Climate Variation Sensitivity in
Building Energy Simulation
Presented By:
Roger
Cladingboel
![Page 2: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/2.jpg)
Learning Objectives
• Understand the difference between RMY/TRY/TMY, AMY, and XMY climate files.
• Understand fundamentals differences in data collection and analysis methods for creating TMY & XMY files.
• Understand the impact climate change is having on EUI across multiple building types and multiple climate zones in the US and Canada.
![Page 3: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/3.jpg)
Acknowledgements
• Nathan Kegel, Megan Tosh, Liam Buckley, IES
• Shona O’Dea, DLR Group
• Craig Burton, PositivEnergy Practice
• Ralph Muehlheisen, Argonne National Lab
![Page 4: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/4.jpg)
Previous Research
• Loveland, J.E. & Brown, G.Z. (1989) Impacts of Climate Change on the Energy Performance of Buildings in the United States
• Crawley, D. (1998) Which weather data should you use for energy simulation of commercial buildings?
• Crawley, D. (2008) Building performance simulation: a tool for policymaking• Sustainable United Nations (2009), Buildings and Climate Change: Summary for
Decision Makers• Larsen, et. al. (2011) Green Building and Climate Resilience: Understanding
impacts and preparing for changing conditions• Bhandari, Srhestha, New (2012) Evaluation of weather data sets for building
simulation
![Page 5: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/5.jpg)
Why care about the Weather?
![Page 6: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/6.jpg)
Why Care About the Climate?
Annual average land surface temperature compared against a 1960-1990 average in °C
Source: http://data.giss.nasa.gov/gistemp/time_series.html
![Page 7: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/7.jpg)
Land and ocean global mean
Annual average land surface temperature compared against a 1960-1990 average in °C
Source: https://data.giss.nasa.gov/gistemp/graphs
![Page 8: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/8.jpg)
Annual average land surface temperature compared against a 1960-1990 average in °C
Source: http://data.giss.nasa.gov/gistemp/time_series.html
Atlanta
Brisbane
Melbourne
Cairns
![Page 9: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/9.jpg)
Annual average land surface temperature compared against a 1960-1990 average in °C
Source: http://data.giss.nasa.gov/gistemp/time_series.html
Atlanta
Miami
Fairbanks
Brisbane
Melbourne
Cairns
![Page 10: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/10.jpg)
Impacts of Climate Change on Building Design & Retrofit
• More frequent extremes– Temperatures, solar radiation, storms, floods, etc.
• Changes in “optimized” solutions– Reduced frequency of “typical” year; increased frequency of “extreme”
years• Cost to building owners
– Insurance premiums due to more extreme weather• Changes to payback calculations, ROI, IRR, etc.
– Passive strategies may be more/less effective• Changes to design recommendations
– Should “traditional local” architecture change?• Changes to Standard 90.1/189
– EUI changes to baseline models driven by climate change
![Page 11: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/11.jpg)
Fundamentals of Weather Data
Multi-SensorRadar Based
Reanalysis ModelsSatellite Based
MADIS – Quality Assured METAR (Ground
Observation Data)
Climate Forecast System Reanalysis –
NOAAs global re-analysis dataset
combining satellites, balloons, radar and
ground observations
![Page 12: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/12.jpg)
Combining CFSR and METARHourly
DataBlended METAR/CFSR data set
Gap Filled
Interpolated
![Page 13: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/13.jpg)
Creation of XMY Files
![Page 14: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/14.jpg)
Creation of TMY Files
TMY 3:
TMY 15:
TMY 7:
1985-2014
2000-2014
2008-2014
Each Variable is weighted
▪ Min/max Temperature: 1/20
▪ Avg Temperature: 2/20
▪ Min/max Dewpoint: 1/20
▪ Avg Dewpoint: 2/20
▪ Min/Max Windspeed: 2/20
▪ Avg GHI/DNI: 5/20
▪ Short Term and long term
weighted averages are
compared
▪ Output is one year of data with
these typical months
▪ Interfaces are smoothed with
Boxcar 5 method
![Page 15: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/15.jpg)
XMY vs. TMY
XMY Strengths:
• Ideal for modeling
building performance
in extreme conditions
• Aids in understanding
the range of a climate
over a number of years
TMY Strengths:
• Ideal for modeling
building performance in
historically typical
conditions
• Displays the most
typical weather patterns
for a range of years
XMY weaknesses:
• Would not optimize
model for historically
typical conditions
• Can be skewed by a
once in a generation
extreme year
TMY Weaknesses:
• Is not representative
of highly volatile
climates
• Does not capture
extreme conditions
![Page 16: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/16.jpg)
AMY Comparison
![Page 17: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/17.jpg)
TMY2 vs. TMY3 Comparison
![Page 18: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/18.jpg)
TMY3 Comparison
![Page 19: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/19.jpg)
![Page 20: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/20.jpg)
EU
IK
btu
/sf/yr
Option 1
90.1-2004U=.46 SHGC=.26
Option 2U=.30 SHGC=.38
Option 3
MN 2000 CodeU=.40 SHGC=.70
Option 4U=.21 SHGC=.37
Previous Work
![Page 21: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/21.jpg)
ASHRAE Climate Zones
![Page 22: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/22.jpg)
![Page 23: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/23.jpg)
Other weather sources:
• Meteonorm – software approach, stochastic and interpolation weather file creation from global monthly data.– Climate change scenarios 3No. IPCC– Extreme years P10, P90 etc
• Local XMY (Extreme Weather Year files) creation on request – Exemplary Energy etc.
