CITY MULTI -- Select Series -- Commissioning Report revision 0811 1. Commissioning Report being rejected. The most current version can be downloaded from: 2. security level, click Tools - Options. On the Security tab, click "Macro Security." 3. copies or faxed copies of this report (with the exception of the cover page discussed below). 4. Electric and will delay the issue of your warranty certificate. 5. Complete the Cover Page. built based on the system type selected. 6. and indoor unit models selected) 7. The Maintenance-Inspection Tab is provided as a reference guide for periodic maintenance. 8. Commissioning Report. Ensure you are using the most current version of this form. Failure to us the most current version http://www.mylinkdrive.com Your macro security level must be set to 'Low' or 'Medium' to use this Commissioning Report form. To This form is to be completed and submitted electronically. Mitsubishi Electric will not accept hand Always clear the Commissioning Report form using the "Clear Form" button on the Cover Page prior to Commissioning Report. Failure to clear the form prior to beginning will result in incorrect data Provide all information requested. Failure to provide complete informaiton will delay the issue Select the system type (outdoor unit series/model type) from the listing provided. The - R2-Series (Modular): PURY models [P~T/Y(S)HMU, P~T/Y(S)JMU]; PQRY models [P~T/YHMU] - Y-Series (Modular): PUHY models [P~T/Y(S)HMU, P~T/Y(S)JMU, HP~T/Y(S)HMU]; PQHY models - S-Series (PUMY): PUMY models [P~NHMU] - R2-Series (TGMU): PURY models [P~TGMU]; PQRY models [P~TGMU] - Y-Series (TGMU): PUHY models [P~TGMU]; PQHY models [P~TGMU] Complete all subsequent pages of the Commissioning Report, again providing all requested information The following fields are calculated fields and are therefore not selectable on the report form for - General Tab: Total Indoor Unit Connected Capacity - Outdoor Tab: Additional Refrigerant Charge (calculated based on data input on the Index & - Index & Charge Calc Tab: Indoor Unit Sizes and Total Connected Capacities (calculated based - Index & Charge Calc Tab: Total System Index (calculated based on the outdoor unit and indoor A Maintenance Tool recording (minimum 2-hour duration) an an as-built Design Tool file must be

Upload: waqar-ul-haq

Post on 25-Oct-2014

61 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: CM SL Commissioning Report 0811

CITY MULTI -- Select Series -- Commissioning Reportrevision 0811

1. Ensure you are using the most current version of this form. Failure to us the most current version will result in your

Commissioning Report being rejected. The most current version can be downloaded from:

2. Your macro security level must be set to 'Low' or 'Medium' to use this Commissioning Report form. To change your macro

security level, click Tools - Options. On the Security tab, click "Macro Security."

3. This form is to be completed and submitted electronically. Mitsubishi Electric will not accept hand written copies, mailed hard

copies or faxed copies of this report (with the exception of the cover page discussed below).

4. Always clear the Commissioning Report form using the "Clear Form" button on the Cover Page prior to beginning a new

Commissioning Report. Failure to clear the form prior to beginning will result in incorrect data being reported to Mitsubishi

Electric and will delay the issue of your warranty certificate.

5. Complete the Cover Page.

built based on the system type selected.

6. Complete all subsequent pages of the Commissioning Report, again providing all requested information about the system.

and indoor unit models selected)

7. The Maintenance-Inspection Tab is provided as a reference guide for periodic maintenance.

8.

Commissioning Report.

http://www.mylinkdrive.com

� Provide all information requested. Failure to provide complete informaiton will delay the issue of your warranty certificate.

� Select the system type (outdoor unit series/model type) from the listing provided. The Commissioning Report form will be

- R2-Series (Modular): PURY models [P~T/Y(S)HMU, P~T/Y(S)JMU]; PQRY models [P~T/YHMU]

- Y-Series (Modular): PUHY models [P~T/Y(S)HMU, P~T/Y(S)JMU, HP~T/Y(S)HMU]; PQHY models [P~T/YHMU]

- S-Series (PUMY): PUMY models [P~NHMU]

- R2-Series (TGMU): PURY models [P~TGMU]; PQRY models [P~TGMU]

- Y-Series (TGMU): PUHY models [P~TGMU]; PQHY models [P~TGMU]

� The following fields are calculated fields and are therefore not selectable on the report form for data input.

