clinic ahu 105-116 latest
TRANSCRIPT
-
7/30/2019 Clinic AHU 105-116 Latest
1/27
S.No. Description W HArea a=HW
(m)
Air Flow
Q (L/s)
Equivalent
Length(m)
Velocity =Q/a
(m/s)
1 Supply air jetdiffuser
0 0 0 0 0.00 0.00
2 Straight Duct 400 400 0.16 410 0.9 2.56
3 VCD 400 400 0 0 0 0.00
4Supply air jet
diffuser0 0 0 0 0.00 0.00
5 Straight Duct 400 400 0.16 410 0.6 2.56
6 VCD 400 400 0 0 0 0.00
7 Straight Duct 800 600 0.48 1640 8.6 3.42
800 400 0.32 1640 5.13
600 400 0.24 1640 6.83
9 Straight Duct 1000 600 0.6 2460 2.8 4.10
900 600 0.54 2460 4.56
800 600 0.48 2460 5.13
11 Straight Duct 900 600 0.54 3280 3 6.07
900 600 0.54 3280 6.07
800 600 0.48 3280 6.83
13 Straight Duct 1000 600 0.6 4100 3.8 6.83
1000 800 0.8 4100 5.13
1000 600 0.6 4100 6.83
15 Straight Duct 1000 800 0.8 4920 3.3 6.15
1100 800 0.88 4920 5.59
1000 800 0.8 4920 6.15
17 Straight Duct 1100 800 0.88 5740 4.1 6.52
1200 800 0.96 5740 5.98
1100 800 0.88 5740 6.52
Reducer
EXTERNAL STATIC PRESS
CSB-ML-45-94-HAH-01 (MECH
8 Reducer
10 Reducer
18 Reducer
12 Reducer
14 Reducer
16
-
7/30/2019 Clinic AHU 105-116 Latest
2/27
19 Straight Duct 1200 800 0.96 6560 2.4 6.83
1400 800 1.12 6560 5.86
1200 800 0.96 6560 6.83
21 Straight Duct 1400 800 1.12 7380 2.6 6.59
1500 800 1.2 7380 6.15
1400 800 1.12 7380 6.59
23 Straight Duct 1500 800 1.2 8200 3 6.83
24 Elbow 1500 800 1.2 8200 1.08 6.83
25 Straight Duct 1500 800 1.2 8200 5.8 6.83
26 Elbow 1500 800 1.2 8200 1.08 6.83
27 Straight Duct 1500 800 1.2 8200 0.5 6.83
1600 800 1.28 8200 6.41
1500 800 1.2 8200 6.83
29 Straight Duct 1600 800 1.28 9020 2.1 7.05
1800 800 1.44 9020 6.26
1600 800 1.28 9020 7.05
31 Straight Duct 1800 800 1.44 10652 4.2 7.40
32 SILENCER 1800 800 1.44 10652 7.40
33 VCD 1800 800 0 10652 0 0.00
34 Straight Duct 1800 800 1.44 10652 2.6 7.40
35 Fire damper 1800 800 1.44 10652 7.40
36 Elbow 1800 800 1.44 10652 1.53 7.40
37 Straight Duct 1800 800 1.44 10652 1.8 7.40
38 Elbow 1800 800 1.44 10652 1.53 7.40
39 Straight Duct 1800 800 1.44 10652 1 7.40
40 Flexible conn. 1800 800 1.44 10652 0.2 7.397222222
Reducer
20 Reducer
Reducer28
Reducer30
22
-
7/30/2019 Clinic AHU 105-116 Latest
3/27
-
7/30/2019 Clinic AHU 105-116 Latest
4/27
Velocity
=Q/a (fpm)
hv=
(V/4005)nhv1 nhv2
n(hv2-
hv1)
Pressure
Drop(Pa/m)
Total
Pressure
Drop(Pa)
0.00 0.00 0.00 0.00 0 67.00
504.43 0.175 0.16
0 0 0 0 0 10.00
0.00 0.00 0.00 0.00 0 67.00
504.43 0.175 0.11
0 0 0 0 0 10.00
0.37 3.18
1008.86 0.063453201 0.0456863 0.0355338 8.88
1345.14 0.112805691 0.08122
0.38 1.06
896.76 0.050135863 0.0360978 0.0095885 2.40
1008.86 0.063453201 0.045686
0.35 1.05
1195.68 0.089130422 0.0641739 0.0170462 4.26
1345.14 0.112805691 0.08122
0.54 2.05
1008.86 0.063453201 0.0456863 0.0355338 8.88
1345.14 0.112805691 0.08122
0.34 1.12
1100.57 0.075514553 0.0543705 0.0114178 2.85
1210.63 0.09137261 0.065788
0.45 1.85
1177.00 0.086366857 0.0621841 0.0118201 2.96
1284.00 0.102783698 0.074004
RE CALCULATION
NICAL PLANT ROOM)
-
7/30/2019 Clinic AHU 105-116 Latest
5/27
0.37 0.89
1152.98 0.082877651 0.0530417 0.0191539 10.00
1345.14 0.112805691 0.072196 0.00
0.3 0.78
1210.63 0.09137261 0.0584785 0.0086524 2.16
1297.10 0.104892026 0.067131
0.36 1.08
0.36 0.39
0.36 2.09
0.36 0.39
0.36 0.18
1261.07 0.099145627 0.0634532 0.0087424 2.19
1345.14 0.112805691 0.072196
0.43 0.90
1233.05 0.094788115 0.0606644 0.016114 4.03
