 and UL 44 type XHHW-2 insulation. 30 b. Shielding: 5 mil copper tape, longitudinally applied with a minimum overlap of 15 31

percent. 32 c. Number of conductors: 3 PH and 3 equally spaced ground conductors. 33

4. Individual conductor color coding: 34 a. ICEA S-58-679, Method 4. 35 b. See PART 3 of this Specification Section for additional requirements. 36

5. When installed exposed outdoors, UL listed and marked as sunlight resistant. 37 6. For continuously corrugated cable, use manufacturer approved fittings. 38 7. Conform to NFPA 70, Type TC. 39

F. Instrumentation Cable: 40 1. Surface mark with manufacturer's name or trademark, conductor size, insulation type and 41

UL label. 42 2. Analog cable: 43

a. Tinned copper conductors. 44 b. 300 V or 600 V PVC insulation with PVC jacket. 45 c. Twisted with 100 percent foil shield coverage with drain wire. 46 d. Four (4) twists per foot minimum. 47 e. Individual conductor color coding: ICEA S-58-679, Method 1, Table E-2. 48 f. Conform to UL 2250, UL 1581 and NFPA 70 Type ITC. 49

3. Digital cable: 50 a. As recommended by equipment (e.g., PLC, RTU) manufacturer. 51 b. Horizontal voice and data cable: 52

1) Category 6 per TIA/EIA/ANSI 568. 53

Page 313: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 5

2) Cable shall be label-verified. 1 3) Cable jacket shall be factory marked at regular intervals indicating verifying 2

organization and performance level. 3 4) Conductors: No. 24 AWG solid untinned copper. 4 5) Rated CMP per NFPA 70. 5

c. Conform to NFPA 262 and NFPA 70 Type ITC. 6

G. Fiber Optic Cable: 7 1. Design and fabrication - Multi-mode: 8

a. Type: 9 1) Outdoor: Loose tube with a wet or dry gel water blocking system. 10

b. Number of fibers: As indicated on the Drawings. 11 c. Fiber size: 62.5/125 micrometer (core diameter/cladding diameter). 12 d. Glass fiber core. 13 e. Step index. 14 f. Maximum attenuation: 15

1) At 850 nm: 3.75 dB/km. 16 2) At 1300 nm: 1.5dB/km. 17

g. Minimum bandwidth: 18 1) At 850 nm: 160 MHz/km. 19 2) At 1300 nm: 500 MHz/km. 20

h. Maximum tensile load: 21 1) Installation: 225 LBS. 22 2) Long term: 67 LBS. 23

i. Cable jacket material: 24 1) PVC, or polyethylene. 25

j. Cables shall be listed and marked in accordance with the requirements of NFPA 70. 26 k. Optical fiber cable type utilized shall be in accordance with NFPA 70. 27 l. Utilize LC type connectors: 28

1) Tip material: Ceramic or ceramic/glass composite. 29 2) Utilize connectors which do not require adhesive, epoxy, or polish. 30

H. Wire Connectors: 31 1. Twist/screw on type: 32

a. Insulated pressure or spring type solderless connector. 33 b. 600 V rated. 34 c. Ground conductors: Conform to UL 486C and/or UL 467 when required by local 35

codes. 36 d. Phase and neutral conductors: Conform to UL 486C. 37

2. Compression and mechanical screw type: 38 a. 600 V rated. 39 b. Ground conductors: Conform to UL 467. 40 c. Phase and neutral conductors: Conform to UL 486A. 41

3. Terminal block type: 42 a. High density, screw-post barrier-type with white center marker strip. 43 b. 600 V and ampere rating as required, for power circuits. 44 c. 600 V, 20 ampere rated for control circuits. 45 d. 300 V, 15 ampere rated for instrumentation circuits. 46 e. Conform to NEMA ICS 4 and UL 486A. 47

I. Insulating and Color Coding Tape: 48 1. Pressure sensitive vinyl. 49 2. Premium grade. 50 3. Heat, cold, moisture, and sunlight resistant. 51 4. Thickness, depending on use conditions: 7, 8.5, or 10 mil. 52 5. For cold weather or outdoor location, tape must also be all-weather. 53

Page 314: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 6

6. Color: 1 a. Insulating tape: Black. 2 b. Color coding tape: Fade-resistant color as specified herein. 3

7. Comply with UL 510. 4

J. Pulling Lubricant: Cable manufacturer's standard containing no petroleum or other products 5 which will deteriorate insulation. 6

PART 3 - EXECUTION 7

3.1 INSTALLATION 8

A. Permitted Usage of Insulation Types: 9 1. Type XHHW-2: 10

a. Building wire and power and control cable in architectural and non-architectural 11 finished areas. 12

b. Building wire and power and control cable in conduit below grade. 13 2. Type THHN/THWN and THHN/THWN-2: 14

a. Building wire and power and control cable No. 8 AWG and smaller in architectural and 15 non-architectural finished areas. 16

3. Type SIS and MTW: 17 a. For the wiring of control equipment within control panels and field wiring of control 18

equipment within switchgear, switchboards, motor control centers. 19

B. Shielded VFD Cable: 20 1. For wiring between a VFD and motor when routing in cable trays or conduit other than RGS 21

or RAC. 22

C. Conductor Size Limitations: 23 1. Feeder and branch power conductors shall not be smaller than No. 12 AWG unless 24

otherwise indicated on the Drawings. 25 2. Control conductors shall not be smaller than No. 14 AWG unless otherwise indicated on the 26

Drawings. 27 3. Instrumentation conductors shall not be smaller than No. 18 AWG unless otherwise 28

indicated on the Drawings. 29

D. Color Code All Wiring as Follows: 30 1. Building wire: 31

32

240 V, 208 V, 240/120 V,

208/120 V 480 V,

480/277 V Phase 1 Black Brown Phase 2 Red * Orange Phase 3 Blue Yellow Neutral White White or Gray Ground Green Green

* Orange when it is a high leg of a 120/240 V Delta system. 33 34

a. Conductors No. 6 AWG and smaller: Insulated phase, neutral and ground conductors 35 shall be identified by a continuous colored outer finish along its entire length. 36

b. Conductors larger than No. 6 AWG: 37 1) Insulated phase and neutral conductors shall be identified by one (1) of the 38

following methods: 39 a) Continuous colored outer finish along its entire length. 40 b) 3 IN of colored tape applied at the termination. 41

Page 315: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 7

2) Insulated grounding conductor shall be identified by one (1) of the following 1 methods: 2 a) Continuous green outer finish along its entire length. 3 b) Stripping the insulation from the entire exposed length. 4 c) Using green tape to cover the entire exposed length. 5

3) The color coding shall be applied at all accessible locations, including but not 6 limited to: Junction and pull boxes, wireways, manholes and handholes. 7

2. Power cables ICEA S-58-679, Method 4 with: 8 a. Phase and neutral conductors identified with 3 IN of colored tape, per the Table herein, 9

applied at the terminations. 10 b. Ground conductor: Bare. 11

3. Shielded VFD cable ICEA S-58-679, Method 4 with: 12 a. Phase conductors identified with 3 IN of colored tape, per the Table herein, applied at 13

the terminations. 14 b. Ground conductor: Green color insulation or bare. 15

4. Control cables ICEA S-58-679, Method 1, Table E-2: 16 a. When a bare ground is not provided, one (1) of the colored insulated conductors shall 17

be re-identified by stripping the insulation from the entire exposed length or using 18 green tape to cover the entire exposed length. 19

b. When used in power applications the colored insulated conductors used as phase and 20 neutral conductors may have to be re-identified with 3 IN of colored tape, per the Table 21 herein, applied at the terminations. 22

E. Install all wiring in raceway unless otherwise indicated on the Drawings. 23

F. Feeder, branch, control and instrumentation circuits shall not be combined in a raceway, cable 24 tray, junction or pull box, except as permitted in the following: 25 1. Where specifically indicated on the Drawings. 26 2. Where field conditions dictate and written permission is obtained from the Engineer. 27 3. Control circuits shall be isolated from feeder and branch power and instrumentation circuits 28

but combining of control circuits is permitted. 29 a. The combinations shall comply with the following: 30

1) 12 Vdc, 24 Vdc and 48 Vdc may be combined. 31 2) 125 Vdc shall be isolated from all other AC and DC circuits. 32 3) AC control circuits shall be isolated from all DC circuits. 33

4. Instrumentation circuits shall be isolated from feeder and branch power and control circuits 34 but combining of instrumentation circuits is permitted. 35 a. The combinations shall comply with the following: 36

1) Analog signal circuits may be combined. 37 2) Digital signal circuits may be combined but isolated from analog signal circuits. 38

5. Multiple branch circuits for lighting, receptacle and other 120 Vac circuits are allowed to be 39 combined into a common raceway. 40 a. Contractor is responsible for making the required adjustments in conductor and 41

raceway size, in accordance with all requirements of the NFPA 70, including but not 42 limited to: 43 1) Up sizing conductor size for required ampacity de-ratings for the number of current 44

carrying conductors in the raceway. 45 2) The neutral conductors may not be shared. 46 3) Up sizing raceway size for the size and quantity of conductors. 47

G. Ground the drain wire of shielded instrumentation cables at one (1) end only. 48 1. The preferred grounding location is at the load (e.g., control panel), not at the source (e.g., 49

field mounted instrument). 50

Page 316: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 8

H. Splices and terminations for the following circuit types shall be made in the indicated enclosure 1 type using the indicated method. 2 1. Feeder and branch power circuits: 3

a. Device outlet boxes: 4 1) Twist/screw on type connectors. 5

b. Junction and pull boxes and wireways: 6 1) Twist/screw on type connectors for use on No. 8 and smaller wire. 7 2) Compression, mechanical screw or terminal block or terminal strip type connectors 8

for use on No. 6 AWG and larger wire. 9 c. Motor terminal boxes: 10

1) Twist/screw on type connectors for use on No. 10 AWG and smaller wire. 11 2) Insulated mechanical screw type connectors for use on No. 8 AWG and larger 12

wire. 13 d. Manholes or handholes: 14

1) Twist/screw on type connectors pre-filled with epoxy for use on No. 8 AWG and 15 smaller wire. 16

2) Watertight compression or mechanical screw type connectors for use on No. 6 17 AWG and larger wire. 18

2. Control circuits: 19 a. Junction and pull boxes: Terminal block type connector. 20 b. Manholes or handholes: Twist/screw on type connectors pre-filled with epoxy. 21 c. Control panels and motor control centers: Terminal block or strips provided within the 22

equipment or field installed within the equipment by the Contractor. 23 3. Instrumentation circuits can be spliced where field conditions dictate and written permission 24

is obtained from the Engineer. 25 a. Maintain electrical continuity of the shield when splicing twisted shielded conductors. 26 b. Junction and pull boxes: Terminal block type connector. 27 c. Control panels and motor control centers: Terminal block or strip provided within the 28

equipment or field installed within the equipment by the Contractor. 29 4. Non-insulated compression and mechanical screw type connectors shall be insulated with 30

tape or hot or cold shrink type insulation to the insulation level of the conductors. 31

I. Provide electrical equipment enclosure and cable sealing bushing when exposed conductors or 32 cables enter the enclosure from cable trays. 33

J. Insulating Tape Usage: 34 1. For insulating connections of No. 8 AWG wire and smaller: 7 mil vinyl tape. 35 2. For insulating splices and taps of No. 6 AWG wire or larger: 10 mil vinyl tape. 36 3. For insulating connections made in cold weather or in outdoor locations: 8.5 mil, all 37

weather vinyl tape. 38

K. Color Coding Tape Usage: For color coding of conductors. 39

L. Fiber Optic Cable: 40 1. Unless indicated otherwise, install all fiber optic cable in conduit. 41

a. In cable trays, the cable(s) shall be installed in an interduct that is placed in the tray for 42 protection of the cable. 43

2. Splicing: 44 a. Optical fibers shall not be spliced. 45

3. Utilize dust tight wall-mounted interconnect center to provide the following: 46 a. Interconnect fiber optic cable to jumper cable assemblies for connection to the opto-47

electronic interface. 48 4. Where exposed to contact with electric light or power conductors, the noncurrent carrying 49

metallic members (if applicable) of optical fiber cables entering buildings shall be grounded 50 as close to the point of entrance as practicable in accordance with NFPA 70. 51

5. Install cables in accordance with the requirements of NFPA 70. 52

Page 317: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 9

3.2 FIELD QUALITY CONTROL 1

A. Acceptance Testing: See Specification Section 16080. 2

END OF SECTION 3

4

Page 318: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRE AND CABLE: 600 VOLT AND BELOW 16120 - 10

1

Page 319: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 1

2014/08/28 1

SECTION 16130 2

RACEWAYS AND BOXES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Material and installation requirements for: 7

a. Conduits. 8 b. Conduit fittings. 9 c. Conduit supports. 10 d. Wireways. 11 e. Outlet boxes. 12 f. Pull and junction boxes. 13

B. Related Specification Sections include but are not necessarily limited to: 14 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 15 2. Division 01 - General Requirements. 16 3. Section 16010 - Electrical: Basic Requirements. 17 4. Section 16120 - Wire and Cable - 600 Volt and Below. 18 5. Section 16135 - Electrical: Exterior Underground. 19 6. Section 16140 - Wiring Devices. 20

1.2 QUALITY ASSURANCE 21

A. Referenced Standards: 22 1. Aluminum Association (AA). 23 2. ASTM International (ASTM): 24

a. F512, Standard Specification for Smooth-Wall Poly(Vinyl Chloride) (PVC) Conduit 25 and Fittings for Underground Installation. 26

3. National Electrical Manufacturers Association (NEMA): 27 a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 28 b. TC 2, Electrical Polyvinyl Chloride (PVC) Tubing and Conduit. 29 c. TC 3, Polyvinyl Chloride (PVC) Fittings for Use with Rigid PVC Conduit and Tubing. 30 d. TC 6&8, Polyvinyl Chloride (PVC) Plastic Utilities Duct for Underground Installations. 31

4. National Electrical Manufacturers Association/American National Standards Institute 32 (NEMA/ANSI): 33 a. C80.5, Electrical Aluminum Rigid Conduit. 34

5. National Fire Protection Association (NFPA): 35 a. 70, National Electrical Code (NEC). 36

6. Underwriters Laboratories, Inc. (UL): 37 a. 1, Standard for Flexible Metal Conduit. 38 b. 50, Enclosures for Electrical Equipment, Non-Environmental Considerations. 39 c. 360, Standard for Liquid-Tight Flexible Steel Conduit. 40 d. 467, Grounding and Bonding Equipment. 41 e. 514B, Conduit, Tubing, and Cable Fittings. 42 f. 651, Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings. 43 g. 651A, Type EB and A Rigid PVC Conduit and HDPE Conduit. 44 h. 870, Standard for Wireways, Auxiliary Gutters, and Associated Fittings. 45

Page 320: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 2

1.3 SUBMITTALS 1

A. Shop Drawings: 2 1. See Specification Section 01340 for requirements for the mechanics and administration of 3

the submittal process. 4 2. Product technical data: 5

a. Provide submittal data for all products specified in PART 2 of this Specification 6 Section except: 7 1) Conduit fittings. 8 2) Support systems. 9

b. See Specification Section 16010 for additional requirements. 10 3. Fabrication and/or layout Drawings: 11

a. Identify dimensional size of pull and junction boxes to be used. 12

1.4 DELIVERY, STORAGE, AND HANDLING 13

A. See Specification Section 16010. 14

PART 2 - PRODUCTS 15

2.1 ACCEPTABLE MANUFACTURERS 16

A. Subject to compliance with the Contract Documents, the following manufacturers are 17 acceptable: 18 1. Rigid metallic conduits: 19

a. Allied Tube and Conduit Corporation. 20 b. Triangle PWC Inc. 21 c. Western Tube and Conduit Corporation. 22 d. Wheatland Tube Company. 23 e. LTV Steel Company. 24 f. EASCO Aluminum. 25 g. Indalex. 26 h. VAW of American, Inc. 27

2. Rigid nonmetallic conduit: 28 a. Carlon. 29 b. Cantex. 30 c. Osburn Associates. 31

3. Flexible conduit: 32 a. AFC Cable Systems. 33 b. Anamet, Inc. 34 c. Electri-Flex. 35 d. Flexible Metal Hose Company. 36 e. International Metal Hose Company. 37 f. Triangle PWC Inc. 38 g. LTV Steel Company. 39

4. Wireway: 40 a. Hoffman Engineering Company. 41 b. Wiegmann. 42 c. Square D. 43

5. Conduit fittings and accessories: 44 a. Appleton Electric Co. 45 b. Carlon. 46 c. Cantex. 47 d. Crouse-Hinds. 48 e. Killark. 49 f. Osburn Associates. 50

Page 321: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 3

g. OZ Gedney Company. 1 h. RACO. 2 i. Steel City. 3 j. Thomas & Betts. 4

6. Support systems: 5 a. Unistrut Building Systems. 6 b. Eaton B-Line. 7 c. Kindorf. 8 d. Minerallac Fastening Systems. 9 e. Caddy. 10 f. Thomas & Betts Superstrut. 11

7. Outlet, pull and junction boxes: 12 a. Appleton Electric Co. 13 b. Eaton Crouse-Hinds. 14 c. Killark. 15 d. O-Z/Gedney. 16 e. Thomas & Betts Steel City. 17 f. Raco. 18 g. Bell. 19 h. Hoffman Engineering Co. 20 i. Wiegmann. 21 j. Eaton B-Line. 22 k. Adalet. 23 l. Rittal. 24 m. Stahlin. 25

B. Submit request for substitution in accordance with Specification Section 01640. 26

2.2 RIGID METALLIC CONDUITS 27

A. Rigid Aluminum Conduit (RAC): 28 1. AA Type 6063 aluminum alloy, T-1 temper. 29 2. Maximum copper content of 0.10 percent. 30 3. Extruded, seamless. 31 4. Standards: NEMA/ANSI C80.5, UL 6. 32

2.3 RIGID NONMETALLIC CONDUIT 33

A. Schedules 40 (PVC-40) and 80 (PVC-80): 34 1. Polyvinyl-chloride (PVC) plastic compound which includes inert modifiers to improve 35

weatherability and heat distribution. 36 2. Rated for direct sunlight exposure. 37 3. Fire retardant and low smoke emission. 38 4. Shall be suitable for use with 90 DegC wire and shall be marked "maximum 90 DegC". 39 5. Standards: NEMA TC 2, UL 651. 40

B. Type EB (PVC-EB): 41 1. Polyvinyl-chloride (PVC) plastic compound. 42 2. Rated for concrete encasement. 43 3. Suitable for use with 90 DegC wire. 44 4. Standards: ASTM F512, NEMA TC 6&8, UL 651A. 45

2.4 FLEXIBLE CONDUIT 46

A. PVC-Coated Flexible Galvanized Steel (liquid-tight) Conduit (FLEX-LT): 47 1. Core formed of continuous, spiral wound, hot-dip galvanized steel strip with successive 48

convolutions securely interlocked. 49 2. Extruded PVC outer jacket positively locked to the steel core. 50 3. Liquid and vapor tight. 51

Page 322: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 4

4. Standard: UL 360. 1

2.5 WIREWAY 2

A. General: 3 1. Suitable for lay-in conductors. 4 2. Designed for continuous grounding. 5 3. Covers: 6

a. Hinged or removable in accessible areas. 7 b. Non-removable when passing through partitions. 8

4. Finish: Rust inhibiting primer and manufacturers standard paint inside and out except for 9 stainless steel type. 10

5. Standards: UL 870, NEMA 250. 11

B. General Purpose (NEMA 1 rated) Wireway: 12 1. 14 or 16 gage steel without knockouts. 13 2. Cover: Solid, non-gasketed and held in place by captive screws. 14

C. Raintight (NEMA 3R) Wiring Trough: 15 1. 14 or 16 GA galvanized steel without knockouts. 16 2. Cover: Non-gasketed and held in place by captive screws. 17

D. Watertight (NEMA 4X rated) Wireway: 18 1. 14 GA Type 304 or 316 stainless steel bodies and covers without knockouts and 10 GA 19

stainless steel flanges. 20 2. Cover: Fully gasketed and held in place with captive clamp type latches. 21 3. Flanges: Fully gasketed and bolted. 22

E. Dusttight (NEMA 12 rated) Wireway: 23 1. 14 GA steel bodies and covers without knockouts and 10 GA steel flanges. 24 2. Cover: Fully gasketed and held in place with captive clamp type latches. 25 3. Flanges: Fully gasketed and bolted. 26

2.6 CONDUIT FITTINGS AND ACCESSORIES 27

A. Fittings for Use with RAC: 28 1. Locknuts: 29

a. Threaded steel or malleable iron. 30 b. Gasketed or non-gasketed. 31 c. Grounding or non-grounding type. 32

2. Bushings: 33 a. Threaded, insulated metallic. 34 b. Grounding or non-grounding type. 35

3. Hubs: Threaded, insulated and gasketed metallic for rain tight connection. 36 4. Couplings: 37

a. Threaded straight type: Same material and finish as the conduit with which they are 38 used on. 39

b. Threadless type: Gland compression or self-threading type, concrete tight. 40 5. Conduit bodies (ells and tees): 41

a. Body: Zinc plated cast iron or cast copper free aluminum with threaded hubs. 42 b. Standard and mogul size. 43 c. Cover: 44

1) Clip-on type with stainless steel screws. 45 2) Gasketed or non-gasketed galvanized steel, zinc plated cast iron or cast copper free 46

aluminum. 47 6. Expansion/deflection couplings: 48

a. 3/4 IN nominal straight-line conduit movement in either direction. 49 b. 30-degree nominal deflection from the normal in all directions. 50 c. Metallic hubs, neoprene outer jacket and stainless steel jacket clamps. 51

Page 323: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 5

d. Internally or externally grounded. 1 e. Watertight, raintight and concrete tight. 2

7. Standards: UL 467, UL 514B, UL 886. 3

B. Fittings for Use with FLEX-LT: 4 1. Connector: 5

a. Straight or angle type. 6 b. Metal construction, insulated and gasketed. 7 c. Composed of locknut, grounding ferrule and gland compression nut. 8 d. Liquid tight. 9

2. Standards: UL 467, UL 514B. 10

C. Fittings for Use with Rigid Nonmetallic PVC Conduit: 11 1. Coupling, adapters and conduit bodies: 12

a. Same material, thickness, and construction as the conduits with which they are used. 13 b. Homogeneous plastic free from visible cracks, holes or foreign inclusions. 14 c. Bore smooth and free of blisters, nicks or other imperfections which could damage the 15

conductor. 16 2. Solvent cement for welding fittings shall be supplied by the same manufacturer as the 17

conduit and fittings. 18 3. Standards: ASTM D2564, NEMA TC 3, UL 651, UL 514B. 19

D. Weather and Corrosion Protection Tape: 20 1. PVC based tape, 10 mils thick. 21 2. Protection against moisture, acids, alkalis, salts and sewage and suitable for direct bury. 22 3. Used with appropriate pipe primer. 23

2.7 ALL RACEWAY AND FITTINGS 24

A. Mark Products: 25 1. Identify the nominal trade size on the product. 26 2. Stamp with the name or trademark of the manufacturer. 27

2.8 OUTLET BOXES 28

A. Cast Outlet Boxes: 29 1. Zinc plated cast iron or die-cast copper free aluminum with manufacturers standard finish. 30 2. Threaded hubs and grounding screw. 31 3. Styles: 32

a. "FS" or "FD". 33 b. "Bell". 34 c. Single or multiple gang and tandem. 35

4. Standards: UL 514A. 36

B. See Specification Section 16140 for wiring devices, wallplates and coverplates. 37

2.9 PULL AND JUNCTION BOXES 38

A. NEMA 1 Rated: 39 1. Body and cover: 14 GA minimum, galvanized steel or 14 GA minimum, steel finished with 40

rust inhibiting primer and manufacturers standard paint inside and out. 41 2. With or without concentric knockouts on four (4) sides. 42 3. Flat cover fastened with screws. 43

B. NEMA 4 Rated: 44 1. Body and cover: 14 GA steel finished with rust inhibiting primer and manufacturers 45

standard paint inside and out. 46 2. Seams continuously welded and ground smooth. 47 3. No knockouts. 48 4. External mounting flanges. 49

Page 324: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 6

5. Hinged or non-hinged cover held closed with stainless steel screws and clamps. 1 6. Cover with oil resistant gasket. 2

C. NEMA 4X Rated (metallic): 3 1. Body and cover: 14 GA Type 304 or 316 stainless steel. 4 2. Seams continuously welded and ground smooth. 5 3. No knockouts. 6 4. External mounting flanges. 7 5. Hinged door and stainless steel screws and clamps. 8 6. Door with oil-resistant gasket. 9

D. NEMA 12 Rated: 10 1. Body and cover: 11

a. 14 GA steel finished with rust inhibiting primer and manufacturers standard paint inside 12 and out. 13

b. Type 5052 H-32 aluminum, unpainted. 14 2. Seams continuously welded and ground smooth. 15 3. No knockouts. 16 4. External mounting flanges. 17 5. Non-hinged cover held closed with captivated cover screws threaded into sealed wells or 18

hinged cover held closed with stainless steel screws and clamps. 19 6. Flat door with oil resistant gasket. 20

E. Miscellaneous Accessories: 21 1. Rigid handles for covers larger than 9 SF or heavier than 25 LBS. 22 2. Split covers when heavier than 25 LBS. 23 3. Weldnuts for mounting optional panels and terminal kits. 24 4. Terminal blocks: Screw-post barrier-type, rated 600 volt and 20 ampere minimum. 25

