FORM X
[See Rule 5(1)(j)]
POWER SUPPLY INSTALLATION ABSTRACTS
SECTION: KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY: CHENNAI METRO
LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm
FOR 25 KV AC Overhead Traction System
S No Type of
Switching Station
Total
Nos.
Chainage (in
KM)
Location and
Nearest
Station
Remarks Ref.
Documents
1. Traction Sub
Stations and
Feeding
Points(FP)
2 10.990 (up &
Dn. Line)
20.0802(up &
Dn. Line)
Koyambedu
Alandur
Sectioning
Diagram
2. Sectioning post
(SNS post)
1 11.698 CMBT Sectioning
Diagram
3. Sub-Sectioning
post (SSP)
2 15.738
16.987
Ashok Nagar
Ashok Nagar
Sectioning
Diagram
4 Auxiliary Sub-
Stations
8 10.617
12.007
13.278
14.542
16.294
18.548
19.826
21.55
Koyambedu
CMBT
Arumbakkam
Vadapalani
Ashok Nagar
Ekkaduthangal
Alandur
St.Thomas
Mount
Power
distribution
diagram.
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
2/21
FORM XI
[See Rule 5(1)(k)]
RESTRICTED OVERHEAD EQUIPMENT CLEARANCE ABSTRACT
SECTION:KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO
LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm
A.OVER LINE STRUCTURES (Shelter for FOCS Between Alandur and St.Thomas Mount)
S
No
Location of over
line structures
(Shelter over
OHE)
Total
Struct
ure
Clearanc
e from
RL. To
the
bottom
of the
structur
e
Height of
the
Contact
wire
below
the
structure
Whether
catenary is
anchored
or freely
running
below /
above the
structure
Minimum
static
clearance
between
25 kV
line and
earth
Rema
rks
Ref.
Document
s
1. Shelter from KM
20.048 to KM
20.600
15 6.50 m 5.00 Running
freely
350 mm Nil OHE lay
out plan
SPS-423-
C2E-
82580-K
sheet
28&29
B. Location of Over head Electrical structure where specified 2 m working clearance not available, and specia
protection measures there for
S No Location Type of nearest
earthing part
Actual
distance
between
Live part
and Earth
(meters)
Details
protection
measures
Remarks Ref. Documents
There is no Over head Electrical structure in Koyambedu St. Thomas mount section
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
3/21
FORM XII
[See Rule 5(1)(l)]
ELECTRICAL CROSSING OVER METRO RAILWAY TRACK ABSTRACT
SECTION:KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO
LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm
S
No
Location Brief
technical
particulars
includingvoltage
Whether
with
Guards
or w/oGuard
Owned
by
Whether
clearance
as per the
regulationsfor
electrical
crossings
available
Remarks Ref.
Documents
There is no ELECTRICAL CROSSING OVER METRO RAILWAY TRACK in KOYAMBEDU
St. THOMAS MOUNT
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
4/21
FORM XIII
[See Rule 5(1)(m)]
TRACTION MAINTENANCE DEPOT ABSTRACT
SECTION: KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO
LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm
S
No
Location Name of the nearest Metro
Station
Remarks Ref. Documents
1. Koyambedu
Depot
Koyambedu station Nil
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
5/21
FORM IX
[See Rule 5(1)(i)]
BRIEF PARTICULARS OF TRACTION INSTALATION
SECTION:KOYAMBEDU St. THOMAS MOUNT METRO RAILWAY : CHENNAI METRO
LENGTH: 11.7942 KMS. (KM 9.5794 to KM 21.3736) GAUGE: 1435 mm
Over head Equipments
1. Salient Features of the Design specially covering following aspects:a) Current carrying Capacity of the system( Annexure-A)b) Design parameters like wind speed, Tension length, Temperature range ( Annexure-B)c)
Speed potential
Design and operating Speed ( Annexure-C)
d) Protection Arrangements ( Annexure-D)e) Power supply from TNSS to TSS ( Annexure-E)f) Power Distribution system from RSS to TSS ( Annexure-F)g) Power feed from TSS to OHE ( Annexure-G)h) Power Distribution system from RSS to ASS ( Annexure-H)i) Traction SCADA System ( Annexure-I)j) Earthing and Bonding System ( Annexure-J)
(Details provided in the Annexure attached)
2. It is Certified that all Warning Boards and Notices as per statutory requirements have been provided atSpecific locations
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
6/21
ATTACHMENT TO FORM IX ( Annexure-A)
Current carrying Capacity of the system
S No DESCRIPTION Value
1. Contact wire Hard drawn copper 150 Sq mm
2. Catenary Wire (Messenger wire )
Cd.Copper
65 Sq mm
3. Feed in point to Neutral section Koyambedu Feed in point KM
10.990
SNS point - KM 11.698
Alandur Feed in point KM
20.0802
4. Current carrying Capacity of the system 600 Amps
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
7/21
ATTACHMENT TO FORM IX ( Annexure-B)
Design parameters like wind speed, Tension length, Temperature range
S No Description Value
1. Wind speed 1m/s (112.5 kg/hr)
2. Temperature range 16 to 45 celsius
3. Tension of Catenary Wire
Tension of Contact Wire
Tension length
12 kN
12 kN
1700 m
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
8/21
ATTACHMENT TO FORM IX ( Annexure-C)