- General Tab: Total Indoor Unit Connected Capacity

- Outdoor Tab: Additional Refrigerant Charge (calculated based on data input on the Index & Charge Calc Tab)

- Index & Charge Calc Tab: Indoor Unit Sizes and Total Connected Capacities (calculated based on the outdoor unit

- Index & Charge Calc Tab: Total System Index (calculated based on the outdoor unit and indoor unit models selected)

A Maintenance Tool recording (minimum 2-hour duration) an an as-built Design Tool file must be submitted with the

Page 2: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division CITY MULTI Commissioning Report Cover Page

CITY MULTI -- Select Series -- Commissioning Report

INSTALLATION DATA:

Site Name:

Site Address:

Address 2: Country:

City: State/Prov: Zip Code:

System Designer: Telephone:

Installing Contractor: Telephone:

Commissioning Agent: Telephone:

E-mail: *

Commissioning Date:

System Reference:

Location:

To be completed by MEUS/HVAC Service Department

Warranty Number:

BEFORE RUNNING THE SYSTEM, CARRY OUT A FULL PRE-COMMISSIONING CHECK OF THE FOLLOWING:

1. Refrigeration pipe work has been pressure tested (600 psig) and evacuated using the triple evacuation method.2. Correct refrigeration trim charge has been added and service valves have been opened.3. All units, remote controllers and centralized controllers in the system have corrrect address settings prior to applying power to the outdoor unit.4. Power supply (source voltage) to all units must be checked prior to switching on. Once the unit has been switched on, the crankcase heater must be left on

for a 12-hour period prior to start-up. Do not connect M-Net terminals during this period. After the 12-hour period has elapsed, turn off the main power circuitbreaker for at least 10 minutes, reconnect the M-Net terminals and then turn the main power circuit breaker back on.

5. All control cable installation is completed using 16 AWG shielded cable. Shield is grounded at the outdoor unit only (NOT at the 'S' terminal) for TGMU models.6. All condensate drainpipe work must be complete.7.

PRESSURE TEST DETAILS: EVACUATION DETAILS:

Test Pressure: PSIG Vacuum Achieved: Microns

Test Period: Hours Hours

Microns

COMMISSIONING AGENT'S COMMENTS: Select your outdoor series/model type: -- S

* Commissioning Agent's E-mail address is required for Mitsubishi Electric to provide registration number.

Original Commissioning Report documents and a CD containing Maintenance Tool recordings and Design Tool files must be received byMitsubishi Electric at the address below no later than 21 days after completion of system starup/commissioning.

Mitsubishi Electric & Electronics USA, Inc.HVAC Advanced Products Division

3400 Lawrenceville-Suwanee Road

EquipmentPurchased From:

CFC Safe HandlingRegistration Number:

CITY MULTIService Course Completion Date:

Submit a Maintenance Tool recording (minimum 2-hours) and an as-built Design Tool file with this commissioning report.

Pressure RiseTest Results:

NOTE:

** Ensure you are using the most current version of this form. Refer to the Instructions tab of this form for instructions on how to download the most current

revision of the Commissioning Report being rejected. **Attn: Service Department

Page 3: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division CITY MULTI Commissioning Report Cover Page

Suwanee, GA 30024

Page 4: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 4 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM:

NO. SYSTEM AND INSTALLATION STATUS REMARKS

1 Installation Location

Outdoor Unit(s)

BC Controller

Location

0

0

0

0

2 Maintenance Accessibility

Outdoor Unit

BC Controller (single)

BC Controller (main)

Sub-BC Controller

2nd Sub-BC Controller

Indoor Units

3 Total Piping Length Ft.

4 Furthest Piping Length Outdoor to Indoor Ft.

5 Height Difference

Outdoor to BC Ft.

Main-BC to Sub-BC Ft.

Sub-BC to 2nd Sub-BC Ft.

BC Controller to Indoor Ft.

Indoor to Indoor (max) Ft.

6 Standard of Pipe-work

7 Standard of Pipe Insulation

8

Outdoor Unit

BC Controller (single)

BC Controller (main)

Sub-BC Controller

2nd Sub-BC Controller

Indoor Units

Electrical Cable Type: Size:

9 Connection of Control System

Outdoor to BC

Main-BC to Sub-BC

Sub-BC to 2nd Sub-BC

BC Controller to Indoor

Indoor to Indoor

Indoor to RC

Control Cable Type: Size:

10 Standard of Electrical Insulation

11 Access to Remove Electrical Covers

12

Serial Number

13 Remote Controller Operation

Ventilation

Cool / Heat

Automatic

14 Connection Options

15 Total Indoor Unit Connection Capacity Btu/h --- 0.00%

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Connection of Main Power Source

Centralized Control Method(if other, please specify in remarks column)

Rooftop

Other Location

Sub-BC

2nd Sub-BC

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

AG-150 TC-24

GB-50A

GB-24A None

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Main-BC

Single-BC

Good Poor

Good Poor

Other

Page 5: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 5 of 46

Page 6: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 6 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM:

NO. SYSTEM AND INSTALLATION STATUS REMARKS

1 Installation Location Outdoor Unit

2 Maintenance AccessibilityOutdoor Unit

Indoor Units

3 Total Piping Length Ft.

4 Furthest Piping Length Outdoor to Indoor Ft.

5 Height DifferenceOutdoor to Indoor Ft.

Indoor to Indoor (max) Ft.