F. Standards: NEMA 250, UL 50. 26

2.10 SUPPORT SYSTEMS 27

A. Multi-conduit Surface or Trapeze Type Support and Pull or Junction Box Supports: 28 1. Material requirements. 29

a. Stainless steel: AISI Type 316. 30 b. Aluminum: AA Type 6063-T6. 31

B. Single Conduit and Outlet Box Support Fasteners: 32 1. Material requirements: 33

a. Stainless steel. 34

2.11 OPENINGS AND PENETRATIONS IN WALLS AND FLOORS 35

A. Sleeves, smoke and fire stop fitting through walls and floors: 36 1. See Specification Section 01800. 37

PART 3 - EXECUTION 38

3.1 RACEWAY INSTALLATION - GENERAL 39

A. Shall be in accordance with the requirements of: 40 1. NFPA 70. 41 2. Manufacturer instructions. 42

B. Size of Raceways: 43 1. Raceway sizes are shown on the Drawings, if not shown on the Drawings, then size in 44

accordance with NFPA 70. 45

Page 325: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 7

2. Unless specifically indicated otherwise, the minimum raceway size shall be: 1 a. Conduit: 3/4 IN. 2 b. Wireway: 2-1/2 IN x 2-1/2 IN. 3

C. Field Bending and Cutting of Conduits: 4 1. Utilize tools and equipment recommended by the manufacturer of the conduit, designed for 5

the purpose and the conduit material to make all field bends and cuts. 6 2. Do not reduce the internal diameter of the conduit when making conduit bends. 7 3. Prepare tools and equipment to prevent damage to the PVC coating. 8 4. Degrease threads after threading and apply a zinc rich paint. 9 5. Debur interior and exterior after cutting. 10

D. Male threads of conduit systems shall be coated with an electrically conductive anti-seize 11 compound. 12

E. The protective coating integrity of conduits, fittings, outlet, pull and junction boxes and 13 accessories shall be maintained. 14 1. Repair galvanized components utilizing a zinc rich paint. 15 2. Repair painted components utilizing touch up paint provided by or approved by the 16

manufacturer. 17 3. Repair surfaces which will be inaccessible after installation prior to installation. 18

F. Remove moisture and debris from conduit before wire is pulled into place. 19 1. Pull mandrel with diameter nominally 1/4 IN smaller than the interior of the conduit, to 20

remove obstructions. 21 2. Swab conduit by pulling a clean, tight-fitting rag through the conduit. 22 3. Tightly plug ends of conduit with tapered wood plugs or plastic inserts until wire is pulled. 23

G. Only nylon or polyethylene rope shall be used to pull wire and cable in conduit systems. 24

H. Where portions of a raceway are subject to different temperatures and where condensation is 25 known to be a problem, as in cold storage areas of buildings or where passing from the interior 26 to the exterior of a building, the raceway shall be sealed to prevent circulation of warm air to 27 colder section of the raceway. 28

I. Fill openings in walls, floors, and ceilings and finish flush with surface. 29 1. See Specification Section 01800. 30

3.2 RACEWAY ROUTING 31

A. Raceways shall be routed in the field unless otherwise indicated. 32 1. Conduit and fittings shall be installed, as required, for a complete system that has a neat 33

appearance and is in compliance with all applicable codes. 34 2. Run in straight lines parallel to or at right angles to building lines. 35 3. Do not route conduits: 36

a. Through areas of high ambient temperature or radiant heat. 37 b. In suspended concrete slabs. 38

4. Conduit shall not interfere with, or prevent access to, piping, valves, ductwork, or other 39 equipment for operation, maintenance and repair. 40

5. Provide pull boxes or conduit bodies as needed so that there is a maximum of 360 degrees 41 of bends in the conduit run or in long straight runs to limit pulling tensions. 42

B. All rigid conduits within a structure shall be installed exposed except as follows: 43 1. As indicated on the Drawings. 44

C. Maintain minimum spacing between parallel conduit and piping runs in accordance with the 45 following when the runs are greater than 30 FT: 46 1. Between instrumentation and telecommunication: 1 IN. 47 2. Between instrumentation and 125 V, 48 V and 24 Vdc: 2 IN. 48 3. Between instrumentation and 600 V and less AC power or control: 6 IN. 49 4. Between telecommunication and 600 V and less AC power or control: 6 IN. 50

Page 326: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 8

5. Between process and water pipes: 6 IN. 1

D. Conduits shall be installed to eliminate moisture pockets. 2 1. Where water cannot drain to openings, provide drain fittings in the low spots of the conduit 3

run. 4

E. Conduit shall not be routed on the exterior of structures except as specifically indicated on the 5 Drawings. 6

F. Where sufficient room exists within the housing of roof-mounted equipment, the conduit shall 7 be stubbed up inside the housing. 8

G. Provide all required openings in walls, floors, and ceilings for conduit penetration. 9 1. See Specification Section 01800. 10 2. New construction: 11

a. Sleeves and blockouts: 12 1) Set in masonry walls during erection. 13 2) Set in concrete walls and floors during forming. 14

b. Sleeves not considered to structurally replace the displaced concrete. 15

3.3 RACEWAY APPLICATIONS 16

A. Permitted Raceway Types Per Wire or Cable Types: 17 1. Power wire or cables: All raceway types. 18 2. Control wire or cables: All raceway types. 19 3. Instrumentation cables: Metallic raceway except nonmetallic may be used underground. 20 4. Motor leads from a VFD: RGS, RAC or shielded VFD cables in all other raceways. 21 5. Telecommunication cables: All raceway types. 22

B. Permitted Raceway Types Per Area Designations: 23 1. Dry areas: 24

a. RAC. 25 2. Wet areas: 26

a. RAC. 27

C. Permitted Raceway Types Per Routing Locations: 28 a. NEMA 1 rated wireway. 29

2. Embedded in poured concrete walls and floors: 30 a. PVC-40. 31

3. Through floor penetrations, see Specification Section 01800: 32 a. RAC wrapped with field applied weather and corrosion protection tape when emerging 33

from concrete into areas designated as dry, wet, corrosive or highly corrosive. 34 4. Direct buried conduits and ductbanks: 35

a. PVC-80. 36 5. Concrete encased ductbanks: 37

a. PVC-EB. 38 b. 90 degree elbows for transitions to above grade: 39

1) PVC-RAC. 40

D. FLEX-LT conduits shall be install as the final conduit connection to light fixtures, dry type 41 transformers, motors, electrically operated valves, instrumentation primary elements, and other 42 electrical equipment that is liable to vibrate. 43 1. The maximum length shall not exceed: 44

a. 1 FT to light fixtures. 45 b. 3 FT to motors. 46 c. 2 FT to all other equipment. 47

E. NEMA 1 Rated Wireway: 48 1. Surface mounted in electrical rooms. 49

Page 327: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 9

F. NEMA 4X Rated Wireway: 1 1. Surface mounted in areas designated as wet and or corrosive. 2

G. NEMA 12 Rated Wireway: 3 1. Surface mounted in areas designated as dry in architecturally and non-architecturally 4

finished areas. 5

H. Underground Conduit: See Specification Section 16135. 6

3.4 CONDUIT FITTINGS AND ACCESSORIES 7

A. Rigid nonmetallic conduit and fittings shall be joined utilizing solvent cement. 8 1. Immediately after installation of conduit and fitting, the fitting or conduit shall be rotated 9

1/4 turn to provide uniform contact. 10

B. Install Expansion Fittings: 11 1. Where conduits are exposed to the sun and conduit run is greater than 200 FT. 12 2. Elsewhere as identified on the Drawings. 13

C. Install Expansion/Deflection Fittings: 14 1. Where conduits enter a structure. 15

a. Except electrical manholes and handholes. 16 b. Except where the ductbank is tied to the structure with rebar. 17

2. Where conduits span structural expansions joints. 18 3. Elsewhere as identified on the Drawings. 19

D. Threaded connections shall be made wrench-tight. 20

E. Conduit joints shall be watertight: 21 1. Where subjected to possible submersion. 22 2. In areas classified as wet. 23 3. Underground. 24

F. Terminate Conduits: 25 1. In metallic outlet boxes: 26

a. RAC}: 27 1) Conduit hub and locknut. 28 2) Insulated bushing and two (2) locknuts. 29 3) Use grounding type locknut or bushing when required by NFPA 70. 30

2. In NEMA 1 rated enclosures: 31 a. RAC: 32

1) Conduit hub and locknut. 33 2) Insulated bushing and two (2) locknuts. 34 3) Use grounding type locknut or bushing when required by NFPA 70. 35

3. In NEMA 12 rated enclosures: 36 a. Watertight, insulated and gasketed hub and locknut. 37 b. Use grounding type locknut or bushing when required by NFPA 70. 38

4. In NEMA 4 and NEMA 4X rated enclosures: 39 a. Watertight, insulated and gasketed hub and locknut. 40

5. When stubbed up through the floor into floor mount equipment: 41 a. With an insulated grounding bushing on metallic conduits. 42 b. With end bells on nonmetallic conduits. 43

G. Threadless couplings shall only be used to join new conduit to existing conduit when the 44 existing conduit end is not threaded and it is not practical or possible to cut threads on the 45 existing conduit with a pipe threader. 46

Page 328: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 10

3.5 CONDUIT SUPPORT 1

A. Permitted multi-conduit surface or trapeze type support system per area designations and conduit 2 types: 3 1. Dry or wet and/or hazardous areas: 4

a. Aluminum system consisting of: Aluminum channels, fittings and conduit clamps with 5 stainless steel nuts and hardware. 6

2. Conduit type shall be compatible with the support system material. 7 a. Stainless steel system may be used with RAC. 8 b. Aluminum system may be used with RAC. 9

B. Permitted single conduit support fasteners per area designations and conduit types: 10 1. Dry or wet areas: 11

a. Material: stainless steel.. 12 b. Types of fasteners: Straps, hangers with bolts, clamps with bolts and bolt on beam 13

clamps. 14 2. Conduit type shall be compatible with the support fastener material. 15

a. Stainless steel system may be used with RAC. 16

C. Conduit Support General Requirements: 17 1. Maximum spacing between conduit supports per NFPA 70. 18 2. Support conduit from the building structure. 19 3. Do not support conduit from process, gas, air or water piping; or from other conduits. 20 4. Provide hangers and brackets to limit the maximum uniform load on a single support to 21

25 LBS or to the maximum uniform load recommended by the manufacturer if the support 22 is rated less than 25 LBS. 23 a. Do not exceed maximum concentrated load recommended by the manufacturer on any 24

support. 25 b. Conduit hangers: 26

1) Continuous threaded rods combined with struts or conduit clamps: Do not use 27 perforated strap hangers and iron bailing wire. 28

c. Do not use suspended ceiling support systems to support raceways. 29 d. Hangers in metal roof decks: 30

1) Utilize fender washers. 31 2) Not extend above top of ribs. 32 3) Not interfere with vapor barrier, insulation, or roofing. 33

5. Conduit support system fasteners: 34 a. Use sleeve-type expansion anchors as fasteners in masonry wall construction. 35 b. Do not use concrete nails and powder-driven fasteners. 36 c. Comply with the requirements of Specification Section 05505 for fasteners in cast-in-37

place concrete construction. 38

3.6 OUTLET, PULL AND JUNCTION BOX INSTALLATION 39

A. General: 40 1. Install products in accordance with manufacturer's instructions. 41 2. See Specification Section 16010 and the Drawings for area classifications. 42 3. Fill unused punched-out, tapped, or threaded hub openings with insert plugs. 43 4. Size boxes to accommodate quantity of conductors enclosed and quantity of conduits 44

connected to the box. 45

B. Outlet Boxes: 46 1. Permitted uses of cast outlet boxes: 47

a. Housing of wiring devices surface mounted in non-architecturally finished dry, wet, 48 corrosive, highly corrosive and hazardous areas. 49

b. Pull and junction box surface mounted in non-architecturally finished dry, wet, 50 corrosive and highly corrosive areas. 51

Page 329: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 11

2. Mount device outlet boxes where indicated on the Drawings and at heights as scheduled in 1 Specification Section 16010. 2

3. Set device outlet boxes plumb and vertical to the floor. 3

C. Pull and Junction Boxes: 4 1. Install pull or junction boxes in conduit runs where indicated or required to facilitate pulling 5

of wires or making connections. 6 a. Make covers of boxes accessible. 7

2. Permitted uses of NEMA 4, painted steel enclosure: 8 a. Pull or junction box surface mounted in areas designated as wet. 9

3. Permitted uses of NEMA 4X, stainless steel metallic enclosure: 10 a. Pull or junction box surface mounted in areas designated as wet and/or corrosive. 11

4. Permitted uses of NEMA 12, Aluminum enclosure: 12 a. Pull or junction box surface mounted in areas designated as dry. 13

END OF SECTION 14

15

Page 330: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - RACEWAYS AND BOXES 16130 - 12

1

Page 331: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CABLE TRAY 16132 - 1

2014/08/28 1

SECTION 16132 2

CABLE TRAY 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Cable tray and associated fittings and supports. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 10400 - Identification Devices. 10 4. Section 16010 - Electrical: Basic Requirements. 11 5. Section 16060 - Grounding. 12 6. Section 16130 - Raceways and Boxes. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. ASTM International (ASTM): 16

a. A123/A123M, Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron 17 and Steel Products. 18

2. National Electrical Manufacturers Association (NEMA): 19 a. VE-1, Metal Cable Tray Systems. 20 b. VE-2, Metal Cable Tray Installation Guidelines. 21

3. Underwriters Laboratories, Inc. (UL). 22 4. National Fire Protection Association (NFPA): 23

a. 70, National Electrical Code (NEC). 24 5. Building Code: 25

a. International Code Council (ICC): 26 1) International Building Code and associated standards, 2012 Edition including all 27

amendments, referred to herein as Building Code. 28

1.3 DEFINITIONS 29

A. Types of Cable Tray: 30 1. Ladder: A prefabricated metal structure consisting of two (2) longitudinal side rails 31

connected by individual transverse members of rungs. 32 2. Ventilated trough: A prefabricated metal structure consisting of two (2) longitudinal side 33

rails and a ventilated bottom with clear openings no greater than 4 IN. 34 3. Solid-bottom: A prefabricated metal structure consisting of two (2) longitudinal side rails 35

and a bottom with no openings within the cable-bearing surface. 36 4. Channel: A prefabricated metal structure consisting of a one-piece ventilated or solid 37

bottom channel section not exceeding 6 IN in width. 38 5. Single-rail: A prefabricated metal structure consisting of one (1) longitudinal rail with 39

transversely connected rungs that project from one (1) or both sides, which may be single- 40 or multi-tier. 41

6. Wire-mesh: A rigid tray systems constructed from high strength wire spaced parallel with 42 2 IN longitudinal and 4 IN transverse wire, spot welded at all intersections. 43

1.4 SYSTEM DESCRIPTION 44

A. The following is a brief description of the types of the trays to be used. 45 1. Collector Building.: Aluminum, ladder type tray. 46

Page 332: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CABLE TRAY 16132 - 2

B. Miscellaneous: 1 1. Cable tray systems are sized on the Drawings. 2 2. When cable tray system size is not shown on the Drawings or scheduled, the cable tray shall 3

be sized in accordance with the NFPA 70 and the requirements of this Specification Section. 4 3. Cable tray runs, where shown, are diagrammatic and intended to be used as a guide, unless 5

otherwise indicated on the Drawings. 6 a. Site conditions may affect actual routing. 7 b. Contractor shall coordinate routing and measurement with other trades and with 8

equipment suppliers to avoid interference with equipment, piping, ductwork, etc. 9

1.5 SUBMITTALS 10

A. Shop Drawings: 11 1. See Specification Section 01340 for requirements for the mechanics and administration of 12

the submittal process. 13 2. Product technical data. 14

a. Provide submittal data for all products specified in PART 2 of this Specification 15 Section. 16

b. See Specification Section 16010 for additional requirements. 17

1.6 DELIVERY, STORAGE, AND HANDLING 18

A. See Specification Section 16010. 19

PART 2 - PRODUCTS 20

2.1 ACCEPTABLE MANUFACTURERS 21

A. Subject to compliance with the Contract Documents, the following manufacturers are 22 acceptable: 23 1. Metallic cable tray systems: 24

a. Eaton B-Line. 25 b. T.J. Cope. 26 c. Husky/Burndy. 27 d. Thomas & Betts. 28 e. P-W Ind. 29

2. Cable tray conduit and ground clamps and brackets: 30 a. Eaton B-Line. 31 b. P-W Ind. 32 c. O.Z. Gedney. 33 d. Thomas & Betts. 34

B. Submit request for substitution in accordance with Specification Section 01640. 35

2.2 COMPONENTS 36

A. Ladder Tray: 37 1. Materials: 38

a. Aluminum: 39 1) Side channels: Heat treatable alloy Type 6063-T6. 40 2) Transverse elements: Heat-treated alloy Type 6063-T6 (solid channel) or Type 41

6063-NHT (tubular). 42 3) Hardware: Stainless steel. 43

2. Fabrication: 44 a. Standard: 45

1) Metallic: NEMA VE-1. 46 b. The working (allowable) load capacity: NEMA VE-1 designation A. 47

Page 333: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CABLE TRAY 16132 - 3

c. Side rails: 1 1) I-beam or channel. 2 2) Flange in or out (full width top opening). 3 3) Useable clear nominal loading depth: 4 IN. 4

d. Transverse elements: Solid bar, tube, or channel with stiffened flanges. 5 e. Maximum centerline rung spacing on straight sections: 9 IN. 6 f. Metallic trays shall be UL classified per NFPA 70 as an equipment grounding 7

conductor. 8

B. Fittings: 9 1. Radius of bends: As required for cable layout in tray. 10 2. Degrees of arc for elbows: As required for cable tray layout. 11

2.3 ACCESSORIES 12

A. Accessories including but not limited to, splice plates, barrier strips, drop outs, box connector, 13 end plate and conduit clamps to be the same material as the tray or other compatible material. 14

B. Cable Tray Ground Clamps: 15 1. Malleable iron or tin-plated extruded aluminum with stainless steel screws. 16 2. Serrated edges to bite into and bond to the cable tray system. 17

C. Support system: 18 1. Material: See Specification Section 16010 for material specifications. 19 2. See PART 3 of this Specification Section for material type. 20

PART 3 - EXECUTION 21

3.1 INSTALLATION 22

A. Install products in accordance with NEMA VE-2 and as recommended by the manufacturer's 23 instructions unless otherwise indicated on the Drawings. 24

B. Install cable tray, fittings and accessories, as required, for a complete system that has a neat 25 appearance and is in compliance with all applicable codes. 26

C. Install cable tray systems as close as practical to the locations and elevations shown on the 27 Drawings. 28 1. Minor changes (12 IN or less) in location or elevation may be made to avoid interference 29

with piping, ductwork and equipment. 30 2. Obtain Engineer's approval prior to making major changes (greater than 12 IN) in location 31

or elevation. 32 3. When cable tray is located adjacent to, beneath or near large piping or major equipment, or 33

terminates at equipment; do not install cable tray until the installation of such piping and 34 equipment is complete. 35

4. Insure openings are provided in walls that cable tray will penetrate. 36

D. Cable Tray Supports: 37 1. Provide supports at required locations to provide the loading capacity per the Contractors 38

fill calculations. 39 2. Cantilever bracket type when cable tray is installed adjacent to a wall. 40 3. Trapeze type hangers for all other applications. 41 4. For vertical runs in excess of 20 FT support the tray by angles bolted through the side rails 42

and suspended from hanger rod, which is connected to a cantilevered support. 43 5. In seismic locations provide required supports and/or sway bracing per local Building 44

Codes. 45

Page 334: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CABLE TRAY 16132 - 4

E. Permitted prefabricated bracket or trapeze type support system per area designations and tray 1 material: 2 1. Dry or wet areas: 3

a. Aluminum system consisting of: Aluminum channels and fittings with stainless steel 4 nuts and hardware and conduit clamps. 5

2. Tray material shall be compatible with the support system material. 6 a. Stainless steel system may be used with zinc coated, stainless steel, aluminum and 7

nonmetallic trays. 8 b. Aluminum system may be used with aluminum trays. 9

F. Maintain electrical continuity of the cable tray system. 10 1. Bolt connectors to each section or fitting. 11 2. Span expansion connectors by a bonding jumper. 12 3. Use one (1) of the following to bond conduits to the tray: 13

a. Conduits connected to the cable tray system by a one-piece conduit clamp shall be 14 considered bonded to the cable tray system. 15

b. Terminate conduits connected to the cable tray system by a bracket and clamp assembly 16 in an insulated grounding bushing and bond to the cable tray system. 17

4. Tighten all bolted connections to manufacturer's recommendations to ensure electrical 18 continuity. 19

G. Cable Tray System Grounding: See Specification Section 16060. 20

H. Conduit terminating at a cable tray system: See Specification Section 16130. 21

I. Use flanged fittings to terminate cable tray systems at switchgear, motor control centers, and 22 other equipment, unless indicated otherwise on the Drawings. 23

J. Install barrier strips in cable tray systems containing both power and control wiring to physically 24 separate the control cables from the power cables. 25

K. Cable Installation: 26 1. Conductors #4/0 AWG and less, shall be in a multi-conductor cable. 27 2. Conductors 250 kcmil and larger, shall be single conductor cables bundled together, Phase 28

A, B, C and neutral and/or ground when required. 29

3.2 FIELD QUALITY CONTROL 30

A. Tray Fill Calculations: 31 1. Cable tray fill shall not exceed NFPA 70 requirements. 32 2. Additional cables will need to be installed in the cable trays by Division 13 (e.g., process 33

control digital communication, security, fire alarm, HVAC). 34

B. Remove trash and accumulated dirt from the entire cable tray system at the completion of the 35 project and install covers where applicable. 36

C. Tagging and Warning Signs: See Specification Section 10400. 37

END OF SECTION 38

Page 335: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: EXTERIOR UNDERGROUND 16135 - 1

2014/08/28 1

SECTION 16135 2

ELECTRICAL: EXTERIOR UNDERGROUND 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Material and installation requirements for: 7

a. Manholes. 8 b. Handhole. 9 c. Underground conduits and ductbanks. 10

B. Related Specification Sections include but are not necessarily limited to: 11 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 12 2. Division 01 - General Requirements. 13 3. Section 02221 - Trenching, Backfilling and Compacting for Utilities. 14 4. Division 03 - Concrete. 15 5. Section 10400 - Identification Devices. 16 6. Section 16060 - Grounding. 17 7. Section 16130 - Raceways and Boxes. 18

1.2 QUALITY ASSURANCE 19

A. Referenced Standards: 20 1. National Electrical Manufacturers Association (NEMA): 21 2. National Fire Protection Association (NFPA): 22

a. 70, National Electrical Code (NEC). 23

1.3 DEFINITIONS 24

A. Direct-buried conduit(s): 25 1. Individual (single) underground conduit. 26 2. Multiple underground conduits, arranged in one or more planes, in a common trench. 27

B. Concrete encased ductbank: An individual (single) or multiple conduit(s), arranged in one or 28 more planes, encased in a common concrete envelope. 29

1.4 SUBMITTALS 30

A. Shop Drawings: 31 1. See Specification Section 01340 for requirements for the mechanics and administration of 32

the submittal process. 33 2. Product technical data: 34

a. Provide submittal data for all products specified in PART 2 of this Specification 35 Section. 36

3. Fabrication and/or layout Drawings: 37 a. Provide dimensional Drawings of each manhole indicating all specified accessories and 38

conduit entry locations. 39

Page 336: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: EXTERIOR UNDERGROUND 16135 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Prefabricated composite handholes: 5

a. Quazite Composolite. 6 b. Armorcast Products Company. 7 c. Synertech. 8

2. Precast manholes.: 9 a. Utility Vault Co. 10 b. Oldcastle Precast, Inc. 11 c. Lister Industries. 12

3. Manhole and handhole and ductbank accessories: 13 a. Neenah. 14 b. Unistrut. 15 c. Condux International, Inc. 16 d. Underground Devices, Inc. 17

B. Submit request for substitution in accordance with Specification Section 01640. 18

2.2 MANHOLES AND HANDHOLES 19

A. Prefabricated Composite Material Handholes: 20 1. Handhole body and cover: Fiberglass reinforced polymer concrete conforming to all test 21

provisions of SCTE 77. 22 2. Minimum load ratings: SCTE 77 Tier 15. 23 3. Open bottom. 24 4. Stackable design as required for specified depth. 25 5. Cover: 26

a. Engraved legend of "FIBER OPTIC". 27 b. Non-gasketed bolt down with stainless steel penta head bolts. 28 c. Gasketed bolt down with stainless steel penta head bolts. 29 d. Lay-in non-bolt down, when cover is over 100 LBS. 30 e. One or multiple sections so the maximum weight of a section is 125 LBS. 31

6. Cover lifting hook: 24 IN minimum in length. 32

B. Precast Manholes: 33 1. Fiberglass reinforced polymer concrete or steel reinforced cement concrete structures: 34 2. AASHTO live load rating: H-20 for full deliberate vehicle traffic. 35 3. Mating edges: Tongue and groove type. 36 4. Solid bottom with a 12 IN x 12 IN or 12 IN DIA french drain in the bottom of each 37

manhole. 38 5. Gasketed removable top slab with lifting eyes and cast in frame for cover. 39 6. Cover extension rings as required. 40 7. Cable pulling eyes opposite all conduit entrances. 41

a. Coordinate exact location with installation contractor. 42

2.3 CONCRETE MANHOLE AND HANDHOLE ACCESSORIES 43

A. Cover and Frame: 44 1. Cast ductile iron: ASTM A536. 45 2. AASHTO live load rating: H-20. 46 3. Diameter: 30 IN. 47 4. Cast the legend "ELECTRICAL" or "FIBER OPTIC" into manholeand handhole covers. 48

a. Stainless steel penta-head bolts. 49

Page 337: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: EXTERIOR UNDERGROUND 16135 - 3

B. Cable Racks and Hooks: 1 1. Material: Heavy-duty nonmetallic (glass reinforced nylon). 2 2. Hook loading capacity: 400 LBS minimum. 3 3. Rack loading capacity: Four (4) hooks maximum. 4 4. Hook deflection: 0.25 IN maximum. 5 5. Hooks: Length, as required, with positive locking device to prevent upward movement. 6 6. Mounding hardware: Stainless steel. 7