1387.18 0.119966208 0.076778
0.34 1.43
30.00
0 0 0 0 0 10.00
0.4 1.04
2
0.4 0.61
0.4 0.72
0.4 0.61
0.4 0.40
1456.14 20
286.70
28.67
315.37
Sub Total
Safety Factor (10%)
Grand total
-
7/30/2019 Clinic AHU 105-116 Latest
6/27
-
7/30/2019 Clinic AHU 105-116 Latest
7/27
S.No. Description W H
Area
a=HW
(m)
Air Flow
Q (L/s)
Equivalent
Length(m)
Velocity
=Q/a
(m/s)
Velocity
=Q/a
(fpm)
1 EggCrate grill 0 0 0 0 0.00 0.00
2 Straight Duct 1000 500 0.5 760 0.4 1.52 299.21
3 VCD 1000 500 0 0 0 0.00
4 Straight Duct 800 400 0.32 1520 6.8 4.75
800 600 0.48 1520 3.17 623.36
800 400 0.32 1520 4.75 935.04
6 Straight Duct 800 600 0.48 2280 3.5 4.75
1000 600 0.6 2280 3.80 748.03
800 600 0.48 2280 4.75 935.04
8 Straight Duct 1000 600 0.6 3800 7.3 6.33
1000 800 0.8 3800 4.75 935.04
1000 600 0.6 3800 6.33 1246.72
10 Straight Duct 1000 800 0.8 5320 7.2 6.65
1200 800 0.96 5320 5.54 1090.88
1000 800 0.8 5320 6.65 1309.05
12 Straight Duct 1200 800 0.96 6080 7.8 6.33
1400 800 1.12 6080 5.43 1068.61
1200 800 0.96 6080 6.33 1246.72
14 Straight Duct 1400 800 1.12 6840 2.8 6.11
1500 800 1.2 6840 5.70 1122.05
1400 800 1.12 6840 6.11 1202.19
16 Straight Duct 1500 800 1.2 8360 6.8 6.97
17 Elbow 1500 800 1.2 8360 1.08 6.97
18 Straight Duct 1500 800 1.2 8360 0.5 6.97
CSB-ML-45-94-HEF-01 (MECHANICAL
Reducer
15 Expansion
EXTERNAL STATIC PRESSURE CA
5 Expansion
11 Expansion
13 Expansion
7
9 Expansion
-
7/30/2019 Clinic AHU 105-116 Latest
8/27
1800 800 1.44 8360 5.81 1142.82
1500 800 1.2 8360 6.97 1371.39
20 Straight Duct 1800 800 1.44 10652 5.9 7.40
21 Elbow 1800 800 1.44 10652 1.53 7.40
22 Straight Duct 1800 800 1.44 10652 8.5 7.40
23Motorized
Damper0 0 0 0 0 0.00 0.00
24 VCD 0 0 0 0 0 0.00 0.00
25 Straight Duct 1800 800 1.44 10652 4.1 7.40
26 SILENCER
27 Elbow 450 1800 800 1.44 10652 1.53 7.40
28 Straight Duct 1800 800 1.44 10652 0.37 7.40
29 Elbow 450 1800 800 1.44 10652 1.53 7.40
30 Straight Duct 1800 800 1.44 10652 6.3 7.40
31 Elbow 450 1800 800 1.44 10652 1.53 7.40
32 Straight Duct 1800 800 1.44 10652 0.37 7.40
33 Elbow 450 1800 800 1.44 10652 1.53 7.40
34 Straight Duct 1800 800 1.44 10652 1.3 7.40
35 Elbow 1800 800 1.44 10652 1.53 7.40
36 Straight Duct 1800 800 1.44 10652 5.8 7.40
37 Straight Duct 2600 500 1.3 10652 1.7 8.19 1612.96
38 Elbow 2600 500 1.3 10652 3.14 8.19
39 Straight Duct 2600 500 1.3 10652 0.9 8.19 1612.96
40 Flexible conn. 2600 500 1.3 10652 0.2 8.19 1612.96
Expansion19
-
7/30/2019 Clinic AHU 105-116 Latest
9/27
-
7/30/2019 Clinic AHU 105-116 Latest
10/27
hv=
(V/4005)nhv1 nhv2
n(hv2-
hv1)
Pressure
Drop(Pa/
m)
Total
Pressure
Drop(Pa)
0.00 0.00 0.00 0.00 0 20.00
0.033 0.01
0 0 0 0 0 10.00
0.47 3.20
0.024225 0.0174423 0.0218028 5.45
0.054507 0.039245
0.34 1.19
0.034885 0.0251169 0.0141282 3.53
0.054507 0.039245
0.46 3.36
0.054507 0.0348845 0.0271324 6.78
0.096901 0.062017
0.4 2.88
0.07419 0.0474817 0.020892 5.22
0.106834 0.068374
0.32 2.50
0.071193 0.0512589 0.0185102 4.63
0.096901 0.069769
0.3 0.84
0.07849 0.056513 0.0083616 2.09
0.090104 0.064875
0.37 2.52
0.37 0.40
0.37 0.19
LANT ROOM)
CULATION
-
7/30/2019 Clinic AHU 105-116 Latest
11/27
0.081424 0.0586254 0.0257952 6.45
0.117251 0.084421
0.4 2.36
0.4 0.61
0.4 3.40
0 0 0 0 10.00
0 0 0 0 0 10.00
0.4 1.64
30.00
0.4 0.31
0.4 0.15
0.4 0.31
0.4 2.52
0.4 0.31
0.4 0.15
0.4 0.31
0.4 0.52