6 Standard of Pipe-work

7 Standard of Pipe Insulation

8

Outdoor Unit

Indoor Units

Electrical Cable Type: Size:

9 Connection of Control System

Outdoor to Indoor

Indoor to Indoor

Indoor to RC

Control Cable Type: Size:

10 Standard of Electrical Insulation

11 Access to Remove Electrical Covers

12

Serial Number

13 Remote Controller OperationVentilation

Cool / Heat

14 Connection Options

15 Total Indoor Unit Connection Capacity Btu/h --- 0.00%

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Connection of Main Power Source

Centralized Control Method(if other, please specify in remarks column)

Rooftop

Other Location

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

AG-150 TC-24

GB-50A

GB-24A None

Good Poor

Good Poor

Good Poor

Other

Page 7: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 7 of 46

Page 8: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 8 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM:

NO. SYSTEM AND INSTALLATION STATUS REMARKS

1 Installation Location

Outdoor Unit(s)

BC Controller

Location

0

0

0

0

2 Maintenance Accessibility

Outdoor Unit

BC Controller (single)

BC Controller (main)

Sub-BC Controller

2nd Sub-BC Controller

Indoor Units

3 Total Piping Length Ft.

4 Furthest Piping Length Outdoor to Indoor Ft.

5 Height Difference

Outdoor to BC Ft.

Main-BC to Sub-BC Ft.

Sub-BC to 2nd Sub-BC Ft.

BC Controller to Indoor Ft.

Indoor to Indoor (max) Ft.

6 Standard of Pipe-work

7 Standard of Pipe Insulation

8

Outdoor Unit

BC Controller (single)

BC Controller (main)

Sub-BC Controller

2nd Sub-BC Controller

Indoor Units

Electrical Cable Type: Size:

9 Connection of Control System

Outdoor to BC

Main-BC to Sub-BC

Sub-BC to 2nd Sub-BC

BC Controller to Indoor

Indoor to Indoor

Indoor to RC

Control Cable Type: Size:

10 Standard of Electrical Insulation

11 Access to Remove Electrical Covers

12

Serial Number

13 Remote Controller Operation

Ventilation

Cool / Heat

Automatic

14 Connection Options

15 Total Indoor Unit Connection Capacity Btu/h --- 0.00%

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Connection of Main Power Source

Centralized Control Method(if other, please specify in remarks column)

Rooftop

Other Location

Sub-BC

2nd Sub-BC

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

AG-150 TC-24

GB-50A

GB-24A None

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Main-BC

Single-BC

Good Poor

Other

Good Poor

Page 9: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 9 of 46

Page 10: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 10 of 46

CITY MULTI -- Select Series -- Commissioning Report

OUTDOOR UNIT:

OUTDOOR UNIT MODEL NUMBER: ADDITIONAL REFRIGERANT CHARGE: oz.

NO. OUTDOOR UNIT MODULES OUTDOOR UNIT #1 (OC) OUTDOOR UNIT #2 (OS1) OUTDOOR UNIT #3 (OS2)

General

1 Unit Address:

2 Model Number:

3 Serial Number:

4 Compressor Model Number:

5 Compressor Serial Number:

6 Vibration/NoiseCompressor

Fan

Line Voltage

7 Voltage L1 - L2 (VAC)

8 Voltage L2 - L3 (VAC)

9 Voltage L1 - L3 (VAC)

10 Current L1 (Amps):

11 Current L2 (Amps):

12 Current L3 (Amps):

Control Voltage

13 Control Voltage - TB3 (VDC)

14 Control Voltage - TB7 (VDC)

1 Heat Exchanger Details: Manufacturer: Serial No.:

2 Inlet Water Temperature REMARKS

3 Outlet Water Temperature REMARKS

4 Inlet Flow Rate GPM REMARKS

BRANCH CONTROLLER:

1 BC Controller Details:

BC Controller (single): Model No: Address: Serial No.

BC Controller (main): Model No: Address: Serial No.

Sub-BC Controller: Model No: Address: Serial No.

2nd Sub-BC Controller: Model No: Address: Serial No.

2 Line Voltage (L1 - L2):

BC Controller (single): VAC REMARKS

BC Controller (main): VAC

Sub-BC Controller: VAC

2nd Sub-BC Controller: VAC

3 Control Voltage (TB2):

BC Controller (single): VDC REMARKS

BC Controller (main): VDC

Sub-BC Controller: VDC

2nd Sub-BC Controller: VDC

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

WATER LOOP: (WR2-series Only)

° F.° F.

