    FORM X

    [See Rule 5(1)(j)]

    POWER SUPPLY INSTALLATION ABSTRACTS

    SECTION: KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY: CHENNAI METRO

    LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm

    FOR 25 KV AC Overhead Traction System

    S No Type of

    Switching Station

    Total

    Nos.

    Chainage (in

    KM)

    Location and

    Nearest

    Station

    Remarks Ref.

    Documents

    1. Traction Sub

    Stations and

    Feeding

    Points(FP)

    2 10.990 (up &

    Dn. Line)

    20.0802(up &

    Dn. Line)

    Koyambedu

    Alandur

    Sectioning

    Diagram

    2. Sectioning post

    (SNS post)

    1 11.698 CMBT Sectioning

    Diagram

    3. Sub-Sectioning

    post (SSP)

    2 15.738

    16.987

    Ashok Nagar

    Ashok Nagar

    Sectioning

    Diagram

    4 Auxiliary Sub-

    Stations

    8 10.617

    12.007

    13.278

    14.542

    16.294

    18.548

    19.826

    21.55

    Koyambedu

    CMBT

    Arumbakkam

    Vadapalani

    Ashok Nagar

    Ekkaduthangal

    Alandur

    St.Thomas

    Mount

    Power

    distribution

    diagram.

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    2/21

    FORM XI

    [See Rule 5(1)(k)]

    RESTRICTED OVERHEAD EQUIPMENT CLEARANCE ABSTRACT

    SECTION:KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO

    LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm

    A.OVER LINE STRUCTURES (Shelter for FOCS Between Alandur and St.Thomas Mount)

    S

    No

    Location of over

    line structures

    (Shelter over

    OHE)

    Total

    Struct

    ure

    Clearanc

    e from

    RL. To

    the

    bottom

    of the

    structur

    e

    Height of

    the

    Contact

    wire

    below

    the

    structure

    Whether

    catenary is

    anchored

    or freely

    running

    below /

    above the

    structure

    Minimum

    static

    clearance

    between

    25 kV

    line and

    earth

    Rema

    rks

    Ref.

    Document

    s

    1. Shelter from KM

    20.048 to KM

    20.600

    15 6.50 m 5.00 Running

    freely

    350 mm Nil OHE lay

    out plan

    SPS-423-

    C2E-

    82580-K

    sheet

    28&29

    B. Location of Over head Electrical structure where specified 2 m working clearance not available, and specia

    protection measures there for

    S No Location Type of nearest

    earthing part

    Actual

    distance

    between

    Live part

    and Earth

    (meters)

    Details

    protection

    measures

    Remarks Ref. Documents

    There is no Over head Electrical structure in Koyambedu St. Thomas mount section

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    3/21

    FORM XII

    [See Rule 5(1)(l)]

    ELECTRICAL CROSSING OVER METRO RAILWAY TRACK ABSTRACT

    SECTION:KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO

    LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm

    S

    No

    Location Brief

    technical

    particulars

    includingvoltage

    Whether

    with

    Guards

    or w/oGuard

    Owned

    by

    Whether

    clearance

    as per the

    regulationsfor

    electrical

    crossings

    available

    Remarks Ref.

    Documents

    There is no ELECTRICAL CROSSING OVER METRO RAILWAY TRACK in KOYAMBEDU

    St. THOMAS MOUNT

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    4/21

    FORM XIII

    [See Rule 5(1)(m)]

    TRACTION MAINTENANCE DEPOT ABSTRACT

    SECTION: KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO

    LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm

    S

    No

    Location Name of the nearest Metro

    Station

    Remarks Ref. Documents

    1. Koyambedu

    Depot

    Koyambedu station Nil

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    5/21

    FORM IX

    [See Rule 5(1)(i)]

    BRIEF PARTICULARS OF TRACTION INSTALATION

    SECTION:KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO

    LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm

    Over head Equipments

    1. Salient Features of the Design specially covering following aspects:a) Current carrying Capacity of the system( Annexure-A)b) Design parameters like wind speed, Tension length, Temperature range ( Annexure-B)c)

    Speed potential

    Design and operating Speed ( Annexure-C)

    d) Protection Arrangements ( Annexure-D)e) Power supply from TNSS to TSS ( Annexure-E)f) Power Distribution system from RSS to TSS ( Annexure-F)g) Power feed from TSS to OHE ( Annexure-G)h) Power Distribution system from RSS to ASS ( Annexure-H)i) Traction SCADA System ( Annexure-I)j) Earthing and Bonding System ( Annexure-J)

    (Details provided in the Annexure attached)

    2. It is Certified that all Warning Boards and Notices as per statutory requirements have been provided atSpecific locations

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    6/21

    ATTACHMENT TO FORM IX ( Annexure-A)