0.4 0.61
0.4 2.32
0.59 1.00
0.59 1.85
0.59 0.53
20.00
170.12
17.01
187.13Grand total
Sub Total
Safety Factor (10%)
-
7/30/2019 Clinic AHU 105-116 Latest
12/27
-
7/30/2019 Clinic AHU 105-116 Latest
13/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)NO:
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
1 Diffuser - - - 54 - - - - -
2 Flexible Duct - - - 54 - - - - -
3
Transition Rectangular to
Round(200x100 to
150)
- - - 54 - - - - - 0
4 VCD - - - 54 - - - - -
5 Duct 200 100 0.020 54 1.1 - 2.7 - -
6 Elbow 200 100 0.020 54 0.91 - 2.7
7 Duct 200 100 0.020 54 2.2 - 2.7 - -
8Reducer
(200x150 to 200x100)- - - - - - 2.7 - - 0
9 Duct 200 150 0.030 116 2.4 - 3.9 - -
10Reducer
(200x200 to 200x150)- - - - - - 3.9 - 0
11 Duct 200 200 0.040 193 2.03 - 4.83 - -
12Reducer
(250x200 to 200x200)- - - - - - 4.83 0
13 Elbow 250 200 0.050 193 1.21 4.83 3.86
14 Duct 250 200 0.050 243 1.15 4.86 - -
15 Elbow 250 200 0.050 243 1.21 4.86
16 Elbow 250 200 0.050 243 1.21 4.86
17Reducer
(300x200 to 250x200)0
18 Duct 250 200 0.050 243 0.26 4.86 - -
19
Transition
Rectangular to Round
(300x200 to 500)
- - - - - 0
20 VAV - - - - - - - - -
21
Transition
Round to Rectangular
(200 to 250x200)
- - - - - 0
22 Duct 250 200 0.050 243 1.57 4.86 - -
23Reducer
(350x350 to 250x200)- - - - - 0
24 Duct 350 350 0.123 544 6.05 4.44 - -
25Reducer
(400x350 to 350x350)- - - - - 0
26 Duct 400 350 0.140 778 7.05 5.56 - -
27 Elbow 400 350 0.140 778 2.74 5.56
28 Duct 400 350 0.140 778 8.18 5.56 - -
ESP Calculations For Supply Air Fan (Clinic Building AHU 105)
Page 13 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
14/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)NO:
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
29Reducer
(550x550 to 400x350)- - - - -
30 Duct 550 550 0.303 1955 3.03 6.46 - -
31 Elbow 550 550 0.303 1955 3.96 6.46
32 Duct 550 550 0.303 1955 0.974 6.46 - -
33 Elbow 550 550 0.303 1955 3.96 6.46
34 Duct 550 550 0.303 1955 7.3 6.46 - -
35 Elbow 45 550 550 - 1955 1.98
36 Duct 550 550 0.303 1955 0.912 6.46 - -
37 Elbow 45 550 550 - 1955 1.98
38 Duct 550 550 0.303 1955 0.368 6.46 - -
39 Elbow 45 550 550 - 1955 1.98
40 Duct 550 550 0.303 1955 0.562 6.46 - -
41 Elbow 45 550 550 - 1955 1.98
42 Duct 550 550 0.303 1955 0.958 6.46 - -
43 Duct 800 600 0.480 3031 3.84 6.31 - -
44 Elbow 800 600 0.480 3031 4.26 6.31
45 Duct 800 600 0.480 3031 2.82 6.31 - -
46 Elbow 30 800 600 - 3031 1.4
47 Duct 800 600 0.480 3031 0.792 6.31 - -
48 Elbow 800 600 0.480 3031 1.26 6.31
49 Air Terminal Device
Reducer
(800x350 to 550 x 350)
50 VCD 800 350 0.280 752
Duct 550 350 0.193 752 15 3.91 - -
Duct 800 350 0.280 752 15 2.69 - -
Duct 850 500 0.425 1432 5 3.37 - -
51 Duct 600 400 0.240 1432 20 5.97 - -
52 Elbow 800 350 0.280 752 4 10 2.69
53 Elbow 850 500 0.425 1432 4 4 3.37 - -
54Reducer
(600x400 to 850x500)
55 Elbow 600 400 0.240 1432 4 5 5.97 - -
56Reducer
(900x400 to 600x400)1432 - - - - -
57 Sound Attenuator - - - - -
58 Fire Damper
59 Duct 900 400 0.360 2860 15 7.94 - -
Plenum 6500
60 Flexible Connector 6500
AHU 6500
61 Louver - - - - - - - - -
Fresh Air Intake
Page 14 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
15/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)NO:
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
62 Inettial separator - - - - - - - - -