C. Cable Pulling Irons: 8 1. 7/8 IN DIA hot-dipped galvanized steel. 9 2. 6000 LB minimum pulling load. 10

D. Ground Rods and Grounding Equipment: See Specification Section 16060. 11

2.4 UNDERGROUND CONDUIT AND ACCESSORIES 12

A. Concrete: Comply with Division 03. 13

B. Duct Terminators: 14 1. Designed for installation into manhole walls for a watertight seal. 15

C. Conduit: See Specification Section 16130. 16

D. Duct Spacers/Supports: 17 1. High density polyethylene or high impact polystyrene. 18 2. Interlocking. 19 3. Provide 2 IN minimum spacing between conduits. 20 4. Accessories, as required: 21

a. Hold down bars. 22 b. Ductbank strapping. 23

PART 3 - EXECUTION 24

3.1 GENERAL 25

A. Drawings indicate the intended location of manholes and handholes and routing of ductbanks. 26 1. Field conditions may affect actual routing. 27

B. Manhole and Handhole Locations: 28 1. Approximately where shown on the Drawings. 29 2. As required for pulling distances. 30 3. As required to keep pulling tensions under allowable cable tensions. 31 4. As required for number of bends in ductbank routing. 32 5. Shall not be installed in a swale or ditch. 33 6. Determine the exact locations after careful consideration has been given to the location of 34

other utilities, grading, and paving. 35 7. Locations are to be approved by the Engineer prior to excavation and placement or 36

construction of manholes and handholes. 37

C. Install products in accordance with manufacturer's instructions. 38

D. Install manholes and handholes in conduit runs where indicated or as required to facilitate 39 pulling of wires or making connections. 40

E. Comply with Specification Section 02221 for trenching, backfilling and compacting. 41

3.2 MANHOLES AND HANDHOLES 42

A. Prefabricated Composite Material Handholes: 43 1. For use in areas subjected to occasional non-deliberate vehicular traffic. 44

Page 338: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: EXTERIOR UNDERGROUND 16135 - 4

2. Place handhole on a foundation of compacted 1/4 to 1/2 IN crushed rock or gravel a 1 minimum of 8 IN thick and 6 IN larger than handholes footprint on all sides. 2

3. Provide concrete encasement ring around handhole per manufacturers installation 3 instructions (minimum of 10 IN wide x 12 IN deep). 4

4. Install so that the surrounding grade is 1 IN lower than the top of the handhole. 5 5. Size: As indicated on the Drawings or as required for the number and size of conduits. 6 6. Provide cable rails and pulling eyes as needed. 7

B. Precast Manholes: 8 1. For use in vehicular and non-vehicular traffic areas. 9 2. Construction: 10

a. Grout or seal all joints, per manufacturer's instructions. 11 b. Support cables on walls by cable racks: 12

1) Provide a minimum of two (2) racks, install symmetrically on each wall of 13 manholes. 14 a) Provide additional cable racks, as required, so that both ends of cable splices 15

will be supported horizontally. 16 2) Equip cable racks with adjustable hooks: Quantity of cable hooks as required by 17

the number of conductors to be supported. 18 c. In each manhole, drive 3/4 IN x 10 FT long copper clad ground rod into the earth with 19

approximately 6 IN exposed above finished floor. 20 1) Drill opening in floor for ground rod. 21 2) Connect all metallic components to ground rod by means of #8 AWG minimum 22

copper wire and approved grounding clamps. 23 3) Utilize a ground bar in the manhole if the quantity of ground wires exceeds three 24

(3). 25 a) Connect ground bar to ground rod with a #2/0 AWG minimum copper wire. 26

3. Place manhole on a foundation of compacted 1/4 to 1/2 IN crushed rock or gravel a 27 minimum of 8 IN thick and 6 IN larger than manholes footprint on all sides. 28

4. Install so that the top of cover is 1 IN above finished grade. 29 a. Where existing grades are higher than finished grades, install sufficient number of 30

courses of curved segmented concrete block between top of manhole frame to 31 temporarily elevate manhole cover to existing grade level. 32

5. After installation is complete, backfill and compact soil around manholes. 33 6. Handhole size: 34

a. Eighteen inches by thirty six inches or as required for the number and size of conduits 35 entering or as indicated on the Drawings. 36

b. Minimum floor dimension of 1.5 FT x 3 FT and minimum depth of 2 FT. 37 7. Manhole size: 38

a. As indicated on the Drawings or as required for the number and size of conduits 39 entering or as indicated on the Drawings. 40

b. Minimum floor dimension of 6 FT x 6 FT and a minimum depth of 6 FT. 41

3.3 UNDERGROUND CONDUITS 42

A. General Installation Requirements: 43 1. Ductbank types per location: 44

a. Concrete encased ductbank: 45 1) Power and data duct bank from multi-terminal cabinet to the collector well. 46 2) Power and data duct bank from the generator to the support wall of the electrical 47

distribution gear. 48 3) As indicated in the Drawings. 49

2. Do not place concrete or soil until conduits have been observed by the Engineer. 50 3. Ductbanks shall be sloped a minimum of 4 IN per 100 FT or as detailed on the Drawings. 51

a. Low points shall be at manholes. 52 4. During construction and after conduit installation is complete, plug the ends of all conduits. 53

Page 339: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: EXTERIOR UNDERGROUND 16135 - 5

5. Provide conduit supports and spacers. 1 a. Place supports and spacers for rigid nonmetallic conduit on maximum centers as 2

indicated for the following trade sizes: 3 1) 3-1/2 to 6 IN: 7 FT. 4

b. Securely anchor conduits to supports and spacers to prevent movement during 5 placement of concrete or soil. 6

6. Stagger conduit joints at intervals of 6 IN vertically. 7 7. Make conduit joints watertight and in accordance with manufacturer's recommendations. 8 8. Accomplish changes in direction of runs exceeding a total of 15 degrees by long sweep 9

bends having a minimum radius of 25 FT. 10 a. Sweep bends may be made up of one or more curved or straight sections or 11

combinations thereof. 12 9. Furnish manufactured bends at end of runs. 13

a. Minimum radius of 18 IN for conduits less than 3 IN trade size and 36 IN for conduits 14 3 IN trade size and larger. 15

10. Field cuts requiring tapers shall be made with the proper tools and shall match factory 16 tapers. 17

11. After the conduit run has been completed: 18 a. Prove joint integrity and test for out-of-round duct by pulling a test mandrel through 19

each conduit. 20 1) Test mandrel: 21

a) Length: Not less than 12 IN 22 b) Diameter: Approximately 1/4 IN less than the inside diameter of the conduit. 23

b. Clean the conduit by pulling a heavy duty wire brush mandrel followed by a rubber 24 duct swab through each conduit. 25

12. Pneumatic rodding may be used to draw in lead wire. 26 a. Install a heavy nylon cord free of kinks and splices in all unused new ducts. 27 b. Extend cord 3 FT beyond ends of conduit. 28

13. Transition from rigid nonmetallic conduit to rigid metallic conduit, per Specification 29 Section 16130, prior to entering a structure or going above ground. 30 a. Except rigid nonmetallic conduit may be extended directly to manholes, handholes, pad 31

mounted transformer boxes and other exterior pad mounted electrical equipment where 32 the conduit is concealed within the enclosure. 33

b. Terminate rigid PVC conduits with end bells. 34 c. Terminate steel conduits with insulated bushings. 35

14. Place warning tape in trench directly over ductbanks, direct-buried conduit, and direct-36 buried wire and cable in accordance with Specification Section 10400. 37

15. Placement of conduits stubbing into handholes and manholes shall be located to allow for 38 proper bending radiuses of the cables. 39

B. Concrete Encased Ductbank: 40 1. Ductbank system consists of conduits completely encased in minimum 2 IN of concrete and 41

with separations between different cabling types as required in Specification Section 16130 42 or as detailed on the Drawings. 43

2. Install so that top of concrete encased duct, at any point: 44 a. Is not less than 36 IN below grade. 45 b. Is below pavement sub-grading. 46

3. Conduit supports shall provide a uniform minimum clearance of 2 IN between the bottom of 47 the trench and the bottom row of conduit. 48

4. Conduit separators shall provide a uniform minimum clearance of 2 IN between conduits or 49 as required in Specification Section 16130 for different cabling types. 50

C. Direct-Buried Conduit(s): 51 1. Install so that the top of the uppermost conduit, at any point: 52

a. Is not less than 36 IN below grade. 53 b. Is below pavement sub-grading. 54

Page 340: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ELECTRICAL: EXTERIOR UNDERGROUND 16135 - 6

2. Provide a uniform minimum clearance of 2 IN between conduits or as required in 1 Specification Section 16130 for different cabling types. 2 a. Maintain the separation of multiple planes of conduits by one of the following methods: 3

1) Install multilevel conduits with the use of conduit supports and separators to 4 maintain the required separations, and backfill with flowable fill (100 psi) or 5 concrete per Specification Section 02221. 6

2) Install the multilevel conduits one level at a time. 7 a) Each level is backfilled with the appropriate amount of soil and compaction, 8

per Specification Section 02221, to maintain the required separations. 9

END OF SECTION 10

Page 341: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRING DEVICES 16140 - 1

2014/08/28 1

SECTION 16140 2

WIRING DEVICES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Material and installation requirements for: 7

a. Light switches. 8 b. Receptacles. 9 c. Device wallplates and coverplates. 10

B. Related Specification Sections include but are not necessarily limited to: 11 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 12 2. Division 01 - General Requirements. 13 3. Section 16010 - Electrical: Basic Requirements. 14 4. Section 16130 - Raceways and Boxes. 15 5. Section 16442 - Motor Control Equipment. 16

1.2 QUALITY ASSURANCE 17

A. Referenced Standards: 18 1. National Electrical Manufacturers Association (NEMA): 19

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 20 b. WD 1, General Color Requirements for Wiring Devices. 21 c. WD 6, Wiring Devices - Dimensional Requirements. 22

2. Underwriters Laboratories, Inc. (UL): 23 a. 20, General-Use Snap Switches. 24 b. 498, Standard for Attachment Plugs and Receptacles. 25 c. 943, Ground-Fault Circuit-Interrupters. 26 d. 1449, Standard for Surge Protective Devices. 27

1.3 SUBMITTALS 28

A. Shop Drawings: 29 1. See Specification Section 01340 for requirements for the mechanics and administration of 30

the submittal process. 31 2. Product technical data: 32

a. Provide submittal data for all products specified in PART 2 of this Specification 33 Section. 34

b. See Specification Section 16010 for additional requirements. 35

PART 2 - PRODUCTS 36

2.1 ACCEPTABLE MANUFACTURERS 37

A. Subject to compliance with the Contract Documents, the following manufacturers are 38 acceptable: 39 1. Light switches and receptacles: 40

a. Bryant. 41 b. Eaton Cooper Wiring Devices. 42 c. Hubbell. 43 d. Leviton. 44 e. Pass & Seymour. 45 f. Eaton Crouse-Hinds. 46

Page 342: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRING DEVICES 16140 - 2

g. Appleton Electric Co. 1 h. Killark. 2

B. Submit request for substitution in accordance with Specification Section 01640. 3

2.2 LIGHT SWITCHES 4

A. General requirements unless modified in specific requirements paragraph of switches per 5 designated areas or types: 6 1. Toggle type, quiet action, Industrial Specification Grade. 7 2. Self grounding with grounding terminal. 8 3. Back and side wired. 9 4. Solid silver cadmium oxide contacts. 10 5. Rugged urea housing and one-piece switch arm. 11 6. Rated 20 A, 120/277 Vac. 12 7. Switch handle color: Black. 13 8. Types as indicated on the Drawings: 14

a. Single-pole. 15 b. 3-way. 16 c. 4-way. 17

9. Standards: UL 20, UL 514A, NEMA WD 6. 18

B. Dry Non-architecturally Finished Areas: 19 1. Coverplate: 20

a. Zinc plated malleable iron or galvanized steel. 21 b. Single or multiple gang as required. 22

C. Wet Non-architecturally Finished Areas: 23 1. Coverplate: 24

a. Gasketed zinc plated malleable iron or aluminum with stainless steel screws utilizing 25 rocker, front mounted toggle or pull type switch. 26

b. Single or multiple gang as required. 27

D. Door Switches: 28 1. Pressure sensitive switch, complete with galvanized box and cover and wire leads. 29 2. Rated 5 A, 120 Vac. 30

2.3 RECEPTACLES 31

A. General requirements unless modified in specific requirements paragraph of receptacles per 32 designated areas: 33 1. Straight blade, Industrial Specification Grade. 34 2. Brass triple wipe line contacts. 35 3. One-piece grounding system with double wipe brass grounding contacts and self grounding 36

strap. 37 4. Back and side wired. 38 5. Rated 20 A, 125 Vac. 39 6. High impact nylon body. 40 7. Receptacle body color: 41

a. Normal power: Black. 42 8. Types as indicated on the Drawings: 43

a. Normal: Self grounding with grounding terminal. 44 b. Ground fault circuit interrupter: Feed-through type with test and reset buttons. 45

9. Duplex or simplex as indicated on the Drawings. 46 10. Configuration: NEMA 5-20R. 47 11. Standards: UL 498, UL 514A, UL 943, NEMA WD 1, NEMA WD 6. 48

B. Dry Non-Architecturally Finished Areas: 49 1. Coverplate: 50

a. Zinc plated malleable iron or galvanized steel. 51

Page 343: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRING DEVICES 16140 - 3

b. Single or multiple gang as required. 1

C. Exterior Locations: 2 1. Coverplate: Weatherproof (NEMA 3R) while in use, gasketed, flame retardant, UV 3

stabilized polycarbonate, 2.5 IN minimum cover depth. 4 2. Coverplate: Weatherproof (NEMA 3R) while in use, gasketed, copper-free aluminum, 2.5 5

IN minimum cover depth. 6 3. Coverplate: Weather resistant zinc plated or aluminum, gasketed, self-closing cover using 7

stainless steel spring. 8

2.4 MISCELLANEOUS WIRING DEVICES 9

A. Manual Motor Starters: Horsepower rated with or without thermal overloads, see Specification 10 Section 16442. 11

PART 3 - EXECUTION 12

3.1 INSTALLATION 13

A. Install products in accordance with manufacturer's instructions. 14

B. Mount devices where indicated on the Drawings and as scheduled in Specification Section 15 16010. 16

C. See Specification Section 16130 for device outlet box requirements. 17

D. Where more than one (1) receptacle is installed in a room, they shall be symmetrically arranged. 18

E. Provide blank plates for empty outlets. 19

END OF SECTION 20

21

Page 344: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - WIRING DEVICES 16140 - 4

1

Page 345: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 1

2014/10/07 1

SECTION 16230 2

ENGINE GENERATOR: DIESEL 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Engine generator set and accessories. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Division 15 - Mechanical. 10 4. Section 16010 - Electrical: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. Environmental Protection Agency (EPA): 14

a. 40 CFR Part 60, Subpart IIII, Protection of Environment, Standards of Performance for 15 New Stationary Sources, Standards for Performance for Stationary Compression 16 Ignition Internal Combustion Engines. 17

2. National Electrical Manufacturers Association (NEMA): 18 a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 19 b. MG 1, Motors and Generators. 20

3. National Fire Protection association (NFPA): 21 a. 70, National Electrical Code (NEC): 22

1) Article 700, Emergency Systems. 23 4. Underwriters Laboratories, Inc. (UL): 24

a. 2200, Standard for Stationary Engine Generator Assemblies. 25

B. The engine generator set manufacturer or authorized supplier is designated to have single source 26 responsibility for the supply of all components and installation of the unit. 27

1.3 SYSTEM DESCRIPTION 28

A. The engine generators will be used and rated for: 29 1. Legally required standby power during a utility power outage, NFPA 70, Article 701. 30 2. Generator shall be sized to start and power two (2) 200 HP, VFD driven water pumps and 31

associated electrical equipment as shown in the drawing set. Estimated size of 500 KW to 32 be confirmed by vendor. 33

1.4 SUBMITTALS 34

A. Shop Drawings: 35 1. See Specification Section 01340 for requirements for the mechanics and administration of 36

the submittal process. 37 2. Product technical data: 38

a. Provide submittal data for all products specified in PART 2 of this Specification 39 Section. 40

b. See Specification Section 16010 for additional requirements. 41 c. Engine/generator performance curves. 42

3. Fabrication and/or layout Drawings. 43 a. Dimensional plan and elevation Drawings. 44 b. Wire interconnection Drawings. 45

Page 346: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 2

4. Test reports: 1 a. Factory test reports. 2

B. Operation and Maintenance Manuals: 3 1. See Specification Section 01342 for requirements for: 4

a. The mechanics and administration of the submittal process. 5 b. The content of Operation and Maintenance Manuals. 6

C. Informational Submittals: 7 1. Unit installation, startup and operational statement. 8 2. Field Quality Control test reports. 9

1.5 SITE CONDITIONS 10

A. Ambient air temperature: 11 1. Minimum: -20 DegF. 12 2. Maximum: 105 DegF. 13

B. Altitude: 1150 FT above sea level. 14

PART 2 - PRODUCTS 15

2.1 ACCEPTABLE MANUFACTURERS 16

A. Subject to compliance with the Contract Documents, the following manufacturers are 17 acceptable: 18 1. Engine generator unit: 19

a. Caterpillar. 20 b. Cummins Onan. 21 c. Kohler. 22 d. Generac. 23 e. Waukesha. 24 f. Detroit Diesel. 25

2. Silencers: 26 a. Maxim. 27 b. GT Exhaust Systems. 28 c. Nelson. 29 d. Cowl. 30 e. Hapco. 31

3. Battery charger: 32 a. Manufacturer's standard. 33

4. Governor: 34 a. Manufacturer's standard. 35

5. Radiator: 36 a. Manufacturer's standard. 37

6. Vibration isolators: 38 a. Caldyne. 39 b. Mason Inds. 40 c. Ace. 41 d. Korfund Dynamics. 42

B. Submit request for substitution in accordance with Specification Section 01640. 43

Page 347: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 3

2.2 EQUIPMENT 1

A. Emissions Requirements: 2 1. A single units emissions shall meet all Federal, State and Local government requirements, 3

including but not limited too: 4 a. Environmental Protection Agencies (EPA) New Source Performance Standards 5

(NSPS), 40 CFR Part 60, Subpart IIII. 6

2.3 COMPONENTS 7

A. Engine Generator Unit General: 8 1. Diesel engine direct-connected to alternating current generator mounted on suitable rigid 9

steel skid supports. 10 2. Mount unit on skid suitable for installation on concrete foundation. 11 3. Base rating on operation at rated RPM when equipped with all operating accessories. 12 4. Standards: UL 2200. 13

B. Engine: 14 1. Four-cycle, full compression ignition, single acting, solid-injection unit, either vertical or V-15

type pistons turbo charged with after cooling. 16 2. Fuel supply: No. 2 Diesel. 17 3. Removable full wet-type cylinder liners of close grained alloy iron, heat treated for proper 18

hardness to obtain maximum life. 19 4. Capable of operating at idle or light loads for extended periods of time. 20

C. Injection Pumps and Valves: 21 1. Type not requiring adjustment in service, which may be individually removed and replaced. 22 2. Individual injection pump and valve for each cylinder. 23 3. Fuel injection pumps: Positive action, constant-stroke, actuated by cam driven by gears 24

from engine crankshaft. 25 4. Fuel lines between injection pumps and valves: Heavy seamless steel tubing. 26 5. Flexible fuel line connectors for supply and return connections at pump. 27

D. Oil Pump: 28 1. Gear-type lubricating oil pump to supply oil under pressure to main bearings, crank pin 29

bearings, pistons, timing gears, camshaft bearings and valve rocker mechanism. 30 2. Spray cool and lubricate pistons. 31 3. Oil filters so located that lubricating oil is continuously filtered, except during periods when 32

oil is automatically by-passed to protect vital parts when filters are clogged. 33 4. Filter elements accessible and easily removable. 34 5. Filter elements: Effective full flow, replaceable resin-impregnated cellulose type. 35 6. Equip filter system with spring-loaded by-pass valve. 36 7. Oil cooler: Water-cooled, engine-mounted. 37

E. Fuel System: 38 1. Fuel pump: Built-in gear-type, engine-driven fuel transfer pump. 39 2. Equip fuel system with replaceable fuel filter elements arranged for easy removal without 40

breaking any fuel line connections or disturbing fuel pumps or any other part of engine. 41 3. Locate all fuel filters in an accessible housing, ahead of injection pumps to thoroughly filter 42

fuel before it reaches the pump. 43 4. Use no screens or filters requiring cleaning or replacement of injection pumps or valve 44

assemblies. 45

F. Governor: Fully enclosed electronic type governor with actuator capable of providing accurate 46 speed control within 1 percent of rated speed, complete with panel-mounted electronic assembly 47 with ramp generator and speed-sensing modules. 48

G. Air Cleaners: Engine-mounted, dry type air cleaners of sufficient capacity. 49

Page 348: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 4

H. Electric Starting System: 1 1. Sufficient capacity to crank at speed which will start engine under normal operating 2

conditions. 3 2. Controls to provide automatic cranking of engine when generator is called to start. 4 3. Prevent excessive cranking which could damage cranking motor. 5 4. Automatic stop controls. 6 5. Starter motors with positive-engagement feature. 7

I. Cooling System: 8 1. Capacity for cooling engine at the specified operating conditions. 9 2. Engine driven, centrifugal type water circulating pump and thermostatic valve to maintain 10

the engine at recommended temperature level. 11 3. Unit mounted radiator. 12

a. Core guard flexible duct adapter. 13 b. Site glass at top of unit. 14 c. Engine driven blower fan. 15 d. Low water level cutoff switch. 16

4. Provide fan guards. 17

J. Heater: 18 1. Thermostatically controlled jacket water heater(s) to maintain cooling jacket at the 19

manufacturer's recommended temperature at the specified low ambient temperature. 20 a. 240V, single phase. 21

2. Lube oil heater, 120V, 300W. 22 3. Battery pad heaters, 120V. 23

K. Silencer: 24 1. Suitable type for industrial silencing. 25 2. Seamless, stainless steel, flexible, exhaust adapter for exhaust outlet to silencer. 26

L. Engine Instruments and Controls: 27 1. Engine-mounted instruments: 28

a. Oil pressure gage. 29 b. Water temperature gage. 30 c. Run time meter. 31 d. Battery voltage meter. 32

2. Automatic cycle cranking and over-crank protection. 33 3. Safety controls: Equip engine with automatic safety controls to shut down engine in event 34

of low lubricating oil pressure, high jacket water temperature, overspeed or overcrank. 35 4. Auxiliary control devices: Either integral with specified engine instruments, control, and 36

safety devices or as separate devices as required to operate various signal circuits specified 37 for remote annunciator panel. 38

5. Three (3) NO auxiliary contacts for interface with louvers, fans or other miscellaneous 39 equipment. 40 a. Contacts shall close when generator is started. 41

M. Fuel Day Tank: 42 1. Double wall sub-base day tank mounted underneath engine generator unit. 43 2. Steel construction, top and bottom baffles, steel channel side supports, weatherproof 44

secondary containment, rust preventive interior coating, rust proofed and finish painted 45 exterior. 46

3. Tank connections: Fuel level gauge, fuel lines to generator, fill, vent, drain and pressure 47 relief. 48

4. Manual overfill protection. 49 5. Low level warning with contacts for remote alarm. 50

a. Set to alarm at 50 percent of capacity. 51 6. Critical low level shutoff with contacts for remote alarm. 52 7. Leak detection alarm with contacts for remote alarm. 53

Page 349: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 5

8. Capacity: Fuel for approximately 16 HRS of run time at full load. 1

N. Batteries: 2 1. Lead acid type. 3 2. Furnish electrolyte separately for use when installation is complete and unit is ready for 4

testing. 5 3. Thermostatically controlled 120Vac battery pad heater. 6

O. Battery Charger: 7 1. Output current rating of at least 1/20th of ampere hour capacity of battery and capable of 8

automatically switching between low rate (float) mode and high rate (equalize) mode. 9 2. Solid state rectifiers, DC voltmeter and ammeter, fuse input and output, and 115 Vac input. 10 3. Malfunction alarm contacts (minimum): Low and high battery voltage, weak battery and 11

charger failure. 12

P. Generator: 13 1. Brushless, 6-pole drip-proof revolving field type with permanent magnet, 2/3 pitch stator, 14

direct-coupled rotor, Class H insulation. 15 2. Minimum continuous standby ratings: 16

a. As indicated on the Drawings, substantiated by manufacturer's standard published 17 curves and conform to NEMA MG 1 specification. 18

b. Special ratings or maximum ratings are not acceptable. 19 3. Rated to serve up to 50 percent non-linear load without exceeding rated temperature rise. 20 4. Minimum efficiency: 92 percent at 50 to 110 percent of nominal standby rating, less than 21

30 percent instantaneous voltage dip at full load and rated power factor and suitable for 22 simultaneous operation with other future units connected in parallel. 23

5. Stator and rotor: 125 DegC temperature rise with minimum Class F insulated with 100 24 percent epoxy impregnation and overcoat of resilient insulating material to reduce possible 25 fungus and/or abrasive deterioration. 26

6. Directly connect stator to engine flywheel housing. 27 7. Drive rotor through semi-flexible driving flange to ensure permanent alignment. 28 8. Self ventilating with suitable blower, air inlet and outlet openings. 29 9. Provide terminal box of adequate size for entrance of conduit and termination of conductors. 30 10. Generator drive free from critical torsional vibration within operating range. 31 11. Provide generator mounted main circuit breaker: 32

a. Solid state molded case type with LSI trip unit. 33 b. Ratings as supplied by the generator manufacturer. 34

Q. Voltage Regulator: 35 1. SCR type, to maintain 2 percent voltage regulation from 0 to full load with steady state 36

modulation not exceeding plus 1/2 percent including cross-current compensation to provide 37 maximum of 5 percent unbalance in kVA load sharing between this unit and possible future 38 generators. 39

2. Automatic protection against short circuits on system. 40 3. Permit unit to operate at no load below rated frequency for engine start up and shut down 41

procedures. 42 4. Provide voltage level and gain controls for normal operating adjustments. 43 5. Provide voltage level control with minimum range of plus or minus 5 percent from rated 44

voltage. 45 6. Mount regulator, volts per hertz type, in generator housing on suitable vibration isolators. 46

