cleanfill 4gvf overfill prevention device en 13616 · 2019. 11. 25. · produt non-contractual...
TRANSCRIPT
-
PRODUCT
Non-contractual document 1/210/2019 39000117UK Ind H
CLEANFILL 4GVFOVERFILL PREVENTION DEVICE EN 13616
Overfill prevention devices
AVANTAGES
- The best high flow on the market for a shorter filling time
- Tubular system. No mechanism outside the cylindrical body
- Integrated vertical mechanism
- Very easy to fit or remove without having to moveout the manhole plate. Female 4” filling sleeve
- Fitted to manhole plate or profiling plate
- Durability of material
- Non-corrodible material
- Numerous fitting accessories for all types of situation
- Vapour tight device, totally vapour proof, allowing to separate the tank gas sky from the atmosphere
Combination of 2 valves to a balanced pressure and rapid re-opening.
Internal float for easy installation and maintenance.
Components designed for perfect sealing and corrosion protection.
The overfill Cleanfill 4’’ is a safety and environmental protection equipment
The patented design allows this limiter into place or remove it without détamponner the manhole plate of the tank
ATEX : INERIS 06ATEX0058 type CE examination certificateATEX marking II 1G c IIB T6Operating temperature: from -25°C to +60°C
KIWA BRL-K636/03
Fabrication Française
-
CONTACTTél. +33 5 57 80 80 80mail. [email protected]
44, avenue Lucien Victor Meunier
33530 Bassens - FranceFind our more
WWW.LAFON.FR
Non contractual documentation 2/2 10/2019 39000117UK Ind H
CLEANFILL 4GVFOVERFILL PREVENTION DEVICE EN 13616
TECHNICAL SPECIFICATIONS
- European EN 13616 standard compliant
- Suitable for direct gravity filling
- Products : hydrocarbons
- Maximum flow rate : 85 m3/h - 1,414 litres/minute
- Minimum flow rate : 3 m3/h - 50 litres/minute
- Maximum pressure : 2 bar
- Re-opening / flow delay : less than one minute
CLEANFILL 4GVF INSTALLATION
No external float Easy Maintenance
10024000 CLEANFILL 4GVF
Easy to install
Reference Description
EN 13616Overfill Prevention Device, for use in installations for the transport/distribution/storage of gas/fuel intended for the supply of building heating/cooling systems Type AEffectiveness of Overfill Prevention Devices — PassDurability of effectiveness against temperature, chemical attack, fatigue and cycling — Pass