63Transition
1500x700 to 800x700- - - - - - 1772 - -
64 Duct 800 700 0.560 1772 13.2
65 Elbow1600x800 1600 800 - 1772 22 - - - -
66Elbow
1600x800- - - 1772 22 - - - -
67 Duct 1600 800 1.280 1772 3
68 Elbow 1600 800 1772 6.7
69 Duct 1600 800 1.280 1772 1
70 Motorised Damper 1600 500 0.800 1772 2.22 436.355 0.0119
71 Flexible Connector 1772
NOTE:
1. Refer Attached Carrier Hand book for reducer and Elbow pressure loss coeffitiants
Page 15 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
16/27
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)h
1 Diffuser - - - 78 - - - - -
2 Flexible Duct - - - 78 - - - - -
3
Expansion Round to
Rectangular (150 to
250x200)
- - - - - - - - -
4 VCD - - - 78 - - - - -
5 Duct 250 200 0.050 78 0.474 - 1.56 - -
6 Elbow 250 200 0.050 78 1.2 - 1.56
7 Duct 250 200 0.050 78 4.5 - 1.56 - -
8 Elbow 45 250 200 - - 0.61 - 2.70 - -
9 Duct 250 200 0.050 78 0.5 - 1.56 - -
10 Elbow 45 250 200 - - 0.61 - 2.70 - -
11 Duct 250 200 0.050 78 0.184 - 1.56 - -
12Expansion
(250x200 to 300x200)- - - - - - - - -
13 Duct 350 300 0.105 213 0.981 - 2.03
14 Elbow 350 300 0.105 213 2.13 - 2.03 - -
15 Duct 350 300 0.105 288 7.3 - 2.74 - -
15-1 VCD - 16 Elbow 45 350 300 0.105 288 1.155 - 2.74
17 Elbow 45 350 300 0.105 288 1.155 - 2.74
18 Duct 350 300 0.105 288 0.447 - 2.74 - -
19 Elbow 350 300 0.105 288 2.74 - 2.74 - -
20 Duct 350 300 0.105 288 6.2 - 2.74 - -
21 Expansion - - - - - - - - -
22 Duct 400 350 0.140 427 0.568 - 3.05 - -
23 Expansion - - - - - - - - -
24 Duct 450 350 0.158 652 1.07 - 4.14 - -
25 Elbow 450 350 652 2.74 - - - -
26 Duct 450 350 0.158 652 6.6 - 4.14 - -
27 Expansion - - - - - - - - -
27-1 Duct 800 600 0.480 2060 12.08 - 4.29 - -
28 Elbow 800 600 0.480 2060 4.27 - 4.29 - -
29 Duct 800 600 0.480 2243 9.5 - - - -
30 Elbow 800 600 0.480 2243 4.27 - 4.67 - -
31 Duct 800 600 0.480 2515 7.8 - 5.24 - -
32 Elbow 800 600 0.480 2515 4.27 - 5.24 - -
33 Riser Duct 800 600 0.480 2515 5.5 - 5.24 - -
-
34Reducer
(800x600 to 600x500)- - - - - - - - - 0.
35 Elbow 600 500 - 2515 3.3 -
ESP Calculations For Return Air Fan (Clinic Building AHU 105)
Second Mezzanine Floor
Page 16 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
17/27
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
36 Tee 45 Entry 0.000 9.7 - - - -
37 Duct 800 700 0.560 4024 1.64 - 7.19 - -
38 Elbow 45 800 700 0.560 4024 2.43 - 7.19 - -
39 Duct 800 700 0.560 4024 0.2 - 7.19 - -
40 Elbow 45 800 700 0.560 4024 2.43 - 7.19 - -
41 Duct 800 700 0.560 4024 5.168 - 7.19 - -
42 Expansion - - - - - - - -
43 Sound Attenuator 1600 1000 1.600 4024 - - 2.52 - -
44 Duct 1600 1000 1.600 4024 3 - 2.52 - -
45 Motorised Damper 1600 1000 1.600 4024 - 2.52 495.455 0.0153
AHU
-
46 Motorised Damper 1600 1000 1.600 1772 - 1.11 218.1775 0.0030
47 Duct 1600 1000 1.600 1772 - - - -
48 Elbow 1600 1000 1.600 1772 - - 1772 - -
49 Sound Attenuator - - - - - - - - -
50
Reducer
(1600x1000 to
800x700)
- - - - - - - - -
51 Duct 800 700 0.560 1772 0.2 - - - - 52 Elbow 800 700 0.560 1772 4.8 -
53 Duct 800 700 0.560 1772 0.3 - - - -
54 Elbow 800 700 0.560 1772 4.8 -
55 Duct 800 700 0.560 1772 7.25 - - - -
56 Elbow 45 800 700 0.560 1772 2.43 -
57 Duct 800 700 0.560 1772 0.3 - - - -
58 Elbow 45 800 700 0.560 1772 2.43 -
59 Duct 800 700 0.560 1772 6.6 - - - -
60 louver - - - - - - - - -
NOTE:
1. Refer Attached Carrier Hand book for reducer and Elbow pressure loss coeffitiants.
Exhaust Air
Page 17 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
18/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)h
1 Diffuser - - - 53 - - - - -
2 Flexible Duct - - - 53 - - - - -
3
Transition rectangular
to Round(200x150 to
150)
- - - 53 - - - - - 0.0
4 VCD 200 150 0.030 53 - - 1.767 348 0.00755
5 Duct 200 150 0.030 53 0.96 - 1.767 - -
6 Elbow 200 150 0.030 53 0.91 - 1.767
7 Duct 200 150 0.030 53 0.184 - 1.767 - -
200 150 0.030 53 - - 1.767 348 -
300 250 0.075 53 - 0.707 139
9 Duct 300 250 0.075 233 6.6 - 3.1 - -
350 300 0.105 233 - 2.2 437 -
300 250 0.075 233 3.1 612
11 Duct 350 300 0.105 233 6.2 - 2.22 - -
12 Elbow 350 300 0.105 - 2.1 - 4.83
13 Elbow 350 300 2.1
14 Duct 400 350 0.140 364 1.5 2.60 - -
400 350 0.140 364 2.60 512
450 DIA 0.159 364 2.29 451
16 VAV - - - - - - - -
350 DIA 0.096 364 3.79 746
300 250 0.075 364 4.85 956
18 Duct 300 250 0.075 364 1.4 4.85 - -
400 300 0.120 364 3.03 598
300 250 0.075 364 4.85 956
20 Duct 400 300 0.120 695 1.24 - 5.79 - -
21 Elbow 45 400 300 0.120 695 1.06 - - - -
22 Duct 400 300 0.120 695 0.5 5.79 - -
23 Elbow 45 400 300 0.120 695 1.06 - - - -
24 Duct 400 300 0.120 695 0.5 5.79 - -
25 Elbow 400 300 0.120 695 2.13 - - - -
25-1 Duct 400 300 0.120 695 6.8 6.8
550 400 0.220 695 - 3.16 622 -
400 300 0.120 695 - 5.79 1141
27 Duct 550 400 0.220 1385 5.6 6.30
550 500 0.275 1385 - 5.04 992 -
550 400 0.220 1385 - 6.30 1240
29 Duct 550 500 0.275 1609 15.8 5.85
600 500 0.300 1955 - 6.52 1284 -
550 500 0.275 1955 - 7.11 1400
31 Duct 600 500 0.300 1955 0.459 6.52
32 Elbow 45 600 500 0.300 1955 1.67 6.52 - -
33 Elbow 45 600 500 0.300 1955 1.67 6.52
0.0
0.1
0.0
- - -
ESP Calculations For Supply Air Fan (Clinic Building AHU 1
Reducer8
Reducer10
Transition Rectangular
to Round15
Transition Round to
Rectangular17
Reducer19
0.0
Reducer26
Reducer28
30 Reducer
0.0
0.0
0.0
0.0
Page 18 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
19/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
33-1 Duct 600 500 0.300 1955 0.6 6.52
34 Elbow 600 500 0.300 1955 3.3 6.52 - -
35 Duct 600 500 0.300 1955 9.1 6.52
36 Elbow 45 600 500 0.300 1955 1.67 6.52 - -
37 Duct 600 500 0.300 1955 0.5 6.52
38 Elbow 45 600 500 0.300 1955 1.67 6.52 - -
39 Duct 600 500 0.300 1955 7 6.52
800 600 0.480 1955 - 4.07 802 -
600 500 0.300 1955 - 6.52 1284
41 Duct 800 600 0.480 3075 9.7
1000 600 0.600 3075 - 5.13 1010 -
800 600 0.480 3075 - 6.41 1262
43 Duct 1000 600 0.600 3998 0.749 6.66 - -
44 Elbow 1000 600 0.600 3998 4.57 6.66
45 Elbow 1000 600 0.600 3998 4.57 6.66 - -
46 Elbow 1000 600 0.600 3998 4.57
47 Duct 1000 600 0.600 3998 0.5 6.66 - -
48 Elbow 1000 600 0.600 3998 4.57 6.66
49 Duct 1000 600 0.600 3998 2.79 6.66
50 Elbow 45 1000 600 0.600 4504 2.3 7.51
51 Duct 1000 600 0.600 4504 1 7.51 - -
52 Elbow 45 1000 600 0.600 4504 2.3 53 Duct 1000 600 0.600 4504 0.3 7.51 - -
54 Elbow 45 1000 600 0.600 4504 2.3
55 Duct 1000 600 0.600 4504 0.5 7.51 - -
56 Duct 1000 600 0.600 4504 7.5 7.51