R. Generator Instruments and Controls: 47 1. Generator mounted NEMA 1 type, illuminated vibration isolated instrument and control 48

panel(s). 49 2. AC voltmeter and phase selector switch. 50 3. AC ammeter and phase selector switch. 51 4. Frequency meter. 52 5. Run-off-auto engine, start-stop control switch. 53

Page 350: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 6

6. Emergency stop. 1 7. Run time meter. 2 8. Governor control rheostat. 3 9. Voltage level adjustment rheostat. 4 10. Cool down time delay 0-15 minute adjustable. 5 11. Cycle cranking control. 6 12. Minimum red shut down indicating lights as follows: 7

a. Overcrank. 8 b. Overspeed. 9 c. Low lubricating oil pressure. 10 d. High engine water temperature. 11

13. Minimum amber alarm indicator lights as follows: 12 a. Control switch not in auto position. 13 b. Low engine water temperature (less than 70 DegF). 14 c. Low fuel in day tank. 15 d. Day tank leak. 16 e. Battery charger malfunctioning. 17 f. Low battery voltage. 18

14. Minimum amber pre-alarm indicator lights as follows: 19 a. High engine water temperature. 20 b. Low lubricating oil pressure. 21

15. Common dry contact and audible alarm to indicate when one (1) or more alarm or pre-alarm 22 conditions exist. 23

S. Vibration Isolators: Vibration system shall consist of engine and generator mount isolators with 24 or without additional mechanical spring isolators rubber pads to control both high and low 25 frequency vibrations between major components, sub-base and structural foundation and to 26 provide required vibration isolation for the seismic zone of the Project. 27

2.4 ACCESSORIES 28

A. Provide interposing relays (24 Vdc to 120 Vac) as required for interfacing with customer's 120 29 Vac monitoring system. 30

B. Generator remote annunciator panel: 31 1. Surface mounted NEMA 1 enclosure capable of dedicated network communication with 32

generator control system at a distance of 2,000 FT minimum. 33 2. Circuits: 34

a. 24 Vdc. 35 3. Provide red and green signal lamps, buzzer, silencing switch, lamp test switch, relays, solid-36

state components, and engraved function identifications. 37 4. Annunciator functions: 38

a. Green light "ON" to indicate generator is operating to supply power to load. 39 b. Separate red light for each shutdown or alarm condition and amber light for each 40

prealarm condition and common buzzer with silence/ acknowledge switch. 41 c. Shut down indicating lights as follows: 42

1) Overcrank. 43 2) Overspeed. 44 3) Low lubricating oil pressure. 45 4) High engine water temperature. 46

d. Alarm indicator lights as follows: 47 1) Control switch not in auto position. 48 2) Low engine water temperature (less than 70 DegF). 49 3) Low fuel in day tank. 50 4) Fuel in day tank rupture basin. 51 5) Battery charger malfunctioning. 52 6) Low battery voltage. 53

Page 351: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 7

e. Pre-alarm indicator lights as follows: 1 1) High engine water temperature. 2 2) Low lubricating oil pressure. 3

C. Manual stop break glass station: Shuts down generator from remote rack next to remote IO 4 panel at utility power incoming location. 5

D. Generator set non-walk-in weather protective enclosure: 6 1. Sheet steel with side servicing panels, air intake louvers and rear control panel access door. 7 2. Side servicing panels shall have two (2) locking points; all panels and doors are key 8

lockable. 9 3. Pitched roof with silencing exhaust muffler mounted inside the enclosure. 10 4. Completely install enclosure on generator set mounting base. 11

2.5 SOURCE QUALITY CONTROL 12

A. Individually test each prime mover. 13 1. Apply derating factors for the proposed site to test data. 14 2. Continuously test for a period no less than 2 HRS. 15 3. Test procedure shall be as follows: 16

a. Start prime mover and upon reaching rated RPM, pick up 100 percent of nameplate 17 KW rating at rated power factor in one (1) step. 18

b. Observe and record the cranking time(s) required to start and run for each prime mover. 19 c. Observe and record the time required to come up to operating speed for each prime 20

mover. 21 d. Record voltage and frequency overshoot for each prime mover. 22 e. Record voltage, frequency and amperes. 23 f. Record oil pressure, water temperature where applicable and battery charge rate at first 24

load acceptance and at 15 minute intervals thereafter for each prime mover. 25

2.6 MAINTENANCE MATERIALS 26

A. Spare Parts: Provide manufacturer's recommended spare parts. 27

PART 3 - EXECUTION 28

3.1 INSTALLATION 29

A. Install all components as indicated and in accordance with manufacturer's recommendations and 30 instructions. 31

B. Fill cooling system with solution of 50-50 water and ethylene glycol anti-freeze to prevent 32 freezing at temperatures as low as minus 30 DegF. 33

C. Provide fuel for a full day tank. 34

D. Install all wiring to engine in conduit. 35 1. Control wiring on engine may be factory installed in high temperature loom. 36

E. Provide control wiring in conduit between generator control panel, remote annunciator panel and 37 remote devices as described under generator instrument and controls paragraph and remote 38 annunciator paragraph of this Specification. 39

F. Mount on concrete pad utilizing vibration/seismic isolators, see structural drawings for pad 40 detail. 41

3.2 FIELD QUALITY CONTROL 42

A. Employ and pay for services of equipment manufacturer's field service representative(s) to: 43 1. Inspect equipment covered by this Specification Section. 44

Page 352: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 8

2. Supervise pre-startup adjustments and installation checks. 1 3. Conduct initial startup of equipment and perform operational checks. 2 4. Provide Owner written statement that manufacturer's equipment has been installed properly, 3

started up, tested, and is ready for operation by Owner's personnel. 4 5. Provide 4 HRS of the manufacturer's technical representative's time for on-site training of 5

Owner's personnel. 6

B. Provide two (2) load tests and one (1) cycle crank test. 7 1. Tests one (1) and two (2) shall be for continuous period of no less than 2 HRS each. 8 2. Engineer and Owner shall be notified seven (7) days prior to testing. 9 3. Test number one: 10

a. With prime mover(s) in a "cold start" condition and emergency load at normal 11 operating level, initiate a normal power failure by opening all switches or breakers 12 supplying normal power to facility. 13

b. Observe and record the time delay on engine start. 14 c. Observe and record the cranking time(s) required to start and run for each prime mover. 15 d. Observe and record the time required to come up to operating speed for each prime 16

mover. 17 e. Record voltage and frequency overshoot for each prime mover. 18 f. Observe and record time required to achieve steady-state condition with all switches 19

transferred to emergency position. 20 g. Record voltage, frequency and amperes. 21 h. Record oil pressure, water temperature where applicable and battery charge rate at 5-22

minute intervals for the first 15 minutes and at 15 minute intervals thereafter for each 23 prime mover. 24

i. Return normal power to facility, record time delay on retransfer to normal for each 25 switch and cool down time delay for each prime mover. 26

4. Test number two: 27 a. Immediately after completion of test number one, start prime mover and upon reaching 28

rated RPM, pick up 100 percent of nameplate KW rating in one (1) step. 29 1) Unity power factor is acceptable for on-site testing. 30

b. Observe and record the cranking time(s) required to start and run for each prime mover. 31 c. Observe and record the time required to come up to operating speed for each prime 32

mover. 33 d. Record voltage and frequency overshoot for each prime mover. 34 e. Observe and record time required to achieve steady-state condition. 35 f. Record voltage, frequency and amperes. 36 g. Record oil pressure, water temperature where applicable and battery charge rate at first 37

load acceptance and at 15 minute intervals thereafter for each prime mover. 38 5. Cycle crank test: 39

a. Perform test for each prime mover. 40 1) Utilize any method recommended by manufacturer to prevent prime mover(s) from 41

running. 42 2) Put control switch into "run" position to cause prime mover to crank. 43

b. A complete cranking cycle shall consist of an automatic crank period of approximately 44 15 seconds duration followed by a rest period of approximately 15 seconds duration. 45 1) Upon starting and running of the prime mover, further cranking shall cease. 46 2) Two (2) means of cranking termination shall be utilized so that one (1) will act as a 47

backup to the other to prevent inadvertent starter engagement. 48 3) Cranking limiter time shall be 75 seconds for cycle crank. 49

6. Furnish load banks of required ratings necessary for tests. 50 7. Record engine fuel consumption by means of test equipment. 51

Page 353: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 9

8. Test all safeties specified for generator instruments and controls and generator remote 1 annunciator panel as recommended by manufacturer and as required to verify proper 2 operation. 3

9. Contractor shall be responsible for fuel and all consumables use during the test. 4

END OF SECTION 5

6

Page 354: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - ENGINE GENERATOR: DIESEL 16230 - 10

1

Page 355: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 1

2014/10/07 1

SECTION 16265 2

VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Variable frequency drives (VFDs) for operation of inverter duty motors. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 10400 - Identification Devices. 10 4. Section 11005 - Equipment: Basic Requirements. 11 5. Section 13441 - Control Loop Descriptions. 12 6. Division 15 - Mechanical. 13 7. Section 16010 - Electrical: Basic Requirements. 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. American National Standards Institute (ANSI). 17 2. ETL Testing Laboratories (ETL). 18 3. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 19

a. 399, Recommended Practice for Industrial and Commercial Power Systems Analysis. 20 b. 519, Recommended Practices and Requirements for Harmonic Control in Electrical 21

Power Systems. 22 c. C62.41, Recommended Practice for Surge Voltages in Low-Voltage AC Power 23

Circuits. 24 4. National Electrical Manufacturer's Association (NEMA): 25

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 26 b. MG 1, Motors and Generators. 27

5. National Fire Protection Association (NFPA): 28 a. 70, National Electrical Code (NEC): 29

1) Article 430, Motors Motor Circuits, and Controllers.. 30 6. Occupational Safety and Health Administration (OSHA). 31 7. Underwriters Laboratory, Inc. (UL): 32

a. 508, Standard for Industrial Control Equipment. 33 b. 508A, Standard for Industrial Control Panels. 34

B. Qualifications: 35 1. Provide drives that are listed and labeled by UL, ETL, or other Nationally Recognized 36

Testing Laboratory (NRTL) as defined by OSHA regulations, or that have been inspected 37 and subsequent field-labeled by such NRTL. 38

2. Where listed drives and other components are installed in a common enclosure, the 39 assembly shall be listed and labeled per UL 508 and UL 508A or equivalent NRTL 40 standard. 41 a. Entire assembly shall be affixed with a UL 508A label "Listed Enclosed Industrial 42

Control Panel" or equivalent NRTL label prior to shipment to the jobsite. 43 3. VFD Supplier shall maintain an authorized service organization within 300 miles of the 44

Project Site. 45

Page 356: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 2

C. Coordination: 1 1. The intent of this Specification Section is to allow the VFD manufacturer to provide the best 2

solution for the harmonic and motor protection outlined herein. 3 a. This solution shall include, but not be limited to, all aspects of the distribution system 4

including standby generation, motor feeder cable type and available floor space. 5 2. Motor and VFD coordination: See Specification Section 11005. 6 3. VFD shall be supplied complete with all required control components. 7

a. Provide control as indicated: 8 1) On the Electrical Drawings. 9 2) As specified in this Specification Section. 10 3) As specified in the process control system loop descriptions. 11

a) See Specification Section 13441. 12 b. VFD manufacturer shall review the application and provide, at no additional cost to the 13

Owner, the hardware and software necessary to allow the VFD to control the driven 14 equipment motor over its required operating range. 15 1) These may include, but are not limited to, analog and digital interface modules, 16

communication interface modules, switches, lights and other devices. 17 c. Coordinate control devices with devices furnished with driven equipment such as 18

vibration switches, thermal sensors, leak detectors, etc. 19 4. Verify plan dimensions with equipment space requirements as indicated on the Drawings. 20

a. Equipment which exceeds the allotted maximum dimensions may not be acceptable. 21 b. Equipment which reduces clear work space below the minimums established by the 22

NFPA 70 will not be acceptable. 23

1.3 DEFINITIONS 24

A. Variable Torque (VT): 25 1. Defines a load characteristic in which the torque delivered from the motor to the load is 26

reduced as speed is reduced below full rated. 27 2. This type of load permits the VFD and the motor to operate at reduced output current at 28

reduced speed. 29

B. Inverter Duty Motor: An AC induction motor complying with all requirements of NEMA MG 1 30 Part 31 for definite-purpose inverter-fed motors. 31

C. Low Voltage: 600 Vac or less. 32

1.4 SUBMITTALS 33

A. Shop Drawings: 34 1. See Specification Section 01340 for requirements for the mechanics and administration of 35

the submittal process. 36 2. Provide a schedule for each VFD including the following information: 37

a. Equipment Tag Number. 38 b. VFD Complete Catalog Number. 39 c. VFD Amp Frame Size. 40 d. Variable or Constant Torque Rating Basis. 41 e. Rated Input Current. 42 f. Rated Continuous Output Current. 43 g. Rated Short Circuit Current. 44 h. VFD cable type specified (shielded or non-shielded). 45 i. VFD Maximum Motor Lead Length for the type of cable used. 46 j. Motor Manufacturer. 47 k. Motor Frame Size. 48 l. Motor Full Load Amps. 49 m. Motor Service Factor. 50 n. As installed motor Lead Length. 51 o. VFD options provided to meet harmonic or motor protection specifications. 52

Page 357: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 3

3. Submit VFD Shop Drawings concurrently with driven equipment and motor Shop 1 Drawings. 2

4. Product technical data: 3 a. Complete electrical ratings and performance specifications confirming compliance with 4

specified ratings and performance. 5 b. Maximum rate of heat rejection from VFD and all related components and associated 6

cooling requirements. 7 c. Manufacturer’s installation instructions. 8 d. Manufacturer’s programming and operating instructions. 9 e. See Specification Section 16010 for additional requirements. 10

5. Fabrication and/or layout Drawings: 11 a. Top, front and side exterior views, with details showing maximum overall dimensions 12

of enclosure, mounting provisions and conduit/cable entry provisions. 13 b. Identify minimum clearances from other VFDs or electrical equipment required for 14

proper cooling at top, bottom, side and back of enclosure. 15 c. Three-line diagrams showing AC schematic of VFD, input, output and bypass devices 16

including device ratings. 17 d. Interior layout Drawings showing location of all components within enclosure, field 18

wiring terminal boards, and power and grounding connections. 19 e. Field wiring diagrams showing locations and sizes of all electrical connections, ground 20

terminations, and requirements for shielded wire usage or any other special installation 21 considerations. 22

6. Certifications: 23 a. Submit with Shop Drawings: 24

1) Identification and location of closest authorized service organization. 25 2) Harmonic analysis at each PCC per Harmonic Protection Requirements Article. 26

b. Submit prior to shipment: 27 1) Certified factory test reports confirming compliance with specified requirements. 28

c. Submit after installation: 29 1) Certified field service reports showing: 30

a) Each VFD is operational. 31 b) Each VFD and its driven equipment motor are compatible. 32 c) Each VFD responds correctly to the input control signals. 33 d) Critical frequencies of the drive system and that the VFD has been set to 34

lockout these frequencies. 35 e) Measured harmonic levels per Harmonic Protection Requirements Article. 36 f) Measured motor terminal peak voltages per Motor Protection Requirements 37

Article. 38

B. Operation and Maintenance Manuals: 39 1. See Specification Section 01342 for requirements for: 40

a. The mechanics and administration of the submittal process. 41 b. The content of Operation and Maintenance Manuals. 42

2. Approved copy of VFD schedule per Submittals Article. 43 3. Manufacturer’s instruction manuals. 44 4. Troubleshooting procedures with a cross-reference between symptoms and corrective 45

recommendations. 46 5. Connection data to permit removal and installation of recommended smallest field-47

replaceable parts. 48 6. Recommended spare parts list. 49 7. Commissioning sheets showing “as-left” values of all user-programmable or adjustable 50

drive parameters. 51

Page 358: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 4

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Allen Bradley. 5 2. ASEA Brown Bovari (ABB). 6 3. Eaton. 7 4. Danfoss. 8 5. General Electric Company. 9 6. Siemens. 10 7. Square D Company. 11 8. Toshiba. 12 9. Yaskawa. 13

B. Submit request for substitution in accordance with Specification Section 01640. 14

2.2 GENERAL 15

A. VFDs shall consist of a rectifier-DC bus-inverter combination producing a sine-coded pulse-16 width-modulated (PWM) output voltage waveform. 17

B. VFDs, whether installed in motor control center (MCC) construction or separately-mounted, 18 shall constitute a complete combination motor controller per NFPA 70, Article 430 and shall 19 provide the following per the requirements of that article without the addition of any external 20 components or devices. 21 1. Motor control. 22 2. Motor overload protection. 23 3. Motor and motor branch circuit short circuit and ground fault protection. 24 4. Motor and controller disconnecting means. 25

C. It is the intent of this Specification that VFDs shall be an “engineered” or “configured” drive 26 package in which the VFD chassis, all input, output and bypass power devices, VFD accessories, 27 ancillary switches, contactors, relays, and related control devices are selected, furnished, factory-28 assembled and -tested by the VFD manufacturer in a single enclosure requiring only connection 29 of the power supply circuit, motor branch circuit, and external control wiring in the field. 30

2.3 PERFORMANCE AND DESIGN REQUIREMENTS 31

A. Application: 32 1. VFD(s) shall be of sufficient capacity and shall provide a quality of output waveform for 33

stepless motor control from 10 to 100 percent of base speed of the driven equipment. 34 2. VFDs shall be compatible with: 35

a. Inverter duty induction motors. 36 3. VFDs shall be suitable for Variable Torque (VT) applications. 37

a. VFD manufacturer shall coordinate with the manufacturer of the driven equipment to 38 identify application. 39

4. VFDs shall be designed to operate successfully under the following site conditions: 40 a. Ambient: 41

1) Temperature: 0-40 DegC. 42 2) 95 percent non-condensing relative humidity. 43

b. Elevation: 950 FT above MSL. 44 c. Power supply characteristics: 45

1) 480Vac, 3 PH, 60 Hz, 3 wire, (+/- 10 percent). 46 2) Effectively grounded. 47

Page 359: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 5

B. Ratings and Performance Specifications: 1 1. Voltage rating: 2

a. Nominal: 480Vac, 3 PH, 60 Hz. 3 b. Range for continuous full load operation: ±10 percent of nominal. 4 c. Voltage imbalance tolerance for full load operation: 3 percent minimum. 5

2. Current ratings: 6 a. Continuous: 7

1) Equal to or greater than the motor nameplate full load. 8 b. Short-term overload: 9

1) VT: 110 percent for 1 minute. 10 2) Permissible for 1 minute every 10 minutes continuously. 11

c. Short circuit: 12 1) 42,000A RMS SYM, minimum. 13 2) Where a short circuit rating is not indicated or specified for individual VFDs, each 14

VFD shall have a rating not less than indicated on the Drawings for the MCC, 15 switchboard or panelboard the VFD is supplied from. 16

3) Where specified short circuit rating indicates additional input impedance is 17 required to protect semiconductors, provide input AC line reactors, whether 18 required to meet harmonic performance specifications or not. 19

3. Efficiency: 20 a. 97 percent, minimum, at full speed and full load. 21 b. 93 percent, minimum at 1/2 speed and full load. 22

4. Displacement power factor: 23 a. 95 percent, minimum from 50 percent to 100 percent speed and load. 24

5. Efficiency and power factor criteria apply from the input terminals to the output terminals of 25 the VFD alone, excluding losses of input and output power circuit accessories. 26

6. Frequency drift: 27 a. +0.5 percent of set frequency. 28

7. Speed regulation (motor dependent): 3 percent. 29 8. Speed range: 10:1. 30 9. Control type: 31

a. Volts/Hertz ratio; constant over the entire operating range of the VFD except: 32 1) When operating under voltage boost. 33 2) At frequencies over 60 Hz. 34

C. Operational Features: 35 1. Insensitive to input phase sequence. 36 2. Continued operation with momentary voltage dips of 25 percent of rated voltage, or single 37

phase condition: 4 second, minimum. 38 3. Controls power loss ride-through: 500 msec, minimum. 39 4. Electronic reversing. 40 5. DC injection braking. 41 6. Anti-windmilling: Synchronization of VFD starting frequency with spinning or coasting 42

load, forward or reverse. 43 7. Critical frequency band lockout: 44

a. Minimum of three (3) settings. 45 b. Adjustable bandwidth, 1 - 5 Hz. 46

8. Capable of operating without the motor connected for start-up and troubleshooting. 47

D. The VFD shall be provided with the following minimum user-programmable parameters: 48 1. Carrier frequency. 49 2. Independent maximum and minimum speeds for forward and reverse operation. 50 3. Start frequency and hold time. 51 4. Independent linear acceleration and deceleration time. 52 5. Preset “jog” speed. 53 6. Three (3) critical frequency bands. 54 7. One (1) preset speed selectable by logic input. 55

Page 360: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 6

8. Volts/Hertz ratio. 1 9. Voltage boost, magnitude and frequency range. 2 10. Process controller gain, offset and bias. 3 11. Current limit. 4 12. Overcurrent pickup. 5 13. Overcurrent delay. 6 14. Ground fault pickup. 7 15. DC injection level and time. 8

E. The VFD shall be designed such that the power circuit components are fully protected from line 9 side disturbances and load side faults: 10 1. General: 11

a. Shutdown conditions associated with supply circuit conditions which can be corrected 12 external to the VFD-motor system shall be provided with automatic reset, with 13 shutdown cause logged in memory: 14 1) Input under voltage. 15 2) Input over voltage. 16 3) Input under frequency. 17 4) Input over frequency. 18 5) Input Phase loss. 19 6) DC Bus under voltage. 20

b. Shutdown conditions which indicate overload or fault within the VFD, the output 21 circuit, or the motor shall require local manual reset at the VFD, requiring operator 22 intervention. 23 1) Over temperature. 24 2) Blown fuse. 25 3) Component failure. 26 4) Overload. 27 5) Short circuit. 28 6) Ground fault. 29 7) DC Bus over voltage. 30 8) External safety input (e.g., motor thermal protection). 31 9) Logic fault. 32

c. When automatic shutdown occurs, VFD shall restart only when remote run signal is 33 removed and reapplied. 34

d. VFD shall hold cause of trip data for a minimum of four (4) shutdowns in memory. 35 1) Data to be accessible through the keypad. 36

2. Input protection: 37 a. Input circuit breaker or current-limiting fuses with externally operable disconnect. 38

1) Fault current interrupting rating equal to or greater than the specified withstand 39 rating of the VFD. 40

2) Handle padlockable in the OFF position. 41 b. Provide full protection for semiconductors integral to the VFD; units requiring current-42

limiting fuses or circuit breakers in the supply circuit are not acceptable. 43 c. Incoming line transient suppression. 44

1) 6000V peak per IEEE C62.41. 45 2) Phase-to-phase and phase-to-ground protection. 46

d. Sustained over voltage trip. 47 3. Internal protection: 48

a. Surge suppression and power device snubbers. 49 b. Power devices rated at 2.5 times line voltage. 50 c. Instantaneous over current trip. 51 d. DC bus over voltage trip. 52 e. Power device over temperature trip. 53 f. Control logic circuit malfunction trip. 54

Page 361: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 7

4. Output protection: 1 a. Inverse-time overload trip: 2

1) UL Class 10 characteristic. 3 b. Over voltage trip. 4 c. Over frequency trip. 5 d. Short circuit trip. 6

1) Line to line and line to ground. 7 e. Ground fault trip. 8

2.4 OPERATOR CONTROL INTERFACE 9

A. Drive controls shall be microprocessor-based with on-board human machine interface. 10 1. All monitoring and control functions, other than those shutdowns specified to be manual 11

reset only, shall be available. 12

B. Control circuits shall be 120 Vac or 24 Vac or 24 Vdc. 13 1. 120 Vac supplied by CPT in the VFD. 14

a. CPT shall have minimum additional capacity of 60 VA greater than that required by 15 control devices. 16

b. CPT shall have two (2) fuses on the primary side and one (1) fuse on the secondary 17 side. 18

c. CPT shall have surge protection on the primary side independent of any other surge 19 protection in the VFD. 20

2. 24 Vac or 24 Vdc supplied by Class 2 power supply in the VFD. 21 a. Power supply shall have minimum additional capacity of 33 percent greater than that 22

required by control devices. 23 b. Provide two (2) current-limiting fuses on the AC supply to the power supply. 24 c. Power supply shall have surge protection on the primary side independent of any other 25

surge protection in the VFD. 26

C. Operator Interface: 27 1. Door mounted sealed keypad, membrane type with LED or LCD display. 28

a. Messages shall be in English and engineering units. 29 b. Drive operating parameters shall be programmable. 30 c. Menu driven. 31 d. Password security. 32 e. Display fault and diagnostic data. 33 f. Operating parameters, fault and diagnostic data maintained in non-volatile memory 34

with historic log of fault and diagnostic data. 35 g. Gold plated plug-in contacts. 36

2. Provide indication and control interface, integral in the keypad, as required in the sequence 37 of operation and Drawings. 38 a. Minimum indications: 39

1) Run. 40 2) Stop. 41 3) Ready. 42 4) Alarm. 43 5) Fault. 44 6) Local control. 45 7) Remote control. 46 8) Control source local. 47 9) Control source remote. 48 10) Speed indication. 49

b. Minimum control functions: 50 1) Local/Remote switch. 51 2) Stop button. 52 3) Start button. 53

Page 362: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 8

4) Reset button. 1 5) Speed control buttons. 2

3. Diagnostic indicators located externally on the face of the drive shall show the type of fault 3 responsible for drive warning, shutdown or failure. 4 a. On occurrence of more than one (1) condition, each shall be recorded or indicated by 5

the diagnostics. 6

D. Remote Control Interface: 7 1. Local portable computer interface via RS232/RS242 serial communications port: 8

a. Capability to: 9 1) Start-Stop VFD. 10 2) Control VFD Speed. 11 3) Access fault and diagnostic data. 12

