1 COBALT PRO series 296÷1983 kW Unique selling points Full inverter and hybrid versions available Up to 2 MW cooling and heating capacity High seasonal efficiency Eurovent A Class Unit Multilogic function Integrated web server Microchannel condensing coil Low refrigerant charge Wide operating limits Integrated hydraulic modules also with a buffer tank. Three types of pumps: standard, oversize and for high percentages of glycol (e.g. up to 50%). General High energy efficiency chillers with screw compressors also driven by inverter and shell&tube exchanger Configurations HE: High efficiency unit LN: Low noise unit SLN: Super Low noise unit HP: Reversible heat pump DS: Unit with desuperheaters DC: Heat exchange condenser HAT: unit for high temperature of external air HWT: unit for production of water at high temperature HEi: unit with hybrid compressors XEi: unit with full inverter compressors Pump and integrated buffer tank available as option

Upload: hakhanh

Post on 27-Jul-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

1

COBALT PRO series296÷1983 kW

Unique selling points

► Full inverter and hybrid versions available

► Up to 2 MW cooling and heating capacity

► High seasonal efficiency

► Eurovent A Class Unit

► Multilogic function

► Integrated web server

► Microchannel condensing coil

► Low refrigerant charge

► Wide operating limits

► Integrated hydraulic modules also with a buffer tank.

► Three types of pumps: standard, oversize and for high percentages of glycol (e.g. up to 50%).

GeneralHigh energy efficiency chillers with screw compressors also driven by inverter and shell&tube exchanger

Configurations HE: High efficiency unit

LN: Low noise unit

SLN: Super Low noise unit

HP: Reversible heat pump

DS: Unit with desuperheaters

DC: Heat exchange condenser

HAT: unit for high temperature of external air

HWT: unit for production of water at high temperature

HEi: unit with hybrid compressors

XEi: unit with full inverter compressors

Pump and integrated buffer tank available as option

2Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

INDEXTECHNICAL FAETURES 3ACCESSORIES 6TECHNICAL DATA - COBALT PRO 8TECHNICAL DATA - COBALT PRO 9TECHNICAL DATA - COBALT PRO 10TECHNICAL DATA - COBALT PRO HE 11TECHNICAL DATA - COBALT PRO HE 12TECHNICAL DATA - COBALT PRO HE 13TECHNICAL DATA - COBALT PRO SLN 14TECHNICAL DATA - COBALT PRO SLN 15TECHNICAL DATA - COBALT PRO SLN 16TECHNICAL DATA - COBALT PRO HEi 17TECHNICAL DATA - COBALT PRO XEi 18ELECTRICAL DATA - COBALT PRO 19ELECTRICAL DATA COBALT PRO HE - COBALT PRO SLN 20ELECTRICAL DATA - COBALT PRO HEi 21ELECTRICAL DATA - COBALT PRO XEi 21OPERATING LIMITS 22COBALT PRO 22COOLING 22HEATING 22RECOVERY 22OPERATING LIMITS 23COBALT PRO HE 23COOLING 23HEATING 23RECOVERY 23OPERATING LIMITS 24COBALT PRO HEi 24OPERATING LIMITS 24COBALT PRO XEi 24COOLING 24COOLING 24NOISE LEVELS 25COBALT PRO 25NOISE LEVELS 25COBALT PRO LN 25NOISE LEVELS 26COBALT PRO HE 26NOISE LEVELS 26COBALT PRO HE LN 26NOISE LEVELS 27COBALT PRO HE SLN 27NOISE LEVELS 28COBALT PRO HEi 28NOISE LEVELS 28COBALT PRO HEi LN 28NOISE LEVELS 29COBALT PRO XEi 29NOISE LEVELS 29COBALT PRO XEi LN 29DIMENSIONAL DRAWING 30DIMENSIONAL DRAWING 32DIMENSIONAL DRAWING 34DIMENSIONAL DRAWING 35

3Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

COBALT PRO

TECHNICAL FAETURESAir-cooled water chiller unit with semi-hermetic screw com-pressors and shell and tube evaporators.

STRUCTUREHolding frame module made of galvanised sheet metal and painted with polyester powders RAL 5014 at 180°C, which guarantee very high resistance to atmospheric agents. Stain-less steel bolts and screws.

COMPRESSORS (version basic, HE and SLN)Screw semihermetic compressors with continuous partialisa-tion from 25% to 100% of the load, which enable to maximise the energy yield of the unit in every functioning condition. Start-up and switch off of the machine happen with a partia-lisation of 25%.

The compressors are equipped with a carter heater, ensure lubrication from the pressure difference between flow and intake, independent cooling circuits.

The motor has an electronic integral protection with tempera-ture sensors directly inserted inside the windings and on the flow piping. Start-up is the ”star-delta” type..

COMPRESSORS (varsion HEi)Version units provide HEi 1 compressor (for units with 2 or 3 circuits) or 2 compressors (for units with 4-circuit) driven by an inverter. SI is semi-hermetic screw compressors with integrated AC inverter and stepless from 25% to 100%.

The other unit compressors are semi-hermetic screw com-pressors with stepped.

The shutting of the entire unit is always of the continuous type, by the minimum step of capacity (the number of compressors) up to 100%.

Goodwill compressor inverter is ”Direct On Line” with an ac-celeration ramp managed by the inverter while the start-up of steps compressor steps is the “star-delta” type.

COMPRESSORS (version XEi)Semi-hermetic screw compressors with integrated AC inverter and stepless partialization from 25% to 100%.

The start of the compressors is ”Direct On line” with an ac-celeration ramp managed by the inverter

CONDENSERS In cooling only units consisting of aluminum microchannel coils, instead are an alluminium-finned copper-tube multi-row coils in the heat pump units.

Through continuous research in the field of metal alloys and sophisticated production techniques, microchannel coils are made using specific aluminum alloys for the tubes and the fins. This drastically reduces the effects of galvanic corrosion, always guaranteeing the protection of pipes that contain the refrigerant. Tubes and fins are also subjected to processes of SilFLUX coating (or equivalent) or the addition of zinc to further

increase the corrosion resistance.

Optional e-coated microchannel coils are available if the unit needs to be installed in environments with a particularly ag-gressive atmosphere. They are strongly recommended for use in coastal or highly industrialised areas.

Using microchannel coils instead of those in copper/aluminum reduce the overall weight of the unit by approx. 10% and that of the refrigerant charge by a least 30%.

The layout of the ”V” coils makes the unit very compact and simultaneously guarantee an increase in the air intake area leaving ample space for the cooling and hydraulic circuit com-ponents to be set.

To protect the exchangers from corrosion and to ensure the unit operates properly, follow the recommendations reported in the use, installation and maintenance manual to clean the coils.

For installations within one kilometre from the coast, we strongly recommend using Cu/Al coils with an anti-corrosion treatment for cold-only units as well.

ELECTRIC FANSOf axial type, with conveyor, studied to optimise efficiency and reduce sound

emission, directly coupled to 6 poles three phase electric mo-tor, with thermal

protection (internal klixon). The protection rating of the motor is IP 54. The fan

includes the accident-prevention grill

EVAPORATORCoating and dry expansion shell and tube.

Optimised for use with R134a, allows to improve the unit COP, containing cooling load and overall sizes.

Insulated with a closed cell expanded material coating and equipped with a temperature probe for the anti-freeze protec-tion of every exchanger

REFRIGERANT CIRCUIT Includes: compressor flow cock, liquid shut-off cock, load in-let, liquid indicator, solid cartridge dehydrator filter, electronic expansion valve, (also acting as a solenoid valve, closing during stops), pressure transducer for reading, from control, the high and low pressure values and relative evaporation and conden-sation temperatures, high and low pressure pressure switches and safety valve.

ELECTRIC CONTROL BOARDThe board includes:

• Main isolating switch;

• Fuses to protect the auxiliary and power circuits;

• Compressors remote control switches;

4Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

• Fans remote control switches;

• Microprocessor for control of the following functions:

- Water temperature adjustment, with control of outlet wa-ter;

- Anti-freeze protection;

- Compressors timing;

- Compressors start-up sequence automatic rotation;

- Alarms signal;

- Alarms reset;

- Partialisation;

- Alarm cumulative contact for remote signal;

- Forcing of partialisation for pressure limit;

- Registration of alarms history;

- RS485 serial port with Modbus protocol

- Ethernet port with integrated webserver

• Display of:

- Temperature of the outlet water;

- Set temperature and differentials set-point;

- Description of the alarms;

- Counter functioning and number of unit, of the com-pressors and pumps (if present);

- High and low pressure, and relative condensation and evaporation temperatures.

• Electric power supply [V/f/Hz]: 400/3~/50 ±5%

CHECKS AND SAFETY DEVICES• High pressure double pressure switch with manual re-inser-

tion for every compressor;

• High pressure safety with automatic re-insertion at limited interventions managed by control;

• Low pressure safety with automatic re-insertion at limited interventions managed by control;

• High pressure safety valve;

• Anti-freeze probe at the outlet of every evaporator;

• Cooled water temperature control probe (located at system flow);

• Compressors and fans over-temperature protection

• Water differential pressure switch

TESTINGAll units are factory tested and supplied complete with oil and refrigerant charge.

COBALT PRO HEThis unit is fitted with smaller compressors and bigger cop-per tube aluminium finned coils, in order to enhance the ratio between heat exchange surfaces and compressor power. This results in greater energy efficiency (high EER and COP) and high seasonal efficiency ratio (ESEER).

COBALT PRO SLN The unit has a soundproofed compressor compartment as in the /LN version, meaning that the fans can run at lower speeds so that at nominal operating conditions the airflow – and consequently the noise level – is less than in the standard version. However, the fan-speed control makes the fans run at full speed when required by the outdoor air temperature, so the unit works within the same operating range of the COBALT PRO HE

COBALT PRO HEiAlso called ”hybrid unit”, in this version the unit uses a com-pressor driven by an inverter together with one or more con-ventional compressors. The control handle the mix of these compressor ensuring ongoing management of partilization from the minimum step up to 100% of the capacity.

The unit is highly efficient with ESEER levels that exceed 4.6.

COBALT PRO XEiFull Inverter version, uses compressors driven by inverter only. The control manages the partialization of the compressors in order to guarantee, in every load condition, the maximum effi-ciency of the unit, reaching levels of ESEER that, in combination with the of EC fans, exceeds 5

/HP: reversible heat pumpAs well as the components of the corresponding base range, the units include:

4-way inversion valve, intake separator, liquid accumulator, se-cond electronic expansion valve. Enabling of the microproces-sor for summer/winter switch-over and automatic defrosting, with Blue Box Patented logic that allows to

optimise the intervention and the duration of defrosting, which is managed independently for every compressor

Options

/DC: unit with recovery condenserAs well as the components of the corresponding base range, on every refrigerant circuit the unit includes a recovery con-denser of 100% of the condensation heat for the production of hot water, a liquid receiver and the refrigerant system for emptying the refrigerant fluid from the condensing coil, when necessary, when recovery is activated. The condenser might be as shell or tube type. The control automatically manages the activation of the recovery on the basis of the water tempera-ture and the deactivation of the safety device of the recovery itself due to high pressure. Not available in the HP version.

/DS: unit with desuperheatersAs well as the components of the corresponding basic ver-sion, on every refrigerant circuit the unit has a recovery heat exchanger of 20% of condensation heat, placed in series with the condensing coil. The heat exchanger is the braze-welded

5Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

plate type or shell and tube. To maximise the use of the ac-cessory, coupling with the fan rev. regulator is recommended. This version is also available in the HP set-up. In this case the interception of the recovery water circuit must be envisioned in installation during functioning in HP mode, as indicated in the manual.