57 Elbow 1000 600 0.600 4504 4.57 7.51
1000 600 0.600 7516 12.53 2468
800 700 0.502 7516 14.96 2947
59 Riser Duct 800 700 0.502 7516 6 14.96
2nd
Mezzanine Floor60 Elbow 800 700 0.502 7516 4.57
61 Elbow 800 700 0.502 7516 4.57
62 Duct 800 700 0.502 7516 1.249
63 Elbow 800 700 0.502 7516 4.87
64 Duct 800 700 0.502 7516 3
65 Elbow 800 700 0.502 7516 4.87
66 Duct 800 700 0.502 7516 2
67 Motorised Damper 800 700 0.502 7516 14.96 2947.157643 0.5415
68 Flexible Connector
AHU
69 Louver - - - - - - - - -
70 Inettial separator - - - - - - - - -
1500 700 1.766 2699 - - 1.53 301 -
800 700 0.502 2699 5.37 1058
72 Duct 1000 800 0.800 2699 13.2
73Elbow 45
1000x8001000 800 0.800 2699 0.38 - - - -
58 Reducer
Fresh Air Intake
40 Reducer
42 Reducer
Transition
1500x700 to 800x70071
Page 19 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
20/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
74 Duct 1000 800 0.800 2699 3.9
Page 20 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
21/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
1000 800 0.800 2699 3.37 665 -
800 1000 0.800 2699 3.37 665
76 Duct 800 1000 0.800 2699 3
800 1000 0.800 2699 3.37 665 -
1000 800 0.800 2699 3.37 665
78 Duct 1000 800 0.800 2699 1.02
79 Elbow 1000 800 0.800 2699 6.1
80 Duct 1000 800 0.800 2699 6
81 Elbow 30 1000 800 0.800 2699 1.73 - - - -
82 Duct 1000 800 0.800 2699 1.1
83 Elbow 30 1000 800 0.800 2699 1.72
84 Duct 1000 800 0.800 2699 1.41
85 Elbow 1000 800 0.800 2699 5.18
86 Duct 1000 800 0.800 2699 3
87 Elbow 1000 800 0.800 2699 5.18
88 Duct 1000 800 0.800 2699 1
89 Motorised Damper 1000 800 0.800 2699 3.37 664.62875 0.0275
90 Flexible Connector 2699
NOTE:
1. Refer Attached Carrier Hand book for reducer and Elbow pressure loss coeffitiants
75 Reducer
Reducer77
Page 21 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
22/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)h
R1 Diffuser - - - - - - - -
R2 Flexible Duct - - - - - - - -
150 dia 0.018 108 - 6.11 1205
200 150 0.030 108 - 3.60 709
R4 VCD 200 150 0.030 108 - - 3.600 709 0.03136
R5 Duct 200 150 0.030 108 1.08 - 3.600 - -
R6 Elbow 200 150 0.030 108 0.91 - 3.600
R7 Duct 300 250 0.075 278 21.5 - 3.707 - -
300 250 0.075 0 - 0.000 0 -
350 300 0.105 0 - 0.000 0
R9 Duct 350 300 0.105 556 4.4 - 5.3 - -
R10 Elbow 350 300 0.105 556 2.1 - 4.83
R11 Elbow 350 300 0.105 556 2.1 -
R12 Duct 350 300 0.105 556 0.3 - 5.30 - -
R12 Duct 350 300 0.105 556 2 - 5.30 - -
R14 Elbow 350 300 0.105 556 2.1 - 4.83
R15 Duct 350 300 0.105 556 1.4 - 5.30 - -
300 250 0.075 0 - 0.000 0 -
350 300 0.105 0 - 0.000 0
R17 Duct 550 500 0.275 1246 9.06 - - - -
R18 Elbow 550 500 0.275 1418 1.67 - 5.16 - -
R19 Duct 550 500 0.275 1418 0.5 - - - -
R20 Elbow 550 500 0.275 1418 1.67 - 5.16 - -
R21 Duct 550 500 0.275 1764 17.18 - - - -
R22 Elbow 550 500 0.275 1764 1.67 - 6.8
R23 Duct 550 500 0.275 1764 5.6 - 6.41
R24 Elbow 45 550 500 0.275 1764 1.67 - 6.41 - -
R25 Elbow 45 550 500 0.275 1764 1.67 - 6.41
R26 Duct 550 500 0.275 1764 11.5 - 6.41
R27 Expansion - - - - - - - - -