2. Analog and discrete inputs: 13 a. Speed reference (setpoint) signal 4-20 mA DC. 14 b. Isolated process PID controller with user-programmable setpoint, gain, rate, reset and 15

span for accepting a remote 4-20 mADC process variable signal. 16 3. Analog and discrete outputs: 17

a. 4-20 mADC output for remote speed indication, as a function of frequency, calibrated 0 18 to 100 percent. 19

b. Drive FAULT contacts. 20 c. Drive RUNNING contacts. 21 d. Drive selector switch in REMOTE status contacts. 22

4. Contacts: 23 a. Contacts shall be rated 2 A inductive at 120 Vac. 24 b. All contacts shall be wired to field wiring terminal boards. 25

5. Drive shutdown on external fault input: 26 a. Provide isolated input for dry contact from external motor or system safety devices to 27

cause immediate shutdown of VFD. 28 b. Safety shutdown to be operable in all operating modes of drive, including local 29

operation from keypad. 30

2.5 HARMONIC PROTECTION REQUIREMENTS 31

A. All VFDs shall be capable of satisfactory operation from a source having voltage distortion and 32 notch characteristics identified as acceptable for a “dedicated system” in IEEE 519 Table 10.2. 33

B. With two VFDs operating under worst-case harmonic current conditions, and the facility 34 supplied from the utility, the VFDs shall not produce harmonic effects in excess of the following 35 limits at any point of common coupling (PCC). 36 1. Voltage distortion and notch characteristics: IEEE 519 Table 10.2 for General System. 37 2. Current distortion: IEEE 519 Table 10.3 based on calculated ISC/IL at each PCC. 38

C. PCC shall be considered: 39 1. Each MCC, switchboard, switchgear, or panelboard supplying a VFD branch circuit. 40

D. The Engineer has performed preliminary calculations based on typical VFD data which indicate 41 that the minimum mitigation measures required to meet the specified harmonic criteria are 42 one (1) of the following topologies: 43 1. 12-pulse rectifier topology for each VFDs. 44 2. 18-pulse rectifier topology for each VFDs. 45 3. Active filters or active front end rectifier topology for each VFDs. 46

E. VFD manufacturer shall determine, for their proposed equipment, uncorrected harmonic 47 distortion levels and mitigation techniques required to meet the specified limits and shall furnish 48 the VFD types and all accessory items and equipment necessary to do so, whether specified 49 herein or not. 50

Page 363: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 9

F. VFD manufacturer shall provide a harmonic analysis of the distribution system based on their 1 proposed specific equipment characteristics and mitigation techniques confirming that the 2 specified levels are not exceeded. 3 1. Analysis shall be based on the methodology of IEEE 519 and IEEE 399. 4 2. Power system data for analysis shall be taken from the Electrical Drawings and approved 5

equipment submittals. 6 a. VFDs provided in a package with equipment specified elsewhere, shall be included in 7

the analysis. 8

G. Following start-up, with facility at full load operation, provide measurement of harmonic 9 voltage, current and notch characteristics at each PCC according to the requirements of 10 IEEE 519 Section 9. 11 1. Values in excess of specified limits require correction by contractor and re-measurement. 12 2. Provide certification of compliant measurements as part of Field Service Engineer’s final 13

report. 14

2.6 MOTOR PROTECTION REQUIREMENTS 15

A. The VFD shall produce a quality of output waveform adequate to allow the motor to produce 16 rated torque at rated RPM continuously without exceeding the temperature rise given in 17 NEMA MG 1 Table 31-2. 18

B. Provide motor overload, short circuit and ground fault protection integral to drive electronics. 19

C. The VFD shall not produce voltage spikes in excess of the following values at the motor 20 terminals when operated with the feeder types shown on the Drawings and the actual installed 21 feeder lengths. 22 1. If unmitigated voltage peaks exceed the specified limits, provide output line reactors, filters, 23

or other devices as required to meet the specified limits: 24 a. Inverter duty motors: 1280 V. 25 b. Rise time shall be greater than or equal to 0.1 microsecond. 26 c. Motor lead length and data shall be determined by the Contractor based on the actual 27

routing of the conductors. 28

D. Following start-up, provide measurement of peak voltage at the terminals of each motor, unless 29 the lead lengths are 10 percent shorter than the manufacturers published literature for maximum 30 lead length for the type of cable installed. 31 1. Values in excess of specified limits require correction by contractor and re-measurement. 32 2. Provide certification of compliant measurements as part of Field Service Engineer’s final 33

report. 34

2.7 EQUIPMENT CONSTRUCTION 35

A. Fabrication and Assembly: 36 1. Each VFD system shall be factory-assembled in an enclosure for remote mounting, and 37

shall utilize interchangeable plug-in printed circuit boards and power conversion 38 components wherever possible. 39 a. Factory assembly shall be performed by the VFD manufacturer or authorized agent. 40 b. Systems fabricated or assembled in whole or in part by parties other than the VFD 41

manufacturer or authorized agent will not be acceptable. 42 2. Reactors and/or filters, where required, shall be mounted within or in an ancillary enclosure 43

adjacent to the drive enclosure, or with the Engineer's permission may be mounted in a 44 separate enclosure. 45

3. Cooling fans, as required, shall be provided to run when drive is running. 46 4. Enclosures for separately mounted VFD's: 47

a. NEMA Type 1 for installation in Electrical Rooms. 48 b. NEMA Type 12 for installation in other unclassified areas. 49

Page 364: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 10

B. Wiring: 1 1. The wiring in the VFD shall be neatly installed in wire ways or with wire ties where wire 2

ways are not practical. 3 a. Where wire ties are used, the wire bundles are to be held at the back panel with a 4

screw-mounted wire tie mounting base. 5 b. Bases with a self-sticking back will not be allowed. 6

2. All plug-in contacts shall be gold-plated. 7 3. Provide terminal boards for all field wiring and inter-unit connections, including analog 8

signals. 9 a. Provide terminals for shield continuity where required. 10

4. Terminal blocks shall be complete with marking strip, covers and pressure connectors. 11 a. Non-brittle, interlocking, track-mounted type. 12 b. Screw terminals will not be allowed. 13 c. A terminal for each conductor of external circuits plus one (1) ground for each shielded 14

cable. 15 d. For free-standing panels, 8 IN of clearance shall be provided between terminals and the 16

panel base for conduit and wiring space. 17 e. Not less than 25 percent spare terminals shall be provided. 18 f. Terminals shall be labeled to agree with identification indicated on the suppliers 19

submittal Drawings. 20 g. Individually fuse each control loop or system and all fuses or circuit breakers shall be 21

clearly labeled and located for easy maintenance. 22 5. All grounding wires shall be attached to the enclosure sheet metal with a ring tongue 23

terminal. 24 a. The surface of the sheet metal shall be prepared to assure good conductivity and 25

corrosion protection. 26 6. Wiring shall not be kinked or spliced and shall have markings on both ends or be color 27

coded. 28 a. Markings or color code shall match the manufacturer's Drawings. 29

7. With the exception of electronic circuits, all interconnecting wiring and wiring to terminals 30 for external connection shall be stranded copper, type MTW or SIS, insulated for not less 31 than 600 V, with a moisture-resistant and flame-retardant covering rated for not less than 32 90 DegC. 33

C. Nameplates: 34 1. All devices mounted on the face of the drive shall be provided with a suitable nameplate as 35

specified in Specification Section 10400. 36 2. Push buttons, selector switches, and pilot lights shall have the device manufacturer's 37

standard legend plate. 38 3. Relays, terminals and special devices inside the control enclosure shall have permanent 39

markings to match identification used on manufacturer's wiring diagrams. 40

D. Painting: Enclosure, after being phosphate washed, shall be thoroughly cleaned and given at 41 least one (1) coat of rust-inhibiting primer on all inner surfaces prior to fabrication. 42

2.8 SOURCE QUALITY CONTROL 43

A. Factory Tests: 44 1. Conduct all standard tests in accordance with NEMA and ANSI standards to ensure 45

conformance to Specification requirements. 46 2. Prior to final assembly: 47

a. Inspect incoming components. 48 b. Test and inspect power devices. 49 c. Circuit cards: 50

1) Component and functional tests: 51 2) Burn-in chamber or temperature cycling test. 52 3) System test after burn-in or temperature cycling. 53

Page 365: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 11

3. After final assembly: 1 a. Continuity and insulation test of 480 power control circuits. 2 b. Drive tests: 3

1) Burn-in complete drive at full load for 24 HRS. 4 2) Verify all auxiliary circuits operation. 5 3) Monitor output variables. 6

c. Systems test: 7 1) Provide inputs to field connections and simulate on-site operation. 8 2) Test all auxiliary equipment. 9

2.9 MAINTENANCE MATERIALS 10

A. Provide manufacturers recommended renewable spare parts (e.g., power and control fuses). 11

B. Spare parts utilized during pre-start-up or start-up and demonstration testing shall be 12 immediately restocked, at no cost to the Owner. 13

PART 3 - EXECUTION 14

3.1 INSTALLATION 15

A. Install products in accordance with manufacturer's instructions and as indicated on the Drawings. 16

B. Verify the installed motor nameplate electrical requirements do not exceed the VFD capacity. 17

C. Provide services of manufacturer's representative to perform start-up services. 18

D. The selection of input and output harmonic and voltage spike protection shall also be made on 19 the available physical space. 20 1. The space available on the Drawings shall not be exceeded. 21

3.2 START UP 22

A. Pre-start-up Services: 23 1. Shall be completed a minimum of 30 days prior to the start-up and demonstration period 24

described in Specification Section 01650. 25 2. Shall consist of: 26

a. Physical and electrical installation check. 27 b. Final adjustments and calibration of drive parameters. 28 c. VFD operation from simulated input signals. 29

3. Shall be complete when VFD(s) are fully operational. 30

B. Field Quality Control: 31 1. Perform field measurement of harmonics at each PCC per Harmonic Protection 32

Requirements Article. 33 a. For each individual VFD. 34 b. For the maximum number of VFDs that will be operational at the same time. 35 c. When all loads are at 75 percent load minimum. 36 d. Duration: 1 HR minimum. 37

2. Perform field measurement of the maximum voltage peak at the terminals of each motor fed 38 from a VFD per Motor Protection Requirements Article. 39 a. Use a high speed oscilloscope to produce a plot of Voltage (Y axis) versus Time (X 40

axis). 41 1) Time shall be measured in microseconds. 42

b. Tests shall be performed at full: 43 1) Full voltage and speed. 44 2) Loaded to 75 percent minimum. 45 3) Duration: 1 HR minimum. 46

3. Record all data necessary for the preparation of required test reports. 47

Page 366: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - VARIABLE FREQUENCY DRIVES: LOW VOLTAGE 16265 - 12

C. Start-up and Demonstration Services: 1 1. Supervise start-up of all units including recheck of settings made during the pre-start-up 2

tests. 3 a. Perform all work in the presence of the Owner's designated representatives. 4

2. Setup all VFDs with carrier frequency at minimum value consistent with proper operation; 5 inform Engineer of carrier frequencies set in excess of 5 kHz and reason for setting. 6

3. Simulate operation of the VFD and its associated control and instrumentation system in both 7 the manual and automatic modes. 8 a. Ensure compatibility of VFD with associated control and instrumentation signals. 9

4. Simulate VFD failures and demonstrate troubleshooting aids. 10

D. Instruct Owner's Designated Personnel: 11 1. Minimum of 8 HRS at the jobsite. 12 2. Include both field and classroom instruction. 13 3. Instructions shall include proper operation and maintenance procedures including, but not 14

limited to: 15 a. Lubrication. 16 b. Troubleshooting. 17 c. Repair and replacement. 18 d. Parts inventory. 19 e. Maintenance records. 20

3.3 SCHEDULES 21

A. Several motors may have full load amps (FLA) greater than that listed in NFPA 70. 22 1. The following table is an estimate for the FLA of the motors based on preliminary Shop 23

Drawings. 24 25

EQUIPMENT TAG HP RPM ESTIMATED FLA

CWP1 200 1183 255

CWP2 200 1183 255

CWP3 200 1183 255

26

END OF SECTION 27

Page 367: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TERMINAL CABINETS 16343 - 1

2014/08/28 1

SECTION 16343 2

TERMINAL CABINETS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Low voltage cable terminal cabinets. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 0 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 1 - General Conditions. 10 3. Section 16010 - Electrical: Basic Requirements. 11

1.2 QUALITY ASSURANCE 12

A. Referenced Standards: 13 1. Institute of Electronic and Electrical Engineers (IEEE): 14

a. C57.12.28, Standard for Pad-Mounted Equipment – Enclosure Integrity. 15

1.3 SUBMITTALS 16

A. Shop Drawings: 17 1. See Specification Section 01340 for requirements for the mechanics and administration of 18

the submittal process. 19 2. Product technical data including: 20

a. Provide submittal data for all products specified in PART 2 of this Specification 21 Section. 22

b. Nameplate data. 23 c. See Specification Section 16010 for additional requirements. 24

3. Fabrication and/or layout drawings: 25 a. General arrangement plan view showing door swings, cable entrance locations, etc. 26

B. Operation and Maintenance Manuals: 27 1. See Specification Section 01340 for requirements for: 28

a. The mechanics and administration of the submittal process. 29 b. The content of Operation and Maintenance Manuals. 30

C. Miscellaneous Submittals: 31 1. See Specification Section 01340 for requirements for the mechanics and administration of 32

the submittal process. 33

1.4 DELIVERY, STORAGE AND HANDLING 34

A. See Specification Section 16010. 35

PART 2 - PRODUCTS 36

2.1 ACCEPTABLE MANUFACTURERS 37

A. Subject to compliance with the Contract Documents, the following manufacturers are 38 acceptable: 39 1. Cooper Power Systems. 40 2. S&C Electric Company. 41

Page 368: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TERMINAL CABINETS 16343 - 2

3. Shallbetter Inc. 1 4. Trinetics. 2

B. Submit request for substitution in accordance with Specification Section 01640. 3

2.2 CABLE TERMINAL CABINETS 4

A. Ratings: 5 1. Voltage: 600 V. 6 2. Amperage: 3000 A. 7 3. Number of phases: 3. 8 4. Number of wires: 4 plus ground. 9 5. Frequency: 60 Hz. 10 6. Short circuit: 50,000 A 11 7. UL Listed. 12

B. Enclosure: 13 1. Material: 0.125 IN 5052H32 aluminum alloy. 14 2. All welded construction. 15 3. Roof cross-kinked for water shedding in all directions. 16 4. Tamperproof per IEEE and ANSI standards. 17 5. Front and rear doors with: 18

a. Stainless steel hinges and hardware. 19 b. Three-point latching mechanism. 20 c. Padlockable. 21 d. Automatically latching door holders. 22

6. Lifting provisions. 23 7. Non-corrosive nameplate. 24 8. Interior and exterior surfaces cleaned and painted with rust inhibiting primer and 25

manufacturer’s standard paint. 26 9. Finish color: Dark green. 27

a. Size: 48 IN x 48 IN x 48 IN minimum. Conduit entry space 45 IN x 45 IN minimum. 28

C. Buses: 29 1. Material: Tin-plated copper. 30 2. Minimum of 18 sets of NEMA two hole pattern. 31 3. Spacing between buses to allow a minimum of 36 cable terminations (back-to-back on each 32

NEMA two hole pattern. 33 4. Bus supports and standoff insulators: porcelain or epoxy. 34

D. Basis of Design: Shallbetter Model STEN. 35

2.3 MAINTENANCE MATERIALS 36

A. Touch-up paint. 37

PART 3 - EXECUTION 38

3.1 INSTALLATION 39

A. Install in accordance with manufacturer's instructions. 40

B. Arrange as shown on the Drawings. 41

C. Pad Mounted Cable Terminal Cabinets: 42 1. Install on concrete pad per detail on the Drawings. 43

D. Miscellaneous: Paint any scratched surfaces with touch-up paint. 44

END OF SECTION 45

Page 369: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SAFETY SWITCHES 16410 - 1

2014/10/07 1

SECTION 16410 2

SAFETY SWITCHES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: Safety switches. 6

B. Related Specification Sections include but are not necessarily limited to: 7 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 8 2. Division 01 - General Requirements. 9 3. Section 16010 - Electrical: Basic Requirements. 10

1.2 QUALITY ASSURANCE 11

A. Referenced Standards: 12 1. National Electrical Manufacturers Association (NEMA): 13

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 14 b. KS 1, Enclosed and Miscellaneous Distribution Equipment Switches (600 Volts 15

Maximum). 16 2. Underwriters Laboratories, Inc. (UL): 17

a. 98, Enclosed and Dead-Front Switches. 18

1.3 SUBMITTALS 19

A. Shop Drawings: 20 1. See Specification Section 01340 for requirements for the mechanics and administration of 21

the submittal process. 22 2. Product technical data: 23

a. Provide submittal data for all products specified in PART 2 of this Specification 24 Section. 25

b. Provide a table that associates safety switch model number with connected equipment 26 tag number. 27

c. See Specification Section 16010 for additional requirements. 28

B. Operation and Maintenance Manuals: 29 1. See Specification Section 01342 for requirements for: 30

a. The mechanics and administration of the submittal process. 31 b. The content of Operation and Maintenance Manuals. 32

PART 2 - PRODUCTS 33

2.1 ACCEPTABLE MANUFACTURERS 34

A. Subject to compliance with the Contract Documents, the following safety switch manufacturers 35 are acceptable: 36 1. Eaton. 37 2. General Electric Company. 38 3. Square D Company. 39 4. Siemens. 40 5. Appleton Electric Company. 41 6. Crouse-Hinds. 42 7. Killark. 43

Page 370: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SAFETY SWITCHES 16410 - 2

B. Submit request for substitution in accordance with Specification Section 01640. 1

2.2 SAFETY SWITCHES 2

A. General: 3 1. Non-fusible or fusible as indicated on the Drawings. 4 2. Suitable for service entrance when required. 5 3. NEMA Type HD heavy-duty construction. 6 4. Switch blades will be fully visible in the OFF position with the enclosure door open. 7 5. Quick-make/quick-break operating mechanism. 8 6. Deionizating arc chutes. 9 7. Manufacture double-break rotary action shaft and switchblade as one (1) common 10

component. 11 8. Clear line shields to prevent accidental contact with line terminals. 12 9. Operating handle: 13

a. Red and easily recognizable. 14 b. Padlockable in the OFF position 15 c. Interlocked to prevent door from opening when the switch is in the ON position with a 16

defeater mechanism. 17

B. Ratings: 18 1. Horsepower rated of connected motor. 19 2. Voltage and amperage: As indicated on the Drawings. 20 3. Short circuit withstand: 21

a. Non-fused: 10,000A. 22 b. Fused: 200,000A. 23

C. Accessories, when indicated in PART 3 of this Specification Section or on the Drawings: 24 1. Neutral kits. 25 2. Ground lug kits. 26 3. Auxiliary contact kits with 1 N.O. and 1 N.C. contact. 27

D. Enclosures: 28 1. NEMA 12 rated: 29

a. Body and cover: Sheet steel finished with rust inhibiting primer and manufacturers 30 standard paint inside and out. 31

b. No knockouts, external mounting flanges, hinged and gasketed door. 32

E. Overcurrent and short circuit protective devices: 33 1. Fuses. 34 2. See Specification Section 16490 for overcurrent and short circuit protective device 35

requirements. 36

F. Standards: NEMA KS 1, UL 98. 37

PART 3 - EXECUTION 38

3.1 INSTALLATION 39

A. Install as indicated and in accordance with manufacturer's instructions and recommendations. 40

B. Install switches adjacent to the equipment they are intended to serve unless otherwise indicated 41 on the Drawings. 42

C. Provide auxiliary contact kit on local safety switches for motors being controlled by a variable 43 frequency drive. 44 1. The VFD is to be disabled with the switch is in the open position. 45

Page 371: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SAFETY SWITCHES 16410 - 3

D. Permitted uses of NEMA 1 enclosure: 1 1. Surface or flush mounted in areas designated dry in non-architecturally finished areas. 2

END OF SECTION 3

4

Page 372: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SAFETY SWITCHES 16410 - 4

1

Page 373: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TRANSFER SWITCHES 16411 - 1

2014/10/03 1

SECTION 16411 2

TRANSFER SWITCHES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Low voltage switchboard with breaker control system. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 16010 - Electrical: Basic Requirements. 11 4. Section 16490 - Overcurrent and Short Circuit Protective Devices. 12 5. Section 16491 - Low Voltage Surge Protective Devices (SPD). 13 6. Section 16493 - Control Equipment Accessories. 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. National Electrical Manufacturers Association (NEMA): 17

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 18 b. PB 2, Deadfront Distribution Switchboards. 19

2. Underwriters Laboratories, Inc. (UL): 20 a. 891, Standard for Safety Dead-Front Switchboards. 21

B. Verify the space required for the switchboard is equal to or less than the space allocated. 22

1.3 SUBMITTALS 23

A. Shop Drawings: 24 1. See Specification Section 01340 for requirements for the mechanics and administration of 25

the submittal process. 26 2. Product technical data. 27

a. Provide submittal data for all products specified in PART 2 of this Specification 28 Section. 29

3. See Specification Section 16010 for additional requirements. 30 4. Fabrication and/or layout drawings: 31

a. Switchboard layout with alphanumeric designation, protective devices size and type, as 32 indicated in the one-line diagram or switchboard schedule. 33

b. Front elevation and plan drawing of the assembly. 34 c. Three-line or single line and schematic diagrams. 35 d. Conduit space locations within the assembly. 36 e. Circuit breaker control diagrams. 37

B. Operation and Maintenance Manuals: 38 1. See Specification Section 01342 for requirements for: 39

a. The mechanics and administration of the submittal process. 40 b. The content of Operation and Maintenance Manuals. 41

2. Fabrication and/or layout drawings updated with as-build conditions 42

C. Informational Submittals: 43 1. See Specification Section 01340 for requirements for the mechanics and administration of 44

the submittal process. 45

Page 374: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TRANSFER SWITCHES 16411 - 2

2. Ground fault protection system test report signed by the projects supervising electrical 1 foreman. 2

PART 2 - PRODUCTS 3

2.1 ACCEPTABLE MANUFACTURERS 4

A. Subject to compliance with the Contract Documents, the following manufacturers are 5 acceptable: 6 1. Eaton. 7 2. General Electric Company. 8 3. Square D Company. 9 4. Siemens. 10

B. Submit request for substitution in accordance with Specification Section 01640. 11

2.2 SWITCHBOARDS 12

A. Ratings: 13 1. Voltage, number of phases, number of wires, and main bus current rating as indicated on the 14

Drawings. 15 2. Assembly short circuit current and interrupting device rating as indicated on the Drawings. 16 3. When low voltage power circuit breakers are utilized, the switchboard shall have a 30 cycle 17

withstand rating corresponding to the breaker rating. 18 4. Service Entrance Equipment rated when indicated on the Drawings. 19

B. Construction: 20 1. Standards: NEMA PB 2, UL 891. 21 2. Completely enclosed, dead-front, self-supporting metal structure. 22 3. Vertical panel sections bolted together. 23 4. Frames bolted together to support and house bus, cables and other equipment. 24 5. Frames and insulating blocks to support and brace main buses for short circuit stresses up to 25

ratings indicated on the Drawings. 26 6. All sections front and rear aligned. 27 7. NEMA 3R rated weatherproof enclosure: 28

a. Nonwalk-in type with sloping roof downward toward rear. 29 b. Thermostatically controlled space heaters to minimize internal condensation. 30 c. Power for heater derived internal to the switchboard. 31

8. Interior and exterior steel surfaces cleaned and painted with rust inhibiting primer and 32 manufacturers standard paint. 33

C. Buses: 34 1. Material: Tin-plated aluminum or silver-plated copper. 35 2. Main horizontal bus: 36

a. Fully rated and continuous over length of switchboard with all three (3) phases 37 arranged in the same vertical plane. 38

b. Sufficient size to limit temperature rise to 65 DegC over average air temperature 39 outside the enclosure of 40 DegC. 40

3. Neutral bus: Fully rated and continuous over length of switchboard. 41 4. Ground bus: 1/4 x 2 IN copper, continuous over length of switchboard and solidly 42

grounded to each vertical section structure. 43 5. Bus joints connected using through bolts and conical spring-type washers for maximum 44

conductivity. 45

D. Overcurrent and Short Circuit Protective Devices: 46 1. Utility Feeder overcurrent protective device: 47

a. Individually mounted, electrically operated, insulated case circuit breaker with arc flash 48 maintenance provision. 49

Page 375: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TRANSFER SWITCHES 16411 - 3

2. Standby Service overcurrent protective devices: 1 a. Individually mounted, electrically operated, insulated case circuit breaker with arc flash 2

maintenance provision. 3 3. See Specification Section 16490 for overcurrent and short circuit protective device 4

requirements. 5 4. Factory installed. 6 5. Means to padlock all main and feeder devices in the open position. 7

E. Surge Protective Device: Integrally mounted, see Specification Section 16491. 8

F. Accessories: 9 1. Thermograph viewing windows for infrared surveys without opening doors. 10 2. Arc Flash reduction system with switch and indicating light integrated into the breaker 11

assembly. 12 3. Main-Generator breaker control system. 13

G. Operation: 14 1. Microprocessor based control module. 15 2. Open transition. 16 3. Red and green indicating lights with fuses, identification nameplates, and test switch on 17

front to simulate normal power failure at switch. 18 4. Engine starting contacts and all other auxiliary contacts and accessory devices for functions 19

to be performed. 20 5. Supervisory voltage relays on each phase of normal source and single phase supervisory 21

voltage and frequency relay for emergency source. 22 a. Normal source voltage sensing. 23

1) Adjustable pickup from 85-100 percent of rated voltage, factory set 90 percent. 24 2) Adjustable dropout from 75-98 percent of pickup setting, factory set 85 percent. 25

b. Emergency source voltage and frequency sensing: 26 1) Adjustable pickup from 85-100 percent of rated voltage, factory set 90 percent. 27 2) Fixed voltage dropout at 85 percent of pickup setting. 28 3) Adjustable pickup from 90-100 percent of rated frequency, factory set 95 percent. 29 4) Fixed frequency dropout at 88 percent of pickup setting. 30