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Page 11: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 11 of 46

Page 12: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 12 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM:

NO. SYSTEM AND INSTALLATION STATUS REMARKS

1 Installation Location Outdoor Unit

2 Maintenance AccessibilityOutdoor Unit

Indoor Units

3 Total Piping Length Ft.

4 Furthest Piping Length Outdoor to Indoor Ft.

5 Height DifferenceOutdoor to Indoor Ft.

Indoor to Indoor (max) Ft.

6 Standard of Pipe-work

7 Standard of Pipe Insulation

8

Outdoor Unit

Indoor Units

Electrical Cable Type: Size:

9 Connection of Control System

Outdoor to Indoor

Indoor to Indoor

Indoor to RC

Control Cable Type: Size:

10 Standard of Electrical Insulation

11 Access to Remove Electrical Covers

12

Serial Number

13 Remote Controller OperationVentilation

Cool / Heat

14 Connection Options

15 Total Indoor Unit Connection Capacity Btu/h --- 0.00%

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Connection of Main Power Source

Centralized Control Method(if other, please specify in remarks column)

AG-150 TC-24

GB-50A

GB-24A None

Good Poor

Good Poor

Rooftop

Other Location

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Other

Page 13: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 13 of 46

Page 14: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 14 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM:

NO. SYSTEM AND INSTALLATION STATUS REMARKS

1 Installation Location Outdoor Unit

2 Maintenance AccessibilityOutdoor Unit

Indoor Units

3 Total Piping Length Ft.

4 Furthest Piping Length Outdoor to Indoor Ft.

5 Height DifferenceOutdoor to Indoor Ft.

Indoor to Indoor (max) Ft.

6 Standard of Pipe-work

7 Standard of Pipe Insulation

8

Outdoor Unit

Indoor Units

Electrical Cable Type: Size:

9 Connection of Control System

Outdoor to Indoor

Indoor to Indoor

Indoor to RC

Control Cable Type: Size:

10 Standard of Electrical Insulation

11 Access to Remove Electrical Covers

12

Serial Number

13 Remote Controller OperationVentilation

Cool / Heat

14 Connection Options

15 Total Indoor Unit Connection Capacity Btu/h --- 0.00%

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Connection of Main Power Source

Centralized Control Method(if other, please specify in remarks column)

Rooftop

Other Location

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

AG-150 TC-24

GB-50A

GB-24A None

Good Poor

Good Poor

Good Poor

Other

Page 15: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportGeneral Information Page 15 of 46

Page 16: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 16 of 46

CITY MULTI -- Select Series -- Commissioning Report

OUTDOOR UNIT:

OUTDOOR UNIT MODEL NUMBER: ADDITIONAL REFRIGERANT CHARGE: oz.

NO. OUTDOOR UNIT MODULES OUTDOOR UNIT #1 (OC) OUTDOOR UNIT #2 (OS1) OUTDOOR UNIT #3 (OS2)

General

1 Unit Address:

2 Model Number:

3 Serial Number:

4 Compressor Model Number:

5 Compressor Serial Number:

6 Vibration/NoiseCompressor

Fan

Line Voltage

7 Voltage L1 - L2 (VAC)

8 Voltage L2 - L3 (VAC)

9 Voltage L1 - L3 (VAC)

10 Current L1 (Amps):

11 Current L2 (Amps):

12 Current L3 (Amps):

Control Voltage

13 Control Voltage - TB3 (VDC)

14 Control Voltage - TB7 (VDC)

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Good Poor

Page 17: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 17 of 46

CITY MULTI -- Select Series -- Commissioning Report

OUTDOOR UNIT:

UNIT ADDRESS: ADDITIONAL REFRIGERANT CHARGE: oz.

General

1 Outdoor Unit Details: Model No.: Serial No.:

2 Compressor Details: Model No.: Serial No.:

3 Vibration/NoiseCompressor: REMARKS

Fan: REMARKS

Line Voltage

4 Line Voltage: L1 - L2: VAC REMARKS

5 Current (Amps): L1: Amps REMARKS

Control Voltage

6 Control Voltage:TB3: VDC REMARKS

TB7: VDC

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

Good Poor

Good Poor

Page 18: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 18 of 46

CITY MULTI -- Select Series -- Commissioning Report

OUTDOOR UNIT:

UNIT ADDRESS: ADDITIONAL REFRIGERANT CHARGE: oz.

General

1 Outdoor Unit Details: Model No.: Serial No.:

2 Compressor Details: Model No.: Serial No.:

3 Compressor Vibration/Noise: REMARKS

Line Voltage

4 Line Voltage:

L1 - L2: VAC REMARKS

L2 - L3: VAC

L1 - L3: VAC

5 Current (Amps):

L1: Amps REMARKS

L2: Amps

L3: Amps

Control Voltage

6 Control Voltage:TB3: VDC REMARKS

TB7: VDC

1 Heat Exchanger Details: Manufacturer: Serial No.:

2 Inlet Water Temperature REMARKS

3 Outlet Water Temperature REMARKS

4 Inlet Flow Rate GPM REMARKS

BRANCH CONTROLLER:

1 BC Controller Details:

BC Controller (single): Model No: Address: Serial No.