    Current carrying Capacity of the system

    S No DESCRIPTION Value

    1. Contact wire Hard drawn copper 150 Sq mm

    2. Catenary Wire (Messenger wire )

    Cd.Copper

    65 Sq mm

    3. Feed in point to Neutral section Koyambedu Feed in point KM

    10.990

    SNS point - KM 11.698

    Alandur Feed in point KM

    20.0802

    4. Current carrying Capacity of the system 600 Amps

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    7/21

    ATTACHMENT TO FORM IX ( Annexure-B)

    Design parameters like wind speed, Tension length, Temperature range

    S No Description Value

    1. Wind speed 1m/s (112.5 kg/hr)

    2. Temperature range 16 to 45 celsius

    3. Tension of Catenary Wire

    Tension of Contact Wire

    Tension length

    12 kN

    12 kN

    1700 m

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    8/21

    ATTACHMENT TO FORM IX ( Annexure-C)

    Speed potential Design and operating Speed

    S No Description Value

    1. Design Speed 100 Km/Hr.

    2. Operating Speed 80 Km/Hr.

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    9/21

    ATTACHMENT TO FORM IX ( Annexure-D)

    Protection Arrangements

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    10/21

    ATTACHMENT TO FORM IX ( Annexure-E)

    Power supply from TNSS to RSS

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    11/21

    ATTACHMENT TO FORM IX ( Annexure-F)

    Power Distribution system from RSS to TSS

  • 7/30/2019 CMRS Forms.docx

    12/21

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    13/21

    ATTACHMENT TO FORM IX ( Annexure-G)

    Power feed from TSS to OHE

  • 7/30/2019 CMRS Forms.docx

    14/21

    S No Description Location No.

    1. Koyambedu TSS to Koyambedu - Test track DP-306

    2. Koyambedu TSS to -Koyambedu Depot DP-115

    3. Koyambedu TSS to - Up main Corridor - 2 10/55A

    4 Koyambedu TSS to -Down main Corridor - 2 DP/56A

    5 Alandur TSS to - Up main Corridor - 2 20/5A

    6 Alandur TSS to -Down main Corridor - 2 20/6A

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    15/21

    ATTACHMENT TO FORM IX ( Annexure-H)

    Power Distribution system from RSS/TSS to ASS

  • 7/30/2019 CMRS Forms.docx

    16/21

  • 7/30/2019 CMRS Forms.docx

    17/21

    S No Feeding Station Receiving Station

    1. Koyambedu TSS Koyambedu station

    2. Koyambedu TSS CMBT3. Koyambedu TSS Arumbakkam

    4 Koyambedu TSS Vadapalani

    5 Alandur TSS Ekkaduthangal

    6 Alandur TSS Alandur

    7 Alandur TSS St. Thomas Mount

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    18/21

    ATTACHMENT TO FORM IX ( Annexure-I)

    Traction SCADA System

  • 7/30/2019 CMRS Forms.docx

    19/21

  • 7/30/2019 CMRS Forms.docx

    20/21

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL

  • 7/30/2019 CMRS Forms.docx

    21/21

    ATTACHMENT TO FORM IX ( Annexure-J)

    Earthing and Bonding System in viaduct

    S No Earthing System Connection type

    1. Buried Earth conductor(BEC)

    35 sq mm copper wire

    Running from Koyambedu to St. Thomas mount

    on Up and Down line

    In the cable tray.

    2. Aerial Earth wire93.0 sq mm ACSR conductor

    Running from Koyambedu to St. Thomas mounton Up and Down line

    And supported on all mast/DA/Portals

    3. Earth electrode for Viaduct The viaduct is supported at regular interval by

    piers. In each viaduct pier some dedicated

    reinforcement rods are taken from the top to the

    bottom of the pier. This acts as earth electrode for

    the pier. This is connected to the viaduct segment

    and parapets reinforcement rods .The same is

    connected to BEC at an interval of 200 m

    4. RETURN CURRENT BUSBAR(MAIN

    LINE)

    Near feed in points

    5. MAIN EARTH TERMINAL On either end of the station and in between

    stations

    6. EARTHING CONNECTION

    BETWEEN BUSBAR AND BUSBAR

    Connection between the Main earth terminals

    7. EARTHING CONNECTION

    BETWEEN BUSBAR AND TRACK

    At feed in points

    8. CONNECTION BETWEEN RAIL-RAIL At either end of each station

    9. CONNECTION BETWEEN BUSBAR -

    BEC

    On either end of the station and in between

    stations

    10 Mast to BEC connection On either end of the station and in between

    stations

    5. BEC to traction rail connection At S bond locations

    6. Up line rail to down line rail At regular interval of 200 m.

    7. Hand rail to BEC At regular interval of 200 m.

    8. Platform reinforcement to BEC-

    MET

    At both ends of the platform.

    Signature

    Name

    Designation

    Responsible (Contractor) (Contractor) GC CMRL