6. Time delays: 31 a. Engine start, adjustable from 0 to 10 seconds, factory set at 4 seconds, to avoid 32

unnecessary starting caused by short time outages. 33 b. Transfer to generator, adjustable from 0 to 120 seconds, factory set at 10 seconds. 34 c. Retransfer to normal, adjustable from 2 to 30 minutes, factory set at 15 minutes to 35

avoid erratic operation caused by short time reestablishment of normal source. 36 1) Automatically bypassed when emergency source fails and normal source is 37

available. 38 d. Generator cool down, adjustable from 0 to 60 minutes, factory set at 10 minutes. 39

7. Exerciser timer: 40 a. Enable and disable function. 41 b. Selectable to exercise with or without transferring load. 42 c. Adjustable exercise duration from 1 minute to 24 HRS, factory set at 15 minutes. 43 d. Adjustable day of the week exercise setting, factory set for Monday. 44

PART 3 - EXECUTION 45

3.1 INSTALLATION 46

A. Install as indicated and in accordance with manufacturer's recommendations and instructions. 47

B. Arrange switchboard as shown on Drawings. 48

Page 376: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - TRANSFER SWITCHES 16411 - 4

C. Outdoor Location: 1 1. NEMA 3R, Non-walk in enclosure. 2 2. Install on concrete housekeeping pad, align front of switchboard with top edge of pad 3

chamfer and securely fasten to pad per vendor details. 4

D. Miscellaneous: 5 1. Provide circuit protective devices and other associated equipment as indicated on the 6

drawings. 7 2. All control wiring shall be neatly laced and have flexibility at hinged locations. 8

3.2 FIELD QUALITY CONTROL 9

A. Test the ground fault protection system as indicated in Specification Section 16490. 10

B. Automatic Transfer Switch Testing: 11 1. Simulate power outage by pulling the PT fuses. 12

a. Verify engine generator starts and switch transfers in the specified time. 13 2. Simulate the return of normal power. 14

a. Verify the switch retransfers and engine generator shuts down in the specified time. 15 3. Perform a manual transfer and retransfer. 16 4. Verify the indicator lights function properly. 17

END OF SECTION 18

Page 377: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SEPARATELY MOUNTED CIRCUIT BREAKERS 16412 - 1

2014/08/28 1

SECTION 16412 2

SEPARATELY MOUNTED CIRCUIT BREAKERS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Separately mounted circuit breakers. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 16010 - Electrical: Basic Requirements. 11 4. Section 16490 - Overcurrent and Short Circuit Protective Devices. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. National Electrical Manufacturers Association (NEMA): 15

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 16 2. Underwriters Laboratories, Inc. (UL): 17

a. 489, Standard for Safety Molded Case Circuit Breakers, Molded Case Switches, and 18 Circuit Breaker Enclosures. 19

1.3 SUBMITTALS 20

A. Shop Drawings: 21 1. See Specification Section 01340 for requirements for the mechanics and administration of 22

the submittal process. 23 2. Product technical data: 24

a. Provide submittal data for all products specified in PART 2 of this Specification 25 Section. 26

b. Provide a table that associates equipment model number with equipment tag number. 27 c. See Specification Section 16010 for additional requirements. 28

B. Operation and Maintenance Manuals: 29 1. See Specification Section 01342 for requirements for: 30

a. The mechanics and administration of the submittal process. 31 b. The content of Operation and Maintenance Manuals. 32

PART 2 - PRODUCTS 33

2.1 ACCEPTABLE MANUFACTURERS 34

A. Subject to compliance with the Contract Documents, the following manufacturers are 35 acceptable: 36 1. Eaton. 37 2. General Electric Company. 38 3. Square D Company. 39 4. Siemens. 40 5. Appleton Electric Company. 41 6. Crouse-Hinds. 42 7. Killark. 43

Page 378: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SEPARATELY MOUNTED CIRCUIT BREAKERS 16412 - 2

B. Submit request for substitution in accordance with Specification Section 01640. 1

2.2 COMPONENTS 2

A. NEMA 4 rated: 3 1. Body and cover: Sheet steel finished with rust inhibiting primer and manufacturers standard 4

paint inside and out. 5 2. No knockouts, external mounting flanges, hinged and gasketed door. 6 3. Front operating handle padlockable in the OFF position and interlocked to prevent door 7

from opening when the breaker is ON. 8 4. Suitable for service entrance. 9

B. NEMA 4X rated: 10 1. Body and cover: Type 304 or 316 stainless steel. 11 2. No knockouts, external mounting flanges, hinged and gasketed door. 12 3. Front operating handle padlockable in the OFF position and interlocked to prevent door 13

from opening when the breaker is ON. 14 4. Suitable for service entrance. 15

C. Standards: UL 489. 16

D. Overcurrent and short circuit protective devices: 17 1. Molded case circuit breaker. 18 2. See Section 16490 for overcurrent and short circuit protective device requirements. 19 3. Factory installed. 20

PART 3 - EXECUTION 21

3.1 INSTALLATION 22

A. Install as indicated and in accordance with manufacturer's recommendations and instructions. 23

B. Permitted uses of NEMA 4 enclosure: 24 1. Surface mounted in areas designated as wet. 25

C. Permitted uses of NEMA 4X enclosure: 26 1. Surface mounted in areas designated as wet and/or corrosive. 27

END OF SECTION 28

Page 379: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SWITCHBOARDS 16440 - 1

2014/10/07 1

SECTION 16440 2

SWITCHBOARDS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Low voltage switchboards. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 16010 - Electrical: Basic Requirements. 11 4. Section 16490 - Overcurrent and Short Circuit Protective Devices. 12 5. Section 16491 - Low Voltage Surge Protective Devices (SPD). 13 6. Section 16493 - Control Equipment Accessories. 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. National Electrical Manufacturers Association (NEMA): 17

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 18 b. PB 2, Deadfront Distribution Switchboards. 19

2. Underwriters Laboratories, Inc. (UL): 20 a. 891, Standard for Safety Dead-Front Switchboards. 21

B. Verify the space required for the switchboard is equal to or less than the space allocated. 22

1.3 SUBMITTALS 23

A. Shop Drawings: 24 1. See Specification Section 01340 for requirements for the mechanics and administration of 25

the submittal process. 26 2. Product technical data. 27

a. Provide submittal data for all products specified in PART 2 of this Specification 28 Section. 29

3. See Specification Section 16010 for additional requirements. 30 4. Fabrication and/or layout drawings: 31

a. Switchboard layout with alphanumeric designation, protective devices size and type, as 32 indicated in the one-line diagram or switchboard schedule. 33

b. Front elevation and plan drawing of the assembly. 34 c. Three-line or single line and schematic diagrams. 35 d. Conduit space locations within the assembly. 36

B. Operation and Maintenance Manuals: 37 1. See Specification Section 01342 for requirements for: 38

a. The mechanics and administration of the submittal process. 39 b. The content of Operation and Maintenance Manuals. 40

2. Fabrication and/or layout drawings updated with as-build conditions 41

C. Informational Submittals: 42 1. See Specification Section 01340 for requirements for the mechanics and administration of 43

the submittal process. 44 2. Ground fault protection system test report signed by the projects supervising electrical 45

foreman. 46

Page 380: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SWITCHBOARDS 16440 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Eaton. 5 2. General Electric Company. 6 3. Square D Company. 7 4. Siemens. 8

B. Submit request for substitution in accordance with Specification Section 01640. 9

2.2 SWITCHBOARDS 10

A. Ratings: 11 1. Voltage, number of phases, number of wires, and main bus current rating as indicated on the 12

Drawings. 13 2. Assembly short circuit current and interrupting device rating as indicated on the Drawings. 14 3. When low voltage power circuit breakers are utilized, the switchboard shall have a 30 cycle 15

withstand rating corresponding to the breaker rating. 16 4. Service Entrance Equipment rated when indicated on the Drawings. 17

B. Construction: 18 1. Standards: NEMA PB 2, UL 891. 19 2. Completely enclosed, dead-front, self-supporting metal structure. 20 3. Vertical panel sections bolted together. 21 4. Frames bolted together to support and house bus, cables and other equipment. 22 5. Frames and insulating blocks to support and brace main buses for short circuit stresses up to 23

ratings indicated on the Drawings. 24 6. All sections front and rear aligned. 25 7. Devices front removable and load connections front accessible for mounting switchboard 26

against a wall. 27 8. NEMA 1 rated enclosure. 28 9. Interior and exterior steel surfaces cleaned and painted with rust inhibiting primer and 29

manufacturers standard paint. 30

C. Buses: 31 1. Material: Tin-plated aluminum or silver-plated copper. 32 2. Main horizontal bus: 33

a. Fully rated and continuous over length of switchboard with all three (3) phases 34 arranged in the same vertical plane. 35

b. Sufficient size to limit temperature rise to 65 DegC over average air temperature 36 outside the enclosure of 40 DegC. 37

3. Neutral bus: Fully rated and continuous over length of switchboard. 38 4. Ground bus: 1/4 x 2 IN copper, continuous over length of switchboard and solidly 39

grounded to each vertical section structure. 40 5. Bus joints connected using through bolts and conical spring-type washers for maximum 41

conductivity. 42

D. Overcurrent and Short Circuit Protective Devices: 43 1. Main overcurrent protective device: 44

a. Individually mounted insulated case circuit breaker with Arc Flash maintenance 45 provision. 46

2. Feeder overcurrent protective devices: 47 a. Group mounted molded case circuit breaker. 48

3. See Specification Section 16490 for overcurrent and short circuit protective device 49 requirements. 50

Page 381: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SWITCHBOARDS 16440 - 3

4. Factory installed. 1 5. Means to padlock all main and feeder devices in the open position. 2

E. Surge Protective Device: Integrally mounted, see Specification Section 16491. 3

F. Accessories: 4 1. Arc flash maintenance key operated switch and indicating light on the front of the gear. 5

PART 3 - EXECUTION 6

3.1 INSTALLATION 7

A. Install switchboards in accordance with manufacturer's instructions. 8

B. Arrange switchboard as shown on the Drawings. 9

C. Indoor Locations: 10 1. NEMA 1 enclosure. 11 2. Install on concrete housekeeping pad, align front of switchboard with top edge of pad 12

chamfer and securely fasten to pad. 13

D. Miscellaneous: 14 1. Provide circuit protective devices and other associated equipment as indicated on the 15

Drawings. 16 2. All control wiring shall be neatly laced and have flexibility at hinge locations. 17

3.2 FIELD QUALITY CONTROL 18

A. Test the ground fault protection system as indicated in Specification Section 16490. 19

END OF SECTION 20

21

Page 382: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - SWITCHBOARDS 16440 - 4

1

Page 383: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PANELBOARDS 16441 - 1

2014/08/15 1

SECTION 16441 2

PANELBOARDS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Lighting and appliance panelboards. 7 2. Power distribution panelboards. 8

B. Related Specification Sections include but are not necessarily limited to: 9 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 10 2. Division 01 - General Requirements. 11 3. Section 16010 - Electrical: Basic Requirements. 12 4. Section 16490 - Overcurrent and Short Circuit Protective Devices. 13 5. Section 16491 - Low Voltage Surge Protective Devices (SPD). 14

1.2 QUALITY ASSURANCE 15

A. Referenced Standards: 16 1. National Electrical Manufacturers Association (NEMA): 17

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 18 b. PB 1, Panelboards. 19

2. National Fire Protection Association (NFPA): 20 a. 70, National Electrical Code (NEC). 21

3. Underwriters Laboratories, Inc. (UL): 22 a. 50, Enclosures for Electrical Equipment, Non-Environmental Considerations. 23 b. 67, Standard for Panelboards. 24

1.3 SUBMITTALS 25

A. Shop Drawings: 26 1. See Specification Section 01340 for requirements for the mechanics and administration of 27

the submittal process. 28 2. Product technical data. 29

a. Provide submittal data for all products specified in PART 2 of this Specification 30 Section. 31

b. See Specification Section 16010 for additional requirements. 32 3. Fabrication and/or layout drawings: 33

a. Panelboard layout with alphanumeric designation, branch circuit breakers size and type, 34 as indicated in the panelboard schedules. 35

B. Operation and Maintenance Manuals: 36 1. See Specification Section 01342 for requirements for: 37

a. The mechanics and administration of the submittal process. 38 b. The content of Operation and Maintenance Manuals. 39

2. Panelboard schedules with as-built conditions. 40

Page 384: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PANELBOARDS 16441 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Eaton. 5 2. General Electric Company. 6 3. Square D Company. 7 4. Siemens. 8

B. Submit request for substitution in accordance with Specification Section 01640. 9

2.2 MANUFACTURED UNITS 10

A. Standards: NEMA PB 1, NFPA 70, UL 50, UL 67. 11

B. Ratings: 12 1. Current, voltage, number of phases, number of wires as indicated on the Drawings. 13 2. Panelboards rated 240 Vac or less: 10,000 amp minimum short circuit rating or as indicated 14

in the schedule. 15 3. Panelboards rated 480 Vac: 14,000 amp minimum short circuit rating or as indicated in the 16

schedule. 17 4. Service Entrance Equipment rated when indicated on the Drawings. 18

C. Construction: 19 1. Interiors factory assembled and designed such that switching and protective devices can be 20

replaced without disturbing adjacent units and without removing the main bus connectors. 21 2. Multi-section panelboards: Feed-through or sub-feed lugs. 22 3. Main lugs: Solderless type approved for copper and aluminum wire. 23

D. Bus Bars: 24 1. Main bus bars: 25

a. Plated aluminum or copper sized to limit temperature rise to a maximum of 65 DegC 26 above an ambient of 40 DegC. 27

b. Drilled and tapped and arranged for sequence phasing of the branch circuit devices. 28 2. Ground bus and isolated ground bus, when indicated on the Drawings: Solderless 29

mechanical type connectors. 30 3. Neutral bus bars: Insulated 100 percent rated or 200 percent rated, when indicated on the 31

Drawings and with solderless mechanical type connectors. 32

E. Enclosure: 33 1. Boxes: Code gage galvanized steel, furnish without knockouts. 34 2. Trim assembly: Code gage steel finished with rust inhibited primer and manufacturers 35

standard paint inside and out. 36 3. Lighting and appliance panelboard: 37

a. Trims supplied with hinged door over all circuit breaker handles. 38 b. Trims for surface mounted panelboards, same size as box. 39 c. Trims for flush mounted panelboards, overlap the box by 3/4 IN on all sides. 40 d. Doors lockable with corrosion resistant chrome-plated combination lock and catch, all 41

locks keyed alike. 42 e. Nominal 20 IN wide and 5-3/4 IN deep with gutter space in accordance with NFPA 70. 43 f. Clear plastic cover for directory card mounted on the inside of each door. 44 g. NEMA 3R or NEMA 12 rated: Door gasketed. 45

4. Power distribution panelboard: 46 a. Trims cover all live parts with switching device handles accessible. 47 b. Less than or equal to 12 IN deep with gutter space in accordance with NFPA 70. 48 c. Clear plastic cover for directory card mounted front of enclosure. 49

Page 385: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PANELBOARDS 16441 - 3

d. NEMA 3R or NEMA 12 rated: Doors gasketed and lockable with corrosion resistant 1 chrome-plated combination lock and catch, all locks keyed alike. 2

F. Overcurrent and Short Circuit Protective Devices: 3 1. Main overcurrent protective device: 4

a. Molded case circuit breaker. 5 2. Branch overcurrent protective devices: 6

a. Mounted molded case circuit breaker. 7 3. See Section 16490 for overcurrent and short circuit protective device requirements. 8 4. Factory installed. 9

PART 3 - EXECUTION 10

3.1 INSTALLATION 11

A. Install as indicated on the Drawings, in accordance with the NFPA 70, and in accordance with 12 manufacturer's instructions. 13

B. Support panelboard enclosures from wall studs or modular channels support structure, per 14 Specification Section 16010. 15

C. Provide NEMA 1, NEMA 3R or NEMA 12 rated enclosure as indicated on the Drawings. 16

D. Provide each panelboard with a typed directory: 17 1. Identify all circuit locations in each panelboard with the load type and location served. 18 2. Mechanical equipment shall be identified by Owner-furnished designation if different than 19

designation indicated on the Drawings. 20 3. Room names and numbers shall be final building room names and numbers as identified by 21

the Owner if different than designation indicated on the Drawings. 22

END OF SECTION 23

24

Page 386: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - PANELBOARDS 16441 - 4

1

Page 387: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MOTOR CONTROL EQUIPMENT 16442 - 1

2014/08/15 1

SECTION 16442 2

MOTOR CONTROL EQUIPMENT 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Separately mounted motor starters (including those supplied with equipment). 7 2. Manual motor starters. 8

B. Related Specification Sections include but are not necessarily limited to: 9 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 10 2. Division 01 - General Requirements. 11 3. Section 16010 - Electrical: Basic Requirements. 12 4. Section 16080 - Acceptance Testing. 13 5. Section 16265 - Variable Frequency Drives - Low Voltage. 14 6. Section 16490 - Overcurrent and Short Circuit Protective Devices. 15 7. Section 16493 - Control Equipment Accessories. 16

1.2 QUALITY ASSURANCE 17

A. Referenced Standards: 18 1. International Electrotechnical Commission (IEC). 19 2. National Electrical Manufacturers Association (NEMA): 20

a. 250, Enclosures for Electrical Equipment (1000 Volt Maximum). 21 b. ICS 2, Controllers, Contactors and Overload Relays Rated 600 V. 22

3. Underwriters Laboratories, Inc. (UL): 23 a. 508, Standard for Industrial Control Equipment. 24

B. Miscellaneous: 25 1. Verify motor horsepower loads, other equipment loads, and controls from approved shop 26

drawings and notify Engineer of any discrepancies. 27 2. Verify the required instrumentation and control wiring for a complete system and notify 28

Engineer of any discrepancies. 29

1.3 SUBMITTALS 30

A. Shop Drawings: 31 1. See Specification Section 01340 for requirements for the mechanics and administration of 32

the submittal process. 33 2. Product technical data: 34

a. Provide submittal data for all products specified in PART 2 of this Specification 35 Section. 36

b. See Specification Section 16010 for additional requirements. 37 3. Fabrication and/or layout Drawings: 38

a. Separately mounted combination starters: 39 1) Unit ladder logic wiring for each unit depicting electrical wiring and identification 40

of terminals where field devices or remote control signals are to be terminated as 41 indicated on the Drawings and/or loop descriptions. 42

B. Operation and Maintenance Manuals: 43 1. See Specification Section 01342 for requirements for: 44

a. The mechanics and administration of the submittal process. 45 b. The content of Operation and Maintenance Manuals. 46

Page 388: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MOTOR CONTROL EQUIPMENT 16442 - 2

c. Fabrication and/or layout drawings updated with as-built conditions. 1

PART 2 - PRODUCTS 2

2.1 ACCEPTABLE MANUFACTURERS 3

A. Subject to compliance with the Contract Documents, the following manufacturers are 4 acceptable: 5 1. Allen-Bradley. 6 2. Eaton. 7 3. General Electric Company. 8 4. Square D Company. 9 5. Siemens. 10

B. Submit request for substitution in accordance with Specification Section 01640. 11

2.2 SEPARATELY MOUNTED COMBINATION STARTERS 12

A. Standards: 13 1. NEMA 250, NEMA ICS 2. 14 2. UL 508. 15

B. Enclosure: 16 1. NEMA 12 rated: 17

a. Body and cover: Sheet steel finished with rust inhibiting primer and manufacturer's 18 standard paint inside and out. 19

b. No knockouts, external mounting flanges, hinged and gasketed door. 20

C. Operating Handle: 21 1. With the door closed the handle mechanism allows complete ON/OFF control of the unit 22

disconnect and clear indication of the disconnect status. 23 2. Circuit breaker and MCP operators includes a separate TRIPPED position. 24 3. Mechanical interlock to prevent to prevent the opening of the door when the disconnect is in 25

the ON position with a defeater mechanism for use by authorized personnel. 26 4. Mechanical interlock to prevent the placement of the disconnect in the ON position with the 27

door open with a defeater mechanism for use by authorized personnel. 28 5. Padlockable in the OFF position. 29

D. External mounted overload relay pushbutton. 30

E. Control Devices: 31 1. Provide control devices as indicated on the Drawings per Specification Section 16493. 32 2. The following devices are the minimum required unless otherwise indicated on the 33

Drawings: 34 a. Three-position switch (HAND-OFF-AUTO). 35 b. Red ON indicator light. 36 c. Non-resetable run time meter. 37

3. Devices will be accessible with the door closed. 38

F. Control Power Transformer: 39 1. 120V secondary. 40 2. Fused on primary and secondary side. 41 3. Sized for 140 percent of required load. 42

G. Fault Current Withstand Rating: Equal to the rating of the electrical gear from which it is fed. 43

H. Motor Starters: See requirements within this Specification Section. 44

I. Disconnect Switch, Overcurrent and Short Circuit Protective Devices: 45 1. Motor circuit protector. 46

Page 389: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MOTOR CONTROL EQUIPMENT 16442 - 3

2. See Specification Section 16490 for overcurrent and short circuit protective device 1 requirements. 2

3. Factory installed. 3

2.3 MOTOR STARTERS 4

A. Standards: 5 1. NEMA ICS 2. 6 2. UL 508. 7

B. Full Voltage Non-Reversing (FVNR) Magnetic Starters: 8 1. NEMA full size rated contactor, size one minimum. 9

a. NEMA half sizes and IEC contactors are not permitted. 10 2. Double-break silver alloy contacts. 11 3. Overload relays: 12

a. Ambient insensitive, adjustable solid state type with phase loss protection, phase 13 imbalance protection and manual reset. 14

4. Interlock and auxiliary contacts, wired to terminal blocks: 15 a. Holding circuit contact, normally open. 16 b. Overload alarm contact, normally open. 17 c. Normally open auxiliary contact, for remote run status. 18 d. Additional field replaceable auxiliary contacts as required per the Sequence of 19

Operation. 20 e. Two (2) additional normally open spare field replaceable auxiliary contacts. 21

C. Variable Frequency Drives: See Specification Section 16265. 22

2.4 MANUAL MOTOR STARTERS 23

A. Standards: 24 1. NEMA 250, NEMA ICS 2. 25 2. UL 508. 26

B. Quick-make, quick-break toggle mechanism that is lockable in the OFF position. 27

C. Types: 28 1. Horsepower rated, for ON/OFF control and thermal overload protection. 29

a. Switch to clearly indicate ON, OFF, and TRIPPED position. 30

D. Voltage and current ratings and number of poles as required for the connected motor. 31

E. Enclosures: 32 1. NEMA 1 rated: 33

a. Galvanized steel or steel finished with rust inhibiting primer and manufacturer's 34 standard paint inside and out. 35

b. With or without concentric knockouts. 36

PART 3 - EXECUTION 37

3.1 INSTALLATION 38

A. Install as indicated on the Drawings and in accordance with manufacturer's recommendations 39 and instructions. 40

B. Mounting height for surface mounted equipment: See Specification Section 16010. 41

C. Overload Heaters: Size for actual motor full load current of the connected motor. 42

D. Combination and Manual Starter Enclosures: 43 1. Permitted uses of NEMA 1 enclosure: 44

a. Surface mounted in non-architecturally finished areas. 45

Page 390: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - MOTOR CONTROL EQUIPMENT 16442 - 4

2. Permitted uses of NEMA 12 enclosure: Surface mounted in areas designated as dry. 1

3.2 FIELD QUALITY CONTROL 2

A. Acceptance Testing: See Specification Section 16080. 3

END OF SECTION 4

Page 391: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - DRY-TYPE TRANSFORMERS 16460 - 1

2014/08/28 1

SECTION 16460 2

DRY-TYPE TRANSFORMERS 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Dry-type transformers, 1000 kVA and less. 7

B. Related Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 16010 - Electrical: Basic Requirements. 11 4. Section 16060 - Grounding. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 15

a. C57.12.01, Standard General Requirements for Dry-Type Distribution and Power 16 Transformers Including Those with Solid Cast and/or Resin-Encapsulated Windings. 17

b. C57.96, Guide for Loading Dry-Type Distribution and Power Transformers. 18 2. National Electrical Manufacturers Association (NEMA): 19

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 20 b. ST 20, Dry-Type Transformers for General Applications. 21 c. TP 1, Guide for Determining Energy Efficiency for Distribution Transformers. 22

3. Underwriters Laboratories, Inc. (UL): 23 a. 506, Standard for Safety Specialty Transformers. 24 b. 1561, Standard for Safety Dry-Type General Purpose and Power Transformers. 25

1.3 SUBMITTALS 26

A. Shop Drawings: 27 1. See Specification Section 01340 for requirements for the mechanics and administration of 28

the submittal process. 29 2. Product technical data: 30

a. Provide submittal data for all products specified in PART 2 of this Specification 31 Section. 32

b. See Specification Section 16010 for additional requirements. 33 3. Fabrication and/or layout drawings. 34

a. Nameplate drawing. 35 4. Certifications: 36

a. Sound level certifications. 37

B. Operation and Maintenance Manuals: 38 1. See Specification Section 01342 for requirements for: 39

a. The mechanics and administration of the submittal process. 40 b. The content of Operation and Maintenance Manuals. 41

Page 392: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - DRY-TYPE TRANSFORMERS 16460 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Eaton. 5 2. General Electric Company. 6 3. Square D Company. 7 4. Siemens. 8 5. Sola/Hevi-Duty. 9

B. Submit request for substitution in accordance with Specification Section 01640. 10

2.2 GENERAL PURPOSE DRY-TYPE TRANSFORMERS 11

A. Ventilated or non-ventilated, air cooled, two (2) winding type. 12

B. Cores: 13 1. High grade, non-aging silicon steel with high magnetic permeability, and low hysteresis and 14

eddy current losses. 15 2. Magnetic flux densities are to be kept well below the saturation point. 16