/LN: low noise unitAs well as the components of the corresponding base range, the unit envisions the compressors compartment completely noise insulated with sound absorbing material and sound im-peding material .

/HAT: High Air TemperatureThe accessory allows the unit to work with outside air tempe-ratures above 45°C as shown in the operating limits specified in the dedicated section and consists of the use, inside the electrical panel, raceways resistant to high temperatures, spe-cial cables and oversized protection.

/HWT: High Water temperatureThanks to the compressors with dedicated electric motor, al-lows to reach temperatures of water produced that are higher than the standard range

/ST: hydraulic module unitThe unit can be supplied with an insulated inertial storage tank and circulation pumps. The following configurations are possible:

• /ST 1P: with 1 pump

• /ST 1PS: with 1 pump and tank

• /ST 2P: with 2 pumps

• /ST 2PS: with 2 pumps and tank

All hydronic models are also available in the following versions:

• For PM and PMS: with increased working head pumps, with and without an inertial tank.

• For PG and PGS: with pumps suitable to work with fluids with glycol up to 50%, with and without a tank.

The version with 2 circulation pumps (one on stand-by for the other, both sized for 100% capacity) switches automatically in case of a fault or if timed. The following accessories will also be included: expansion tank, check valves (with the exception of the 1P and 1PS version) and an intake gate valve (only in the versions with a tank).

.

6Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

ACCESSORIESRefrigerant circuit accessories• Condensing control with fans speed adjuster

• Pressure gauges

• Liquid receiver (standard on HP and DC versions)

• Compressor suction valves

• Dual relief safety valve (CH units)

• Dual relief safety valve (HP or DC units)

• Liquid line solenoid valve

• Capacitive buffer battery for electronic thermostatic valve

• Brine Kit

• Refrigerant leak detection

• Refrigerant leak detection and automatic pump down

Fans accessories• EC fans

• Oversized EC fans

• Pressure recovery

Hydraulic circuit accessories• Insulated pumps vane

• Inverter driven pump on user side (for modules with 1 or 2 standard pumps)

• Inverter driven pump on user side (for modules with 1 or 2 oversized pumps)

• Inverter driven pump on user side (for modules with 1 or 2 pumps for glycole between 40 and 50%)

• No-frost electric heater (version ST excluded)

• No-frost electric heater (for ST 1P-2P versions)

• No-frost electric heater (for ST 1PS-2PS versions)

• Safety valve on water side

• Flowswitch

Electrical accessories• BACnet protocol over TCP-IP

• Lon Gateway

• Multilogic function for Master unit to manage up to 2 Slaves

• Multilogic function for Master unit to manage up to 6 Slaves

• Multilogic function for Slave unit

• Limitation of absorbed current by digital input

• Limitation of absorbed current by integrated meter

• Power factor correction cos Ø ≥ 0,9

• Dual set point from digital input

• Variable set-point by remote signal (0-1V, 0-10V, 4-20mA)

• Set point compensated according to external air tempera-ture

• Relè for management of 1 external pump

• Relè for management of 2 external pumps

• Electronic soft-starter

• Remote shared terminal

• Power supply 400/3/50

• Power supply 415/3/50

• Double power supply with manual switching

• Double power supply with automatic switching

• Maximum and minimum voltage relay

• Automatic circuit breakers (instead of fuses)

• Unit shutdown for temperatures below the operating limits

• Heater for electrical panel

• SMARTLINK (Mandatory accessory for Swegon Solutions)

Various accessories• Rubber antivibration mounts

• Spring antivibration mounts

• Anti-intrusion grills

• E-coated microchannel coils (for chiller version only)

• Cu/Al Coils (for chiller version only)

• Pre-painted aluminium condensing coil (for /HP version only)

• Condensing coil treated with anti-corrosion paint (for chiller version only)

• Condensing coil treated with anti-corrosion paint (for /HP version only)

• Partially assembled execution

• Special pallet/skid for shipping in container

• Water filter

7Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

8Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PROCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

33.2 35.2 37.2 40.2 43.2 51.2 54.2 58.2 67.2 73.2 80.2

kW 308 340 373 410 459 483 539 612 689 736 787(2) kW 107 110 128 148 168 173 193 224 243 253 264

2,88 3,09 2,92 2,77 2,73 2,79 2,79 2,73 2,84 2,91 2,98

kW 307 339 371 408 458 482 537 611 687 734 785(2) kW 108 111 129 150 169 175 195 226 245 255 266

2,85 3,05 2,88 2,73 2,70 2,75 2,75 2,70 2,80 2,87 2,95C B C C C C C C C C B

3,60 3,82 3,71 3,65 3,64 3,66 3,67 3,65 3,61 3,61 3,60

kW 297 329 359 394 440 464 518 588 662 708 758(2) kW 109 112 130 151 172 177 197 229 248 258 269

2,72 2,94 2,75 2,61 2,55 2,61 2,63 2,56 2,67 2,74 2,82

kW 296 328 358 392 439 463 517 586 660 705 756(2) kW 110 113 132 153 173 179 199 231 250 260 271

2,69 2,90 2,72 2,57 2,53 2,59 2,60 2,54 2,64 2,71 2,79D B C D D D D D D C C

3,48 3,72 3,59 3,52 3,49 3,53 3,55 3,51 3,48 3,49 3,49

kW 302 333 368 401 435 472 533 614 668 722 775(2) kW 96 104 116 128 140 150 170 196 213 226 239

3,13 3,21 3,18 3,14 3,11 3,14 3,13 3,13 3,14 3,20 3,24

kW 302,9 334,1 369,8 403,0 436,4 473,2 534,8 615,9 670,0 724,3 777,2(2) kW 97,26 104,80 117,41 129,66 140,89 151,45 171,86 198,06 214,83 228,51 241,09

3,11 3,19 3,15 3,11 3,10 3,12 3,11 3,11 3,12 3,17 3,22B B B B B B B B B B A

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2% 12% 13% 13% 11% 13% 12% 12% 12% 13% 12% 13%kg 39 44 44 46 43 48 52 63 70 75 83kg 108 128 128 130 127 147 166 190 211 230 253

n° 5 6 6 6 6 7 8 9 10 11 12m3/h 21000 / 20000

n° 1 1 1 1 1 1 1 1 1 1 1(6) m3/h 53,0 58,5 64,1 70,5 78,9 83,1 92,7 105,3 118,5 126,6 135,3(6) m3/h 51,0 56,5 61,7 67,7 75,7 79,8 89,2 101,1 113,8 121,7 130,3(6) kPa 32 38 44 54 28 40 48 35 43 48 33(6) kPa 30 35 41 50 26 30 36 33 40 45 30

P2 P2 P2 P3 P3 P7 P7 P8 P8 P13 P13l - - - - - 740 740 740 740 900 900

kPa 227 210 191 251 249 223 207 249 215 234 242kPa 204 184 161 216 227 198 179 216 199 217 223

P3 P3 P3 P4 P4 P8 P8 P9 P9 P14 P14kPa 309 294 276 305 297 260 244 320 287 285 293kPa 287 268 246 270 275 236 215 286 271 268 274

P19 P20 P20 P21 P21 P21 P21 P13 P13 P22 P22kPa 182 243 205 204 209 183 193 187 200 184 196kPa 149 204 158 150 178 147 151 135 178 160 169

(5) dB(A) 94 95 95 96 96 97 98 98 99 100 100(4) dB(A) 62 63 63 64 64 65 66 66 67 67 67(5) dB(A) 89 90 90 91 91 92 93 93 94 95 95(4) dB(A) 57 58 58 59 59 59 61 60 62 63 63

mm 3870 3870 3870 3870 3870 5020 5020 6165 6165 7310 7310mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

9Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PROCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

85.2 90.2 95.2 100.2 105.2 115.2 120.2 130.2 140.3 150.3 160.3

kW 840 890 952 995 1047 1115 1203 1291 1442 1500 1546(2) kW 293 323 342 360 380 403 428 452 523 544 562

2,87 2,76 2,78 2,76 2,75 2,77 2,81 2,86 2,76 2,76 2,75

kW 837 887 949 991 1043 1113 1201 1288 1438 1496 1542(2) kW 295 325 346 364 384 405 431 455 527 548 566

2,84 2,73 2,74 2,72 2,72 2,75 2,79 2,83 2,73 2,73 2,72C C C C C C C C C C C

3,61 3,62 3,62 3,62 3,62 3,63 3,61 3,62 3,61 3,61 3,61

kW 807 856 915 957 - - - - - - -(2) kW 299 329 350 368 - - - - - - -

2,70 2,60 2,62 2,60 - - - - - - -

kW 804,7 853,0 912,2 953,4 - - - - - - -(2) kW 301,2 331,6 352,7 371,0 - - - - - - -

2,67 2,57 2,59 2,57 - - - - - - -D D D D - - - - - - -

3,48 3,50 3,49 3,50 - - - - - - -

kW 810 869 935 1000 - - - - - - -(2) kW 255 273 291 310 - - - - - - -

3,17 3,19 3,21 3,23 - - - - - - -

kW 812,7 872,3 938,2 1004,0 - - - - - - -(2) kW 257,60 275,41 294,57 313,71 - - - - - - -

3,15 3,17 3,18 3,20 - - - - - - -B B B A - - - - - - -

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 3/3 3/3 3/3% 12% 13% 12% 13% 12% 13% 13% 13% 8% 8% 8%kg 83 87 98 102 115 122 132 136 149 160 165kg 253 255 279 298 - - - - - - -

n° 12 12 13 14 15 16 18 18 20 21 22m3/h 21000 / 20000

n° 1 1 1 1 1 1 1 1 1 1 1(6) m3/h 144,4 153,0 163,7 171,1 180,0 191,8 207,0 222,1 247,9 258,0 265,9(6) m3/h 138,8 147,2 157,4 164,6 - - - - - - -(6) kPa 36 42 50 55 49 25 29 32 39 34 36(6) kPa 34 39 46 51 - - - - - - -

P13 P13 P13 P13 P14 P14 P17 P17 P17 P17 P17l 900 900 900 900 900 900 1000 1000 - - -

kPa 231 217 206 183 231 241 224 213 192 187 181kPa 210 195 184 157 203 211 189 174 167 161 154

P14 P14 P14 P14 P15 P15 P18 P18 P18 P18 P18kPa 283 269 258 235 285 289 313 302 280 275 269kPa 262 247 236 209 256 258 277 263 256 249 242

P23 P23 P24 P24 P24 P24 P25 P25 P25 P25 P25kPa 176 155 178 153 170 198 171 155 203 187 187kPa 146 122 143 115 129 153 118 96 165 147 145

(5) dB(A) 100 100 101 101 102 102 102 103 104 105 106(4) dB(A) 68 68 68 68 69 69 69 70 71 71 72(5) dB(A) 95 95 96 96 97 97 97 98 99 100 101(4) dB(A) 63 62 63 63 64 64 64 65 66 67 68

mm 7310 7310 8465 8465 9610 9610 10755 10755 11965 13110 13110mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

10Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PROCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

108.4 116.4 134.4 146.4 160.4 170.4 180.4 190.4 200.4

kW - - - - - 1679 1779 1904 1990(2) kW - - - - - 586 645 685 720

- - - - - 2,87 2,76 2,78 2,76

kW - - - - - 1675 1774 1898 1983(2) kW - - - - - 590 650 691 727

- - - - - 2,84 2,73 2,75 2,73- - - - - C C C C- - - - - 3,62 3,64 3,62 3,64

kW 1037 1175 1324 1415 1515 1614 1711 1831 1914(2) kW 395 459 496 516 538 598 658 699 735