• Weathershift – online algorithmic approach converting existing EPW files.
![Page 24: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/24.jpg)
Weathershift service:
• This tool uses data from global climate change modeling to produce EPW weather files adjusted for changing climate conditions. Cost to building owners
• The projected data can be viewed for three future time periods based on the emission scenario selected to the left.Passive strategies may be more/less effective
• The RCP’s (Representative Concentration Pathways) are greenhouse gas emission scenarios for the 21st century that result in the CO2 equivalent atmospheric concentrations
• Weathershift adjusts weatherfiles for future climate conditions based on RCP 4.5 (moderately aggressive mitigation) and RCP 8.5 (business as usual)
![Page 25: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/25.jpg)
GHG Concentrations / Emission Scenarios
RCP 8.5 – Business As Usual, RCP 4.5 more typical
![Page 26: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/26.jpg)
Predicted temperature increase scenarios, 10/50/90th percentiles default
• Typical city RCP 8.5 2090 prediction
![Page 27: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/27.jpg)
Sydney EPW - weathershifted
![Page 28: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/28.jpg)
Sydney EPW - weathershifted
Default EPW
2050 RCP 8.5 90th
Percentile
![Page 29: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/29.jpg)
The Research Project
• Used geometry from DOE Reference Buildings• Used 90.1-2007 PRM Space-by-Space baseline• 16 Reference Building Types• 16 Climate Zones• 8 Climate Data Sets per Climate Zone
– 5 TMY (or CWEC)– 3 XMY
• 2,048 Simulations
![Page 30: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/30.jpg)
Parametric Tool
Features:• Grouping can vary studies i.e:
• weather variable x7 (then)• extract variable x3 (then)• flow variable x3
• Total of 13 simulations
• Or variables can be ‘Combined’ then the variables that are defined as ‘Link’ will run as follows:
• weather variable x1 • (then for that weather) extract variable x3 • (then for that weather) flow variable x3
• repeat for each weather variable
• Total of 42 simulations
![Page 31: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/31.jpg)
Reference Buildings
![Page 32: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/32.jpg)
Locations Used
• 1A – Miami, FL• 2A – Houston, TX• 2B – Phoenix, AZ• 3A – Atlanta, GA• 3B – Las Vegas, NV• 3C – San Francisco, CA• 4A – Baltimore, MD• 4B – Albuquerque, NM• 4C – Portland, OR• 5A – Chicago, IL• 5B – Boulder, CO• 5C – Vancouver, BC• 6A – Minneapolis, MN• 6B – Helena, MT• 7 – Duluth, MN• 8 – Fairbanks, AK
![Page 33: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/33.jpg)
![Page 34: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/34.jpg)
Method
1. Selected Location2. Created Geometry/Zones3. Assigned constructions
1. ASHRAE 90.1-2007 baseline for new construction4. Assigned internal gains/schedules
1. ASHRAE 90.1-2007 Space-by-Space Method5. Created HVAC systems
1. ASHRAE Baseline Systems as appropriate per 90.1-2007 PRM6. Assigned Zones to HVAC systems7. Sized HVAC systems (auto-sized)
1. Design-day sizing using ASHRAE Heat Balance Method8. Ran Energy Simulations
1. Parametric runs - varied climate data set1. TMY2 (or CWEC), TMY3 (DOE), TMY3 (WA), TMY(7), TMY(15), XMY(MAX), XMY(MIN), XMY (MIN-MAX)
![Page 35: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/35.jpg)
Results
• Over 1 TB of data generated from the 2,048 simulations (used fully detailed results)– Max simulation time (12 minutes – Hospital)– Hardware used: i7 laptop, 1 TB HD, 12 GB RAM
(purchased in 2013)– Software used: IES <VE> 2014 Feature Pack 1
• Every building type shows significant EUI (Energy Use Intensity) variance based on varying the weather data
![Page 36: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/36.jpg)
Medium Office
![Page 37: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/37.jpg)
Hospital
![Page 38: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/38.jpg)
Secondary School
![Page 39: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/39.jpg)
Small Hotel
![Page 40: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/40.jpg)
Strip Mall
![Page 41: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/41.jpg)
Full Service Restaurant
![Page 42: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/42.jpg)
Warehouse
![Page 43: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/43.jpg)
Conclusions• TMY2 and TMY3 data is not appropriate for making future
decisions (aka design decisions) for all building types• XMY file types likely give better understanding of EUI, energy end-
use, and other building performance metrics when considering climate change, but…
• XMY files on their own are likely insufficient to understand future “typical” climates
• Multiple climate files are needed to understand the broader impacts of building performance over time in the face of rapid climate change
![Page 44: Climate Variation Sensitivity in Building Energy Simulation · 2017-11-19 · –Max simulation time (12 minutes –Hospital) –Hardware used: i7 laptop, 1 TB HD, 12 GB RAM (purchased](https://reader033.vdocument.in/reader033/viewer/2022050210/5f5ce7494893a134ab600e9a/html5/thumbnails/44.jpg)
What can you do?
• Consider accounting for climate change in energy simulation (and by extension) your design process and actual building performance:
• www.betterenergymodels.org