R28 Duct 800 600 0.480 2664 4.2 - 5.55
R29 VCD 800 600 0.502 2664 - 5.30 1045 0.0680
R30 Duct 800 600 0.480 2664 0.3 - 5.55
R31 Expansion - - - - - - - - -
R32 Duct 1200 600 0.720 2664 3.9 - 3.70
R33 Elbow 1200 600 0.720 2664 4.6 - 3.7
R34 Duct 1200 600 0.720 3719 1.3 - 5.17
R35 Duct 1200 600 0.720 3719 0.5 - 5.17 - -
R36 Elbow 1200 600 0.720 3719 4.6 - 5.17 - -
R37 Elbow 1200 600 0.720 3719 4.6 - 5.17
R38 Duct 1200 600 0.720 3951 1.79 - 5.49
R39 Elbow 45 1000 600 0.600 3951 2.28 - 6.59
R40 Elbow 45 1000 600 0.600 3951 2.28 - 6.59 - -
R41 Duct 1000 600 0.600 3951 0.68 - 1200 600 0.720 3848 - 5.3 1053 -
1000 600 0.600 3848 - 6.4 1263
ESP Calculations For Return Air Fan (Clinic Building AHU 111)
R8 Expansion 0.0
Transition Round
Rectangular (150 to
200x150)
R42 Reducer
R16 Expansion
R3 0.0
0.0
0.0
Page 22 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
23/27
SMRC PROJECT
CLINIC BUILDING
S.No. Description W HArea a=HW
(m)
Air Flow Q
(L/s)
Length
(m)
Equivalent
Dia(m)
Velocity =Q/a
(m/s)
Velocity =Q/a
(fpm)
hv= (V/4005)
(in. Wg)
R43 Duct 1000 600 0.600 3951 4.5 -
R44 Elbow 1000 600 0.600 3951 4.6 - 6.59 - -
R45 Duct 1000 600 0.600 3951 4.6 - 6.59
1000 600 0.600 3848 - 6.41 1263
800 700 0.502 3848 - 7.66 1509
R47 Riser Duct 800 700 0.560 6358 6 - 11.35
2nd
Mezzanine Floor -
R48 Elbow 800 700 0.560 6358 4.57 - 11.35
R49 Duct 800 700 0.560 6358 4.57 - 11.35
R50 Elbow 800 700 0.560 6358 1.249 - 11.35
R51 Duct 800 700 0.560 6358 4.87 - 11.35
R52 Elbow 800 700 0.560 6358 3 - 11.35
R53 Duct 800 700 0.560 6358 4.87 - 11.35
R54 Plenum - - - - - - - - -
R55 Sound Attenuator 800 700 0.560 6358 4.87 - -
R56 Elbow 800 700 0.560 6358 4.87 - 11.35
R57 Duct 800 700 0.560 6358 2 - 11.35
R58 Motorised Damper 800 700 0.560 6358 - 11.35 2237 0.3119 R58-1 Flexible Connector -
- AHU -
-
R59 Louver - - - - - - - - -
R60 Duct 1000 850 0.850 2699 0.464 -
R61Elbow 45
1000x8001000 850 0.850 2699 2.74 - - - -
R62 Duct 1000 850 0.850 2699 6.5 -
R63 Expansion - - - - - - - -
R64 Duct 800 700 0.560 2699 1.62 - - - -
R65 Elbow 800 700 0.560 2699 4.9 - - - -
R66 Duct 800 700 0.560 2699 9.1 - - - -
R67 Elbow 800 700 0.560 2699 4.9 - - - -
R68 Duct 800 700 0.560 2699 11.6 - - - - R69 Elbow 800 700 0.560 2699 4.9 - - - -
R70 Duct 800 700 0.560 2699 5.3 - - - -
R71 Elbow 800 700 0.560 2699 4.9 - - - -
R72 Duct 800 700 0.560 2699 3.6 - - - -
R73 Elbow 45 800 700 0.560 2699 2.45 - - - -
R74 Duct 800 700 0.560 2699 0.645 - - - -
R75 Elbow 45 800 700 0.560 2699 2.45 - - - -
R76 Duct 800 700 0.560 2699 0.3 - - - -
R77 Sound Attenuator 1600 1000 1.600 2699 - - - -
R78 Elbow 1600 1000 1.600 2699 6.4 - - - -
R79 Duct 1600 1000 1.600 2699 3 - - - -
R80 Motorised Damper 1600 1000 1.600 2699 - 1.69 332.31 0.0069
R81 Flexible Connector 2699
NOTE:
1. Refer Attached Carrier Hand book for reducer and Elbow pressure loss coeffitiants
Exhaust Air
R46
Transition Rectangular
to Round
Page 23 of 27
-
7/30/2019 Clinic AHU 105-116 Latest
24/27
ESP For AHU- H-03-45-70-HAH-05
S.No. Description W H
Area
a=HW