2,63 2,56 2,67 2,74 2,82 2,70 2,60 2,62 2,60

kW 1034 1173 1320 1412 1512 1610 1707 1825 1907(2) kW 397 461 500 519 541 602 663 705 741

2,60 2,54 2,64 2,72 2,79 2,67 2,57 2,59 2,57D D D C C D D D D

3,56 3,54 3,49 3,52 3,50 3,49 3,53 3,50 3,53

kW 1066 1228 1336 1443 1550 1621 1739 1869 2000(2) kW 340 392 425 452 478 511 545 582 619

3,13 3,13 3,14 3,20 3,24 3,17 3,19 3,21 3,23

kW 1069 1231 1340 1447 1554 1625 1744 1876 2007(2) kW 343 396 430 455 482 515 550 589 627

3,11 3,11 3,12 3,18 3,23 3,16 3,17 3,19 3,20B B B B A B B B A

n°/n° 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4% 6% 6% 6% 6% 6% 6% 6% 6% 6%kg 104 126 141 150 167 167 174 195 205kg 332 380 422 461 505 505 510 558 596

n° 16 18 20 22 24 24 24 26 28m3/h 21000 / 20000

n° 2 2 2 2 2 2 2 2 2(6) m3/h 293,7 311,1 332,9 347,9(6) m3/h 178,3 202,2 227,7 243,4 260,7 277,6 294,3 314,9 329,2(6) kPa 36 42 50 55(6) kPa 36 33 40 45 30 34 39 46 51

- - - - - - - - -l - - - - - - - - -

kPa - - - - - - - - -kPa - - - - - - - - -

- - - - - - - - -kPa - - - - - - - - -kPa - - - - - - - - -

- - - - - - - - -kPa - - - - - - - - -kPa - - - - - - - - -

(5) dB(A) 101 101 102 103 103 103 103 104 104(4) dB(A) 69 69 70 70 70 71 71 71 71(5) dB(A) 96 96 97 98 98 98 98 99 99(4) dB(A) 64 63 65 66 66 66 65 66 66

mm 10040 12330 12330 14620 14620 14620 14620 16930 16930mm 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440

11Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO HE

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO HECooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO HE /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell anf tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

33.2 35.2 37.2 40.2 43.2 51.2 54.2 58.2 67.2 73.2 80.2

kW 329 367 387 442 492 518 573 674 732 770 813(2) kW 104 117 123 140 157 165 182 214 234 246 259

3,16 3,14 3,15 3,15 3,15 3,14 3,15 3,14 3,13 3,13 3,15

kW 328 366 387 441 491 516 572 672 730 768 811(2) kW 105 118 124 142 158 166 183 216 236 248 261

3,12 3,11 3,12 3,11 3,10 3,11 3,12 3,12 3,10 3,10 3,11A A A A A A A A A A A

3,89 3,85 3,94 3,85 3,81 3,74 3,75 3,84 3,73 3,71 3,74

kW 317 355 375 427 475 500 555 650 706 742 787(2) kW 106 119 125 143 160 168 185 218 238 250 263

3,00 2,98 3,00 2,99 2,97 2,98 3,00 2,98 2,96 2,97 3,00

kW 316,41 354,16 374,14 425,56 473,84 499,08 553,97 648,61 704,65 740,65 784,76(2) kW 106,81 119,85 125,91 144,17 160,65 168,85 186,04 219,73 239,75 252,14 264,67

2,96 2,96 2,97 2,95 2,95 2,96 2,98 2,95 2,94 2,94 2,97B B B B B B B B B B B

3,84 3,80 3,90 3,80 3,77 3,69 3,72 3,78 3,68 3,65 3,71

kW 318 367 396 433 470 504 578 661 704 757 811(2) kW 98 111 120 132 143 153 176 202 215 229 242

3,25 3,29 3,31 3,29 3,28 3,29 3,29 3,28 3,27 3,31 3,36

kW 318,9 367,3 397,4 434,6 471,3 505,2 579,2 662,5 705,2 759,4 813,6(2) kW 98,84 112,02 120,83 132,84 144,30 154,59 176,59 202,90 217,05 230,53 244,14

3,23 3,28 3,29 3,27 3,27 3,27 3,28 3,27 3,25 3,29 3,33A A A A A A A A A A A

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2% 12% 12% 13% 11% 13% 12% 12% 12% 13% 12% 13%kg 46 52 52 56 56 68 77 83 83 92 92kg 130 147 166 169 169 190 229 253 253 272 291

n° 6 7 8 8 8 9 11 12 12 13 14m3/h 21000 / 20000

n° 1 1 1 1 1 1 1 1 1 1 1(6) m3/h 56,55 63,16 66,64 76,01 84,70 89,04 98,63 115,84 125,89 132,44 139,92(6) m3/h 54,59 61,04 64,52 73,41 81,67 86,03 95,44 111,79 121,46 127,70 135,35(6) kPa 37 21 24 36 41 27 32 25 28 32 36(6) kPa 35 20 28 33 22 25 18 24 26 30 35

P2 P2 P2 P3 P3 P7 P7 P8 P8 P13 P13l - - - - - 740 740 740 740 900 900

kPa 214 211 196 239 212 231 214 230 219 244 233kPa 189 180 161 195 187 203 181 186 202 225 212

P3 P3 P3 P4 P4 P8 P8 P9 P9 P14 P14kPa 297 297 282 285 252 267 250 302 293 296 285kPa 272 266 248 242 227 239 217 259 276 277 264

P20 P20 P20 P21 P21 P21 P21 P13 P13 P22 P22kPa 249 236 213 196 180 193 160 224 216 200 178kPa 212 188 159 131 104 152 110 159 145 174 149

(5) dB(A) 94 95 95 96 96 97 98 98 99 100 100(4) dB(A) 62 62 62 63 63 65 66 66 67 67 67(5) dB(A) 89 90 90 91 91 92 93 93 94 95 95(4) dB(A) 57 58 58 59 59 59 61 60 62 62 62

mm 3870 5020 5020 5020 5020 6165 7310 7310 7310 8465 8465mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

12Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO HE

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO HECooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO HE /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

85.2 90.2 95.2 100.2 105.2 115.2 120.2 80.4 86.4 102.4 108.4

kW 886 953 1024 1085 1140 1208 1300 - - - -(2) kW 281 303 325 344 364 386 415 - - - -

3,15 3,15 3,15 3,16 3,13 3,13 3,13 - - - -

kW 883 950 1020 1081 1138 1206 1297 - - - -(2) kW 284 306 329 348 366 388 418 - - - -

3,11 3,10 3,11 3,11 3,11 3,10 3,10 - - - -A A A A A A A - - - -

3,65 3,71 3,73 3,91 3,78 3,79 3,78 - - - -

kW - - - - - - - 854 950 1000 1110(2) kW - - - - - - - 286 319 336 370

- - - - - - - 2,99 2,97 2,98 3,00

kW - - - - - - - 851,38 947,91 998,39 1108,19(2) kW - - - - - - - 288,09 321,06 337,48 371,85

- - - - - - - 2,96 2,95 2,96 2,98- - - - - - - B B B B- - - - - - - 3,80 3,78 3,71 3,72

kW - - - - - - - 867 941 1008 1156(2) kW - - - - - - - 263 287 307 351

- - - - - - - 3,29 3,28 3,29 3,29

kW - - - - - - - 868,9 942,5 1010,2 1158,3(2) kW - - - - - - - 265,41 288,39 308,94 352,96

- - - - - - - 3,27 3,27 3,27 3,28- - - - - - - A A A A

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/4 4/4 4/4 4/4% 12% 13% 12% 13% 12% 13% 13% 6% 6% 6% 6%kg 105 111 128 128 141 145 154 112 112 136 154kg - - - - - - - 337 337 380 457

n° 15 16 17 18 19 21 22 16 16 18 22m3/h 21000 / 20000

n° 1 1 1 1 1 1 1 2 2 2 2(6) m3/h 152,31 163,91 176,07 186,69 196,07 207,80 223,68 - - - -(6) m3/h - - - - - - - 146,81 163,33 172,06 190,89(6) kPa 43 50 48 53 26 29 33 - - - -(6) kPa - - - - - - - 33 22 25 18

P13 P13 P13 P13 P14 P14 P17 - - - -l 900 900 900 900 900 900 1000 - - - -

kPa 214 196 183 168 236 214 212 - - - -kPa 192 171 155 138 205 179 172 - - - -

P14 P14 P14 P14 P15 P15 P18 - - - -kPa 266 248 234 218 281 250 300 - - - -kPa 244 223 206 188 250 215 261 - - - -

P23 P23 P24 P24 P24 P24 P25 - - - -kPa 200 170 168 158 194 174 242 - - - -kPa 167 133 127 114 148 121 182 - - - -

(5) dB(A) 100 100 101 101 102 102 102 99 99 100 101(4) dB(A) 67 67 68 68 69 69 69 66 66 68 69(5) dB(A) 95 95 96 96 97 97 97 94 94 95 96(4) dB(A) 62 62 63 63 64 64 64 62 62 62 64

mm 9610 9610 10755 10755 11965 13110 13110 10040 10040 12330 14620mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

13Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO HE

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO HECooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO HE /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

116.4 134.4 146.4 160.4

kW - 1464 1540 1627(2) kW - 468 491 517

- 3,13 3,13 3,15

kW - 1461 1536 1623(2) kW - 471 495 521

- 3,10 3,10 3,11- A A A- 3,73 3,72 3,75

kW 1300 1412 1485 1574(2) kW 437 476 501 525

2,98 2,96 2,97 3,00

kW 1297,49 1409,60 1481,65 1569,91(2) kW 439,20 479,21 503,94 528,94

2,95 2,94 2,94 2,97B B B B

3,79 3,69 3,66 3,73

kW 1322 1407 1515 1623(2) kW 403 431 457 484

3,28 3,27 3,31 3,36

kW 1324,7 1410,2 1518,3 1626,8(2) kW 405,53 433,80 460,70 487,85

3,27 3,25 3,30 3,33A A A A

n°/n° 4/4 4/4 4/4 4/4% 6% 6% 6% 6%kg 167 167 185 185kg 505 505 544 583

n° 24 24 26 28m3/h 21000 / 20000

n° 2 2 2 2(6) m3/h - 251,78 264,87 279,84(6) m3/h 223,57 242,92 255,39 270,69(6) kPa - 28 32 36(6) kPa 24 26 30 35

l - - - -kPa - - - -kPa - - - -

- - - -kPa - - - -kPa - - - -

- - - -kPa - - - -kPa - - - -

(5) dB(A) 101 102 103 103(4) dB(A) 69 70 70 70(5) dB(A) 96 97 98 98(4) dB(A) 63 65 65 65

mm 14620 14620 16930 16930mm 2260 2260 2260 2260mm 2440 2440 2440 2440

14Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO SLN

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO SLNCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO SLN /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AssialiQuantityAir flow single fan chiller / heat pumpEvaporatorType FascioQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitDimensions LenghtWidthHeight

33.2 35.2 37.2 40.2 43.2 51.2 54.2 58.2 67.2 73.2 80.2

kW 317 354 376 425 472 498 554 648 703 740 783(2) kW 105 118 123 142 160 167 184 217 238 249 261

3,01 3,00 3,05 2,99 2,95 2,98 3,02 2,99 2,96 2,97 3,00

kW 316 354 375 424 471 497 553 647 702 738 781(2) kW 106 119 124 143 161 168 185 218 239 251 263

