APPLICATION NOTICE: CONTROLS RELATED PRODUCTS All Mr. Slim Indoor Units CITY MULTI Controls Network MHK-1 RedLINK Wireless Wall Mounted Remote Controller Kit MAC-399IF MNET Interface for M-Series MAC-397IF MA & Contact Terminal Interface The MHK-1 Kit, MAC-399IF, and MAC-397IF Interfaces connect to Mr. Slim indoor unit control boards on CN105. Only ONE interface at a time can be connected to an indoor unit. Example A: If using a MNET Interface on a M-Series indoor unit for BACnet or LonWorks, and need zone level control, use the BMS front end or a central controller (AG-150/GB-50ADA) or a wireless handheld remote controller. Example B: If using a MA & Contact Terminal Interface on a Model MFZ, MSZ, or MSY indoor unit for use with a PAR-21MAAU or On/Off control, a MNET Interface or MHK-1 Kit cannot be used . Example C: If using a PAR-21MAAU on a SEZ or SLZ connecting to TB15, a MNET Interface can be used. Example D: If using a MNET Interface on a P-Series outdoor unit (PAC-SF81MA) for BACnet or LonWorks, and need zone level control, use a MHK-1 RedLINK Wireless Wall Mounted Remote Controller Kit or a PAR-21MAAU connecting to TB-15 (SEZ, SLZ, PEAD, PEA) or TB5 (PKA, PCA, PLA). This product notice is for indoor units only, P-Series ODU is unaffected. January 2012 rev 2 Gunder & Associates, LLC. Engineered Products Group 1 Mr. Slim IDU 2 Interface Unit using CN105 MIFH1 Wireless Receiver MAC-399IF MAC-397IF 3 Remote Controller MRCH-1 Wireless Remote Controller PAR-21MAA Deluxe MA PAR-F27MA ME Remote Controller MAC-821SC-E CN105 3 1 2

Upload: john-chavez

Post on 26-Jul-2015

160 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: CN105 Gunder notice_jan_2012rev2

APPLICATION NOTICE: CONTROLS

RELATED PRODUCTS

All Mr. Slim Indoor UnitsCITY MULTI Controls Network

MHK-1 RedLINK Wireless Wall Mounted Remote Controller KitMAC-399IF MNET Interface for M-Series

MAC-397IF MA & Contact Terminal Interface

The MHK-1 Kit, MAC-399IF, and MAC-397IF Interfaces connect to Mr. Slim indoor unit control boards on CN105. Only ONE interface at a time can be connected to an indoor unit.

Example A:

If using a MNET Interface on a M-Series indoor unit for BACnet or LonWorks, and need zone level control, use the BMS front end or a central controller (AG-150/GB-50ADA) or a wireless handheld remote controller.

Example B:

If using a MA & Contact Terminal Interface on a Model MFZ, MSZ, or MSY indoor unit for use with a PAR-21MAAU or On/Off control, a MNET Interface or MHK-1 Kit cannot be used.

Example C:

If using a PAR-21MAAU on a SEZ or SLZ connecting to TB15, a MNET Interface can be used.

Example D:

If using a MNET Interface on a P-Series outdoor unit (PAC-SF81MA) for BACnet or LonWorks, and need zone level control, use a MHK-1 RedLINK Wireless Wall Mounted Remote Controller Kit or a PAR-21MAAU connecting to TB-15 (SEZ, SLZ, PEAD, PEA) or TB5 (PKA, PCA, PLA). This product notice is for indoor units only, P-Series ODU is unaffected.

January 2012 rev 2   Gunder & Associates, LLC. Engineered Products Group

1 Mr. Slim IDU

2 Interface Unit using CN105" MIFH1 Wireless Receiver" MAC-399IF" MAC-397IF"3 Remote Controller" MRCH-1 Wireless Remote Controller" PAR-21MAA Deluxe MA" PAR-F27MA ME Remote Controller MAC-821SC-E

CN105

3

1 2