C. Coils: Continuous wound with electrical grade aluminum. 17

D. Non-ventilated Units: 18 1. Core and coil assembly encapsulated in a proportioned mixture of resin and aggregate to 19

provide a moisture proof, shock resistant seal. 20 2. Totally enclosed, NEMA 3R, steel enclosure finished with a weather-resistant enamel. 21

E. Ventilated Units: 22 1. Core and coils assembly impregnated with non-hygroscopic, thermosetting varnish and 23

cured to reduce hot spots and seal out moisture and completely isolated from the enclosure 24 by means of vibration dampening pads. 25

2. Drip proof, NEMA 1, steel enclosure finished with a weather-resistant enamel and 26 ventilation openings protected from falling dirt. 27

F. Furnish Taps for Transformers as follows: 28 1. 1 PH, 3 to 25 kVA: Two (2) 5 percent FCBN. 29 2. 3 PH, 15 kVA and above: Two (2) 2.5 percent FCAN and four (4) 2.5 percent FCBN. 30

G. Sound Levels: 31 1. Manufacturer shall guarantee not to exceed the following: 32

a. 10 to 50 kVA: 45 dB. 33

H. Efficiency: 34 1. Ventilated, 15 kVA and larger: Energy efficient meeting NEMA TP 1 requirements. 35 2. Non-ventilated: Standard efficiency. 36

I. Insulating Material (600 V and below): 37 1. 15 kVA and above units: 220 DegC insulation system with a 150 DegC rise. 38

J. Ratings: 60 Hz, voltage, KVA and phase, as indicated on the Drawings. 39

K. Finish: Rust inhibited primer and manufacturers standard paint inside and out. 40

L. Standards: IEEE C57.96, NEMA ST 20, NEMA TP 1, UL 506, UL 1561. 41

Page 393: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - DRY-TYPE TRANSFORMERS 16460 - 3

PART 3 - EXECUTION 1

3.1 INSTALLATION 2

A. Install products in accordance with manufacturer's instructions. 3

B. Indoor Locations: 4 1. Provide ventilated type for 15 kVA units and above. 5 2. Provide non-ventilated type for 9 kVA units and below and were indicated on the Drawings. 6 3. Mount 15 kVA units and above on chamfered 4 IN high concrete housekeeping pad or from 7

wall and/or ceiling, at 7 FT above finished floor, using equipment support brackets per 8 Section 16010. 9

4. Provide rubber vibrations isolation pads. 10

C. Outdoor Locations: 11 1. Provide non-ventilated type. 12 2. Mount ventilated type with weather shields on a concrete pad. 13 3. Mount non-ventilated type on concrete pad for units weighting greater than 400 LBS and 14

mount units weighting less than 400 LBS on channel support structure per detail on 15 Drawings. 16

D. Enclosures: Painted steel in all areas except stainless steel in highly corrosive areas. 17

E. Ground in accordance with Section 16060. 18

END OF SECTION 19

20

Page 394: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - DRY-TYPE TRANSFORMERS 16460 - 4

1

Page 395: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES 16490 - 1

2014/08/28 1

SECTION 16490 2

OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Low voltage circuit breakers. 7

B. Related Specification Sections include but are not necessarily limited to: 8 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 9 2. Division 01 - General Requirements. 10 3. Section 16010 - Electrical: Basic Requirements. 11 4. Section 16080 - Acceptance Testing. 12

1.2 QUALITY ASSURANCE 13

A. Referenced Standards: 14 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 15

a. C37.13, Standard for Low-Voltage AC Power Circuit Breakers Used in Enclosures. 16 b. C37.16, Low-Voltage Power Circuit Breakers and AC Power Circuit Protectors - 17

Preferred Ratings, Related Requirements, and Application Recommendations. 18 2. National Electrical Manufacturers Association (NEMA): 19

a. AB 1, Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker 20 Enclosures. (Equivalent to UL 489) 21

3. National Fire Protection Association (NFPA): 22 a. 70, National Electrical Code (NEC). 23

4. Underwriters Laboratories, Inc. (UL): 24 a. 489, Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches, and 25

Circuit-Breaker Enclosures. 26 b. 943, Standard for Safety for Ground-Fault Circuit-Interrupters. 27 c. 1066, Standard for Low-Voltage AC and DC Power Circuit Breakers Used in 28

Enclosures. 29

1.3 SUBMITTALS 30

A. Shop Drawings: 31 1. See Specification Section 01340 for requirements for the mechanics and administration of 32

the submittal process. 33 2. Product technical data including: 34

a. Provide submittal data for all products specified in PART 2 of this Specification 35 Section. 36

b. See Specification Section 16010 for additional requirements. 37

B. Operation and Maintenance Manuals: 38 1. See Specification Section 01342 for requirements for: 39

a. The mechanics and administration of the submittal process. 40 b. The content of Operation and Maintenance Manuals. 41

C. Informational Submittals: 42 1. See Specification Section 01340 for requirements for the mechanics and administration of 43

the submittal process. 44 2. Ground fault protection system test reports signed by the projects supervising electrical 45

foreman. 46

Page 396: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES 16490 - 2

3. Reports: 1 a. As-left condition of all circuit breakers that have adjustable settings. 2

PART 2 - PRODUCTS 3

2.1 ACCEPTABLE MANUFACTURERS 4

A. Subject to compliance with the Contract Documents, the following manufacturers are 5 acceptable: 6 1. Circuit breakers: 7

a. Eaton. 8 b. General Electric Company. 9 c. Square D Company. 10 d. Siemens. 11

B. Submit request for substitution in accordance with Specification Section 01640. 12

2.2 CIRCUIT BREAKERS 13

A. Molded Case Type: 14 1. General: 15

a. Standards: NEMA AB 1, UL 489. 16 b. Unit construction. 17 c. Over-center, toggle handle operated. 18 d. Quick-make, quick-break, independent of toggle handle operation. 19 e. Manual and automatic operation. 20 f. All poles open and close simultaneously. 21 g. Three (3) position handle: On, off and tripped. 22 h. Molded-in ON and OFF markings on breaker cover. 23 i. One-, two- or three-pole as indicated on the Drawings. 24 j. Current and interrupting ratings as indicated on the Drawings. 25 k. Bolt on type. 26

2. Thermal magnetic type: 27 a. Inverse time overload and instantaneous short circuit protection by means of a thermal 28

magnetic element. 29 b. Frame size 150 amp and below: 30

1) Non-interchangeable, non-adjustable thermal magnetic trip units. 31 c. Frame sizes 225 to 400 amp (trip settings less than 400A): 32

1) Interchangeable and adjustable instantaneous thermal magnetic trip units. 33 d. Ground Fault Circuit Interrupter (GFCI) Listed: 34

1) Standard: UL 943. 35 2) One- or two-pole as indicated on the Drawings. 36 3) Class A ground fault circuit. 37 4) Trip on 5 mA ground fault (4-6 mA range). 38

3. Solid state trip type: 39 a. Inverse time overload, instantaneous short circuit and ground fault protection by means 40

of a solid state trip element, associated current monitors and flux shunt trip mechanism. 41 b. Frame size 400 amp to 1200 amp (trip settings between 400 and 1200A): 42

1) Standard rating. 43 2) Interchangeable current sensor or rating plug. 44 3) Adjustable long time pick-up setting. 45

a) Adjustable from 50 to 100 percent of the current sensor or rating plug. 46 4) Adjustable short time pick-up setting. 47 5) Adjustable instantaneous pick-up. 48 6) Fixed ground fault pick-up, when indicated on the Drawings. 49

Page 397: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES 16490 - 3

c. Frame size 1600 amp and above: 1 1) 100 percent rated. 2 2) Interchangeable current sensor or rating plug. 3 3) Adjustable long time pick-up setting. 4

a) Adjustable from 50 to 100 percent of the current sensor or rating plug. 5 4) Adjustable long time delay setting. 6 5) Adjustable short time pick-up setting. 7 6) Adjustable instantaneous pick-up setting. 8 7) Adjustable ground fault pick-up setting, when indicated on the Drawings. 9 8) Adjustable ground fault delay setting, when indicated on the Drawings. 10

4. Motor circuit protector: 11 a. Adjustable instantaneous short circuit protection by means of a magnetic or solid state 12

trip element. 13 b. Sized for the connected motor. 14

B. Insulated Case Type: 15 1. Inverse time overload, instantaneous short circuit and ground fault protection by means of a 16

solid state trip element, associated current monitors and two-step stored energy trip 17 mechanism. 18

2. Standards: NEMA AB 1, UL 489. 19 3. 100 percent rated. 20 4. Manually operated (MO) unless electrically operated (EO) is indicated on the Drawings. 21 5. Electrically operated breakers: 22

a. 120 Vac operators. 23 b. Close/open pushbuttons. 24 c. Red and green indicators to indicated breaker position. 25 d. AC source: Control power transformer internal to the switchgear. 26

6. Motor driven operator for charging mechanism with open, close and charge push button. 27 7. Current and interrupting ratings as indicated on the Drawings. 28 8. Frame size 400 amp and above: 29

a. Interchangeable current sensor or rating plug: 30 b. Adjustable long time pick-up setting. 31

1) Adjustable from 50 to 100 percent of the current sensor or rating plug. 32 c. Adjustable long time delay setting. 33 d. Adjustable short time pick-up setting. 34 e. Adjustable instantaneous pick-up setting. 35 f. Adjustable ground fault pick-up setting, when indicated on the Drawings. 36 g. Adjustable ground fault delay setting, when indicated on the Drawings. 37

PART 3 - EXECUTION 38

3.1 INSTALLATION 39

A. Current and interrupting ratings as indicated on the Drawings. 40

B. Series rated systems not acceptable. 41

C. Devices shall be ambient temperature compensated. 42

D. Circuit Breakers: 43 1. Molded case circuit breakers shall incorporate the following, unless indicated otherwise on 44

the Drawings: 45 a. Frame sizes 400 amp and less with trip setting less than 400A shall be thermal magnetic 46

type. 47 b. Frame sizes 800 amp and larger shall be solid state trip type. 48 c. Frame sizes 1000 amp and above shall include integral ground fault protection, when 49

indicated on the Drawings. 50

Page 398: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - OVERCURRENT AND SHORT CIRCUIT PROTECTIVE DEVICES 16490 - 4

d. Motor circuit protectors sized for the connected motor. 1 2. Insulated case circuit breakers shall incorporate the following, unless indicated otherwise on 2

the Drawings: 3 a. Set current sensor or rating plugs long time pick-up setting so that the indicated trip 4

level is near the 75 percent trip point. 5 b. Frame sizes 1000 amp and above shall include integral ground fault protection, when 6

indicated on the Drawings. 7

3.2 FIELD QUALITY CONTROL 8

A. Adjustable Circuit Breakers: 9 1. Set all circuit breaker adjustable taps as defined on the Drawings, except adjust motor 10

circuit protectors per the motor nameplate and NFPA 70 requirements. 11

B. Ground Fault Protection System: 12 1. Single source system: 13

a. Main breaker using the residual sensing method system. 14 b. Main and feeder breakers: Utilize four (4) individual current sensors; the phase sensors 15

are integral to the circuit breaker and the neutral sensor is external to the circuit breaker. 16

C. Testing: 17 1. Acceptance testing: See Specification Section 16080. 18

END OF SECTION 19

Page 399: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16491 - 1

2014/08/28 1

SECTION 16491 2

LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Type 3 SPD - Medium exposure locations (switchboard, panelboard and motor control 7

center), integrally mounted. 8 2. Type 4 SPD - Medium exposure location (switchboard, panelboard and motor control 9

center), externally mounted. 10

B. Related Sections include but are not necessarily limited to: 11 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 12 2. Division 01 - General Requirements. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 16

a. C62.41, Recommended Practice for Surge Voltages in Low-Voltage AC Power 17 Circuits. 18

b. C62.41.1, Guide on the Surge Environment in Low-Voltage (1000V and Less) AC 19 Power Circuits. 20

c. C62.41.2, Recommended Practice on Characterization of Surges in Low-Voltage (1000 21 V and Less) AC Power Circuits. 22

d. C62.45, Recommended Practice on Surge Testing For Equipment Connected to Low-23 Voltage (1000V and Less) AC Power Circuits. 24

2. National Electrical Manufacturers Association (NEMA): 25 a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 26 b. LS 1, Low Voltage Surge Protective Devices. 27

3. National Fire Protection Association (NFPA): 28 a. 70, National Electrical Code (NEC). 29

4. Underwriters Laboratories, Inc. (UL): 30 a. 1283, Standard for Electromagnetic Interference Filters. 31 b. 1449, Standard for Safety Transient Voltage Surge Suppressors. 32

B. Qualifications: 33 1. Provide devices from a manufacturer who has been regularly engaged in the development, 34

design, testing, listing and manufacturing of SPDs of the types and ratings required for a 35 period of 10 years or more and whose products have been in satisfactory use in similar 36 service. 37 a. Upon request, suppliers or manufacturers shall provide a list of not less than three (3) 38

customer references showing satisfactory operation. 39

1.3 DEFINITIONS 40

A. Clamping Voltage: 41 1. The applied surge shall be induced at the 90 degree phase angle of the applied system 42

frequency voltage. 43 2. The voltage measured at the end of the 6 IN output leads of the SPD and from the zero 44

voltage reference to the peak of the surge. 45

Page 400: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16491 - 2

B. Let-Through Voltage: 1 1. The applied surge shall be induced at the 90 degree phase angle of the applied system 2

frequency voltage. 3 2. The voltage measured at the end of the 6 IN output leads of the SPD and from the system 4

peak voltage to the peak of the surge. 5

C. Maximum Continuous Operating Voltage (MCOV): The maximum steady state voltage at 6 which the SPD device can operate and meet its specification within its rated temperature. 7

D. Maximum Surge Current: 8 1. The maximum 8 x 20 microsecond surge current pulse the SPD device is capable of 9

surviving on a single-impulse basis without suffering either performance degradation or 10 more than 10 percent deviation of clamping voltage at a specified surge current. 11

2. Listed by mode, since number and type of components in any SPD may very by mode. 12

E. MCC: Motor Control Center. 13

F. Protection Modes: This parameter identifies the modes for which the SPD has directly 14 connected protection elements, i.e., line-to-neutral (L-N), line-to-line (L-L), line-to-ground (L-15 G), neutral-to-ground (N-G). 16

G. Surge Current per Phase: 17 1. The per phase rating is the total surge current capacity connected to a given phase 18

conductor. 19 a. For example, a wye system surge current per phase would equal L-N plus L-G; a delta 20

system surge current per phase would equal L-L plus L-G. 21 b. The N-G mode is not included in the per phase calculation. 22

H. System Peak Voltage: The electrical equipment supply voltage sine wave peak (i.e., for a 23 480/277 V system the L-L peak voltage is 679V and the L-N peak voltage is 392 V). 24

1.4 SUBMITTALS 25

A. Shop Drawings: 26 1. See Specification Section 01340 for requirements for the mechanics and administration of 27

the submittal process. 28 2. Product technical data including: 29

a. Manufacturer's qualifications. 30 b. Standard catalog cut sheet. 31 c. Electrical and mechanical drawing showing unit dimensions, weights, mounting 32

provisions, connection details and layout diagram of the unit. 33 d. Testing procedures and testing equipment data. 34 e. Create a Product Data Sheet for each different model number of SPD provided (i.e., 35

Model XYZ with disconnect and Model XYZ without disconnect, each require a 36 Product Data Sheet). 37 1) Data in the Product Data Sheet heading: 38

a) SPD Type Number per PART 2 of the Specification. 39 b) Manufacturer’s Name. 40 c) Product model number. 41

2) Data in the Product Data Sheet body: 42 a) Column one: Specified value/feature of every paragraph of PART 2 of the 43

Specification. 44 b) Column two: Manufacturer’s certified value confirming the product meets the 45

specified value/feature. 46 c) Name of the nationally recognized testing laboratory that preformed the tests. 47 d) Warranty information. 48

3) Data in the Product Data Sheet closing: 49 a) Signature of the manufacturer’s official (printed and signed). 50 b) Title of the official. 51

Page 401: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16491 - 3

4) Date of signature. 1

B. Operation and Maintenance Manuals: 2 1. See Specification Section 01342 for requirements for: 3

a. The mechanics and administration of submittal process. 4 b. The content of the Operation and Maintenance Manuals. 5

2. Warranty. 6

1.5 WARRANTY 7

A. Minimum of a five (5) year Warranty from date of shipment against failure when installed in 8 compliance with applicable national/local electrical codes and the manufacturer's installation, 9 operation and maintenance instructions. 10

PART 2 - PRODUCTS 11

2.1 GENERAL 12

A. Standards: IEEE C62.41.1, IEEE C62.41.2, IEEE C62.45, NEMA LS 1, MIL-STD 220B, 13 UL 1283, UL 1449. 14

2.2 TYPE 3 SPD 15

A. Product: 16 1. Integrally mounted in a switchboard, panelboards or motor control centers. 17 2. Hybrid solid state high performance suppression system. 18

a. Do not use gas tubes, spark gaps or other components in suppression system which 19 might short or crowbar the line resulting in interruption of normal power flow to 20 connected loads. 21

3. Do not connect multiple SPD modules in series to achieve the specified performance. 22 4. Designed for parallel connection. 23 5. Field connection: Use mechanical or compression lugs for each phase, neutral and ground 24

that will accept bus bar or #10 through #1/0 conductors. 25 6. Device monitor: 26

a. Long-life, solid state, externally visible indicators and Form C contact(s) that monitor 27 the on-line status of each mode of the units suppression filter system or power loss in 28 any of the phases. 29

b. A fuse status only monitor system is not acceptable. 30

B. Operating Voltage: The nominal unit operating voltage and configuration as indicated on the 31 Drawings. 32

C. Modes of Protection: All modes. 33 1. Three phase (delta): L-L, L-G. 34 2. Three phase (wye): L-N, L-L, L-G and N-G. 35 3. Single phase (2 pole): L-L, L-N, L-G and N-G. 36 4. Single phase: L-N, L-G and N-G. 37

D. Maximum Continuous Operating Voltage: Less than 130 percent of system peak voltage. 38

E. Operating Frequency: 45 to 65 Hz. 39

F. Short Circuit Rating: Equal to or greater than rating of equipment SPD is connected to. 40

G. Maximum Surge Current: 160,000 A per phase, 80,000 A per mode minimum. 41

H. Minimum Repetitive Surge Current Capacity: 4000 IEEE C High or B combination waveform 42 impulses with no degradation of more than 10 percent deviation of the clamping voltage. 43

Page 402: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16491 - 4

I. SPD Protection: 1 1. Integral unit level and/or component level overcurrent fuses and sustained overvoltage 2

thermal cutout device. 3 2. An IEEE B combination wave shall not cause the fuse to open and render the SPD 4

inoperable. 5

J. Maximum Clamping Voltages: Dynamic test at the 90 degree phase angle including 6 IN lead 6 length and measured from the zero voltage reference: 7

8

System Voltage Test

Mode IEEE C62.41

UL 1449 B Comb. Wave B3 Ring Wave L-L < 250 V L-N < 150 V

L-L 1000 V 700 V 800 V L-N 600 V 400 V 500 V L-G 800 V 550 V 600 V N-G 800 V 550 V 600 V

L-L > 250 V L-N > 150 V

L-L 2000 V 1400 V 1800 V L-N 1150 V 800 V 1000 V L-G 1550 V 1000 V 1200 V N-G 1550 V 1000 V 1200 V

9

K. EMI-RFI Noise Rejection: Attenuation greater than 30 dB for frequencies between 100 kHz and 10 100 MHz. 11

2.3 TYPE 4 SPD 12

A. Product: 13 1. SPD tag number or electrical equipment tag number SPD is connected to CTC cabinet. 14 2. Externally mounted next to Switchgear, Switchboards or Motor Control Centers. 15 3. Hybrid solid state high performance suppression system. 16

a. Do not use gas tubes, spark gaps or other suppression system components which might 17 short or crowbar the line resulting in interruption of normal power flow to connected 18 loads. 19

4. Do not connect multiple SPD modules in series to achieve the specified performance. 20 5. Designed for parallel connection. 21 6. Enclosure: 22

a. Metallic NEMA 4 or 12 for interior locations. 23 b. Metallic NEMA 4 or 4X for exterior locations. 24

7. Field connection: 25 a. Mechanical or compression lugs for each phase, neutral and ground that will accept #10 26

through #1/0 conductors. 27 8. Device monitor: 28

a. Long-life, solid state, externally visible indicators and Form C dry contact(s) that 29 monitor the on-line status of each mode of the units suppression filter system or power 30 loss in any of the phase. 31

b. A fuse status only monitor system is not acceptable. 32 9. Accessories (when specifically specified): Unit mounted disconnect switch. 33

B. Operating Voltage: Nominal unit operating voltage and configuration as indicated on the 34 Drawings. 35

C. Modes of Protection: All modes. 36 1. Three phase (delta): L-L, L-G. 37 2. Three phase (wye): L-N, L-L, L-G and N-G. 38 3. Single phase (2 pole): L-L, L-N, L-G and N-G. 39 4. Single phase: L-N, L-G and N-G. 40

D. Maximum Continuous Operating Voltage: Less than 130 percent of system peak voltage. 41

Page 403: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16491 - 5

E. Operating Frequency: 45 to 65 Hz. 1

F. Maximum Surge Current: 120,000 A per phase, 60,000 A per mode minimum. 2

G. Minimum Repetitive Surge Current Capacity: 4000 IEEE C High or B combination waveform 3 impulses with no degradation of more than 10 percent deviation of the clamping voltage. 4

H. SPD Protection: 5 1. Integral unit level and/or component level overcurrent fuses and sustained overvoltage 6

thermal cutout device. 7 2. An IEEE B combination wave shall not cause the fuse to open and render the SPD 8

inoperable. 9

I. Maximum Clamping Voltages: Dynamic test at the 90 degree phase angle including 6 IN lead 10 length and measured from the zero voltage reference: 11

J. EMI-RFI Noise Rejection: Attenuation greater than 30 dB for frequencies between 100 kHz and 12 100 MHz. 13

2.4 SOURCE QUALITY CONTROL 14

A. SPD approvals and ratings shall be obtained by manufacturers from nationally recognized testing 15 laboratories. 16

B. The SPD are to be tested as a complete SPD system including: 17 1. Integral unit level and/or component level fusing. 18 2. Neutral and ground shall not be bonded during testing. 19 3. 6 IN lead lengths. 20 4. Integral disconnect switch when provided. 21

C. The “as installed” SPD system including the manufacturers recommended circuit breaker, the 22 SPD is connected to, will not open when tested with a IEEE C3 combination waveform. 23

D. Tests to be performed in accordance with IEEE C62.45: 24 1. Clamping voltage performance testing using IEEE C62.41 Category waveforms. 25 2. Single pulse surge current capacity test. 26 3. Repetitive surge current capacity testing. 27 4. Spectrum analysis for EMI-RFI noise rejection. 28

PART 3 - EXECUTION 29

3.1 INSTALLATION 30

A. Install products in accordance with manufacturer's instructions. 31

B. Type 3 SPD: 32 1. Connected in parallel to the equipment. 33 2. Install in dedicated electrical equipment compartment, bucket or panelboard box at the 34

factory before shipment. 35 3. Provide leads that are as short and straight as possible. 36 4. Maximum lead length: 12 IN. 37 5. Minimum lead size: #2 stranded AWG or bus bar. 38 6. Connect leads to the equipment to be protected by one (1) of the following means: 39

a. Through a circuit breaker or molded case switch mounted in the equipment. 40 b. Use manufacturer recommended circuit breaker size. 41 c. Circuit breaker or switch to be operable from the equipment exterior or from behind a 42

hinged door. 43

C. Type 4 SPD: 44 1. Mounting options: 45

a. Nipple connection directly to the equipment to be protected. 46

Page 404: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - LOW VOLTAGE SURGE PROTECTION DEVICES (SPD) 16491 - 6

2. Install leads as short and straight as possible. 1 3. Maximum lead length: 5 FT. 2 4. Minimum lead size: 3

a. #2 stranded AWG. 4 5. When conduit connection is used, provide a minimum of four (4) twists per foot in the lead 5

conductors and install in NFPA 70 sized conduit. 6 6. Connect leads to the equipment to be protected by one (1) of the following means: 7

a. Through a circuit breaker or molded case switch mounted in the equipment. 8 1) Use manufacturer recommended circuit breaker size. 9

b. Directly to the protected equipment bus, when SPD has integral disconnect switch. 10

END OF SECTION 11

Page 405: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL EQUIPMENT ACCESSORIES 16493 - 1

2014/08/28 1

SECTION 16493 2

CONTROL EQUIPMENT ACCESSORIES 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Operator control devices (selector switches, pushbuttons, indicator lights, etc.). 7 2. Control devices (timers, relays, contactors, etc.). 8 3. Control panels and operator stations. 9

B. Related Sections include but are not necessarily limited to: 10 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 11 2. Division 01 - General Requirements. 12 3. Section 16010 - Electrical: Basic Requirements. 13

1.2 QUALITY ASSURANCE 14

A. Referenced Standards: 15 1. National Electrical Manufacturers Association (NEMA): 16

a. 250, Enclosures for Electrical Equipment (1000 Volts Maximum). 17 b. ICS 2, Industrial Control and System Controllers, Contactors and Overload Relays 18

Rated 600 Volts. 19 2. Underwriters Laboratories, Inc. (UL): 20

a. 508, Standard for Safety Industrial Control Equipment. 21 b. 508A, Standard for Safety Industrial Control Panels. 22

B. Miscellaneous: 23 1. Supplier of Industrial Control Panels shall build control panel under the provisions of 24

UL 508A. 25 a. Entire assembly shall be affixed with a UL 508A label "Listed Enclosed Industrial 26

Control Panel" prior to shipment to the jobsite. 27

1.3 SUBMITTALS 28

A. Shop Drawings: 29 1. See Specification Section 01340 for requirements for the mechanics and administration of 30

the submittal process. 31 2. Product technical data: 32

a. Provide submittal data for all products specified in PART 2 of this Specification: 33 b. Control panel bill of material. 34 c. See Section 16010 for additional requirements. 35