2,97 2,97 3,02 2,96 2,92 2,95 2,99 2,96 2,93 2,94 2,97B B B B B B B B B B B

3,85 3,81 3,90 3,81 3,77 3,70 3,71 3,80 3,69 3,67 3,70

kW 306 343 364 412 457 482 537 628 680 715 759(2) kW 106 119 124 144 162 169 185 219 240 252 263

2,89 2,88 2,93 2,87 2,82 2,85 2,90 2,86 2,83 2,84 2,88

kW 305 342 363 411 455 481 536 626 678 714 757(2) kW 107 120 125 145 163 170 187 221 242 254 265

2,86 2,85 2,91 2,84 2,79 2,82 2,87 2,84 2,80 2,81 2,85C C B C C C C C C C C

3,79 3,75 3,85 3,75 3,70 3,64 3,66 3,74 3,62 3,61 3,65

kW 318 367 396 433 470 504 578 661 704 757 811(2) kW 98 111 120 132 143 153 176 202 215 229 242

3,25 3,29 3,31 3,29 3,28 3,29 3,29 3,28 3,27 3,31 3,36

kW 319 367 397 435 471 505 579 662 705 759 814(2) kW 99 112 121 133 144 155 177 203 217 231 244

3,23 3,28 3,29 3,27 3,27 3,27 3,28 3,27 3,25 3,29 3,33A A A A A A A A A A A

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2 2/2% 12% 12% 13% 11% 13% 12% 12% 12% 13% 12% 13%kg 46 52 52 56 56 68 77 83 83 92 92kg 130 147 166 169 169 190 229 253 253 272 291

n° 6 7 8 8 8 9 11 12 12 13 14m3/h 16000 / 15000

n° 1 1 1 1 1 1 1 1 1 1 1(6) m3/h 54,44 60,94 64,59 73,18 81,23 85,72 95,35 111,52 120,96 127,26 134,75(6) m3/h 52,69 58,98 62,60 70,82 78,52 82,91 92,42 107,93 116,88 123,00 130,50(6) kPa 34 20 22 33 38 25 30 24 26 30 33(6) kPa 32 18 21 31 36 23 29 22 25 28 31

P2 P2 P2 P3 P3 P7 P7 P8 P8 P13 P13l - - - - - 740 740 740 740 900 900

kPa 214 211 196 239 212 231 214 230 219 244 233kPa 189 180 161 195 187 203 181 186 202 225 212

P3 P3 P3 P4 P4 P8 P8 P9 P9 P14 P14kPa 297 297 282 285 252 267 250 302 293 296 285kPa 272 266 248 242 227 239 217 259 276 277 264

P20 P20 P20 P21 P21 P21 P21 P13 P13 P22 P22kPa 249 236 213 196 180 193 160 224 216 200 178kPa 212 188 159 131 104 152 110 159 145 174 149

(5) dB(A) 86 87 87 88 88 89 90 90 91 92 92(4) dB(A) 54 55 54 56 56 57 58 58 59 59 59

mm 3870 5020 5020 5020 5020 6165 7310 7310 7310 8465 8465mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

15Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO SLN

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO SLNCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO SLN /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AssialiQuantityAir flow single fan chiller / heat pumpEvaporatorType FascioQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitDimensions LenghtWidthHeight

85.2 90.2 95.2 100.2 105.2 115.2 120.2 80.4 86.4 102.4 108.4

kW 853 919 986 1045 1097 1166 1254 - - - -(2) kW 285 307 331 350 370 389 421 - - - -

3,00 2,99 2,98 2,99 2,97 3,00 2,98 - - - -

kW 850 916 982 1041 1095 1164 1251 - - - -(2) kW 287 311 334 353 372 391 423 - - - -

2,96 2,95 2,94 2,95 2,95 2,97 2,95 - - - -B B B B B B B - - - -

3,61 3,67 3,69 3,87 3,74 3,75 3,74 - - - -

kW - - - - - - - 823 913 964 1075(2) kW - - - - - - - 287 324 339 370

- - - - - - - 2,87 2,82 2,85 2,90

kW - - - - - - - 821 911 962 1072(2) kW - - - - - - - 289 326 340 373

- - - - - - - 2,84 2,79 2,83 2,88- - - - - - - C C C C- - - - - - - 3,75 3,71 3,66 3,66

kW - - - - - - - 867 941 1008 1156(2) kW - - - - - - - 263 287 307 351

- - - - - - - 3,29 3,28 3,29 3,29

kW - - - - - - - 869 942 1010 1158(2) kW - - - - - - - 265 288 309 353

- - - - - - - 3,27 3,27 3,27 3,28- - - - - - - A A A A

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 2/2 4/4 4/4 4/4 4/4% 12% 13% 12% 13% 12% 13% 13% 6% 6% 6% 6%kg 105 111 128 128 141 145 154 56 56 68 77kg - - - - - - - 169 169 190 229

n° 15 16 17 18 19 21 22 16 16 18 22m3/h 16000 / 15000

n° 1 1 1 1 1 1 1 2 2 2 2(6) m3/h 146,70 158,06 169,52 179,72 188,77 200,64 215,61 - - - -(6) m3/h - - - - - - - 141,64 157,04 165,83 184,85(6) kPa 40 47 45 49 24 27 30 - - - -(6) kPa - - - - - - - 31 36 23 29

P13 P13 P13 P13 P14 P14 P17 - - - -l 900 900 900 900 900 900 1000 - - - -

kPa 214 196 183 168 236 214 212 - - - -kPa 192 171 155 138 205 179 172 - - - -

P14 P14 P14 P14 P15 P15 P18 - - - -kPa 266 248 234 218 281 250 300 - - - -kPa 244 223 206 188 250 215 261 - - - -

P23 P23 P24 P24 P24 P24 P25 - - - -kPa 200 170 168 158 194 174 242 - - - -kPa 167 133 127 114 148 121 182 - - - -

(5) dB(A) 92 92 93 93 94 94 94 91 91 92 93(4) dB(A) 59 59 60 60 61 61 61 59 59 60 61

mm 9610 9610 10755 10755 11965 13110 13110 10040 10040 12330 14620mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

16Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO SLN

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO SLNCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERCOBALT PRO SLN /HPCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERHeating (A7/87%; W45) (GROSS)Heating capacityTotal absorbed powerCOPHeating (A7/87%; W45) (EN 14511:2011-3)Heating capacityTotal absorbed powerCOPEfficiency class COPCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fan chiller / heat pumpEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Water flow HP (A35; W7)Pressure drop CH (A35; W7)Pressure drop HP (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitDimensions LenghtWidthHeight

116.4 134.4 146.4 160.4

kW - 1407 1480 1567(2) kW - 475 499 523

- 2,96 2,97 3,00

kW - 1404 1477 1563(2) kW - 478 502 526

- 2,94 2,94 2,97- B B B- 3,69 3,68 3,70

kW 1255 1359 1430 1517(2) kW 439 481 504 527

2,86 2,83 2,84 2,88

kW 1253 1357 1427 1514(2) kW 441 483 507 530

2,84 2,81 2,82 2,86C C C C

3,75 3,63 3,62 3,67

kW 1322 1407 1515 1623(2) kW 403 431 457 484

3,28 3,27 3,31 3,36

kW 1325 1410 1518 1627(2) kW 406 434 461 488

3,27 3,25 3,30 3,33A A A A

n°/n° 4/4 4/4 4/4 4/4% 6% 6% 6% 6%kg 83 83 92 92kg 253 253 272 291

n° 24 24 26 28m3/h 16000 / 15000

n° 2 2 2 1(6) m3/h 241,92 254,52 269,50 73,18(6) m3/h 233,75 246,01 261,01 70,82(6) kPa 26 30 33 33(6) kPa 25 28 31 31

- - - -l - - - -

kPa - - - -kPa - - - -

- - - -kPa - - - -kPa - - - -

- - - -kPa - - - -kPa - - - -

(5) dB(A) 94 95 95 88(4) dB(A) 62 62 62 56

mm 14620 16930 16930 5020mm 2260 2260 2260 2260mm 2440 2440 2440 2440

17Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO HEi

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO HEiCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERESEER EC fansCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AxialQuantityAir flow single fanEvaporatorType Shell and tubeQuantityWater flow CH (A35; W7)Pressure drop CH (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

58.2 67.2 73.2 80.2 85.2 90.2 100.3 105.3 115.3 134.4 146.4

kW 567 655 727 782 889 948 1031 1092 1147 1310 1455(2) kW 173 203 231 245 281 300 320 346 360 407 461

3,27 3,22 3,15 3,20 3,16 3,16 3,23 3,16 3,18 3,22 3,15

kW 565,53 653,42 725 780 887 945 1029 1090 1145 1307 1451(2) kW 174,29 204,96 233 247 284 303 321 348 363 410 465

3,24 3,19 3,12 3,16 3,12 3,12 3,20 3,13 3,16 3,19 3,12A A A A A A A A A A A

4,63 4,60 4,60 4,60 4,61 4,61 4,60 4,61 4,60 4,62 4,614,75 4,72 4,72 4,72 4,73 4,73 4,72 4,73 4,72 4,74 4,73

n°/n° 2/2 2/2 2/2 2/2 2/2 2/2 3/3 3/3 3/3 4/4 4/4% 12,5% 11,0% 10,0% 9,4% 8,4% 7,8% 7,0% 6,7% 6,4% 5,5% 5,0%kg 83 91 102 107 119 132 178 182 187 183 205kg - - - - - - - - - - -

n° 12 13 14 15 16 18 20 21 22 26 28m3/h 21000

n° 1 1 1 1 1 1 1 1 1 2 2(6) m3/h 97,44 112,64 125,09 134,58 152,97 163,10 177,36 187,83 197,32 225,28 250,19(6) kPa 20 27 34 39 38 41 23 26 28 27 34

P7 P8 P13 P13 P13 P13 P13 P14 P14 - -l 740 740 900 900 900 900 900 900 900 - -

kPa 222 229 243 229 216 197 198 229 211 - -kPa 188 212 225 209 192 170 167 196 175 - -

P8 P9 P14 P14 P14 P14 P14 P15 P15 - -kPa 259 301 294 281 268 248 247 271 244 - -kPa 224 285 276 261 245 222 217 238 209 - -

P13 P13 P22 P22 P23 P23 P24 P24 P24 - -kPa 224 216 200 178 200 170 158 194 174 - -kPa 159 145 174 149 167 133 114 148 121 - -

(5) dB(A) 99 100 101 101 101 103 102 103 103 103 104(4) dB(A) 67 67 68 68 68 70 69 69 69 70 71(5) dB(A) 95 96 97 97 97 99 98 99 99 99 100(4) dB(A) 63 63 64 64 64 66 65 65 65 66 67

mm 7310 8465 8465 9610 9610 10755 11965 13110 13110 16930 16930mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

18Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

TECHNICAL DATA - COBALT PRO XEi

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

COBALT PRO HEiCooling (A35; W7) (GROSS)Cooling capacityTotal absorbed powerEER 100%Cooling (A35; W7) (EN 14511:2011-3)Cooling capacityTotal absorbed powerEER 100%Efficiency class EERESEERESEER EC fansCompressorsQuantity/Refrigerant circuitsCapacity stepsRefrigerant charge CHRefrigerant charge HPFansType AssialiQuantityAir flow single fanEvaporatorType FascioQuantityWater flow CH (A35; W7)Pressure drop CH (A35; W7)Hydraulic moduleSTD: pressure head (Px)Buffer tank capacitySTD: pressure head 1PSTD: pressure head 2PMAG: pressure head (Px)MAG: pressure head 1PMAG: pressure head 2PGLI: pressure head (Px)GLI: pressure head 1PGLI: pressure head 2PNoiseSound power basic unitSound pressure basic unitSound power LN versionSound pressure LN varsionDimensions LenghtWidthHeight

