OVERVIEW
Mike Kerkhof
Senior Application Engineer
Distribution Automation Integration
- 2
-
COM600 Station Computer
- 3
-
Content
Basic Introduction
COM 600 Product Overview
Applications
Technical data
Configuration Procedure
- 4
-
Basic introduction
COM 600 Station Computer Provides substation data to any personnel
through local HMI in substation or/and to any user through WAN/LAN networks
Easy to use web-browser user interface
SW bundled with ruggedized industrial HW
Fully complaint to IEC 61850 standard
Efficient and easy engineering with ABB IED’s
Compatible with any IED using open protocols
Suitable for any indoor installation
- 5
-
Basic introduction
Control and Monitoring
Parameter settings & DR
Local HMI
StationCommunication
NCC Communication
External OPC client
Remote parameter
setting
COM 600 Industrial Embedded Computer
L
AN
/WA
N/
Intr
anet
/In
tern
et
- 6
-
Content
Basic Introduction
COM 600 Product Overview
Applications
Technical data
Configuration Procedure
- 7
-
Product overview – COM 600
HMI functionality - true web based HMI for substations Single line diagram
Dynamic busbar coloring
Controls, secured
Alarms & Events
Measurements
Disturbance record upload
Parameter setting for the IEDs
System diagnostics
Multi language support
User management
- 8
-
Product overview – COM 600
OPC/IEC 61850 based architecture IEC 61850 Data Modelling
Cross referencing between protocols base on IEC 61850 data models
Drag and Drop signal mapping
Supports all utility required protocols
for communication to NCC
Supports OPC client/server principal
- 9
-
Single line diagram
SLD uses one screen only Zoom in/out, Pan, Freeze
Two different voltage levels One voltage level in one row Automatic setting of default
scale Symbols for MV process
Local/Remote switch / bay / station
“All” MV apparatuses, ANSI and IEC style
Measurements Free text tags
Configurable colors, fonts, line styles
- 10
-
SLD Editor Tool
Configuration of IED is retrieved by means of a Connectivity Package, which can include also the Single-Line-Diagram Still it’s freely configurable Predefined set of IEC and
ANSI symbols
Simple and easy to use Guides You to do logically
relevant configuration
IEC 61850-6 (SCL) import/export of SLD information
- 11
-
Alarms
Alarm list with following columns: Date & Time Bay (from substation structure) Device (from substation structure) Object text (from d attribute of data) Status (from the event handling
definition for the data) Alarms are divided to two groups,
persisting and fleeting alarms based on current status of an alarm. Alarms can be acknowledged one by one as all of at once.
Filtering per bay, voltage level Filtering can be done automatically
from the substation structure tree Audio alarm supported for web
browsers
- 12
-
Events
Event list page with columns: Date & Time Bay (from substation structure) Device (from substation
structure) Object text (from d attribute of
data) Event (from the event handling
definition for the data
Filtering can be applied per bay, voltage level
Filtering can be done automatically from the substation structure tree
- 13
-
Control dialogs
Controllable switches SBO and direct controls
Support for IEC 61850 interlocking, synchro-check and reservation information
Forced cancel operation Station/remote/local authority
handling Freely definable web-links
- 14
-
Measurements
All measurements available in IED can be displayed
Measurement display is configurable Scaling factor Texts Units Configuration can be
retrieved also from ConPkg or SCL files
- 15
-
Disturbance record upload
The protection and control device generates disturbance records that can be uploaded from the HMI for further analysis.
Supported format is COMTRADE via IEC 61850-8-1
- 16
-
Busbar coloring
Busbar coloring needs no additional configuration!
4 different modes: Powered/Unpowered based
Different voltage level
Powered/Unpowered parts
Earthed part
Voltage level based Voltage source based
Incoming/Outgoing
No busbar coloring
Freely configurable colors
- 17
-
Parameters setting
Simple, but visual parameter setting tool Parameters coming from Conn.
