cliv-acc-061-a3s-e

2
Clima-Flex, S.A. de C.V. Av. Central #285 Parque Industrial Logistico / Delegacion La Pila / San Luis Potosí, México / ZIP Code 78422 Phone +52 (444) 161-5043 Facebook/clima-flex @climaflexMexico www.clima-flex.com Standard Characteristics Limited Warranty for Clima-Flex units. • 1 year warranty for funcional equipment parts. • 2 years warranty for compressor. Notes 1. EER and IPLV mentioned in the tables above are applied with non-ducted indoor units. Values are based on AHRI Standar 550 / 590 and are subject to change without previous notice. Performance data can be found on the AHRI website http://ww.ahridirectory.org/ 2. All communication cable to be minimum 18 AGW, 3 conductor, stranded, shielded and must comply with applicable local and national code. 3. The rated data mentioned in this technical data is applied with non-ducted indoor units. 4. Values include elevation over sea level correction factor. 5. The voltage tolerance is ±10%. 6. Power wiring cable size must comply with the applicable local and national code. Cable THW at 75°C Cal. 6. 7. Efficiency data do not consider circulator water pump. 8. Installation and maintenance must be performaed by properly trained and qualified personnel equipped with the proper tools. COOLING MODE Nominal Capacity (BTU/hr) Rated Capacity (BTU/hr) EER (BTU/W*h) IPLV (EER) COPR 61,000 51,900 11.51 15.78 3.37 HEATING MODE Heating Capacity (BTU/hr) Power Consumption (kW) COPH Leaving water temperature (°F) 64,562 4.70 4.03 110 UNIT DATA Refrigerant Type Refrigerant Weight (lbs) Sound Level (Db) Net Weight (lbs) Operation Weight (lbs) Controller Total Water Pressure Drop (ft WG) R410-A 3.50 68 319.20 327.40 Digital 8.50 DIMENSIONS Length (in) Width (in) Height (in) Inlet/Outlet water (in) 43.25 20.00 40.00 1 1/4 COMPRESSOR Compressor Type Quantity Power Consumption (kW) Current Consumption (A) Two Stages Scroll 1 3.71 11.40 FAN Type Air Pressure Drop (inH 2 O) Air Operating Range (°F) Power Consumption (kW) Current Consumption (A) Axial 0.40 55 / 120 0.80 2.80 CONDENSER Type Air Flow (CFM) Area (ft 2 ) Air Pressure Drop (inH 2 O) Microchannel 4,000 8.75 0.40 SELECTION CONDITIONS Elevation over sea level (ft) Ambient temperature (°F) Leaving water temperature (°F) 0.0 95 44 CLIV UNIT EVAPORATOR Type Water Flow (GPM) Inlet Water Temperature (°F) Outlet Water Temperature (°F) Stainless Steel Plates 12 54 44 Rev. 2014-12-17 CLIV SERIES CLIV-ACH-061-A3S HEAT PUMP Mini Chiller Air Cooled Axial Fan ELECTRICAL DATA Power source (V,Φ,Hz) MOP (A) MCA (A) Total Current Consumption (A) Total Power Consumption (kW) 220 / 3 / 60 28.50 17.80 14.20 4.51

Upload: clima-flex

Post on 06-Apr-2016

234 views

Category:

Documents


2 download

DESCRIPTION

CLIV-ACC-061-A3S-E Technical diagram, HEAT PUMP Mini Chiller Air Cooled Axial Fan

TRANSCRIPT

Page 1: CLIV-ACC-061-A3S-E

Clima-Flex, S.A. de C.V. Av. Central #285 Parque Industrial Logistico / Delegacion La Pila / San Luis Potosí, México / ZIP Code 78422

Phone +52 (444) 161-5043 Facebook/clima-flex @climaflexMexico www.clima-flex.com

Standard CharacteristicsLimited Warranty for Clima-Flex units.• 1 year warranty for funcional equipment parts.• 2 years warranty for compressor.

Notes1. EER and IPLV mentioned in the tables above are applied with non-ducted indoor units.Values are based on AHRI Standar 550 / 590 and are subject to change without previous notice. Performance data can be found on the AHRI website http://ww.ahridirectory.org/2. All communication cable to be minimum 18 AGW, 3 conductor, stranded, shielded and must comply with applicable local and national code.3. The rated data mentioned in this technical data is applied with non-ducted indoor units.4. Values include elevation over sea level correction factor.5. The voltage tolerance is ±10%.6. Power wiring cable size must comply with the applicable local and national code. Cable THW at 75°C Cal. 6.7. Efficiency data do not consider circulator water pump. 8. Installation and maintenance must be performaed by properly trained and qualified personnel equipped with the proper tools.

COOLING MODE

Nominal Capacity (BTU/hr)Rated Capacity (BTU/hr)EER (BTU/W*h)IPLV (EER)COPR

61,00051,900

11.5115.78

3.37

HEATING MODE

Heating Capacity (BTU/hr)Power Consumption (kW)COPH

Leaving water temperature (°F)

64,5624.704.03110

UNIT DATA

Refrigerant TypeRefrigerant Weight (lbs)Sound Level (Db)Net Weight (lbs)Operation Weight (lbs)Controller Total Water Pressure Drop (ft WG)

R410-A3.50

68319.20327.40Digital

8.50

DIMENSIONS

Length (in)Width (in)Height (in)Inlet/Outlet water (in)

43.2520.0040.001 1/4

COMPRESSOR

Compressor TypeQuantityPower Consumption (kW)Current Consumption (A)

Two Stages Scroll1

3.7111.40

FAN

TypeAir Pressure Drop (inH2O)Air Operating Range (°F)Power Consumption (kW)Current Consumption (A)

Axial0.40

55 / 1200.802.80

CONDENSER

TypeAir Flow (CFM)Area (ft2)Air Pressure Drop (inH2O)

Microchannel4,000

8.750.40

SELECTION CONDITIONS

Elevation over sea level (ft)Ambient temperature (°F)Leaving water temperature (°F)

0.09544

CLIV UNIT

EVAPORATOR

TypeWater Flow (GPM)Inlet Water Temperature (°F)Outlet Water Temperature (°F)

Stainless Steel Plates125444

Rev. 2014-12-17

CLIV SERIESCLIV-ACH-061-A3S

HEAT PUMP

Mini Chiller Air Cooled Axial Fan

ELECTRICAL DATA

Power source (V,Φ,Hz)MOP (A)MCA (A)Total Current Consumption (A)Total Power Consumption (kW)

220 / 3 / 6028.5017.8014.20

4.51

Page 2: CLIV-ACC-061-A3S-E

Clima-Flex, S.A. de C.V. Av. Central #285 Parque Industrial Logistico / Delegacion La Pila / San Luis Potosí, México / ZIP Code 78422

Phone +52 (444) 161-5043 Facebook/clima-flex @climaflexMexico www.clima-flex.com

CLIV SERIESCLIV-ACH-061-A3S

HEAT PUMP

Mini Chiller Air Cooled Axial Fan