30.1 35.1 45.1 55.2 65.2 70.2 80.2 90.2 100.3 110.4 130.4

kW 286 357 446 568 642 724 801 892 1011 1136 1285(2) kW 88 113 148 175 201 228 261 296 316 351 402

3,26 3,15 3,01 3,24 3,19 3,17 3,07 3,01 3,20 3,24 3,19

kW 285,60 356,01 445,22 567,18 641,01 721,71 798,74 889,63 1009,06 1134,58 1282,30(2) kW 88,66 114,83 148,92 176,40 202,63 230,19 263,72 298,65 318,10 352,59 404,98

3,22 3,10 2,99 3,22 3,16 3,14 3,03 2,98 3,17 3,22 3,17A A B A A A B B A A A

4,74 4,72 4,63 4,83 4,80 4,81 4,81 4,80 4,81 4,83 4,804,93 4,86 4,83 5,05 5,01 5,03 5,03 5,02 5,02 5,06 5,03

n°/n° 1/1 1/1 1/1 2/2 2/2 2/2 2/2 2/2 3/3 4/4 4/4% 25% 20% 16% 13% 11% 10% 9% 8% 7% 6% 5%kg 44 56 68 83 96 111 140 160 187 167 192kg - - - - - - - - - - -

n° 6 8 10 12 14 16 18 20 22 24 28m3/h 21000

n° 1 1 1 1 1 1 1 1 1 2 2(6) m3/h 49,27 61,47 76,74 97,73 110,50 124,46 137,80 153,48 173,87 195,46 220,99(6) kPa 30 47 22 20 26 33 40 40 22 20 26

P1 P2 P3 P6 P7 P7 P12 P13 P13 - -l - - - 740 740 900 900 900 900 - -

kPa 168 186 240 176 197 164 164 209 203 - -kPa 146 155 192 142 154 146 143 184 174 - -

P2 P3 P4 P7 P8 P8 P13 P14 P14 - -kPa 231 271 283 222 233 200 225 261 253 - -kPa 210 240 236 187 191 182 204 236 224 - -

P19 P20 P21 P13 P13 P22 P22 P23 P24 - -kPa 182 243 209 187 200 184 196 155 153 - -kPa 149 204 178 135 178 160 169 122 115 - -

(5) dB(A) 99 100 101 102 103 103 104 104 105 105 106(4) dB(A) 67 68 69 69 70 70 71 71 71 72 73(5) dB(A) 95 96 97 98 99 99 100 100 101 101 102(4) dB(A) 63 64 65 65 66 66 67 67 67 68 69

mm 3870 5020 5165 7310 8465 9610 10755 11965 13110 14620 16930mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440

19Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

ELECTRICAL DATA - COBALT PRO

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

33.2 35.2 37.2 40.2 43.2 51.2 54.2 58.2 67.2 73.2 80.2

(8)kW 143,5 153,9 173,6 192,5 211,3 225,7 255,6 289,5 308,0 327,2 346,5

(149,0) (159,4) (179,1) (200,0) (218,8) (234,9) (264,8) (300,5) (319,0) (342,2) (361,5)

(8)A 240,0 258,2 285,4 319,0 352,6 378,2 428,1 481,7 511,0 539,3 567,6

(250,4) (268,6) (295,8) (333,3) (366,9) (394,9) (444,8) (502,0) (531,3) (565,5) (593,8)

(8)A 316 334 385 391 424 481 525 684 713 746 775

(326) (344) (395) (405) (439) (497) (542) (704) (733) (773) (801)n° x kW 5 x 2,0 6 x 2,0 6 x 2,0 6 x 2,0 6 x 2,0 7 x 2,0 8 x 2,0 9 x 2,0 10 x 2,0 11 x 2,0 12 x 2,0n° x A 5 x 4,3 6 x 4,3 6 x 4,3 6 x 4,3 6 x 4,3 7 x 4,3 8 x 4,3 9 x 4,3 10 x 4,3 11 x 4,3 12 x 4,3

kW 5,5 5,5 5,5 7,5 7,5 9,2 9,2 11,0 11,0 15,0 15,0A 10,4 10,4 10,4 14,3 14,3 16,7 16,7 20,3 20,3 26,2 26,2

kW 7,5 7,5 7,5 11,0 11,0 11,0 11,0 15,0 15,0 18,5 18,5A 14,3 14,3 14,3 20,3 20,3 20,3 20,3 26,2 26,2 32,9 32,9kW 9,2 9,2 9,2 11,0 11,0 11,0 11,0 15,0 15,0 18,5 18,5

A 16,7 16,7 16,7 20,3 20,3 20,3 20,3 26,2 26,2 32,9 32,9V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

85.2 90.2 95.2 100.2 105.2 115.2 120.2 130.2 140.3 150.3 160.3

(8)kW 372,9 399,4 425,8 452,3 482,3 512,2 553,0 588,2 652,1 678,6 736,2

(387,9) (414,4) (440,8) (467,3) (500,8) (530,7) (575,0) (610,2) (674,1) (700,6) (758,2)

(8)A 615,6 663,6 706,9 750,2 797,5 844,8 923,4 923,4 1.082,0 1.125,3 1.215,6

(641,8) (689,8) (733,1) (776,4) (830,4) (877,7) (961,6) (961,6) (1.120,2) (1.163,5)(1.253,8)

(8)A 896 944 1.012 1.055 1.215 1.262 1.417 1.417 1.387 1.430 1.633

(922) (970) (1.038) (1.081) (1.247) (1.295) (1.456) (1.456) (1.425) (1.469) (1.671)n° x kW 12 x 2,0 12 x 2,0 13 x 2,0 14 x 2,0 15 x 2,0 16 x 2,0 18 x 2,0 18 x 2,0 20 x 2,0 21 x 2,0 22 x 2,0n° x A 12 x 4,3 12 x 4,3 13 x 4,3 14 x 4,3 15 x 4,3 16 x 4,3 18 x 4,3 18 x 4,3 20 x 4,3 21 x 4,3 22 x 4,3

kW 15,0 15,0 15,0 15,0 18,5 18,5 22,0 22,0 22,0 22,0 22,0A 26,2 26,2 26,2 26,2 32,9 32,9 38,2 38,2 38,2 38,2 38,2

kW 18,5 18,5 18,5 18,5 22,0 22,0 30,0 30,0 30,0 30,0 30,0A 32,9 32,9 32,9 32,9 38,2 38,2 53,6 53,6 53,6 53,6 53,6kW 22,0 22,0 30,0 30,0 30,0 30,0 37,0 37,0 37,0 37,0 37,0

A 38,2 38,2 53,6 53,6 53,6 53,6 65,8 65,8 65,8 65,8 65,8V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

108.4 116.4 134.4 146.4 160.4 170.4 180.4 190.4 200.4

(8)kW 511,2 579,1 616,0 654,5 693,0 745,9 798,7 851,7 904,7

(511,2) (579,1) (616,0) (654,5) (693,0) (745,9) (798,7) (851,7) (904,7)

(8)A 856,2 963,4 1.022,0 1.078,6 1.135,2 1.231,2 1.327,2 1.413,8 1.500,4

(856,2) (963,4) (1.022,0)(1.078,6)(1.135,2) (1.231,2)(1.327,2) (1.413,8) (1.500,4)

(8)A 953 1.165 1.224 1.286 1.342 1.511 1.607 1.719 1.805

(953) (1.165) (1.224) (1.286) (1.342) (1.511) (1.607) (1.719) (1.805)n° x kW 16 x 2,0 18 x 2,0 20 x 2,0 22 x 2,0 24 x 2,0 24 x 2,0 24 x 2,0 26 x 2,0 28 x 2,0n° x A 16 x 4,3 18 x 4,3 20 x 4,3 22 x 4,3 24 x 4,3 24 x 4,3 24 x 4,3 26 x 4,3 28 x 4,3

kW 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0A 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0

kW 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0A 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0kW 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0

A 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

20Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

ELECTRICAL DATA COBALT PRO HE - COBALT PRO SLN

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

33.2 35.2 37.2 40.2 43.2 51.2 54.2 58.2 67.2 73.2 80.2

(8)kW 145,0 165,8 177,6 196,5 215,3 229,7 261,6 295,5 312,0 331,2 350,5

(150,5) (171,3) (183,1) (204,0) (222,8) (238,9) (270,8) (306,5) (323,0) (346,2) (365,5)

(8)A 244,3 276,1 294,0 327,6 361,2 386,8 441,0 494,6 519,6 547,9 576,2

(254,7) (286,5) (304,4) (341,9) (375,5) (403,5) (457,7) (514,9) (539,9) (574,1) (602,4)

(8)A 320 375 393 399 433 489 538 697 722 755 783

(331) (386) (404) (414) (447) (506) (555) (717) (742) (781) (809)n° x kW 6 x 2,0 7 x 2,0 8 x 2,0 8 x 2,0 8 x 2,0 9 x 2,0 11 x 2,0 12 x 2,0 12 x 2,0 13 x 2,0 14 x 2,0n° x A 6 x 4,3 7 x 4,3 8 x 4,3 8 x 4,3 8 x 4,3 9 x 4,3 11 x 4,3 12 x 4,3 12 x 4,3 13 x 4,3 14 x 4,3

kW 5,5 5,5 5,5 7,5 7,5 9,2 9,2 11,0 11,0 15,0 15,0A 10,4 10,4 10,4 14,3 14,3 16,7 16,7 20,3 20,3 26,2 26,2

kW 7,5 7,5 7,5 11,0 11,0 11,0 11,0 15,0 15,0 18,5 18,5A 14,3 14,3 14,3 20,3 20,3 20,3 20,3 26,2 26,2 32,9 32,9kW 9,2 9,2 9,2 11,0 11,0 11,0 11,0 15,0 15,0 18,5 18,5

A 16,7 16,7 16,7 20,3 20,3 20,3 20,3 26,2 26,2 32,9 32,9V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

85.2 90.2 95.2 100.2 105.2 115.2 120.2 80.4 86.4 102.4 108.4

(8)kW 378,9 407,4 433,8 460,3 490,3 522,2 561,0 393,0 430,7 459,5 523,2

(393,9) (422,4) (448,8) (475,3) (508,8) (540,7) (583,0) (393,0) (430,7) (459,5) (523,2)

(8)A 628,5 680,8 724,1 767,4 814,7 866,3 940,6 655,2 722,4 773,6 882,0

(654,7) (707,0) (750,3) (793,6) (847,6) (899,2) (978,8) (655,2) (722,4) (773,6) (882,0)

(8)A 909 961 1.029 1.072 1.232 1.283 1.435 727 794 876 979

(935) (987) (1.055) (1.099) (1.265) (1.316) (1.473) (727) (794) (876) (979)n° x kW 15 x 2,0 16 x 2,0 17 x 2,0 18 x 2,0 19 x 2,0 21 x 2,0 22 x 2,0 16 x 2,0 16 x 2,0 18 x 2,0 22 x 2,0n° x A 15 x 4,3 16 x 4,3 17 x 4,3 18 x 4,3 19 x 4,3 21 x 4,3 22 x 4,3 16 x 4,3 16 x 4,3 18 x 4,3 22 x 4,3

kW 15,0 15,0 15,0 15,0 18,5 18,5 22,0 0,0 0,0 0,0 0,0A 26,2 26,2 26,2 26,2 32,9 32,9 38,2 0,0 0,0 0,0 0,0

kW 18,5 18,5 18,5 18,5 22,0 22,0 30,0 0,0 0,0 0,0 0,0A 32,9 32,9 32,9 32,9 38,2 38,2 53,6 0,0 0,0 0,0 0,0kW 22,0 22,0 30,0 30,0 30,0 30,0 37,0 0,0 0,0 0,0 0,0