BC Controller (main): Model No: Address: Serial No.

Sub-BC Controller: Model No: Address: Serial No.

2nd Sub-BC Controller: Model No: Address: Serial No.

2 Line Voltage (L1 - L2):

BC Controller (single): VAC REMARKS

BC Controller (main): VAC

Sub-BC Controller: VAC

2nd Sub-BC Controller: VAC

3 Control Voltage (TB2):

BC Controller (single): VDC REMARKS

BC Controller (main): VDC

Sub-BC Controller: VDC

2nd Sub-BC Controller: VDC

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

WATER LOOP: (WR2-series Only)

° F.° F.

Good Poor

Page 19: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 19 of 46

Page 20: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 20 of 46

CITY MULTI -- Select Series -- Commissioning Report

OUTDOOR UNIT:

UNIT ADDRESS: ADDITIONAL REFRIGERANT CHARGE: oz.

General

1 Outdoor Unit Details: Model No.: Serial No.:

2 Compressor Details: Model No.: Serial No.:

3 Compressor Vibration/Noise: REMARKS

Line Voltage

4 Line Voltage:

L1 - L2: VAC REMARKS

L2 - L3: VAC

L1 - L3: VAC

5 Current (Amps):

L1: Amps REMARKS

L2: Amps

L3: Amps

Control Voltage

6 Control Voltage:TB3: VDC REMARKS

TB7: VDC

1 Heat Exchanger Details: Manufacturer: Serial No.:

2 Inlet Water Temperature REMARKS

3 Outlet Water Temperature REMARKS

4 Inlet Flow Rate GPM REMARKS

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

WATER LOOP: (WR2-series Only)

° F.° F.

Good Poor

Page 21: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportOutdoor Unit Page 21 of 46

Page 22: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 22 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #1 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #2 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #3 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #4 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #5 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #6 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 23: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 23 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #7 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #8 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #9 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #10 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #11 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #12 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 24: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 24 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #13 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #14 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #15 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #16 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #17 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #18 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 25: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 25 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #19 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #20 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #21 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #22 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #23 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #24 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 26: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 26 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #25 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #26 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #27 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #28 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #29 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #30 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 27: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 27 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #31 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #32 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #33 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #34 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #35 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #36 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 28: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 28 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #37 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #38 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #39 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #40 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #41 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #42 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 29: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 29 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #43 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #44 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #45 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #46 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #47 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #48 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 30: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 30 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

0 INDOOR UNIT #49 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

0 INDOOR UNIT #50 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 31: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 31 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

INDOOR UNIT #1 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

INDOOR UNIT #2 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

INDOOR UNIT #3 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

INDOOR UNIT #4 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

INDOOR UNIT #5 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

INDOOR UNIT #6 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 32: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 32 of 46

CITY MULTI -- Select Series -- Commissioning Report

INDOOR UNITS:

INDOOR UNIT #7 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

INDOOR UNIT #8 REMARKS

Model No. Unit Address Number

Serial No. Remote Controller Address Number

Location

VoltageLine Voltage VAC

Control Voltage TB5 VDC TB15 VDC

Inlet Air Temperature Cooling Heating

Outlet Air Temperature Cooling Heating

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

DB°F DB°FDB°F DB°F

DB°F DB°FDB°F DB°F

Page 33: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportIndoor Units Page 33 of 46

Page 34: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 34 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM INDEX CALCULATION:

Indoor Unit Unit Size Indoor Unit Unit Size1 0 Btu/h 26 0 Btu/h2 0 Btu/h 27 0 Btu/h3 0 Btu/h 28 0 Btu/h4 0 Btu/h 29 0 Btu/h5 0 Btu/h 30 0 Btu/h6 0 Btu/h 31 0 Btu/h7 0 Btu/h 32 0 Btu/h8 0 Btu/h 33 0 Btu/h9 0 Btu/h 34 0 Btu/h

10 0 Btu/h 35 0 Btu/h11 0 Btu/h 36 0 Btu/h12 0 Btu/h 37 0 Btu/h13 0 Btu/h 38 0 Btu/h14 0 Btu/h 39 0 Btu/h15 0 Btu/h 40 0 Btu/h16 0 Btu/h 41 0 Btu/h17 0 Btu/h 42 0 Btu/h18 0 Btu/h 43 0 Btu/h19 0 Btu/h 44 0 Btu/h20 0 Btu/h 45 0 Btu/h21 0 Btu/h 46 0 Btu/h22 0 Btu/h 47 0 Btu/h23 0 Btu/h 48 0 Btu/h24 0 Btu/h 49 0 Btu/h25 0 Btu/h 50 0 Btu/h