(m)
Air Flow
Q (L/s)
Length
(m)NO:
Velocity
=Q/a
(m/s)
Velocity
=Q/a
(fpm)
hv=
(V/4005)
(in. Wg)
hv1 hv2n(hv2-
hv1)
Pr
D
SUPPLY SIDE
1 Air Terminal Device
2Reducer
(800x350 to 550 x 350)
3 VCD 800 350 0.280 752
4 Duct 550 350 0.193 752 15 3.91 - - - - -
5 Duct 800 350 0.280 752 15 2.69 - - - - -
6 Fire Damper 850 500
7 Duct 850 500 0.425 1432 5 3.37 - - - - -
8 Duct 600 400 0.240 1432 20 5.97 - - - - -
9 Elbow 800 350 0.280 752 4 10 2.69
10 Elbow 850 500 0.425 1432 4 4 3.37 - - - - -
11Reducer
(600x400 to 850x500)
12 Elbow 600 400 0.240 1432 4 5 5.97 - - - - -
13Reducer
(900x400 to 600x400)1432 - - - - -
14 Sound Attenuator - - - - - - - -
15 Fire Damper
16 Duct 900 400 0.360 2860 15 7.94 - - - - -
17 Plenum 6500
18 Flexible Connector 6500
AHU 6500
SUBTOTAL
15 % Safety Factor
TOTAL
-
7/30/2019 Clinic AHU 105-116 Latest
25/27
ESP For AHU- H-03-45-70-HAH-05
S.No. Description W H
Area
a=HW
(m)
Air Flow
Q (L/s)
Length
(m)NO:
Velocity
=Q/a
(m/s)
Velocity
=Q/a
(fpm)
hv=
(V/4005)
(in. Wg)
hv1 hv2n(hv2-
hv1)
P
D
FRESH AIR SIDE
1 Architectural Louvre
2 Sand Trap Louvre
3 Duct 950 900 0.855 6500 72 7.60
4 Fire Damper 950 900 2
5 Elbow 950 900 0.855 6500 6 12 7.60 - - - - -
6 Sound Attenuator
7 Plenum
8 Flexible Connector
AHU
SUBTOTAL
15 % Safety Factor
TOTAL
-
7/30/2019 Clinic AHU 105-116 Latest
26/27
ESP For AHU- H-ML-45-96-HAH-01
S.No. DescriptionW
(mm)
H
(mm)
Area
a=HW
(m)
Air Flow
Q (L/s)
Length
(m)NO:
Velocity
=Q/a
(m/s)
Velocity
=Q/a
(fpm)
hv=
(V/4005)
(in. Wg)
hv1 hv2 n(hv2-hv1)
Pressure
Drop(Pa/
m)
Total
Pressure
Drop(Pa)
1 Air Terminal Device 50.000
2 Flexible connection 10.000
3 Duct 200 200 0.040 99 8 2.48 0.7 5.600
4 Elbow 200 200 0.040 99 3 1 2.48 0.7 2.1
5 VCD 200 200 0.040 99 30
6Reducer
(300x250 to 200 x 200)3.000
7 Duct 300 250 0.075 198 12 2.64 0.4 4.800
8 Motorized Damper 15.000
9 Duct 300 300 0.090 396 12 4.40 1.1 13.200
10 Elbows 300 300 0.090 396 4.6 3 4.40 1.1 15.18
11 VCD 300 300 0.090 396 30
12 MSFD 300 300 0.090 396 15
13 Duct 400 600 0.240 2298 8 9.58 1.6 12.800
14 VCD 400 600 0.240 2298 30
15 MSFD 400 600 0.240 2298 15
16 Elbows 400 600 0.240 2298 6 1 9.58 1.1 6.6
17Reducer
(600x400 to 300x300)45
18Reducer
(600x400 to 850x500)26
19 Duct 500 850 0.425 3021 2 7.11 1.1 2.200
20 Duct 500 1100 0.550 4654 35 8.46 1 35.000
21 Elbows 500 1100 0.550 4654 8 3 8.46 1 24
22 Elbows 500 850 0.425 3021 8 1 7.11 1.1 8.8
23Reducer
(1100x500 to 850x500)26
24 MSFD / SD 500 1100 0.550 4654 4 120
25 Sound Attenuator 80
26 Duct 800 800 0.640 4654 4 7.27 0.6 2.400
27 Elbows 800 800 0.640 4654 9 1 7.27 0.6 5.4
28 Reducer(1100x500 to 800x800)
15
29 Flexible Connector 4654 20
30 Plenum 4654 10.000
-
7/30/2019 Clinic AHU 105-116 Latest
27/27
31 Plenum 4654 10.000
32Reducer
(1600x500 to 800x800)20.000
33 Duct 800 800 0.640 4654 45 7.27 0.6 27.000
34 Elbows 800 800 0.640 4654 9 9 7.27 0.6 48.6
35 Sound Attenuator 80
36 Flexible Connector 4654 20
37Reducer
(1600x500 to 800x800)20.000
38Reducer
(1300x500 to 800x800)15.000
SUBTOTAL 918.680
15 % Safety Factor 137.802
TOTAL 1056.482