A 38,2 38,2 53,6 53,6 53,6 53,6 65,8 0,0 0,0 0,0 0,0V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

116.4 134.4 146.4 160.4

(8)kW 591,1 624,0 662,5 701,0

(591,1) (624,0) (662,5) (701,0)

(8)A 989,2 1.039,2 1.095,8 1.152,4

(989,2) (1.039,2) (1.095,8) (1.152,4)

(8)A 1.191 1.241 1.303 1.359

(1.191) (1.241) (1.303) (1.359)n° x kW 24 x 2,0 24 x 2,0 26 x 2,0 28 x 2,0n° x A 24 x 4,3 24 x 4,3 26 x 4,3 28 x 4,3

kW 0,0 0,0 0,0 0,0A 0,0 0,0 0,0 0,0

kW 0,0 0,0 0,0 0,0A 0,0 0,0 0,0 0,0kW 0,0 0,0 0,0 0,0

A 0,0 0,0 0,0 0,0V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

21Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

ELECTRICAL DATA - COBALT PRO HEi

ELECTRICAL DATA - COBALT PRO XEi

(1) External air temperature 35 ° C, water inlet-outlet temperature 12-7 ° C (2) The total power is the sum of the power absorbed by the compressors and fans (3) External air temperature 7 ° C DB, 6 ° C WB;-condenser outlet water temperature 40-45 ° C (4) Sound pressure levels measured at 10 meters from the unit in free field conditions direction factor Q = 2. (5) Sound power levels calculated according to ISO 3744 (6) Inlet-outlet evaporator water temperature 12-7 ° C (7) Inlet-outlet condenser water temperature 40-45 ° C(8) The value in parentheses refers to the machine with pumps on board

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

Unit size

Max. absorbed power

Max. absorbed current

Max. starting current

Nominal fans powerNominal fans currentNominal standard pump powerNominal standard pump currentNominal oversized pump powerNominal oversized pump currentNominal glycol pump powerNominal glycol pump currentPower supplyAuxiliaries powersupply

58.2 67.2 73.2 80.2 85.2 90.2 100.3 105.3 115.3 134.4 146.4

(8)kW 235,8 269,7 302,5 321,7 370,2 400,7 427,7 460,5 479,7 539,4 605,0

(245,0) (280,7) (317,5) (336,7) (385,2) (415,7) (442,7) (479,0) (498,2) (539,4) (605,0)

(8)A 407,3 460,9 511,2 539,5 613,8 670,4 725,0 775,3 803,6 921,8 1.022,4

(424,0) (481,2) (537,4) (565,7) (640,0) (696,6) (751,2) (808,2) (836,5) (921,8) (1.022,4)

(8)A 510 663 713 747 792 950 927 977 1.011 1.124 1.224

(526) (683) (739) (773) (818) (977) (953) (1.010) (1.044) (1.124) (1.224)n° x kW 12 x 2,0 13 x 2,0 14 x 2,0 15 x 2,0 16 x 2,0 18 x 2,0 20 x 2,0 21 x 2,0 22 x 2,0 26 x 2,0 28 x 2,0n° x A 12 x 4,3 13 x 4,3 14 x 4,3 15 x 4,3 16 x 4,3 18 x 4,3 20 x 4,3 21 x 4,3 22 x 4,3 26 x 4,3 28 x 4,3

kW 9,2 11,0 15,0 15,0 15,0 15,0 15,0 18,5 18,5 0,0 0,0A 16,7 20,3 26,2 26,2 26,2 26,2 26,2 32,9 32,9 0,0 0,0

kW 11,0 15,0 18,5 18,5 18,5 18,5 18,5 22,0 22,0 0,0 0,0A 16,7 20,3 26,2 26,2 26,2 26,2 26,2 32,9 32,9 0,0 0,0kW 15,0 15,0 18,5 18,5 22,0 22,0 30,0 30,0 30,0 0,0 0,0

A 26,2 26,2 32,9 32,9 38,2 38,2 53,6 53,6 53,6 0,0 0,0V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

30.1 35.1 45.1 55.2 65.2 70.2 80.2 90.2 100.3 110.4 130.4

(8)kW 111,7 146,5 197,0 223,4 258,2 293,0 343,5 394,0 404,7 446,8 516,4

(115,7) (152,0) (204,5) (230,9) (267,4) (302,2) (354,5) (409,0) (419,7) (446,8) (516,4)

(8)A 196,8 251,4 330,0 393,6 448,2 502,8 581,4 660,0 699,6 787,2 896,4

(204,6) (261,8) (344,3) (407,9) (464,9) (519,5) (601,7) (686,2) (725,8) (787,2) (896,4)

(8)A 31 39 48 228 236 291 299 378 488 621 684

(39) (50) (62) (242) (253) (308) (320) (404) (514) (621) (684)n° x kW 6 x 2,0 8 x 2,0 10 x 2,0 12 x 2,0 14 x 2,0 16 x 2,0 18 x 2,0 20 x 2,0 22 x 2,0 24 x 2,0 28 x 2,0n° x A 6 x 4,3 8 x 4,3 10 x 4,3 12 x 4,3 14 x 4,3 16 x 4,3 18 x 4,3 20 x 4,3 22 x 4,3 24 x 4,3 28 x 4,3

kW 4,0 5,5 7,5 7,5 9,2 9,2 11,0 15,0 15,0 0,0 0,0A 7,8 10,4 14,3 14,3 16,7 16,7 20,3 26,2 26,2 0,0 0,0

kW 5,5 7,5 11,0 9,2 11,0 11,0 15,0 18,5 18,5 0,0 0,0A 7,8 10,4 14,3 14,3 16,7 16,7 20,3 26,2 26,2 0,0 0,0kW 9,2 9,2 11,0 15,0 15,0 18,5 18,5 22,0 30,0 0,0 0,0

A 16,7 16,7 20,3 26,2 26,2 32,9 32,9 38,2 53,6 0,0 0,0V/ph/Hz 400/3~/50V/ph/Hz 230-24/1~/50

22Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

-10

-5

0

5

10

15

20

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

HATFSA

BKG

LYIN

V.P.

FSA + LW

GLYBK

-10

-5

0

5

10

15

20

25 30 35 40 45 50 55 60

25

30

35

40

45

50

55

60

65

-15 -10 -5 0 5 10 15 20 25 30 35

FSA

OPERATING LIMITS

COBALT PRO

COOLING

RECOVERY

HEATING

user

sid

e w

ater

out

let

tem

pera

ture

(°C

)us

er s

ide

wat

er o

utle

t te

mpe

ratu

re (°

C)

user

sid

e w

ater

out

let

tem

pera

ture

(°C

)

External air temperature (°C)

recovery water outlet temperature (°C)

External air temperature (°C)

FSA + LW -> obbligatorio accessorio controllo di condensazione, in assenza di ventoFSA -> mandatory condensation control accessoryHAT -> mandatory accessory HATINV.P. -> inverter driven pump allowedGLY -> with ethylen glycolBK -> with Brine kit accessory

GLY -> with ethylen glycolBK -> with Brine kit accessory

FSA -> mandatory condensation control accessory

Operating limit in CH

Operating limit in DC

Operating limit in HP

Operating limit in CH with forced capacity control

23Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

HATFSA

BKG

LYIN

V.P.

FSA + LW

-10

-5

0

5

10

15

20

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55G

LYBK

-10

-5

0

5

10

15

20

25 30 35 40 45 50 55 60 65

25

30

35

40

45

50

55

60

65

-15 -10 -5 0 5 10 15 20 25 30 35

FSA

OPERATING LIMITS

COBALT PRO HE

COOLING

RECOVERY

HEATING

user

sid

e w

ater

out

let

tem

pera

ture

(°C

)us

er s

ide

wat

er o

utle

t te

mpe

ratu

re (°

C)

user

sid

e w

ater

out

let

tem

pera

ture

(°C

)

External air temperature (°C)

recovery water outlet temperature (°C)

External air temperature (°C)

FSA + LW -> obbligatorio accessorio controllo di condensazione, in assenza di ventoFSA -> mandatory condensation control accessoryHAT -> mandatory accessory HATINV.P. -> inverter driven pump allowedGLY -> with ethylen glycolBK -> with Brine kit accessory

GLY -> with ethylen glycolBK -> with Brine kit accessory

FSA -> mandatory condensation control accessory

Operating limit in CH

Operating limit in DC

Operating limit in DC with HWT accessory

Operating limit in HP

Operating limit in HP with HWT accessory

Operating limit in CH with forced capacity control

24Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

HATFSA

BKG

LYIN

V.P.

FSA + LW

-10

-5

0

5

10

15

20

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

-10

-5

0

5

10

15

20

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55

HATFSA

BKG

LYIN

V.P.

FSA + LW

OPERATING LIMITS

COBALT PRO HEi

OPERATING LIMITS

COBALT PRO XEi

COOLING

COOLING

user

sid

e w

ater

out

let

tem

pera

ture

(°C

)us

er s

ide

wat

er o

utle

t te

mpe

ratu

re (°

C)

External air temperature (°C)

External air temperature (°C)

FSA + LW -> obbligatorio accessorio controllo di condensazione, in assenza di ventoFSA -> mandatory condensation control accessoryHAT -> mandatory accessory HATINV.P. -> inverter driven pump allowedGLY -> with ethylen glycolBK -> with Brine kit accessory

FSA + LW -> obbligatorio accessorio controllo di condensazione, in assenza di ventoFSA -> mandatory condensation control accessoryHAT -> mandatory accessory HATINV.P. -> inverter driven pump allowedGLY -> with ethylen glycolBK -> with Brine kit accessory

Operating limit in CH

Operating limit in CH

Operating limit in CH with forced capacity control

25Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

NOISE LEVELS

COBALT PRO

NOISE LEVELS

COBALT PRO LN

Lw: sound power values measured in free field calculated according to standard ISO 3744.Lp: sound pressure levels measured at 1 metre from the unit in free field under nominal operating conditions, according to ISO 3744.