TOTAL: 0 Btu/h

(Total connected indoor unit capacity) (Total System Index)

0x 100 = 0.00%

0(Outdoor unit capacity)

ADDITIONAL REFRIGERANT CHARGE CALCULATION:

R2-series System (PURY) Total connected indoor unit capacity

HP: (1-1/8") Ft. x 3.88 = oz. ~ to 27 71 oz.HP: (7/8") Ft. x 2.48 = oz. 28 to 54 89 oz.HP: (3/4") Ft. x 1.73 = oz. 55 to 126 106 oz.HP: (5/8") Ft. x 1.19 = oz. 127 to 144 124 oz.Liquid: (5/8") Ft. x 2.16 = oz. 145 to 180 159 oz.Liquid: (1/2") Ft. x 1.30 = oz. 181 to 234 177 oz.Liquid: (3/8") Ft. x 0.65 = oz. 235 to 273 212 oz.Liquid: (1/4") Ft. x 0.26 = oz. 274 to 307 283 oz.

Total: 0 oz. 308 to 342 318 oz.0 (see table at right) oz. 343 to 411 353 oz.

P 0 (see table below) oz. ### 412 to ~ 424 oz.0 (see table below) oz.0 (see table below) oz.

oz.

a4ERROR MESSAGES:

P oz. 0 0 oz.P oz. 1 71 oz.P oz.P oz.P oz.P oz. 0 0 oz.P oz. 1 36 oz.P oz. 2 71 oz.P oz.P oz.

a1

a1a2a3a4

TOTAL: (in ounces):

Total Outdoor Capacity

a2 QTY HA-BC Controller

QTY Sub-BC Controller

a3

Page 35: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 35 of 46

Page 36: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 36 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM INDEX CALCULATION:

Indoor Unit Unit Size Indoor Unit Unit Size1 0 Btu/h 26 0 Btu/h2 0 Btu/h 27 0 Btu/h3 0 Btu/h 28 0 Btu/h4 0 Btu/h 29 0 Btu/h5 0 Btu/h 30 0 Btu/h6 0 Btu/h 31 0 Btu/h7 0 Btu/h 32 0 Btu/h8 0 Btu/h 33 0 Btu/h9 0 Btu/h 34 0 Btu/h

10 0 Btu/h 35 0 Btu/h11 0 Btu/h 36 0 Btu/h12 0 Btu/h 37 0 Btu/h13 0 Btu/h 38 0 Btu/h14 0 Btu/h 39 0 Btu/h15 0 Btu/h 40 0 Btu/h16 0 Btu/h 41 0 Btu/h17 0 Btu/h 42 0 Btu/h18 0 Btu/h 43 0 Btu/h19 0 Btu/h 44 0 Btu/h20 0 Btu/h 45 0 Btu/h21 0 Btu/h 46 0 Btu/h22 0 Btu/h 47 0 Btu/h23 0 Btu/h 48 0 Btu/h24 0 Btu/h 49 0 Btu/h25 0 Btu/h 50 0 Btu/h

TOTAL: 0 Btu/h

(Total connected indoor unit capacity) (Total System Index)

0x 100 = 0.00%

0(Outdoor unit capacity)

ADDITIONAL REFRIGERANT CHARGE CALCULATION:

R2-series System (PURY) Total connected indoor unit capacity

Liquid: (3/4") Ft. x 3.10 = oz. ~ to 27 71 oz.

Liquid: (5/8") Ft. x 2.15 = oz. 28 to 54 89 oz.

Liquid: (1/2") Ft. x 1.29 = oz. 55 to 126 106 oz.

Liquid: (3/8") Ft. x 0.65 = oz. 127 to 144 124 oz.

Liquid: (1/4") Ft. x 0.26 = oz. 145 to 180 160 oz.

Total: 0 oz. 181 to 234 177 oz.

0 (see table at right) oz. 235 to 273 212 oz.

oz. 274 to 307 283 oz.

308 to 342 318 oz.

343 to 411 353 oz.

412 to 480 424 oz.

481 to ~ 494 oz.

ERROR MESSAGES:

a1

a1TOTAL: (in ounces):

Page 37: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 37 of 46

Page 38: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 38 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM INDEX CALCULATION:

Indoor Unit Unit Size Indoor Unit Unit Size1 0 Btu/h 5 0 Btu/h2 0 Btu/h 6 0 Btu/h3 0 Btu/h 7 0 Btu/h4 0 Btu/h 8 0 Btu/h

TOTAL: 0 Btu/h

(Total connected indoor unit capacity) (Total System Index)

0x 100 = 0.00%

0(Outdoor unit capacity)

ADDITIONAL REFRIGERANT CHARGE CALCULATION:

R2-series System (PURY) ERROR MESSAGES:

Liquid: (3/8") Ft. x 0.65 = oz.