3. Fabrication and/or layout drawings. 36 a. Control panel interior and exterior layout. 37 b. Control panel wiring diagrams. 38

B. Operation and Maintenance Manuals: 39 1. See Specification Section 01342 for requirements for: 40

a. The mechanics and administration of submittal process. 41 b. The content of Operation and Maintenance Manuals. 42

Page 406: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL EQUIPMENT ACCESSORIES 16493 - 2

PART 2 - PRODUCTS 1

2.1 ACCEPTABLE MANUFACTURERS 2

A. Subject to compliance with the Contract Documents, the following manufacturers are 3 acceptable: 4 1. Pilot devices and relays: 5

a. Idec. 6 b. Potter & Brumfield. 7 c. ATC Diversified Electronics. 8

2. Contactors: 9 a. Automatic Switch Company (ASCO). 10 b. Eaton. 11 c. General Electric Company. 12 d. Square D Company. 13 e. Siemens. 14 f. Allen Bradley. 15

3. Photocells: 16 a. Grasslin. 17 b. Tork. 18 c. Intermatic. 19 d. Paragon. 20

4. Terminal blocks: 21 a. Phoenix Contact. 22 b. Allen-Bradley. 23

5. Enclosures: 24 a. Hoffman Engineering Co. 25 b. Wiegmann. 26 c. Eaton B-Line. 27 d. Adalet. 28 e. Stahlin. 29

B. Submit request for substitution in accordance with Specification Section 01640. 30

2.2 PILOT DEVICES 31

A. General Requirements: 32 1. Standards: NEMA ICS 2, UL 508. 33 2. Heavy-duty NEMA 4/13 watertight/oiltight. 34 3. Mounting hole: 30.5 mm. 35 4. Contact blocks: 10 amp, NEMA A600 rated, number as required to fulfill functions shown 36

or specified. 37 5. Legend plate marked as indicated on Drawings or specified. 38

B. Selector Switches: 39 1. Two, three- or four-position rotary switch as required to fulfill functions shown or specified. 40 2. Maintained contact type. 41 3. Knob or lever type operators. 42

C. Pushbuttons: 43 1. Non-illuminated type: 44

a. Protective boot. 45 b. Momentary contact. 46 c. Standard flush and mushroom operators. 47 d. Red colored buttons for START or ON and green color for STOP or OFF. 48 e. Emergency stop pushbuttons: Mushroom head operator and maintained contact. 49

Page 407: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL EQUIPMENT ACCESSORIES 16493 - 3

D. Indicating Lights: 1 1. Allowing replacement of bulb without removal from control panel. 2 2. Lamp: LED, 120 V or 24 V as required. 3 3. Full voltage type. 4 4. Push-to-test indicating lights. 5 5. Glass lens. 6 6. Color code lights as follows: 7

a. Green: OFF or stopped valve open. 8 b. Amber: Standby; auto mode; ready. 9 c. Red: ON or running; valve closed. 10

2.3 RELAYS 11

A. General Requirements: 12 1. Standards: NEMA ICS 2, UL 508. 13

B. Control Relays: 14 1. General purpose (ice cube) type: 15

a. Plug-in housing. 16 b. Clear polycarbonate dust cover with clip fastener. 17 c. Coil voltage: 120 Vac or as required. 18 d. Contacts: 19

1) 10 amp continuous. 20 2) Silver cadmium oxide. 21 3) Minimum of 3 SPDT contacts. 22

e. Sockets: DIN rail mounted. 23 f. Internal neon or LED indicator is lit when coil is energized. 24 g. Manual operator switch. 25

2. Industrial type: 26 a. Coil voltage: 120 Vac or as required. 27 b. Contacts: 28

1) 10 amp, NEMA A600 rated. 29 2) Double break, silver alloy. 30 3) Convertible from normally open to normally closed or vice versa, without 31

removing any wiring. 32 4) Expandable from 2 poles to 12 poles. 33

c. Provide contacts for all required control plus two spares. 34

C. Time Delay Relays: 35 1. General purpose type: 36

a. Timing modes: On and Off delay, interval, one shot and repeat cycle. 37 b. Plug-in housing. 38 c. Polycarbonate dust cover with clip fastener. 39 d. Coil voltage: 120 Vac or as required. 40 e. Contacts: 41

1) 10 amp continuous. 42 2) Silver cadmium oxide. 43 3) Two normally open and two normally closed DPDT contacts. 44 4) Instantaneous contact as well as timed. 45

f. Sockets: DIN rail mounted. 46 g. External timing adjustment knob. 47 h. Timing ranges: 0.05 seconds to 16.65 HRS. 48 i. Repeat accuracy: +1 percent. 49

2. Solid State industrial type: 50 a. Timing modes: On and Off delay and repeat cycle. 51 b. Industrial housing. 52 c. Coil voltage: 120 Vac or as required. 53

Page 408: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL EQUIPMENT ACCESSORIES 16493 - 4

d. Contacts: 1 1) 5 amp, NEMA B150 rated. 2 2) Silver alloy. 3 3) Convertible On Delay and Off Delay contacts. 4 4) Normally open and normally closed timed contacts or interposing relays as 5

required. 6 5) Normally open and normally closed instantaneous contacts or interposing relays as 7

required. 8 e. Furnish with "on" and "timing out" indicators. 9 f. External timing adjustment knob. 10 g. Timing ranges: 0.05 seconds to 10 HRS. 11 h. Repeat accuracy: +1 percent. 12

2.4 CONTACTORS 13

A. General Requirements: 14 1. Standards: NEMA ICS 2, UL 508. 15

B. Definite Purpose: 16 1. Coil voltage: 120 Vac or as required. 17 2. Contacts: Totally enclosed, double-break silver-cadmium-oxide. 18 3. Resistive load and horsepower rated. 19 4. Number of poles, continuous ampere rating and voltage, as indicated on Drawings or as 20

specified. 21 5. Auxiliary contacts, as indicated on Drawings or as specified. 22

2.5 PHOTOCELLS AND TIME CLOCKS 23

A. Photocells: 24 1. Weatherproof enclosure. 25 2. Adjustable turn-on range, initially set at 1.0 footcandles. 26

a. Turn-off level approximately three times turn-on. 27 3. Provide time delay device to eliminate nuisance switching. 28 4. Voltage, amperage and/or wattage ratings as required for the application. 29

2.6 MISCELLANEOUS DEVICES 30

A. Run Time Meters: 31 1. Six-digit wheels including a 1/10 digit. 32 2. Non-reset type. 33 3. Time range in hours. 34 4. Automatic recycle at zero. 35 5. Accuracy: 1 percent. 36 6. Sealed against dirt and moisture. 37 7. Tamperproof. 38

2.7 TERMINATION EQUIPMENT 39

A. General Requirements: 40 1. Modular type with screw compression clamp. 41 2. Screws: Stainless steel. 42 3. Current bar: Nickel-plated copper alloy. 43 4. Thermoplastic insulation rated for -40 to +90 DegC. 44 5. Wire insertion area: Funnel-shaped to guide all conductor strands into terminal. 45 6. End sections and end stops at each end of terminal strip. 46 7. Machine-printed terminal markers on both sides of block. 47 8. Spacing: 6 mm. 48 9. Wire size: 22-12 AWG. 49 10. Rated voltage: 600 V. 50

Page 409: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL EQUIPMENT ACCESSORIES 16493 - 5

11. DIN rail mounting. 1

B. Standard-type block: 2 1. Rated current: 30 A. 3 2. Color: Gray body. 4

C. Bladed-type disconnect block: 5 1. Terminal block with knife blade disconnect which connects or isolated the two sides of the 6

block. 7 2. Rated current: 10 A. 8 3. Color: 9

a. Panel control voltage leaves enclosure - normal: Gray body, orange switch. 10 b. Foreign voltage entering enclosure: Orange body, orange switch. 11

D. Grounded-type block: 12 1. Electrically grounded to mounting rail. 13 2. Terminal ground wires and analog cable shields. 14 3. Color: Green and yellow body. 15

E. Fuse Holders: 16 1. Blocks can be ganged for multi-pole operation. 17 2. Spacing: 9.1 mm. 18 3. Wire size: 30-12 AWG. 19 4. Rated voltage: 300 V. 20 5. Rated current: 12 A. 21 6. Fuse size: 1/4 x 1-1/4. 22 7. Blown fuse indication. 23 8. DIN rail mounting. 24

2.8 ENCLOSURES 25

A. Control Panels: 26 1. NEMA 4 rated: 27

a. Seams continuously welded and ground smooth. 28 b. No knockouts. 29 c. External mounting flanges. 30 d. Hinged or non-hinged cover held closed with stainless steel screws and clamps. 31 e. Cover with oil resistant gasket. 32

2. NEMA 4X rated: 33 a. Body and cover: 14 GA Type 304 or 316 stainless steel. 34 b. Seams continuously welded and ground smooth. 35 c. No knockouts. 36 d. External mounting flanges. 37 e. Hinged door and stainless steel screws and clamps. 38 f. Door with oil-resistant gasket. 39

3. NEMA 12 enclosure: 40 a. Body and cover: 14 GA steel finished with rust inhibiting primer and manufacturers 41

standard paint inside and out. 42 b. No knockouts. 43 c. External mounting flanges. 44 d. Non-hinged stainless steel cover held closed with captivated cover screws threaded into 45

sealed wells or hinged cover held closed with stainless steel screws and clamps. 46 e. Flat door with oil resistant gasket. 47

4. Control panel miscellaneous accessories: 48 a. Back plane mounting panels: Steel with white enamel finish or Type 304 stainless 49

steel. 50 b. Interiors shall be white or light gray in color. 51

Page 410: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - CONTROL EQUIPMENT ACCESSORIES 16493 - 6

c. Wire management duct: 1 1) Bodies: PVC with side holes. 2 2) Cover: PVC snap-on. 3 3) Size as required. 4

d. Rigid handles for covers larger than 9 SF or heavier than 25 LBS. 5 e. Split covers when heavier than 25 LBS. 6 f. Floor stand kits made of same material as the enclosure. 7 g. Weldnuts for mounting optional panels and terminal kits. 8 h. Ground bonding jumper from door, across hinge, to enclosure body. 9

5. Standards: NEMA 250, UL 508. 10

B. Operator Control Stations: 11 1. NEMA 4X rated: 12

a. Type 304 or 316 stainless steel body. 13 b. Gasketed Type 304 or 316 stainless steel cover. 14 c. Number of device mounting holes as required. 15

PART 3 - EXECUTION 16

3.1 INSTALLATION 17

A. Install as indicated and in accordance with manufacturer's recommendations and instructions. 18

B. Control Panels: 19 1. Size as required to mount the equipment. 20 2. Permitted uses of NEMA 4 enclosure: 21

a. Surface mounted in areas designated as wet. 22 3. Permitted uses of NEMA 4X enclosure: 23

a. Surface mounted in areas designated as wet. 24 4. Permitted uses of NEMA 12 enclosure: 25

a. Surface mounted in areas designated as dry and/or dusty architecturally or non-26 architecturally finished areas. 27

C. Operator Control Stations: 28 1. Permitted uses of NEMA 4/13 enclosure: 29

a. Surface mounted in areas designated as dry and/or dusty architecturally or non-30 architecturally finished areas and wet. 31

3.2 FIELD QUALITY CONTROL 32

A. See Section 16010. 33

END OF SECTION 34

Page 411: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INTERIOR AND EXTERIOR LIGHTING 16500 - 1

2014/08/28 1

SECTION 16500 2

INTERIOR AND EXTERIOR LIGHTING 3

PART 1 - GENERAL 4

1.1 SUMMARY 5

A. Section Includes: 6 1. Material and installation requirements for: 7

a. Interior building lighting fixtures. 8 b. Exterior building and site lighting fixtures. 9 c. Lamps. 10 d. Ballasts. 11 e. Lighting control. 12

B. Related Specification Sections include but are not necessarily limited to: 13 1. Division 00 - Bidding Requirements, Contract Forms, and Conditions of the Contract. 14 2. Division 01 - General Requirements. 15 3. Section 16010 - Electrical: Basic Requirements. 16 4. Section 16120 - Wire and Cable - 600 Volt and Below. 17

1.2 QUALITY ASSURANCE 18

A. Referenced Standards: 19 1. American National Standards Institute (ANSI). 20 2. Certified Ballast Manufacturers (CBM). 21 3. Federal Communications Commission (FCC): 22

a. Code of Federal Regulations (CFR), 47 CFR 18, Industrial, Scientific and Medical 23 Equipment. 24

4. National Electrical Manufacturers Association (NEMA): 25 a. 250, Enclosures for Electrical Equipment (1000Volts Maximum). 26

5. National Electrical Manufacturers Association/American National Standards Institute 27 (NEMA/ANSI): 28 a. C82.1, Lamp Ballasts - Line Frequency Fluorescent Lamp Ballast. 29 b. C82.4, Ballasts for High-Intensity Discharge and Low-Pressure Sodium (LPS) Lamps 30

(Multiple-Supply Type). 31 c. C82.11, High-Frequency Fluorescent Lamp Ballasts - Supplements. 32

6. National Fire Protection Association (NFPA): 33 a. 70, National Electrical Code (NEC). 34 b. 101, Life Safety Code. 35

7. Underwriters Laboratories, Inc. (UL): 36 a. 924, Standard for Emergency Lighting and Power Equipment. 37 b. 935, Standard for Fluorescent-Lamp Ballasts. 38 c. 1029, Standard for High-Intensity-Discharge Lamp Ballasts. 39 d. 1598, Luminaires. 40

1.3 SUBMITTALS 41

A. Shop Drawings: 42 1. See Specification Section 01340 for requirements for the mechanics and administration of 43

the submittal process. 44 2. Product technical data: 45

a. Provide submittal data for all products specified in PART 2 of this Specification 46 Section. 47

Page 412: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INTERIOR AND EXTERIOR LIGHTING 16500 - 2

b. Identify fixtures by Fixture Schedule number. 1 c. Fixture data sheet including: 2

1) Photometric performance data including candlepower distribution and coefficient 3 of utilization (CU) table. 4

d. See Specification Section 16010 for additional requirements. 5

PART 2 - PRODUCTS 6

2.1 ACCEPTABLE MANUFACTURERS 7

A. Subject to compliance with the Contract Documents, the following manufacturers are 8 acceptable: 9 1. Lighting fixtures: See Fixture Schedule. 10 2. Lamps: 11

a. Osram/Sylvania. 12 b. General Electric. 13 c. Philips. 14 d. Venture. 15

3. Ballasts: Fixture manufacturer's standard. 16 4. Emergency ballasts: Bodine. 17 5. Emergency transfer devices: Bodine. 18

B. Submit request for substitution in accordance with Specification Section 01640. 19

2.2 GENERAL REQUIREMENTS 20

A. All lighting fixtures and electrical components: 21 1. UL labeled. 22 2. Fixtures complete with lamps and ballasts. 23 3. Rated for area classification as indicated on the Drawings. 24

B. Provide standard plaster frame for all recessed lighting fixtures installed in plaster walls or 25 ceilings. 26 1. Design, finish and fabricate material to preclude possibility of rust stain in plaster. 27

C. No live parts normally exposed to contact. 28

D. When intended for use in wet areas: Mark fixtures "Suitable for wet locations." 29

E. When intended for use in damp areas: Mark fixtures "Suitable for damp locations" or "Suitable 30 for wet locations." 31

2.3 LIGHT FIXTURES 32

A. Fluorescent: 33 1. UL 1598. 34 2. Finish: 35

a. Manufacturer's standard polyester, acrylic enamel or epoxy powder coating applied 36 after fabrication. 37

b. Manufacturer's standard color or special color specified in Fixture Schedule. 38 3. Prewired and provided with lamps that are properly mated to the ballast operating 39

characteristics. 40

B. High Intensity Discharge: 41 1. UL 1598. 42 2. Finish: 43

a. Manufacturer's standard polyester, acrylic enamel or epoxy powder coating applied 44 after fabrication. 45

b. Manufacturer's standard color or special color specified in Fixture Schedule. 46

Page 413: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INTERIOR AND EXTERIOR LIGHTING 16500 - 3

3. Prewired and provided with lamps that are properly mated to the ballast operating 1 characteristics. 2

4. Provided with safety chain. 3

C. Exit Signs and Emergency Lighting Units: 4 1. UL 924, NFPA 101. 5

2.4 LAMPS 6

A. Fluorescent: 7 1. T8 (265 mA) instant or rapid-start medium bipin lamps. 8

a. Correlated color temperature of 3500 degrees Kelvin. 9 b. Minimum color rendering index (CRI) of 70. 10 c. Minimum initial lumen ratings for each lamp type shall be: 11

1) 1300 lumens for 24 IN, 17 watt F17T8 lamp. 12 2) 2025 lumens for 36 IN, 25 watt F25T8 lamp. 13 3) 2800 lumens for 48 IN, 32 watt F32T8 lamp. 14 4) 5700 lumens for 96 IN, 59 watt F96T8 lamp. 15

2. T5 instant or rapid-start 4 pin (2G11 base) compact fluorescent lamps. 16 a. Correlated color temperature of 4100 degrees Kelvin. 17 b. Minimum color rendering index (CRI) of 80. 18 c. Minimum initial lumen ratings for each lamp type shall be: 19

1) 1250 lumens for 10.5 IN, 18 watt F18BX lamp. 20 2) 1800 lumens for 12.8 IN, 24 or 27 watt F27BX lamp. 21 3) 2850 lumens for 16.5 IN, 36 or 39 watt F39BX lamp. 22 4) 3150 lumens for 22.5 IN, 39 watt F39BX lamp. 23

3. T4 twin-tube, quad-tube, and/or triple twin-tube compact fluorescent lamps. 24 a. Correlated color temperature of 4100 degrees Kelvin. 25 b. Minimum color rendering index (CRI) of 80. 26 c. Minimum initial lumen ratings for rapid-start 4-pin triple twin-tube lamps with a 27

GX24q-2 or GX24q-3 base shall be: 28 1) 1120 lumens for 4.6 IN, 18 watt CF18TTT lamp. 29 2) 1610 lumens for 5.2 IN, 26 watt CF26TTT lamp. 30 3) 2200 lumens for 5.8 IN, 32 watt CF32TTT lamp. 31 4) 3200 lumens for 6.3 IN, 42 watt CF42TTT lamp. 32

B. High Intensity Discharge (HID) Lamps: 33 1. Metal halide lamps: 34

a. Metal halide lamps shall be pulse-start type. 35 1) If used in an open luminaire, the lamp shall be rated for use in an open fixture and 36

incorporate a protective arc tube shroud design. 37 b. Clear lamps: 38

1) Correlated color temperature of 4000 degrees Kelvin. 39 2) Minimum color rendering index (CRI) of 65. 40

c. Minimum initial lumen ratings for metal halide lamps with a medium base in a vertical 41 position shall be: 42 1) 14250 lumens for 150 watt, ED-17 (ANSI M102) clear lamp. 43 2) 17500 lumens for 175 watt, ED-17 (ANSI M137) clear lamp. 44

d. Minimum initial lumen ratings for metal halide lamps with a mogul base in a vertical 45 position shall be: 46 1) 14250 lumens for 150 watt, ED-28 (ANSI M102) clear lamp. 47 2) 17500 lumens for 175 watt, ED-28 (ANSI M137) clear lamp. 48

2.5 BALLASTS 49

A. Fluorescent Electromagnetic Ballasts: 50 1. UL 935. 51 2. High-efficiency energy saving electromagnetic core and coil design. 52

Page 414: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INTERIOR AND EXTERIOR LIGHTING 16500 - 4

3. CBM certification for full light output. 1 4. Operate lamps at a frequency of 60 Hz. 2 5. Power factor: Greater than 90 percent. 3 6. Input current with Total Harmonic Distortion (THD) of less than 32 percent. 4 7. Lamp current crest factor: Less than 1.7, in accordance with lamp manufacturer's 5

recommendations and NEMA/ANSI C82.1. 6 8. Ballast factor: Greater than the following per NEMA/ANSI C82.1: 7

a. 0.925 for rapid start 265 mA (T8) and 430 mA (T12) ballasts. 8 9. Audible noise rating: Greater than or equal to the following: 9

a. Class A for rapid start 265 mA (T8) and 430 mA (T12) ballasts. 10 10. Coil temperature not to exceed 65 DegC (150 DegF) temperature rise over 40 DegC (105 11

DegF) ambient. 12 a. Maximum case temperature not to exceed 90 DegC (195 DegF). 13

11. Meet the requirements of the FCC 47 CFR 18, for non-consumer equipment for EMI and 14 RFI. 15

12. Meet all applicable ANSI and IEEE standards regarding harmonic distortion and transient 16 protection such as IEEE C62.41, Cat. A, for transient protection. 17

13. UL listed, Class P. 18 14. Fully encapsulated (potted) to ensure maximum thermal and structural integrity. 19 15. Contain no polychlorinated biphenyls (PCB's). 20

B. Fluorescent High Frequency Electronic Ballasts: 21 1. UL 935. 22 2. "High Frequency" electronic operating lamps at a frequency of 20 KHz or higher without 23

visible flicker. 24 3. Power factor: Greater than 90 percent. 25 4. Input current total harmonic distortion (THD) of less than 20 percent. 26 5. Lamp current crest factor: Less than 1.7, in accordance with lamp manufacturer's 27

recommendations and NEMA/ANSI C82.11. 28 6. Instant start with lamps wired in parallel. 29 7. Support a sustained short to ground or open circuit of any output leads without damage to 30

the ballast. 31 8. Ballast Factor: Greater than 0.85 per NEMA/ANSI C82.11. 32 9. Audible noise rating: Class A or better. 33 10. Operation in ambient temperatures up to 40 DegC (105 DegF) without damage. 34 11. Light output to remain constant for a line voltage fluctuation of +5 percent. 35 12. Meet the requirements of the FCC 47 CFR 18, for non-consumer equipment for EMI and 36

RFI. 37 13. Meet NEMA/ANSI C82.11 standards regarding harmonic distortion. 38 14. Meet IEEE C62.41 Cat. A for transient protection. 39 15. Comply with all applicable state and federal efficiency standards. 40 16. UL listed, Class P. 41 17. Contain no Polychlorinated Biphenyls (PCB's). 42

C. Fluorescent Emergency Ballasts: 43 1. UL 924, NFPA 101. 44 2. High temperature, 24 Watt-hour, maintenance-free nickel cadmium battery with charger. 45 3. Charging indicator light (LED) to monitor the charger and battery. 46 4. Double-pole test switch. 47 5. Light one (1) lamp for 90 minutes in 1, 2 and 3-lamp fixtures. 48 6. Dual input voltage (120/277V), 4 Watts input. 49 7. Compatible with the install lamp type. 50 8. Initial lumen output: 975 to 1400. 51 9. Contain no Polychlorinated Biphenyls (PCB's). 52

D. High Intensity Discharge Ballasts: 53 1. NEMA/ANSI C82.4, UL 1029. 54

Page 415: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INTERIOR AND EXTERIOR LIGHTING 16500 - 5

2. Metal halide: 1 a. Input voltage variation: +10 percent. 2 b. Maximum lamp regulation spread: 20 percent. 3 c. Minimum power factor: 90 percent. 4 d. Starting current: Not greater than operating current. 5 e. Maximum input voltage dip: 40 percent. 6 f. Crest factor: 1.5 to 1.8. 7 g. Types: 8

1) Lead-type regulators: Constant wattage autotransformer (CWA) and pulse start. 9 2) Lag-type regulators: Magnetic regulator and pulse start. 10

h. Contain no Polychlorinated Biphenyls (PCB's). 11 3. Ballasts for interior use: 12

a. Encased and potted type. 13 b. Audible noise rating of B or better. 14 c. Built-in automatic resetting thermal protection switch. 15

4. Ballasts for exterior use: 16 a. Starting temperature: -20 DegF. 17

2.6 MAINTENANCE MATERIALS 18

A. Furnish a minimum of 2 or 10 percent of total of each type and wattage of lamps, whichever is 19 greater. 20

B. Furnish a minimum of 10 percent of total of each type and amperage of fuses for fixtures 21 indicated to be fused. 22

C. Spare parts are to be stored in a box clearly labeled as to its contents. 23

PART 3 - EXECUTION 24

3.1 INSTALLATION 25

A. Coordinate fixture types with ceiling construction. 26 1. Provide mounting hardware for the ceiling system in which the fixture is to be installed. 27

B. Provide mounting brackets and/or structural mounting support for wall-mounted fixtures. 28 1. Do not support fixture from conduit system. 29 2. When fixtures are supported from outlet boxes, install per NFPA 70. 30 3. Supports for fixtures mounted on exterior walls shall not be attached to exterior face of the 31

wall. 32

C. Provide pendant HID fixtures with swivel hangers which will allow fixture to swing in any 33 direction but will not permit stem to rotate. 34 1. Provide hangers with enclosure rating (NEMA 1, 4, or 7) equal to enclosure requirements of 35

area in which they are installed. 36 2. Swivel hangers for fixtures in mechanical equipment areas: Shock absorbing type. 37 3. Secure HID fixtures with safety chain. 38

D. Pendant mounted, open, industrial fluorescent fixtures: 39 1. Not in continuous rows, shall be supported by conduit or by approved chains: 40

a. Hardwired to ceiling mounted junction box. 41

E. Mount lighting fixtures at heights indicated in Specification Section 16010 or per fixture 42 schedule or as indicted on the Drawings. 43

F. Install exterior fixtures so that water can not enter or accumulate in the wiring compartment. 44

G. Ground fixtures and ballasts. 45

Page 416: City of Yankton, SD

135-223788-003 City of Yankton, SD 2014 Water Treatment Plant Improvements, Horizontal Collector Well - INTERIOR AND EXTERIOR LIGHTING 16500 - 6

3.2 ADJUST AND CLEAN 1

A. See Specification Section 01710. 2

B. Replace all inoperable lamps with new lamps prior to final acceptance. 3

C. Aim all emergency lighting units, so that, the path of egress is illuminated. 4

END OF SECTION 5