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

Total [dB(A)]

Lw Lp

Total [dB(A)]

Lw Lp

33.2 71 39 74 42 89 57 90 58 91 59 86 54 79 47 71 39

35.2 73 41 82 50 90 58 91 59 92 60 87 55 79 47 71 39

37.2 73 41 84 52 90 58 91 59 92 60 88 56 78 46 70 38

40.2 70 38 79 47 88 56 95 63 93 61 86 54 76 44 68 36

43.2 66 34 67 35 86 54 95 63 93 61 85 53 74 42 67 35

51.2 68 36 71 39 87 55 95 63 94 62 88 56 75 43 68 36

54.2 76 44 77 45 87 55 95 63 95 63 90 58 76 44 70 38

58.2 77 45 87 55 94 62 95 63 96 64 88 56 80 48 71 39

67.2 77 45 90 58 97 65 94 62 97 65 88 56 83 51 73 41

73.2 77 45 90 58 99 67 96 64 97 65 90 58 83 51 73 41

80.2 76 44 88 56 100 68 97 65 97 65 90 58 82 50 73 41

85.2 76 44 87 55 101 69 97 65 96 64 91 59 80 48 72 40

90.2 76 44 86 54 102 70 97 65 95 63 91 59 77 45 71 39

95.2 76 44 87 55 102 70 98 66 97 65 92 60 80 48 73 41

100.2 75 43 87 55 101 69 97 65 98 66 91 59 82 50 73 41

105.2 81 49 87 55 101 69 97 65 100 68 91 59 82 50 74 42

115.2 82 50 86 54 100 68 96 64 100 68 90 58 81 49 74 42

120.2 81 49 79 47 97 65 99 67 100 68 92 60 83 51 73 41

130.2 82 50 80 48 98 66 100 68 101 69 93 61 84 52 74 42

140.3 78 46 90 58 105 73 100 68 101 69 94 62 84 52 75 43

150.3 79 47 90 58 105 73 101 69 102 70 95 63 85 53 77 45

160.3 83 51 91 59 106 74 101 69 104 72 95 63 86 54 77 45

33.2 67 35 70 38 84 52 85 53 86 54 81 49 75 43 67 35

35.2 69 37 77 45 85 53 86 54 87 55 82 50 75 43 67 35

37.2 69 37 80 48 85 53 86 54 87 55 83 51 74 42 66 34

40.2 66 34 75 43 83 51 90 58 88 56 81 49 72 40 64 32

43.2 63 31 64 32 82 50 90 58 88 56 80 48 70 38 63 31

51.2 65 33 67 35 82 50 90 58 89 57 83 51 71 39 64 32

54.2 72 40 73 41 82 50 90 58 90 58 85 53 72 40 66 34

58.2 73 41 83 51 89 57 89 57 90 58 84 52 76 44 67 35

67.2 73 41 86 54 92 60 89 57 92 60 84 52 79 47 69 37

73.2 73 41 85 53 94 62 91 59 92 60 85 53 79 47 70 38

80.2 72 40 84 52 95 63 91 59 92 60 85 53 77 45 70 38

85.2 72 40 83 51 96 64 92 60 91 59 86 54 76 44 68 36

90.2 72 40 81 49 97 65 92 60 90 58 86 54 73 41 67 35

95.2 72 40 82 50 97 65 93 61 92 60 87 55 76 44 69 37

100.2 71 39 82 50 96 64 92 60 93 61 86 54 77 45 69 37

105.2 76 44 83 51 96 64 92 60 95 63 86 54 78 46 70 38

115.2 78 46 82 50 95 63 91 59 95 63 86 54 77 45 70 38

120.2 77 45 75 43 92 60 94 62 94 62 87 55 79 47 70 38

130.2 77 45 75 43 93 61 95 63 95 63 88 56 80 48 70 38

140.3 74 42 85 53 100 68 95 63 96 64 90 58 79 47 72 40

150.3 75 43 86 54 100 68 96 64 97 65 90 58 81 49 73 41

160.3 79 47 86 54 100 68 96 64 99 67 91 59 82 50 74 42

94 62

95 63

95 63

96 64

96 64

97 65

98 66

98 66

99 67

100 67

100 67

100 68

100 68

101 68

101 68

102 69

102 69

102 69

103 70

104 71

105 71

106 72

89 57

90 58

90 58

91 59

91 59

92 59

93 61

93 60

94 62

95 63

95 63

95 63

95 62

96 63

96 63

97 64

97 64

97 64

98 65

99 66

100 67

101 68

26Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

NOISE LEVELS

COBALT PRO HE

NOISE LEVELS

COBALT PRO HE LN

Lw: sound power values measured in free field calculated according to standard ISO 3744.Lp: sound pressure levels measured at 1 metre from the unit in free field under nominal operating conditions, according to ISO 3744.

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

Total [dB(A)]

Lw Lp

Total [dB(A)]

Lw Lp

33.2 71 39 74 42 89 57 90 58 91 59 86 54 79 47 71 39

35.2 73 41 82 50 90 58 91 59 92 60 87 55 79 47 72 40

37.2 73 41 84 52 90 58 91 59 92 60 88 56 79 47 71 39

40.2 70 38 79 47 88 56 95 63 93 61 86 54 76 44 69 37

43.2 67 35 68 36 86 54 95 63 93 61 85 53 74 42 67 35

51.2 68 36 71 39 87 55 95 63 94 62 88 56 76 44 69 37

54.2 76 44 77 45 87 55 95 63 95 63 90 58 77 45 71 39

58.2 77 45 87 55 94 62 94 62 95 63 89 57 81 49 72 40

67.2 77 45 90 58 97 65 94 62 97 65 88 56 83 51 73 41

73.2 77 45 90 58 99 67 96 64 97 65 90 58 83 51 74 42

80.2 76 44 88 56 100 68 97 65 97 65 90 58 82 50 74 42

85.2 76 44 87 55 101 69 97 65 96 64 91 59 80 48 73 41

90.2 76 44 86 54 102 70 97 65 95 63 91 59 78 46 72 40

95.2 76 44 87 55 102 70 98 66 97 65 92 60 81 49 73 41

100.2 75 43 87 55 101 69 97 65 98 66 91 59 82 50 74 42

105.2 81 49 87 55 101 69 97 65 100 68 91 59 82 50 75 43

115.2 82 50 86 54 100 68 96 64 100 68 90 58 82 50 75 43

120.2 81 49 79 47 97 65 99 67 100 68 92 60 84 52 74 42

33.2 67 35 70 38 84 52 85 53 86 54 81 49 75 43 67 35

35.2 69 37 77 45 85 53 86 54 87 55 82 50 75 43 68 36

37.2 69 37 80 48 85 53 86 54 87 55 83 51 74 42 67 35

40.2 66 34 75 43 83 51 90 58 88 56 81 49 72 40 65 33

43.2 63 31 64 32 82 50 90 58 88 56 80 48 70 38 64 32

51.2 65 33 67 35 82 50 90 58 89 57 83 51 71 39 65 33

54.2 72 40 73 41 82 50 90 58 90 58 85 53 73 41 67 35

58.2 73 41 82 50 89 57 89 57 90 58 84 52 76 44 68 36

67.2 73 41 86 54 92 60 89 57 92 60 84 52 79 47 69 37

73.2 73 41 85 53 94 62 91 59 92 60 85 53 79 47 70 38

80.2 72 40 84 52 94 62 91 59 92 60 85 53 78 46 70 38

85.2 72 40 83 51 96 64 92 60 91 59 86 54 76 44 69 37

90.2 72 40 81 49 97 65 92 60 90 58 86 54 74 42 68 36

95.2 72 40 82 50 97 65 92 60 92 60 87 55 77 45 70 38

100.2 71 39 82 50 96 64 92 60 93 61 87 55 78 46 70 38

105.2 76 44 82 50 96 64 92 60 95 63 87 55 78 46 71 39

115.2 78 46 82 50 95 63 91 59 95 63 86 54 78 46 71 39

120.2 77 45 75 43 92 60 94 62 94 62 87 55 79 47 70 38

94 62

95 62

95 62

96 63

96 63

97 65

98 66

98 66

99 67

100 67

100 67

100 67

100 67

101 68

101 68

102 69

102 69

102 69

89 57

90 58

90 58

91 59

91 59

92 59

93 61

93 60

94 62

95 62

95 62

95 62

95 62

96 63

96 63

97 64

97 64

97 64

27Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

NOISE LEVELS

COBALT PRO HE SLN

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

Total [dB(A)]

Lw Lp

33.2 65 33 68 36 81 49 82 50 83 51 78 46 72 40 65 33

35.2 66 34 74 42 82 49 83 51 84 51 79 47 72 40 65 33

37.2 67 34 77 44 82 49 83 50 84 51 80 48 72 39 65 32

40.2 64 31 72 40 80 48 87 54 85 52 78 46 70 37 63 30

43.2 61 28 62 29 79 46 87 55 85 52 77 45 68 36 62 29

51.2 62 30 65 33 80 47 87 54 86 53 80 48 69 37 63 30

54.2 70 37 71 38 80 47 87 54 87 55 82 50 71 38 65 32

58.2 71 38 80 47 86 53 86 54 87 55 81 48 74 41 66 33

67.2 70 38 83 50 89 56 86 54 89 56 81 48 76 44 67 34

73.2 70 37 83 50 91 58 88 55 89 56 82 49 76 43 68 35

80.2 69 36 81 48 91 58 88 55 89 56 83 50 75 42 68 35

85.2 69 36 80 47 93 60 89 56 88 55 83 50 73 40 67 34

90.2 69 36 79 46 94 61 89 56 87 54 83 50 71 38 66 33

95.2 70 37 80 47 94 61 89 56 89 56 84 51 74 41 67 34

100.2 69 36 80 47 93 60 89 56 90 57 84 51 75 42 68 35

105.2 74 41 80 47 93 60 89 56 92 59 84 51 76 43 69 36

115.2 76 43 79 46 92 59 88 55 92 59 83 50 75 42 69 36

120.2 74 41 72 39 89 56 91 58 91 58 84 51 77 44 68 35

86 54

87 55

87 54

88 56

88 56

89 57

90 58

90 58

91 59

92 59

92 59

92 59

92 59

93 60

93 60

94 61

94 61

94 61

28Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

NOISE LEVELS

COBALT PRO HEi

NOISE LEVELS

COBALT PRO HEi LN

Lw: sound power values measured in free field calculated according to standard ISO 3744.Lp: sound pressure levels measured at 1 metre from the unit in free field under nominal operating conditions, according to ISO 3744.

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

Total [dB(A)]

Lw Lp

Total [dB(A)]

Lw Lp

58.2 82 49 75 43 84 52 92 59 98 65 91 58 80 48 73 40

67.2 82 50 87 55 93 61 92 60 98 66 90 58 83 50 74 41

73.2 97 64 92 59 94 62 98 66 96 64 94 62 85 53 74 42

80.2 97 64 91 58 96 64 99 66 96 63 95 62 84 52 74 42

85.2 98 65 92 59 96 64 99 67 96 64 95 63 85 53 75 42

90.2 99 66 92 60 100 68 101 68 97 64 97 64 86 53 75 43

95.3 83 51 88 56 95 62 95 63 100 68 93 60 84 51 75 43

100.3 84 51 91 59 97 65 96 63 101 68 92 60 85 53 76 44

105.3 98 65 94 61 98 65 100 68 99 67 96 63 87 55 77 44

115.3 98 65 93 61 99 66 100 68 99 66 96 63 87 54 77 44

58.2 78 46 72 40 81 48 88 55 94 61 87 55 77 44 70 37

67.2 79 46 84 51 89 57 89 56 94 62 87 54 79 47 71 38

73.2 93 60 88 55 90 58 94 62 92 60 90 58 81 49 71 39

80.2 93 60 87 55 92 60 94 62 92 59 91 58 81 48 71 39

85.2 94 61 88 55 92 60 95 63 92 60 91 59 82 49 72 39

90.2 95 62 89 56 96 64 97 64 93 60 93 60 82 50 72 40

95.3 80 47 85 52 91 58 91 59 96 64 89 57 80 48 72 40

100.3 80 48 87 55 93 61 92 59 97 64 89 56 82 49 73 41

105.3 94 61 90 58 94 61 96 64 95 62 92 59 84 51 73 41

115.3 94 61 90 57 95 62 96 64 95 62 92 60 83 51 73 41

99 67

100 67

101 68

101 68

101 68

103 70

102 69

102 69

103 69

103 69

95 63

96 63

97 64

97 64

97 64

99 66

98 65

98 65

99 65

99 65

29Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

NOISE LEVELS

COBALT PRO XEi

NOISE LEVELS

COBALT PRO XEi LN

Lw: sound power values measured in free field calculated according to standard ISO 3744.Lp: sound pressure levels measured at 1 metre from the unit in free field under nominal operating conditions, according to ISO 3744.