Pkgs Visible parameters are to be
filtered on configuration phase
Changed parameters are indicated as bold
Configurable descriptions Features to ease the use and
avoid mistakes: Changed parameters bolded
after modifications Ranges, units are shown and
checked run-time
- 18
-
Multilanguage support
- 19
-
System diagnostics
Communication structure tree view shows quickly the health of secondary systems
Each object has mode detailed diagnostic information available
- 20
-
User Management
Four different type of users Viewer Operator Engineer Administrator
User management is done from Web HMI Add user Change Password Administration of existing users
For security reasons Default password has to be
changed Certain Password length is
required
- 21
-
… and more
Zoom in/out Ctrl +/-
Pan screen Alt + mouse
Several browser windows can used run in large/multi-monitor setups
Use browser features like Favorites to navigate to Your stations
And of course… Application can be accessed from anywhere
Fully web-based – real thin client
- 22
-
On-line diagnostics
Web server for diagnostic information
- 23
-
Other Features
Value manipulation facilities Linear and step-wise linear scales Inverting of signals
High performance on the gateway function – protocol mapping is done on the start-up phase, not on run-time
Proven protocol quality and interoperability SNTP time synchronization support (client and server)
- 24
-
Content
Basic Introduction
COM 600 Product Overview
Applications
Technical data
Configuration Procedure
- 25
-
Applications – COM 600
NCC and / or DCSconnection
Suitable both for Utility and Industry Applications
Providing Communication Gateway and HMI function typically for one MV substation up to 40 bays
Transferring all needed substation data to Network Control Center or Distributed Control System
HMI can be displayed Monitor/Touch Screen connected to unit locally PC directly connected to unit Through LAN/WAN networks (Intranet/Internet)
Remote/Local safety operations with Switchgear and IEDs
Flexible installation Thanks to size unit can be installed in low-
voltage compartment of Medium Voltage Switchgear
- 26
-
Network Control Centers
COM 600
Touch Screen for Local HMI Functions
Local access
LAN/WAN
LAN/WAN
Remote communication
Process Communication
Remote access
Utility Applications
- 27
-
Industrial ApplicationsProcess Control System
COM 600
Touch Screen for Local HMI Functions
Local Access
LAN/WAN
LAN/WAN
OPC Client/Server (DA, AE)
LV Devices & Energy Meters
Modbus RTU
Process Communication
- 28
-
COM600 Supported communication protocols
Master protocol Slave protocol
DNP3 LAN/WAN DNP3 LAN/WAN
DNP3 Serial DNP3 Serial
Modbus Serial Modbus Serial
Modbus TCP Modbus TCP
IEC 61850-8-1 External OPC
IEC 60870-5-101 IEC 60870-5-101
IEC 60870-5-103 IEC 60870-5-104
IEC 60870-5-104 SPA router
LON - LAG
MNS iS Connectivity
SPA
- 29
-
Single Channel - Tree Topology
- 30
-
Single Channel - Ring Topology at Station Level
- 31
-
Content
Basic Introduction
COM 600 Product Overview
Applications
Technical data
Configuration Procedure
- 32
-
Technical data - HW
Industrial Computer (no moving parts) Intel Pentium M (1.6 GHz) 1 GB SDRAM, 8 GB SSD Industrial Flash Memory Power supply option (High voltage: 76 – 240VDC) 2 x Ethernet 100BaseTX 4 x COM (1 x RS485/232, 3 x RS 232) 4 x USB and SVGA, Audio 1 slot for extension (LON, RS232/485, 2xLAN) Hardware watchdog Dimensions 214(W) x 122,5(H) x 313(D) IP 4x enclosure Operating Ambient Temperature -25°C… +70°C Storage Temperature -40°C… +70°C Operating Humidity – 95% EMC CE/FCC class B RoHS compliant
- 33
-
Interfaces
Indication LEDs
ON/OFF
PCMCIA(not used at the moment)
Compact Flash
PowerInput
LAN’sAudio
USB
PCI
Serial portsRS 232
Serial portsRS 232/485
VGA
All Interfaces are accessible from the front
- 34
-
PCI card extensions
RS 232/485 4 or 8 additional - 9 pin inputs
Operating temp. 0°C-65°C
OR
Extension of Ethernet 2 additional RJ 45
Operating temp. 0°C-60°C
All PCI cards are RoHS certified
- 35
-
Content
Basic Introduction
COM 600 Product Overview
Applications
Technical data
Configuration Procedure
- 36
-
OPC Client
Configuration tool on a PC Web Server
OPC Server
IEC 61850
SCL
Connectivity Package’s for IEDs and/or device profiles
Conf
IEC 61850-8-1
Standard web-browser
Con
figur
atio
n P
hase
- O
fflin
e
DNP 3.0 Slave
OPC Client
Onl
ine
Ope
ratio
n
COM 600 – software environment
Remote control
Har
den
ed X
P e
mb
ed
ded
HMI application
- 37
-
Configuration data flows
ABB IEDConnectivityPackages
SABdatabase
COM 600
ABB IEDconfiguration
data
IEC 61850 interface
descriptions =ICD/CID
SCD files
Stationlayout
Local namingconventions
Interface requirements and specs
HMI and gateway configuration
Com
munication P
aram
eter
s,co
lors
IED productinformation
IED instance information
Info
rmat
ion fr
om 3r
d par
ty
IEDs
SABuser
SL
D
NCCresponsible
Manually collected information
Automatically collected information
Information modeling, cross-referencing
Other requirements
- 38
-
Configuration Work Flow
Define project and it’s basic
settings
Create communication structure for
the station
Own IP addressUser management
Add protocols, communication lines, sub networks …Add IEDs, using ConPkg tools or Generic IEDs. Copy/paste “type” solution
Finalize substation structure
Add/modify substations, voltage levels, bays, if not retrieved from ConPkgs/SCL files. Finalize “type” solutions
Finalize single-line diagram
Fine-tune layout, connect bays to busbars, add descriptive texts, choose coloring, add extra objects, define power source.
Customize Alarm & Event
handling
Customize IED parameter
settings
Project specific event and alarm handling can be defined for any signal. Default handling can be modified/removed /new handling added
To keep HMI simple, a subset of available parameters can be selected to be shown
Configure NCC links
Add slave protocol lines, assign addresses. Review / finalize with NCC.
Upload configuration
Upload the configuration to the device. Ready!