Liquid: (1/4") Ft. x 0.26 = oz.

Less outdoor pre-charge for up to 164' pipe length - 106 oz.

oz.

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

TOTAL: (in ounces):

Page 39: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 39 of 46

Page 40: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity Index Additional Refrigerant Charge Calculation Page 40 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM INDEX CALCULATION:

Indoor Unit Unit Size Indoor Unit Unit Size1 0 Btu/h 26 0 Btu/h2 0 Btu/h 27 0 Btu/h3 0 Btu/h 28 0 Btu/h4 0 Btu/h 29 0 Btu/h5 0 Btu/h 30 0 Btu/h6 0 Btu/h 31 0 Btu/h7 0 Btu/h 32 0 Btu/h8 0 Btu/h 33 0 Btu/h9 0 Btu/h 34 0 Btu/h

10 0 Btu/h 35 0 Btu/h11 0 Btu/h 36 0 Btu/h12 0 Btu/h 37 0 Btu/h13 0 Btu/h 38 0 Btu/h14 0 Btu/h 39 0 Btu/h15 0 Btu/h 40 0 Btu/h16 0 Btu/h 41 0 Btu/h17 0 Btu/h 42 0 Btu/h18 0 Btu/h 43 0 Btu/h19 0 Btu/h 44 0 Btu/h20 0 Btu/h 45 0 Btu/h21 0 Btu/h 46 0 Btu/h22 0 Btu/h 47 0 Btu/h23 0 Btu/h 48 0 Btu/h24 0 Btu/h 49 0 Btu/h25 0 Btu/h 50 0 Btu/h

TOTAL: 0 Btu/h

(Total connected indoor unit capacity) (Total System Index)

0x 100 = 0.00%

0(Outdoor unit capacity)

ADDITIONAL REFRIGERANT CHARGE CALCULATION:

R2-series System (PURY) Total connected indoor unit capacity

Liquid: (3/4") Ft. x 3.10 = oz. ~ to oz.

Liquid: (5/8") Ft. x 2.15 = oz. to oz.

Liquid: (1/2") Ft. x 1.29 = oz. to oz.

Liquid: (3/8") Ft. x 0.65 = oz. to oz.

Liquid: (1/4") Ft. x 0.26 = oz. to oz.

Total: 0 oz. to oz.

0 (see table at right) oz. to oz.

oz. to oz.

ERROR MESSAGES:

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

a1

a1

TOTAL: (in ounces):

Page 41: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity Index Additional Refrigerant Charge Calculation Page 41 of 46

Page 42: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCapacity index Additional Refrigerant Charge Calculation Page 42 of 46

CITY MULTI -- Select Series -- Commissioning Report

SYSTEM INDEX CALCULATION:

Indoor Unit Unit Size Indoor Unit Unit Size1 0 Btu/h 26 0 Btu/h2 0 Btu/h 27 0 Btu/h3 0 Btu/h 28 0 Btu/h4 0 Btu/h 29 0 Btu/h5 0 Btu/h 30 0 Btu/h6 0 Btu/h 31 0 Btu/h7 0 Btu/h 32 0 Btu/h8 0 Btu/h 33 0 Btu/h9 0 Btu/h 34 0 Btu/h

10 0 Btu/h 35 0 Btu/h11 0 Btu/h 36 0 Btu/h12 0 Btu/h 37 0 Btu/h13 0 Btu/h 38 0 Btu/h14 0 Btu/h 39 0 Btu/h15 0 Btu/h 40 0 Btu/h16 0 Btu/h 41 0 Btu/h17 0 Btu/h 42 0 Btu/h18 0 Btu/h 43 0 Btu/h19 0 Btu/h 44 0 Btu/h20 0 Btu/h 45 0 Btu/h21 0 Btu/h 46 0 Btu/h22 0 Btu/h 47 0 Btu/h23 0 Btu/h 48 0 Btu/h24 0 Btu/h 49 0 Btu/h25 0 Btu/h 50 0 Btu/h

TOTAL: 0 Btu/h

(Total connected indoor unit capacity) (Total System Index)

0x 100 = 0.00%

0(Outdoor unit capacity)

ADDITIONAL REFRIGERANT CHARGE CALCULATION:

R2-series System (PURY) Total connected indoor unit capacity

HP: (1-1/8") Ft. x 3.90 = oz. ~ to oz.

HP: (1") Ft. x 3.33 = oz. to oz.

HP: (7/8") Ft. x 2.47 = oz. to oz.