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

MODEL

Octave bands [dB]

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

Total [dB(A)]

Lw Lp

Total [dB(A)]

Lw Lp

30.1 82 50 74 42 76 44 88 56 98 66 90 58 80 48 72 40

35.1 98 66 91 59 88 56 98 66 94 62 95 63 84 52 73 41

45.1 99 67 92 60 89 57 99 67 95 63 96 64 85 53 74 42

55.2 86 54 77 45 79 47 91 59 101 69 93 61 83 51 75 43

65.2 98 66 91 59 89 57 99 67 99 67 96 64 86 54 76 44

70.2 101 69 94 62 92 60 101 69 97 65 98 66 87 55 76 44

80.2 101 69 94 62 92 60 102 70 97 65 98 66 88 56 77 45

90.2 102 70 95 63 92 60 102 70 98 66 99 67 88 56 77 45

100.3 101 69 94 62 92 60 102 70 100 68 98 66 88 56 78 46

30.1 79 47 71 39 73 41 84 52 94 62 86 54 76 44 69 37

35.1 94 62 87 55 85 53 94 62 90 58 91 59 81 49 70 38

45.1 95 63 88 56 86 54 95 63 91 59 92 60 82 50 71 39

55.2 82 50 74 42 76 44 87 55 97 65 89 57 79 47 72 40

65.2 94 62 87 55 85 53 95 63 95 63 92 60 82 50 73 41

70.2 97 65 90 58 88 56 97 65 93 61 94 62 84 52 73 41

80.2 97 65 91 59 88 56 98 66 93 61 94 62 84 52 74 42

90.2 98 66 91 59 89 57 98 66 94 62 95 63 85 53 74 42

100.3 97 65 90 58 88 56 98 66 96 64 95 63 84 52 75 43

99 67

100 68

101 69

102 69

103 70

103 70

104 71

104 71

105 71

95 63

96 64

97 65

98 65

99 66

99 66

100 67

100 67

101 67

30Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

COBALT PRO 33.2-160.3 A4F256-A

Denomination - Dimensional Drawing Drawing Rev.

DraftsmanDateScale Checked bySheet N. of

Replace draw. Replaced by draw. Weight [kg]

DIMENSIONAL DRAWING KAPPA REV 33.2-160.3A4F256- / A

CECCAROLI 2

/ /

1/26/02/20141:60

/

Code

MTE 56 rev. 04 date: 07/04/11Reserved property, reproduction prohibited accordin to existentlaws.Copyright.

Rev. Date Draftman Checked by Revision description

VERSION 1PS-2PS SIZE 58.2-160.3

2443

LENGHT

1800

1500

1500

UinUout

Uout Uin

UoutUin

St

Es

Pu *

*Pu*

Sc Ep*

2260

VERSION 1PS .2PS SIZE 51.2-54.2

* OPTIONAL

UinUout

VERSION 1P-2P

1500

DIMENSIONAL DRAWING

31Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

Denomination Drawing Rev.

DraftsmanDateScale Checked bySheet N. of

Replace draw. Replaced by draw. Weight [kg]

DIMENSIONAL DRAWING KAPPA REV 33.2-160.3A4F256- / A

CECCAROLI 2

/ /

2/26/02/20141:50

/

Code

MTE 56 rev. 04 date: 07/04/11Reserved property, reproduction prohibited accordin to existentlaws.Copyright.

Size LENGHT Uin (ST) Uin 1P‐2P Uin 1PS‐2PS Uout

33.2 3870 OD 114.3 OD 114.3 ‐ OD 114.335.2 3870 OD 114.3 OD 114.3 ‐ OD 114.337.2 3870 OD 114.3 OD 114.3 ‐ OD 114.340.2 3870 OD 114.3 OD 114.3 ‐ OD 114.343.2 3870 OD 139.7 OD 114.3 ‐ OD 139.751.2 5020 OD 139.7 OD 114.3 OD 114.3 OD 139.754.2 5020 OD 139.7 OD 114.3 OD 114.3 OD 139.758.2 6170 OD 139.7 OD 139.7 OD 139.7 OD 139.767.2 6170 OD 168.3 OD 139.7 OD 139.7 OD 168.373.2 7310 OD 168.3 OD 139.7 OD 139.7 OD 168.380.2 7310 OD 168.3 OD 139.7 OD 139.7 OD 168.385.2 7310 OD 168.3 OD 139.7 OD 139.7 OD 168.390.2 7310 OD 168.3 OD 139.7 OD 139.7 OD 168.395.2 8465 OD 219.1 OD 168.3 OD 168.3 OD 219.1100.2 8465 OD 219.1 OD 168.3 OD 168.3 OD 219.1105.2 9610 OD 219.1 OD 168.3 OD 168.3 OD 219.1115.2 9610 OD 219.1 OD 168.3 OD 168.3 OD 219.1120.2 10760 OD 219.1 OD 168.3 OD 168.3 OD 219.1130.2 10760 OD 219.1 OD 168.3 OD 168.3 OD 219.1140.3 11970 OD 273.0 OD 219.1 ‐ OD 273.0150.3 13110 OD 273.0 OD 219.1 ‐ OD 273.0160.3 13110 OD 273.0 OD 219.1 ‐ OD 273.0

32Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

COBALT PRO HE 33.2-120.2 A4F257-A

Denomination - Dimensional Drawing Drawing Rev.

DraftsmanDateScale Checked bySheet N. of

Replace draw. Replaced by draw. Weight [kg]

DIMENSIONAL DRAWING KAPPA REV HE 33.2-120.2A4F257- / A

CECCAROLI 2

/ /

1/26/02/20141:60

/

Code

MTE 56 rev. 04 date: 07/04/11Reserved property, reproduction prohibited accordin to existentlaws.Copyright.

Rev. Date Draftman Checked by Revision description

VERSION 1PS-2PS SIZE 51.2-120.2

2443

LENGHT

1800

1500

1500

UinUout

Uout Uin

UoutUin

ø168.3 ø168.3

St

Es

Pu *

*Pu*

Sc Ep*

2260

VERSION 1PS .2PS SIZE 35.2-43.2

* OPTIONAL

UinUout

VERSION 1P-2P

1500

DIMENSIONAL DRAWING

33Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

Denomination Drawing Rev.

DraftsmanDateScale Checked bySheet N. of

Replace draw. Replaced by draw. Weight [kg]

DIMENSIONAL DRAWING KAPPA REV HE 33.2-120.2A4F257- / A

CECCAROLI 2

/ /

2/26/02/20141:50

/

Code

MTE 56 rev. 04 date: 07/04/11Reserved property, reproduction prohibited accordin to existentlaws.Copyright.

Size LENGHT Uin (ST) Uin 1P‐2P Uin 1PS‐2PS Uout

33.2 3870 OD 114.3 OD 114.3 ‐ OD 114.335.2 5020 OD 139.7 OD 114.3 OD 114.3 OD 139.737.2 5020 OD 139.7 OD 114.3 OD 114.3 OD 139.740.2 5020 OD 139.7 OD 114.3 OD 114.3 OD 139.743.2 5020 OD 139.7 OD 114.3 OD 114.3 OD 139.751.2 6170 OD 139.7 OD 114.3 OD 114.3 OD 139.754.2 7310 OD 139.7 OD 114.3 OD 114.3 OD 139.758.2 7310 OD 168.3 OD 114.3 OD 114.3 OD 168.367.2 7310 OD 168.3 OD 139.7 OD 139.7 OD 168.373.2 8465 OD 168.3 OD 139.7 OD 139.7 OD 168.380.2 8465 OD 168.3 OD 139.7 OD 139.7 OD 168.385.2 9610 OD 219.1 OD 139.7 OD 139.7 OD 219.190.2 9610 OD 219.1 OD 139.7 OD 139.7 OD 219.195.2 10760 OD 219.1 OD 168.3 OD 168.3 OD 219.1100.2 10760 OD 219.1 OD 168.3 OD 168.3 OD 219.1105.2 11970 OD 219.1 OD 168.3 OD 168.3 OD 219.1115.2 13110 OD 219.1 OD 168.3 OD 168.3 OD 219.1120.2 13110 OD 219.1 OD 168.3 OD 168.3 OD 219.1

34Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

COBALT PRO HEi 58.2-115.3 A4F259-A

Denomination - Dimensional Drawing Drawing Rev.

DraftsmanDateScale Checked bySheet N. of

Replace draw. Replaced by draw. Weight [kg]

DIMENSIONAL DRAWING KAPPA REV HEi 58.2-115.3A4F259- / A

CECCAROLI 1

/ /

1/26/02/20141:60

/

Code

MTE 56 rev. 04 date: 07/04/11Reserved property, reproduction prohibited accordin to existentlaws.Copyright.

Rev. Date Draftman Checked by Revision description

VERSION 2P

VERSION 1PS-2PS24

43

1500

Uout Uin

1500

1500

UinUout

LENGHT

Uin Uout

St

Sc*

*

Pu

Pu

*

*

2260

2161

282

1800

* OPTIONAL

Size LENGHT Uin (ST) Uin 1P‐2P Uin 1PS‐2PS Uout

58.2 7370 OD 168.3 OD 114.3 OD 114.3 OD 168.367.2 8527 OD 168.3 OD 139.7 OD 139.7 OD 168.373.2 8527 OD 219.1 OD 139.7 OD 139.7 OD 219.180.2 9670 OD 219.1 OD 139.7 OD 139.7 OD 219.185.2 9670 OD 219.1 OD 139.7 OD 139.7 OD 219.190.2 10820 OD 219.1 OD 139.7 OD 139.7 OD 219.1100.3 12030 OD 273.0 OD 168.3 ‐ OD 273.0105.3 13170 OD 273.0 OD 168.3 ‐ OD 273.0115.3 13170 OD 273.0 OD 168.3 ‐ OD 273.0

DIMENSIONAL DRAWING

35Swegon reserves the right to alter specifications. www.swegon.com

COBALT PRO

COBALT PRO XEi 30.1-100.3 A4F260-A

Denomination - Dimensional Drawing Drawing Rev.

DraftsmanDateScale Checked bySheet N. of

Replace draw. Replaced by draw. Weight [kg]

DIMENSIONAL DRAWING KAPPA REV XEi 30.1-100.3A4F260- / A

CECCAROLI 1

/ /

1/11/03/20141:60

/

Code

MTE 56 rev. 04 date: 07/04/11Reserved property, reproduction prohibited accordin to existentlaws.Copyright.

Rev. Date Draftman Checked by Revision description

VERSION 2P

VERSION 1PS-2PS24

43

1500

Uout Uin

1500

1500

UinUout

LENGHT

Uin Uout

St

Sc*

*

Pu

Pu

*

*

2260

2161

282

1800

* OPTIONAL

Size LENGHT Uin (ST) Uin 1P‐2P Uin 1PS‐2PS Uout

30.1 3930 OD 114.3 OD 114.3 ‐ OD 114.335.1 5080 OD 114.3 OD 114.3 OD 114.3 OD 114.345.1 6230 OD 139.7 OD 114.3 OD 114.3 OD 139.755.2 7370 OD 168.3 OD 114.3 OD 114.3 OD 168.365.2 8530 OD 168.3 OD 139.7 OD 139.7 OD 168.370.2 9670 OD 219.1 OD 139.7 OD 139.7 OD 219.180.2 10820 OD 219.1 OD 139.7 OD 139.7 OD 219.190.2 12030 OD 219.1 OD 139.7 OD 139.7 OD 219.1100.3 13170 OD 273.0 OD 168.3 OD 168.3 OD 273.0

DIMENSIONAL DRAWING

36

602

2010

00

02_2

0-0

3-2

014

_CO

BA

LT P

RO