Speed potential Design and operating Speed
S No Description Value
1. Design Speed 100 Km/Hr.
2. Operating Speed 80 Km/Hr.
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
9/21
ATTACHMENT TO FORM IX ( Annexure-D)
Protection Arrangements
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
10/21
ATTACHMENT TO FORM IX ( Annexure-E)
Power supply from TNSS to RSS
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
11/21
ATTACHMENT TO FORM IX ( Annexure-F)
Power Distribution system from RSS to TSS
-
7/30/2019 CMRS Forms.docx
12/21
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
13/21
ATTACHMENT TO FORM IX ( Annexure-G)
Power feed from TSS to OHE
-
7/30/2019 CMRS Forms.docx
14/21
S No Description Location No.
1. Koyambedu TSS to Koyambedu - Test track DP-306
2. Koyambedu TSS to -Koyambedu Depot DP-115
3. Koyambedu TSS to - Up main Corridor - 2 10/55A
4 Koyambedu TSS to -Down main Corridor - 2 DP/56A
5 Alandur TSS to - Up main Corridor - 2 20/5A
6 Alandur TSS to -Down main Corridor - 2 20/6A
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
15/21
ATTACHMENT TO FORM IX ( Annexure-H)
Power Distribution system from RSS/TSS to ASS
-
7/30/2019 CMRS Forms.docx
16/21
-
7/30/2019 CMRS Forms.docx
17/21
S No Feeding Station Receiving Station
1. Koyambedu TSS Koyambedu station
2. Koyambedu TSS CMBT3. Koyambedu TSS Arumbakkam
4 Koyambedu TSS Vadapalani
5 Alandur TSS Ekkaduthangal
6 Alandur TSS Alandur
7 Alandur TSS St. Thomas Mount
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
18/21
ATTACHMENT TO FORM IX ( Annexure-I)
Traction SCADA System
-
7/30/2019 CMRS Forms.docx
19/21
-
7/30/2019 CMRS Forms.docx
20/21
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL
-
7/30/2019 CMRS Forms.docx
21/21
ATTACHMENT TO FORM IX ( Annexure-J)
Earthing and Bonding System in viaduct
S No Earthing System Connection type
1. Buried Earth conductor(BEC)
35 sq mm copper wire
Running from Koyambedu to St. Thomas mount
on Up and Down line
In the cable tray.
2. Aerial Earth wire93.0 sq mm ACSR conductor
Running from Koyambedu to St. Thomas mounton Up and Down line
And supported on all mast/DA/Portals
3. Earth electrode for Viaduct The viaduct is supported at regular interval by
piers. In each viaduct pier some dedicated
reinforcement rods are taken from the top to the
bottom of the pier. This acts as earth electrode for
the pier. This is connected to the viaduct segment
and parapets reinforcement rods .The same is
connected to BEC at an interval of 200 m
4. RETURN CURRENT BUSBAR(MAIN
LINE)
Near feed in points
5. MAIN EARTH TERMINAL On either end of the station and in between
stations
6. EARTHING CONNECTION
BETWEEN BUSBAR AND BUSBAR
Connection between the Main earth terminals
7. EARTHING CONNECTION
BETWEEN BUSBAR AND TRACK
At feed in points
8. CONNECTION BETWEEN RAIL-RAIL At either end of each station
9. CONNECTION BETWEEN BUSBAR -
BEC
On either end of the station and in between
stations
10 Mast to BEC connection On either end of the station and in between
stations
5. BEC to traction rail connection At S bond locations
6. Up line rail to down line rail At regular interval of 200 m.
7. Hand rail to BEC At regular interval of 200 m.
8. Platform reinforcement to BEC-
MET
At both ends of the platform.
Signature
Name
Designation
Responsible (Contractor) (Contractor) GC CMRL