HP: (3/4") Ft. x 1.72 = oz. to oz.

HP: (5/8") Ft. x 1.18 = oz. to oz.

Liquid: (1/2") Ft. x 1.29 = oz. to oz.

Liquid: (3/8") Ft. x 0.65 = oz. to oz.

Liquid: (1/4") Ft. x 0.26 = oz. to oz.

Total: 0 oz.

0 (see table at right) oz. ERROR MESSAGES:

0 (see table below) oz.

oz.

0 0 oz.

1 36 oz.

2 71 oz.

COMMISSIONING AGENT'S COMMENTS AND POINTS FOR ATTENTION:

a1

a1a2

TOTAL: (in ounces):

QTY Sub-BC Controller

a2

Page 43: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportPeriodic Inspection Schedule Log Page 43 of 46

CITY MULTI -- Select Series -- Commissioning Report

PERIODIC INSPECTION:

Equipment PartsService Cycle

Service Action1 Mo. 6 Mo. 1 Yr. 2 Yr. 3 Yr. 4 Yr. 5 Yr.

Common Parts Visual inspection

Frame

Fan

Motor W W W W W W W

Check for clogging by dust

Drain Pan

Check for clogging by dust

Frame

Fan

Motor W W W W W W W

Check for clogging by dust

Compressor

External Panel

Detail ofService

When service is neglected

Insulators / PCBs

Tighten terminals as necessary on

insulators & PCBs

Nuisance tripping or failure of components

CITY MULTI Indoor Unit

Casing (Appearance)

Visual check for damage & dust appearance where

required

Clean with neutral detergent solution. Repaint if necessary

Visual check for rust. Visual check for integrity

of insulation

Repair if rusting is serious. Repair

degraded or improper insulation

Unit corrosion by rust. Condensation buildup

due to im-proper insulation

Visual check for dust/dirt buildup on fan blades,

which may lead to the fan running out of balance

Clean fan blades as necessary to prevent

out of balance run

Premature failure of fan

Visual check of wiring. Insulation resistance

check to be carried out annually

Measure insulation resistance. Should read greater than

1MW

Possible failure of motor

Heat Exchanger

Clean air inlet side as necessary

Lowered cooling / heating capacity due

to low airflow rate

Check for obstructions and free flow of water

Clean as necessary to eliminate obstruc-tions & check condi-

tion of drain pan

Overflow by clogged drain pan

High Efficiency Filter

Replace filter as necessary

Lowered cooling / heating capacity due to low air-flow rate

Temperature Readings

Measure supply and return air temperature

Measure temp. of the unit's supply and

return air

CITY MULTI Outdoor Unit

Visual check for rust. Visual check for integrity

of insulation

Repair if rusting of frame is serious.

Repair degraded or improper insulation

Unit corrosion by rust. Condensation buildup

due to im-proper insulation

Visual check for dust/dirt buildup on fan blades,

which may lead to the fan running out of balance

Clean fan blades as necessary to prevent

out of balance run

Premature failure of fan

Visual check of wiring. Insulation resistance

check to be carried out annually

Measure insulation resistance. Should read greater than

1MW

Possible failure of motor

Heat Exchanger

Clean heat exchanger coils as

necessary

Lowered cooling / heating capacity due

to low airflow rate

Check high / low pressure. Measure insulation

resistance. Audibly check compressor noise level

Measure insulation resistance. Should read greater than

1MW

Generation of abnormal sound.

Compressor burnout / lock

Operational Readings

Record operational readings in Cool / Heat

Use dipswitch SW1 functions (refer to service handbook)

Magnetic Contactor

Check for loose terminal connections

Tighten terminals as necessary

Improper contact can result in nuisance

tripping or coil burnout

Electrical Connections

Check all electrical terminal connections

(primary power, communications, etc.)

Tighten terminals as necessary on

insulators, terminals & PCB's

Improper contact can result in nuisance

tripping or premature failure of components

Visual check for damage and rust. Wax panels

periodically

Repair / repaint as necessary

NOTE: Frequency of maintenance may increase dependent upon the equipment’s environment. Failure to maintain the system to the above minimum recommendations may result in the warranty becoming null and void

Page 44: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportPeriodic Inspection Schedule Log Page 44 of 46

CITY MULTI -- Select Series -- Commissioning Report

MAINTENANCE LOG:

Maintenance Action Description / Remarks Technician's SignatureMainenance

DateCompressor Run Hours

Page 45: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCommissioning Notes Comments Page 45 of 46

CITY MULTI -- Select Series -- Commissioning Report

NOTES / COMMENTS:

Page 46: CM SL Commissioning Report 0811

Mitsubishi Electric Electronics USAHVAC Advanced Products Division

CITY MULTI Commissioning ReportCommissioning Notes Comments Page 46 of 46